Bill of Quantity - Electrical Works
Sl.
DESCRIPTION QTY UNIT RATE (₹) AMOUNT (₹)
No
QUOTATION OF HT PANEL
PART (A) - SUPPLY OF HT PANEL
11 KV Compact Switch gear (SINGLE VCB) - 11 KV Panel
1
Providing, testing and commissioning of 11 KV, 630 amp, 18.4
KA Indoor compact switchgear as per following details -
(Make : ABB / Schneider / Siemens )
(a) Supply of 11kV , 3Phase, 50Hz, 3 wire , earthed neutral, Indoor
type floor mounted, non extensible, having hinged arc proof
cable doors, breaking capacity 18.4 kA, VCB Unit enclosed in
robotically laser welded stainless steel tank having IP67 degree
of protection consisting of following:-
(i) 1 No. 630 Amps tee off spring assisted type vacuum circuit
breaker unit with self powered series trip microprocessor based
numerical over current 50 / 51 (instantinous / IDMT O/C relay)
and 51N (IDMT) Earth fault relay for protection, fitted with fixed
type voltage indicator device as per IEC 61958 along with fault
passage indicatorand & ring core type protection Current
transformer along with LV compartment with Ammeter with
selector switches. CT ratio - 3 CT's of 25/5/5A protection class - 1 SET
5P10 & Metering Class 1.0, All relays should be operated at
Minimum 10% of total selected CT load.
(ii) Air Insulated Metering panel connected along with above
unit, 18.4 kA , 630 amps, having Potential transformer, connected
jumpers / Bus Bar, LV Compartment to incorporate Votmeter and
Energy analyser (digital type) consisting of I, V, KW, KWH,
KVA, PF, HZ, MDI as per the requirement.
TOTAL (PART -A)
QUOTATION OF TRANSFORMER
PART (B) - SUPPLY OF TRANSFORMER
1 TRANSFORMER (11 KV / 0.4 KV)
Supply, testing & commissioning of Outdoor mounted type 11
KV / 433 Volt Transfomer (as per IS : 2026, P1 to P5), 3 phase,
4.5% impedance, Dyn 11 vector group, 50 cycles, (ONAN) oil
immersed naturally cooled, step down, copper wound,
continuous duty, temperature rise above 50oC in oil by
thermometer 40oC, in winding by resistance 45oC and other
standard accessories as required including followings :
The Transformer losses should confirm to IS : 1180
(Part
1)- 2014 with energy efficiency level - 2.
Sl.
DESCRIPTION QTY UNIT RATE (₹) AMOUNT (₹)
No
Make:- Crompton / Kirlosker / Schneider / Voltamp / Sudhir
Intra
/ Esennar / Kotsons / PVJ Power
a) Cable Termination box with disconnecting facility for 11
KV 3C- 185 sq mm XLPE cable at 11 KV side
b) Cable Termination box with disconnecting facility for
required nos. LT cable at LT side.
c) Off circuit Tap Changer on HV side + 10 % to - 10 % @ 2.5%
in manual mode with position indicator and locking arrangements.
d) Unidirectional rollers.
e) Oil Conservator with filter cap, drain plug & oil level gauge
f) Earthing terminals 2 nos for body earthing.
g) 0.415 KV neutral seperately bought out on a bushing for
neutral earthing.
h) Pressure release device. Double diaphragm explosion vent.
i) Radiators Detachable type with top & bottom shut off valve.
j) First filling of filtered dehydrated oil as per IS : 335
including make up fill during installation & 10% extra.
k) Silica gel breather with connecting pipe & oil seal.
l) Rating, Diagram & Terminal marking plate of SS.
m) Sampling Valves for filteration, drainage and filling with
plugs.
n) Air release plugs.
o) Thermometer pocket with plug.
p) Lifting Lugs.
q) Buchholz relay with gas release cock, alarm & shut off
valve with separate set of contacts for trip and alarm.
r) 150 mm Oil temperature indicator (OTI) with alarm
s) Marshalling Box.
t) Clamping device.
u) Jacking Pads.
The work shall be complete in all respects up to the satisfaction
of
Engg-in-charge.
400 KVA 1 Set
TOTAL (PART -B)
Sl.
DESCRIPTION QTY UNIT RATE (₹) AMOUNT (₹)
No
QUOTATION OF DG SET
PART (C) - SUPPLY OF DG SETS
DIESEL GENERATING SET
1 Supply, testing and Commissioning of Silent type
Diesel Generating Set at 0.8 PF, 415 Volts, 50 cycles per second,
1500 rpm, 3 phase, suitable for parallel operation / PLC
based load management, 0.85 load factor including circuit
breaker for isolation, sound proof acoustic and weather proof
enclosure, residential type silencer (as per CPCB norms-2)
fabricated out of CRCA sheet of 14/16 SWG thickness with 9
tank pretreated before powder coating with ventillation system
complete in all respects comprising of the following.
OEM - Jakson Ltd (Cummins) / Sudhir / Jakson & Co.
(Kirloskar)
/ Sterling / TIL / Kohler {Engine - Cummins, MTU, Mitsubishi
Japan and Caterpillar, Volvo Penta, Kirloskar} {Alternator -
Stamford / Leroy Somer / Greaves / Marathon}
Diesel Engine -
Diesel Engine suitable for driving alternator of above
rating, compression ignition, 4 stroke cycle, Radiator
cooled, turbo charged, battery starting, 1500 RPM, suitable
for above output of alternator at 40oC, 50% RH & at 210 M
MSL and confirming to BS 5514, BS 649, IS 10000, capable of
taking 10% overloading for one hour after 12 hrs of prime
continuous loading, complete with all the accessories i.e.
tachometer with hour meter, flexible coupling with guard, crank
case of steel, crank shaft, conncting rods, electronic (250
KVA) / mechanical (125 KVA) governing system, dynamically
balanced flywheel, air intake manifold, Air cleaner, anti
vibration pads, starter motor, including all other accessories
required to complete the system.
Instrument Panel - Engine mounted Instrument Panel
fitted
with and having digital display for followings :
Start stop switch with key
Water temperature indication
Lubrication oil pressure indication.
Lubrication oil temperature indication.
Battery charging indication
RPM indication
Over speed indication
Low Lube oil trip indication
Engine hours indication
Sl.
DESCRIPTION QTY UNIT RATE (₹) AMOUNT (₹)
No
Alternator -
Synchronous Alternator of above capacity at 0.8 PF, 3 phase, 415
volts, 50 cycles, 4 wire, 1500 RPM, suitable for operation at 40
deg C, 50% RH & at 210 meter above MSL, capable of
taking 10% overlioading for one hour after 12 hrs of prime
continuous loading, brushless, self excited, self regulated through
AVR, continuous duty confirming to IS 4722, BS 2613
suitable for tropical conditions, class H insulation, including
terminal box suitable for cable termination as required.
Base Frame - Both the engine and alternator shall be mounted on
suitable base frame made of MS channel which shall be installed
on cement concrete foundation and vibration isolating
arrangement as per recommendations of manufacturer.
Inbuilt Fuel tank of standard capacity complete with inlet
and outlet connections, oil indication gauge, drain plug, air
breather, fuel transfer system for automatic fuel refilling system
with pump, piping, valves, level indicators etc. complete.
Daily service Fuel tank of 990 liters capacity fabricated out
of 2 mm thick MS sheet complete with inlet and outlet
connections, oil indication gauge, drain plug, air breather,
provision for fuel transfer system, level indicators and all
standard accessories etc. as required.
Exhaust Silencer - Exhaust manifold with residential silencer.
The D G set should be supplied with required hardware for
external PLC based auto load management system / AMF Panel.
Starting system - 24 Volt DC starting system comprising of
starter motors : voltage regulator and arrangement for initial
excitation complete with 12/24 Volts suitable nos. lead acid
type
batteries of suitable AH.
Ventillation System - Arrangement for fresh air intake for
cooling of the engine & alternator, extraction, discharging hot
air into the atmosphere as per standard specifications.
30 KVA 24KW 3 PHASE JAKSON CUMMINS DG 1 SET
TOTAL (PART -C)
Sl.
DESCRIPTION QTY UNIT RATE (₹) AMOUNT (₹)
No
QUOTATION OF LT PANEL
PART (D) - SUPPLY OF MAIN LT PANELS, CAPACITOR PANEL & AC PANELS
1 Main L.T. Panel
Design, manufacture, supply inspection, handling,
assembling, affecting proper connections, testing and
commissioning of 14 SWG CRCA sheet steel fabricated
cubical type Main L.T. Panel with D G AMF Panel, floor
mounting, dust & vermin proof, front operated construction,
enclosure class - IP 52, powder coated after proper treatment
with 9 tank process with top/bottom removable gland plates,
as required, double compression type cable glands, earth bus,
hinged and lockable doors to achieve dust and vermin proof
complete with all inter connections small wiring by min. 2.5 sq.
mm. FRLS copper wires, ckt labels etc. The Aluminium Bus Bar
shall be of suitable length, 500 volts, 3 phase 50 Hz
TPN, electrolytic aluminium as per IS 8623 . The panel feeders
shall be suitable for terminating suitable nos. 3.5 / 4
core armoured aluminium cable or Aluminium Bus Duct as
required.
All incoming / bus coupler MCCB shall be microprocessor
based with O/L & S/C and E/F protection and all Outgoings
MCCB's shall be thermo-magnetic based O/L & S/C protection.
All MCCB's shall be Ics = 100% Icu, with rotary handle &
pad locking arrangement, with adjustable O/L & S/C trip setting
as per load requirement. All TP MCCB shall be with heavy
duty solid isolable neutral link.
The breaking capacity specified for all ACB's and
MCCB's
breakers is Ics value (service rating).
The instrument chamber shall be separate and shall comprise
of flush type ammeter, voltmeter, selector switches, cast resin
type CT's & PT's, etc. Separate CT's shall be provided for
protective and measuring system and for APFCR of capacitor
bank with suitable VA.
Each section of Panel shall have door opearted light of sufficent
lux to illumunate that section & each section of capacitor,
buscoupler, transformer and DG incomers shall have
exhaust fans for ventilation purpose.
All Energy Analyser / TVM Shall have RS 485
Modbus
RTU on board Communication protocol for
SCADA communication.
Note - Panel shall have self powered with inbuilt
UPS
and required battery sets.
GA drawings shall be got approved from Owners / Architects /
Consultants before fabrication.The panel has to be specifically
fabricated as per the space available at Ground level.
Sl.
DESCRIPTION QTY UNIT RATE (₹) AMOUNT (₹)
No
MCCB Make and model :- ABB - T-max, L&T - D sine,
Schneider - Compact NS / NSX, Siemens - 3VL, Legrand-DPX
INCOMER from 400 KVA Transformer
1 nos. 630 AMP. Four Pole, microprocessor based MCCB
(25 KA) + 1 nos 630 AMP, Four Pole Power Contactor
heavy
duty (fault withstand capacity 25 KA)
Contactor shall be electrically interlocked with all
incoming Supply (MCCB + Contactor) in such a way that at
any one time two supply should not get mixed up.
1 nos. 15 KVAR capacitor bank with 40 amp TP MCCB (25 KA)
for transformer incomer.
Protection releases / relays, Metering & Accessories
for
each Transformer incomers
Surge Protection Device - Type - 01 (Class - B), 10/350 µ
sec.
(100/ 25KA)
Auto manual selector switch.
Over Voltage / Under Voltage relay / release (3 phase) with timer.
IDMT earth fault relay.
1 nos. 0-500 volt range digital type voltmeter with selector switch
1 set of 3 CT's of ratio 600/5A, Class 1.0 accuracy 15 VA burden
for metering.
1 set of 3 CT's of ratio 600/5A, Class 1.0 accuracy 15 VA burden
for APFCR.
1 set - 415 / √3 / 110 / √3 Class 1.0 accuracy 100 VA burden
PT
along with primary and secondary fuse.
1 set. CT's of ratio 600/5A, Class 5P20 for protection.
1 no. 0-600 Amp range digital type ammeter with selector switch.
Energy analyser (digital type) consisting of I, V, KW, KWH,
KVA, PF, HZ, MDI (EM 6400 of Conzerve or equi.) with RS
485 communication port for communication / report generation.
Power factor meter.
Frequency meter.
3 Nos. LED type phase indicating lamps, each lamp shall be
with bakup MCB along with hooter, auxillary relay, 2 sets of
push buttons.
3 Nos. LED type indicating lamp for indicating the status of
feeder - ON / OFF / TRIP . Each lamp shall be with bakup MCB.
INCOMER from 1 Nos. 250 KVA D G set
1 nos. 400 AMP (25 KA) . Four Pole, MCCB + 1 nos 400
AMP (25 KA) Four Pole Power Contactor (Heavy Duty).
Sl.
DESCRIPTION QTY UNIT RATE (₹) AMOUNT (₹)
No
The Incomer Contactor shall be electrically & Mechanically
interlocked with Transformer incomer contactor,
Bus coupler's
c ontactor & other DG incomer's contactor in such a a
way t
any instant two supply should never get mixed up.
Protection releases / relays, Metering & Accessories for each
D
G set incomers
Reverse power relay.
TNC switch.
Auto / manual / test selector switch
1 Set - 415 /v3 / 110 / v3 Volts PT Class 1.0 accuracy and 100
VA burden along with primary & secondary MCB.
0-500 volt range digital type voltmeter with selector switch
1 set - 3 CTs of ratio : 400/5A , Class 1.0 accuracy 15 VA
each
burden for metering.
1 set - 3 CTs of ratio : 400/5A , Class 5P20 accuracy 20 VA
each
burden for protection.
0-400 Amp range digital type ammeter with selector switch.
Energy analyser (digital type) consisting of I, V, KW, KWH,
KVA, PF, HZ, MDI (EM 6400 of Conzerve or equi.)
with RS 485 communication port for communication / report
generation.
Frequency meter.
Power Factor meter.
3 Nos. LED type phase indicating lamps, each lamp shall be
with bakup HRC fuse/MCB along with hooter, auxillary
relay, 2 sets of push buttons.
4 Nos. LED type indicating lamp for indicating the status of
feeder - ON / OFF / TRIP / Reverse power (Trip). Each lamp
shall
be with bakup HRC fuse/MCB.
12 window annunciator with accept / reset / test push button
for each DG set for following indications and alarm : set fail
to start, engine over heat, high temperature, excitation failure,
low lube oil pressure, over speed, low fuel oil level, cooling
water flow failure, breaker trip, generator fault, DC control
supply failure, out of limit voltages and spares.
Push buttons for Test. Accept. Reset. Fault Reset. Engine
start, Engine stop, ACB close, ACB Trip Emergency stop.
Shut down due to low lube oil pressure/High
water
temp/Over speed/Low fuel level - set of 4 indication lamps.
D G control incorporating engine start / stop indicating
three
attempt facility and on failure to start, engine lock out.
1 nos battery charger with DC voltmeter and ammeter suitable
for
the 250 KVA DG sets
Sl.
DESCRIPTION QTY UNIT RATE (₹) AMOUNT (₹)
No
Note : In normal case all three lamps shall be ON to indicate that
incoming power supply is available. In case of power
resumption after failure buzzer shall ring to indicate the
power supply is resumed. There shall be one push button to
acknowledge the same.
DG AMF LOGIC (for DG set 250 KVA)
Automatic mains failure control including auto by-pass suitable
for silent type DG set complete with relays, timers set of
CTs for metering & proyection and energy analyser to
indicate currents, phase and line voltages, frequency, power
factor, KWH , KVARH & provision for overload, short circuit,
restricted earth fault, under frequency, control cabling from
AMF panel to diesel engine and elsewhere if required, all
complete and inter locking including the following:
Auto/Manual/Test/Off selector switch
D G Start / stop push button, emergency stop push button,
2 Nos. over voltage relay , 2 Nos. reverse power relay and 2
Nos.
under voltage relay.
3 sets of current transformers 15 P 10 accuracy for protection and
15 VA class-I for metering
Energy analyser unit to indicate current voltage
frequency
power factor and KWH
Indicating lamps for Mains ON/OFF, DG supply
ON/OFF,
DG running, DG fails to start.
Fuse for instruments
Battery charger, complete with transformer/ rectifier, D.C.
voltmeter and ammeter, selector switch for trickle, off and
boost
and current adjustment.
Main supply failure monitor
Supply failure timer
Restoration timer
Control unit with three impulse automatic engine
start/stop
and failure to start lockout.
Impulse counter with locking and reset facility.
ON/OFF/Control circuit switch with indicator
Sl.
DESCRIPTION QTY UNIT RATE (₹) AMOUNT (₹)
No
INCOMER from 1 Nos. 125 KVA D G set
1 nos. 200 AMP (25 KA) . Four Pole, MCCB + 1 nos 200
AMP (25 KA) Four Pole Power Contactor (Heavy Duty).
The Incomer Contactor shall be electrically &
Mechanically
interlocked with Transformer incomer contactor,
Bus coupler's
c ontactor & other DG incomer's contactor in such a a
way t
any instant two supply should never get mixed up.
Protection releases / relays, Metering & Accessories for each
D
G set incomers
Reverse power relay.
TNC switch.
Auto / manual / test selector switch
1 Set - 415 /v3 / 110 / v3 Volts PT Class 1.0 accuracy and 100
VA burden along with primary & secondary MCB.
0-500 volt range digital type voltmeter with selector switch
1 set - 3 CTs of ratio : 200/5A , Class 1.0 accuracy 15 VA each
burden for metering.
1 set - 3 CTs of ratio : 200/5A , Class 5P20 accuracy 20 VA each
burden for protection.
0-200 Amp range digital type ammeter with selector switch.
Energy analyser (digital type) consisting of I, V, KW, KWH,
KVA, PF, HZ, MDI (EM 6400 of Conzerve or equi.)
with RS 485 communication port for communication / report
generation.
Frequency meter.
Power Factor meter.
3 Nos. LED type phase indicating lamps, each lamp shall be
with bakup HRC fuse/MCB along with hooter, auxillary
relay, 2 sets of push buttons.
4 Nos. LED type indicating lamp for indicating the status of
feeder - ON / OFF / TRIP / Reverse power (Trip). Each lamp shall
be with bakup HRC fuse/MCB.
12 window annunciator with accept / reset / test push button
for each DG set for following indications and alarm : set fail
to start, engine over heat, high temperature, excitation failure,
low lube oil pressure, over speed, low fuel oil level, cooling
water flow failure, breaker trip, generator fault, DC control
supply failure, out of limit voltages and spares.
Push buttons for Test. Accept. Reset. Fault Reset. Engine
start, Engine stop, ACB close, ACB Trip Emergency stop.
Shut down due to low lube oil pressure/High water
temp/Over speed/Low fuel level - set of 4 indication lamps.
Sl.
DESCRIPTION QTY UNIT RATE (₹) AMOUNT (₹)
No
D G control incorporating engine start / stop indicating
three
attempt facility and on failure to start, engine lock out.
1 nos battery charger with DC voltmeter and ammeter suitable
for
the 125 KVA DG sets
Note : In normal case all three lamps shall be ON to indicate that
incoming power supply is available. In case of power
resumption after failure buzzer shall ring to indicate the
power supply is resumed. There shall be one push button to
acknowledge the same.
DG AMF LOGIC (for DG set 125 KVA)
Automatic mains failure control including auto by-pass suitable
for silent type DG set complete with relays, timers set of
CTs for metering & proyection and energy analyser to
indicate currents, phase and line voltages, frequency, power
factor, KWH , KVARH & provision for overload, short circuit,
restricted earth fault, under frequency, control cabling from
AMF panel to diesel engine and elsewhere if required, all
complete and inter locking including the following:
Auto/Manual/Test/Off selector switch
D G Start / stop push button, emergency stop push button,
2 Nos. over voltage relay , 2 Nos. reverse power relay and 2
Nos.
under voltage relay.
3 sets of current transformers 15 P 10 accuracy for protection and
15 VA class-I for metering
Energy analyser unit to indicate current voltage
frequency
power factor and KWH
Indicating lamps for Mains ON/OFF, DG supply
ON/OFF,
DG running, DG fails to start.
Fuse for instruments
Battery charger, complete with transformer/ rectifier, D.C.
voltmeter and ammeter, selector switch for trickle, off and
boost
and current adjustment.
Main supply failure monitor
Supply failure timer
Restoration timer
Control unit with three impulse automatic engine
start/stop
and failure to start lockout.
Impulse counter with locking and reset facility.
ON/OFF/Control circuit switch with indicator
INCOMERS from Solar PV Panel
1 nos. 200 AMP. FP MCCB 25 KA, microprocessor based
with KWAH meter along all accessories.
Sl.
DESCRIPTION QTY UNIT RATE (₹) AMOUNT (₹)
No
The feeder shall be provided with 3 nos. phase indicating
lights, flush mounted Ammeter, Voltmeter, & kWHR meter
CT's, PT's, selector switches, protective fuses etc. at Incomer
with all inter connections by min. 2.5 sq.mm. Copper wires.
BUS COUPLER
1 nos. 200 AMP. Four Pole, microprocessor based MCCB
(25 KA) + 1 nos 200 AMP, Four Pole Power Contactor
Heavy
duty (fault withstand capacity 25 KA)
The bus coupler shall be electrically & Mechanically
interlocked with
Transformer incomer contactor, & both DG sets incomer's contact
or in such a way at any instant two supply should never get
mixed up.
TNC switch.
Auto / manual selector switch
3 Nos. LED type indicating lamp for indicating the status of
feeder - ON / OFF / TRIP . Each lamp shall be with bakup
HRC
fuse/MCB.
BUS BARS
Bus Bar Make :- HINDALCO / JINDAL.
1 section of 600 AMP & 1 section of 300 AMP, 500 Volts, 3
phase
50 HZ TPN high conductivity electrolytic Aluminium bus
bar of suitable length, SMC / DMC supports, with colour
coding and insulated by heat shrinkable sleeves and clips on
shrouds for joints.
The current density of bus bar up to 1000 Amp shall be minimum
1.00 sq mm / amp.
The Maximum allowable temperature for the Bus bar to
be restricted to 85 deg C. The temperature rise should be
restricted
to 35 deg C above ambient temperature.
OUTGOINGS -
1 nos 300 AMP TP MCCB (25 KA)
3 nos 250 AMP TP MCCB (25 KA)
2 nos 40 AMP TP MCCB (25 KA)
10 nos 63 AMP FP MCB (10 KA)
4 nos 40 AMP FP MCB (10 KA)
1 nos 25 AMP DP MCB (10 KA)
1 nos 6 AMP DP MCB (10 KA)
Main LT Panel as described above 1 Set
Sl.
DESCRIPTION QTY UNIT RATE (₹) AMOUNT (₹)
No
2 AUTOMATIC POWER FACTOR CORRECTION PANEL (125 KVAR)
Design, manufacture, supply, inspection, handling,
assembling, affecting proper connections, testing and
commissioning of 14 SWG CRCA sheet steel fabricated cubical
type 125 KVAR A P F C Panel consisting of 5 / 10 / 20
/
25 KVAR (at 415 Volts rated voltage of bank shall be 440
Volts) capacitor units in tier formation, housed in an integrated
cubicle type automatic switching ON and OFF control panel,
floor mounting, dust & vermin proof, front operated
construction, enclosure class - IP 52, powder coated after proper
treatment with 9 tank process with top/bottom removable
gland plates, as required, double compression type cable glands,
earth bus, hinged and lockable doors to achieve dust and vermin
proof complete with all inter connections small wiring by
min.
2.5 sq. mm. copper wires, ckt labels etc. The Aluminium Bus Bar
shall be of suitable length, 500 volts, 3 phase 50 Hz TPN,
electrolytic aluminium as per IS 8623.
All outgoings MCCB's shall be thermal-magnetic based
with
inbuilt O/L & S/C release.
All MCCB's shall be Ics = 100% Icu, with rotary handle &
pad locking arrangement, with adjustable O/L & S/C trip setting
as per load requirement. All TP MCCB shall be with heavy
duty solid isolable neutral link. The breaking capacity
specified is Ics value. The instrument chamber shall be
separate and shall comprise of flush type ammeter, voltmeter,
selector switches, CT's, PT's, etc
Capacitor duty contactors should be used for
switching
individual capacitor banks.
The fault withstanding capacity of panel & its control gear shall
be min.25 KA rms for 1 sec.
Each section of capacitor panel shall have Verticle hood
&
exhaust fans for ventilation purpose.
INCOMING
Incomer circuit breaker has been included in the Normal Main
LT
Panel.
1 set-3 CTs , ratio 300/5A Class 1.0 accuracy 15 VA burden
for
metering.
1Nos- (0-300A) digital Ameter with selector switch
Micro processor based automatic power factor control relay
(3 phase) (including power factor meter) in 8 steps for automatic
cut off or add on capacitor units to keep the power factor at 0.95
with variation of loads. All associated auxiliary contactors / relays
shall be provided with in the scope of work.
Sl.
DESCRIPTION QTY UNIT RATE (₹) AMOUNT (₹)
No
Phase indicating lamps with HRC fuses, and indicating
in
each capacitor chamber unit to indicate On/Off status of
capacitor unit.
BUS BARS
400 AMP, 500 Volts, 3 phase 50 HZ TPN high
conductivity electrolytic Aluminium bus bar with conductivity on
min 57 to 58% of suitable length, SMC / DMC supports, with
colour coding and insulated by heat shrinkable sleeves and clips
on shrouds for joints. The current density of bus bar shall be
minimum 1.00 sq mm / amp.
The Maximum allowable temperature for the Bus bar
to
be restricted to 85 deg C. The temperature rise should be
restricted to 35 deg C above ambient temperature.
OUTGOINGS -
3 nos. of 63 AMPS TPN 25 KA MCCB and Capacitor duty
contactor with 25 KVAR heavy duty MPP type at 415 V
capacitor bank (rated Voltage 440 Volts) , auto-manual selector
switch, start stop push button for manual operation including
on/off indicating lamps and delay timer complete.
1 no. of 63 AMPS TPN 25 KA MCCB and Capacitor duty
contactor with 20 KVAR heavy duty MPP type at 415 V
capacitor bank (rated Voltage 440 Volts) , auto-manual selector
switch, start stop push button for manual operation including
on/off indicating lamps and delay timer complete.
2 no. of 32 AMPS TPN 25 KA MCCB and Capacitor
duty contactor with 10 KVAR heavy duty MPP type at 415 V
capacitor bank (rated Voltage 440 Volts) , auto-manual selector
switch, start stop push button for manual operation including
on/off indicating lamps and delay timer complete.
2 no. of 16 AMPS TPN 25 KA MCCB and Capacitor
duty contactor with 5 KVAR heavy duty MPP type at 415
V capacitor bank (rated Voltage 440 Volts) , auto-manual
selector switch, start stop push button for manual operation 1 Set
including on/off indicating lamps and delay timer complete.
3 Design, manufacture, supply, testing and commissioning of AC
Panel - 1 fabricated out of 16 SWG CRCA sheet steel, IP 42,
wall
/ floor mounting type. The sheet steel shall undergo minimum 9
tank treatment followed by finishing powder coating of
min
60 micron thickness. the board includes 415 V electrolitic
Aluminium Bus Bar, removable gland plates, cable glands,
including connection with outgoing feeders complete in all
respect.
Sl.
DESCRIPTION QTY UNIT RATE (₹) AMOUNT (₹)
No
The incoming MCCB shall be thermal-magnetic based with
inbuilt O/L & S/C release with E/F protection and all
Outgoings MCCB's shall be thermal-magnetic based with inbuilt
O/L & S/C release.
All MCCB's shall be Ics = 100% Icu, with rotary handle &
pad locking arrangement, with adjustable O/L & S/C trip setting
as per load requirement. All TP MCCB shall be with solid
isolable neutral link. The breaking capacity specified is Ics value.
All outgoing MCB's shall be C type with 10 KA breaking
capacity.
The above board shall be complete with 3 nos. phase
indicating lights, flush mounted Ammeter, Voltmeter, CT's,
PT's, selector switches, protective fuses etc. at Incomer with all
inter connections by min. 2.5 sq.mm. Copper wires.
INCOMER : 250 AMP FP MCCB (25 KA)
BUS BAR : 300 AMP, 500 Volts, 3 phase 50 HZ FP high
conductivity electrolytic Aluminium bus bar with conductivity of
min 57 to 58% of suitable length, insulated by heat shrinkable
sleeves. The current density of bus bar shall be minimum 1.00 sq
mm / amp.
The Maximum allowable temperature for the Bus bar to
be restricted to 85 deg C. The temperature rise should be
restricted
to 35 deg C above ambient temperature.
OUT GOINGS :
9 nos 20 AMP FP MCB (10 KA)
34 nos 20 AMP DP MCB (10 KA) 1 SET
4 Design, manufacture, supply, testing and commissioning
of AC Panel - 2 fabricated out of 16 SWG CRCA sheet steel, IP
42, wall / floor mounting type. The sheet steel shall undergo
minimum 9 tank treatment followed by finishing powder
coating of min 60 micron thickness. the board includes 415
V electrolitic Aluminium Bus Bar, removable gland plates,
cable glands, including connection with outgoing feeders
complete in all respect.
The incoming MCCB shall be thermal-magnetic based with
inbuilt O/L & S/C release with E/F protection and all
Outgoings MCCB's shall be thermal-magnetic based with inbuilt
O/L & S/C release.
All MCCB's shall be Ics = 100% Icu, with rotary handle &
pad locking arrangement, with adjustable O/L & S/C trip setting
as per load requirement. All TP MCCB shall be with solid
isolable neutral link. The breaking capacity specified is Ics value.
All outgoing MCB's shall be C type with 10 KA breaking
capacity.
Sl.
DESCRIPTION QTY UNIT RATE (₹) AMOUNT (₹)
No
The above board shall be complete with 3 nos. phase
indicating lights, flush mounted Ammeter, Voltmeter, CT's,
PT's, selector switches, protective fuses etc. at Incomer with all
inter connections by min. 2.5 sq.mm. Copper wires.
INCOMER : 250 AMP FP MCCB (25 KA)
BUS BAR : 300 AMP, 500 Volts, 3 phase 50 HZ FP
high conductivity electrolytic Aluminium bus bar with
conductivity of min 57 to 58% of suitable length, insulated by
heat shrinkable sleeves. The current density of bus bar shall be
minimum 1.00 sq mm / amp.
The Maximum allowable temperature for the Bus bar to
be restricted to 85 deg C. The temperature rise should be
restricted
to 35 deg C above ambient temperature.
OUT GOINGS :
5 nos 20 AMP FP MCB (10 KA)
40 nos 20 AMP DP MCB (10 KA) 1 SET
L T Breaker (near Transformer)
5 Supply, testing and commissioning of 630 AMP.
Four Pole, 25 KA MCCB along with 4 Nos. LED type indicating
lamp for indicating the status of feeder - ON / OFF / TRIP
due to over current, TRIP due to earth fault. Each lamp
shall be with bakup HRC fuse/MCB.
Make / model :- ABB , L&T, Schneider, Siemens, Legrand.
The Breaker will be provised inside outdoor type enclosure
of suitable size made out of CRCA M.S. sheet 2 mm thick (14
SWG) with locking arrangement (IP-54), powder coated
after proper treatment with 9 tank process, duly fixed on
MS angle iron frame work of size 50mm x 50mm x 6mm, 90
cm long legs out of which 45 cm duly grouted in cement concrete
1:2:4 (1 cement : 2 sand :4 stone aggrete 20mm), The sheet
steel shall undergo minimum 9 tank treatment followed by
finishing powder coating of min 60 micron thickness. The
1 Sets
bottom having removable gland plates, as required, double
compression type cable glands, earth bus, hinged and
lockable doors to achieve dust and vermin proof complete
with all inter connections small wiring by min. 2.5 sq. mm. FRLS
copper wires, ckt labels etc.. The panel feeders shall be
suitable for terminating suitable 2 runs of 3.5 / 4 core
armoured aluminium cable
TOTAL (PART -D)
Sl.
DESCRIPTION QTY UNIT RATE (₹) AMOUNT (₹)
No
QUOTATION OF ELECTRICAL INSTALLATIONS
PART (E) - SUPPLY OF HT & LT CABLES
SUPPLY AND LAYING OF CABLES & ACCESSORIES
1 Supply of ISI marked aluminium conductor XLPE
insulated
cable as per IS 7098, armoured, served, sheathed 1100 volts
grade.
(Make : Finolex / Polycab / Skytone / RR
4 x 10 Sqmm 100 M
4 x 16 Sqmm 300 M
3 1/2 x 150 Sqmm 350 M
3 1/2 x 240 Sqmm 15 M
3 1/2 x 300 Sqmm 150 M
2 Supply of 1000V grade bare copper conductor XLPE low smoke
halogen free insulated with fire rated glass mica tape LSZH
inner and outer sheathed armored fire survival cable,
having fire resistance and all other parameters conforming to
IS- 17505. (For Elevator and Fire Fighting System).
(Make : Polycab / Frtek / KEI / RR)
4 x 10 Sqmm 175 M
3 Supply of ISI marked Copper conductor PVC insulated cable
as per IS 1554 armoured, served, sheathed 1100 volts grade.
(Make : Universal (Satna) / CCI / Nicco / Finolex / Polycab
/
Skytone/ RR)
2 x 1.5 Sqmm 100 M
2 x 4 Sqmm 2,000 M
4 x 4 Sqmm 475 M
4 Laying and testing of aluminium / copper conductor cable
PVC / XLPE insulated armoured, served, sheathed 1100 volts
grade. On surface the cable run shall be fixed by GI clamps
etc. of suitable size or on existing cable tray or inside
existing RCC / HDPE DWC pipe complete in all respect .The
armouring of the cable shall be properly connected with the
earth conductor including fixing of palm or pin type
copper tin plated cable socket (lug) / end terminations to
the cable leads, insulating with tape and making connections
with brass / nickle plated flame proof double
compression glands, providing cable tags complete in all
respect upto the satisfaction of Engineer-in-charge. (The
supply of terminations and glands shall be under seperate item)
Sl.
DESCRIPTION QTY UNIT RATE (₹) AMOUNT (₹)
No
2 x 1.5 Sqmm 100 M 2,912.00
2 x 4 Sqmm 2,000 M 53,760.00
4 x 4 Sqmm 475 M 17,556.00
4 x 10 Sqmm 275 M 14,168.00
4 x 16 Sqmm 300 M 16,464.00
3 1/2 x 150 Sqmm 350 M 29,792.00
3 1/2 x 240 Sqmm 15 M 1,528.80
3 1/2 x 300 Sqmm 150 M 22,680.00
5 Supply and laying of ISI marked Copper conductor PVC
insulated control cable as per IS 1554 PVC sheathed 1100
volts grade. On surface the cable run shall be fixed by GI clamps
etc. of suitable size or on existing cable tray complete in all
respect.The armouring of the cable shall be properly
connected with the earth conductor including fixing of palm
or pin type copper tin plated cable socket (lug) to the
cable leads, insulating with tape and making connections
complete in all respect including end termination, flame proof
double compression glands, including supply of clamps, lugs,
tape etc complete upto the satisfaction of Engineer-in-charge.
(Make : Finolex / Polycab / Skytone / RR)
Armoured
6 x 2.5 Sqmm (DG to Main LT panel interfacing) 150 M
12 x 2.5 Sqmm (2 runs DG controlling) & (
For 375 M
Transformer control wiring)
2 x 4 sq mm armoured (for Battery charging) 150 M
6 Supply of 3 core stranded aluminium conductor 11 KV
grade XLPE (E) (Cross linked Polyethylene) insulated
PVC bedded, Galvanised flat steel strip armoured cable
confirming to IS : 7098 (part II with latest amendments)
(Make : Universal (Satna) / CCI / Nicco / Finolex / Polycab
/
Skytone
185 sq. mm 3 core 50 M
7 Laying and testing of 3 core stranded aluminium conductor
XLPE insulated armoured cable 11 KV grade, at a depth of
900 mm below ground level over a cushion of 100 mm thick fine
river sand alround and protected with well burnt bricks on sides
and on top put across or on surface fixed on GI clamps or on cable
trey or inside pipe etc as required excluding the supply of
sand, bricks and clamps etc. The armouring of the cable shall be
properly connected with earth conductor by clamps etc.
185 sq. mm 3 core 50 M
Sl.
DESCRIPTION QTY UNIT RATE (₹) AMOUNT (₹)
No
8 Supply fixing of plam type heavy duty aluminium cable
socket (lug) to the cable leads, insulating with tape and
making connections etc. complete in all respects as per
direction of Engineer-in-charge.
10 sq.mm. 8 NOS
16 sq.mm. 64 NOS
70 sq.mm. 10 NOS
120 sq.mm. 2 NOS
150 sq.mm. 34 NOS
240 sq.mm. 6 NOS
300 sq.mm. 12 NOS
9 Supply fixing of plam type heavy duty Copper cable
socket (lug) (for Fire Survival Cable) to the cable leads,
insulating with tape and making connections etc. complete in all
respects as per direction of Engineer-in-charge.
10 sq.mm. 24 NOS
10 Supply and fixing brass nickle plated flame proof
double compression glands for PVC / XLPE insulated armoured,
served, sheathed cable including rubber ring etc. complete in all
respect. The armouring of the cable shall be properly
connected with the earth conductor.
10 sqmm 4 core 8 NOS
16 sqmm 4 core 16 NOS
150 sqmm 3 1/2 core 10 NOS
240 sqmm 3 1/2 core 2 NOS
300 sqmm 3 1/2 core 4 NOS
11 Supply and making heat shrinkable type Indoor end
termination Kit of 11 KV XLPE cable. (Make : Raychem / 3M)
185 sq. mm 3 core 5 Set
12 Supply and making heat shrinkable type Outdoor end
termination Kit of 11 KV XLPE cable. (Make : Raychem / 3M)
185 sq. mm 3 core 1 Set
TOTAL (PART -E)
Sl.
DESCRIPTION QTY UNIT RATE (₹) AMOUNT (₹)
No
QUOTATION OF ELECTRICAL INSTALLATIONS
PART (F) - BALANCE WORKS
1 INSTALLATION OF 11 KV PANEL.
The instalation of panel will include receiving, storing,
handling, installation, testing and commissioning,
affecting proper connections with the power and control
cables, coordination with the Panel manufacturers, civil
contractors etc complete in all respects. The small items such
as nut, bolts and other accesories required for erection of panel
will be included in the rates. (The civil work for the foundation
will be seperate)
a 11 KV Panel 1 SET
2 Instalation of Transformer - The instalation of Transformer
will include receiving, storing, handling, installation, testing
and commissioning, affecting proper connections with the
power and control cables, coordination with the transformer
manufacturers / supplier, civil contractors etc complete in all
respects. The small items / accessories required for erection
of transformer will be included in the rates. (The civil work
for the foundation will be seperate)
a 400 KVA 1 SET
3 Installation of Silent Type D G Set - The instalation of D
G Set will include receiving, unloading, loading at
designated place, installation, testing and commissioning,
affecting proper connections with the power and control
cables, coordination with the D G Set supplier, civil
contractors and inlcuding the arrangement of required amount
of fuel oil, lubricating oil, artificial load for testing of first run
etc complete in all respects. The small items / accessories
required for erection of D G Set will be included in the rates.
(The civil work for the D G Set foundation will be seperate)
a 125 KVA 1 SET
b 250 KVA 1 SET
4 INSTALLATION OF PANELS
The installation of panel will include receiving, storing,
handling, installation, testing and commissioning,
affecting proper connections with the power and control
cables, coordination with the Panel manufacturers, civil
contractors etc complete in all respects. The small items such
as nut, bolts and other accesories required for erection of panel
will be included in the rates.
a Main L T Panel 1 SET
Sl.
DESCRIPTION QTY UNIT RATE (₹) AMOUNT (₹)
No
b APFC Panel 1 SET
c L T Breaker (MCCB) (near Transformer) 1 SET
d AC Panel - 1 / 2 2 SET
CABLE TRAY
5 Supply and erection of Perforated type cable trays made out of
prefabricated Galvanized sheet steel including tees, bends,
crossings, reducers, couplings to be laid in cable trenches or
installed over head on wall or hanged from ceiling
including all neccessary supports, brackets at every 1500 mm
c/c, grouting, levelling, suspention and fixing arrangements,
dash fastners, G.I. nuts & bolts complete in all respects.
The support for 1000mm, 900 mm and 750 mm wide cable tray
will be by 50 x 50 x 6 mm MS angle, for 600mm and 450
mm wide cable tray will be by 40 x 40 x 5 mm MS angle, for
300mm wide cable tray will be by 32 x 32 x 5 mm MS angle,
for 150mm wide cable tray will be by 25 x 25 x 4 mm MS angle.
750 mm (W) X 50 mm (H) X 2 mm (T) 35 M
600 mm (W) X 50 mm (H) X 2 mm (T) 25 M
450 mm (W) X 50 mm (H) X 2 mm (T) 35 M
300 mm (W) X 35 mm (H) X 1.5 mm (T) 100 M
150 mm (W) X 35 mm (H) X 1.5 mm (T) (for LV services) 200 M
6 Supply and erection of pregalvanized Ladder type cable
trays made out 25mm x 75mm x 25mm x 2.5mm GI Section all
along (as runner) and 20mm x 30mm x 20mm x 2.5 mm GI
Section (as rungs) at every 250mm interval c/c including tees,
bends, crossings, reducers, couplings to be laid over head on
wall or hanged from ceiling including all neccessary
supports, brackets (50x50x6 MS Angle) at every 1500 mm
c/c, grouting, levelling, suspention and fixing arrangements,
dash fastners, G.I. nuts & bolts complete in all respects.
750 mm (W) X 75 mm (H) 10 M
MISCELLANEOUS ITEMS
7 Providing and fixing M.V. danger notice plate of 200 mm x 150
mm made of mild steel, 2 mm thick and vitreous enamelled
6 NOS
painting white on both sides, and with inscription in single
red
colour on front side as required .
8 Providing and fixing H.V. danger notice plate of 250 mm x 200
mm made of mild steel, 2 mm thick and vitreous enamelled
2 NOS
painting white on both sides, and with inscription in single
red
colour on front side as required .
Sl.
DESCRIPTION QTY UNIT RATE (₹) AMOUNT (₹)
No
9 S/F of shock treatment chart (prescribed under I.E.rules)
duly framed with glass and supported from back with hard
board with supply of all material labour T & P etc for proper 1 NOS
completion of work. (Approx front area = 1.20 sq M)
10 Supply and fixing of First aid box as approved by Indian
1 NOS
red
cross conforming to IS : 2217.
11 Supply of rubber gloves of 11 KV grade as per IS : 4770. 1 Set
12 Supply, laying, jointing, testing and commissioning of ISI
marked (IS : 16205 Part -24 (2018) H.D.P.E. (DWC)
Double wall
Corrugated pipe for cable laying having corrugation on outer
wall and plain smooth surface at inner side including
transportation upto the site, jointing, providing and fixing of
sockets and couplers etc including excavation in all kind of soil
upto 1 meter depth of suitable width with back filling of soil into
trenches to complete the works in all respects. (Make : Duraline /
Jain / Reliance)
47 mm. ID / 63 mm OD 100 M
150 mm. ID / 200 mm OD 150 M
13 Supply and fixing of cable route maker as directed
2 NOS
by
Engg-in- charge.
14 Supplying and laying of 1000 mm wide x 2 mm thick insulated
mat with glowing strip made from highly electrical resistant
elastomer of tested quality to withstand 30 KV dielectric strength
as per IS 15652 6 M
: 2006 complete in all respects. (For LT Panels) (Makes - Marvel,
RMG, Premier, Electromat)
15 Supplying and laying of 1000 mm wide x 2.5 mm thick
insulated mat with glowing strip made from highly
electrical resistant elastomer of tested quality to withstand 30 KV
dielectric strength as per IS 15652 : 2006 complete in all respects. 1 M
(For 11 KV panels) (Makes - Marvel, RMG, Premier, Electromat)
EARTHING
BODY / SAFETY EARTHING (FOR BODY OF ALL ELECTRICAL EQUIPMENTS LIKE TRANSFORMER,
Sl.
DESCRIPTION QTY UNIT RATE (₹) AMOUNT (₹)
No
16 Maintenance Free Earthing : - Supply of Low carbon high
tensile Copper Bonded Ground rods having min 250 micron of
copper coating . The diameter of Rod should be 17.2 mm with the
length of 3000 mm . The ground rod should be UL approved and
tested from CPRI. The earthing include 400 mm square C.I. frame
with hinged cover, masonry housing including excavation and
back filling.
The Rod should be surrounded with Earth Enhance compound of
25 Kg tested as per IEC 62561-2 for the rod & IEC 62561 -7 for 18 NOS
compound. (borh are from same manufacturer)
Exothermic welding shall be used for connection between main
electrode (copper bonded rod) and copper strip of size 32 x 6 mm.
Further GI strips from equipments shall be connected to Copper
strips by means of special bi-matellic connector (i.e. stainless
steel). please refer submitted drawing.
17 Maintenance Free Earthing : - Supply of Low carbon high
tensile Copper Bonded Ground rods having min 250 micron of
copper coating . The diameter of Rod should be 17.2 mm with the
length of 3000 mm . The ground rod should be UL approved and
tested from CPRI. The earthing include 400 mm square C.I. frame
with hinged cover, masonry housing including excavation and
back filling.
The Rod should be surrounded with Earth Enhance compound of
25 Kg tested as per IEC 62561-2 for the rod & IEC 62561 -7 for 6 NOS
compound. (borh are from same manufacturer)
Exothermic welding shall be used for connection between main
electrode (copper bonded rod) and copper strip of size 32 x 6 mm.
Further GI strips from equipments shall be connected to Copper
strips by means of special bi-matellic connector (i.e. stainless
steel). please refer submitted drawing. (For DG Sets &
Transformers)
18 Providing and laying 6 SWG dia G.I. wire under ground
along 100 M
with cable for loop earthing including conections as required
and directed at site.
19 Providing & fixing 25mm x 5mm G.I. strip on surface, in
recess or in ground including connections etc. as required 250 M
(Elevator
Panel & AC Panels).
20 Providing & fixing 32mm x 6mm G.I. strip on surface, in recess
or in ground including connections etc. as required (For Cable
Trays & Pig Tails of Transformer, DG sets & LT Panel & 950 M
Main Earth Grid & Interconnecting Strip).
21 Providing & fixing 32mm x 6mm G.I. strip on surface, in
recess 60 M
or in ground including connections etc. as required (For
Neutral of Transformer & DG sets)
Sl.
DESCRIPTION QTY UNIT RATE (₹) AMOUNT (₹)
No
22 LIGHTNING PROTECTION (CONVENTIONAL) AS PER IS - 62305-3:2010 Vendor / Makes : - DEHN,
Note - Before start working, Vendor should submit final Shop Drawing as per site conditions / requirement after
a) Maintenance Free Earting : - Supply of Low carbon high
tensile Copper Bonded Ground rods having min 250 micron
of copper coating . The diameter of Rod should be 17.2 mm with
the length of 3000 mm . The ground rod should be UL approved
and tested from CPRI. The earthing include 400 mm square C.I.
frame with hinged cover, masonry housing including excavation
and back filling.
The Rod should be surrounded with Earth Enhance compound
of
25 Kg tested as per IEC 62561-2 for the rod & IEC
62561 10 NOS
-7 for compound. (borh are from same manufacturer)
Exothermic welding shall be used for connection between
main electrode (copper bonded rod) and copper strip of size 32
x 6 mm. Further GI strips as down conductor (with test joint)
shall be connected to Copper strips by means of special bi-
matellic connector (i.e. stainless steel). please refer submitted
drawing.
b) Providing & fixing 8 mm dia Al conductor or G.I.tape 20 mm
x
3 mm thick on parapet or surface of wall for lighting 300 M
conductor complete with required numbers of cross
connectors, expansion pieces & horizontal conductor holder as
required ( For horizontal run ).
c) Providing & fixing 8 mm dia Al conductor or G.I.tape 20 mm
x
3 mm thick on parapet or surface of wall for lighting
conductor complete with required numbers of cross 175 M
connectors, expansion pieces & verticcle conductor holder as
required as required ( For vertical run )
d) Providing and fixing testing joint, made of 8 mm dia
Al conductor or 20mm. x 3 mm thick G.I. strip, 125mm. long,
with 4 nos of G.I. bolts, nuts, check nuts and spring 10 Each
washers etc. complete as required.
e) Providing and fixing interception rod of 2 mtr height
complete with stand & concrete block etc. complete as required. 2 Each
f) Providing & laying G.I. tape, 25mm x 5 mm thick,
250 M
from
earth electrode directly in ground as erquired.
Sl.
DESCRIPTION QTY UNIT RATE (₹) AMOUNT (₹)
No
23 Supply, erection, testing and commissioning of steel Two
pole structure of 8 meter height (height of pole to be confirm
from local electricity authority) above ground lavel for receiving
power supply from SEB 11 KV over head line complete with all
the accessories and mounting channels etc consisting of
followings :
Steel structure made out of ISMC 200 and 100x50 MS
channel along with protection, guarding and fencing etc,
insulators and necessary civil foundation work including 1 nos.
11 KV 400 amp 3 pole isolator with handle, 3 nos. 11 KV, 10 KA
station type lightning arrestors, 3 nos. D O Fuses, 2 nos. Earthing
pits with G I Pipe, 50x6 mm GI strip, 6 nos. 11 KV pin 1 Set 0
insulator, necessary ACSR conductors, Pot head (ACSR
conductor to XLPE cable termination) and vertical pipes or cables
complete as required at site.
TOTAL (PART -F)
COST SUMMARY OF EXTERNAL ELECTRICAL WORKS
Sl
DESCRIPTION AMOUNT
No
i) PART (A) - SUPPLY OF HT PANEL Rs.
ii) PART (B) - SUPPLY OF TRANSFORMER Rs.
iii) PART (C) - SUPPLY OF DG SETS Rs.
iv) PART (D) - SUPPLY OF MAIN LT PANELS, CAPACITOR PANEL & AC PANELS Rs.
v) PART (E) - SUPPLY OF HT & LT CABLES Rs.
vi) PART (F) - BALANCE WORKS Rs.
TOTAL COST Rs.