Simense Acb Catalogue
Simense Acb Catalogue
© Siemens AG 2015
1/2 Introduction
1
3WL air circuit breakers/
non-automatic air circuit breakers
up to 6300 A (AC), IEC
1/9 Introduction
1/10 3-pole, fixed-mounted versions
1/17 3-pole, withdrawable versions
1/24 4-pole, fixed-mounted versions
1/31 4-pole, withdrawable versions
1/38 Options
1/45 Accessories and spare parts
Siemens LV 10 · 2015
© Siemens AG 2015
Introduction
1 ■ Overview
Devices Page Applications/ Standards Used in
Individual components
Non-residential
Residential
buildings
buildings
Industry
3WL air circuit breakers/ 1/10 ... As incoming-feeder, distribution, tie, IEC 60947-2, ✓ -- ✓
non-automatic air circuit breakers 1/37 and outgoing-feeder circuit breakers in climate-proof acc. to
up to 6300 A (AC), IEC electrical installations IEC 60068-2-30
For switching and protecting motors,
capacitors, generators, transformers,
busbars and cables
3WL non-automatic air circuit 1/67 ... As incoming-feeder, distribution, tie, IEC 60947-2, ✓ -- ✓
breakers up to 4000 A (DC) 1/69 and outgoing-feeder circuit breakers in climate-proof acc. to
electrical installations IEC 60068-2-30
For switching and protecting motors,
capacitors, generators, transformers,
busbars and cables
Protective device with device holder 1/52 Electronic Trip Unit with protection As for circuit breakers ✓ -- ✓
and optional measurement function functions LI, LSI, LSING and LSIN(G),
(ETU) with or without measurement function
Plus
Rating plugs 1/52 For rated currents In from 250 A to As for circuit breakers ✓ -- ✓
6300 A. The maximum rated current
n = 3 2 0 0 A of the circuit breaker must not be
N S E 0 _ 0 0 9 9 2 b exceeded.
5 1
G F M A T 4 5 B Ground-fault modules 1/52 With alarm and tripping As for circuit breakers ✓ -- ✓
g T R IP A L A R M A L A R M J g (s ) 1 2 Jg
G A .5 .1
B .4 .2
C T R IP .3 .3
D .2 .4
O F F E .1 .5
N S E 0 _ 0 1 0 2 7 a
N S E 0 _ 0 1 6 0 9
Current transformers 1/52 Internal transformers for N conductors, As for circuit breakers ✓ -- ✓
for N conductor protection external transformers for N conductors
N S E 0 _ 0 0 9 9 0 a
Locking devices 1/53 Interlocking set for mechanical ON/OFF, As for circuit breakers ✓ -- ✓
locking devices against unauthorized
closing in operator panels/
for withdrawable circuit breakers,
locking devices for operating
NSE0_00982 mechanism handle with padlock,
locking devices to prevent movement of
the withdrawable circuit breakers,
interlocking systems
Locking mechanisms 1/54 To prevent movement of the As for circuit breakers ✓ -- ✓
withdrawable circuit breakers into
disconnected position, to prevent
opening of the cabinet door in
NSE0_00987 ON position, to prevent opening of the
cabinet door, to prevent movement with
the cabinet door open
Interlocks 1/55 Mutual mechanical interlocking, As for circuit breakers ✓ -- ✓
couplings on the circuit breaker
(with ring) for mutual interlocking,
Bowden wire
NSE0_00989
Introduction
1
Devices Page Applications/ Standards Used in
Individual components
Non-residential
Residential
buildings
buildings
Industry
Transfer control devices Ch. 12 The transfer control device, equipped with two IEC 60947-6-1 ✓ ✓ ✓
3KC ATC5300 motor-driven circuit breakers, serves as a transfer DIN VDE 0660-114
system that automatically or manually switches UL 508
between two power supply systems in low-voltage CSA 22.2 No. 14
power distribution applications.
Test devices 1/55 Manual tester Release 2 for Electronic Trip Units, As for circuit breakers ✓ -- ✓
function testers
Capacitor storage devices 1/55 For shunt releases As for circuit breakers ✓ -- ✓
Indicators, control elements 1/56 Ready-to-close signaling switches, signaling As for circuit breakers ✓ -- ✓
switches, tripped signaling switches,
operating cycles counters,
stored energy status signaling switches,
position signaling switches for guide frames,
electric ON buttons,
motor shutdown switches,
N S E 0 _ 0 0 9 9 5 a EMERGENCY-STOP buttons
Auxiliary conductor 1/57 Male connectors for circuit breakers, As for circuit breakers ✓ -- ✓
connections extension for 1000 V male connector versions,
male connectors and extension for 1000 V,
auxiliary supply connectors for circuit breakers or
N S E 0 _ 0 1 2 6 9
guide frames,
coding kits,
sliding contacts for guide frames,
blanking blocks for circuit breakers
Auxiliary releases 1/58 Closing solenoids/shunt releases, As for circuit breakers ✓ -- ✓
undervoltage releases
Operating mechanisms 1/58 Motorized operating mechanism As for circuit breakers ✓ -- ✓
Door sealing frames, hoods, 1/59 Door sealing frames, IP55 protective covers, As for circuit breakers ✓ -- ✓
shutters shutters
Arc chutes 1/59 Arc chutes, arc chute covers As for circuit breakers ✓ -- ✓
Coding for withdrawable 1/59 By customer, for 36 coding variants As for circuit breakers ✓ -- ✓
version
Grounding connection 1/60 Grounding connection between the guide frame As for circuit breakers ✓ -- ✓
and the withdrawable circuit breaker,
contacting modules for withdrawable circuit
breakers
NSE0 01018a
Support brackets 1/60 For mounting fixed-mounted circuit breakers on As for circuit breakers ✓ -- ✓
vertical plane
CubicleBUS modules 1/60 Digital and analog input and output modules, As for circuit breakers ✓ -- ✓
Zone Selective Interlocking modules
Parameterization systems 1/60 Breaker Data Adapter (BDA), BDA Plus, As for circuit breakers ✓ -- ✓
Connection cables for BDA Plus,
powerconfig parameterization software
Accessories for 1/61 Factory-fitted cables for CubicleBUS modules, As for circuit breakers ✓ -- ✓
communications SENTRON manuals for communication solutions,
voltage transformers
1 2 3 4 5 6 7 8 9 Retrofitting and spare parts 1/61 PROFIBUS retrofit kits, As for circuit breakers ✓ -- ✓
COM15 PROFIBUS modules,
Device
COM16 MODBUS modules,
PROFIBUS DP
CubicleBus MODBUS IEC retrofit kits,
Breaker Status Sensor (BSS),
measurement function Plus
NSE-01025
Main conductor 1/62, Front-accessible main connections with double or As for circuit breakers ✓ -- ✓
connections, 1/63 single hole, rear vertical main connections, rear
fixed-mounted, main horizontal main connections, circuit connecting
conductor connections, flanges, supports for front and DIN connecting
withdrawable bars
NSE-01010
Introduction
1
Degree of protection
With cover IP55 IP55
Without cover IP41 IP41
(with door sealing frame)
Dimensions W mm 320/410 460/590 460/590 704/914 460/590
3-/4-pole Fixed- H mm 434 434 434 434 434
W D mounted D mm 291 291 291 291 291
Withdrawable H mm 465.5 465.5 465.5 465.5 465.5
D mm 471 471 471 471 471
H
NSS0_00535
NSE0_01109a
NSE0_01108a
NSE0_01107a
NSE0_01106a
NSE0_01111a
Rating Plug
Introduction
Breaking capacity 1
Size I II III
Type 3WL11 3WL12 3WL13
Breaking capacity N S H N S H C H C C
N S H N S H C H C C
3-pole 4-pole
Short-circuit breaking capacity
Rated operational voltage Ue
up to 415 V AC
Icu kA 55 66 85 66 80 100 130 100 150 130
Ics kA 55 66 85 66 80 100 130 100 150 130
Icm kA 121 145 187 145 176 220 286 220 330 286
Rated operational voltage Ue
up to 500 V AC
Icu kA 55 66 85 66 80 100 130 100 150 130
Ics kA 55 66 85 66 80 100 130 100 150 130
Icm kA 121 145 187 145 176 220 286 220 330 286
Rated operational voltage Ue
up to 690 V AC
Icu kA 42 50 66 50 75 85 100 85 150 130
Ics kA 42 50 66 50 75 85 100 85 150 130
Icm kA 88 105 145 105 165 187 220 187 330 286
Rated operational voltage Ue
up to 1000 V/1150 V AC
Icu kA -- -- 509) -- -- 50 -- 50 704) 704)
Ics kA -- -- 509) -- -- 50 -- 50 704) 704)
Icm kA -- -- 1059) -- -- 105 -- 105 1544) 1544)
Rated short-time withstand
current Icw3)
0.5 s kA 55 66 75 66 80 100 100 100 100 100
1s kA 42 50 66 55 66 80 100 100 100 100
2s kA 29.5 35 46 39 46 651)/702) 70 80 80 80
3s kA 24 29 44 32 44 501)/652) 65 65 65 65
Rated conditional short-circuit
current Icc of the non-automatic
air circuit breakers
Up to 500 V AC kA 55 66 75 66 80 100 130 100 100 100
Up to 690 V AC kA 42 50 66 50 75 85 100 85 100 100
Up to 1000 V /1150 V AC kA -- -- 509) -- -- 504) -- 504) 704) 704)
Size I II
DC DC
N Circuit breakers with ECO breaking capacity N Abbreviations* English long text Explanation
Circuit breakers with standard breaking capacity S (functions)
S
L Long Time Delay Overload protection
H Circuit breakers with high breaking capacity H
S Short Time Delay Short-circuit protection
C Circuit breakers with very high breaking capacity C (short-time delayed)
Non-automatic air circuit breakers with DC breaking capacity I Instantaneous Short-circuit protection
DC (instantaneous)
These breaking capacities are indicated in the corresponding tables by N Neutral Protection Neutral conductor protection
the symbols shown on orange backgrounds. G Ground Fault Ground-fault protection
Note: * Designations according to IEC 60947-2, Appendix K.
For further technical specifications, see the configuration
manual "Air Circuit Breakers". Free download from: 4)
Rated operational voltage Ue = 1150 V.
www.siemens.com/lowvoltage/manuals 5)
At Ue = 220 V DC.
6)
1) At Ue = 300 V DC.
Size II with In max. ≤ 2500 A. 7)
2) At Ue = 600 V DC.
Size II with In max. = 3200 A and In max. = 4000 A. 8)
3) At Ue = 1000 V DC.
At a rated voltage of ≥ 690 V, the Icw value of the circuit breaker cannot be 9)
greater than the Icu or Ics value at 690 V. Values also apply to 690 V + 20 % version with Z-option "A16".
Introduction
1 3WL air circuit breakers:
3WL air circuit breakers are extremely flexible in use and offer
consistent communication capability. With the 3WL circuit
breakers, just three sizes cover a performance range of
630 A to 6300 A. All models are characterized by the same
design, the same operation and the same comprehensive
accessories.
7
2
3 8
5
4
9
1
25
21
10
19
22 11
23
12
24 18 13
17
14
NSE0_01887d
20
16
15
$ Guide frame (pages 1/46 to 1/51) 4 Operating cycles counters (pages 1/40 and 1/56)
% Main circuit connection front, flange, horizontal, vertical 5 Breaker status sensor (BSS) (pages 1/41 and 1/61)
(pages 1/43, 1/62 and 1/63) 6 Protective device with device holder, Electronic Trip Unit (ETU)
& Position signaling switch (pages 1/41 and 1/56) (page 1/52)
( Grounding connection, leading (page 1/60) 7 Remote reset solenoid (pages 1/40 and 1/53)
) Shutters (pages 1/41 and 1/59) 8 Breaker data adapter (BDA Plus) (page 1/60)
* COM15 PROFIBUS module or COM16 MODBUS module 9 Four-line display (page 1/52)
(pages 1/41 and 1/61) : Ground-fault protection module (page 1/52)
+ External CubicleBUS modules (page 1/60) ; Rating plug (pages 1/39 and 1/52)
, Closing coil, auxiliary release (pages 1/38, 1/40 and 1/58) < Measurement function module (pages 1/41 and 1/52)
- Auxiliary conductor plug-in system (pages 1/42 and 1/57) = Circuit breaker (pages 1/10 to 1/37)
. Auxiliary switch block (pages 1/38 and 1/58)
/ Door sealing frame (pages 1/40 and 1/59)
0 Interlocking set for mechanical ON/OFF (page 1/53)
1 Transparent panel, function insert (page 1/53)
2 EMERGENCY-STOP pushbutton, key operated (page 1/56)
3 Motorized operating mechanism (pages 1/40 and 1/58)
Introduction
Communication-capable circuit breakers (with ETU45B or ETU76B Electronic Trip Unit) 1
20
Ethernet
18
19
PROFIBUS
PROFINET
13 14 15 16 17 7
4 5 6 21
CubicleBUS
3VA-line 3VA-line 9
10 8
2
1 1 1 11
12
NSE0_01105n
3
Introduction
1
11
6 7 8 10
3VA-line 3VA-line
9
5
3
1 1 1 2 4
I201_19162
1 3VA Molded Case Circuit Breakers 7 COM100 breaker data server
2 3WL air circuit breaker 8 7KM PAC4200 measuring device
3 COM16 MODBUS module 9 7KM PAC3100 measuring device
4 3VL molded case circuit breaker 10 7KM PAC3200 measuring device
5 COM21 MODBUS module 11 powerconfig configuration software from V2.3
6 COM800 breaker data server
Characteristics
• Coordinated communication concept using the PROFIBUS DP Communication:
or MODBUS, ranging from 16 A to 6300 A with 3VL molded • For air circuit breakers with optional communication function
case circuit breakers and 3WL air circuit breakers (ETU45B or ETU76B Electronic Trip Unit),
• The high level of modularity of circuit breakers and accessories see pages 1/10 to 1/37
allows easy retrofitting of all communication components • For accessories, see pages 1/60 and 1/61
• Significant additional benefits for the switchboard due to the • For more information, see also chapters "Measuring Devices
possibility of linking up external input and output modules to and Power Monitoring" and "Software"
the circuit breaker-internal CubicleBUS of the 3WL air circuit
breaker
• Innovative software products for parameterization, operation,
monitoring, and diagnostics of circuit breakers, both locally or
via PROFIBUS DP, MODBUS or Ethernet/Intranet/Internet
• Complete integration of the circuit breakers into the Totally
Integrated Power and Totally Integrated Automation solutions
■ Benefits • Measured values are the basis for efficient load management, 1
for drawing up power demand profiles and for allocating
Low space requirements energy to cost centers
• Preventive maintenance reduces the risk of expensive plant
The 3WL air circuit breakers require very little space. downtimes
Size I devices (up to 2000 A) fit into a 400 mm wide switchboard
• Measurement function with a very wide range of measured
panel. Size III devices (up to 6300 A) are the smallest of their
values, such as current, voltage, energy, power etc.
kind and with their construction width of 704 mm fit into an
800 mm wide switchboard panel. • Can be used in 690 V networks
Conductor cross-sections
Size I II
Type Up to 3WL11 12 3WL11 16 3WL11 20 3WL12 08 3WL12 10 3WL12 12 3WL12 16 3WL12 20
3WL11 10
Permissible load • Up to 55 °C (Cu bare) A 1000 1250 1600 2000 800 1000 1250 1600 2000
for withdrawable • Up to 60 °C A 1000 1250 1600 1930 800 1000 1250 1600 2000
versions (Cu bare)1) A
at rear horizontal • Up to 70 °C 1000 1210 14902) 1780 800 1000 1250 1600 2000
main connections (Cu painted black)1)
Main conductor • Copper bars, Unit(s) 1 × 2× 2× 3× 1× 1× 2× 2× 3×
minimum bare mm2 60 × 10 40 × 10 50 × 10 50 × 10 50 × 10 60 × 10 40 × 10 50 × 10 50 × 10
cross-sections Unit(s) 1× 2× 2× 3× 1× 1× 2× 2× 3×
• Copper bars,
painted black mm2 60 × 10 40 × 10 50 × 10 50 × 10 50 × 10 60 × 10 40 × 10 50 × 10 50 × 10
Size II III
Type 3WL12 25 3WL12 32 3WL12 403) 3WL13 40 3WL13 50 3WL13 633)
Permissible load • Up to 55 °C (Cu bare) A 2500 3200 39504) 4000 5000 5920
for withdrawable • Up to 60 °C (Cu A 2500 3020 3810 4000 5000 5810
versions at rear bare)1) A
horizontal main • Up to 70 °C 2280 2870 3600 4000 5000 5500
connections (Cu painted black)1)
Main conductor • Copper bars, Unit(s) 2 × 3× 4× 4x 6x 6x
minimum bare mm2 100 × 10 100 × 10 120 × 10 100 x 10 100 x 10 120 x 10
cross-sections • Copper bars, Unit(s) 2 × 3× 4× 4× 6× 6×
painted black mm2 100 × 10 100 × 10 100 × 105) 100 × 10 100 × 10 120 × 10
1) ETU76B with graphics display can be used up to max. 55 °C
2) At breaking capacity H: 1600 A up to 70 °C
3) With rear vertical connections
4) Size II, 3-pole, in fixed-mounted version
5) Minimum main conductor cross-sections for 4-pole withdrawable circuit
breakers: 4 × 120 mm × 10 mm
Additional
Options price
Non-automatic air circuit Without Electronic Trip Units AA None
breakers2)
Electronic Trip Units Versions without ground-fault
protection
ETU15B: Protection functions LI6) BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN3) EB ✓
ETU45B: Protection functions LSIN3) FB ✓
with 4-line display
ETU76B: Protection functions LSIN3) NB ✓
with graphics display
Versions with ground-fault
protection
ETU27B: Protection functions LSING4) DG ✓
ETU45B: Protection functions EG ✓
LSING3)5)
ETU45B: Protection functions FG ✓
LSING3)5) with 4-line display
ETU76B: Protection functions NG ✓
LSING3)5) with graphics display
Operating mechanism, Manual operating mechanism with 1AA2 None
auxiliary release, mechanical closing, without 1st and
auxiliary switch 2nd auxiliary releases; auxiliary switch
2 NC + 2 NO
For further Article No. supplements,
see page 1/38
✓ Additional price 3) Current transformers for protection of the N conductor and current trans-
1) The rated current is determined by the rating plug. For the standard formers for detection of the ground-fault current in the grounded neutral
version, the supplied module is equal to the maximum rated current. point of the transformer are to be ordered separately, see page 1/52.
If a lower rated current is required, adaptation by order code on page 1/39. 4) Current transformers for protection of the N conductor are to be ordered
2) For permissible rated short-time current Icc and rated short-circuit making separately, see page 1/52.
capacity Icm for non-automatic air circuit breakers, see page 1/5. 5) ETU45B and ETU76B with ground-fault protection module GFM AT
(alarm and tripping), see page 1/52.
6) ETU15B cannot be used with 3WL circuit breakers, size III.
Additional
Options price
Non-automatic air circuit Without Electronic Trip Units AA None
breakers2)
Electronic Trip Units Versions without ground-fault
protection
ETU15B: Protection functions LI6) BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN3) EB ✓
ETU45B: Protection functions LSIN3) FB ✓
with 4-line display
ETU76B: Protection functions LSIN3) NB ✓
with graphics display
Versions with ground-fault
protection
ETU27B: Protection functions LSING4) DG ✓
ETU45B: Protection functions EG ✓
LSING3)5)
ETU45B: Protection functions FG ✓
LSING3)5) with 4-line display
ETU76B: Protection functions NG ✓
LSING3)5) with graphics display
Operating mechanism, Manual operating mechanism with 1AA2 None
auxiliary release, mechanical closing, without 1st and
auxiliary switch 2nd auxiliary releases; auxiliary switch
2 NC + 2 NO
For further Article No. supplements,
see page 1/38
✓ Additional price 3) Current transformers for protection of the N conductor and current trans-
1) The rated current is determined by the rating plug. For the standard formers for detection of the ground-fault current in the grounded neutral
version, the supplied module is equal to the maximum rated current. point of the transformer are to be ordered separately, see page 1/52.
If a lower rated current is required, adaptation by order code on page 1/39. 4) Current transformers for protection of the N conductor are to be ordered
2) For permissible rated short-time current Icc and rated short-circuit making separately, see page 1/52.
capacity Icm for non-automatic air circuit breakers, see page 1/5. 5) ETU45B and ETU76B with ground-fault protection module GFM AT
(alarm and tripping), see page 1/52.
6) ETU15B cannot be used with 3WL circuit breakers, size III.
Additional
Options price
Non-automatic air circuit Without Electronic Trip Units AA None
breakers2)
Electronic Trip Units Versions without ground-fault
protection
ETU15B: Protection functions LI6) BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN3) EB ✓
ETU45B: Protection functions LSIN3) FB ✓
with 4-line display
3)
ETU76B: Protection functions LSIN NB ✓
with graphics display
Versions with ground-fault
protection
ETU27B: Protection functions DG ✓
LSING4)
ETU45B: Protection functions EG ✓
LSING3)5)
ETU45B: Protection functions FG ✓
LSING3)5) with 4-line display
ETU76B: Protection functions NG ✓
LSING3)5) with graphics display
Operating mechanism, Manual operating mechanism with 1AA2 None
auxiliary release, mechanical closing, without 1st and
auxiliary switch 2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO
For further Article No. supplements,
see page 1/38
3)
✓ Additional price Current transformers for protection of the N conductor and current trans-
1)
The rated current is determined by the rating plug. For the standard formers for detection of the ground-fault current in the grounded neutral
version, the supplied module is equal to the maximum rated current. point of the transformer are to be ordered separately, see page 1/52.
4)
If a lower rated current is required, adaptation by order code on page 1/39. Current transformers for protection of the N conductor are to be ordered
2)
For permissible rated short-time current Icc and rated short-circuit making separately, see page 1/52.
5)
capacity Icm for non-automatic air circuit breakers, see page 1/5. ETU45B and ETU76B with ground-fault protection module GFM AT
(alarm and tripping), see page 1/52.
6)
ETU15B cannot be used with 3WL circuit breakers, size III.
Additional
Options price
Non-automatic air circuit Without Electronic Trip Units AA None
breakers2)
Electronic Trip Units Versions without ground-fault
protection
ETU15B: Protection functions LI6) BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN3) EB ✓
ETU45B: Protection functions LSIN3) FB ✓
with 4-line display
ETU76B: Protection functions LSIN3) NB ✓
with graphics display
Versions with ground-fault
protection
ETU27B: Protection functions DG ✓
LSING4)
ETU45B: Protection functions EG ✓
LSING3)5)
ETU45B: Protection functions FG ✓
LSING3)5) with 4-line display
ETU76B: Protection functions NG ✓
LSING3)5) with graphics display
Operating mechanism, Manual operating mechanism with 1AA2 None
auxiliary release, mechanical closing, without 1st and
auxiliary switch 2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO
For further Article No. supplements,
see page 1/38
3)
✓ Additional price Current transformers for protection of the N conductor and current trans-
1)
The rated current is determined by the rating plug. For the standard formers for detection of the ground-fault current in the grounded neutral
version, the supplied module is equal to the maximum rated current. point of the transformer are to be ordered separately, see page 1/52.
4)
If a lower rated current is required, adaptation by order code on page 1/39. Current transformers for protection of the N conductor are to be ordered
2)
For permissible rated short-time current Icc and rated short-circuit making separately, see page 1/52.
5)
capacity Icm for non-automatic air circuit breakers, see page 1/5. ETU45B and ETU76B with ground-fault protection module GFM AT
(alarm and tripping), see page 1/52.
6)
ETU15B cannot be used with 3WL circuit breakers, size III.
Additional
Options price
Non-automatic air circuit Without Electronic Trip Units AA None
breakers2)
Electronic Trip Units Versions without ground-fault
protection
ETU15B: Protection functions LI6) BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN3) EB ✓
ETU45B: Protection functions LSIN3) FB ✓
with 4-line display
ETU76B: Protection functions LSIN3) NB ✓
with graphics display
Versions with ground-fault
protection
ETU27B: Protection functions LSING4) DG ✓
ETU45B: Protection functions EG ✓
LSING3)5)
ETU45B: Protection functions FG ✓
LSING3)5) with 4-line display
ETU76B: Protection functions NG ✓
LSING3)5) with graphics display
Operating mechanism, Manual operating mechanism with 1AA2 None
auxiliary release, mechanical closing, without 1st and
auxiliary switch 2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO
For further Article No. supplements,
see page 1/38
4)
✓ Additional price Current transformers for protection of the N conductor are to be ordered
1) separately, see page 1/52.
The rated current is determined by the rating plug. For the standard
5)
version, the supplied module is equal to the maximum rated current. ETU45B and ETU76B with ground-fault protection module GFM AT
If a lower rated current is required, adaptation by order code on page 1/39. (alarm and tripping), see page 1/52.
2) For permissible rated short-time current I and rated short-circuit making 6) ETU15B cannot be used with 3WL circuit breakers, size III.
cc
capacity Icm for non-automatic air circuit breakers, see page 1/5.
3)
Current transformers for protection of the N conductor and current trans-
formers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 1/52.
Additional
Options price
Non-automatic air circuit Without Electronic Trip Units AA None
breakers2)
Electronic Trip Units Versions without ground-fault
protection
ETU15B: Protection functions LI6) BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN3) EB ✓
ETU45B: Protection functions LSIN3) FB ✓
with 4-line display
ETU76B: Protection functions LSIN3) NB ✓
with graphics display
Versions with ground-fault
protection
ETU27B: Protection functions DG ✓
LSING4)
ETU45B: Protection functions EG ✓
LSING3)5)
ETU45B: Protection functions FG ✓
LSING3)5) with 4-line display
ETU76B: Protection functions NG ✓
LSING3)5) with graphics display
Operating mechanism, Manual operating mechanism with 1AA2 None
auxiliary release, mechanical closing, without 1st and
auxiliary switch 2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO
For further Article No. supplements,
see page 1/38
✓ Additional price 3) Current transformers for protection of the N conductor and current trans-
1) The rated current is determined by the rating plug. For the standard formers for detection of the ground-fault current in the grounded neutral
version, the supplied module is equal to the maximum rated current. point of the transformer are to be ordered separately, see page 1/52.
If a lower rated current is required, adaptation by order code on page 1/39. 4) Current transformers for protection of the N conductor are to be ordered
2) For permissible rated short-time current Icc and rated short-circuit making separately, see page 1/52.
capacity Icm for non-automatic air circuit breakers, see page 1/5. 5) ETU45B and ETU76B with ground-fault protection module GFM AT
(alarm and tripping), see page 1/52.
6) ETU15B cannot be used with 3WL circuit breakers, size III.
Additional
Options price
Non-automatic air circuit Without Electronic Trip Units AA None
breakers2)
Electronic Trip Units Versions without ground-fault
protection
ETU15B: Protection functions LI3) BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN4) EB ✓
ETU45B: Protection functions LSIN4) FB ✓
with 4-line display
ETU76B: Protection functions LSIN4) NB ✓
with graphics display
Versions with ground-fault
protection
ETU27B: Protection functions DG ✓
LSING5)
ETU45B: Protection functions EG ✓
LSING4)6)
ETU45B: Protection functions FG ✓
LSING4)6) with 4-line display
ETU76B: Protection functions NG ✓
LSING4)6) with graphics display
Operating mechanism, Manual operating mechanism with 1AA2 None
auxiliary release, mechanical closing, without 1st and
auxiliary switch 2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO
For further Article No. supplements,
see page 1/38
3)
✓ Additional price ETU15B cannot be used with 3WL circuit breakers, size III.
1) 4)
The rated current is determined by the rating plug. For the standard Current transformers for protection of the N conductor and current trans-
version, the supplied module is equal to the maximum rated current. formers for detection of the ground-fault current in the grounded neutral
If a lower rated current is required, adaptation by order code on page 1/39. point of the transformer are to be ordered separately, see page 1/52.
2) 5)
For permissible rated short-time current Icc and rated short-circuit making Current transformers for protection of the N conductor are to be ordered
capacity Icm for non-automatic air circuit breakers, see page 1/5. separately, see page 1/52.
6)
ETU45B and ETU76B with ground-fault protection module GFM AT
(alarm and tripping), see page 1/52.
Additional
Options price
Non-automatic air circuit Without Electronic Trip Units AA None
breakers3)
Electronic Trip Units Versions without ground-fault
protection
ETU15B: Protection functions LI BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN4) EB ✓
ETU45B: Protection functions LSIN4) FB ✓
with 4-line display
ETU76B: Protection functions LSIN4) NB ✓
with graphics display
Versions with ground-fault
protection
ETU27B: Protection functions DG ✓
LSING5)
ETU45B: Protection functions EG ✓
LSING4)6)
ETU45B: Protection functions FG ✓
LSING4)6) with 4-line display
ETU76B: Protection functions NG ✓
LSING4)6) with graphics display
Operating mechanism, Manual operating mechanism with 1AA2 None
auxiliary release, mechanical closing, without 1st and
auxiliary switch 2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO
For further Article No. supplements,
see page 1/38
4)
✓ Additional price Current transformers for protection of the N conductor and current trans-
1)
The rated current is determined by the rating plug. For the standard formers for detection of the ground-fault current in the grounded neutral
version, the supplied module is equal to the maximum rated current. point of the transformer are to be ordered separately, see page 1/52.
5)
If a lower rated current is required, adaptation by order code on page 1/39. Current transformers for protection of the N conductor are to be ordered
2)
Z options which are installed on the guide frame are not available. separately, see page 1/52.
6)
3)
For permissible rated short-time current Icc and rated short-circuit making ETU45B to ETU76B with ground-fault protection module GFM AT
capacity Icm for non-automatic air circuit breakers, see page 1/5. (alarm and tripping), see page 1/52.
Additional
Options price
Non-automatic air circuit Without Electronic Trip Units AA None
breakers3)
Electronic Trip Units Versions without ground-fault
protection
ETU15B: Protection functions LI BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN4) EB ✓
ETU45B: Protection functions LSIN4) FB ✓
with 4-line display
ETU76B: Protection functions LSIN4) NB ✓
with graphics display
Versions with ground-fault
protection
ETU27B: Protection functions DG ✓
LSING5)
ETU45B: Protection functions EG ✓
LSING4)6)
ETU45B: Protection functions FG ✓
LSING4)6) with 4-line display
ETU76B: Protection functions NG ✓
LSING4)6) with graphics display
Operating mechanism, Manual operating mechanism with 1AA2 None
auxiliary release, mechanical closing, without 1st and
auxiliary switch 2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO
For further Article No. supplements,
see page 1/38
✓ Additional price 4) Current transformers for protection of the N conductor and current trans-
1) The rated current is determined by the rating plug. For the standard formers for detection of the ground-fault current in the grounded neutral
version, the supplied module is equal to the maximum rated current. point of the transformer are to be ordered separately, see page 1/52.
If a lower rated current is required, adaptation by order code on page 1/39. 5) Current transformers for protection of the N conductor are to be ordered
2) Z options which are installed on the guide frame are not available. separately, see page 1/52.
6) ETU45B to ETU76B with ground-fault protection module GFM AT
3) For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers, see page 1/5. (alarm and tripping), see page 1/52.
Additional
Options price
Non-automatic air circuit Without Electronic Trip Units AA None
breakers3)
Electronic Trip Units Versions without ground-fault
protection
ETU15B: Protection functions LI BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN4) EB ✓
ETU45B: Protection functions LSIN4) FB ✓
with 4-line display
ETU76B: Protection functions LSIN4) NB ✓
with graphics display
Versions with ground-fault
protection
ETU27B: Protection functions DG ✓
LSING5)
ETU45B: Protection functions EG ✓
LSING4)6)
ETU45B: Protection functions FG ✓
LSING4)6) with 4-line display
ETU76B: Protection functions NG ✓
LSING4)6) with graphics display
Operating mechanism, Manual operating mechanism with 1AA2 None
auxiliary release, mechanical closing, without 1st and
auxiliary switch 2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO
For further Article No. supplements,
see page 1/38
4)
✓ Additional price Current transformers for protection of the N conductor and current trans-
1)
The rated current is determined by the rating plug. For the standard formers for detection of the ground-fault current in the grounded neutral
version, the supplied module is equal to the maximum rated current. point of the transformer are to be ordered separately, see page 1/52.
5)
If a lower rated current is required, adaptation by order code on page 1/39. Current transformers for protection of the N conductor are to be ordered
2)
Z options which are installed on the guide frame are not available. separately, see page 1/52.
6)
3)
For permissible rated short-time current Icc and rated short-circuit making ETU45B to ETU76B with ground-fault protection module GFM AT
capacity Icm for non-automatic air circuit breakers, see page 1/5. (alarm and tripping), see page 1/52.
Additional
Options price
Non-automatic air circuit Without Electronic Trip Units AA None
breakers3)
Electronic Trip Units Versions without ground-fault
protection
ETU15B: Protection functions LI BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN4) EB ✓
ETU45B: Protection functions LSIN4) FB ✓
with 4-line display
ETU76B: Protection functions LSIN4) NB ✓
with graphics display
Versions with ground-fault
protection
ETU27B: Protection functions DG ✓
LSING5)
ETU45B: Protection functions EG ✓
LSING4)6)
ETU45B: Protection functions FG ✓
LSING4)6) with 4-line display
ETU76B: Protection functions NG ✓
LSING4)6) with graphics display
Operating mechanism, Manual operating mechanism with 1AA2 None
auxiliary release, mechanical closing, without 1st and
auxiliary switch 2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO
For further Article No. supplements,
see page 1/38
4)
✓ Additional price Current transformers for protection of the N conductor and current trans-
1)
The rated current is determined by the rating plug. For the standard formers for detection of the ground-fault current in the grounded neutral
version, the supplied module is equal to the maximum rated current. point of the transformer are to be ordered separately, see page 1/52.
5)
If a lower rated current is required, adaptation by order code on page 1/39. Current transformers for protection of the N conductor are to be ordered
2)
Z options which are installed on the guide frame are not available. separately, see page 1/52.
6)
3)
For permissible rated short-time current Icc and rated short-circuit making ETU45B to ETU76B with ground-fault protection module GFM AT
capacity Icm for non-automatic air circuit breakers, see page 1/5. (alarm and tripping), see page 1/52.
Additional
Options price
Non-automatic air circuit Without Electronic Trip Units AA None
breakers3)
Electronic Trip Units Versions without ground-fault
protection
ETU15B: Protection functions LI7) BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN4) EB ✓
ETU45B: Protection functions LSIN4) FB ✓
with 4-line display
ETU76B: Protection functions LSIN4) NB ✓
with graphics display
Versions with ground-fault
protection
ETU27B: Protection functions LSING5) DG ✓
ETU45B: Protection functions EG ✓
LSING4)6)
ETU45B: Protection functions FG ✓
LSING4)6) with 4-line display
ETU76B: Protection functions NG ✓
LSING4)6) with graphics display
Operating mechanism, Manual operating mechanism with 1AA2 None
auxiliary release, mechanical closing, without 1st and
auxiliary switch 2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO
For further Article No. supplements,
see page 1/38
4)
✓ Additional price Current transformers for protection of the N conductor and current trans-
1) The rated current is determined by the rating plug. For the standard formers for detection of the ground-fault current in the grounded neutral
version, the supplied module is equal to the maximum rated current. point of the transformer are to be ordered separately, see page 1/52.
5) Current transformers for protection of the N conductor are to be ordered
If a lower rated current is required, adaptation by order code on page 1/39.
2) separately, see page 1/52.
Z options which are installed on the guide frame are not available.
3) 6)
For permissible rated short-time current Icc and rated short-circuit making ETU45B to ETU76B with ground-fault protection module GFM AT
capacity Icm for non-automatic air circuit breakers, see page 1/5. (alarm and tripping), see page 1/52.
7)
ETU15B cannot be used with 3WL circuit breakers, size III.
Additional
Options price
Non-automatic air circuit Without Electronic Trip Units AA None
breakers3)
Electronic Trip Units Versions without ground-fault
protection
ETU15B: Protection functions LI7) BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN4) EB ✓
ETU45B: Protection functions LSIN4) FB ✓
with 4-line display
ETU76B: Protection functions LSIN4) NB ✓
with graphics display
Versions with ground-fault
protection
ETU27B: Protection functions LSING5) DG ✓
ETU45B: Protection functions EG ✓
LSING4)6)
ETU45B: Protection functions FG ✓
LSING4)6) with 4-line display
ETU76B: Protection functions NG ✓
LSING4)6) with graphics display
Operating mechanism, auxil- Manual operating mechanism with 1AA2 None
iary release, auxiliary switch mechanical closing, without 1st and
2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO
For further Article No. supplements,
see page 1/38
✓ Additional price 4) Current transformers for protection of the N conductor and current trans-
1)
The rated current is determined by the rating plug. For the standard formers for detection of the ground-fault current in the grounded neutral
version, the supplied module is equal to the maximum rated current. point of the transformer are to be ordered separately, see page 1/52.
5)
If a lower rated current is required, adaptation by order code on page 1/39. Current transformers for protection of the N conductor are to be ordered
2)
Z options which are installed on the guide frame are not available. separately, see page 1/52.
6)
3) For permissible rated short-time current I and rated short-circuit making ETU45B to ETU76B with ground-fault protection module GFM AT
cc
capacity Icm for non-automatic air circuit breakers, see page 1/5. (alarm and tripping), see page 1/52.
7) ETU15B cannot be used with 3WL circuit breakers, size III.
Additional
Options price
Non-automatic air circuit Without Electronic Trip Units AA None
breakers3)
Electronic Trip Units Versions without ground-fault
protection
ETU15B: Protection functions LI4) BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN5) EB ✓
ETU45B: Protection functions LSIN5) FB ✓
with 4-line display
ETU76B: Protection functions LSIN5) NB ✓
with graphics display
Versions with ground-fault
protection
ETU27B: Protection functions DG ✓
LSING6)
ETU45B: Protection functions EG ✓
LSING5)7)
ETU45B: Protection functions FG ✓
LSING5)7) with 4-line display
ETU76B: Protection functions NG ✓
LSING5)7) with graphics display
Operating mechanism, Manual operating mechanism with 1AA2 None
auxiliary release, mechanical closing, without 1st and
auxiliary switch 2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO
For further Article No. supplements,
see page 1/38
4)
✓ Additional price ETU15B cannot be used with 3WL circuit breakers, size III.
1) 5)
The rated current is determined by the rating plug. For the standard Current transformers for protection of the N conductor and current trans-
version, the supplied module is equal to the maximum rated current. formers for detection of the ground-fault current in the grounded neutral
If a lower rated current is required, adaptation by order code on page 1/39. point of the transformer are to be ordered separately, see page 1/52.
2) 6)
Z options which are installed on the guide frame are not available. Current transformers for protection of the N conductor are to be ordered
3)
For permissible rated short-time current Icc and rated short-circuit making separately, see page 1/52.
7)
capacity Icm for non-automatic air circuit breakers, see page 1/5. ETU45B to ETU76B with ground-fault protection module GFM AT
(alarm and tripping), see page 1/52.
Additional
Options price
Non-automatic air circuit Without Electronic Trip Units AA None
breakers2)
Electronic Trip Units Versions without ground-fault
protection
ETU15B: Protection functions LI BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN3) EB ✓
ETU45B: Protection functions LSIN3) FB ✓
with 4-line display
ETU76B: Protection functions LSIN3) NB ✓
with graphics display
Versions with ground-fault
protection
ETU27B: Protection functions DG ✓
LSING3)
ETU45B: Protection functions EG ✓
LSING3)4)
ETU45B: Protection functions FG ✓
LSING3)4) with 4-line display
ETU76B: Protection functions NG ✓
LSING3)4) with graphics display
Operating mechanism, Manual operating mechanism with
auxiliary release, mechanical closing, without 1st and 1AA2 None
auxiliary switch 2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO
For further Article No. supplements,
see page 1/38
3)
✓ Additional price Current transformers for protection of the N conductor and current trans-
1)
The rated current is determined by the rating plug. For the standard formers for detection of the ground-fault current in the grounded neutral
version, the supplied module is equal to the maximum rated current. point of the transformer are to be ordered separately, see page 1/52. The
If a lower rated current is required, adaptation by order code on page 1/39. internal current transformers for N conductors can be ordered by adding
2)
the supplement "–Z" and the order code "F23", see page 1/41.
For permissible rated short-time current Icc and rated short-circuit making 4)
capacity Icm for non-automatic air circuit breakers, see page 1/5. ETU45B to ETU76B with ground-fault protection module GFM AT
(alarm and tripping), see page 1/52.
Size Max. rated circuit Rated current1) Breaking capacity DT Icu 55/66 kA at 500 V, PU PS*/ PG Weight
1
breaker current In Icu = Ics ECO breaking capacity N N (UNIT, P. unit per PU
In max. SET, M) approx.
Article No. Basic price
www.siemens.com/ per PU
product?Article No.
A A kA kg
Front main circuit connection, single hole
I 630 630 55 3WL1106-2@@43-@@@@ 1 1 unit 103 50.000
800 800 3WL1108-2@@43-@@@@ 1 1 unit 103 50.000
1000 1000 3WL1110-2@@43-@@@@ 1 1 unit 103 50.000
1250 1250 3WL1112-2@@43-@@@@ 1 1 unit 103 50.000
1600 1600 3WL1116-2@@43-@@@@ 1 1 unit 103 50.000
II 800 800 66 3WL1208-2@@43-@@@@ 1 1 unit 103 67.000
1000 1000 3WL1210-2@@43-@@@@ 1 1 unit 103 67.000
1250 1250 3WL1212-2@@43-@@@@ 1 1 unit 103 67.000
1600 1600 3WL1216-2@@43-@@@@ 1 1 unit 103 67.000
2000 2000 3WL1220-2@@43-@@@@ 1 1 unit 103 67.000
2500 2500 3WL1225-2@@43-@@@@ 1 1 unit 103 71.000
3200 3200 3WL1232-2@@43-@@@@ 1 1 unit 103 77.000
Front main circuit connection, double hole
I 630 630 55 3WL1106-2@@44-@@@@ 1 1 unit 103 50.000
800 800 3WL1108-2@@44-@@@@ 1 1 unit 103 50.000
1000 1000 3WL1110-2@@44-@@@@ 1 1 unit 103 50.000
1250 1250 3WL1112-2@@44-@@@@ 1 1 unit 103 50.000
1600 1600 3WL1116-2@@44-@@@@ 1 1 unit 103 50.000
2000 2000 3WL1120-2@@44-@@@@ 1 1 unit 103 50.000
II 800 800 66 3WL1208-2@@44-@@@@ 1 1 unit 103 67.000
1000 1000 3WL1210-2@@44-@@@@ 1 1 unit 103 67.000
1250 1250 3WL1212-2@@44-@@@@ 1 1 unit 103 67.000
1600 1600 3WL1216-2@@44-@@@@ 1 1 unit 103 67.000
2000 2000 3WL1220-2@@44-@@@@ 1 1 unit 103 67.000
2500 2500 3WL1225-2@@44-@@@@ 1 1 unit 103 71.000
3200 3200 3WL1232-2@@44-@@@@ 1 1 unit 103 77.000
Additional
Options price
Non-automatic air circuit Without Electronic Trip Units AA None
breakers2)
Electronic Trip Units Versions without ground-fault
protection
ETU15B: Protection functions LI BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN3) EB ✓
ETU45B: Protection functions LSIN3) FB ✓
with 4-line display
ETU76B: Protection functions LSIN3) NB ✓
with graphics display
Versions with ground-fault
protection
ETU27B: Protection functions DG ✓
LSING3)
ETU45B: Protection functions EG ✓
LSING3)4)
ETU45B: Protection functions FG ✓
LSING3)4) with 4-line display
ETU76B: Protection functions NG ✓
LSING3)4) with graphics display
Operating mechanism, Manual operating mechanism with
auxiliary release, mechanical closing, without 1st and 1AA2 None
auxiliary switch 2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO
For further Article No. supplements,
see page 1/38
3)
✓ Additional price Current transformers for protection of the N conductor and current trans-
1)
The rated current is determined by the rating plug. For the standard formers for detection of the ground-fault current in the grounded neutral
version, the supplied module is equal to the maximum rated current. point of the transformer are to be ordered separately, see page 1/52. The
If a lower rated current is required, adaptation by order code on page 1/39. internal current transformers for N conductors can be ordered by adding
2)
the supplement "–Z" and the order code "F23", see page 1/41.
For permissible rated short-time current Icc and rated short-circuit making 4)
capacity Icm for non-automatic air circuit breakers, see page 1/5. ETU45B to ETU76B with ground-fault protection module GFM AT
(alarm and tripping), see page 1/52.
Additional
Options price
Non-automatic air circuit Without Electronic Trip Units AA None
breakers2)
Electronic Trip Units Versions without ground-fault
protection
ETU15B: Protection functions LI BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN3) EB ✓
ETU45B: Protection functions LSIN3) FB ✓
with 4-line display
3)
ETU76B: Protection functions LSIN NB ✓
with graphics display
Versions with ground-fault
protection
ETU27B: Protection functions DG ✓
LSING3)
ETU45B: Protection functions EG ✓
LSING3)4)
ETU45B: Protection functions FG ✓
LSING3)4) with 4-line display
ETU76B: Protection functions NG ✓
LSING3)4) with graphics display
Operating mechanism, Manual operating mechanism with
auxiliary release, mechanical closing, without 1st and 1AA2 None
auxiliary switch 2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO
For further Article No. supplements,
see page 1/38
3)
✓ Additional price Current transformers for protection of the N conductor and current trans-
1)
The rated current is determined by the rating plug. For the standard formers for detection of the ground-fault current in the grounded neutral
version, the supplied module is equal to the maximum rated current. point of the transformer are to be ordered separately, see page 1/52. The
If a lower rated current is required, adaptation by order code on page 1/39. internal current transformers for N conductors can be ordered by adding
2)
the supplement "–Z" and the order code "F23", see page 1/41.
For permissible rated short-time current Icc and rated short-circuit making 4)
capacity Icm for non-automatic air circuit breakers, see page 1/5. ETU45B to ETU76B with ground-fault protection module GFM AT
(alarm and tripping), see page 1/52.
Size Max. rated circuit Rated current1) Breaking capacity DT Icu 66/80 kA at 500 V, PU PS*/ PG Weight
1
breaker current In Icu = Ics standard breaking capacity S S (UNIT, P. unit per PU
In max. SET, M) approx.
Article No. Basic price
www.siemens.com/ per PU
product?Article No.
A A kA kg
Front main circuit connection, single hole
I 630 630 66 3WL1106-3@@43-@@@@ 1 1 unit 103 50.000
800 800 3WL1108-3@@43-@@@@ 1 1 unit 103 50.000
1000 1000 3WL1110-3@@43-@@@@ 1 1 unit 103 50.000
1250 1250 3WL1112-3@@43-@@@@ 1 1 unit 103 50.000
1600 1600 3WL1116-3@@43-@@@@ 1 1 unit 103 50.000
II 800 800 80 3WL1208-3@@43-@@@@ 1 1 unit 103 67.000
1000 1000 3WL1210-3@@43-@@@@ 1 1 unit 103 67.000
1250 1250 3WL1212-3@@43-@@@@ 1 1 unit 103 67.000
1600 1600 3WL1216-3@@43-@@@@ 1 1 unit 103 67.000
2000 2000 3WL1220-3@@43-@@@@ 1 1 unit 103 67.000
2500 2500 3WL1225-3@@43-@@@@ 1 1 unit 103 71.000
3200 3200 3WL1232-3@@43-@@@@ 1 1 unit 103 77.000
Front main circuit connection, double hole
I 630 630 66 3WL1106-3@@44-@@@@ 1 1 unit 103 50.000
800 800 3WL1108-3@@44-@@@@ 1 1 unit 103 50.000
1000 1000 3WL1110-3@@44-@@@@ 1 1 unit 103 50.000
1250 1250 3WL1112-3@@44-@@@@ 1 1 unit 103 50.000
1600 1600 3WL1116-3@@44-@@@@ 1 1 unit 103 50.000
2000 2000 3WL1120-3@@44-@@@@ 1 1 unit 103 50.000
II 800 800 80 3WL1208-3@@44-@@@@ 1 1 unit 103 67.000
1000 1000 3WL1210-3@@44-@@@@ 1 1 unit 103 67.000
1250 1250 3WL1212-3@@44-@@@@ 1 1 unit 103 67.000
1600 1600 3WL1216-3@@44-@@@@ 1 1 unit 103 67.000
2000 2000 3WL1220-3@@44-@@@@ 1 1 unit 103 67.000
2500 2500 3WL1225-3@@44-@@@@ 1 1 unit 103 71.000
3200 3200 3WL1232-3@@44-@@@@ 1 1 unit 103 77.000
Additional
Options price
Non-automatic air circuit Without Electronic Trip Units AA None
breakers2)
Electronic Trip Units Versions without ground-fault
protection
ETU15B: Protection functions LI BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN3) EB ✓
ETU45B: Protection functions LSIN3) FB ✓
with 4-line display
ETU76B: Protection functions LSIN3) NB ✓
with graphics display
Versions with ground-fault
protection
ETU27B: Protection functions DG ✓
LSING3)
ETU45B: Protection functions EG ✓
LSING3)4)
ETU45B: Protection functions FG ✓
LSING3)4) with 4-line display
ETU76B: Protection functions NG ✓
LSING3)4) with graphics display
Operating mechanism, Manual operating mechanism with
auxiliary release, mechanical closing, without 1st and 1AA2 None
auxiliary switch 2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO
For further Article No. supplements,
see page 1/38
3)
✓ Additional price Current transformers for protection of the N conductor and current trans-
1)
The rated current is determined by the rating plug. For the standard formers for detection of the ground-fault current in the grounded neutral
version, the supplied module is equal to the maximum rated current. point of the transformer are to be ordered separately, see page 1/52. The
If a lower rated current is required, adaptation by order code on page 1/39. internal current transformers for N conductors can be ordered by adding
2)
the supplement "–Z" and the order code "F23", see page 1/41.
For permissible rated short-time current Icc and rated short-circuit making 4)
capacity Icm for non-automatic air circuit breakers, see page 1/5. ETU45B to ETU76B with ground-fault protection module GFM AT
(alarm and tripping), see page 1/52.
Additional
Options price
Non-automatic air circuit Without Electronic Trip Units AA None
breakers2)
Electronic Trip Units Versions without ground-fault
protection
ETU15B: Protection functions LI5) BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN3) EB ✓
ETU45B: Protection functions LSIN3) FB ✓
with 4-line display
ETU76B: Protection functions LSIN3) NB ✓
with graphics display
Versions with ground-fault
protection
ETU27B: Protection functions LSING3) DG ✓
ETU45B: Protection functions EG ✓
LSING3)4)
ETU45B: Protection functions FG ✓
LSING3)4) with 4-line display
ETU76B: Protection functions NG ✓
LSING3)4) with graphics display
Operating mechanism, Manual operating mechanism with
auxiliary release, mechanical closing, without 1st and 1AA2 None
auxiliary switch 2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO
For further Article No. supplements,
see page 1/38
3)
✓ Additional price Current transformers for protection of the N conductor and current trans-
1) The rated current is determined by the rating plug. For the standard formers for detection of the ground-fault current in the grounded neutral
version, the supplied module is equal to the maximum rated current. point of the transformer are to be ordered separately, see page 1/52. The
If a lower rated current is required, adaptation by order code on page 1/39. internal current transformers for N conductors can be ordered by adding
2) the supplement "–Z" and the order code "F23", see page 1/41.
For permissible rated short-time current Icc and rated short-circuit making 4) ETU45B to ETU76B with ground-fault protection module GFM AT
capacity Icm for non-automatic air circuit breakers, see page 1/5.
(alarm and tripping), see page 1/52.
5)
ETU15B cannot be used with 3WL circuit breakers, size III.
* You can order this quantity or a multiple thereof.
1/28 Siemens LV 10 · 2015
© Siemens AG 2015
Size Max. rated circuit Rated current1) Breaking capacity DT Icu 85/100 kA at 500 V, PU PS*/ PG Weight
1
breaker current In Icu = Ics high breaking capacity H H (UNIT, P. unit per PU
In max. SET, M) approx.
Article No. Basic price
www.siemens.com/ per PU
product?Article No.
A A kA kg
Front main circuit connection, single hole
II 800 800 100 3WL1208-4@@43-@@@@ 1 1 unit 103 67.000
1000 1000 3WL1210-4@@43-@@@@ 1 1 unit 103 67.000
1250 1250 3WL1212-4@@43-@@@@ 1 1 unit 103 67.000
1600 1600 3WL1216-4@@43-@@@@ 1 1 unit 103 67.000
2000 2000 3WL1220-4@@43-@@@@ 1 1 unit 103 67.000
2500 2500 3WL1225-4@@43-@@@@ 1 1 unit 103 71.000
3200 3200 3WL1232-4@@43-@@@@ 1 1 unit 103 77.000
III 4000 4000 100 3WL1340-4@@43-@@@@ 1 1 unit 103 99.000
Front main circuit connection, double hole
I 630 630 85 3WL1106-4@@44-@@@@ 1 1 unit 103 50.000
800 800 3WL1108-4@@44-@@@@ 1 1 unit 103 50.000
1000 1000 3WL1110-4@@44-@@@@ 1 1 unit 103 50.000
1250 1250 3WL1112-4@@44-@@@@ 1 1 unit 103 50.000
1600 1600 3WL1116-4@@44-@@@@ 1 1 unit 103 50.000
2000 2000 3WL1120-4@@44-@@@@ 1 1 unit 103 50.000
II 800 800 100 3WL1208-4@@44-@@@@ 1 1 unit 103 67.000
1000 1000 3WL1210-4@@44-@@@@ 1 1 unit 103 67.000
1250 1250 3WL1212-4@@44-@@@@ 1 1 unit 103 67.000
1600 1600 3WL1216-4@@44-@@@@ 1 1 unit 103 67.000
2000 2000 3WL1220-4@@44-@@@@ 1 1 unit 103 67.000
2500 2500 3WL1225-4@@44-@@@@ 1 1 unit 103 71.000
3200 3200 3WL1232-4@@44-@@@@ 1 1 unit 103 77.000
III 4000 4000 100 3WL1340-4@@44-@@@@ 1 1 unit 103 99.000
Additional
Options price
Non-automatic air circuit Without Electronic Trip Units AA None
breakers2)
Electronic Trip Units Versions without ground-fault
protection
ETU15B: Protection functions LI5) BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN3) EB ✓
ETU45B: Protection functions LSIN3) FB ✓
with 4-line display
ETU76B: Protection functions LSIN3) NB ✓
with graphics display
Versions with ground-fault
protection
ETU27B: Protection functions LSING3) DG ✓
ETU45B: Protection functions EG ✓
LSING3)4)
ETU45B: Protection functions FG ✓
LSING3)4) with 4-line display
ETU76B: Protection functions NG ✓
LSING3)4) with graphics display
Operating mechanism, Manual operating mechanism with
auxiliary release, mechanical closing, without 1st and 1AA2 None
auxiliary switch 2nd auxiliary releases; auxiliary switch
2 NC + 2 NO
For further Article No. supplements,
see page 1/38
✓ Additional price
1)
The rated current is determined by the rating plug. For the standard
version, the supplied module is equal to the maximum rated current.
If a lower rated current is required, adaptation by order code on page 1/39.
2)
For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers, see page 1/5.
3)
Current transformers for protection of the N conductor and current trans-
formers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 1/52. The
internal current transformers for N conductors can be ordered by adding
the supplement "–Z" and the order code "F23", see page 1/41.
4)
ETU45B to ETU76B with ground-fault protection module GFM AT
(alarm and tripping), see page 1/52.
5)
ETU15B cannot be used with 3WL circuit breakers, size III.
Additional
Options price
Non-automatic air circuit Without Electronic Trip Units AA None
breakers2)
Electronic Trip Units Versions without ground-fault
protection
ETU15B: Protection functions LI3) BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN4) EB ✓
ETU45B: Protection functions LSIN4) FB ✓
with 4-line display
ETU76B: Protection functions LSIN4) NB ✓
with graphics display
Versions with ground-fault
protection
ETU27B: Protection functions DG ✓
LSING4)
ETU45B: Protection functions EG ✓
LSING4)5)
ETU45B: Protection functions FG ✓
LSING4)5) with 4-line display
ETU76B: Protection functions NG ✓
LSING4)5) with graphics display
Operating mechanism, Manual operating mechanism with
auxiliary release, mechanical closing, without 1st and 1AA2 None
auxiliary switch 2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO
For further Article No. supplements,
see page 1/38
3)
✓ Additional price ETU15B cannot be used with 3WL circuit breakers, size III.
1) 4)
The rated current is determined by the rating plug. For the standard Current transformers for protection of the N conductor and current trans-
version, the supplied module is equal to the maximum rated current. formers for detection of the ground-fault current in the grounded neutral
If a lower rated current is required, adaptation by order code on page 1/39. point of the transformer are to be ordered separately, see page 1/52. The
2)
For permissible rated short-time current Icc and rated short-circuit making internal current transformers for N conductors can be ordered by adding
capacity Icm for non-automatic air circuit breakers, see page 1/5. the supplement "–Z" and the order code "F23", see page 1/41.
5)
ETU45B to ETU76B with ground-fault protection module GFM AT
(alarm and tripping), see page 1/52.
Additional
Options price
Non-automatic air circuit Without Electronic Trip Units AA None
breakers3)
Electronic Trip Units Versions without ground-fault
protection
ETU15B: Protection functions LI BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN4) EB ✓
ETU45B: Protection functions LSIN4) FB ✓
with 4-line display
ETU76B: Protection functions LSIN4) NB ✓
with graphics display
Versions with ground-fault
protection
ETU27B: Protection functions DG ✓
LSING4)
ETU45B: Protection functions EG ✓
LSING4)5)
ETU45B: Protection functions FG ✓
LSING4)5) with 4-line display
ETU76B: Protection functions NG ✓
LSING4)5) with graphics display
Operating mechanism, Manual operating mechanism with
auxiliary release, mechanical closing, without 1st and 1AA2 None
auxiliary switch 2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO
For further Article No. supplements,
see page 1/38
✓ Additional price 4) Current transformers for protection of the N conductor and current trans-
1) The rated current is determined by the rating plug. For the standard formers for detection of the ground-fault current in the grounded neutral
version, the supplied module is equal to the maximum rated current. point of the transformer are to be ordered separately, see page 1/52. The
If a lower rated current is required, adaptation by order code on page 1/39. internal current transformers for N conductors can be ordered by adding
2)
the supplement "–Z" and the order code "F23", see page 1/41.
Z options which are installed on the guide frame are not available. 5)
3)
ETU45B to ETU76B with ground-fault protection module GFM AT
For permissible rated short-time current Icc and rated short-circuit making (alarm and tripping), see page 1/52.
capacity Icm for non-automatic air circuit breakers, see page 1/5.
Additional
Options price
Non-automatic air circuit Without Electronic Trip Units AA None
breakers3)
Electronic Trip Units Versions without ground-fault
protection
ETU15B: Protection functions LI BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN4) EB ✓
ETU45B: Protection functions LSIN4) FB ✓
with 4-line display
ETU76B: Protection functions LSIN4) NB ✓
with graphics display
Versions with ground-fault
protection
ETU27B: Protection functions DG ✓
LSING4)
ETU45B: Protection functions EG ✓
LSING4)5)
ETU45B: Protection functions FG ✓
LSING4)5) with 4-line display
ETU76B: Protection functions NG ✓
LSING4)5) with graphics display
Operating mechanism, Manual operating mechanism with
auxiliary release, mechanical closing, without 1st and 1AA2 None
auxiliary switch 2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO
For further Article No. supplements,
see page 1/38
4)
✓ Additional price Current transformers for protection of the N conductor and current trans-
1)
The rated current is determined by the rating plug. For the standard formers for detection of the ground-fault current in the grounded neutral
version, the supplied module is equal to the maximum rated current. point of the transformer are to be ordered separately, see page 1/52. The
If a lower rated current is required, adaptation by order code on page 1/39. internal current transformers for N conductors can be ordered by adding
2)
the supplement "–Z" and the order code "F23", see page 1/41.
Z options which are installed on the guide frame are not available. 5)
3)
ETU45B to ETU76B with ground-fault protection module GFM AT
For permissible rated short-time current Icc and rated short-circuit making (alarm and tripping), see page 1/52.
capacity Icm for non-automatic air circuit breakers, see page 1/5.
Size Max. rated circuit Rated current1) Breaking capacity DT Icu 66/80 kA at 500 V, PU PS*/ PG Weight
1
breaker current In Icu = Ics standard breaking capacity S S (UNIT, P. unit per PU
In max. SET, M) approx.
Article No. Basic price
www.siemens.com/ per PU
product?Article No.
A A kA kg
Without guide frames2)
(for guide frames, see pages 1/46 to 1/51)
I 630 630 66 3WL1106-3@@45-@@@@ 1 1 unit 103 54.000
800 800 3WL1108-3@@45-@@@@ 1 1 unit 103 54.000
1000 1000 3WL1110-3@@45-@@@@ 1 1 unit 103 54.000
1250 1250 3WL1112-3@@45-@@@@ 1 1 unit 103 54.000
1600 1600 3WL1116-3@@45-@@@@ 1 1 unit 103 54.000
2000 2000 3WL1120-3@@45-@@@@ 1 1 unit 103 54.000
II 800 800 80 3WL1208-3@@45-@@@@ 1 1 unit 103 72.000
1000 1000 3WL1210-3@@45-@@@@ 1 1 unit 103 72.000
1250 1250 3WL1212-3@@45-@@@@ 1 1 unit 103 72.000
1600 1600 3WL1216-3@@45-@@@@ 1 1 unit 103 72.000
2000 2000 3WL1220-3@@45-@@@@ 1 1 unit 103 72.000
2500 2500 3WL1225-3@@45-@@@@ 1 1 unit 103 76.000
3200 3200 3WL1232-3@@45-@@@@ 1 1 unit 103 82.000
4000 4000 3WL1240-3@@45-@@@@ 1 1 unit 103 84.000
With guide frames, horizontal main circuit connection
I 630 630 66 3WL1106-3@@46-@@@@ 1 1 unit 103 84.000
800 800 3WL1108-3@@46-@@@@ 1 1 unit 103 84.000
1000 1000 3WL1110-3@@46-@@@@ 1 1 unit 103 84.000
1250 1250 3WL1112-3@@46-@@@@ 1 1 unit 103 84.000
1600 1600 3WL1116-3@@46-@@@@ 1 1 unit 103 84.000
2000 2000 3WL1120-3@@46-@@@@ 1 1 unit 103 84.000
II 800 800 80 3WL1208-3@@46-@@@@ 1 1 unit 103 109.000
1000 1000 3WL1210-3@@46-@@@@ 1 1 unit 103 109.000
1250 1250 3WL1212-3@@46-@@@@ 1 1 unit 103 109.000
1600 1600 3WL1216-3@@46-@@@@ 1 1 unit 103 109.000
2000 2000 3WL1220-3@@46-@@@@ 1 1 unit 103 109.000
2500 2500 3WL1225-3@@46-@@@@ 1 1 unit 103 123.000
3200 3200 3WL1232-3@@46-@@@@ 1 1 unit 103 136.000
Additional
Options price
Non-automatic air circuit Without Electronic Trip Units AA None
breakers3)
Electronic Trip Units Versions without ground-fault
protection
ETU15B: Protection functions LI BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN4) EB ✓
ETU45B: Protection functions LSIN4) FB ✓
with 4-line display
ETU76B: Protection functions LSIN4) NB ✓
with graphics display
Versions with ground-fault
protection
ETU27B: Protection functions DG ✓
LSING4)
ETU45B: Protection functions EG ✓
LSING4)5)
ETU45B: Protection functions FG ✓
LSING4)5) with 4-line display
ETU76B: Protection functions NG ✓
LSING4)5) with graphics display
Operating mechanism, Manual operating mechanism with
auxiliary release, mechanical closing, without 1st and 1AA2 None
auxiliary switch 2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO
For further Article No. supplements,
see page 1/38
4)
✓ Additional price Current transformers for protection of the N conductor and current trans-
1)
The rated current is determined by the rating plug. For the standard formers for detection of the ground-fault current in the grounded neutral
version, the supplied module is equal to the maximum rated current. point of the transformer are to be ordered separately, see page 1/52. The
If a lower rated current is required, adaptation by order code on page 1/39. internal current transformers for N conductors can be ordered by adding
2)
the supplement "–Z" and the order code "F23", see page 1/41.
Z options which are installed on the guide frame are not available. 5)
3)
ETU45B to ETU76B with ground-fault protection module GFM AT
For permissible rated short-time current Icc and rated short-circuit making (alarm and tripping), see page 1/52.
capacity Icm for non-automatic air circuit breakers, see page 1/5.
Additional
Options price
Non-automatic air circuit Without Electronic Trip Units AA None
breakers3)
Electronic Trip Units Versions without ground-fault
protection
ETU15B: Protection functions LI BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN4) EB ✓
ETU45B: Protection functions LSIN4) FB ✓
with 4-line display
ETU76B: Protection functions LSIN4) NB ✓
with graphics display
Versions with ground-fault
protection
ETU27B: Protection functions DG ✓
LSING4)
ETU45B: Protection functions EG ✓
LSING4)5)
ETU45B: Protection functions FG ✓
LSING4)5) with 4-line display
ETU76B: Protection functions NG ✓
LSING4)5) with graphics display
Operating mechanism, Manual operating mechanism with
auxiliary release, mechanical closing, without 1st and 1AA2 None
auxiliary switch 2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO
For further Article No. supplements,
see page 1/38
4)
✓ Additional price Current transformers for protection of the N conductor and current trans-
1)
The rated current is determined by the rating plug. For the standard formers for detection of the ground-fault current in the grounded neutral
version, the supplied module is equal to the maximum rated current. point of the transformer are to be ordered separately, see page 1/52. The
If a lower rated current is required, adaptation by order code on page 1/39. internal current transformers for N conductors can be ordered by adding
2)
the supplement "–Z" and the order code "F23", see page 1/41.
Z options which are installed on the guide frame are not available. 5)
3)
ETU45B to ETU76B with ground-fault protection module GFM AT
For permissible rated short-time current Icc and rated short-circuit making (alarm and tripping), see page 1/52.
capacity Icm for non-automatic air circuit breakers, see page 1/5.
Size Max. rated circuit Rated current1) Breaking capacity DT Icu 85/100 kA at 500 V, PU PS*/ PG Weight
1
breaker current In Icu = Ics high breaking capacity H H (UNIT, P. unit per PU
In max. SET, M) approx.
Article No. Basic price
www.siemens.com/ per PU
product?Article No.
A A kA kg
Without guide frames2)
(for guide frames, see pages 1/46 to 1/51)
I 630 630 85 3WL1106-4@@45-@@@@ 1 1 unit 103 54.000
800 800 3WL1108-4@@45-@@@@ 1 1 unit 103 54.000
1000 1000 3WL1110-4@@45-@@@@ 1 1 unit 103 54.000
1250 1250 3WL1112-4@@45-@@@@ 1 1 unit 103 54.000
1600 1600 3WL1116-4@@45-@@@@ 1 1 unit 103 54.000
2000 2000 3WL1120-4@@45-@@@@ 1 1 unit 103 54.000
II 800 800 100 3WL1208-4@@45-@@@@ 1 1 unit 103 72.000
1000 1000 3WL1210-4@@45-@@@@ 1 1 unit 103 72.000
1250 1250 3WL1212-4@@45-@@@@ 1 1 unit 103 72.000
1600 1600 3WL1216-4@@45-@@@@ 1 1 unit 103 72.000
2000 2000 3WL1220-4@@45-@@@@ 1 1 unit 103 72.000
2500 2500 3WL1225-4@@45-@@@@ 1 1 unit 103 76.000
3200 3200 3WL1232-4@@45-@@@@ 1 1 unit 103 82.000
4000 4000 3WL1240-4@@45-@@@@ 1 1 unit 103 84.000
III 4000 4000 100 3WL1340-4@@45-@@@@ 1 1 unit 103 106.000
5000 5000 3WL1350-4@@45-@@@@ 1 1 unit 103 106.000
6300 6300 3WL1363-4@@45-@@@@ 1 1 unit 103 108.000
With guide frames, horizontal main circuit connection
I 630 630 85 3WL1106-4@@46-@@@@ 1 1 unit 103 84.000
800 800 3WL1108-4@@46-@@@@ 1 1 unit 103 84.000
1000 1000 3WL1110-4@@46-@@@@ 1 1 unit 103 84.000
1250 1250 3WL1112-4@@46-@@@@ 1 1 unit 103 84.000
1600 1600 3WL1116-4@@46-@@@@ 1 1 unit 103 84.000
2000 2000 3WL1120-4@@46-@@@@ 1 1 unit 103 84.000
II 800 800 100 3WL1208-4@@46-@@@@ 1 1 unit 103 109.000
1000 1000 3WL1210-4@@46-@@@@ 1 1 unit 103 109.000
1250 1250 3WL1212-4@@46-@@@@ 1 1 unit 103 109.000
1600 1600 3WL1216-4@@46-@@@@ 1 1 unit 103 109.000
2000 2000 3WL1220-4@@46-@@@@ 1 1 unit 103 109.000
2500 2500 3WL1225-4@@46-@@@@ 1 1 unit 103 123.000
3200 3200 3WL1232-4@@46-@@@@ 1 1 unit 103 136.000
III 4000 4000 100 3WL1340-4@@46-@@@@ 1 1 unit 103 190.000
5000 5000 3WL1350-4@@46-@@@@ 1 1 unit 103 190.000
Additional
Options price
Non-automatic air circuit Without Electronic Trip Units AA None
breakers3)
Electronic Trip Units Versions without ground-fault
protection
ETU15B: Protection functions LI6) BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN4) EB ✓
ETU45B: Protection functions LSIN4) FB ✓
with 4-line display
ETU76B: Protection functions LSIN4) NB ✓
with graphics display
Versions with ground-fault
protection
ETU27B: Protection functions LSING4) DG ✓
ETU45B: Protection functions EG ✓
LSING4)5)
ETU45B: Protection functions FG ✓
LSING4)5) with 4-line display
ETU76B: Protection functions NG ✓
LSING4)5) with graphics display
Operating mechanism, Manual operating mechanism with
auxiliary release, mechanical closing, without 1st and 1AA2 None
auxiliary switch 2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO
For further Article No. supplements,
see page 1/38
✓ Additional price 4) Current transformers for protection of the N conductor and current trans-
1)
The rated current is determined by the rating plug. For the standard formers for detection of the ground-fault current in the grounded neutral
version, the supplied module is equal to the maximum rated current. point of the transformer are to be ordered separately, see page 1/52. The
If a lower rated current is required, adaptation by order code on page 1/39. internal current transformers for N conductors can be ordered by adding
2) the supplement "–Z" and the order code "F23", see page 1/41.
Z options which are installed on the guide frame are not available. 5)
3) For permissible rated short-time current I and rated short-circuit making ETU45B to ETU76B with ground-fault protection module GFM AT
cc (alarm and tripping), see page 1/52.
capacity Icm for non-automatic air circuit breakers, see page 1/5. 6)
ETU15B cannot be used with 3WL circuit breakers, size III.
Additional
Options price
Non-automatic air circuit Without Electronic Trip Units AA None
breakers3)
Electronic Trip Units Versions without ground-fault
protection
ETU15B: Protection functions LI6) BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN4) EB ✓
ETU45B: Protection functions LSIN4) FB ✓
with 4-line display
ETU76B: Protection functions LSIN4) NB ✓
with graphics display
Versions with ground-fault
protection
ETU27B: Protection functions LSING4) DG ✓
ETU45B: Protection functions EG ✓
LSING4)5)
ETU45B: Protection functions FG ✓
LSING4)5) with 4-line display
ETU76B: Protection functions NG ✓
LSING4)5) with graphics display
Operating mechanism, Manual operating mechanism with
auxiliary release, mechanical closing, without 1st and 1AA2 None
auxiliary switch 2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO
For further Article No. supplements,
see page 1/38
4)
✓ Additional price Current transformers for protection of the N conductor and current trans-
1)
The rated current is determined by the rating plug. For the standard formers for detection of the ground-fault current in the grounded neutral
version, the supplied module is equal to the maximum rated current. point of the transformer are to be ordered separately, see page 1/52. The
If a lower rated current is required, adaptation by order code on page 1/39. internal current transformers for N conductors can be ordered by adding
2)
the supplement "–Z" and the order code "F23", see page 1/41.
Z options which are installed on the guide frame are not available. 5)
3)
ETU45B to ETU76B with ground-fault protection module GFM AT
For permissible rated short-time current Icc and rated short-circuit making (alarm and tripping), see page 1/52.
capacity Icm for non-automatic air circuit breakers, see page 1/5. 6)
ETU15B cannot be used with 3WL circuit breakers, size III.
Size Max. rated circuit Rated current1) Breaking capacity DT Icu 130/150 kA at 500 V, PU PS*/ PG Weight
1
breaker current In Icu = Ics very high breaking capacity C C (UNIT, P. unit per PU
In max. SET, M) approx.
Article No. Basic price
www.siemens.com/ per PU
product?Article No.
A A kA kg
Without guide frames2)
(for guide frames, see pages 1/46 to 1/51)
II 1600 1600 130 3WL1216-5@@45-@@@@ 1 1 unit 103 83.000
2000 2000 3WL1220-5@@45-@@@@ 1 1 unit 103 83.000
2500 2500 3WL1225-5@@45-@@@@ 1 1 unit 103 83.000
3200 3200 3WL1232-5@@45-@@@@ 1 1 unit 103 83.000
III 4000 4000 130 3WL1340-5@@45-@@@@ 1 1 unit 103 115.000
5000 5000 3WL1350-5@@45-@@@@ 1 1 unit 103 106.000
6300 6300 3WL1363-5@@45-@@@@ 1 1 unit 103 108.000
With guide frames, horizontal main circuit connection
II 1600 1600 130 3WL1216-5@@46-@@@@ 1 1 unit 103 148.000
2000 2000 3WL1220-5@@46-@@@@ 1 1 unit 103 148.000
2500 2500 3WL1225-5@@46-@@@@ 1 1 unit 103 148.000
3200 3200 3WL1232-5@@46-@@@@ 1 1 unit 103 148.000
III 4000 4000 130 3WL1340-5@@46-@@@@ 1 1 unit 103 190.000
5000 5000 3WL1350-5@@46-@@@@ 1 1 unit 103 190.000
With guide frames, vertical main circuit connection
II 1600 1600 130 3WL1216-5@@47-@@@@ 1 1 unit 103 148.000
2000 2000 3WL1220-5@@47-@@@@ 1 1 unit 103 148.000
2500 2500 3WL1225-5@@47-@@@@ 1 1 unit 103 148.000
3200 3200 3WL1232-5@@47-@@@@ 1 1 unit 103 148.000
III 4000 4000 130 3WL1340-5@@47-@@@@ 1 1 unit 103 190.000
5000 5000 3WL1350-5@@47-@@@@ 1 1 unit 103 190.000
6300 6300 3WL1363-5@@47-@@@@ 1 1 unit 103 227.000
Additional
Options price
Non-automatic air circuit Without Electronic Trip Units AA None
breakers3)
Electronic Trip Units Versions without ground-fault
protection
ETU15B: Protection functions LI4) BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN5) EB ✓
ETU45B: Protection functions LSIN5) FB ✓
with 4-line display
ETU76B: Protection functions LSIN5) NB ✓
with graphics display
Versions with ground-fault
protection
ETU27B: Protection functions DG ✓
LSING5)
ETU45B: Protection functions EG ✓
LSING5)6)
ETU45B: Protection functions FG ✓
LSING5)6) with 4-line display
ETU76B: Protection functions NG ✓
LSING5)6) with graphics display
Operating mechanism, Manual operating mechanism with
auxiliary release, mechanical closing, without 1st and 1AA2 None
auxiliary switch 2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO
For further Article No. supplements,
see page 1/38
✓ Additional price 4) ETU15B cannot be used with 3WL circuit breakers, size III.
1) The rated current is determined by the rating plug. For the standard 5) Current transformers for protection of the N conductor and current trans-
version, the supplied module is equal to the maximum rated current. formers for detection of the ground-fault current in the grounded neutral
If a lower rated current is required, adaptation by order code on page 1/39. point of the transformer are to be ordered separately, see page 1/52.
2) Z options which are installed on the guide frame are not available. The internal current transformers for N conductors can be ordered by
3)
adding the supplement "–Z" and the order code "F23", see page 1/41.
For permissible rated short-time current Icc and rated short-circuit making 6)
capacity Icm for non-automatic air circuit breakers, see page 1/5. ETU45B to ETU76B with ground-fault protection module GFM AT
(alarm and tripping), see page 1/52.
Operating mechanisms
Manual operating mechanism with mechanical closing 1 None
Manual operating mechanism with mechanical and electrical closing,
closing coil suitable for uninterrupted duty, 100 % OP
50/60 Hz V AC V DC
110 110 ... 125 2 ✓
230 220 3 ✓
Manual/motorized operating mechanism with mechanical and electrical closing,
closing coil suitable for uninterrupted duty, 100 % OP
Motor Closing solenoid
50/60 Hz V AC V DC 50/60 Hz V AC V DC
208 ... 240 220 ... 250 230 220 4 ✓
110 ... 127 110 ... 125 110 110 ... 125 5 ✓
-- 24 -- 24 6 ✓
Note
To order different voltages for motorized operating mechanism and closing solenoid or
closing coil for synchronization purposes:
"1" at the 13th digit of the Article No. and order codes, see page 1/40.
1st auxiliary release
Type Condition Us 50/60 Hz V AC Us V DC
Without 1st auxiliary -- -- -- A None
release
Shunt release suitable Operating range -- 24 B ✓
for uninterrupted duty, 0.85 ... 1.1 × Us -- 30 C ✓
100 % OP
-- 48 D ✓
-- 60 E ✓
110 ... 127 110 ... 125 F ✓
208 ... 240 220 ... 250 G ✓
2nd auxiliary release
Type Condition Us 50/60 Hz V AC Us V DC
Without 2nd auxiliary -- -- -- A None
release
Shunt release suitable Operating range -- 24 B ✓
for uninterrupted duty, 0.85 ... 1.1 × Us -- 30 C ✓
100 % OP
-- 48 D ✓
-- 60 E ✓
110 ... 127 110 ... 125 F ✓
208 ... 240 220 ... 250 G ✓
Undervoltage release, Operating range -- 24 J ✓
instantaneous 0.85 ... 1.1 × Us -- 30 K ✓
(≤ 80 ms),
short-delay (≤ 200 ms) -- 48 L ✓
-- 60 U ✓
110 ... 127 110 ... 125 M ✓
208 ... 240 220 ... 250 N ✓
380 ... 415 -- P ✓
Undervoltage release, Operating range -- 48 Q ✓
can be delayed between 0.85 ... 1.1 × Us 110 ... 127 110 ... 125 R ✓
0.2 s and 3.2 s
208 ... 240 220 ... 250 S ✓
380 ... 415 -- T ✓
Auxiliary switches
1st auxiliary switch block
2 NO + 2 NC 2 None
1st + 2nd auxiliary switch block
4 NO + 4 NC 4 ✓
6 NO + 2 NC 7 ✓
5 NO + 3 NC 8 ✓
✓ Additional price
Operating manuals
Printed version French/Italian A 1 1
Spanish/Portuguese A 1 2
Rated voltage 1000 V AC and 690 V IT networks Additional price Additional price
Conditions Size Rated current In 3-pole 4-pole
Only for circuit breakers with high breaking I1) Up to 2000 A A 0 5 ✓ ✓
capacity H (8th digit of the Article No. is a "4"). II1)2) Up to 2000 A A 0 5 ✓ ✓
Cannot be combined with "Rated voltage
1150 V AC order code "A15". 2500 A A 0 5 ✓ ✓
3200 A A 0 5 ✓ ✓
III1)3) 4000 A A 0 5 ✓ ✓
5000 A A 0 5 ✓ ✓
6300 A A 0 5 ✓ ✓
Rated voltage 1150 V AC
Conditions Size Rated current In
Only for circuit breakers with high breaking II2) Up to 2000 A A 1 5 ✓ ✓
capacity H (8th digit of the Article No. is a "4") 2500 A A 1 5 ✓ ✓
Cannot be combined with "Rated voltage
1000 V AC order code "A05". 3200 A A 1 5 ✓ ✓
4000 A A 1 5 ✓ ✓
Note
For size III select a circuit breaker with very high breaking capacity C,
which can be used as standard up to 1150 V AC.
Rated voltage 690 V AC (+ 20 %)
Conditions Size Rated current In
Only for 3WL11 circuit breakers, size I, I Up to 2000 A A 1 6 ✓ ✓
with high breaking capacity H
(8th digit of the Article No. is a "4").
Tinned version of the customer's connections on the guide frame4)5)
Conditions Size
Only for circuit breakers in withdrawable version I A 0 8 ✓ ✓
with horizontal connection or flange connection. II A 0 8 ✓ ✓
The normal delivery time increases to 15 work days.
III A 0 8 ✓ ✓
Special packaging (moisture protection) Additional price
Special packaging for extended technical requirements
Cardboard packaging with water-repellent coating on corrugated cardboard A 6 1 ✓
(moisture protection)
Rating plugs Additional price
Conditions Size Rated current In
A
Only one module is possible per circuit breaker I, II 250 B 0 2 None
(not in conjunction with Electronic Trip Unit 315 B 0 3 None
ETU15B).
As standard the Electronic Trip Units are equipped 400 B 0 4 None
with a rating plug which is equal to the maximum 500 B 0 5 None
rated current circuit breaker (In max.). The rated
current of the selected rating plug must be smaller 630 B 0 6 None
than In max.. 800 B 0 8 None
1000 B 1 0 None
I, II, III 1250 B 1 2 None
1600 B 1 6 None
2000 B 2 0 None
II, III 2500 B 2 5 None
3200 B 3 2 None
4000 B 4 0 None
III 5000 B 5 0 None
6300 B 6 3 None
✓ Additional price
1) If ordering withdrawable circuit breaker and guide frame separately,
specify order code "A05" for withdrawable circuit breaker and guide frame.
2) Not possible for circuit breakers with very high breaking capacity C.
3) Not necessary for circuit breakers with very high breaking capacity C as
these circuit breakers can be used as standard up to 1150 V AC.
4) Front connections are tinned as standard.
5) The permissible temperature-rise limits according to IEC 60947-2 are 5 K
lower for a tin surface than for a silver surface.
✓ Additional price
1)
Padlocks not included in scope of supply.
2)
If ordering withdrawable circuit breaker and guide frame separately,
specify order code "F02" or "F12" for withdrawable circuit breaker only.
3)
Additional voltage transformers are required for connection of the
measurement function Plus, see page 1/61.
✓ Additional price
1)
Locks must be ordered from the manufacturer.
2)
Padlock not included in the scope of supply.
For withdrawable circuit breakers with guide frames or for guide frames1) Additional price Additional price
Note 3-pole 4-pole
To select this connection method the 12th digit of the Article No. for the circuit breaker
must be a "6".
Connection methods for main connections Size Rated current In
Top and bottom:2) I Up to 1600 A P 0 0 ✓ ✓
accessible from front, II Up to 2000 A P 0 0 ✓ ✓
single hole
Up to 2500 A P 0 0 ✓ ✓
Up to 3200 A P 0 0 ✓ ✓
III Up to 4000 A P 0 0 ✓ ✓
Connection methods for main connections Size Rated current In
Top and bottom: I Up to 2000 A P 0 1 ✓ ✓
accessible from front, II Up to 2000 A P 0 1 ✓ ✓
double hole
Up to 2500 A P 0 1 ✓ ✓
Up to 3200 A P 0 1 ✓ ✓
III Up to 4000 A P 0 1 ✓ ✓
Connection methods for main connections Size Rated current In
Top:2) I Up to 1600 A P 0 7 ✓ ✓
horizontal II Up to 2000 A P 0 7 ✓ ✓
Bottom:
accessible from front, Up to 2500 A P 0 7 ✓ ✓
single hole Up to 3200 A P 0 7 ✓ ✓
III Up to 4000 A P 0 7 ✓ ✓
Connection methods for main connections Size Rated current In
Top: I Up to 2000 A P 1 8 ✓ ✓
vertical II Up to 2000 A P 1 8 ✓ ✓
Bottom:
horizontal Up to 2500 A P 1 8 ✓ ✓
Up to 3200 A P 1 8 ✓ ✓
III Up to 4000 A P 1 8 ✓ ✓
Up to 5000 A P 1 8 ✓ ✓
Connection methods for main connections Size Rated current In
Top: I Up to 2000 A P 1 9 ✓ ✓
connecting flange II Up to 2000 A P 1 9 ✓ ✓
Bottom:
horizontal Up to 2500 A P 1 9 ✓ ✓
Up to 3200 A P 1 9 ✓ ✓
III Up to 4000 A P 1 9 ✓ ✓
Connection methods for main connections Size Rated current In
Top: I Up to 2000 A P 2 3 ✓ ✓
horizontal II Up to 2000 A P 2 3 ✓ ✓
Bottom:
vertical Up to 2500 A P 2 3 ✓ ✓
Up to 3200 A P 2 3 ✓ ✓
III Up to 4000 A P 2 3 ✓ ✓
Up to 5000 A P 2 3 ✓ ✓
Connection methods for main connections Size Rated current In
Top: I Up to 2000 A P 2 8 ✓ ✓
horizontal II Up to 2000 A P 2 8 ✓ ✓
Bottom:
connecting flange Up to 2500 A P 2 8 ✓ ✓
Up to 3200 A P 2 8 ✓ ✓
III Up to 4000 A P 2 8 ✓ ✓
✓ Additional price
1) Only horizontal connection and vertical connection are available for circuit
breakers with very high breaking capacity C.
2) Not for 3WL size I with high breaking capacity H.
■ Overview
1
Determination of the number of auxiliary supply connectors required
This selection is only required if the guide frame is ordered under a The required number of auxiliary supply connectors
separate Article No. depends on the:
• Operating mechanism type
X6 X5 • Electronic Trip Unit with/without current transformer
X7
• Type and number of auxiliary releases
NSE0_01104
X8
• Number of auxiliary switches
• COM15/COM16 communication interface
Number of Terminal
auxiliary supply
connectors
a The first auxiliary supply connector X6 is always required. 1 X6
b Operating mechanisms
b1 Manual operating mechanism with stored-energy feature with mechanical closing 0
b2 Manual operating mechanism with stored-energy feature with mechanical and electrical closing 0 X6
b3 Manual/motorized operating mechanism with stored-energy feature with mechanical and electrical closing +1 X5
c Electronic Trip Units
c1 Electronic Trip Units ETU15B, ETU25B, ETU27B 0
c2 Electronic Trip Units ETU45B, ETU76B (internal CubicleBUS) +1 X8
Connections for external current transformers for overload protection in the N conductor and ground-fault protection
c3 Current transformer installed in the N conductor (required with 3-pole circuit breakers if c2 is not selected) +1 X8
c4 Current transformer in the neutral point of the transformer (required if c2 or c3 is not selected) +1 X8
d Auxiliary releases
d1 With/without 1st auxiliary release (shunt release F1) 0 X6
d2 2nd auxiliary release (shunt release F2, undervoltage release F3, delayable undervoltage release F4) +1 X5
e Auxiliary switch blocks
e1 1st auxiliary switch block 2 NO + 2 NC 0 X6
e2 1st and 2nd auxiliary switch block 4 NO + 4 NC or 6 NO + 2 NC or 5 NO + 3 NC (required if b3 or d2 is not selected) +1 X5
f Communication modules
f1 Without communication module COM15/COM16 0
f2 With communication module COM15/COM16 – +1 X7
occupies the entire terminal strip X7, making the following options no longer possible:
• Tripped signal switch S24
• Stored-energy status indication S21
• Electrical ON button S10
• Signaling switch on first and second auxiliary release S22 + S23
g Optional signals/accessories
g1 Tripped signaling switch S24 (only when f2 not selected) +1 X7
g2 Stored-energy status indicator S21 (only when f2 not selected, required if g1 not selected) +1 X7
g3 Electric ON button S10 (only when f2 not selected, required if g1 or g2 not selected) +1 X7
g4 Signaling switch at first auxiliary release S22 (only when f2 not selected, required if g1, g2 or g3 not selected) +1 X7
g5 Signaling switch at second auxiliary release S23 (only when f2 not selected, required if g1, g2, g3 or g4 not selected) +1 X7
g6 Switch on ready-to-close signaling switch S20 0 X6
g7 Motor shutdown switch S12 (only if motorized operating mechanism selected) 0 X5
g8 Remote reset solenoid F7 (required if c2 not selected) +1 X8
h Total number of auxiliary supply connectors (max. 4)
For ordering the auxiliary supply connectors, see under "Accessories and spare parts, Guide frames for AC circuit
breakers/non-automatic air circuit breakers", pages 1/46 to 1/51 and under "Accessories and spare parts, Auxiliary conductor
connections, Auxiliary supply connectors", page 1/57.
Size Max. rated circuit breaker Breaking DT Guide frames for 3-pole circuit breakers/ PU PS*/ PG Weight
current capacity non-automatic air circuit breakers (UNIT, P. unit per PU
In max. Icu = Ics Article No. Basic price SET, M) approx.
www.siemens.com/ per PU
product?Article No.
A kA kg
Front main circuit connection, single hole
I 1000 ... 66 3WL9211-1AA@@-@@A1 1 1 unit 103 25.000
1600 ... 66 3WL9211-2AA@@-@@A1 1 1 unit 103 25.000
II 2000 ... 100 3WL9212-3AA@@-@@A1 1 1 unit 103 31.000
2500 ... 100 3WL9212-4AA@@-@@A1 1 1 unit 103 39.000
3200 ... 100 3WL9212-5AA@@-@@A1 1 1 unit 103 45.000
III 4000 ... 100 3WL9213-6AA@@-@@A1 1 1 unit 103 60.000
Front main circuit connection, double hole
I 1000 ... 66 3WL9211-1AB@@-@@A1 1 1 unit 103 25.000
1600 ... 66 3WL9211-2AB@@-@@A1 1 1 unit 103 25.000
20001) ... 85 3WL9211-3AB@@-@@A1 1 1 unit 103 25.000
II 2000 ... 100 3WL9212-3AB@@-@@A1 1 1 unit 103 31.000
2500 ... 100 3WL9212-4AB@@-@@A1 1 1 unit 103 39.000
3200 ... 100 3WL9212-5AB@@-@@A1 1 1 unit 103 45.000
III 4000 ... 100 3WL9213-6AB@@-@@A1 1 1 unit 103 60.000
Horizontal main circuit connection
I 1000 ... 66 3WL9211-1AC@@-@@A1 1 1 unit 103 25.000
1600 ... 66 3WL9211-2AC@@-@@A1 1 1 unit 103 25.000
20001) ... 85 3WL9211-3AC@@-@@A1 1 1 unit 103 25.000
II 2000 ... 100 3WL9212-3AC@@-@@A1 1 1 unit 103 31.000
2500 ... 100 3WL9212-4AC@@-@@A1 1 1 unit 103 39.000
3200 ... 100 3WL9212-5AC@@-@@A1 1 1 unit 103 45.000
3200 ... 130 3WL9212-5AC@@-@@C1 1 1 unit 103 54.000
III 4000 ... 100 3WL9213-6AC@@-@@A1 1 1 unit 103 60.000
5000 ... 100 3WL9213-7AC@@-@@A1 1 1 unit 103 60.000
4000 ... 150 3WL9213-6AC@@-@@C1 1 1 unit 103 63.000
5000 ... 150 3WL9213-7AC@@-@@C1 1 1 unit 103 63.000
Additional
Options price
Number of auxiliary supply None 0 None
connectors
1 connector 1 ✓
2 connectors 2 ✓
3 connectors 3 ✓
4 connectors 4 ✓
Note
For required number of auxiliary supply connectors,
see table on page 1/45.
Type of auxiliary circuit None 0 None
connections
With screw connection 1 ✓
(SIGUT, standard)
With screwless connection 2 ✓
method (tension spring)
Position signaling switches None 0 None
Option 1: 1 ✓
Connected position 1 CO,
test position 1 CO,
disconnected position 1 CO
Option 2: 2 ✓
Connected position 3 CO,
test position 2 CO,
disconnected position 1 CO
Shutters None A None
With shutter, Size I B ✓
2-part, Size II B ✓
lockable
Size III B ✓
✓ Additional price
1) For 3WL circuit breakers size I from 630 A to 2000 A with high breaking
capacity H and 3WL circuit breakers size I with rated current In = 2000 A.
✓ Additional price
1)
Front connections are tinned as standard.
2)
The permissible temperature-rise limits according to IEC 60947-2 are 5 K
lower for a tin surface than for a silver surface.
Add "-Z" to the complete Article No. and indicate the 3WL921.-.....-....-Z Additional
appropriate order code(s). @ @ @ price
✓ Additional price
1)
For 3WL circuit breakers size I from 630 A to 2000 A with high breaking
capacity H and 3WL circuit breakers size I with rated current In = 2000 A.
✓ Additional price
1)
Front connections are tinned as standard.
2)
The permissible temperature-rise limits according to IEC 60947-2 are 5 K
lower for a tin surface than for a silver surface.
Add "-Z" to the complete Article No. and indicate the 3WL921.-.....-....-Z Additional
appropriate order code(s). @ @ @ price
• GFM AT 45B (only for ETU45B) alarm and tripping 1 1 unit 103 0.030
O F F E .1 .5
N S E 0 _ 0 1 0 2 7 a 3WL9111-0AT53-0AA0
• GFM AT 55B–76B (only for ETU76B) alarm and tripping 3WL9111-0AT56-0AA0 1 1 unit 103 0.030
3WL9111-0AT53-0AA0
Displays 3WL9111-0AT81-0AA0 1 1 unit 103 0.060
• For ETU45B
• 4-line
N S E 0 _ 0 1 6 0 9
3WL9111-0AT81-0AA0
Internal current transformers for N conductor
Including wiring kit
ETU Release 2 Size
-- I 3WL9111-0AA11-0AA0 1 1 unit 103 0.200
II 3WL9111-0AA12-0AA0 1 1 unit 103 0.280
N S E 0 _ 0 0 9 9 0 a
III 3WL9111-0AA13-0AA0 1 1 unit 103 0.500
3WL9111-0AA2.-0AA0 ✓ I 3WL9111-0AA14-0AA0 1 1 unit 103 0.200
II 3WL9111-0AA15-0AA0 1 1 unit 103 0.280
III 3WL9111-0AA16-0AA0 1 1 unit 103 0.500
External current transformers for N conductor
For T5, "Measurement Method" function, see Technical Informa-
tion at www.siemens.com/lowvoltage/product-support.
N S E 0 _ 0 0 9 9 1 a
Copper connection pieces Size
3WL9111-0AA3.-0AA0
-- I 3WL9111-0AA21-0AA0 1 1 unit 103 0.300
II 3WL9111-0AA22-0AA0 1 1 unit 103 0.380
III 3WL9111-0AA23-0AA0 1 1 unit 103 0.680
✓ I 3WL9111-0AA31-0AA0 1 1 unit 103 1.600
II 3WL9111-0AA32-0AA0 1 1 unit 103 4.260
III 3WL9111-0AA33-0AA0 1 1 unit 103 8.500
EMC filters
• Common-mode interference suppressor filters
(e.g. in IT networks, caused by frequency converters)
• Insertion loss (asymmetric) in the range 40 kHz to 10 MHz >40 dB
Versions
• Not for ETU Release 2 3WL9111-0AK32-0AA0 1 1 unit 103 0.280
• Only for ETU Release 2 3WL9111-0AK34-0AA0 1 1 unit 103 0.280
1) For replacement in existing circuit breakers please specify the circuit breaker 3)
For direct measurement of the ground-fault current, e.g. in the neutral point of
ID No. when ordering. the transformer, a 1.200 A/1 A current transformer, class 1, is required. The
2) internal load of the 3WL circuit breaker is 0.11 m. If the ground-fault current is
With the rating plug selected, the maximum rated current In max. of the circuit
breaker must not be exceeded. The following applies In ≤ In max. to be determined using the vectorial sum of the phases, a transformer must be
installed in the neutral conductor.
Versions
• For ETU15B to ETU45B 3WL9111-0AT45-0AA0 1 1 unit 103 0.050
ETU25B • For ETU76 3WL9111-0AT46-0AA0 1 1 unit 103 0.050
Automatic reset of the reclosing lockout 3WL9111-0AK21-0AA0 1 1 unit 103 0.050
Spare part for option K01, see "-Z" + order code, page 1/40.
Remote reset coils1)
• For mechanical tripped indicator
• Spare part for option K10 to K13, see "-Z" + order code,
page 1/40.
Note
3WL9111-0AT45-0AA0
Automatic reset of the reclosing lockout
F 7 3WL9111-0AK21-0AA0 also needed.
Versions
• 24 V DC 3WL9111-0AK03-0AA0 1 1 unit 103 0.200
• 48 V DC 3WL9111-0AK04-0AA0 1 1 unit 103 0.200
• 120 V AC/125 V DC 3WL9111-0AK05-0AA0 1 1 unit 103 0.200
• 208-250 V AC/208-250 V DC 3WL9111-0AK06-0AA0 1 1 unit 103 0.200
N S E 0 _ 0 0 9 9 9 a
Retrofittable internal CubicleBUS wiring for connection to 3WL9111-0AK30-0AA0 1 1 unit 103 0.150
3WL9111-0AK0.-0AA0 terminal X8
• For ETU45B and ETU76B
• Without male connector2)
Retrofittable internal wiring for connection of the external 3WL9111-0AK31-0AA0 1 1 unit 103 0.020
N- and G-transformers to terminal X8
• Not for ETU Release 2
• Without male connector
Retrofittable internal wiring for connection of the external 3WL9111-0AK33-0AA0 1 1 unit 103 0.020
N- and G-transformers to terminal X8
• For ETU Release 2
• Without male connector
Locking devices
Interlocking set for mechanical ON/OFF
• Consisting of 2 transparent covers each for sealing or for
attaching padlocks4),
• Cover with 6.35 mm hole (for tool actuation)
• Lock mount for safety lock for key operation
Versions
NSE00980
• Spare part for option S01 to S09, see "-Z" + order code,
page 1/42.
Versions
• Assembly kit FORTRESS or CASTELL3) 3WL9111-0BA31-0AA0 1 1 unit 103 0.200
• Made by Ronis 3WL9111-0BA33-0AA0 1 1 unit 103 0.400
• Made by KIRK-Key3) 3WL9111-0BA34-0AA0 1 1 unit 103 0.270
3WL9111-0BA31-0AA0 • Made by Profalux 3WL9111-0BA35-0AA0 1 1 unit 103 0.250
• Made by CES 3WL9111-0BA36-0AA0 1 1 unit 103 0.200
• Made by IKON 3WL9111-0BA38-0AA0 1 1 unit 103 0.200
• Assembly kit for padlocks4) 3WL9111-0BA41-0AA0 1 1 unit 103 0.360
Locking devices against unauthorized closing, for
withdrawable circuit breakers
• The disconnector unit fulfills the requirements for main circuit
breakers acc. to EN 60204-1
• Consisting of lock in the cabinet door, active in connected
NSE0_00982
position; function is retained when circuit breaker is replaced
• Spare part for option R60, R61, R68, see "-Z" + order code,
3WL9111-0BA53-0AA0 page 1/42.
Versions
• Made by CES 3WL9111-0BA51-0AA0 1 1 unit 103 0.300
• Made by IKON 3WL9111-0BA53-0AA0 1 1 unit 103 0.300
• Made by KIRK-Key3) 3WL9111-0BA57-0AA0 1 1 unit 103 0.300
• Made by Ronis 3WL9111-0BA58-0AA0 1 1 unit 103 0.300
• Made by Profalux 3WL9111-0BA50-0AA0 1 1 unit 103 0.227
1) Can only be used in conjunction with "automatic reset of reclosing lockout", 3) Locks, cylinders and keys must be ordered from the manufacturer.
e.g. "–Z" + "K01", 3WL9 111-0AK21-0AA0. 4) Padlock not included in the scope of supply.
2) Required if communication is retrofitted.
NSE00984
3WL9111-0BA71-0AA0
Locking devices to prevent movement of the withdrawable
circuit breakers
• Safety lock for mounting on the circuit breaker
• Spare part for option S71, S75, S76, see "-Z" + order code,
page 1/42.
NSE0_00986
Versions
3WL9111-0BA76-0AA0 • Made by CES 3WL9111-0BA73-0AA0 1 1 unit 103 0.300
• Made by IKON 3WL9111-0BA75-0AA0 1 1 unit 103 0.200
• Made by Profalux 3WL9111-0BA76-0AA0 1 1 unit 103 0.300
• Made by Ronis 3WL9111-0BA77-0AA0 1 1 unit 103 0.300
• Made by KIRK-Key2) 3WL9111-0BA80-0AA0 1 1 unit 103 0.400
Interlocking systems 3WL9111-0BA43-0AA0 1 1 unit 103 0.360
• Made by CES
• 2 of the same keys for 3 circuit breakers
• Locking device in OFF position
• Lock in the operator panel
• A maximum of 2 circuit breakers can be switched on
Locking mechanisms
Locking devices to prevent movement of the withdrawable
circuit breakers in disconnected position
• Consisting of Bowden wire and lock in the cabinet door on
the circuit breaker
NSE0_00987
• Spare part for option R81, R85, R86, see "-Z" + order code,
3WL9111-0BA83-0AA0 page 1/42.
Versions
• Made by CES 3WL9111-0BA81-0AA0 1 1 unit 103 0.800
• Made by IKON 3WL9111-0BA83-0AA0 1 1 unit 103 0.800
• Made by Profalux 3WL9111-0BA85-0AA0 1 1 unit 103 0.800
• Made by Ronis 3WL9111-0BA86-0AA0 1 1 unit 103 0.800
Note
Not possible in combination with "Locking device to prevent
opening of the cabinet door" (order code "R30") or "Locking
device to prevent movement with the cabinet door open"
(order code "R50").
Locking devices to prevent opening of the cabinet door in 3WL9111-0BB12-0AA0 1 1 unit 103 0.600
ON position
• Fixed-mounted
NSE0_00988
• Can be defeated
• Spare part for option S30, see "-Z" + order code, page 1/42.
3WL9111-0BB12-0AA0
Locking devices to prevent opening of the cabinet door 3WL9111-0BB13-0AA0 1 1 unit 103 0.150
• Guide frames
• Can be defeated
• Spare part for option R30, see "-Z" + order code, page 1/42.
Note
Not possible in combination with "Locking device to prevent
movement of the withdrawable circuit breakers in discon-
nected position" (order codes "R81", "R85" or "R86").
Locking devices to prevent movement with the cabinet 3WL9111-0BB15-0AA0 1 1 unit 103 0.150
door open
• Guide frames
• Spare part for option R50, see "-Z" + order code, page 1/42.
Note
Not possible in combination with "Locking device to prevent
movement of the withdrawable circuit breakers in discon-
nected position" (order codes "R81", "R85" or "R86").
1)
Padlock not included in the scope of supply.
2)
Locks, cylinders and keys must be ordered from the manufacturer.
NSE0_01886
3WL9112-8HA47-0AA0
Bowden wires
Versions
2 000 mm 3WL9111-0BB45-0AA0 1 1 unit 103 0.150
3 000 mm 3WL9111-0BB46-0AA0 1 1 unit 103 0.220
4 500 mm 3WL9111-0BB47-0AA0 1 1 unit 103 0.360
Transfer control devices
3KC ATC5300 transfer control devices
See chapter "Monitoring Devices".
3KC9000-8TL30
Test devices
Manual tester Release 2 for Electronic Trip Units ETU15B to 3WL9111-0AT32-0AA0 1 1 unit 103 1.100
ETU76B
For testing the Electronic Trip Unit functions of all 3WL ETUs
(release 1 and release 2)
Function testers 3WL9111-0AT44-0AA0 1 1 unit 103 8.210
For testing the tripping characteristics for Electronic Trip Units
ETU15B to ETU76B
Capacitor storage devices
Capacitor storage devices 3WL9111-0BA14-0AA0 1 1 unit 103 0.520
• For shunt releases
• Storage time 5 min
Rated control supply voltage/rated operational voltage
50/60 Hz V AC V DC
220 ... 240 220 ... 250
Note
• Rated control supply voltage must match the rated control
supply voltage of the shunt release
• Suitable also for 3VL and 3WN circuit breakers
N S E 0 _ 0 0 9 9 3 a
3WL9111-0AH01-0AA0
Signaling switches1)2) 3WL9111-0AH02-0AA0 1 1 unit 103 0.020
• 1st or 2nd auxiliary release
• Spare part for option C26 and C27, see "-Z" + order code,
page 1/40.
N S E 0 _ 0 0 9 9 4 b
3WL9111-0AH02-0AA0
1st tripped signaling switch1)2) 3WL9111-0AH14-0AA0 1 1 unit 103 0.080
• 1 CO contact
• Spare part for option K07, see "-Z" + order code, page 1/40.
2nd tripped signaling switch1)2)3) 3WL9111-0AH17-0AA0 1 1 unit 103 0.080
• 1 NO contact
• Spare part for option K06, see "-Z" + order code, page 1/40.
Operating cycles counter 3WL9111-0AH07-0AA0 1 1 unit 103 0.100
• Mechanical4)
• Spare part for option C01, see "-Z" + order code, page 1/40.
N S E 0 _ 0 0 9 9 5 a
3WL9111-0AH07-0AA0
Stored energy status signaling switches1)2) 3WL9111-0AH08-0AA0 1 1 unit 103 0.030
• 1 NO contact
• Spare part for option C20, see "-Z" + order code, page 1/40.
Position signaling switches for guide frames
Spare part for option R15 and R16, see "-Z" + order code,
page 1/41.
Versions
N S E 0 _ 0 0 9 9 6 a
• 1st block (3 CO contacts) 3WL9111-0AH11-0AA0 1 1 unit 103 0.200
3WL9111-0AH12-0AA0
• 2nd block (6 CO contacts) 3WL9111-0AH12-0AA0 1 1 unit 103 0.400
Electrical ON buttons1)5)
• Button + wiring2)
• For operator panel
• Spare part for option C11 and C12, see "Z" + order code,
page 1/40.
N S E 0 0 0 9 9 7 a
Versions
3WL9111-0AJ0.-0AA0 • With sealing cap C11 3WL9111-0AJ02-0AA0 1 1 unit 103 0.150
• With CES C12 assembly kit 3WL9111-0AJ03-0AA0 1 1 unit 103 0.140
• With IKON assembly kit 3WL9111-0AJ05-0AA0 1 1 unit 103 0.140
Note
Possible only for circuit breakers with closing coil.
Motor shutdown switches 6) 3WL9111-0AJ06-0AA0 1 1 unit 103 0.100
• Mounting on operator panel
• Spare part for option S25, see "-Z" + order code, page 1/40.
EMERGENCY-STOP pushbuttons 3WL9111-0BA72-0AA0 1 1 unit 103 0.080
• Mushroom pushbutton instead of the mechanical
OFF pushbutton
• Spare part for option S24, see "-Z" + order code, page 1/40.
NSE00985
3WL9111-0BA72-0AA0
1) Not possible with communications interface option, order code "F02" or 4) Only in conjunction with motorized operating mechanism.
"F12". 5) Not possible with motor shutdown switch.
2) X7 auxiliary supply connector required for circuit breakers or guide frames. 6) Not possible with electrical ON button.
If this is not already available, please order additionally (see pages 1/45
and 1/57).
3) Can only be used in combination with 1st tripped signaling switch.
3WL9111-0AB01-0AA0
Extension for the 1000 V male 3WL9111-0AB02-0AA0 1 1 unit 103 0.150
connector versions
Male connector must be ordered separately.
Male connectors and extension for 1000 V 3WL9111-0AB10-0AA0 1 1 unit 103 1.000
3WL9111-0AB03-0AA0
N S E 0 _ 0 1 2 6 9
3WL9111-0AB04-0AA0
Coding kits 3WL9111-0AB07-0AA0 1 1 unit 103 0.020
For fixed-mounted versions (X5 to X8) &
NSE00974
3WL9111-0AB07-0AA0
Sliding contact modules for guide frames ( 3WL9111-0AB08-0AA0 1 1 unit 103 0.100
a
7 7
0 9
_ 0
S E 0
N
3WL9111-0AB08-0AA0
One-part sliding contact modules for guide 3WL9111-0AB18-0AA0 1 1 unit 103 0.120
frames
NSE0_01586
3WL9111-0AB18-0AA0
Blanking blocks for circuit breakers 3WL9111-0AB12-0AA0 1 1 unit 103 0.030
NSE01002
3WL9111-0AE1.-0AA0
Operating mechanisms
Motorized operating mechanisms2)
Versions
• 24 ... 30 V DC 3WL9111-0AF01-0AA0 1 1 unit 103 1.510
I • 48 ... 60 V DC 3WL9111-0AF02-0AA0 1 1 unit 103 1.510
• 110 ... 125 V DC/110 ... 127 V AC 3WL9111-0AF03-0AA0 1 1 unit 103 1.510
• 220 ... 250 V DC/208 ... 240 V AC 3WL9111-0AF04-0AA0 1 1 unit 103 1.510
N S E 0 _ 0 1 0 0 3 a
3WL9111-0AF0.-0AA0
Auxiliary contacts
Auxiliary switch blocks
Versions
• 2 NO contacts+ 2 NC contacts 3WL9111-0AG01-0AA0 1 1 unit 103 0.180
• 2 NO contacts 3WL9111-0AG02-0AA0 1 1 unit 103 0.080
• 1 NO contact + 1 NC contact 3WL9111-0AG03-0AA0 1 1 unit 103 0.070
NSE0_01004
3WL9111-0AG03-0AA0
1)
Overexcited, i.e. operating time 50 ms (standard >80 ms).
2)
X5 auxiliary supply connector required for circuit breakers or guide frames.
If this is not already available, please order additionally (see pages 1/45
and 1/48).
NSE0_01028a
3WL9111-0AP02-0AA0
Shutters
Spare part for option R21, see "-Z" + order code,
page 1/41.
Number of poles Size
3-pole I 3WL9111-0AP04-0AA0 1 1 unit 103 0.500
II1) 3WL9111-0AP06-0AA0 1 1 unit 103 0.630
II C 3WL9111-0AP43-0AA0 1 1 unit 103 0.630
III 3WL9111-0AP07-0AA0 1 1 unit 103 0.860
NSE0_01006 4-pole I 3WL9111-0AP08-0AA0 1 1 unit 103 0.600
II1) 3WL9111-0AP11-0AA0 1 1 unit 103 0.770
3WL9111-0AP0.-0AA0 II C 3WL9111-0AP44-0AA0 1 1 unit 103 0.770
III 3WL9111-0AP12-0AA0 1 1 unit 103 1.070
Arc chutes
Arc chutes
Versions Size
690 V I 3WL9111-0AS01-0AA0 1 1 unit 103 1.110
II1) 3WL9111-0AS02-0AA0 1 1 unit 103 1.680
II C 3WL9111-0AS10-0AA0 1 1 unit 103 3.520
III 3WL9111-0AS03-0AA0 1 1 unit 103 2.980
NSE0_01007
3WL9111-0AS0.-0AA0
3WL9111-0AR12-0AA0
3WL9111-0AR13-0AA0
1) Cannot be used for 3WL size II with very high breaking capacity C
2)
Not available for
- 1000 V version (order code "A05")
- 1150 V version (order code "A15")
- DC version
- 4000 A size II
- Circuit breaker with very high breaking capacity C
3WL9111-0BB50-0AA0
CubicleBUS modules3)6)
Digital output moduleswith rotary coding switch, 3WL9111-0AT26-0AA0 1 1 unit 103 0.240
relay outputs
Digital output modules, configurable, relay outputs 3WL9111-0AT20-0AA0 1 1 unit 103 0.310
Digital input modules 3WL9111-0AT27-0AA0 1 1 unit 103 0.240
Analog output modules 3WL9111-0AT23-0AA0 1 1 unit 103 0.240
Zone Selective Interlocking modules 3WL9111-0AT21-0AA0 1 1 unit 103 0.240
N S E 0 _ 0 1 0 2 3 a
3WL9111-0AT23-0AA0
Parameterization systems6)
BDA Plus4)5) 3WL9111-0AT33-0AA0 1 1 unit 103 1.200
• Parameterization, operation, monitoring and diagnostics of
3WL air circuit breakers using the local interface
• Breaker Data Adapter, connection cable to the 3WL air circuit
breaker and to the programming device (e.g. notebook)
• Can be run with Internet Explorer
with JAVA2 VM 1.4.0-01 and higher
• With Ethernet interface for connection to Ethernet/Intranet/
Internet
N S E 0 _ 0 1 0 2 4 a
3WL9111-0AT28-0AA0
Connection cables for BDA Plus 3WL9111-0BC21-0AA0 1 1 unit 103 0.350
• Connection cable for connection of BDA Plus to terminal X8 of
the 3WL air circuit breaker
• Required if neither COM15 nor COM16 nor other external
CubicleBUS modules are available
• Length 2 m
powerconfig parameterization software
• Parameterization, operation, monitoring and diagnostics of
3WL air circuit breakers using powerconfig software, see
section entitled "Software", "Configuring, Visualizing and
Controlling with SENTRON".
• powerconfig is available free of charge at
http://support.automation.siemens.com/WW/view/en/63452759
1) 4)
For 60 kA ground short-circuit current, order 2. A 24 V DC power supply unit is required.
2) 5)
Cannot be used for size II with very high breaking capacity C and size II, Operation under Windows Vista and Windows 7 possible with restrictions.
4000 A. 6)
3) Each CubicleBUS module is supplied with a 0.2 m factory-fitted cable to All communication components, CubicleBUS modules and measurement
functions are available for the ETU45B and ETU76B Electronic Trip Units.
connect the modules with each other. A longer factory-fitted cable is
required for connection to the circuit breaker.
CubicleBus
PROFIBUS DP
NSE-01025
3WL9111-0AT15-0AA0
COM16 MODBUS modules 3WL9111-0AT17-0AA0 1 1 unit 103 0.140
For ETU45B and ETU76B Electronic Trip Units
1)
Is required for operation of the measurement function Plus.
2)
A measuring accuracy of 3 % is reached if retrofitted.
3)
All communication components, CubicleBUS modules and measurement
functions are available for the ETU45B and ETU76B Electronic Trip Units.
3WL9111-0AM03-0AA0
1)
Not for 3WL size I with high breaking capacity H.
2)
In the case of vertical connection size I with breaking capacity N and S,
up to 1000 A one 3WL9 111–0AM01-0AA0 vertical connection is required,
up to 2000 A or with breaking capacity H two 3WL9 111-0AM01-0AA0
vertical connections are required.
3)
In the case of vertical connection size II, up to 2500 A one
3WL9 111-0AM02-0AA0 vertical connection is required, up to 3200 A
two 3WL9 111-0AM02-0AA0 vertical connections are required.
4)
Not for circuit breakers with very high breaking capacity C.
NSE-01014
II3) Up to 2000 A 3WL9111-0AN11-0AA0 1 1 unit 103 2.000
Up to 2500 A 3WL9111-0AN12-0AA0 1 1 unit 103 3.700
3WL9111-0AN14-0AA0 Up to 3200 A 3WL9111-0AN13-0AA0 1 1 unit 103 3.600
III Up to 4000 A 3WL9111-0AN14-0AA0 1 1 unit 103 6.400
Supports for front and DIN connecting bars
Number of poles Size
3-pole for 3 bars I 3WL9111-0AN41-0AA0 1 1 unit 103 0.700
II 3WL9111-0AN42-0AA0 1 1 unit 103 1.350
III 3WL9111-0AN43-0AA0 1 1 unit 103 2.420
4-pole for 4 bars I 3WL9111-0AN44-0AA0 1 1 unit 103 1.200
II 3WL9111-0AN45-0AA0 1 1 unit 103 2.200
III 3WL9111-0AN46-0AA0 1 1 unit 103 3.200
NSE-01017
3WL9111-0AN41-0AA0
Rear vertical main connections
Size Rated current In
NSE-01015 I Up to 1000 A 2) 3WL9111-0AN15-0AA0 1 1 unit 103 0.660
3WL9111-0AN23-0AA0 1250 A ... 2000 A 3WL9111-0AN16-0AA0 1 1 unit 103 0.870
II Up to 2000 A 3) 3WL9111-0AN17-0AA0 1 1 unit 103 1.150
Up to 2500 A 3) 3WL9111-0AN18-0AA0 1 1 unit 103 1.490
Up to 3200 A3) 3WL9111-0AN21-0AA0 1 1 unit 103 2.580
1600 ... 3200 A4) 3WL9111-0AN38-0AA0 1 1 unit 103 2.600
III Up to 5000 A 3WL9111-0AN22-0AA0 1 1 unit 103 6.380
Up to 6300 A, 3 busbar 3WL9111-0AN23-0AA0 1 1 unit 103 19.170
connection pieces for 3-pole
circuit breakers
Up to 6300 A, at top, 3WL9111-0AN20-0AA0 1 1 unit 103 18.410
4 busbar connection pieces
for 4-pole circuit breakers
Up to 6300 A, at bottom, 3WL9111-0AN10-0AA0 1 1 unit 103 18.300
4 busbar connection pieces
for 4-pole circuit breakers
Rear horizontal main connections
Size Rated current In
I Up to 1000 A 2) 3WL9111-0AN32-0AA0 1 1 unit 103 0.630
1250 A ... 2000 A 3WL9111-0AN33-0AA0 1 1 unit 103 0.770
II Up to 2000 A 3) 3WL9111-0AN34-0AA0 1 1 unit 103 1.020
Up to 2500 A 3) 3WL9111-0AN35-0AA0 1 1 unit 103 1.240
Up to 3200 A3) 3WL9111-0AN36-0AA0 1 1 unit 103 2.170
1600 ... 3200 A4) 3WL9111-0AN47-0AA0 1 1 unit 103 2.150
III Up to 5000 A 3WL9111-0AN37-0AA0 1 1 unit 103 3.860
Connecting flange
Size Rated current In
I Up to 1000 A 2) 3WL9111-0AN24-0AA0 1 1 unit 103 0.610
1250 A ... 2000 A 3WL9111-0AN25-0AA0 1 1 unit 103 0.640
II3)
NSE-01016
1)
Conversion from fixed-mounted to withdrawable is not possible for
3WL circuit breakers with very high breaking capacity C.
2)
Not for circuit breakers with very high breaking capacity C.
3)
Please specify the circuit breaker ID No. in plain text when ordering.
4)
Replacement of the main contact elements for 3WL circuit breakers with
very high breaking capacity C is only possible at the factory.
L1 L2 L3 L1 L2 L3
NSE0_01116
NSE0_01113 NSE0_01112
NSE0_01119
N L1 L2 L3 N L1 L2 L3
NSE0_01117
Top and bottom system components are short-circuited and grounded Top system component is short-circuited and grounded,
(as-supplied state) infeed from bottom
NSE0_01120
NSE0_01122a
L1 L2 L3
NSE0_01115 NSE0_01114
NSE0_01121
NSE0_01123a
N L1 L2 L3
Withdrawable bridging unit, infeed and outgoing sides are permanently Bottom system component is short-circuited and grounded,
connected to each other infeed from top
Documentation
Operating manual German/English Article No. 3ZX18 12-0WL00-0AN1 Delivery time class C
Complete set French/Italian Article No. 3ZX18 12-0WL00-0AJ1 On request
Spanish/Portuguese Article No. 3ZX18 12-0WL00-0AL1 On request
PROFIBUS German Article No. A5E0151347
Communication manual English Article No. A5E0151353
MODBUS German Article No. 3ZX10 12-0WL10-1AB1
Communication manual English Article No. 3ZX10 12-0WL10-1AC1
■ More information
Up-to-date information on the Internet at:
www.siemens.com/sentron
Size Max. rated circuit breaker current DT 4-pole non-automatic air circuit PU PS*/ PG Weight
In max. breakers DC (UNIT, P. unit per PU
SET, M) approx.
Article No.: www.siemens.com/ Price
A product?Article No. per PU kg
Horizontal main circuit connection
I3) 2000 3WL1120-8@@42-@@@@ 1 1 unit 103 50.000
II 1000 3WL1210-8@@42-@@@@ 1 1 unit 103 67.000
2000 3WL1220-8@@42-@@@@ 1 1 unit 103 67.000
40001) 3WL1240-8@@42-@@@@ 1 1 unit 103 77.000
Vertical main circuit connection
I3) 2000 3WL1120-8@@41-@@@@ 1 1 unit 103 50.000
II 1000 3WL1210-8@@41-@@@@ 1 1 unit 103 75.000
2000 3WL1220-8@@41-@@@@ 1 1 unit 103 75.000
40001) 3WL1240-8@@41-@@@@ 1 1 unit 103 103.000
Front main circuit connection, single hole
II 1000 3WL1210-8@@43-@@@@ 1 1 unit 103 67.000
2000 3WL1220-8@@43-@@@@ 1 1 unit 103 67.000
Front main circuit connection, double hole
II 1000 3WL1210-8@@44-@@@@ 1 1 unit 103 67.000
2000 3WL1220-8@@44-@@@@ 1 1 unit 103 67.000
Add "-Z" to the complete Article No. and indicate the appropriate 3WL12.0-8....-....-Z Additional price
order code(s). @ @ @ 3-pole 4-pole
Additional
Options price
Non-automatic air circuit Without Electronic Trip AA None
breakers2) Units
Operating mechanisms Manual operating 1AA2 None
mechanism with
mechanical closing
For further Article No.
supplements,
see page 1/38
Add "-Z" to the complete Article No. and indicate the 3WL12.0-8..3.-....-Z Additional price
appropriate order code(s). @@@ 3-pole
Additional
Options price
Non-automatic air circuit Without Electronic Trip AA None
breakers2) Units
Operating mechanisms Manual operating mecha- 1AA2 None
nism with mechanical
closing
For further Article No. sup-
plements, see page 1/38
Add "-Z" to the complete Article No. and indicate the 3WL12.0-8..4.-....-Z Additional price
appropriate order code(s). @@@ 4-pole
Add "-Z" to the complete Article No. and indicate 3WL9212-.....-..A1-Z Additional
the appropriate order code(s). @@@ price
✓ Additional price
1) The permissible temperature-rise limits according to IEC 60947-2 are
5 K lower for a tin surface than for a silver surface.
Add "-Z" to the complete Article No. and indicate 3WL9212-.....-..A1-Z Additional
the appropriate order code(s). @@@ price
✓ Additional price
1)
The permissible temperature-rise limits according to IEC 60947-2 are
5 K lower for a tin surface than for a silver surface.