SF17 Sect07
SF17 Sect07
SPEEDFAXTM 2017
contents
7 Section
7
3VA Molded Case Circuit Breakers
Catalog Numbering System 7-45
CIRCUIT BREAKERS
MOLDED CASE
QR Circuit Breakers 3VA51 125A Thermal-magnetic Trip Circuit Breakers 7-46 – 7-49
3VA61 150A Electronic Trip Circuit Breakers 7-50 – 7-53
3VA52 250A Thermal-magnetic Trip Circuit Breakers 7-54 – 7-57
3VA62 250A Electronic Trip Circuit Breakers 7-58 – 7-61
3VA53 400A Thermal-magnetic Trip Circuit Breakers 7-62 – 7-63
3VA63 400A Electronic Trip Circuit Breakers 7-64 – 7-66
3VA 3VA54 600A Thermal-magnetic Trip Circuit Breakers 7-67
molded 3VA64 600A Electronic Trip Circuit Breakers 7-68 – 7-70
case
circuit
3VA Molded Case Switch and Motor Circuit Protector 7-71
breakers 3VA Internal Accessories 7-73
3VA Breaker Operators 7-74 – 7-79
3VA Connection Technology 7-80 – 7-86
3VA Plug-in and Draw-out Technology 7-87 – 7-89
3VA Communication and Testing/Commissioning Devices 7-90 – 7-93
3VA Accessories and Electrical Requirements 7-94 – 7-99
(continued on next page)
Scan to connect
online to the
most up-to-
date version of
this Section of
SPEEDFAX.
(Section was last modified on 02/12/20) Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-1
Molded Case Circuit Breakers
SPEEDFAXTM 2017
contents
Sentron Thermal Magnetic and Electronic Circuit Breakers
7 Section
7
The Dual Function Circuit Breaker combines n Extensive and flexible accessories
GFCI and AFCI, protecting against both Arc Common internal accessories for
CIRCUIT BREAKERS
MOLDED CASE
n
Faults and Ground Faults. This, along with the the entire breaker family
new Self-Test & Lockout feature, makes it the
first in class in electrical safety for homeowners. n Power metering with the series-8
LCD electronic trip
n Faster Installation
n Illuminated rotary handles show
n Cost savings
switch position
n Smaller Device
n Smaller footprint than Sentron or
n Self Test & Lockout feature as required by VL breakers
UL 943 effective June 2015 n Enhanced Tools and Resources
trip unit and 6 lugs in separate packages. important to connect the power supply
By suffixing this number with “L” (e.g. “zig-zag” through the breaker as shown
MOLDED CASE
CIRCUIT BREAKERS
JD63B400L), you will receive frame, trip in the figure below. This assures that the
unit and lugs assembled in one container. Voltage between phases on the breaker
Pursuant to UL 489, a product ordered terminals is uniformly distributed.
thus will have the markings “LINE” and See below for an alternative connection
“LOAD”, and may not be “reverse fed” diagram. For a list of Sentron breakers
(with power flowing from the “OFF” end with the DC ratings, please refer to
of the breaker toward the “ON” end). pages 7-12 to 7-16.
Non-Interchangeable Trip Breakers
If you place an “X” after the frame size
designator (e.g. JXD63B400), you will 300 V 300 V
receive a frame and trip unit assembled, MAX. MAX.
with the trip unit made non-removable.
If you suffix an “L” to this catalog
number (e.g. JXD63B400L), you will
receive the breaker, non-removable trip
unit and lugs assembled. Unless you Load/Carga/
anticipate a specific need to change the Charge
breaker’s ampere rating in the future,
this is the preferred ordering method, as
the products are assembled to Siemens’
specifications in our factories. These
breakers are suitable for use reverse fed
according to UL 489, since the trip unit is
not removable.
W-C-375C/GEN
Interrupting Rating Breaker Type
Symmetrical (All Circuit Breakers Meet or Exceed
Class Amperesa Volts AC 60HZ Poles Range of Current Tripc the Indicated Class Level)
10ab 5,000 120/240 1 or 2 15–100 QP, BQ, QT, BL
10b 5,000 240 2 or 3 15–100 QP, BQ, BQD, CQD, BL
11a 7,500 120 1 15–100 QP, BQ, BQD, CQD, BL
11b 7,500 240 2 or 3 15–100 QP, BQ, BQD, CQD, BL
12ab 10,000 120/240 1 or 2 15–100 QP, BQ, QT, ED2, BL
12b 10,000 240 2 or 3 15–225 QP, BQ, QJ2, ED2, BQD, CQD, BL
12c 10,000 277 1 15–100 bqd, cqd, NGG, NGB, NEG, NEB
13a 14,000 277 1 15–100 ed4, bqd, cqd, NGG, NGB, NEG, NEB
13b 14,000 277/480 1, 2, or 3 15–100 ed4, bqd, cqd
14a 22,000 120/240 1 or 2 15–100 qph, bqh, blh
14b 22,000 240 2 or 3 70–400 qjh2, qj2-h, bqh, bqd, cqd, blh
15a 65,000 120/240 1 or 2 15–100 hqp, hbq, ed4, hed4, NGG, NGB
ed6, ed4, fxd6, fd6, hed4, bqd, cqd, hqj2h,
15b 65,000 240 2 or 3 15–225
NGG, NGB, NEG, NEB
16a 100,000 480 2 or 3 15–225 cfd6, ced6
16b 100,000 600 2 or 3 15–600 ced6, cfd6, cjd6, scjd6, cld6, scld6
17a 200,000 600 2 or 3 70–2000 —
18,000 240
18a 14,000 480 2 or 3 15–125 ed6, hed6, hhed6
14,000 600
22,000 240
19a 18,000 480 2 or 3 70–225 fxd6, fd6, cfd6, hfd6
14,000 600
25,000 240
20a 22,000 480 2 or 3 70–225 fxd6-a, fd6-a, cfd6, hfd6
22,000 600
hfd6, cfd6, jxd6(A), JD6(A), SJD6-B, hjd(a),
42,000 240 hjxd6(a), hhjd6, SHJD6-B, cjd6, SCJD6-B,
21a 30,000 480 2 or 3 70–800 lxd6(a), ld6(a), SLD6-B, hld6(a), hlxd6(a),
22,000 600 hhld6, SLD6-B, SHLD6-B, cld6, SCLD6-B,
lmd6, lmxd6, hlmd6, hlmxd6, md6, mxd6,
SMD6-B, hmd6, hmxd6, SHMD6-B, cmd6, SCMD6-B
65,000 240
22a 25,000 480 2 or 3 15–125 ced6, ed6, hed6, hhed6, fxd6-a, fd6-a
18,000 600
7
HHED6, FXD6-A, FD6-A, hfd6, hhfd6, cfd6,
Jd6(a), jxd6(a), SJD6-B, hjd6(a), hjxd6(a),
SHJD6-B, hhjd6, hhjxd6, cjd6, SCJD6-B,
CIRCUIT BREAKERS
MOLDED CASE
65,000 240 lxd6(a), ld6(a), SLD6-B, hld6(a), hlxd6(a),
23a 35,000 480 2 or 3 70–1200 SHLD6-B, hhld6, hhlxd6, cld6, SCLD6-B,
25,000 600 lmd6, lmxd6, hlmd6, hlmxd6, md6, mxd6,
SMD6-B, hmd6, hmxd6, SHMD6-B, cmd6, SCMD6-B,
nd6, nxd6, snd6-B, hnd6, hnxd6, shnd6-B,
cnd6, scnd6-B
65,000 240
PD6, PXD6, HPD6, HPXD6, CPD6
24a 50,000 480 2 or 3 1200–2000
RD6, RXD6, HRD6, HRXD6, SPD6-B, SHPD6-B
42,000 600
125,000 240
HHLD6, CLD6, CMD6, CND6
25a 80,000 480 2 or 3 600–4000
SCLD6-B, SCMD6-B, SCND6-B, CPD6
60,000 600
Applicable Standards UL486B — Wire Connectors and UL50 — Cabinets and Boxes
UL489 — Molded Case Circuit Breakers Solderless Lugs for use with UL869 — Service Equipment
and Circuit Breaker Enclosures. aluminum wire
NEMA AB-1 — Molded Case Circuit
UL486A — Wire Connectors and UL943 — Ground Fault Interrupters (for Breakers and Molded Case Switches
Solderless Lugs for use with copper wire personnel protectors)
CSA–C22.2 No. 5, C22.2 No. 14
UL1087 — Molded Case Switches
Note: 75°C wire for circuit breakers having a rated ampacity of a Interrupting ratings are not limited to the values or groups of
(A) Molded case circuit breakers are designed and tested 100 amperes or less. Circuit breakers having a rated ampacity values listed. However, the values listed are minimum values
in accordance to applicable portions of UL489 and meet greater than 100 amperes shall only be cabled with 75°C for the class specified.
application requirements of the National Electric Code. cable unless otherwise indicated on the circuit breaker b Single-unit or duplex construction must be specified.
Unless marked otherwise, circuit breakers are 80% duty rated. label. Exceptions to this rule are outlined in the article c Use minimum frame size for ampere rating.
(B) Molded case circuit breakers are to be connected with 60 or 110-14 C(1)(2) of the 2005 National Electric Code.
Interrupt 600V — — — — — — — — —
Rating
2-Pole
lCU — — — — — — — — —
Symmetrical
220/ lCS — — — — — — — — —
RMS
240V
2, 3-Pole
lCU — — — — — — — — —
Amperes
lCS — — — — — — — — —
IEC 2-Pole
lCU — — — — — — — — —
947-2 380/ lCS — — — — — — — — —
50/ 415V
2, 3-Pole
lCU — — — — — — — — —
60Hz
i
lCS — — — — — — — — —
2-Pole
lCU — — — — — — — — —
lCS — — — — — — — — —
500V
2, 3-Pole
lCU — — — — — — — — —
lCS — — — — — — — — —
2-Pole — — — — — — — — —
DC 125/250 V DC Interrupting Rating
3-Pole — — — — — — — — —
10-50A — 2.87 2.87 — — — 3.56 3.56 3.75
Height 10-60A 3.12 — — — — — — — —
ud ud uf uf u u u
Accessories & Auxilary Switch — — — — uf — u u u
Modifications Alarm Switch — — — — — — — — —
Mechanical Interlock — — — — — — — — —
Fungus Proofing (ref. page 7-146) — — — — — — u u u
Type 1 - Indoor Surface u u u u u —
Individual
Type 1 - Indoor, Flush — u u u u —
Enclosures
Type 3R - Outdoor-Rainproof — u u u u —
14,000 14,000b
Interrupt 600/347V 10,000 14,000 14,000 18,000 25,000
22,000b 65,000
Rating 600V — — — — — — —
Symmetrical
RMS 2-Pole
lCU 18,000 — — — — — —
Amperes
220/ lCS 9,000 — — — — — —
240V l
2, 3-Pole CU
65,000 — — — — — —
lCS 33,000 — — — — — —
IEC
2-Pole
lCU — — — — — — —
947-2 380/ lCS — — — — — — —
50/ 415V l
2, 3-Pole CU
18,000 — — — — — —
60Hz lCS 9,000 — — — — — —
2-Pole
lCU — — — — — — —
500V
lCS — — — — — — —
l
2, 3-Pole CU
— — — — — — —
lCS — — — — — — —
125/250 V DC Interrupting 2-Pole 14,000 14,000 14,000 14,000 — — —
DC
Rating 3-Pole — — — — — — —
5.00b 5.00b 5.00b
10-50A 4.50 — — —
5.40 5.40 5.40
Height 10-60A — — — — — — —
5.00b 5.00b 5.00b
Dimensions 55-125A 4.50 5.1 5.1 5.1
5.40 5.40 5.40
in Inches
1-Pole 1.00 1.00 1.00 1.00 1.0 1.0 1.0
Width 2-Pole 2.00 2.00 2.00 2.00 2.0 2.0 2.0
3-Pole 3.00 3.00 3.00 3.00 3.0 3.0 3.0
Depth 2.69 2.71 2.71 2.71 3.6 3.6 3.6
Thermal and Fixed magnetic Trip u u u u u u u
Thermal and Adjustable Magnetic trip — — — — — — —
Overcurrent
7
Adjustable Magnetic trip only — — — — — — —
Devices
Motor Circuit Protector — — — — — — —
Molded Case Switch — — — — — — —
CIRCUIT BREAKERS
MOLDED CASE
Undervoltage Trip — — — — √ √ √
Shunt Trip u u u u √ √ √
Accessories & Auxilary Switch u u u u √ √ √
Modifications Alarm Switch u u u u √ √ √
Mechanical Interlock — — — — √ √ √
Fungus Proofing (ref. page 7-146) u u u u
Type 1 - Indoor Surface
Individual
Type 1 - Indoor, Flush
Enclosures
Type 3R - Outdoor-Rainproof
NGB1B030B
1-Pole
220/ Ics — — — — — — —
240V Icu — — — — — — —
2,3-Pole
Ics — — — — — — —
Icu — — — — — — —
IEC 1-Pole
947-2 380/ Ics — — — — — — —
50/ 415V Icu — — — — — — —
60Hz 2,3-Pole
Ics — — — — — — —
Icu — — — — — — —
1-Pole
Ics — — — — — — —
500V
Icu — — — — — — —
2,3-Pole
Ics — — — — — — —
Volts — 2-Pole — — — — — — —
DC
Interrupting Rating — DC Amperes — — — — — — —
15–50A 3.75 3.75 4.00 — — — —
Height 55–125A 4.00 4.00 4.00 — — — —
60–225A — — — 7.00 7.00 7.00 7.00
Dimensions
1-Pole 1.00 1.00 1.00 — — — —
in inches
Width 2-Pole 2.00 2.00 2.00 3.00 3.00 3.00 3.00
3-Pole 3.00 3.00 3.00 4.50 4.50 4.50 4.50
Depth 2.37 2.37 2.37 2.53 2.53 2.53 2.53
Overcurrent Thermal and Fixed Magnetic Trip u u u u u u u
7
Shunt Trip u u u u u u u
Accessories and Auxiliary Switch u u u u u u u
Modifications Alarm Switch — — — — — — —
Mechanical Interlock — — — u u u u
Fungus Proofing (ref. page 7-146) u u u u u u u
Type 1 — Indoor Surface u u u u u u u
Individual Type 1 — Indoor, Flush u u u u u u u
Enclosures Type 3R — Outdoor-Rainproof u u u u u u u
Type 5, 12 — Lint, Fine Dust, Oils, Coolants — — — — — — —
1-Pole
220/ Ics 9,000d 12,500 — —
240V 2,3- Icu 65,000d 65,000 — —
Pole Ics 32,500d 32,500 — —
Icu — — — —
IEC 1-Pole
947-2 380/ Ics — — — —
50/ 415V 2,3- Icu 18,000d 25,000 — —
60Hz Pole Ics 9,000d 12,500 — —
Icu — — — —
1-Pole
Ics — — — —
500V
2,3- Icu — — — —
Pole Ics — — — —
Volts — 2-Pole 125/250 125/250 125/250 125/250
DC
Interrupting Rating — DC Amperes 14,000 14,000 14,000 14,000
15–50A 4.50 5.40 5.40 5.40
Height 55–125A 4.50 5.40 5.40 5.40
60–225A — — — —
Dimensions
1-Pole 1.00 1.00 1.00 1.00
in inches
Width 2-Pole 2.00 2.00 2.00 2.00
3-Pole 3.00 3.00 3.00 3.00
Depth 2.87 2.90 2.90 2.90
Overcurrent Thermal and Fixed Magnetic Trip u u u u
7
Devices Molded Case Switch — — — —
Undervoltage Trip — — — —
CIRCUIT BREAKERS
MOLDED CASE
Shunt Trip u u u u
Accessories and Auxiliary Switch u u u u
Modifications Alarm Switch u u u u
Mechanical Interlock — — — —
Fungus Proofing (ref. page 7-146) u u u u
Type 1 — Indoor Surface — u u u
Individual Type 1 — Indoor, Flush — u u u
Enclosures Type 3R — Outdoor-Rainproof — u u u
Type 5, 12 — Lint, Fine Dust, Oils, Coolants — — u u
CQD120 LGG2B020L
For inches / millimeters conversion, see Application Data section.
CQD breakers are rated 14,000 KAIC at 480/277V. 3-pole only.
Type CQD6—CSA only. d Applicable for 15-30A breakers only.
Applicable Standards:
n UL489 - Molded Case Circuit Breakers
n UL486B- Wire connectors and solderless lugs for n EN 60947-1 AMD 2 - Molded case circuit breakers
n UL486A - Wire connectors and solderless lugs for use with aluminum wire n EN 60947-2 AMD 2 2013
use with copper
n CSA-22.2 No. 5-13 - Molded Case Circuit Breakers, n EN 50581 2012 - RoHS compliant
Molded case switches and circuit breaker enclosures
8 8 8 8 8 8
M H C L E M H C H E M H C L E M H C L E M H C M H C
MDAE HDAE CDAE LDAE EDAE MFAE HFAE CFAE MFAE EFAE MJAE HJAE CJAE LJAE EJAE MLAE HLAE CLAE LLAE ELAE MMAE HMAE CMAE MMNAE HMNAE CMNAE
-Y -Y -Y -Y -Y
— — — — — — — — — — — — — — — — — — — — — — — — — —
100 100 200 200 — 100 100 200 200 — 100 100 200 200 — 100 100 200 200 — 100 150 200 100 150 200
— — — — — — — — — — — — — — — — — — — — — — — — — —
— — — — — — — — — — — — — — — — — — — — — — — — — —
35 65 100 150 200 35 65 100 150 200 35 65 100 150 200 35 65 100 150 200 35 65 100 35 65 100
35 65 100 150 200 35 65 100 150 200 35 65 100 150 200 35 65 100 150 200 35 65 100 35 65 100
7
18 22 35 50 100 18 22 35 50 100 18 22 35 50 100 18 22 35 50 100 25 35 50 25 35 50
18 22 35 50 100 — — — — 100 18 22 35 50 100 18 22 35 50 100 25 35 50 25 35 50
— — — — — — — — — — — — — — — — — — — — — — — — — —
CIRCUIT BREAKERS
MOLDED CASE
— — — — — — — — — — — — — — — — — — — — — — — — — —
— — — — — — — — — — — — — — — — — — — — — — — — — —
— — — — — — — — — — — — — — — — — — — — — — — — — —
— — — — — — — — — — — — — — — — — — — — — — — — — —
— — — — — — — — — — — — — — — — — — — — — — — — — —
M H C L E M H C L E M H C L E M H C L E M H C M H C
480V — 18,000 25,000 142,000 65,000 200,000 35,000 65,000 100,000 200,000
600V — — 18,000 — 18,000 100,000 22,000 25,000 25,000 100,000
Interrupt Rating
u u u u u u u u u u
Electric Motor Operator u u u u u u u u u u
Plug-In Mounting Assembly (3 Pole Only) u u u u u u u u u u
Fungus Proofing (ref. page 7-146) u u u u u u u u u u
Type 1 — Indoor Surface u u u u u u u u u u
Type 1 — Indoor, Flush u u u u u u — u — u
Type 3R — Outdoor-Rainproof u u u u u u u u u u
Individual
Type 7 — Flammable Gas Atmosphere u u u u u — u u u —
Enclosures
Type 9 — Combustion Dusttight u u u u u — u u u —
Type 5, 12 — Lint, Fine Dust, Oils, Coolants u u u u u u u u u u
Type 12K — Semi-Dusttight u u u u u u u u u u
7
Type 1 — Indoor, Flush — — — — — — — — —
Type 3R — Outdoor-Rainproof u u u u u u u u u
Individual
CIRCUIT BREAKERS
MOLDED CASE
Enclosures Type 7 — Flammable Gas Atmosphere u u u u — u u u —
Type 9 — Combustion Dusttight u u u u — u u u —
Type 5, 12 — Lint, Fine Dust, Oils, Coolants u u u u u u u u u
Type 12K — Semi-Dusttight u u u u u u u u u
UL 480V 50,000 65,000 50,000 65,000 100,0001 50,000 65,000 100,000 50,000 65,000 100,000
AC 600V 25,000 50,000 25,000 50,000 65,0001 25,000 50,000 65,000 25,000 50,000 65,000
Ratings
Type 3R — Outdoor-Rainproof u u u u u u u u — — —
Type 7 — Flammable Gas Atmosphere — — — — — — — — — — —
Type 9 — Combustion Dusttight — — — — — — — — — — —
Type 5, 12 — Lint, Fine Dust, Oils,
— — — — — — — — — — —
Coolants
Type 12K — Semi-Dusttight u u u u u u u u — — —
a For DC UPS application. b Requires Connect-all mounting assembly. Dimensions c Only applicable to non-interchangeable trip unit types:
shown are for circuit breaker only. NXD6, HNXD6, MXD6 and HMXD6
General Purpose
Thermal-Magnetic Trip Breakers
Breakers Solid State Trip Circuit Breakers
& Electronic Trip Breakers
RD6,a HRD6,a
RXD6 a HRXD6a SJD6 SHJD6 SCJD6 SLD6 SHLD6 SCLD6
Page 7-129 7-129 7-109 7-109 7-109 7-113 7-113 7-113
Poles 3 3 3 3 3 3 3 3
Amperes, Continuous 1600-2000 1600-2000 200-400 200-400 200-400 300-600 300-600 300-600
Volts 50/60 HZ 3-Pole 600 600 600 600 600 600 600 600
240V 65,000 100,000 65,000 100,000 200,000 65,000 100,000 200,000
UL 480V 50,000 65,000 35,000 65,000 150,000 35,000 65,000 150,000
600V 25,000 50,000 25,000 35,000 100,000 25,000 35,000 100,000
AC
Ratings Interrupt Rating Icu — — — — — — — —
Symmetrical RMS 220/240V
Ics — — — — — — — —
Amperes
IEC60947-2 Icu — — — — — — — —
380/415V
50/60HZ Ics — — — — — — — —
Icu — — — — — — — —
500V
Ics — — — — — — — —
2-Pole 250V DC Interrupting Ratings 30,000 30,000 — — — — — —
DC
3-Pole, 500V DC Interrupting Ratingsa 25,000 50,000 — — — — — —
Height 16.00 16.00 11.00 11.00 17.86 11.0 11.00 17.86
Dimensions in Width 3-Pole 9.00 9.00 7.50 7.50 7.50 7.50 7.50 7.50
inches
Depth 6.19 6.19 4.00 4.00 4.00 4.00 4.00 4.00
Solid State Trip — — u u u u u u
Optional DAS / Maintenance Mode — — u u u u u u
Overcurrent Thermal and Adjustable Magnetic Trip u u — — — — — —
Devices Adjustable Magnetic Trip Only — — — — — — — —
Motor Circuit Protector
Molded Case Switch u — — — — — — —
Undervoltage Trip u u u u u u u u
Shunt Trip u u u u u u u u
Auxiliary Switch u u u u u u u u
Accessories & Alarm Switch u u u u u u u u
Modifications Mechanical Interlock u u u u u u u u
Rear Connections Studs — — u u u u u u
Electric Motor Operator u u u u u u u u
Plug-In Mounting Assembly — — u u u u u u
Fungus Proofing (ref. page 7-146) u u u u u u u u
7
Mounting Block (required) u u — — — — — —
Type 1 — Indoor Surface u u u u u u u u
CIRCUIT BREAKERS
MOLDED CASE
Type 1 — Indoor, Flush — — — — — — — —
Type 3R — Outdoor-Rainproof — — u u — u u —
Individual Type 7 — Flammable Gas Atmosphere — — u u — u u —
Enclosures
Type 9 — Combustion Dusttight — — u u — u u —
Type 5, 12 — Lint, Fine Dust, Oils, Coolants — — u u u u u u
Type 12K — Semi-Dusttight — — u u u u u u
u u u u u u
MOLDED CASE
CIRCUIT BREAKERS
7
Rear Connecting Studs u u u
Plug-In Mounting Assy. w/Trip Interlock u u u
Draw-Out Assembly
CIRCUIT BREAKERS
MOLDED CASE
u u u
Handle Mechanism Options u u u
NEMA 1 – Indoor, Surface Mount u u
NEMA 1 – Indoor, Flush Mount u u
NEMA 3R – Outdoor, Rain Proof u u
Enclosures
NEMA 4, 4X – Stainless Steel u u
NEMA 7, 9 – Hazardous Locations
NEMA 12 – Dust u u
Terminal Shields u u u
Distribution Lugs u u u
Ground Sensor (Neutral Transformer) u u u
Draw-Out Assembly u u
Handle Mechanism Options u u u u
Terminal Shields u u u u
Distribution Lugs
Ground Sensor (Neutral Transformer) u u u u
a Communications available via COMPRO or COMMOD modules using Profibus or Modbus protocol.
b 500Vdc nominal, 600Vdc max. for ungrounded DC UPS systems.
c DC Interrupting Ratings are not applicable to electronic circuit breakers.
LG frame maximum 500A.
Special version, see page 7-194.
Special 600Vac 25kA version available, see page 7-178.
Circuit Breakers
Arc-Fault and Ground-Fault Breakers Selection/Wiring Diagrams
QAF2N 15 QA115AFCN — —
Plug-on Neutral/1-Pole 120V AC 20 QA120AFCN — —
QAF/QAFH 15 Q215AFCN — —
Plug-on Neutral/2-Pole 120/240V AC 20 Q220AFCN — —
7
20 QF120Aa QF120AHna QF120AHHna
1-Pole 120V AC 1-Pole AFCI 1-Pole Dual Function
30 QF130Aa QF130AHna QF130AHHna
15 QF215A QF215AHn — Plug-on Neutral Plug-on Neutral
CIRCUIT BREAKERS
MOLDED CASE
20 QF220A QF220AHn —
QPF/QPHF 30 QF230A QF230AHn —
2-Pole 120/240V AC 40 QF240A QF240AHn —
50 QF250A QF250AHn —
60 QF260A QF260AHn —
15 QF115AN — —
QPF2N 20 QF120AN — —
Plug-on Neutral/1-Pole 120V AC
30 QF130AN — —
QAF2/QPF/QE/QPF2 Accessories
Description Catalog Number
Padlocking Device 1-Pole ECPLD1 n Built to order. Allow 8 -10 weeks for delivery.
a L Listed as SWD (Switching Duty) Rated, suitable
U
Padlocking Device 2-Pole ECPLD2 for 120V AC Fluorescent Lighting.
Handle Block ECBX231M
Circuit Breakers
Type QP with INSTA-WIRE Selection
50 Q250R — —
n Built to order. Allow 2-3 weeks for delivery. c UL Listed for frequent switching applications (SWD). f Shipped 6 per sleeve.
a UL
120V AC Fluorescent Lighting. g Shipped 4 per sleeve.
Listed for use with 60/75° wire through 40 amps, d UL Listed for use on 3-phase grounded “B” systems — h UL Listed 5 KA IR.
UL listed for use with 75° wire only for 50 amps 10,000 for this application. i Type
QP1, UL listed for 16 AWG conductors and
and above, HACR rated. e Shipped 12 per sleeve. multiple wires.
b 1A and 1B contacts.
7-20 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category RESI
Circuit Breakers
Duplex, Triplex and Quadplex Plug-In Breakers Selection
7
QT 15 15 Q21515CT2
2-Pole 15 30 Q21530CT2
CIRCUIT BREAKERS
MOLDED CASE
10K AIC 20 20 Q22020CT2
120/240V AC 20 50 Q22050CT2
Inner and 30 20 Q23020CT2 QT Quadplex
Outter 2 Poles
30 25 Q23025CT2 These space saver quadplex breakers provide
Common Trip
30 30 Q23030CT2 two sets of common trip, two-pole breakers for
30 50 Q23050CT2 120/240V AC circuits, and require two panel
40 20 Q24020CT2 spaces. HACR rated.
40 30 Q24030CT2
40 40 Q24040CT2
SHIPPING: 6 per carton, (Wt. 4.8 lbs.)
For inches / millimeters conversion, see Application Data n Built to order. Allow 2–3 weeks for delivery. a on-CTL. For replacement use only in panels manufac-
N
section. tured before 1968
Product Category RESI Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-21
Circuit Breakers
Special Application Breakers Selection
HID Lighting
For high-intensity discharge lamp loads having in-rush currents
above the instantaneous trip setting of a standard breaker.
Breaker Wiring Complete Breaker UL Unenclosed
Type Diagram Ampere Rating Catalog Number
QP 15 Q115HID a n
1-Pole Figure 1 20 Q120HID a
120V AC 30 Q130HID
QP 15 Q215HID
2-Pole Figure 2 20 Q220HID n
120/240V AC 30 Q230HID n
No-Noise
For applications that require a reduction in the 60-cycle hum of
a standard breaker. Figure 3 Figure 4
QP 50 Q250NNn
2-Pole Figure 2
60 Q260NN
120/240V AC
Switching Neutrals
Used where all conductors are required to be disconnected.
Neutral pole of the circuit breaker does not connect to load Wiring Diagrams
center bus. One side is wired to neutral and the other side to
the device.
QG
7
2-Wire 15 QG215
Figure 3
Common Trip 20 QG220
120V AC
MOLDED CASE
CIRCUIT BREAKERS
QG
3-Wire Figure 4 20 QG320
Common Trip
120/240V AC
a UL Listed as SWD (Switching Duty) Rated, suitable for 120V AC Fluorescent Lighting.
n Built to order. Allow 2–3 weeks for delivery.
Note: All circuit breakers on this page are 10K AIC
7-22 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category RESI
Circuit Breakers
3/4 Inch Plug-In Breakers Selection
Features
b 3/4" format
b HACR Rated
b UL Classified for use in certain Square D
load centers
Type QD Circuit Breakers
The Type QD circuit breaker line is
available in 1-pole and 2-pole common
trip versions listed on this page.
The circuit breakers are UL Classified D120 D220
and UL Listed.
All QD breakers are supplied with load
side connectors suitable for 60/75°C 1-Pole 2-Pole
Continuous
wire and are calibrated for 40°C Current Rating 120V 120/240V Common Trip
maximum ambient applications. @ 40°C Catalog Number Catalog Number
15 D115 a D215
UL Classified
20 D120 a D220
Siemens Type QD circuit breakers are 30 D130 D230
UL Classified for use in specific Square 40 D140 D240
D load centers in place of Square D Type 50 D150 D250
QO® circuit breakers. A Panelboard 60 D160 D260
Compatibility List packaged with each
QD breaker shows which type QD Shipping Weights
circuit breakers are acceptable for
use in Square D load centers. Number of Number Per Shipping
The interrupting rating on these circuit Poles Carton Weight (lbs.)
breakers is 10,000A IR maximum and 1 16 3.8
2 8 4.2
they are not series rated with Square D
circuit breakers or equipment. This UL
Classification allows a Siemens Type QD Panelboard Compatibility List
circuit breaker to be used in place of a Listed Panelboards—Square D—Catalog Numbers
Square D Type QO circuit breaker in
those load centers that are specifically QO2L30F/S QO12M100/RB QO120-30M150/RB QO130-40M200
shown on the Panelboard Compatibility QO2-4L70F/S QO16-20M100/RB QO124L150G QO130M200/RB
list. For additional information, contact QO2-4L70TS QO16M100/RB QO124M150 QO130-40L200G/RB
7
QO2-4L70RB QO20M100/RB QO130L150G/RB QO140M200/RB
your local Siemens sales engineer.
QO6-12L100F/S QO112L125G/RB QO130M150/RB QO16L200/RB
CIRCUIT BREAKERS
MOLDED CASE
QO6-12L100DF/S QO112-24L125G/RB QO16L150/RB QO16M200/RB
QO6-12L100TF/S QO112-24L125GWGC QO16M150/RB QO18-16M200FTRB
QO6-12L100DTF/S QO116L125G QO16-30L150/RB QO20-40L200/RB
QO6-12L100RB QO116-24L125G/RB QO18-16M150FTRB QO20-40M200TF/S
QO8-16L100F/S QO12-24L125/RB QO20-30M150/RB QO20-40M200/RB
QO8-16L100DF/S QO120-24L125G QO20-30M150TF/S QO24L200/RB
QO8-16L100TF/S QO120-24L125GWGC QO20-30L150 QO24M200/RB
QO8-16L100DTF/S QO120L125G QO24L150/RB QO30L200/RB
QO8-16L100RB QO124L125G/RB QO24M150/RB QO30M200/RB
QO112M100/RB QO124M125/RB QO30L150/RB QO30-40L200/RB
QO116M100/RB QO16L125/RB QO30M150/RB QO30-40M200/RB
QO120M100/RB QO16-12M125FTRB QO8-16M200FT/RB QO40M200/RB
QO124M100 QO16-24L125/RB QO112L200G/RB QO140M225
QO12L100DF/S QO20L125/RB QO120-40M200/RB QO142L225G/RB
QO12L100RB QO20-24L125/RB QO120-40M200TC
QO12-20M100/RB QO24L125/RB QO124M200
QO12-20M100TF/S QO120-30L150G QO130L200G/RB
For inches / millimeters conversion, see Application Data a L Listed for frequent switching applications (SWD).
U
section. 120V AC Fluorescent Lighting. One or two load
conductors.
Product Category RESI Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-23
Revised on 10/31/18
Circuit Breakers
Main and Branch Circuit Breakersa Selection
Requires 6 spaces due to cross over design. Fits only EQIII 125-400A 3-phase
load centers
SHIPPING: 5 per carton (Wt. 17 lbs.)
MBK MBK
(100,125)A (150,200,225)A
UL Interrupting
Breaker Ampere Catalog Breaker Ratings (kA)
Type Rating Number Volts AC 120/240
125 Q2125B 10
QPP
7
150 Q2150B 10
2-Pole 175 Q2175Bn 10
120/240V AC 200 Q2200B 10
MOLDED CASE
CIRCUIT BREAKERS
225 Q2225B 10
125 Q2125BH 22
QPPH 150 Q2150BH 22
2-Pole 175 Q2175BHn 22
120/240V AC 200 Q2200BH 22
225 Q2225BHn 22 QPJ
HQPH 100 HQ2100H 100
2-Pole, 120/240V AC 125 HQ2125H 100
125
HQPP 150
2-Pole 175 Obsolete
120/240V AC 200
225
100
125
HQPPH 150
2-Pole Obsolete
175
120/240V AC
200
2-Pole QPP
225
For inches / millimeters conversion, see Application Data section. a All circuit breakers on this page are common trip. e NR required for horizontal applications or vertical
Q
b Reverse handle. applications where the lugs are facing up. The QN
n Built to order. Allow 2–3 weeks for delivery. c CSA Listed. breaker is required for vertical applications where the
d MBK100A
for use in 100 and 125A load centers. lugs are facing down as shown.
MBK125A for use in 125A load centers.
MBK150A for use in 150, 200 and 225A load centers.
MBK200A for use in 200 and 225A load centers.
MBK225A for use in 225A load centers.
MBK175A for use in 200 and 225A load centers.
7-24 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category RESI
Revised on 10/31/18
Circuit Breakers
Main and Branch Circuit Breakers
QS Breaker
PowerMod's core offering of residential Meter Stacks, type WMM, offers the Front View
widest product offering & flexibility in the industry. Each meter stack houses the
QuickSystem features to maximize productivity and minimize labor costs. To
further simplify installation, our 225 Amp meter stacks feature the QS breaker.
The QS breaker adds to the Siemens exclusive feature set in our Power Mod
product line. Benefits and part numbers include:
QS Breaker
Breaker Type QS QSH QSHH HQS HQSH
Amperage 10K AIC 22K AIC 42K AIC 65K AIC 100K AIC
100 QS2100 QS2100H QSH2100 QS2100HH HQS2100H
110 QS2110 QS2110H QSH2110 QS2110HH HQS2110H
125 QS2125 QS2125H QSH2125 QS2125HH HQS2125H
150 QS2150 QS2150H QSH2150 QS2150HH HQS2150H
175 QS2175 QS2175H QSH2175 QS2175HH HQS2175H
200 QS2200 QS2200H QSH2200 QS2200HH HQS2200H
225 QS2225 QS2225H QSH2225 QS2225HH HQS2225H
7
CIRCUIT BREAKERS
MOLDED CASE
CAUTION PRECAUCION
1.38
7.89
4.31
000A
000000
ON
20 2.22
NEUTRAL
.99
20
OFF
.19
.28
3"
23/8"
31/8"
QP, QPH, HQP Type QT Type QPF, QPHF, QE, QAF2, QAF2H
7
Type QN, QNH, HQN Type QNR, QNRH, HQNR Type QPP, QPPH, HQPP, HQPPH
Circuit Breakers
Lug Data Reference
QT 15–35
1
1
#14–#6 AWG Cu
#14–#6 AWG Al
40 1 #8 AWG CU-Al
40–50 Exception: 1 #8–#6 AWG Cu
1 & 2-pole QP at 55-60 1 #8–#4 AWG Al
7
EQ8693-Ultimate, PL, ES 150 1 #1–300kcmil Cu-Al
EQ8695-Ultimate, PL, ES
CIRCUIT BREAKERS
MOLDED CASE
200 1 #1–300kcmil Cu-Al
EQ9675-EQIII 100
1
1
#8-#2/0 AWG Cu
#8-#2/0 AWG Al
EQ9677-EQIII 125
1
1
#8-#2/0 AWG Cu
#8-#2/0 AWG Al
EQ9683-EQIII 150
1
1
#1/0 AWG Cu
#3/0 AWG Al
EQ9684 175
1
1
#3/0 AWG Cu
250kcmil AWG Al
EQ9685-EQIII 200
1
1
#2/0 AWG Cu
#4/0 AWG Al
EQ9686-EQIII 225
1
1
#4/0 AWG Cu
300kcmil AWG Al
Benefits
By installing a Siemens Circuit Breaker and Surge Protective Device (SPD) in the
load center of the residence, surge protection is provided for all branch circuits.
Two green LED indicator lights are provided to show that surge protection is pro-
vided for all circuits connected to the load center. These breakers should be used
for circuit protection of frequently used household or facility circuits because the
lights and devices connected to these circuits provide an effective indication that
surge protection is being provided.
The circuit breaker and SPD utilize Siemens-built 150V AC, 40mm, metal oxide
varistors (MOVs). The maximum impulse rating for the SPD module is 40kA. The
standard interrupting rating for the circuit breakers is 10k AIC. All Type QP circuit
breakers and SPD are plug-on style, with load terminals provided. The devices
are rated for 120/240V AC and are calibrated for 40 degrees C maximum ambient
applications.
Breaker Type Ampere Rating Catalog Number Surge Type
QP
(2) 15 QSA1515SPD SPD
1- Pole
120/240V AC
(2) 20 QSA2020SPD SPD
10K AIC
Amperage 15 or 20 Amp
Number of Poles (2) 1-Pole Circuit Breakers
MOLDED CASE
CIRCUIT BREAKERS
7-28 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category RESI
Molded Case Circuit Breakers
Panelboard Mounting with INSTA-WIRE Selection
7
3-Pole Bolt-On (Common-Trip 240V AC)g
CIRCUIT BREAKERS
MOLDED CASE
15 B315 B315H B315HH
20 B320 B320H B320HH
25 B325 B325H B325HHn
30 B330 B330H B330HH
35 B335 B335Hn B335HHn
40 B340 B340H B340HH
45 B345 B345Hn B345HHn
50 B350 B350H B350HH
60 B360 B360H B360HH Breaker Dimensions
70 B370 B370H B370HH Type Amperes L D1 D2
80 B380 B380Hn B380HH BL, BLH 15–50 39⁄16 23⁄8 3
90 B390 B390Hn B390HH BL, BLH 55–125 33⁄4 23⁄8 3
100 B3100 B3100H B3100HH HBL 15–125 33⁄4 23⁄8 3
c UL Listed for use on 3-phase grounded “B” systems — g Shipped 4 per sleeve.
n Built to order. Allow 2-3 weeks for delivery
10,000 for this application. h ULListed 5KA IR.
a UL Listed for use with 60/75° wire through 40 amps, d UL Listed for frequent switching applications (SWD). i 10Amp breaker does not have INSTA-WIRE.
UL listed for use with 75° wire only for 50 amps e Shipped 12 per sleeve. j For 3 Phase Applications.
and above, HACR rated. 120V AC Fluorescent Lighting. f Shipped 6 per sleeve. UL Listed for reverse feed."
b 1A and 1B contacts.
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-29
Revised on 09/30/19
Bolt-On Bolt-On
BAF2/BLF2/BLE Accessories
1-Pole Equipment 2-Pole Equipment
Description Catalog Number
Protection Protection
Padlocking Device 1-Pole ECPLD1
Padlocking Device 2-Pole ECPLD2
Handle Block ECBX231M Wiring Diagrams
7-30 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
Molded Case Circuit Breakers
Panelboard Mounting Circuit Breakers Selection
HID Lighting a
For high-intensity discharge lamp loads having in-rush
currents above the instantaneous trip setting of a standard
breaker.
15 B115HID bn
BL 20 B120HID b
1-Pole
30 B130HID n
15 B215HID bn
BL 20 B220HID b
2-Pole
30 B230HID n Switching Neutrals
7
CIRCUIT BREAKERS
MOLDED CASE
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-31
Revised on 10/31/18
BQD d
1-Pole 2-Polec 3-Polec
480Y/277V AC–
Continuous Current 277V AC–125V DC 125/250V DC 480Y/277V AC
Rating @ 40°C Catalog Number Catalog Number Catalog Number
15 BQD115 a b BQD215 e BQD315e
20 BQD120 a b BQD220 e BQD320e
25 BQD125 b BQD225 e BQD325e
30 BQD130 b BQD230 e BQD330e
35 BQD135 b BQD235 e BQD335e
40 BQD140 b BQD240 e BQD340e
45 BQD145 bn BQD245 e BQD345e
50 BQD150 b BQD250 e BQD350e
60 BQD160 BQD260 BQD360
BQD, BQD6
70 BQD170n BQD270 BQD370
80 BQD180n BQD280 BQD380
90 BQD190n BQD290 BQD390
100 BQD1100n BQD2100 BQD3100
Interrupting Ratings (max. RMS symmetrical amperes kA) Lugs For 60/75°C Wire
UL IEC 947-2f BQD – Load End Only
7
7-32 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
Revised on 05/31/18
7
100 HGB1B100B HGB2B100B HGB3B100B 100 LGB1B100B LGB2B100B LGB3B100B
110 HGB1B110B HGB2B110B HGB3B110B 110 LGB1B110B LGB2B110B LGB3B110B
125 HGB1B125B HGB2B125B HGB3B125B 125 LGB1B125B LGB2B125B LGB3B125B
CIRCUIT BREAKERS
MOLDED CASE
Shipping Weights Lugs for 60/75°C Wire
Number of Number per Shipping Ampere Catalog
Poles Carton Weight lbs. (kg) Type Rating Wire Size Number
1 1 0.9 (0.4) #14-#6 AWG Cu TC1Q1 (qty. 1)
NGB 15-30A
2 1 1.9 (0.9) #12-#6 AWG Al 3TC1Q1 (qty. 3)
3 1 2.9 (1.2) HGB
LGB #8-1/0 AWG Cu
35-125A 3TC1GG20
#8-2/0 AWG Al
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-33
Revised on 10/31/18
a SWD rated. Suitable for reverse feed applications For external accessories, please refer
b HID rated. f3 pole breakers suitable for single phase applications to pages 7-150 to 7-155
c 2-pole only. g xGB2 breakers require different strap kits than xGB. Refer to For internal accessories, please refer
2-pole only or two outer poles of 3-pole breaker Section 11 for specific catalog numbers. to page 7-35
7-34 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
Revised on 05/04/17
Shunt Trip
BQD, BQD6, CQD, CQD6,
NGG, HGG, LGG, NGB, HGB,
Control Voltage LGB, NGB2, HGB2 and LGB2
V AC V DC Catalog Number
120 — CQDST120
240 — CQDST240s
277 — CQDST277s
480 — CQDST480s
600 — CQDST600
— 012 CQDST12
— 024 CQDST24
— 048 CQDST48
— 125 CQDST125
Auxiliary Switch
BQD, BQD6, CQD,
Maximum CQD6, NGG, HGG, LGG,
Voltage Number NGB, HGB, LGB, NGB2, CQDST120AAS
of HGB2 and LGB2
AC DC Contacts Catalog Number
240 125 1A–1B CQDA1
240 125 2A–2B CQDA2
Alarm Switch
BQD, BQD6, CQD, CQD6,
NGG, HGG, LGG, NGB, HGB,
Maximum Voltage LGB, NGB2, HGB2 and LGB2
AC DC Catalog Number
7
Shunt Trip NGG, HGG, LGG, NGB, HGB,
Voltage LGB, NGB2, HGB2 and LGB2
AC DC Catalog Number
CIRCUIT BREAKERS
MOLDED CASE
24 — CQDST24AASs
120 — CQDST120AASs
240 — CQDST240AASs CQD with Accessory Installed
277 — CQDST277AASs
480 — CQDST480AASs
600 — CQDST600AASs
— 12 CQDST12DASs
— 24 CQDST24DASs
— 48 CQDST48DASs
— 125 CQDST125DASs
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-35
Revised on 11/30/19
7
125 A 125 A
3VA41 1 in 2 2 (50.8) 5.1 (129.4) 3.6 (92.2) 0.94 0.43 1 in 2-pole 3-pole
/2-pole
3VA41 2 2 (50.8) 5.1 (129.4) 3.6 (92.2) 1.13 0.51
CIRCUIT BREAKERS
MOLDED CASE
3VA41 3 3 (76.2) 5.1 (129.4) 3.6 (92.2) 1.64 0.74
125 A 125 A
Universal release
UVR
UNI
x
x
x
x
Description Catalog Number Other
Padlocking Device for 3VA4 breaker 3VA9038-0LB11 Cylinder lock (type Ronis) x
Circuit Breakers
Lug-In/Lug-Out with INSTA-WIRE Selection
All BQ/BQH/HBQ circuit breakers are supplied with load side lugs. If line side lugs are required, add suffix “L” to catalog number. Consult Siemens
for any additional charge. All standard circuit breakers are calibrated for 40°C maximum ambient application.
80 BQ2H080n — —
90 BQ2H090n — —
MOLDED CASE
CIRCUIT BREAKERS
100 BQ2H100n — —
3-Pole
3-Pole (Common-Trip 240V AC)g
15 BQ3B015 BQ3B015H HB3B015n
20 BQ3B020 BQ3B020H HB3B020n
25 BQ3B025n BQ3B025Hn HB3B025
30 BQ3B030 BQ3B030H HB3B030
35 BQ3B035n BQ3B035H HB3B035
40 BQ3B040 BQ3B040H HB3B040
45 BQ3B045n BQ3B045H HB3B045
50 BQ3B050 BQ3B050H HB3B050
60 BQ3B060 BQ3B060H HB3B060 Factory Modifications
70 BQ3B070 BQ3B070H HB3B070n Description Catalog Number
80 BQ3B080 BQ3B080Hn HB3B080n Line Side Lugs add suffix...L
90 BQ3B090 BQ3B090Hn HB3B090n Quick Connect Lug add suffix...QX
100 BQ3B100 BQ3B100H HB3B100
400Hz Calibration add suffix...Y h
Marine 50˚ C Ambient
add suffix...M
Calibration
BQ / BQH / HBQ Internal Accessories Fungus Proofing add suffix...F
Description Catalog Number Field/Factory Installed
120VAC Shunt Trip add suffix...00S01n Factory
24VAC Shunt Trip add suffix...00S07n Factory For external accessories, please refer
to page 7-148
120V Auxiliary Switch add suffix...01nb Factory
n Built to order. Allow 2-3 weeks for delivery b 1A and 1B contacts. e Shipped
12 per sleeve.
c UL
Listed for use on 3-phase grounded “B” systems — f Shipped
6 per sleeve.
a ULListed for use with 60/75° wire through 40 amps, 10,000 for this application. g Shipped
4 per sleeve.
UL listed for use with 75° wire only for 50 amps d UL
Listed for frequent switching h UL
Listed 5KA IR.
and above, HACR rated. applications (SWD). 120V AC Fluorescent Lighting. Refer to Table A on page 7-143
7-38 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
Revised on 11/30/19
Interrupting Ratings
(KA) (RMS Symmetrical
Breaker Ampere Catalog Line Side Load Side Amperes) Volts AC
Type Rating Number Connector Connector 120 120/240
7
60 BQ2B060QXD TA1Q1 Quick-Connect 10
CIRCUIT BREAKERS
MOLDED CASE
Lugs-For Use with BQXD BQ Enclosures
Circuit Cab. Lug Type Catalog Number d
Breaker Per Wire Range Catalog
Amp. Rtg. Lug AWG Number 1 EB3100S c
Line Side 3R WB3100
10–40 1 #16–#6 Cu
1 #12–#6 Al TC1Q1 a b
45–125 1 #8–#1 Cu BQ Breaker Dimensions
1 #6–#1/0 Al TA1Q1
Dimensions (inches)
Number of Poles Breaker Type Amperes L D1 D2
Finger Safe Terminal Shield
Protects against accidental contact with 1, 2 BQ 15-50 3¾ 23⁄8 3
lugs–1 per lug. Fits line and load end. 1, 2 BQH, HBQ 15-50 4 23⁄8 3
Catalog Number Qty 1, 2 BQ, BQH, HBQ 55-125 4 23⁄8 3
BQFS2 2 3 BQ, BQH, HBQ 15-100 4 23⁄8 3
BQFS1K 1000 1, 2 BQXD 15-60 4½ 23⁄8 3
For inches / millimeters conversion, bConnector has steel construction. Type BQXD uses TA1Q1 or TC1Q1 lugs on line side of
see Application Data section. cSurface mounted indoor. If flush mounting is required, circuit breaker.
replace suffix “S” in catalog number with suffix “F”.
n Built to order. Allow 2–3 weeks for delivery. Neutral included in enclosure.
a UL
Enclosures, see Section 6
Listed for use with 60/75° wire through 40 amps, Enclosure will not accept circuit breakers with shunt
UL listed for use with 75° wire only for 50 amps For external accessories, please refer
trips or auxiliary switches installed.
and above, HACR rated. to pages 7-148, 7-150 to 7-155
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-39
Revised on 05/04/17
7’’
3’’
2.5 D
3’’
2-pole
4.5’’ 3-pole
n Built to order. Allow 2–3 weeks for delivery. a See Note: A page 7-137.
Note: QR breakers are UL Listed for reverse feed
applications. Enclosures Section 6
b HACR rated. For external accessories, please refer
to pages 7-150 to 7-155
7-40 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
Revised on 04/10/17
Shunt Trip
Shunt Trip and Auxiliary
Control Voltage Shunt Trip Switch Combination
AC DC In Rush Catalog Number Catalog Number
— 24 1.1A S07QR2 S07QR2A
120 - 240 48 2.0A AC / 1.8A DC S01QR2 S01QR2A
Auxiliary Switch
Contains (1) or (2) sets of “A” contacts and “B” contacts
External Accessories
Description Catalog Number
Padlock Device HPLQR
Padlock
Padlock
Device
Device
Padlock HPLQR
HPLQR
Device HPLQR Handle
HandleBlock
HandleBlock
Device
Device
Block HBLQR
HBLQR
Device HBLQR Mechanical
MechanicalInterlock
MechanicalInterlock
SBMIQR
SBMIQR
Interlock SBMIQR
7
CIRCUIT BREAKERS
MOLDED CASE
Type CQD (Cable In - Cable Out) DIN Rail Mountc Shipping Weights
1-Pole 2-Pole 3-Pole Number of Number per Shipping
Continuous 277V AC 480Y/277V AC Poles Carton Weight lbs. (kg)
Current Rating 125V DC 125/250V DC 480Y/277V AC 1 1 0.5 (0)
@ 40°C Catalog Number Catalog Number Catalog Number 2 1 1.0 (0)
115 CQD115 ab CQD215b CQD315b 3 1 1.5 (1)
120 CQD120 ab CQD220b CQD320b
125 CQD125 b CQD225b CQD325b
130 CQD130 b CQD230b CQD330b Lugs For 60/75°C Wire
135 CQD135bn CQD235bn CQD335b
Amps Wire Size
140 CQD140bn CQD240b CQD340b
15–40 #14–#6 AWG Cu
145 CQD145bn CQD245bn CQD345bn
#12–#6 AWG Al
150 CQD150bn CQD250b CQD350b
160 CQD160n CQD260 CQD360 45–100 #8–#1 AWG Cu
#6–#1/0 AWG Al
170 CQD170n CQD270 CQD370
180 CQD180n CQD280 CQD380
190 CQD190n CQD290n CQD390
100 CQD1100n CQD2100 CQD3100
CQD
MOLDED CASE
CIRCUIT BREAKERS
7-42 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
Revised on 11/30/19
Line and load lugs are included as standard. If no lugs are required, remove the “L” suffix.
HACR rated. GG
Suitable for screws or DIN rail mounting.
Type HGG (Cable In - Cable Out) Type LGG (Cable In - Cable Out)
Continuous Continuous
1-Pole 2-Pole 3-Pole 1-Pole 2-Pole 3-Pole
Current Rating Current Rating
@ 40°C Catalog Number Catalog Number Catalog Number @ 40°C Catalog Number Catalog Number Catalog Number
15 HGG1B015Lb HGG2B015Lb HGG3B015Lb 15 LGG1B015Lb LGG2B015Lb LGG3B015Lb
20 HGG1B020Lb HGG2B020Lb HGG3B020Lb 20 LGG1B020Lb LGG2B020Lb LGG3B020Lb
25 HGG1B025Lb HGG2B025Lb HGG3B025Lb 25 LGG1B025Lb LGG2B025Lb LGG3B025Lb
30 HGG1B030Lb HGG2B030Lb HGG3B030Lb 30 LGG1B030Lb LGG2B030Lb LGG3B030Lb
35 HGG1B035Lb HGG2B035Lb HGG3B035Lb 35 LGG1B035Lb LGG2B035Lb LGG3B035Lb
40 HGG1B040Lb HGG2B040Lb HGG3B040Lb 40 LGG1B040Lb LGG2B040Lb LGG3B040Lb
45 HGG1B045Lb HGG2B045Lb HGG3B045Lb 45 LGG1B045Lb LGG2B045Lb LGG3B045Lb
50 HGG1B050Lb HGG2B050Lb HGG3B050Lb 50 LGG1B050Lb LGG2B050Lb LGG3B050Lb
60 HGG1B060L HGG2B060L HGG3B060L 60 LGG1B060L LGG2B060L LGG3B060L
70 HGG1B070L HGG2B070L HGG3B070L 70 LGG1B070L LGG2B070L LGG3B070L
80 HGG1B080L HGG2B080L HGG3B080L 80 LGG1B080L LGG2B080L LGG3B080L
7
90 HGG1B090L HGG2B090L HGG3B090L 90 LGG1B090L LGG2B090L LGG3B090L
100 HGG1B100L HGG2B100L HGG3B100L 100 LGG1B100L LGG2B100L LGG3B100L
CIRCUIT BREAKERS
MOLDED CASE
110 HGG1B110L HGG2B110L HGG3B110L 110 LGG1B110L LGG2B110L LGG3B110L
125 HGG1B125L HGG2B125L HGG3B125L 125 LGG1B125L LGG2B125L LGG3B125L
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-43
Molded Case Circuit Breakers
Accessoriesa Selection
Shunt Trip
BQD, BQD6, CQD,
NGG, HGG, LGG, NGB,
Control Voltage HGB and LGB
V AC V DC Catalog Number
120 — CQDST120
240 — CQDST240s
277 — CQDST277s
480 — CQDST480s
600 — CQDST600
— 012 CQDST12
— 024 CQDST24
— 048 CQDST48
— 125 CQDST125
Auxiliary Switch
BQD, BQD6, CQD,
Maximum Number NGG, HGG, LGG, NGB,
Voltage of HGB and LGB CQDST120AAS
AC DC Contacts Catalog Number
240 125 1A–1B CQDA1
240 125 2A–2B CQDA2
Alarm Switch
BQD, BQD6, CQD,
NGG, HGG, LGG, NGB,
Maximum Voltage HGB and LGB
AC DC Catalog Number
24 — CQDST24AASs
120 — CQDST120AASs
240 — CQDST240AASs
CQD with Accessory Installed
277 — CQDST277AASs
480 — CQDST480AASs
600 — CQDST600AASs
— 12 CQDST12DASs
— 24 CQDST24DASs
— 48 CQDST48DASs
— 125 CQDST125DASs
7-44 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
Revised on 12/31/19
3VA 6 1 40 – 5 HL 3 1 – 0 A A0
Breaker Designation
Thermal magnetic panelboard breakers 4
Thermal magnetic (Cable-in Cable-out) breakers 5
Electronic trip breakers 6
Frame Size
125/150A 1
250A 2
400A 3
600A 4
Rated Current
3VA41/3VA51 3VA52 3VA53 3VA54 3VA61 3VA62 3VA63 3VA64
15A 95
20A 200A 200A 20
225A 225A 22
25A 250A 250A 250A 250A 25
30A 300A 30
35A 350A 35
40A 40A 400A 40A 400A 400A 40
45A 45A 450A 45
50A 50A 500A 50
60A 60A 600A 600A 60
70A 70A 70
80A 80A 80
90A 90A 90
100A 100A 100A 100A 10
110A 110A 11
125A 125A 12
150A 150A 15
175A 17
Interrupting Capacity @ 480V
3VA4/3VA5 3VA6
MCP/MCS 0
MCP/MCS MCP/MCS 1
25K 4
35K 35K 5
65K 65K 6
100K 100K 7
150K 8
Trip Unit Protection Functions
3VA4/3VA5 L I N
TM230 MCCB fix adj EC
TM210 MCCB fix fix ED
TM240 MCCB adj adj EF
TM230 MCCB fix adj 100% GC
TM210 MCCB fix fix 100% GD
7
TM240 MCCB adj adj 100% GF
TM110M MSP fix MG
TM120M MSP adj MH
CIRCUIT BREAKERS
MOLDED CASE
TM120M MSP adj MU
MCS110 MSC fix BB
3VA6 L S I G N LCD com. measurement values
ETU320 LI MCCB adj adj 0%/50%/100% HL
ETU330 LIG MCCB adj adj adj 0%/50%/100% HM
ETU350 LSI MCCB adj adj fix 0%/50%/100% HN
ETU550 LSI MCCB adj adj adj 20/40%...100/160% yes yes standard JP
ETU556 LSI(G) MCCB adj adj adj alarm 20/40%...100/160% yes yes standard JT
ETU560 LSIG MCCB adj adj adj adj 20/40%...100/160% yes yes standard JQ
ETU820 LI MCCB adj adj 20/40%...100/160% yes yes advanced KL
ETU830 LIG MCCB adj adj adj 20/40%...100/160% yes yes advanced KM
ETU850LSI MCCB adj adj adj 20/40%...100/160% yes yes advanced KP
ETU856 LSI(G) MCCB adj adj adj alarm 20/40%...100/160% yes yes advanced KT
ETU860 LSIG MCCB adj adj adj adj 20/40%...100/160% yes yes advanced KQ
ETU310M MCP adj MS
MCS110 MCS fix BB
Number of Poles
1 pole 1
2 pole 2
3 pole 3
4 pole 4
1-in-2 pole 5
2-in-3 pole 6
Connection Technology
blank, punched copper bar without any lugs 1
Regional Specifics (as applicable)
Standard 0
NAVAL/50C 1
100% Rated (3VA6) 2
Auxixliary Releases Without A
Auxiliary/Alarm Switches Without A0
7
125 3VA5112-4EC31-0AA0 3VA5112-5EC31-0AA0 3VA5112-6EC31-0AA0
TM240 ATAM Enclosures (3-pole only)
CIRCUIT BREAKERS
MOLDED CASE
15 3VA5195-4EF31-0AA0 3VA5195-5EF31-0AA0 3VA5195-6EF31-0AA0 Nema Type Catalog Number
20 3VA5120-4EF31-0AA0 3VA5120-5EF31-0AA0 3VA5120-6EF31-0AA0 1 surface 3VAE125N1S
30 3VA5130-4EF31-0AA0 3VA5130-5EF31-0AA0 3VA5130-6EF31-0AA0 1 flush 3VAE125N1F
40 3VA5140-4EF31-0AA0 3VA5140-5EF31-0AA0 3VA5140-6EF31-0AA0 3R 3VAE125N3R
50 3VA5150-4EF31-0AA0 3VA5150-5EF31-0AA0 3VA5150-6EF31-0AA0 12 3VAE125N12
60 3VA5160-4EF31-0AA0 3VA5160-5EF31-0AA0 3VA5160-6EF31-0AA0 4X (304) 3VAE125N4X
70 3VA5170-4EF31-0AA0 3VA5170-5EF31-0AA0 3VA5170-6EF31-0AA0 4X (316) 3VAE125N4X316
80 3VA5180-4EF31-0AA0 3VA5180-5EF31-0AA0 3VA5180-6EF31-0AA0 Neutral N250X
100 3VA5110-4EF31-0AA0 3VA5110-5EF31-0AA0 3VA5110-6EF31-0AA0 200% Neutral N2250X
7
Steel wrap around (Cu AWG
3/0 3VA9133-0JA11 3VA9134-0JA11
cable only), 1 cable lugs 14
CIRCUIT BREAKERS
MOLDED CASE
Aluminum body lug small AWG AWG
3VA9133-0JB10 3VA9134-0JB10 125 A 125 A
(Cu/Al cable), 1 cable lug 14 10
Aluminum body lug (Cu/Al AWG Slot No.: 23 22 21 23 22 21 11 12 13
3/0 3VA9133-0JB11 3VA9134-0JB11
cable), 1 cable lugs 14 Auxiliary switch Type
Aluminum body lug small AUX_HQ x x x x x x x x x
AWG AWG
with control wire tap (Cu/Al 3VA9133-0JG10 3VA9134-0JG10 AUX_HQ_el x x x x x x x x x
14 10 Auxiliary switch
cable), 1 cable lug x x x
Aluminum body lug with AUX_HP
AWG x x x
control wire tap (Cu/Al 3/0 3VA9133-0JG11 3VA9134-0JG11
14 LCS_HQ x
cable), 1 cable lugs Leading
Aluminum body lug large (Cu/ LCS_HQ_el x
changeover switch
AWG 300
Al cable), 1 cable lugs with 1 3VA9133-0JJ12 LCS_HP x
4 kcmil
extended terminal cover Alarm switch Type
Aluminum body lug large TAS_HQ x x x x x x
with control wire tap (Cu/Al AWG 300
3VA9133-0JC12 Trip alarm switch TAS_HQ_el x x x x x x
cable), 1 cable lug and 4 kcmil
1 extended terminal cover TAS_HP x x x
Distribution lug, 6 cables (Cu/ SAS_HQ
AWG AWG Short circuit alarm switch
Al cable), 1 cable lugs with 3VA9133-0JF60 3VA9134-0JF60 SAS_HQ_el
14 2
1 extended terminal cover
Auxiliary release Type
Copper body lug small (Cu AWG AWG
3VA9133-0JD10 3VA9134-0JD10
cable only), 1 cable lugs 14 10 4 Shunt trip flexible STF
STL
x
x
x
x
Copper body lug (Cu cable AWG Shunt trip left
2/0 3VA9133-0JD11 3VA9134-0JD11 STL_el
only), 1 cable lugs 14
Copper body lug small with Residual current release RCR
AWG AWG
control wire tap (Cu cable 3VA9133-0JK10 3VA9134-0JK10 Undervoltage release UVR x x
14 10
only), 1 cable lugs Universal release UNI x x
Copper body lug with Other
AWG
control wire tap (Cu cable 2/0 3VA9133-0JK11 3VA9134-0JK11
14 Cylinder lock (type Ronis) x
only), 1 cable lugs
Ordering Information
The catalog numbers listed below are for complete, non-interchangable
trip circuit breakers without lugs.
Order required lugs or connection technology separately for field installation.
All 3VA61 electronict trip circuit breakers are UL listed for reverse feed applications.
All 3VA61 electronic trip circuit breakers are available with 100% ratings.
For 100% rated electronic trip circuit breakers, change the 13th digit of the
catalog number to the number "2". (For example, a 35KA @480VAC, 40A,
3-pole, 100% rated 3VA61 would be catalog number 3VA6140-5HL31-2AA0)
Requires the use of rated lugs — see lug table below.
All 3VA6 circuit breakers are certified to UL 489 Supplement SB, are marked
3VA61 150A 3-Pole “Naval”, and are suitable for use at 50C.
Ordering Information
The catalog numbers listed below are for complete, non-interchangable
trip circuit breakers without lugs.
Order required lugs or connection technology separately for field installation.
All 3VA61 electronict trip circuit breakers are UL listed for reverse feed applications.
All 3VA61 electronic trip circuit breakers are available with 100% ratings.
For 100% rated electronic trip circuit breakers, change the 13th digit of the
catalog number to the number "2". (For example, a 35KA @480VAC, 40A,
3-pole, 100% rated 3VA61 would be catalog number 3VA6140-5HL31-2AA0)
Requires the use of rated lugs — see lug table below.
All 3VA6 circuit breakers are certified to UL 489 Supplement SB, are marked
3VA61 150A 4-Pole “Naval”, and are suitable for use at 50C.
7
40 3VA6140-5JT41-0AA0 3VA6140-6JT41-0AA0 3VA6140-7JT41-0AA0 3VA6140-8JT41-0AA0 —
100 3VA6110-5JT41-0AA0 3VA6110-6JT41-0AA0 3VA6110-7JT41-0AA0 3VA6110-8JT41-0AA0 —
CIRCUIT BREAKERS
MOLDED CASE
150 3VA6115-5JT41-0AA0 3VA6115-6JT41-0AA0 3VA6115-7JT41-0AA0 3VA6115-8JT41-0AA0 —
ETU560 LSIG with LCD
40 3VA6140-5JQ41-0AA0 3VA6140-6JQ41-0AA0 3VA6140-7JQ41-0AA0 3VA6140-8JQ41-0AA0 —
100 3VA6110-5JQ41-0AA0 3VA6110-6JQ41-0AA0 3VA6110-7JQ41-0AA0 3VA6110-8JQ41-0AA0 —
150 3VA6115-5JQ41-0AA0 3VA6115-6JQ41-0AA0 3VA6115-7JQ41-0AA0 3VA6115-8JQ41-0AA0 —
ETU820 LI LCD with Metering
40 3VA6140-5KL41-0AA0 3VA6140-6KL41-0AA0 3VA6140-7KL41-0AA0 3VA6140-8KL41-0AA0 —
100 3VA6110-5KL41-0AA0 3VA6110-6KL41-0AA0 3VA6110-7KL41-0AA0 3VA6110-8KL41-0AA0 —
150 3VA6115-5KL41-0AA0 3VA6115-6KL41-0AA0 3VA6115-7KL41-0AA0 3VA6115-8KL41-0AA0 —
ETU830 LIG with LCD and Metering
40 3VA6140-5KM41-0AA0 3VA6140-6KM41-0AA0 3VA6140-7KM41-0AA0 3VA6140-8KM41-0AA0 —
100 3VA6110-5KM41-0AA0 3VA6110-6KM41-0AA0 3VA6110-7KM41-0AA0 3VA6110-8KM41-0AA0 —
150 3VA6115-5KM41-0AA0 3VA6115-6KM41-0AA0 3VA6115-7KM41-0AA0 3VA6115-8KM41-0AA0 —
ETU850 LSI with LCD and Metering
40 3VA6140-5KP41-0AA0 3VA6140-6KP41-0AA0 3VA6140-7KP41-0AA0 3VA6140-8KP41-0AA0 —
100 3VA6110-5KP41-0AA0 3VA6110-6KP41-0AA0 3VA6110-7KP41-0AA0 3VA6110-8KP41-0AA0 —
150 3VA6115-5KP41-0AA0 3VA6115-6KP41-0AA0 3VA6115-7KP41-0AA0 3VA6115-8KP41-0AA0 —
ETU856 LSI(G Alarm) with LCD and Metering
40 3VA6140-5KT41-0AA0 3VA6140-6KT41-0AA0 3VA6140-7KT41-0AA0 3VA6140-8KT41-0AA0 3VA6160-0KT41-0AA0a
100 3VA6110-5KT41-0AA0 3VA6110-6KT41-0AA0 3VA6110-7KT41-0AA0 3VA6110-8KT41-0AA0 3VA6110-0KT41-0AA0
150 3VA6115-5KT41-0AA0 3VA6115-6KT41-0AA0 3VA6115-7KT41-0AA0 3VA6115-8KT41-0AA0 3VA6115-0KT41-0AA0
ETU860 LSIG with LCD and Metering
40 3VA6140-5KQ41-0AA0 3VA6140-6KQ41-0AA0 3VA6140-7KQ41-0AA0 3VA6140-8KQ41-0AA0 3VA6160-0KQ41-0AA0a
100 3VA6110-5KQ41-0AA0 3VA6110-6KQ41-0AA0 3VA6110-7KQ41-0AA0 3VA6110-8KQ41-0AA0 3VA6110-0KQ41-0AA0
150 3VA6115-5KQ41-0AA0 3VA6115-6KQ41-0AA0 3VA6115-7KQ41-0AA0 3VA6115-8KQ41-0AA0 3VA6115-0KQ41-0AA0
a The lowest amperage trip unit available for the EDAE class breakers is 60 amps.
ETU550-LSI, ETU556 LSI(A), ETU560-LSIG, ETU820-LI, ETU830-LIG, ETU850-LSI, ETU856 LSI(A), ETU860-LSIG
Continuous LSI 3P with LI, LIG, LSI, LSIG,
Amperage LI, LIG, LSI, LSIG, LSI(G) LSI, LSIG, LSI(G) LIG, LSIG, LSI(G) External CT LSI(G) 4P only
In (Amp) Ir(Amp) (L) tld (sec) (L) Ii (Amp) (I) Isd (Amp) (S) tsd (sec) (S) Ig (Amp) (G) tg (G) IN=xIr (Amp) IN (Amp)
40 15 - 40 0.5 - 25 60-480 24 - 400 0.05 - 0.5 15 - 40 0.05 - 0.8 15 - 64 / OFF 15 - 64 / OFF
100 40 - 100 0.5 - 25 150-1200 60 - 1000 20 - 100 20 - 160 / OFF 20 - 150 / OFF
150 60 - 150 0.5 - 20 225-1500 90 - 1500 30 - 150 30 - 240 / OFF 30 - 150 / OFF
For specific trip settings refer to the Electronic Trip Unit section3VA
of the
UL3VA Systems
Molded Manual,
Case Circuit Breakers
which can be found in the document download center at https://www.siemens.com/download?BTLV_50412.
Accessories and Spare Parts
Internal accessories
Internal accessories 3VA6 3VA6
Optional equipment 150/250 A 150/250 A
3-pole 4-pole
250 A 250 A
Slot No.: 24 23 22 21 11 12 13 14 34 33 32 31 24 23 22 21 11 12 13 14
Auxiliary switch Type
AUX_HQ x x x x x x x x x x x x x x x x x x x x
AUX_HQ_el x x x x x x x x x x x x x x x x x x x x
Auxiliary switch
AUX_HP x x x x x x x x x x
x x x x x
LCS_HQ x x
7
Leading changeover switch LCS_HQ_el x x
LCS_HP x x
CIRCUIT BREAKERS
MOLDED CASE
Alarm switch Type
TAS_HQ x x x x x x x x
Trip alarm switch TAS_HQ_el x x x x x x x x
TAS_HP x x x x
EAS_HQ x x
Electrical alarm switch
EAS_HQ_el x x
Auxiliary release Type
7
250 3VA5225-5EC31-0AA0 3VA5225-6EC31-0AA0 3VA5225-7EC31-0AA0 number "1". (For example, a 35KA
TM240 ATAM @480VAC, 150A, 3-pole, NAVAL
rated 3VA52 would be catalog
CIRCUIT BREAKERS
MOLDED CASE
70 3VA5270-5EF31-0AA0 3VA5270-6EF31-0AA0 3VA5270-7EF31-0AA0
80 3VA5280-5EF31-0AA0 3VA5280-6EF31-0AA0 3VA5280-7EF31-0AA0 number 3VA5215-5ED31-1AA0)
100 3VA5210-5EF31-0AA0 3VA5210-6EF31-0AA0 3VA5210-7EF31-0AA0
125 3VA5212-5EF31-0AA0 3VA5212-6EF31-0AA0 3VA5212-7EF31-0AA0
150 3VA5215-5EF31-0AA0 3VA5215-6EF31-0AA0 3VA5215-7EF31-0AA0 Enclosures (3-pole only)
175 3VA5217-5EF31-0AA0 3VA5217-6EF31-0AA0 3VA5217-7EF31-0AA0 Nema Type Catalog Number
200 3VA5220-5EF31-0AA0 3VA5220-6EF31-0AA0 3VA5220-7EF31-0AA0 1 surface 3VAE250N1S
250 3VA5225-5EF31-0AA0 3VA5225-6EF31-0AA0 3VA5225-7EF31-0AA0 1 flush 3VAE250N1F
3R 3VAE250N3R
12 3VAE250N12
Dimensions Shipping Weight 4X (304) 3VAE250N4X
Breaker Poles W in. (mm) H in. (mm) D in. (mm) lbs. kg 4X (316) 3VAE250N4X316
3VA52 2(3-) pole 4.1 (105) 7.3 (185) 3.3 (83) 4.1 1.9 Neutral N250X
3VA52 3-pole 4.1 (105) 7.3 (185) 3.3 (83) 4.5 2.1 200% Neutral N2250X
7
x x
Aluminum body lug large LCS_HQ x
with control wire tap Leading
CIRCUIT BREAKERS
MOLDED CASE
(Cu/Al cable) single cable AWG 2 350 kcmil 3VA9233-0JC13 LCS_HQ_el x
changeover switch
lugs and 1 extended LCS_HP x
terminal cover Alarm switch Type
Aluminum body lug,
TAS_HQ x x x x
2 cables (Cu/Al cable)
AWG 4 300 kcmil 3VA9233-0JJ22 Trip alarm switch TAS_HQ_el x x x x
with control wire tap and
1 extended terminal cover TAS_HP x x
Distribution lug, 6 Cables Auxiliary release Type
(Cu/Al cable) with 1 AWG 14 AWG 2 3VA9233-0JF60
extended terminal cover STF x
Shunt trip flexible
Copper body lug
(Cu cable only) AWG 6 350 kcmil 3VA9233-0JD12
single cable lugs Shunt trip left STL x
Copper body lug with 4
control wire tap (Cu cable AWG 6 350 kcmil 3VA9233-0JK12 Undervoltage release UVR x
only) single cable lugs
Universal release UNI x
See page 7-73 for internal accessory Other
part numbers.
Cylinder lock (type Ronis) x
I201_19494
Ordering Information
The catalog numbers listed below are for complete, non-interchangable
trip circuit breakers without lugs.
Order required lugs or connection technology separately for field installation.
All 3VA62 electronic trip circuit breakers are UL listed for reverse feed applications.
All 3VA62 electronic trip circuit breakers are available with 100% ratings.
For 100% rated electronic trip circuit breakers, change the 13th digit of the
catalog number to the number "2". (For example, a 35KA @480VAC, 100A,
3-pole, 100% rated 3VA62 would be catalog number 3VA6210-5HL31-2AA0)
Requires the use of rated lugs — see lug table below.
All 3VA6 circuit breakers are certified to UL 489 Supplement SB, are marked
3VA62 250A 3-Pole “Naval”, and are suitable for use at 50C.
Ordering Information
The catalog numbers listed below are for complete, non-interchangable
trip circuit breakers without lugs.
Order required lugs or connection technology separately for field installation.
All 3VA62 electronict trip circuit breakers are UL listed for reverse feed applications.
All 3VA62 electronic trip circuit breakers are available with 100% ratings.
For 100% rated electronic trip circuit breakers, change the 13th digit of the
catalog number to the number "2". (For example, a 35KA @480VAC, 100A,
3-pole, 100% rated 3VA62 would be catalog number 3VA6210-5HL31-2AA0)
Requires the use of rated lugs — see lug table below.
All 3VA6 circuit breakers are certified to UL 489 Supplement SB, are marked
3VA62 250A 4-Pole “Naval”, and are suitable for use at 50C.
7
250 3VA6225-5JT41-0AA0 3VA6225-6JT41-0AA0 3VA6225-7JT41-0AA0 3VA6225-8JT41-0AA0 —
ETU560 LSIG with LCD
CIRCUIT BREAKERS
MOLDED CASE
100 3VA6210-5JQ41-0AA0 3VA6210-6JQ41-0AA0 3VA6210-7JQ41-0AA0 3VA6210-8JQ41-0AA0 —
250 3VA6225-5JQ41-0AA0 3VA6225-6JQ41-0AA0 3VA6225-7JQ41-0AA0 3VA6225-8JQ41-0AA0 —
ETU820 LI with LCD and Metering
100 3VA6210-5KL41-0AA0 3VA6210-6KL41-0AA0 3VA6210-7KL41-0AA0 3VA6210-8KL41-0AA0 —
250 3VA6225-5KL41-0AA0 3VA6225-6KL41-0AA0 3VA6225-7KL41-0AA0 3VA6225-8KL41-0AA0 —
ETU830 LIG with LCD and Metering
100 3VA6210-5KM41-0AA0 3VA6210-6KM41-0AA0 3VA6210-7KM41-0AA0 3VA6210-8KM41-0AA0 —
250 3VA6225-5KM41-0AA0 3VA6225-6KM41-0AA0 3VA6225-7KM41-0AA0 3VA6225-8KM41-0AA0 —
ETU850 LSI with LCD and Metering
100 3VA6210-5KP41-0AA0 3VA6210-6KP41-0AA0 3VA6210-7KP41-0AA0 3VA6210-8KP41-0AA0 —
250 3VA6225-5KP41-0AA0 3VA6225-6KP41-0AA0 3VA6225-7KP41-0AA0 3VA6225-8KP41-0AA0 —
ETU856 LSI(G Alarm) with LCD and Metering
100 3VA6210-5KT41-0AA0 3VA6210-6KT41-0AA0 3VA6210-7KT41-0AA0 3VA6210-8KT41-0AA0 —
250 3VA6225-5KT41-0AA0 3VA6225-6KT41-0AA0 3VA6225-7KT41-0AA0 3VA6225-8KT41-0AA0 3VA6225-0KT41-0AA0
ETU860 LSIG with LCD and Metering
100 3VA6210-5KQ41-0AA0 3VA6210-6KQ41-0AA0 3VA6210-7KQ41-0AA0 3VA6210-8KQ41-0AA0 —
250 3VA6225-5KQ41-0AA0 3VA6225-6KQ41-0AA0 3VA6225-7KQ41-0AA0 3VA6225-8KQ41-0AA0 3VA6225-0KQ41-0AA0
ETU550-LSI, ETU556 LSI(A), ETU560-LSIG, ETU820-LI, ETU830-LIG, ETU850-LSI, ETU856 LSI(A), ETU860-LSIG
Continuous LSI 3P with LI, LIG, LSI, LSIG,
Amperage LI, LIG, LSI, LSIG, LSI(G) LSI, LSIG, LSI(G) LIG, LSIG, LSI(G) External CT LSI(G) 4P only
In (Amp) Ir(Amp) (L) tld (sec) (L) Ii (Amp) (I) Isd (Amp) (S) tsd (sec) (S) Ig (Amp) (G) tg (G) IN=xIr (Amp) IN (Amp)
100 40 - 100 0.5 - 25 150-1200 60 - 1000 20 - 100 20 - 160 / OFF 20 - 160 / OFF
0.05 - 0.5 0.05 - 0.8
250 100 - 250 0.5 - 13 375-2500 150 - 2500 50 - 250 50 - 400 / OFF 50 - 250 / OFF
For specific trip settings refer to the Electronic Trip Unit section3VA UL3VA
of the Molded Case
Systems Circuit Breakers
Manual,
which can be found in the document download center at https://www.siemens.com/download?BTLV_50412
Accessories and Spare Parts
Internal accessories
Internal accessories 3VA6 3VA6
Optional equipment 150/250 A 150/250 A
3-pole 4-pole
250 A 250 A
Slot No.: 24 23 22 21 11 12 13 14 34 33 32 31 24 23 22 21 11 12 13 14
Auxiliary switch Type
AUX_HQ x x x x x x x x x x x x x x x x x x x x
AUX_HQ_el x x x x x x x x x x x x x x x x x x x x
Auxiliary switch
AUX_HP x x x x x x x x x x
x x x x x
LCS_HQ x x
Leading changeover switch LCS_HQ_el x x
LCS_HP x x
7
Alarm switch Type
TAS_HQ x x x x x x x x
CIRCUIT BREAKERS
MOLDED CASE
Trip alarm switch TAS_HQ_el x x x x x x x x
TAS_HP x x x x
EAS_HQ x x
Electrical alarm switch
EAS_HQ_el x x
Auxiliary release Type
Slot No.: 25 24 23 22 21 11 12 13 14 15 35 34 33 32 31 2
225 3VA5322-5GF41-0AA0 3VA5322-6GF41-0AA0 3VA5322-7GF41-0AA0 Auxiliary switch Type
250 3VA5325-5GF41-0AA0 3VA5325-6GF41-0AA0 3VA5325-7GF41-0AA0 AUX_HQ x x x x x x x x x x x x x x x
300 3VA5330-5GF41-0AA0 3VA5330-6GF41-0AA0 3VA5330-7GF41-0AA0 Auxiliary switch
AUX_HQ_el x x x x x x x x x x x x x x x
AUX_HP x x x x x x
350 3VA5335-5GF41-0AA0 3VA5335-6GF41-0AA0 3VA5335-7GF41-0AA0 x x x x x x
400 3VA5340-5GF41-0AA0 3VA5340-6GF41-0AA0 3VA5340-7GF41-0AA0 LCS_HQ x
Leading
changeover LCS_HQ_el x
switch LCS_HP x
Alarm switch Type
7
Dimensions Shipping Weight Trip alarm switch
TAS_HQ
TAS_HQ_el
x
x
x
x
x
x
x
x
Breaker Poles W in. (mm) H in. (mm) D in. (mm) lbs. kg TAS_HP x x
CIRCUIT BREAKERS
MOLDED CASE
Auxiliary release Type
3VA53 3 6.4 (162) 10.3 (262) 6.7 (170) 11.5 5.2
3VA53 4 8.2 (208) 10.3 (262) 6.7 (170) 15.0 6.8 Shunt trip flexible STF x x
Ordering Information
The catalog numbers listed below are for complete, non-interchangable
trip circuit breakers without lugs.
Order required lugs or connection technology separately for field installation.
All 3VA63 electronict trip circuit breakers are UL listed for reverse feed applications.
3VA63 electronic trip circuit breakers are available with 100% ratings (250A only).
For 100% rated electronic trip circuit breakers, change the 13th digit of the
catalog number to the number "2". (For example, a 35KA @480VAC, 250A,
3-pole, 100% rated 3VA63 would be catalog number 3VA6325-5HL31-2AA0)
Requires the use of rated lugs — see lug table below.
All 3VA6 circuit breakers are certified to UL 489 Supplement SB, are marked
3VA63 400A 3-Pole “Naval”, and are suitable for use at 50C.
7
400 3VA6340-5JT41-0AA0 3VA6340-6JT41-0AA0 3VA6340-7JT41-0AA0 3VA6340-8JT41-0AA0 —
ETU560 LSIG with LCD
CIRCUIT BREAKERS
MOLDED CASE
250 3VA6325-5JQ41-0AA0 3VA6325-6JQ41-0AA0 3VA6325-7JQ41-0AA0 3VA6325-8JQ41-0AA0 —
400 3VA6340-5JQ41-0AA0 3VA6340-6JQ41-0AA0 3VA6340-7JQ41-0AA0 3VA6340-8JQ41-0AA0 —
ETU820 LI with LCD and Metering
250 3VA6325-5KL41-0AA0 3VA6325-6KL41-0AA0 3VA6325-7KL41-0AA0 3VA6325-8KL41-0AA0 —
400 3VA6340-5KL41-0AA0 3VA6340-6KL41-0AA0 3VA6340-7KL41-0AA0 3VA6340-8KL41-0AA0 —
ETU830 LIG with LCD and Metering
250 3VA6325-5KM41-0AA0 3VA6325-6KM41-0AA0 3VA6325-7KM41-0AA0 3VA6325-8KM41-0AA0 —
400 3VA6340-5KM41-0AA0 3VA6340-6KM41-0AA0 3VA6340-7KM41-0AA0 3VA6340-8KM41-0AA0 —
ETU850 LSI with LCD and Metering
250 3VA6325-5KP41-0AA0 3VA6325-6KP41-0AA0 3VA6325-7KP41-0AA0 3VA6325-8KP41-0AA0 —
400 3VA6340-5KP41-0AA0 3VA6340-6KP41-0AA0 3VA6340-7KP41-0AA0 3VA6340-8KP41-0AA0 —
ETU856 LSI(G Alarm) with LCD and Metering
250 3VA6325-5KT41-0AA0 3VA6325-6KT41-0AA0 3VA6325-7KT41-0AA0 3VA6325-8KT41-0AA0 3VA6325-0KT31-0AA0
400 3VA6340-5KT41-0AA0 3VA6340-6KT41-0AA0 3VA6340-7KT41-0AA0 3VA6340-8KT41-0AA0 3VA6340-0KT31-0AA0
ETU860 LSIG with LCD and Metering
250 3VA6325-5KQ41-0AA0 3VA6325-6KQ41-0AA0 3VA6325-7KQ41-0AA0 3VA6325-8KQ41-0AA0 3VA6325-0KQ31-0AA0
400 3VA6340-5KQ41-0AA0 3VA6340-6KQ41-0AA0 3VA6340-7KQ41-0AA0 3VA6340-8KQ41-0AA0 3VA6340-0KQ31-0AA0
25 24 23 22 21 11 12 13 14 15 35 34 33 32 31 25 24 23 22 21 11 12 13 14 15
Auxiliary switch Type
NEMA Type Catalog Number
AUX_HQ x x x x x x x x x x x x x x x x x x x x x x x x x
ETU550-LSI, ETU556 LSI(A), ETU560-LSIG, ETU820-LI, ETU830-LIG, ETU850-LSI, ETU856 LSI(A), ETU860-LSIG
Continuous LSI 3P with LI, LIG, LSI, LSIG,
Amperage LI, LIG, LSI, LSIG, LSI(G) LSI, LSIG, LSI(G) LIG, LSIG, LSI(G) External CT LSI(G) 4P only
In (Amp) Ir(Amp) (L) tld (sec) (L) Ii (Amp) (I) Isd (Amp) (S) tsd (sec) (S) Ig (Amp) (G) tg (G) IN=xIr (Amp) IN (Amp)
250 100 - 250 0.5 - 25 375-3000 150 - 2500 50 - 250 50 - 400 / OFF 50 - 400 / OFF
4/6 0.05Siemens
- 0.5 · 04/2017 0.05 - 0.8
400 150 - 400 0.5 - 17 600-4000 240 - 4000 80 - 400 80 - 640 / OFF 80 - 400 / OFF
For specific trip settings refer to the Electronic Trip Unit section of the 3VA Systems Manual,
which can be found in the document download center at https://www.siemens.com/download?BTLV_50412
7
600 3VA5460-5EF41-0AA0 3VA5460-6EF41-0AA0 3VA5460-7EF41-0AA0
TM230 FTFM 100% Neutral
450 3VA5445-5GC41-0AA0 3VA5445-6GC41-0AA0 3VA5445-7GC41-0AA0
CIRCUIT BREAKERS
MOLDED CASE
500 3VA5450-5GC41-0AA0 3VA5450-6GC41-0AA0 3VA5450-7GC41-0AA0
3VA54 600A 3-Pole
600 3VA5460-5GC41-0AA0 3VA5460-6GC41-0AA0 3VA5460-7GC41-0AA0
TM240 ATAM 100% Neutral
450 3VA5445-5GF41-0AA0 3VA5445-6GF41-0AA0 3VA5445-7GF41-0AA0
500 3VA5450-5GF41-0AA0 3VA5450-6GF41-0AA0 3VA5450-7GF41-0AA0
Ordering Information
600 3VA5460-5GF41-0AA0 3VA5460-6GF41-0AA0 3VA5460-7GF41-0AA0 The catalog numbers listed here are
for complete, non-interchangable trip
circuit breakers without lugs.
Dimensions Shipping Weight
Breaker Poles W in. (mm) H in. (mm) D in. (mm) lbs. kg Order required lugs or connection
3VA54 3 6.4 (162) 10.3 (262) 6.7 (170) 11.5 5.2
technology separately for field
3VA54 4 8.2 (208) 10.3 (262) 6.7 (170) 15.0 6.8
installation.
All 3VA54 thermal-magnetic trip
circuit breakers are UL listed for
Interrupting Ratings for 3VA54 reverse feed applications.
RMS Symmetrical Amperes (kA)
Volts AC (50/60 Hz) Volts DC
For NAVAL rated thermal-magnetic
trip circuit breakers, change the
Interrupting Breaker 480Y/ 600Y/ 250 600 750 750 1000 13th digit of the catalog number
Class Type 240 277V 480 347V 600 (2P) (3P) (3P) (4P) (4P)
to the number "1". (For example,a
M MLAS 85 35 35 18 18 50 50 10 50 10
35KA@480VAC, 600A, 3-pole, rated
H HLAS 100 65 65 25 25 85 85 10 85 10
3VA54 would be catalog number
C CLAS 200 100 100 35 35 100 100 10 100 10
3VA5460-5EC31-1AA0)
a Available with NAVAL/50C ratings.
Ordering Information
The catalog numbers listed below are for complete, non-interchangable
trip circuit breakers without lugs.
Order required lugs or connection technology separately for field installation.
All 3VA64 electronict trip circuit breakers are UL listed for reverse feed applications.
3VA64 electronic trip circuit breakers are available with 100% ratings (400A only).
For 100% rated electronic trip circuit breakers, change the 13th digit of the
catalog number to the number "2". (For example, a 35KA @480VAC, 400A,
3-pole, 100% rated 3VA64 would be catalog number 3VA6440-5HL31-2AA0)
Requires the use of copper lugs — see lug table below.
All 3VA6 circuit breakers are certified to UL 489 Supplement SB, are marked
3VA64 600A 3-Pole “Naval”, and are suitable for use at 50C.
7
600 3VA6460-5JT41-0AA0 3VA6460-6JT41-0AA0 3VA6460-7JT41-0AA0 3VA6460-8JT41-0AA0 —
ETU560 LSIG with LCD
CIRCUIT BREAKERS
MOLDED CASE
400 3VA6440-5JQ41-0AA0 3VA6440-6JQ41-0AA0 3VA6440-7JQ41-0AA0 3VA6440-8JQ41-0AA0 —
600 3VA6460-5JQ41-0AA0 3VA6460-6JQ41-0AA0 3VA6460-7JQ41-0AA0 3VA6460-8JQ41-0AA0 —
ETU820 LI with LCD and Metering
400 3VA6440-5KL41-0AA0 3VA6440-6KL41-0AA0 3VA6440-7KL41-0AA0 3VA6440-8KL41-0AA0 —
600 3VA6460-5KL41-0AA0 3VA6460-6KL41-0AA0 3VA6460-7KL41-0AA0 3VA6460-8KL41-0AA0 —
ETU830 LIG with LCD and Metering
400 3VA6440-5KM41-0AA0 3VA6440-6KM41-0AA0 3VA6440-7KM41-0AA0 3VA6440-8KM41-0AA0 —
600 3VA6460-5KM41-0AA0 3VA6460-6KM41-0AA0 3VA6460-7KM41-0AA0 3VA6460-8KM41-0AA0 —
ETU850 LSI with LCD and Metering
400 3VA6440-5KP41-0AA0 3VA6440-6KP41-0AA0 3VA6440-7KP41-0AA0 3VA6440-8KP41-0AA0 —
600 3VA6460-5KP41-0AA0 3VA6460-6KP41-0AA0 3VA6460-7KP41-0AA0 3VA6460-8KP41-0AA0 —
ETU856 LSI(G Alarm) with LCD and Metering
400 3VA6440-5KT41-0AA0 3VA6440-6KT41-0AA0 3VA6440-7KT41-0AA0 3VA6440-8KT41-0AA0 —
600 3VA6460-5KT41-0AA0 3VA6460-6KT41-0AA0 3VA6460-7KT41-0AA0 3VA6460-8KT41-0AA0 3VA6460-0KT41-0AA0
ETU860 LSIG with LCD and Metering
400 3VA6440-5KQ41-0AA0 3VA6440-6KQ41-0AA0 3VA6440-7KQ41-0AA0 3VA6440-8KQ41-0AA0 —
600 3VA6460-5KQ41-0AA0 3VA6460-6KQ41-0AA0 3VA6460-7KQ41-0AA0 3VA6460-8KQ41-0AA0 3VA6460-0KQ41-0AA0
Slot No.: 25 24 23 22 21 11 12 13 14 15 35 34 33 32 31 25 24 23 22 21 11 12 13 14 15
NEMA Type Catalog Number Auxiliary switch Type
AUX_HQ x x x x x x x x x x x x x x x x x x x x x x x x x
1 Surface 3VAE6001S AUX_HQ_el x x x x x x x x x x x x x x x x x x x x x x x x x
Auxiliary switch
AUX_HP x x x x x x x x x x
1 Flush 3VAE6001F x x x x x x x x x x
LCS_HQ x x
3R 3VAE6003R Leading changeover switch LCS_HQ_el x x
LCS_HP x x
12 3VAE60012
Alarm switch Type
EAS_HQ_el x x
Auxiliary release Type
200% Neutral HN678ACB
MOLDED CASE
CIRCUIT BREAKERS
7
CIRCUIT BREAKERS
MOLDED CASE
Interrupting Ratings
RMS Symmetrical Amperes (kA)
Volts AC (50/60 Hz) Volts DC
Breaker 600Y/
Frame Type 240 480 347V 600 125 (1P) 250 (2P) 500d (3P) 600 (3P)
3VA51 HEAP 150 65 25 — 30 100 100 —
HFAP 100 65 25 25 85 85
3VA52
CFAP 200 100 35 35 100 100
HJAP 100 65 25 25 — — — —
3VA53
CHAP 200 100 35 35 — — — — a Rated at 600 Y/347 V AC.
HLAP 100 65 25 25 — — — —
b SCCR is 100kA at 480 V. SCCR rating is the maximum
3VA54 permissible short circuit current of the MCP in combina-
CLAP 200 100 35 35 — — — — tion with an appropriate overload protection device.
3VA61 CDAR 200 100 35 35 — — — — c SCCR is 65kA at 480 V. SCCR rating is the maximum
3VA62 CFAR 200 100 35 — — — — — permissible short circuit current of the MCP in combination
with an appropriate overload protection device.
3VA63 CJAR 200 100 35 35 — — — — d 2 poles required for 500VDC for breaker types HFAP
3VA64 CLAR 200 100 35 35 — — — — and CFAP.
Shunt Trips
Catalog Number Auxiliary switches and
Type VAC 50/60 Hz VDC (3 slots) alarm switches HP
380 ... 600 — 3VA9978-0BL20
— 12 3VA9978-0BL10
Shunt Trip Left 24 24 ... 30 3VA9978-0BL30
(STL) 48 ... 60 — 3VA9978-0BL31
110 ... 127 110 ... 127 3VA9978-0BL32
208 ... 277 220 ... 250 3VA9978-0BL33
24 — 3VA9978-0BA20
48 ... 60 — 3VA9978-0BA21
Shunt Trip Flexible 110 ... 127 — 3VA9978-0BA22
(STF)b 208 ... 277 — 3VA9978-0BA23
380 ... 500 — 3VA9978-0BA24
600 — 3VA9978-0BA25
AUX LCS TAS
Undervoltage Release
— 12 3VA9978-0BB10
— 24 3VA9978-0BB11 Shunt trip left Undervoltage
— 48 3VA9978-0BB12 STL releases UVR
7
— 125 ... 127 3VA9978-0BB14
Undervoltage Release
— 250 3VA9978-0BB16
(UVR)
24 — 3VA9978-0BB20
CIRCUIT BREAKERS
MOLDED CASE
120 ... 127 — 3VA9978-0BB24
208 ... 230 — 3VA9978-0BB25
440 ... 480 — 3VA9978-0BB27
a Use only with 3VA6. b Shunt trip flexible can be used in the left pocket of the
3VA5 breakers. They can be used in the left or right
pocket of the 3VA6 breakers.
— — — u 3VA9447-0EK31
Standard with door interlock, Gray u — — — 3VA9137-0EK33
MOLDED CASE
CIRCUIT BREAKERS
7
Standard with Gray u — — — 3VA9137-0PK13
illumination kit — u u — 3VA9277-0PK13
CIRCUIT BREAKERS
MOLDED CASE
EMERGENCY-OFF Yellow-Red u — — — 3VA9137-0PK15
— u u — 3VA9277-0PK15
n Without mounting plate EMERGENCY-OFF Yellow-Red u — — — 3VA9137-0PK17
n Rotary operator with shaft 300 mm with illumination kit — u u — 3VA9277-0PK17
n Handle with masking plate 75 x 75 mm
n Degree of protection
Type 1, 12, 3R and 4X
Standard with mounting plate Gray u — — — 3VA9137-0PK51
— u u — 3VA9277-0PK51
Standard with mounting plate, Gray u — — — 3VA9137-0PK53
with illumination kit — u u — 3VA9277-0PK53
EMERGENCY-OFF with Yellow-Red u — — — 3VA9137-0PK55
mounting plate — u u — 3VA9277-0PK55
n With mounting plate EMERGENCY-OFF with mounting Yellow-Red u — — — 3VA9137-0PK57
n Rotary operator with short shaft plate, with illumination kit — u u — 3VA9277-0PK57
n Handle with masking plate 75 x 75 mm
n Degree of protection
Type 1, 12, 3R and 4X
Standard for use with the side wall Gray u — — — 3VA9177-0VF40
mounted rotary operators — u u — 3VA9277-0VF40
n Without mounting plate
Side
Mounted
Rotary
Operator
Door
Interlock
7
8 mm shaft 600 mm long (for pistol grip handles) u u u u 3VA9477-0GF11
(Fixing bracket required)
CIRCUIT BREAKERS
MOLDED CASE
Adapter for Shaft for door mounted operator u u u u 8UD1900-2DA00
— u u u 3VA9477-0GA80
7
Bowden Cable, 84 inches (2.1m) — — — u 3VA9578-0CC50
Bowden Cable, 96 inches (2.4m) — — — u 3VA9578-0CC60
CIRCUIT BREAKERS
MOLDED CASE
Bowden Cable, 120 inches (3.0m) — — — u 3VA9578-0CC70
Bowden Cable, 144 inches (3.6m) — — — u 3VA9578-0CC80
MaxFlex Auxiliary switch u u u u 3VA9478-0CX10
(leading from On to Off)
n 1 CO
Box Terminals
For molded case circuit breakers/
Minimum Maximum rated current
cable cross- cable cross- 3VA5
section section 3VA6 3VA6
(standard) (standard) 3VA5 3VA5 150A 400A
Type Class B Class B 125A 250A 250A 600A Part Number
Steel wrap-around lug AWG 14 3/0 u — — — 3VA9133-0JA11
(Cu cable only) AWG 10 3/0 — u — — 3VA9233-0JA11
kit of 3 single lugs
AWG 4 350 kcmil — u — — 3VA9233-0JA12
AWG 10 3/0 — — u — 3VA9143-0JA12
AWG 4 350 kcmil — — u — 3VA9243-0JA12
1/0 500 kcmil — — — u 3VA9473-0JA13
Steel wrap-around lug AWG 14 AWG 10 u — — — 3VA9134-0JA11
(Cu cable only) AWG 10 3/0 — — u — 3VA9144-0JA12
kit of 4 single lugs
AWG 4 350 kcmil — — u — 3VA9244-0JA12
1/0 500 kcmil — — — u 3VA9474-0JA13
3 lug 4 lug
7
2 Cables with control wire AWG 4 300 kcmil — — u — 3VA9243-0JC22a 3VA9243-0JC28
tap (Cu/Al cable)
2/0 600 kcmil - - - u 3VA9473-0JC23 3VA9473-0JC28
kit of 3 single lugs and
CIRCUIT BREAKERS
MOLDED CASE
1 extended terminal cover
7
CIRCUIT BREAKERS
MOLDED CASE
Front bus connectors 32 mm / 10 mm / — u u — 3VA9273-0QB00
extended kit of 3 single connectors 1.3 inch 0.4 inch
and 1 insulating plate 40 mm / 12.5 mm / — — — u 3VA9473-0QB00
1.6 inch 0.5 inch
— — u — 3VA9241-0QF10
— — — u 3VA9471-0QF10
7
CIRCUIT BREAKERS
MOLDED CASE
Terminal cover extended for u — — — 3VA9131-0WF40
4-pole breakers — — u — 3VA9271-0WF40
— — — u 3VA9471-0WF40
Plug-in socket
For molded case circuit breakers /
rated current
3VA61/62 3VA63 3VA64
Type 150A/250A 400A 600A Part Number
Plug-in unit, 3-pole, complete kit u — — 3VA9143-0KP00
Consists of: Plug-in socket, Plug-in unit, — u — 3VA9343-0KP00
conversion kit, Mounting screw kit
— — u 3VA9443-0KP00
3 pole 4 pole
3 pole 4 pole
Draw-out units
For molded case circuit breakers /
rated current
3VA61/62 3VA63 3VA64
Type 150A/250A 400A 600A Part Number
Draw-out unit, 3-pole, complete kit u — — 3VA9143-0KD00
Consists of: Draw-out socket, Draw-out unit, conversion — u — 3VA9343-0KD00
7
kit, Mounting screw kit
— — u 3VA9443-0KD00
CIRCUIT BREAKERS
MOLDED CASE
Draw-out unit, 4-pole, complete kit u — — 3VA9144-0KD00
Consists of: Draw-out socket, Draw-out unit, — u — 3VA9344-0KD00
conversion kit, Mounting screw kit
— — u 3VA9444-0KD00
3 pole 4 pole
Note: Crank handle for the drawout unit must be ordered seperately.
Accessories
For molded case circuit breakers /
rated current
3VA61/62 3VA63/64
Type 150A/250A 400A/600A Part Number
Cable cage for plug-in/draw-out unit 3-/4- u — 3VA9167-0KB02
pole (spare part) Cable duct for routing of
the required cables from the internal acc.
on the back of the breaker.
— u 3VA9367-0KB02
— u 3VA9347-0KT00
— u 3VA9344-0KB01
MOLDED CASE
CIRCUIT BREAKERS
Other Accessories
Type Part Number
Communication link for draw-out unit 3VA9977-0KC00
Consists of: Cable kit with 3 special position signaling switches,
connecting cable 3VA9987-0KC10
7
n For plug-in units
CIRCUIT BREAKERS
MOLDED CASE
Cylinder lock (type Ronis) 3VA9980-0VL10
n Includes a lock with 2 keys
3VA9980-0VL30
n For locking
PROFIBUS
I201_19498
Ethernet (Modbus TCP)
SIMATIC S7
PROFINET
3VA-line
T-Connector T-Connector
4
7
COM800 DSP800
breaker data server display
MOLDED CASE
CIRCUIT BREAKERS
Modules
For molded case circuit
breakers / rated current
3VA61/62 3VA63/64
Type 150A/250 A 400A/600A Part Number
24 V Module u — 3VA9177-0TB50
n 24 V DC
— u 3VA9377-0TB50
n For mounting in the right-hand accessories compartment
of the 3VA6
n Optional energy supply for the ETU, also includes contiunous
or RS485 module
7
n 2 terminating resistors
CIRCUIT BREAKERS
MOLDED CASE
n Ethernet 10/100 Mbit/s interface
or RS485 module
the COM800/COM100 breaker data server, and the 3VA molded case circuit
breakers conneccted to it, to PROFIBUS DPV1
n The 7KM PAC PROFIBUS DP expansion module provides the status and measured
quantities of the 3VA molded case circuit breaker for the PROFIBUS DP master.
It receives information (e.g. commands) from the PROFIBUS DP master, and
forwards this information to the 3VA molded case circuit breaker
7KM PAC Switched Ethernet PROFINET expansion module 7KM9300-0AE01-0AA0
n The 7KM PAC Switched Ethernet PROFINET expansion module is used to connect
the COM800/COM100 breaker data server, and the connected 3VA molded case
circuit breaker, to PROFINET via two Ethernet interfaces
n The 7KM PAC Switched Ethernet PROFINET expansion module provides the status
and measured quantities of the 3VA molded case circuit breaker to PROFINET via
the PROFINET IO, PROFIenergy and Modbus TCP protocols
COM100 breaker data server, and the 3VA molded case circuit breaker connected
to it, to Modbus RTU
n The 7KM PAC RS485 Modbus expansion module provides the status and measured
quantities of the 3VA molded case circuit breaker for the Modbus RTU master.
It receives information (e.g. commands) from the Modbus RTU master, and forwards
this information to the 3VA molded case circuit breaker
n Provides spur line feeder to COM060 and loops to the nextcircuit breaker
Preassembled T-Connector-to-T-Connector or
T-Connector-to-COM800/ COM100 connecting cable
n 0.4 m long 3VA9987-0TC10
n 1 m long 3VA9987-0TC20
n 2 m long 3VA9987-0TC30
n 4 m long 3VA9987-0TC40
transformer for the N conductor for 3-pole 3VA6 molded case circuit breakers for 5-series and
8-series ETUs (ETU850, ETU856, ETU860), including connecting cable
MOLDED CASE
CIRCUIT BREAKERS
of the COM800/COM100 and the connected 3VA6 molded case circuit breaker
EFB300 3VA9977-0UA10
n External function box for connection to the ETU of the 3VA6 molded case circuit breaker
n ZSI functionality
n S0 interface
Test devices
Type Part Number
TD300 3VA9977-0MA10
n Connection to the front interface of the ETU
n Test device for activating the ETU and triggering a test trip
TD500 3VA9977-0MB10
n Connection to the front interface of the ETU
n ETU parameterization
n Including external power supply unit with adapter for Europe, UL and GB
7
CIRCUIT BREAKERS
MOLDED CASE
Spare part: Cable for connecting to the TD500 to the 3VA6 molded 3VA9977-0MY10
case circuit breaker
to the lowest possible value through an external signal (e.g. door contact)
n Available for all 3VA6 circuit breakers with electronic trip unit
3VA5/3VA6 3VA4
Adapter kit for mounting the cylinder lock u — — — 3VA9137-0LF10
(type Ronis) in the accessories compartment — u — — 3VA9237-0LF10
of the molded case circuit breaker
— — u — 3VA9147-0LF10
Comprising 2 cylinder lock casings (one for locking
and one for interlocking) and the appropriate mounting — — — u 3VA9347-0LF10
module
n To implement an interlock or a lock: select suitable cyl-
inder lock(s)
n For an interlock: select the same cylinder lock number
compartment
7
7
Cover frame for door cut-out for MO320 u — — — 3VA9033-0SB10
motor operators — u u — 3VA9237-0SB30
CIRCUIT BREAKERS
MOLDED CASE
— — — u 3VA9377-0SB30
Cover frame for door cut-out for front u — — — 3VA9033-0SB10
mounted rotary operators — u u — 3VA9143-0SB10
— — — u 3VA9373-0SB10
Cover frame for door cut-out for front — — — u 3VA9377-0SB30
mounted rotary operator with door
interlock
Cover frame for door cut-out for door — u u — 3VA9233-0SB20
feedthrough — — — u 3VA9333-0SB20
a 2 mounting plates are required. They are screwed onto b Breakers with plug-in unit can be mounted on the
the profile rail that can be ordered above. Different mounting plates, but the profile rails cannot be used.
breakers can be mutually interlocked.
Other accessories
For molded case circuit break-
ers/rated current
3VA5
3VA6 3VA6
3VA5 3VA5 150A 400A
Type 125A 250A 250A 600A Part Number
Busbar adapter system with 60 mm u — — — 8US1211-4SS00
busbar center-to-center spacing — u u — 8US1213-4AP03
3-pole
— — — u 8US1213-4AH04
Internal accessories
Auxiliary switches electrical requirements
Auxiliary switches and Auxiliary switches and alarm Auxiliary switches and
alarm switches HQ switches HQ_electronic alarm switches HP
AUX LCS TAS EAS AUX LCS TAS EAS AUX LCS TAS
Rated Ue V AC 240 24 600
operational 50 Hz
voltage V DC 250 24 250
Conventional Ith = Ie A 6 0.3 10
free-air thermal
current
IEC AC-12 12 V A 6 0.3 10
Ratings 24 V A 6 0.3 10
Listed 48 V A 6 -- 10
125 V A 6 -- 10
220/240 V A 6 -- 10
380/440 V A -- -- 6
600 V A -- -- 2
AC-15 12 V A 3 0.3 6
2/4 V A 3 0.3 6
48 V A 3 -- 6
125 V A 3 -- 6
220/240 V A 3 -- 6
380/440 V A -- -- 2
600 V A -- -- 0.6
DC-12 12 V A 6 0.1 6
24 V A 4 0.1 6
48 V A 2 -- 2
110 V A 0.5 -- 0.6
7
250 V A 0.25 -- 0.3
DC-13 12 V A 1 0.07 3
24 V A 0.8 0.07 3
CIRCUIT BREAKERS
MOLDED CASE
48 V A 0.4 -- 0.8
110 V A 0.2 -- 0.2
250 V A 0.1 -- 0.1
Max. rated Inductive load 24 V A 3 0.3 6
current (UL/CSA) (0.75-0.8 AC) 300 V A 3 -- 6
600 V A -- -- 6
Pilot duty (AC) 24 V A 3 -- 6
127 V A 3 -- 6
240 V A 3 -- 3
480 V A -- -- 1.5
600 V A -- -- 1.2
Resistive load (DC) 24 V A 0.25 0.1 0.3
250 V A 0.25 -- 0.3
Resistive load - pilot 125 V A 0.6 -- 0.9
duty sequence (DC) 250 V A 0.3 -- 0.55
Minimum load At 24 mA 70 0.5 70
V DC
At 5 V DC mA -- 1 --
Power consumption Ue 12 V DC W 50 -- -- --
24 50 V AC/60 Hz VA 50 -- -- --
24 ... 30 V DC W 7 ... 50 -- -- --
48 ... 60 50 V AC/60 Hz VA 15 ... 20 -- -- --
48 ... 60 V DC W 20 ... 30 -- -- --
110 ... 127 50 V AC/60 Hz VA 30 ... 40 -- -- --
110 ... 127 V DC W 30 ... 40 -- -- --
208 ... 277 50 V AC/60 Hz VA 16 ... 35 -- -- --
220 ... 250 V DC W 28 ... 35 -- -- --
380 ... 600 50 V AC/60 Hz VA 10 ... 30 -- -- --
24 50 V AC/60 Hz VA -- 300 -- --
48 ... 60 50 V AC/60 Hz VA -- 340 ... 600 -- --
110 ... 127 50 V AC/60 Hz VA -- 500 ... 650 -- --
208 ... 277 50 V AC/60 Hz VA -- 360 ... 650 -- --
380 ... 500 50 V AC/60 Hz VA -- 330 ... 600 -- --
600 50 V AC/60 Hz VA -- 300 -- --
12 V DC W -- -- < 2.5 --
24 V DC W -- -- < 2.5 --
48 V DC W -- -- < 2.5 --
60 V DC W -- -- < 2.5 --
125 ... 127 V DC W -- -- < 2.5 --
220 ... 230 V DC W -- -- < 2.5 --
7
48 50 V AC/60 Hz VA -- -- <2 --
60 50 V AC/60 Hz VA -- -- <2 --
110 50 V AC/60 Hz VA -- -- <2 --
120 ... 127 50 V AC/60 Hz VA -- -- <2 --
208 ... 230 50 V AC/60 Hz VA -- -- <2 --
380 ... 400 50 V AC/60 Hz VA -- -- < 2.5 --
440 ... 480 50 V AC/60 Hz VA -- -- < 2.5 --
12 V DC (Cat II; W -- -- -- UVR: < 2.5
PELV/SELV) SHT: 20
24 V DC (Cat II; W -- -- -- UVR: < 2.5
PELV/SELV) SHT: 20
48 V DC (Cat II; W -- -- -- UVR: < 2.5
PELV/SELV) SHT: 20
7
a mounting frame that is installed instead of the accessories it resets the breaker.
mode, the lid of the molded case circuit breaker. MO320
Motor operator electrical requirements Furthermore, the motor operator can be locked in the
CIRCUIT BREAKERS
MOLDED CASE
matically
nal before Technical specifications
OFF position by means of several padlocks.
3VA5 Degree
MO320 motor operator 3VA5 3VA5 3VA6 3VA6 Rated c
125 A 250 A 150 A/ 400 A/ (operat
250 A 600 A supply
Degree of protection NEMA 1
Rated control supply voltage 24 V ... 60 V DC (0.85 ... 1.26)
Rating
(operating range of control 110 V ... 230 V AC/ Make ti
supply voltage) 110 V ... 250 V DC (0.85 ... 1.1) Break t
Rating 250 W, max. 500 W (60 ms)
Make time, typically < 800 ms < 1000 ms < 1700 ms
Break time, typically < 800 ms < 1000 ms < 1400 ms
X D
NOTE:
Ordering Instructions
All ED Frame Sentron circuit breakers are supplied with load side lugs. If line side lugs are required, add ”L” suffix to catalog number.
Consult Siemens sales office for any addditional charge
50°C Calibration, 400HZ - see page 7-146. All ED frame circuit breakers may be reverse connected
7
080 ED41B080n ED42B080n ED43B080 All ED, HED, HHED, CED CCE125 2/0
090 ED41B090n ED42B090n ED43B090
CIRCUIT BREAKERS
MOLDED CASE
100 ED41B100 ED42B100 ED43B100
110 ED41B110 ED42B110n ED43B110
125 — ED42B125 ED43B125 Enclosures (Neutral Included)
Type Catalog Number
Type ED6e Blue Label
1 (Surface) E2N1S (15–100A)
1-Pole 2-Pole 3-Pole 3-Pole 1 (Flush) E2N1F (15–100A)
Continuous 3R E2N3R (15–100A)
Current 4–4X ED6SS4 (15–125A)
Rating 347V AC 600V AC 250V DC 600V AC 500V DC 600V DC
7–9 EA (15–60A)
@ 40° C Catalog Number Catalog Number Catalog Number Catalog Number 7–9 EB (70–100A)
15 ED61B015 — — ED63D015L 12 E2N12 (15–100A)
20 ED61B020 ED62B020 ED63B020 ED63D020L 1 (Surface) CED6N1S b
25 ED61B025 ED62B025n ED63B025 ED63D025L 1 (Flush) CED6N1F b
30 ED61B030 ED62B030 ED63B030 ED63D030L 3R CED6N3R b
12 CED6N12 b
35 ED61B035 — ED63B035 ED63D035L
40 ED61B040 — ED63B040 ED63D040L
45 ED61B045n — ED63B045 ED63D045L
50 ED61B050 — ED63B050 ED63D050L
60 ED61B060 — ED63B060 ED63D060L
70 ED61B070n — ED63B070 —
80 ED61B080 — ED63B080 —
90 ED61B090 — ED63B090 —
100 ED61B100n — ED63B100 —
110 — — ED63B110 —
125 — — ED63B125 —
Note: ED frame circuit breakers qualified to UL 489 b For
CED types and all 110–125 ampere ED frames.
Supplement SB “Naval”— See page 7-146 for c See Note: A, page 7-143. Modifications page 7-146
additional information d SWD rated. Enclosures Section 6
n Built to order. Allow 2–3 weeks for delivery. e HACR rated. Accessoriespages7-103and7-150to7-155
a CSA Certified only (Not UL) Not for use with HHED6 breakers.
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-101
Revised on 07/31/19
�
Continuous D
�
Current Rating 277V AC 125V DC 480V AC 250V DC 480V AC
�
@ 40° C Catalog Number Catalog Number Catalog Number
015 HED41B015a HED42B015 HED43B015
�
D1
�
020 HED41B020a HED42B020 HED43B020
25 HED41B025 HED42B025n HED43B025 H
030 HED41B030 HED42B030 HED43B030
35 HED41B035n HED42B035n HED43B035
040 HED41B040 HED42B040 HED43B040 � �
�
45 HED41B045n HED42B045n HED43B045 � � � �
W3
050 HED41B050n HED42B050 HED43B050 W1 W2
060 HED41B060n HED42B060n HED43B060
070 HED41B070n HED42B070n HED43B070 1-POLE 2-POLE 3-POLE
80 HED41B080n HED42B080n HED43B080
90 HED41B090n HED42B090n HED43B090 FIGURE 2 - CED (3-Pole shown)
100 HED41B100n HED42B100n HED43B100
110 — HED42B110n HED43B110
�
D
�
125 — HED42B125n HED43B125
�
D1
�
Fuseless Current Limiting
H
Type HHED6 Black Label Type CED6 Red Label
3-Pole 2-Pole 3-Pole
Continuous
Current 600V AC, 600V AC,
Rating 600V AC 250V DC 500V DC b
@ 40°C Catalog Number Catalog Number Catalog Number
�
015 HHED63B015A CED62B015 CED63B015 � �
110 — — CED63B110n
125 — CED62B125n CED63B125
Interrupting Ratings
UL 489 AIR (File #E10848) IEC 947-2
RMS Symmetrical Amperes (KA) Volts AC (50/60Hz)
Volts AC Volts DC 220/240 380/415 500
Breaker Type 120 240 277 347 480 600 125 250 500 600 lcu lcs lcu lcs lcu lcs
ED2 (1-P) 10 — — — — — 5 — — — — — — — — —
ED2 (2, 3-P) — 10 — — — — — 5 (2-P) — — — — — — — —
ED4 (1-P) 65 — 22 — — — 30 — — — — — — — — —
ED4 (2, 3-P) — 65 — — 18 — — 30 (2-P) — — — — — — — —
ED6 (1P) — — — 30 — — — 30 — — — — — — — —
ED6 (2, 3-P) — 65 — — 25 18 — — 18 (3-P) — 65 17 35 9 18 5
ED6 (3-P) — — — — — — — — — 10g — — — — — —
HED4 (1-P)
100 — 65 — — — 30 — — — — — — — — —
(15–30A)
HED4 (1-P)
100 — 25 — — — 30 — — — — — — — — —
(35–100A)
HED4 (2, 3-P) — 100 — — 42 — — 30 (2-P) — — — — — — — —
HHED6 (2, 3-P) — 100 — — 65 18 — — — — — — — — — —
CED6 (2, 3-P) — 200 — — 200 100 — 50 (2-P) 30 (3-P) — — — — — — —
n Built to order. Allow 2–3 weeks for delivery. c ED6-ETI,CED6-ETI, see page 7-130 for ordering eHACR
rated.
a SWD rated. information. f HHED63B015A is rated 18KAIC at 600/347V.
dSingle
Pole 15-30A 30KA @ 347V non-UL. g 600VDC
only applies to ED63D___ breakers
bWhen wired as shown on page 7-4, this circuit breaker is
35-100A 18KA @ 347V non-UL.
UL listed and rated for use on 500V DC ungrounded UPS
systems.
7-102 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
Revised on 12/31/19
Equipment 120
208
U01ED60
U02ED60s
U01ED62A
U02ED62As
U01ED62ABs
U02ED62ABs
U01ED62Bs
U02ED62Bs
U01ED62AAs
U02ED62AAs
Ground Sensing 240 U03ED60 U03ED62As U03ED62ABs U03ED62Bs U03ED62AAs
A field addable kit containing 30mA or 277 U16ED60s U16ED64As U16ED64ABs U16ED64Bs —
480 U06ED60s U06ED64As U06ED64ABs U06ED64Bs —
5 mA ground fault accessory module, 600 U08ED60s — — — —
current transformer with 24 inch leads, 024 U13ED60 U13ED62As U13ED62ABs U13ED62Bs U13ED62AAs
and current transformer mounting 048 U14ED60s U14ED62As U14ED62ABs U14ED62Bs U14ED62AAs
equipment. Current transformer to 125 U10ED60s U10ED62As U10ED62ABs U10ED62Bs U10ED62AAs
mount in gutter of lighting panel or 250 U12ED60s U12ED62As — — U12ED62AAs
any control panel. Accessory module
operates from separate 120V control
power source. Auxiliary Switch Combinations
Maximum 1 Alarm Switch and 1 Alarm Switch and
Both 30MA and 5MA devices are Voltage 1 Auxiliary Switch 1 Auxiliary Switch 2 Auxiliary Switches 2 Auxiliary Switches
equipment protection devices only.
AC DC Catalog Number Catalog Number Catalog Number Catalog Number
7
Do not use for personnel protection.
240 250 A01ED62 A01ED62B A02ED62 A02ED62B
480 A01ED64 A01ED64B — —
CIRCUIT BREAKERS
MOLDED CASE
Maximum
Voltage 1 Auxiliary Switch
AC DC Catalog Number
24 A01EDLV Gold Plated Contacts—for PLC use
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-103
Revised on 05/31/18
Nominal Instantaneous Values n Built to order. Allow 2–3 weeks for delivery.
a Type FXD6-A circuit breakers are UL Listed for reverse
+20% +20%
Breaker Ampere Tolerance Tolerance fed applications.
b 2-pole units are 3-pole width.
Rating Low 2 3 4 5 6 7 High c When
wired as shown on page 7-4, this circuit breaker is
170-90 600 640 690 730 770 810 850 900 UL listed and rated for use on 500V DC ungrounded UPS
systems only.
100-110 700 770 840 920 990 1060 1140 1200 d Order neutral as separate item.
125-150 800 900 1000 1100 1200 1300 1400 1500 e See Note: A, page 7-143.
175-200 900 1060 1210 1370 1520 1780 1930 2000 f HACR rated.
225-250 1100 1300 1500 1700 1900 2100 2300 2500 g Only applicable to interchangable trip unit types:
FXD6A, HFXD6A.
Note: FD frame qualified to UL489 supplement SB “NAVAL”.
See page 7-146 for additional information.
7-104 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
Molded Case Circuit Breakers
FD 250A Frame Sentron Series Selection/Dimensions
�
Interchangeable Trip
Continuous Complete Breaker
Current Rating Unassembled w/Lugs Frame Only Trip Unit Only
@ 40°C Catalog Number Catalog Number Catalog Number
2-Pole 600V AC, 250V DC (3-Pole Width)
70 HFD62B070n FD62T070n L
80 HFD62B080n FD62T080n
90 HFD62B090n FD62T090n
100 HFD62B100n FD62T100n
110 HFD62B110n FD62T110n
125 HFD62B125n HFD62F250 FD62T125n
150 HFD62B150n FD62T150n
�
175 HFD62B175n FD62T175n
200 HFD62B200n FD62T200n � W �
D
225 HFD62B225n FD62T225n
250 HFD62B250n FD62T250n Figure 1 Figure 2
3-Pole 600V AC, 500V DC
70 HFD63B070n FD63T070n Dimensions (in inches)
80 HFD63B080n FD63T080n Breaker D1
90 HFD63B090n FD63T090n Type W L D (to
100 HFD63B100 FD63T100 handle)
110 HFD63B110n FD63T110n
Figure 1
125 HFD63B125 HFD63F250 FD63T125
FXD6-A, FD6-A,
150 HFD63B150 FD63T150 HFD6, HFXD6, 4.50 09.50 4 5.25
175 HFD63B175 FD63T175 HHFD6, FD6-ETI
200 HFD63B200 FD63T200
Figure 2
225 HFD63B225 FD63T225
CFD6,
250 HFD63B250 FD63T250 4.50 14.25 4 5.25
CFD6-ETI
Type HHFD, HHFXD6 bc
3-Pole 600V AC, Extra High Interrupting Shipping Weights
70 HHFD63B070n FD63T070n Number of Number per Shipping
80 HHFD63B080n FD63T080n Poles Carton Weight (lbs.)
90 HHFD63B090n FD63T090n FD6-A, HFD6, HHFD6, FXD6-A
100 HHFD63B100 FD63T100 Assembled Circuit Breaker (less connectors)
110 HHFD63B110n FD63T110n 2 1 08.6
125 HHFD63B125 HHFD63F250 FD63T125 3 1 10
150 HHFD63B150 FD63T150 FD6-A, HFD6, HHFD6 Frame Only
175 HHFD63B175 FD63T175
7
2 1 07.5
200 HHFD63B200 FD63T200 3 1 08.7
225 HHFD63B225 FD63T225
FD6 Trip Unit Only
CIRCUIT BREAKERS
MOLDED CASE
250 HHFD63B250 FD63T250
2 1 01.1
3 1 01.3
Type CFD6-Ac CFD6 Assembled Circuit Breaker (less terminals)
Fuseless Current Limiting Red Label 3 1 16
n Built to order. Allow 2–3 weeks for delivery. breaker, change prefix identifier from HFD6 to HFXD6. d FXD6, ETI, CFD6, ETI — See page 7-130 for
a When Price equals frame and trip prices combined, e.g. price ordering information.
wired as shown on page 7-4, this circuit breaker
of HFXD63B250 equals price of HFD63F250 plus price of HACR rated.
is UL listed and rated for use on 500V DC ungrounded
FD63T250. Order lugs separately.
UPS systems. c Type HFXD6, HHFXD6, CFD6 are UL Listed for reverse
b For non-interchangeable trip 3-pole HFD6 type circuit
feed applications.
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-105
Revised on 12/31/19
7-106 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
Revised on 05/31/18
7
300 JD63B300 JD63T300
350 JD63B350 JD63T350 Lugs For 75°C Wire c
400 JD63B400 JD63T400
CIRCUIT BREAKERS
MOLDED CASE
Cables
Interrupting Ratings Catalog
Number
per
Lug
Wire
Range
RMS Symmetrical Amperes (KA) TA2J6500 1, 2 #3/0-500 kcmil Cu
UL 489 AIR (File E10848) IEC 947-2e 2 #4/0-500 kcmil Al
TA1L6750 1 500-750 kcmil Al
Volts AC Volts DC Volts AC (50/60Hz) 1 500-600 kcmil Cu
(50/60Hz) 220/240 380/415 500 TC1J6600 1 #3/0-600 kcmil Cu
Breaker
TC2J6500 1, 2 #3/0-500 kcmil Cu
Type 240 480 600 250 500 b lcu lcs lcu lcs lcu lcs
Compression Lug
JXD2-A 065 — — 30 (2-P) — — — — — — —
CCL600 1 500 kcmil Cu/Al
JXD6-A, JD6-A 065 035 025 30 (2-P) 25 (3-P) 065 033 040 20 — —
HJD6-A, HJXD6-A 100 065 035 30 (2-P) 35 (3-P) 100 050 065 33 — —
HHJD6, HHJXD6 200 100 050 — — — — — — — —
CJD6-A 200 150 100 30 (2-P) 50 (3-P) — — — — — —
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-107
Molded Case Circuit Breakers
JD 400A Frame Sentron Series Selection/Dimensions
D
200 HJD63B200 JD63T200
225 HJD63B225 JD63T225 Figure 1 Figure 2
250 HJD63B250 HJD63F400 JD63T250
300
350
HJD63B300
HJD63B350
JD63T300
JD63T350
Dimensions (in inches)
400 HJD63B400 JD63T400 To
Breaker Handle
Type W L D D1
Figure 1
Type HHJD6, HHJXD6 bdf Black Label JXD2-A, JXD6-A, JD6-A
HJD6-A, HJXD6-A, HHJD6, 7.5 11 4 5.44
2-Pole 600V AC (3-Pole Width) HJD6, HJXD6, HHJXD6,
200 HHJD62B200n JD62T200n JXD6-ETI,c SJD6, SHJD6
225 HHJD62B225n JD62T225n Figure 2
7.5 17.86 4 5.44
250 HHJD62B250n HHJD62F400n JD62T250n CJD6, CJD6-ETI,c SCJD6
300 HHJD62B300n JD62T300n
350 HHJD62B350n JD62T350n Enclosures (Except SCJD6)
400 HHJD62B400n JD62T400
3-Pole 600VAC Type Catalog Number
200 HHJD63B200 JD63T200 1 J6N1
225 HHJD63B225 JD63T225 3R J6N3R
250 HHJD63B250 HHJD63F400 JD63T250 12 J6N12
300 HHJD63B300 JD63T300 4X LD6SS4
7, 9 (200-250A) EC4
350 HHJD63B350 JD63T350
7, 9 (300-400A) EE
400 HHJD63B400 JD63T400
W60992
7
Neutral
7-108 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
Revised on 10/31/18
Current Limiting
Type SJD6-B Type SHJD6-B Type SCJD6-B
Blue Label Black Label Red Label
Max 3-Pole, 600V AC 3-Pole, 600V AC 3-Pole, 600V AC
Current Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number
Rating (Advanced trip unit)c (Basic trip unit) (Advanced trip unit)c (Basic trip unit) (Advanced trip unit)c (Basic trip unit)
200 SJD6A200LI SJD6B200LI SHJD6A200LI SHJD6B200LI SCJD6A200LI SCJD6B200LI
300 SJD6A300LI SJD6B300LI SHJD6A300LI SHJD6B300LI SCJD6A300LI SCJD6B300LI
400 SJD6A400LI SJD6B400LI SHJD6A400LI SHJD6B400LI SCJD6A400LI SCJD6B400LI
200 SJD6A200LIG SJD6B200LIG SHJD6A200LIG SHJD6B200LIG SCJD6A200LIG SCJD6B200LIG
300 SJD6A300LIG SJD6B300LIG SHJD6A300LIG SHJD6B300LIG SCJD6A300LIG SCJD6B300LIG
400 SJD6A400LIG SJD6B400LIG SHJD6A400LIG SHJD6B400LIG SCJD6A400LIG SCJD6B400LIG
200 SJD6A200LSI SJD6B200LSI SHJD6A200LSI SHJD6B200LSI SCJD6A200LSI SCJD6B200LSI
300 SJD6A300LSI SJD6B300LSI SHJD6A300LSI SHJD6B300LSI SCJD6A300LSI SCJD6B300LSI
400 SJD6A400LSI SJD6B400LSI SHJD6A400LSI SHJD6B400LSI SCJD6A400LSI SCJD6B400LSI
200 SJD6A200LSIG SJD6B200LSIG SHJD6A200LSIG SHJD6B200LSIG SCJD6A200LSIG SCJD6B200LSIG
300 SJD6A300LSIG SJD6B300LSIG SHJD6A300LSIG SHJD6B300LSIG SCJD6A300LSIG SCJD6B300LSIG
400 SJD6A400LSIG SJD6B400LSIG SHJD6A400LSIG SHJD6B400LSIG SCJD6A400LSIG SCJD6B400LSIG
7
300 SJD6A300LSIGH SJD6B300LSIGH SHJD6A300LSIGH SHJD6B300LSIGH Type Carton Weight (lbs)
400 SJD6A400LSIGH SJD6B400LSIGH SHJD6A400LSIGH SHJD6B400LSIGH SJD6-B 1 20
CIRCUIT BREAKERS
MOLDED CASE
SHJD6-B 1 20
Trip Unit Adjustable Functions SCJD6-B 1 33
Short Short
Suffix Cont Long Instan- Short Time Time Ground Ground
Letter Trip Current Time taneous Time Fixed
2
lt Fault Fault Lugs for 75° C Wire a
Code Type Setting Delay Pick Up Pick Up Delay Delay Pick Up Delay
No. of
LI LI u u u
cables
LIG LIG u u u u u Catalog per con- Wire
LSI LSI u u u u u u Number nector Range
LSIG LSIG u u u u u u u u 2 #3/0-500 kcmil Cu
TA2J6500
2 #4/0-500 kcmil Al
Note: “G” suffix in catalog number denotes circuit All breakers built to order. Allow 2–3 weeks for delivery.
breaker for 3-phase, 3-wire systems. a Foradditional information, see Note: A, page 7-143.
For 3-phase, 4-wire, order correct 4th wire (neutral) Refer to the NEC for proper application of 100%
transformer as separate and additional item.
b
Enclosures Section 6
rated devices.
c Advanced trip unit equipped with DAS /
Accessories pages 7-110 and 7-150 to 7-155
Maintenance Mode. Requires customer-supplied 24V
external power supply, maintenance switch and light.
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-109
Revised on 12/31/19
Note: Accessory modules can only be added to right s Built to order. Allow 6–8 weeks for delivery.
side pole of solid state SJD and SLD frame circuit
breakers. No accessories can be added if
mechanical interlock is used. All accessories on this
page are useable on superseded JD2, JJ6, JL6, HJ6,
SJL, LJ6, LL6, HL6 and SLL circuit breakers.
7-110 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
Revised on 05/31/18
7
Type 240 480 600 250 500 c 220/240 380/415 500 LXD6, LD6, HLD6, HHLD6
(lcu) (lcs) (lcu) (lcs) (lcu) (lcs) Assembled Breaker (less terminals)
LD6-A, LXD6-A 065 035 025 30 (2-P) 25 (3-P) 065 033 040 20 — — 2 1 17.5
CIRCUIT BREAKERS
MOLDED CASE
3 1 19.5
HLD6-A, HLXD6-A 100 065 035 30 (2-P) 35 (3-P) 100 050 065 33 — —
LD6, HLD6, HHLD6 Frame Only
HHLD6, HHLXD6 200 100 050 — — — — — — — —
2 1 14
CLD6-A 200 150 100 — 50 (3-P) — — — — — — 3 1 15.5
LD6, HHLD6 Trip Unit Only
Instantaneous Adjustment Trip Range 2
3
1
1
03.5
04
Nominal Instantaneous Values CLD6 Complete Assembled Breaker
+20% +20% (less terminals)
Breaker Ampere Tolerance Tolerance 3 1 31.5
Rating Low 2 3 4 5 6 7 High
250-300 1250 1430 1610 1790 1960 2140 2320 2500
350-450 2000 2290 2570 2860 3140 3430 3710 4000 Lugs For 75°C Wire c
500-600 3000 3430 3800 4290 4710 5140 5570 6000 Cables
Catalog per Wire
Number Lug Range
TA2J6500 1, 2 #3/0 500 kcmil Cu
2 #4/0 500 kcmil Al
n Built to order. Allow 2–3 weeks for delivery. TC2J6500 2 #3/0-500 kcmil Cu
a Type LXD6A circuit breakers are UL Listed for reverse TA1L6750 1 500-750 kcmil Al
fed applications. 1 500-600 kcmil Cu
b When
wired as shown on page 7-4, this circuit breaker is
UL listed and rated for use on 500V DC ungrounded
TC1J6600 1 #3/0-600 kcmil Cu
UPS systems only. Compression Lug
c See Note: A, page 7-143.
Modifications page 7-146 CCL600 1 500 kcmil Cu/Al
d HACR rated.
e Only applicable to interchangable trip unit types: Enclosures Section 6
LXD6, HLXD6. Accessories pages 7-114 and 7-150 to 7-155
Note: LD frame qualified to UL489 supplement SB “NAVAL”.
See page 7-146 for additional information.
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-111
Molded Case Circuit Breakers
LD 600A Frame Sentron Series Selection/Dimensions
Neutral W60993
Type CLD6-Acf
Fuseless Current Limiting Red Label
Non-Interchangeable Trip (Assembled Circuit Breaker
Without Lugs)
Continuous 2-Pole 3-Pole
Current Rating 600V AC/250V DC 600V AC/500V DC
@ 40°C Catalog Number Catalog Number
450 For 2-pole application CLD63B450n
500 use outside poles of CLD63B500
600 3-pole circuit breaker CLD63B600
n Built to order. Allow 2–3 weeks for delivery. b For complete assembled 3-pole HLD6 or HHLD6 type cType HLXD6, HHLXD6, & CLD6 Circuit Breakers are UL
a When circuit breaker change the prefix identifier HLD6 or Listed for reverse feed applications.
wired as shown on page 7-4, this circuit breaker is
HHLD6 to HLXD6 or HHLXD6. Price is sum of frame and d LXD6-ETI, CLD6-ETI see page 7-130 for ordering information.
UL listed and rated for use on 500V DC ungrounded
trip units prices, e.g. price of HLXD63B400 is the price of e CE Applies to non-interchangeable type HLXD only.
UPS systems only.
HLD63F600 plus the price of LD63T600. Order the f HACR rated.
terminal connectors separately.
7-112 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
Revised on 10/31/18
Current Limiting
Type SLD6-B Type SHLD6-B Type SCLD6-B
Blue Label Black Label Red Label
Max 3-Pole, 600V AC 3-Pole, 600V AC 3-Pole, 600V AC
Current Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number
Rating (Advanced trip unit)a (Basic trip unit) (Advanced trip unit)a (Basic trip unit) (Advanced trip unit)a (Basic trip unit)
300 SLD6A300LI SLD6B300LI SHLD6A300LI SHLD6B300LI SCLD6A300LI SCLD6B300LI
400 SLD6A400LI SLD6B400LI SHLD6A400LI SHLD6B400LI SCLD6A400LI SCLD6B400LI
500 SLD6A500LI SLD6B500LI SHLD6A500LI SHLD6B500LI SCLD6A500LI SCLD6B500LI
600 SLD6A600LI SLD6B600LI SHLD6A600LI SHLD6B600LI SCLD6A600LI SCLD6B600LI
300 SLD6A300LIG SLD6B300LIG SHLD6A300LIG SHLD6B300LIG SCLD6A300LIG SCLD6B300LIG
400 SLD6A400LIG SLD6B400LIG SHLD6A400LIG SHLD6B400LIG SCLD6A400LIG SCLD6B400LIG
500 SLD6A500LIG SLD6B500LIG SHLD6A500LIG SHLD6B500LIG SCLD6A500LIG SCLD6B500LIG
600 SLD6A600LIG SLD6B600LIG SHLD6A600LIG SHLD6B600LIG SCLD6A600LIG SCLD6B600LIG
300 SLD6A300LSI SLD6B300LSI SHLD6A300LSI SHLD6B300LSI SCLD6A300LSI SCLD6B300LSI
400 SLD6A400LSI SLD6B400LSI SHLD6A400LSI SHLD6B400LSI SCLD6A400LSI SCLD6B400LSI
500 SLD6A500LSI SLD6B500LSI SHLD6A500LSI SHLD6B500LSI SCLD6A500LSI SCLD6B500LSI
600 SLD6A600LSI SLD6B600LSI SHLD6A600LSI SHLD6B600LSI SCLD6A600LSI SCLD6B600LSI
300 SLD6A300LSIG SLD6B300LSIG SHLD6A300LSIG SHLD6B300LSIG SCLD6A300LSIG SCLD6B300LSIG
400 SLD6A400LSIG SLD6B400LSIG SHLD6A400LSIG SHLD6B400LSIG SCLD6A400LSIG SCLD6B400LSIG
500 SLD6A500LSIG SLD6B500LSIG SHLD6A500LSIG SHLD6B500LSIG SCLD6A500LSIG SCLD6B500LSIG
600 SLD6A600LSIG SLD6B600LSIG SHLD6A600LSIG SHLD6B600LSIG SCLD6A600LSIG SCLD6B600LSIG
7
Interrupting Ratings Neutral Transformers
Shipping Weights
CIRCUIT BREAKERS
MOLDED CASE
RMS Symmetrical kA
UL 489 (File E10848) Ampere Rating Catalog Number
Breaker
300 N03SJD Breaker Number per Shipping
Type 240V AC 480V AC 600V AC
Type Carton Weight (lbs)
400 N04SJD
SLD6-B 65 35 25
500 N05SLD SLD6-B 1 20
SHLD6-B 100 65 35
600 N06SLD SHLD6-B 1 20
SCLD6-B 200 150 100
SCLD6-B 1 33
Note: “G” suffix in catalog number denotes circuit For ordering information and terminal connectors see a Advanced trip unit equipped with DAS / Maintenance
breaker for 3-phase, 3-wire circuits. page 7-111; for enclosures, see page 7-112. Mode. Requires customer-supplied 24V external power
For 3-phase, 4-wire, order correct 4th wire (neutral) 100% Rated – Not available in SLD6 Frame. supply, maintenance switch and light.
transformer as separate and additional item.
All breakers built to order. Allow 2-3 weeks for delivery.
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-113
Revised on 12/31/19
Note: Accessory modules can only be added to right s Built to order. Allow 6–8 weeks for delivery.
side pole of solid state SJD and SLD frame circuit
breakers. No accessories can be added if
mechanical interlock is used. All accessories on this
page are useable on superseded JD2, JJ6, JL6, HJ6,
SJL, LJ6, LL6, HL6 and SLL circuit breakers.
7-114 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
Molded Case Circuit Breakers
LMD 800A Frame Sentron Series Selection
7
LMD6, HLMD6 Trip Unit Only
2 1 4.5
CIRCUIT BREAKERS
MOLDED CASE
3 1 6.5
n Built to order. Allow 2–3 weeks for delivery. c See Note: A, page 7-143.
a LMXD6 circuit breakers are UL Listed for reverse
d HACR rated. Modifications page 7-146
connected applications. Enclosures Section 6
bWhen wired as shown on page 7-4, this circuit breaker is Accessories pages 7-117 and 7-150 to 7-155
UL listed and rated for use on 500VDC ungrounded UPS
systems only.
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-115
Molded Case Circuit Breakers
LMD 800A Frame Sentron Series Selection/Dimensions
Interrupting Ratings
UL 489A IR
RMS Symmetrical Amperes (KA)
Dimensions (in inches)
Volts AC Volts DC Breaker
Breaker Type W L D D1
Type 240 480 600 250 500
LMD6,
7
LMXD6-ETI b
Enclosures
Type Catalog Number
1 LMD1
3R LMD3R
12 LMD12n
Neutral W63623
n Built to order. Allow 2–3 weeks for delivery. c When wired as shown on page 7-4, this circuit breaker
a HLMXD6 is UL listed and rated for use on 500VDC ungrounded
circuit breakers are UL Listed for reverse
UPS systems only.
connection applications. d HACR rated.
b LMXD6-ETI, see page 7-130 for catalog information.
7-116 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
Revised on 12/31/19
7
Alarm Switch Combinations
CIRCUIT BREAKERS
MOLDED CASE
Maximum 1 Alarm Switch and 1 Alarm Switch and
Voltage 1 Alarm Switch 1 Auxiliary Switch 2 Auxiliary Switches
AC DC Catalog Number Catalog Number CatalogNumber
480 250 B01JLD64 A01JLD64B A02JLD64B
Note: Accessory modules can only be added to right s Built to order. Allow 6–8 weeks for delivery.
side pole of solid state SJD and SLD frame circuit
breakers. No accessories can be added if
mechanical interlock is used. All accessories on this
page are useable on superseded JD2, JJ6, JL6, HJ6,
SJL, LJ6, LL6, HL6 and SLL circuit breakers.
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-117
Revised on 12/31/19
Enclosures
Type Catalog Number
1 MND61
3R MND63
12 MND612n
Neutral W63623
n Built to order. Allow 2–3 weeks for delivery. d See Note: A, page 7-143.
e 80% rated breakers with the CE mark will also be
MXD6 circuit breakers are UL Listed for reverse
a
connection applications. marked in the 100% rated version.
b 2-pole
f HACR rated.
Modifications page 7-146
units available in 3-pole width only.
cWhen wired as shown on page 7-4, this circuit breaker Note: MD frame qualified to UL489 supplement B “NAVAL”. Enclosures Section 6
is UL listed and rated for use on 500V DC ungrounded See page 7-146 for additional information. Accessories pages 7-121 and 7-150 to 7-155
UPS systems.
7-118 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
Revised on 05/31/18
Type CMD6 ae
Fuseless Current Limiting Red Label
Non-Interchangeable Trip (Assembled Circuit Breaker
Without Lugs) Lug
Continuous 2-Pole 3-Pole
600V AC/250V DC 600V AC/500V DC When wire lug shield NDTS is used.
Current Rating
Note: NDTS lug shields are required when oversized lugs
@ 40°C Catalog Number Catalog Number
7
are used. The kits include the NDTS shield.
600 For 2-pole application CMD63B600n
700 use outside poles of CMD63B700n
CIRCUIT BREAKERS
MOLDED CASE
800
3-pole circuit breaker
CMD63B800 Dimensions (in inches)
(To
Breaker Handle)
Interrupting Ratings Type W L D D1
MD6, MXD6, HMD6,
UL 489 AIR—File E10848 IEC 947-2 AIRf HMXD6, CMD6,
RMS Symmetrical Amperes (KA) Volts AC (50/60HZ) MXD6-ETI, CMD6-ETI, 9 16 6 8.25
Volts AC Volts DC 220/240 380/415 500 SMD6-B, SHMD6-B,
Breaker and SCMD6-B
Type 240 480 600 250 500 d (lcu) (lcs) (lcu) (lcs) (lcu) (lcs
with lug shields 9 24 6 8.25
MD6, MXD6 065 050 25 30 (2-P) 25 (3-P) 065 033 040 20 — —
HMD6, HMXD6 100 065 50 30 (2-P) 50 (3-P) 100 050 065 33 — —
CMD6 200 100 65 — 50 (3-P) — — — — — —
n Built to order. Allow 2–3 weeks for delivery. d When wired as shown on page 7-4, this circuit breaker is
a HMXD6 UL listed and rated for use on 500V DC ungrounded UPS
and CMD circuit breakers are UL listed for
systems only.
reverse connection applications. e HACR rated.
b 2-pole units available in 3-pole width only.
f Only applicable to interchangable trip unit types:
c MXD6-ETI, CMD6-ETI see page 7-130 for catalog information.
MXD6, HMXD6
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-119
Revised on 12/31/19
Current Limiting
Type SMD6 Type SHMD6-B Type SCMD6-B
Blue Label Black Label Red Label
Max 3-Pole, 600V AC 3-Pole, 600V AC 3-Pole, 600V AC
Current Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number
Rating (Advanced trip unit)c (Basic trip unit) (Advanced trip unit)c (Basic trip unit) (Advanced trip unit)c (Basic trip unit)
600 SMD6A600LI SMD6B600LI SHMD6A600LI SHMD6B600LI SCMD6A600LI SCMD6B600LI
700 SMD6A700LI SMD6B700LI SHMD6A700LI SHMD6B700LI SCMD6A700LI SCMD6B700LI
800 SMD6A800LI SMD6B800LI SHMD6A800LI SHMD6B800LI SCMD6A800LI SCMD6B800LI
600 SMD6A600LIG SMD6B600LIG SHMD6A600LIG SHMD6B600LIG SCMD6A600LIG SCMD6B600LIG
700 SMD6A700LIG SMD6B700LIG SHMD6A700LIG SHMD6B700LIG SCMD6A700LIG SCMD6B700LIG
800 SMD6A800LIG SMD6B800LIG SHMD6A800LIG SHMD6B800LIG SCMD6A800LIG SCMD6B800LIG
600 SMD6A600LSI SMD6B600LSI SHMD6A600LSI SHMD6B600LSI SCMD6A600LSI SCMD6B600LSI
700 SMD6A700LSI SMD6B700LSI SHMD6A700LSI SHMD6B700LSI SCMD6A700LSI SCMD6B700LSI
800 SMD6A800LSI SMD6B800LSI SHMD6A800LSI SHMD6B800LSI SCMD6A800LSI SCMD6B800LSI
600 SMD6A600LSIG SMD6B600LSIG SHMD6A600LSIG SHMD6B600LSIG SCMD6A600LSIG SCMD6B600LSIG
700 SMD6A700LSIG SMD6B700LSIG SHMD6A700LSIG SHMD6B700LSIG SCMD6A700LSIG SCMD6B700LSIG
800 SMD6A800LSIG SMD6B800LSIG SHMD6A800LSIG SHMD6B800LSIG SCMD6A800LSIG SCMD6B800LSIG
Ordering Information
Lugs for 75° C Wire b
MOLDED CASE
CIRCUIT BREAKERS
Pricing information for all Digital Sentron Series MD frames is for Catalog Cables Wire Each kit contains
complete breaker only. Price requires lugs or lug kits as separate items. Number per Lug Range the following:
Lugs are suitable for 75°C wire or as noted. Connector wire ranges TA2K500 2 #1-500 kcmil Cu/Al 3TA4P8500 -
and cavities are established in conjunction with Table 6.1.4.2.1 of UL TA3K500 3 #1-500 kcmil Cu/Al 3 connectors plus
489 standards. Choose actual connector for circuit breakers based on 1 NDTS end barrier
customer requirements. TC2K500 2 #1-500 kcmil Cu
Kits (3 lugs/kit) 3TA3N8750 -
Recommended Terminal Connectors
3 connectors plus
Breaker Frame Ampere Rating Connector or Connector Kit 3TA4N8500 4 250-500 kcmil Cu/Al
1 NDTS end barrier
MD 500-600 TA2K500 3TA4P8500 4 250-500 kcmil Cu/Al
3TA2N8750 -
MD 700-800 TA3K500 3TA2N8750 2 500-750 kcmil Cu/Al 3 connectors plus
Types SMD6-B, SHMD6-B and SCMD6-B are acceptable for reverse 3TA3N8750 3 500-750 kcmil Cu/Al 1 NDTS end barrier
connection applications
7-120 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
Revised on 12/31/19
7
480 250 A01MN64 A02MN64
— 24 A01MNDLVs A02MNDLVs
CIRCUIT BREAKERS
MOLDED CASE
Alarm Switch Combinations
Maximum 1 Alarm Switch and 1 Alarm Switch and
Voltage 1 Alarm Switch 1 Auxiliary Switch 2 Auxiliary Switches
AC DC Catalog Number Catalog Number Catalog Number
480 250 B00MN64 A01MN64B A02MN64B
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-121
Revised on 12/31/19
Enclosures
Type Catalog Number
1 MND61
3R MND63
12 MND612 n
Neutral W63623
n Built to order. Allow 2–3 weeks for delivery. e Use 2 – 3TA4N8500 for 3-pole or 2 – 2TA4N8500 for
a NXD6 2-pole. Rated for 75°C cable.
circuit breakers are UL listed for reverse f See Note: A, page 7-143.
connection applications. g 80% rated breakers with the CE mark will also be
b 2-pole units available in 3-pole width only.
marked in the 100% rated version. Modifications page 7-146
c When wired as shown on page 7-4, this circuit breaker is
h HACR rated. Enclosures Section 6
UL listed and rated for use on 500VDC ungrounded UPS
systems only.
i Only applicable to interchangable trip unit types: Accessories pages 7-125 and 7-150 to 7-155
d Use 2 – 3TA4P8500 kits for 3-pole, or 2 – 2TA4P8500 NXD6, HNXD6.
Note: ND frame qualified to UL489 supplement B “NAVAL”.
kits for 2-pole. Rated for 90° C cable. Use for 100% rated
See page 7-146 for additional information.
breakers.
7-122 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
Revised on 02/06/18
Type CND6 ad
Fuseless Current Limiting Red Label
Non-Interchangeable Trip (Assembled Circuit Breaker)
Lugs
Continuous
Current Rating 2-Pole 3-Pole
When lugs shield NDTS is used.
@ 40°C Catalog Number Catalog Number
Note: NDTS lug shields are required when oversized lugs
7
0900 For 2-pole application, CND63B900n TA4P8500 or TA4N8500 are used. The kits include
1000 use outside poles of CND63B100 the NDTS shield.
3-pole circuit breaker
1200 CND63B120
CIRCUIT BREAKERS
MOLDED CASE
Dimensions (in inches)
Shipping Weights Breaker
Type W L D D1
Number of Number per Shipping ND6, NXD6, HND6,
Poles Carton Weight (lbs.)
HNXD6, CND6,
ND6, HND6, NXD6, HNXD6, CND6 9 16 6 8.25
SND6-B, SHND6-B,
Assembled Breaker (less terminals)
and SCND6-B
2 1 53
3 1 61.5 with NDTS
lug shield 9 24 6 8.25
ND6, HND6 Frame Only
2 1 42.25
3 1 46
ND6, HND6 Trip Unit Only
2 1 04.5
3 1 06.5
n Built to order. Allow 2–3 weeks for delivery. c When wired as shown on page 7-4, this circuit breaker is
a HNXD6 UL listed and rated for use on 500V DC ungrounded
and CND6 circuit breakers are UL Listed for
UPS systems only.
reverse connection applications. d HACR rated.
b 2-pole units available in 3-pole width only.
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-123
Revised on 02/28/19
Current Limiting
Type SND6-B Type SHND6-B Type SCND6-B
Blue Label Black Label Red Label
Max 3-Pole, 600V AC 3-Pole, 600V AC 3-Pole, 600V AC
Current Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number
Rating (Advanced trip unit)c (Basic trip unit) (Advanced trip unit)c (Basic trip unit) (Advanced trip unit)c (Basic trip unit)
800 SND6A800LI SND6B800LI SHND6A800LI SHND6B800LI SCND6A800LI SCND6B800LI
1000 SND6A100LI SND6B100LI SHND6A100LI SHND6B100LI SCND6A100LI SCND6B100LI
1200 SND6A120LI SND6B120LI SHND6A120LI SHND6B120LI SCND6A120LI SCND6B120LI
800 SND6A800LIG SND6B800LIG SHND6A800LIG SHND6B800LIG SCND6A800LIG SCND6B800LIG
1000 SND6A100LIG SND6B100LIG SHND6A100LIG SHND6B100LIG SCND6A100LIG SCND6B100LIG
1200 SND6A120LIG SND6B120LIG SHND6A120LIG SHND6B120LIG SCND6A120LIG SCND6B120LIG
800 SND6A800LSI SND6B800LSI SHND6A800LSI SHND6B800LSI SCND6A800LSI SCND6B800LSI
1000 SND6A100LSI SND6B100LSI SHND6A100LSI SHND6B100LSI SCND6A100LSI SCND6B100LSI
1200 SND6A120LSI SND6B120LSI SHND6A120LSI SHND6B120LSI SCND6A120LSI SCND6B120LSI
800 SND6A800LSIG SND6B800LSIG SHND6A800LSIG SHND6B800LSIG SCND6A800LSIG SCND6B800LSIG
1000 SND6A100LSIG SND6B100LSIG SHND6A100LSIG SHND6B100LSIG SCND6A100LSIG SCND6B100LSIG
1200 SND6A120LSIG SND6B120LSIG SHND6A120LSIG SHND6B120LSIG SCND6A120LSIG SCND6B120LSIG
7-124 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
Revised on 12/31/19
7
480 250 A01MN64 A02MN64
— 24 A01MNDLVs A02MNDLVs
CIRCUIT BREAKERS
MOLDED CASE
Alarm Switch Combinations
Maximum 1 Alarm Switch and 1 Alarm Switch and
Voltage 1 Alarm Switch 1 Auxiliary Switch 2 Auxiliary Switches
AC DC Catalog Number Catalog Number Catalog Number
480 250 B00MN64 A01MN64B A02MN64B
Interrupting Ratings
UL 489 A IR
RMS Symmetrical KA
Volts AC Volts DC a
Breaker
Type 240 480 600 250 500
PD6, PXD6 65 50 25 30 (2P) 25 (3P)
HPD6, HPXD6 100 65 50 30 (2P) 50 (3P)
CPD6 200 100 65 30 (2P) 50 (3P)
n Built to order. Allow 2–3 weeks for delivery. UL listed and rated for use on 500V DC ungrounded UPS e HACR rated.
systems only. Note: PD frame qualified to UL489 supplement B “NAVAL”.
s Built to order. Allow 6–8 weeks for delivery. c PXD6, HPXD6 and CPD6 type circuit breakers are UL See page 7-146 for additional information.
a Use two outside poles of a 3-pole circuit breaker for 250V Listed for reverse feed applications.
b When wired as shown on page 7-4, this circuit breaker is d For additional information See Note: A, page 7-143.
7-126 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
Revised on 05/31/18
Ordering Information
Type SPD6-B Type SHPD6-B
Pricing information for all Digital
Blue Label Black Label Sentron Series PD frame unit is
for breaker only. Price required
Max 3-Pole, 600V AC 3-Pole, 600V AC mounting block assembly and
Current Catalog Number Catalog Number Catalog Number Catalog Number necessary terminal connectors
Rating (Advanced trip unit)c (Basic trip unit) (Advanced trip unit)c (Basic trip unit)
as separate items.
1400 SPD6A140LI SPD6B140LI SHPD6A140LI SHPD6B140LI
1600 SPD6A160LI SPD6B160LI SHPD6A160LI SHPD6B160LI SPD6-B and SHPD6-B are
1400 SPD6A140LIG SPD6B140LIG SHPD6A140LIG SHPD6B140LIG acceptable for reverse connection
1600 SPD6A160LIG SPD6B160LIG SHPD6A160LIG SHPD6B160LIG applications.
1400 SPD6A140LSI SPD6B140LSI SHPD6A140LSI SHPD6B140LSI
1600 SPD6A160LSI SPD6B160LSI SHPD6A160LSI SHPD6B160LSI
1400 SPD6A140LSIG SPD6B140LSIG SHPD6A140LSIG SHPD6B140LSIG Lugsa
1600 SPD6A160LSIG SPD6B160LSIG SHPD6A160LSIG SHPD6B160LSIG No. of
cables
Catalog per con- Wire
Trip Unit Adjustable Functions Number nector Range
TA5P600 1-5 pcs. 300-600 kcmil Cu/Al
Short Short
Suffix Cont Long Instan- Short Time Time Ground Ground TC5R600 1-5 pcs. 300-600 kcmil Cu Only
2
Letter Trip Current Time taneous Time Fixed lt Fault Fault TA6R600 1-6 pcs. 300-600 kcmil Cu/Al
Code Type Setting Delay Pick Up Pick Up Delay Delay Pick Up Delay
LI LI u u u
LIG LIG u u u u u Neutral Transformers
LSI LSI u u u u u u
LSIG LSIG u u u u u u u u Ampere Rating Catalog Number
1400 N14SPD
1600 N16SPD
Interrupting Mounting Block
Ratings (Required)b
Breaker RMS Symmetrical kA UL 489
Catalog Number
Enclosure
Type 240V AC 480V AC 600V AC
MB9301 Type Catalog Number
SPD6-B 65 50 25
SHPD6-B 100 65 50 MBR9302 1 PRD6N1
7
CIRCUIT BREAKERS
MOLDED CASE
All PD, RD Frames:
MB9301 (shown)
MBR9302 MBR9302 MB9301 MBR9302 MB9301
Note: “G” suffix in catalog number denotes circuit All breakers built to order. Allow 2–3 weeks for delivery. c Advanced trip unit equipped with DAS / Maintenance
breaker for 3-phase, 3-wire circuits. a For additional information, see Note: A, page 7-143. Mode. Requires customer-supplied 24V external power
For 3-phase, 4-wire, order correct 4th wire (neutral) b The PD frame circuit breaker requires the use of a supply, maintenance switch and light.
transformer as separate and additional item. connect-all mounting assembly to allow for placing
into service.
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-127
Revised on 12/31/19
7-128 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
Molded Case Circuit Breakers
RD 2000A Frame Sentron Series Selection
Type RXD6 d
3-Pole 600V AC, 250-500V DC a Blue Label
Non-Interchangeable Trip (Assembled Circuit Breaker Only Without Lugs)
Continuous Complete Breaker Assembled
Current (Frame/Trip Unit Only) Mounting Assembly Lugs (6 required)
Rating @ 40°C Catalog Number Catalog Number Catalog Number
1600 RXD63B160 MB9301
1800 RXD63B180 -or- TC5R600
2000 RXD63B200 MBR9302
Type RD6 d
3-Pole 600V AC, 250-500V DC a Blue Label
Interchangeable Trip (Unassembled Circuit Breaker with Lugs)
Continuous Complete Breaker Mounting
Current Unassembled Frame Only Trip Unit Only Assembly Lugs (6 required) RXD63B200
Rating @ Catalog Catalog Catalog Catalog Catalog
40°C Number Number Number Number Number
1600 RD63B160n RD63T160n MB9301 Mounting Block
1800 RD63B180 RD63F200 RD63T180 -or- TC5R600 Catalog
2000 RD63B200 RD63T200 MBR9302 Number Connection Points
MB9301 Front
Type HRXD6 d Black Label MBR9302 Rear
7
1800 HRD63B180 HRD63F200 RD63T180 -or- TC5R600 MB9301 1 53.0
2000 HRD63B200 RD63T200 MBR9302 MBR9302 1 50.9
CIRCUIT BREAKERS
MOLDED CASE
Interrupting Ratings Lugs (6 required per breaker)e
UL 489 A IR No of
RMS Symmetrical KA Catalog Cables per
Number Connector Wire Range
Breaker Volts AC Volts DC a TC5R600 1-5 300-600 kcmil Cu only
Type 240 480 600 250 500 TA6R600 1-6 300-600 kcmil Cu/Al
RD6, RXD6 65 50 25 30 (2P) 25 (3P)
HRD6, HRXD6 100 65 50 30 (2P) 50 (3P)
n Built to order. Allow 2–3 weeks for delivery. b When wired as shown on page 7-4, this circuit breaker is d HACR rated.
UL listed and rated for use on 500V DC ungrounded e For additional information See Note: A, page 7-143.
s Built to order. Allow 6–8 weeks for delivery. UPS systems only. Note: RD frame qualified to UL489 supplement B “NAVAL”.
a Use
two outside poles of a 3-pole circuit breaker for c RXD6 and HRXD6 type circuit breakers are UL Listed for See page 7-146 for additional information.
250V DC applications. reverse feed applications. For required mounting base (MB9301 or MBR9302) see
page 7-127.
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-129
Revised on 02/28/19
JXD6(A)a 400
400
1250
2000
02500
04000
—
JXD62H400n
JXD63L400
JXD63H400
600V AC
250V DC SHIPPING: 16 lbs. each 20 lbs. each
7
CJD6 a 400
400
1250
2000
02500
04000
—
—
CJD63L400n
CJD63H400n
600V AC
MOLDED CASE
CIRCUIT BREAKERS
LXD6(A) a 600
600
2000
3000
04000
06000
LXD62L600n
—
LXD63L600n
LXD63H600
600V AC
250V DC SHIPPING: 16 lbs. each 20 lbs. each
CLD6 a 600
600
2000
3000
04000
06000
—
—
CLD63L600n
CLD63H600n
600V AC
250V DC SHIPPING: 31.5 lbs. each
LMXD6 d 800
800
2800
3200
06000
08000
—
—
LMXD63L800n
LMXD63A800
600V AC
250V DC SHIPPING: 35 lbs. each
800 3000 06000 — MXD63L800n
MXD6 d 800 4000 08000 — MXD63A800n
600V AC 800 5000 10000 — MXD63H800
250V DC
SHIPPING: 33 lbs. each
800 3000 06000 — CMD63L800n
CMD6 d 800 4000 08000 — CMD63A800n
600V AC 800 5000 10000 — CMD63H800n
250V DC
SHIPPING: 80 lbs. each
Important Information
Lug Information pages 7-143 to 7-145
ETI interrupting ratings are determined through combination tests with properly sized overload relays and contactors. Enclosures Section 6
e Connectors included when ordering by circuit breaker catalog number for HEM, ED and CED6 ETIs. Order ETI Accessories pages 7-150 to 7-155
circuit breaker and lugs (2 per pole) separately for the FXD6, CFD6, MXD6, CMD6, JXD6, CJD6, LXD6 and CLD6 ETI’s. Application data pages 7-131 to 7-132
7-130 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
Revised on 02/28/19
Motor ETI Trip Setting ETI Trip Setting ETI Trip Setting
Full Load Catalog Adjust- Motor Full Catalog Adjust- Motor Full Catalog Adjust-
Amperes Number ment Amperes Load Amperes Number ment Amperes Load Amperes Number ment Amperes
.20 – .33 Low 2.6 8.84 – 14.22 Low 115 95.00 – 110.00 Low 1250
.34 – .45 2 4.5 14.23 – 19.60 2 185 110.00 – 124.00 2 1430
.46 – .56 ED63A001 3 6 19.61 – 24.99 ED63A040 3 255 138.00 – 151.00 JXD63L400 4 1790
.57 – .68 CED63A001 4 7.5 25.00 – 28.83 CED63A040 4 325 165.00 – 178.00 CJD63L400 6 2140
.69 – .81 High 9 28.84 – 34.00 High 375 178.00 – 192.00 7 2320
192.00 – 227.00 High 2500
.53 – .83 Low 7 13.84 – 23.06 Low 180
.84 – 1.14 2 11 23.07 – 31.52 2 300 154.00 – 176.00 Low 2000
1.15 – 1.45 ED63A002 3 15 31.53 – 39.99 ED63A050 3 410 176.00 – 198.00 2 2290
1.46 – 1.68 CED63A002 4 19 40.00 – 46.14 CED63A050 4 520 220.00 – 242.00 JXD63H400 4 2860
1.69 – 2.00 High 22 46.15 – 54.50 High 600 264.00 – 285.00 CJD63H400 6 3430
285.00 – 308.00 7 3710
.76 – 1.29 Low 10 24.23 – 41.52 Low 315 308.00 – 326.00 High 4000
1.30 – 1.75 2 17 41.53 – 56.91 2 540
1.76 – 2.29 ED63A003 3 23 56.92 – 68.45 ED63A100 3 740 155.00 – 176.00 Low 2000
2.30 – 2.68 CED63A003 4 30 68.46 – 76.91 CED63A100 4 890 176.00 – 198.00 2 2290
2.69 – 3.18 High 35 76.92 – 90.90 High 1000 220.00 – 242.00 LXD63L600 4 2860
264.00 – 285.00 CLD63L600 6 3430
1.23 – 1.99 Low 16 38.46 – 55.37 Low 500 285.00 – 308.00 7 3710
2.00 – 2.75 2 26 55.38 – 70.75 2 720 308.00 – 326.00 High 4000
2.76 – 3.52 ED63A005 3 36 70.76 – 84.60 ED63A125 3 920
3.53 – 4.14 CED63A005 4 46 84.61 – 96.14 CED63A125 4 1100 231.00 – 264.00 Low 3000
4.15 – 4.90 High 54 96.15 – 113.60 High 1250 264.00 – 292.00 2 3430
7
330.00 – 362.00 LXD63H600 4 4290
2.30 – 3.83 Low 30 30.76 – 35.37 Low 400 395.00 – 428.00 CLD63H600 6 5140
3.84 – 5.37 2 50 35.38 – 39.99 2 460 428.99 – 462.00 7 5570
5.38 – 6.52 ED63A010 3 70 44.51 – 49.23 FXD63L150 4 580 462.00 – 490.00 High 6000
6.53 – 7.68 CED63A010 4 85 53.84 – 58.45 CFD63L150 6 700
CIRCUIT BREAKERS
MOLDED CASE
7.69 – 9.10 High 100 58.46 – 63.06 7 760 215.00 – 238.00 Low 2800
63.07 – 74.50 High 820 238.00 – 261.00 2 3100
4.23 – 6.91 Low 55 261.00 – 284.00 3 3400
6.92 – 9.61 2 90 61.53 – 69.22 Low 800 308.00 – 369.00 LMXD63L800 5 4000
9.62 – 11.91 ED63A025 3 125 69.23 – 76.91 2 900 369.00 – 423.00 6 4800
11.92 – 13.83 CED63A025 4 155 84.61 – 92.29 FXD63A150 4 1100 423.00 – 462.00 7 5500
13.84 – 16.40 High 180 100.00 – 108.00 CFD63A150 6 1300 462.00 – 490.00 High 6000
108.00 – 115.00 7 1400
6.15 – 10.37 Low 80 115.00 – 136.00 High 1500 246.00 – 269.00 Low 3200
10.38 – 14.22 2 135 269.00 – 284.00 2 3500
14.23 – 18.06 ED63A030 3 185 85.00 – 100.00 Low 1100 284.00 – 323.00 3 3700
18.07 – 20.75 CED63A030 4 235 100.00 – 115.00 2 1300 362.00 – 492.00 LMXD63A800 5 4700
20.76 – 24.50 High 270 131.00 – 146.00 FXD63A250 4 1700 492.00 – 562.00 6 6400
162.00 – 177.00 CFD63A250 6 2100 562.00 – 616.00 7 7300
177.00 – 192.00 7 2300 616.00 – 660.00 High 8000
192.00 – 227.00 High 2500
231.00 – 264.00 Low 3000
264.00 – 292.00 2 3430
292.00 – 330.00 3 3800
362.00 – 395.00 MXD63L800 5 4710
428.00 – 462.00 CMD63L800 7 5570
462.00 – 490.00 High 6000
308.00 – 352.00 Low 4000
352.00 – 442.00 2 4570
442.00 – 447.00 3 5740
483.00 – 527.00 MXD63A800 5 6280
571.00 – 616.00 CMD63A800 7 7240
616.00 – 660.00 High 8000
385.00 – 440.00 Low 5000
495.00 – 550.00 MXD63H800 3 6430
605.00 – 660.00 CMD63H800 5 7860
660.00 – 695.00 6 8575
Breaker Mounted at a Distance From circuit-breaker ratings in Table 2 provide Interrupt Ratings
Motor Starter adequate time delay for starting the For normal commercial purposes,
ET thermal-magnetic circuit breakers majority of three phase induction motors. available fault current can conveniently
conform to the National Electrical Code To determine the ampere ratings of the ET be obtained in the Interrupting
table 430-52 requirements for motor breaker to protect a motor feeder, add the Selector Tables.
branch and feeder circuit protection rating of the ET breaker used to protect
when properly applied in conjunction with the largest motor branch circuit in the
motor-running overcurrent protective group to the full-load currents of the
devices. The recommended remaining motors in the group.
200 and 208V Motors 230V Motors 460V Motors 575V Motors
Motor 240V Circuit Breaker Data a 240V Circuit Breaker Data a 480V Circuit Breaker Data a 600V Circuit Breaker Data a
Horse-
power Breaker Catalog Ampere Breaker Catalog Ampere Breaker Catalog Ampere Breaker Catalog Ampere
Rating Type Number Rating Type Number Rating Type Number Rating Type Number Rating
0001⁄2 BQ3B015 015 BQ3B015 015 ED43B015 015 ED63B015 015
0003⁄4 BQ3B015 015 BQ3B015 015 ED43B015 015 ED63B015 015
001 BQ3B015 015 BQ3B015 015 ED43B015 015 ED63B015 015
BQ b
BQ b
ED4 ED6
001 ⁄2
1
BQ3B015 015 BQ3B015 015 ED43B015 015 ED63B015 015
002 BQ3B020 020 BQ3B015 015 ED43B015 015 ED63B015 015
003 BQ3B030 030 BQ3B020 020 ED43B015 015 ED63B015 015
005 BQ3B040 040 BQ3B030 030 ED43B015 015 ED63B015 015
007 ⁄2
1
BQ3B060 060 BQ3B050 050 ED43B030 030 ED63B020 020
010 BQ b
BQ3B070 070 BQ b
BQ3B070 070 ED4 ED43B030 030 ED6 ED63B030 030
015 BQ3B100 100 BQ3B090 090 ED43B040 040 ED63B035 035
020 BQ3B100 100 ED43B050 050 ED63B050 050
025 FXD63B125 125 FXD63B125 125 FXD63B090 090 FXD63B060 060
030 FXD63B150 150 FXD63B150 150 FXD63B100 100 FXD63B070 070
FXD6
040 FXD6 FXD63B175 175 FXD6 FXD63B175 175 FXD6 FXD63B125 125 FXD63B090 090
050 FXD63B200 200 FXD63B200 200 FXD63B150 150 FXD63B100 100
FXD63B225 225
060 JXD2 JXD23B300 300 — — — FXD6, FD6 FXD63B150 150 FXD6 FXD63B100 100
075 JXD2 JXD23B400 400 JXD2 JXD23B350 350 FXD6, FD6 FXD63B200 200 FXD6, FD6 FXD63B125 125
FD6 c
FD63B250 250
100 JXD2 JXD23B400 400 JXD2 JXD23B400 400 FXD6, FD6 FD63B175 175
JD6 c JD63B250 250
LD6 c
or LD63B600 LD6 c
or LD63B500 or FXD6, FD6 FXD63B200 200
125 600 500 JD6 c JD63B300 300
LMD6 LMD63B600 LMD6 LMD63B500 OR JD6 c JD63B200 200
LD6 c
or LD63B600 or LD63B600 or FXD6 or FXD63B225 225
150 600 LMD6 600 JD6 c
JD63B300 300
LMD6 LMD63B600 LMD63B600 JD6 c JD63B225 225
200 LMD6 LMD63B800 800 LMD6 LMD63B800 800 JD6 c
JD63B350 350 JD6 c
JD63B300 300
7
LD6 c or LD63B500 or
350 — — — — — — LMD6 LMD63B700 700 500
LMD6 LMD63B500
LD6 c or LD63B600 or
400 — — — — — — LMD6 LMD63B800 800 600
LMD6 LMD63B600
500 — — — — — — — — — LMD6 LMD63B800 800
a Theselection of breakers for this table is in accordance with b Forpanelboard applications, substitute the BL breaker for c Fornon-interchangeable trip applications, substitute the
Article 430, 2005 National Electric Code. Recommended the BQ, ED2 circuit breakers may also be used. FXD6 for the FD6, the JXD6 for the JD6, or the LXD6 for
circuit breakers are for full voltage starting, special the LD6.
consideration is necessary for reduced voltage starting.
7
150 800 900 1000 1100 1200 1300 1400 1500 — HFD62B150 HFD63B150
175 900 1060 1210 1370 1520 1780 1930 2000 — HFD62B175 HFD63B175
200 900 1060 1210 1370 1520 1780 1930 2000 — HFD62B200 HFD63B200
CIRCUIT BREAKERS
MOLDED CASE
225 1100 1300 1500 1700 1900 2100 2300 2500 — HFD62B225 HFD63B225
250 1100 1300 1500 1700 1900 2100 2300 2500 — HFD62B250 HFD63B250
70 600 640 690 730 770 810 850 900 — — HHFD63B070
80 600 640 690 730 770 810 850 900 — — HHFD63B080
90 600 640 690 730 770 810 850 900 — — HHFD63B090
100 700 770 840 920 990 1060 1140 1200 — — HHFD63B100
110 700 770 840 920 990 1060 1140 1200 — — HHFD63B110
HHFD6 125 800 900 1000 1100 1200 1300 1400 1500 — — HHFD63B125
150 800 900 1000 1100 1200 1300 1400 1500 — — HHFD63B150
175 900 1060 1210 1370 1520 1780 1930 2000 — — HHFD63B175
200 900 1060 1210 1370 1520 1780 1930 2000 — — HHFD63B200
225 1100 1300 1500 1700 1900 2100 2300 2500 — — HHFD63B225
250 1100 1300 1500 1700 1900 2100 2300 2500 — — HHFD63B250
70 600 640 690 730 770 810 850 900 — CFD62B070 CFD63B070
80 600 640 690 730 770 810 850 900 — CFD62B080 CFD63B080
90 600 640 690 730 770 810 850 900 — CFD62B090 CFD63B090
100 700 770 840 920 990 1060 1140 1200 — CFD62B100 CFD63B100
110 700 770 840 920 990 1060 1140 1200 — CFD62B110 CFD63B110
125 800 900 1000 1100 1200 1300 1400 1500 — CFD62B125 CFD63B125
CFD6 150 400 460 520 580 640 700 760 820 CFD63L150 — —
150 800 900 1000 1100 1200 1300 1400 1500 CFD63A150 CFD62B150 CFD63B150
150 1100 1300 1500 1700 1900 2100 2300 2500 CFD63H150 — —
175 900 1060 1210 1370 1520 1780 1930 2000 — CFD62B175 CFD63B175
200 900 1060 1210 1370 1520 1780 1930 2000 — CFD62B200 CFD63B200
225 1100 1300 1500 1700 1900 2100 2300 2500 — CFD62B225 CFD63B225
250 1100 1300 1500 1700 1900 2100 2300 2500 CFD63A250 CFD62B250 CFD63B250
Note: T
olerances for instantaneous trip points meet UL 489 Instantaneous trip adjustment is made through the n Built to order. Allow 2–3 weeks for delivery.
(7.3). Nominal AC instantaneous trip points are given breaker cover on all frame breakers. To change instan-
in the tables. For DC instantaneous trip points, add 15% taneous trip point on circuit breaker, depress indicating
to nominal values. knob, then rotate to desired position.
LD6(A) 400 2000 2290 2570 2860 3140 3430 3710 4000 — LD62B400 LD63B400
450 2000 2290 2570 2860 3140 3430 3710 4000 — LD62B450 LD63B450
500 3000 3430 3800 4290 4710 5140 5570 6000 — LD62B500 LD63B500
MOLDED CASE
CIRCUIT BREAKERS
600 2000 2290 2570 2860 3140 3430 3710 4000 LXD63L600 — —
600 3000 3430 3800 4290 4710 5140 5570 6000 LXD63H600 LD62B600 LD63B600
250 1250 1430 1610 1790 1960 2140 2320 2500 — HLD62B250 HLD63B250
300 1250 1430 1610 1790 1960 2140 2320 2500 — HLD62B300 HLD63B300
350 2000 2290 2570 2860 3140 3430 3710 4000 — HLD62B350 HLD63B350
HLD6(A) 400 2000 2290 2570 2860 3140 3430 3710 4000 — HLD62B400 HLD63B400
450 2000 2290 2570 2860 3140 3430 3710 4000 — HLD62B450 HLD63B450
500 3000 3430 3860 4290 4710 5140 5570 6000 — HLD62B500 HLD63B500
600 3000 3430 3860 4290 4710 5140 5570 6000 — HLD62B600 HLD63B600
250 1250 1430 1610 1790 1960 2140 2320 2500 — HHLD62B250 HHLD63B250
300 1250 1430 1610 1790 1960 2140 2320 2500 — HHLD62B300 HHLD63B300
350 2000 2290 2570 2860 3140 3430 3710 4000 — HHLD62B350 HHLD63B350
HHLD6 400 2000 2290 2570 2860 3140 3430 3710 4000 — HHLD62B400 HHLD63B400
450 2000 2290 2570 2860 3140 3430 3710 4000 — HHLD62B450 HHLD63B450
500 3000 3430 3860 4290 4710 5140 5570 6000 — HHLD62B500 HHLD63B500
600 3000 3430 3860 4290 4710 5140 5570 6000 — HHLD62B600 HHLD63B600
250 1250 1430 1610 1790 1960 2140 2320 2500 — — CJD63B250
300 1250 1430 1610 1790 1960 2140 2320 2500 — — CJD63B300
350 2000 2290 2570 2860 3140 3430 3710 4000 — — CJD63B350
400 2000 2290 2570 2860 3140 3430 3710 4000 — — CLD63B400
CLD6
450 2000 2290 2570 2860 3140 3430 3710 4000 — — CLD63B450
500 3000 3430 3860 4290 4710 5140 5570 6000 — — CLD63B500
600 2000 2290 2570 2860 3140 3430 3710 4000 CLD63L600 — —
600 3000 3430 3860 4290 4710 5140 5570 6000 CLD63H600 — CLD63B600
500 3000 3430 3860 4290 4710 5140 5570 6000 — — LMXD63B500
600 3000 3430 3860 4290 4710 5140 5570 6000 — LMXD62B600 LMXD63B600
LMXD6 700 3200 3500 3700 4200 4700 6400 7300 8000 — LMXD62B700 LMXD63B700
800 2800 3100 3400 3700 4000 4800 5500 6000 LMXD63L800 — —
800 3200 3500 3700 4200 4700 6400 7300 8000 LMXD63A800 LMXD62B800 LMXD63B800
500 3000 3430 3860 4290 4710 5140 5570 6000 — LMD62B500 LMD63B500
600 3000 3430 3860 4290 4710 5140 5570 6000 — LMD62B600 LMD63B600
LMD6
700 3200 3500 3700 4200 4700 6400 7300 8000 — LMD62B700 LMD63B700
800 3200 3500 3700 4200 4700 6400 7300 8000 — LMD62B800 LMD63B800
7
HND6 1000 5000 5715 6430 7145 7860 8575 9290 10000 — HND62B100 HND63B100
1200 5000 5715 6430 7145 7860 8575 9290 10000 — HND62B120 HND63B120
CIRCUIT BREAKERS
MOLDED CASE
900 5000 5715 6430 7145 7860 8575 9290 10000 — — HNXD63B900
HNXD6 1000 5000 5715 6430 7145 7860 8575 9290 10000 — — HNXD63B100
1200 5000 5715 6430 7145 7860 8575 9290 10000 — — HNXD63B120
800 4000 4570 5140 5710 6280 6850 7420 8000 — — CND63B800
900 5000 5715 6430 7145 7860 8575 9290 10000 — — CND63B900
CND6 1000 5000 5715 6430 7145 7860 8575 9290 10000 — — CND63B100
1200 5000 5715 6430 7145 7860 8575 9290 10000 — — CND63B120
1200 5000 5715 6430 7145 7860 8575 9290 10000 — — PD63B120
PD6 1400 5000 5715 6430 7145 7860 8575 9290 10000 — — PD63B140
1600 5000 5715 6430 7145 7860 8575 9290 10000 — — PD63B160
1200 5000 5715 6430 7145 7860 8575 9290 10000 — — PXD63B120
PXD6 1400 5000 5715 6430 7145 7860 8575 9290 10000 — — PXD63B140
1600 5000 5715 6430 7145 7860 8575 9290 10000 — — PXD63B160
1200 5000 5715 6430 7145 7860 8575 9290 10000 — — HPD63B120
HPD6 1400 5000 5715 6430 7145 7860 8575 9290 10000 — — HPD63B140
1600 5000 5715 6430 7145 7860 8575 9290 10000 — — HPD63B160
1200 5000 5715 6430 7145 7860 8575 9290 10000 — — HPXD63B120
HPXD6 1400 5000 5715 6430 7145 7860 8575 9290 10000 — — HPXD63B140
1600 5000 5715 6430 7145 7860 8575 9290 10000 — — HPXD63B160
1200 5000 5715 6430 7145 7860 8575 9290 10000 — — CPD63B120
CPD6 1400 5000 5715 6430 7145 7860 8575 9290 10000 — — CPD63B140
1600 5000 5715 6430 7145 7860 8575 9290 10000 — — CPD63B160
1800 5000 5715 6430 7145 7860 8575 9290 10000 — — RD63B180
RD6 2000 5000 5715 6430 7145 7860 8575 9290 10000 — — RD63B200
1800 5000 5715 6430 7145 7860 8575 9290 10000 — — RXD63B180
RXD6 2000 5000 5715 6430 7145 7860 8575 9290 10000 — — RXD63B200
1800 5000 5715 6430 7145 7860 8575 9290 10000 — — HRD63B180
HRD6 2000 5000 5715 6430 7145 7860 8575 9290 10000 — — HRD63B200
1800 5000 5715 6430 7145 7860 8575 9290 10000 — — HRXD63B180
HRXD6 2000 5000 5715 6430 7145 7860 8575 9290 10000 — — HRXD63B200
2-Pole 3-Pole
Maximum Self-Protective Ordering Information
Frame Instantaneous
Amp Rating Catalog Number Catalog Number Override±20%c Order by catalog number. Switches
BQ2S060 n BQ3S060n 11000 include frame and self protective trip
1100 unit only. Order lugs separately from
BQ2S100n BQ3S100n 11000
1125 ED22S100An ED23S100A 11000 pages 7-143 to 7-145.
ED42S100An ED43S100A 11000
ED42S125An ED43S125A 11000
ED62S100An ED63S100A 11000
— ED63S125A 11000
CED62S100An CED63S100An 11000
CED62S125An CED63S125An 11000
1250 — HQR23S250HA 12000
FXD62S250A FXD63S250A 13200
HFXD62S250An HFXD63S250An 13200
a CFD63S250An 13200
1400 JXD22S400An JXD23S400A 16000
— JXD63S400A 16000
— HJXD63S400An 16000
a
CJD63S400An 16000
1600 — LXD63S600A 16000
— HLXD63S600An 16000
a
CLD63S600An 16000
1800 — LMXD63S800An 18000
— MXD63S800A 18000
a
CMD63S800A 18000
1200 — NXD63S120A 10000
a
CND63S120An 10000
1600 a
PXD63S160Ae 10000
2000 a
RXD63S200Ane 10000
7 MOLDED CASE
CIRCUIT BREAKERS
7-136 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
Revised on 05/31/18
Typical Trip Unit Labeling and Adjustment Positions for the Sentron Sensitrip Circuit Breaker.
LI Trip Unitsa
7
CIRCUIT BREAKERS
MOLDED CASE
LSIG Trip Unitsa
ln = Maximum circuit breaker ampere rating Ig = Ground fault pickup expressed in amperes
lr = Continuous current rating expressed in amperes tsd = Short time delay - either fixed or I2t time delay function
Ii = Instantaneous pickup expressed in amperes tld = Long time delay - I2t time delay function
Isd = Short time pickup expressed in multiples of Ir tg = Ground fault delay - I2t time delay function
NOTE: Frame rating (In) of 600A shown as an example. a Schematic of advanced trip unit shown. Basic trip units
Trip unit settings will vary based on the specific frame are identical but do not include DAS / Maintenance
rating (In) of the device. Mode functionality.
(tsd)
Rating (In) Continuous Current Setting (Ir) Long Time Delay Setting (tld) Instantaneous Pickup Setting (Ii)
Setting 600A 200 2.5 750
Description 600A max current rating 200A 2.5 sec to trip @ 6 x Ir [6 x 200A = 1200A] 750A
Breaker Description
The ever-increasing use of plant and Trip Units
energy management systems has The electronic, micro processor-based b Manual operating mechanism with
intensified the demand for circuit trip unit is auxiliary voltage-independent mechanical and electrically
breakers supporting multiple open for all protective functions and enables interlocked closing
protocols to monitor and control the flow adaptation to the different protection
of energy in the power system. The b Motorized operating mechanism with
requirements of distribution systems, mechanical and electrically interlocked
extensive and modular WL family of motors, transformers and generators. closing. Operating mechanisms with
circuit breakers and accessories provides electrically interlocked closing are
this for applications from 200A to 6000A. Non-Automatic Switch
suitable for synchronizing tasks
Applications A special version of the circuit breaker is
used as a non-automatic switch. Auxiliary Contacts
WL breakers can be applied as main, tie,
The non-automatic switch is constructed Auxiliary switches can be added accord-
feeder or distribution breakers in
without a trip unit and has no protective ing to the type of installation. They are
low-voltage electrical power systems.
function. A possible application is for use easily mounted via front, top mounted
Versions as a tie in systems with parallel feeds. terminal blocks.
b Frame ratings: 800A to 6000A Main Bus Connectors Modularity
b 3 physical frame sizes Breakers are equipped with standard Common guide frames for the draw-out
b Rated nominal operating voltage up vertical main bus connections. Horizontal version make them completely inter-
to 635VAC bus connections are available as an changeable between the UL 489 and
b Seven interrupting classes from 50kA option in Frame Size 1 and 2 up to ANSI / UL 1066 rated circuit breakers.
to 200kA at 480V 2000A. Components, such as auxiliary releases,
b Circuit breaker or non-automatic switch Communication Capability motorized operating mechanisms, trip
units, current sensors, auxiliary
b WL Circuit Breakers are delivered as MODBUS or PROFIBUS communica-
signal switches, automatic reset devices
complete assembled breakers or tions transmit the acquired and metered
or interlocks can be used to modify or
individual frames, guide frames, and data, such as current values, breaker
accessories retrofit any circuit breaker to meet
status, trip log, etc. to a central
changing requirements. The main con-
Installation Types monitoring computer. With a factory
tacts can be replaced to extend the life
installed metering function option, the
Fixed-mounted or Draw-out version. of the circuit breaker and feature inte-
WL acquires data useful for power
grated contact wear indicators.
Standards management and can contribute to a
significant savings in energy costs. A Electronic Trip Unit Modularity
b WL ANSI / UL 1066 Circuit Breakers
will satisfy: C37.13, C37.16, C37.17, new, internal circuit breaker bus enables Modularity is the outstanding feature of
C37.50, NEMA SG3 the expansion of breaker functionality the new WL Circuit Breakers. The trip
through the integration of many
7
units themselves can be retrofitted with
b WL UL 489 Circuit Breakers will secondary functions which were
satisfy: UL 489 special LCDs, ground fault modules,
previously separate, including: rating plugs and communication
CIRCUIT BREAKERS
MOLDED CASE
b WL Circuit Breakers are suitable for
use in UL 1558 LV Switchgear and UL b Control of analog displays modules.100% Rated Circuit Breaker WL
circuit breakers are designed for
891 LV Switchboards b Options for testing the
communication setup continuous operation at 100% of their
Conditions of Application current rating without the need for
WL Circuit Breakers are designed to b Display of breaker status and reason external heat sinks.
for trip
meet standard Industrial and Commercial
Conditions of Application
application requirements. b Input modules for reading other
external signals and transmitting WL Circuit Breakers are designed to
Uniform Dimensions these signalsvia PROFIBUS or meet standard Industrial and Commercial
WL Circuit Breaker dimensions differ MODBUS communication application requirements.
only in the device width, which varies by
b A selection of output modules to
frame size. With the exception of the provide contact closures based on
200kA ANSI Frame Size II which has an events or measured-value setpoints.
additional 5” in depth to accommodate It is not only possible to monitor the
integral fuses and the UL489 Frame Size breaker remotely, it is also possible
I which measures only 15” in height to to open and close the breaker as well
allow six-high stacking in switchboards. as setting parameters remotely
Minimal Space Requirements Operating Mechanisms
The WL design is extremely compact Circuit breakers can be optionally
without sacrificing performance and does delivered with different operating
not use energy-wasting heat sinks. mechanisms, including:
b Manual operating mechanism with
mechanical closing (standard)
Additional Functions
Selectable neutral protection l l l
Defeatable short-time protection l — l
Defeatable instantaneous protection l — l
Selectable thermal memory l l l
Zone selective interlocking l l l
Selectable I2t or fixed short-time delay l l l
Adjustable instantaneous pick-up l — l
Selectable I2t or I4t long-time delay l l l
Adjustable short-time delay and pick-up l l l
Selectable and adjustable neutral protection l l l
Dual protective setting capability — — l
7
Dynamic arc-flash sentry — — l
Extended instantaneous protection l l l
CIRCUIT BREAKERS
MOLDED CASE
Parameterization and Displays
Parameterization by rotary switches (10 steps) l l —
Parameterization by communication (absolute values) — l l
Parameterization by menu/keypad (absolute values) — — l
Remote parameterization of the basic functions — — l
Remote parameterization of the additional functions — — l
Alphanumeric LCD u u —
Graphical LCD — — l
Metering Function
Metering function u u u
Communication
CubicleBUS l l l
Communication via PROFIBUS-DP u u u
Rating Plug a wide range of locking devices can be b Spring charge indicator
It is no longer necessary to replace the installed or retrofit, including: Rear vertical main contacts
b
current transformer to change the rated b Lockable drawout version to protect
current of the breaker. Instead, you b Main contact replacement flag
against unauthorized removal
simply replace the rating plug which is (standard) b Auxiliary plug system with bare wire
easily accessible on the front of the trip pressure screw terminals. Delivery
unit. The circuit breaker is set to the new b High degree of protection through includes all auxiliary plugs necessary
rated current quickly and is already Plexiglas cover
correctly labeled. for both factory installed and future
Long Time Overcurrent Protection b Mechanical reclosing lockout after field installed accessories
with Switchable I2t/I4t Characteristics long-time, short-time or instantaneous Mechanical trip indicator of the
trip (optional) b
The long time overcurrent overcurrent release system
protection in the ETU745, ETU755 and b Devices with trip unit ETU745 or b Automatic reset after trip
ETU776 trip units can be switched higher are equipped with temperature
between an I2t and I4t characteristic to sensors on the BSS and b The front panel cannot be removed if
improve coordination between upstream COM15/COM16 (standard) the circuit breaker closed
circuit breakers and fuses. Laminated main contact fingers as part
Front Panel b Lock provision for locking the breaker b
in the OPEN position of the breaker contact strip on
The front panel is designed so that it can the drawout circuit breaker
be accessed through a cutout in the b Lockable covers for the CLOSE button
door, which means that all controls and b Breaker position display in the
displays are accessible even when the b Lockable racking handle prevents operator’s panel
moving the breaker
cubicle door is closed. The front panels Captive crank handle for racking out
b
of all Frame Size II and Frame Size III b Lockable charging handle prevents the breaker
circuit breakers are identical, and allow charging the springs
for two different through-door access Standard Version Features b Guide frame with guide rails for easy
designs: Trip unit and front panel controls handling of draw-out version
or front panel controls only. The degree WL Circuit Breakers have the following
of protection of the front panel is IP 20. standard equipment: b Breaker cannot be moved in the
Environmental Protection CLOSED state
b Mechanical CLOSE and mechanical
The plastics used are halogen-free and OPEN push buttons b Rated current coding between the
recyclable. guide frame and the breaker
b Manual operating mechanism with
Safety and Reliability mechanical closing b Suitable for reverse feed applications
In order to help protect the electrical The breaker is always equipped with
distribution system and circuit breaker b Contact position indicator b
the required number of secondary
against unauthorized breaker operations, b Front panel ready-to-close indicator disconnect blocks
Exclusive Features
Generator/Utility Dynamic Arc-Flash Sentry (DAS) employs the instantaneous function is switched
7
Protection Sets the unique dual protective setting capa- off on an ‘LSI’ trip unit, can only be
24/7/365 power availability is critical for bility of the 776 trip unit, coupled with applied up to it’s short-time rating,
the ability to easily toggle to a lower arc commonly 85kA or less. For application
MOLDED CASE
CIRCUIT BREAKERS
Lug Information
Mechanical Lug Selection
Table A
7
For Use Circuit Breaker
With Type(s) Ampere Rating Cables Per Lug Lug Wire Range Number of Poles
Load Side
CIRCUIT BREAKERS
MOLDED CASE
#8–#4 AWG Cu-Al
This exception is applicable
BQ, BL, QP 55-60 1 #3 AWG requires 22 or 65
to 1- and 2-pole only
kAIC
Note:
(A) Molded case circuit breakers having a rated ampacity a Lug
is steel.
of 125 amperes or less are to be connected with 60 or b Sold
in package of six.
75°C wire. Circuit breakers having a rated ampacity c One
nut keeper plate is required with each lug on the
greater than 125 amperes shall only be cabled with NGG breaker.
75°C cable unless otherwise indicated on the circuit
breaker label. Exceptions to this rule are outlined in
article 110-14 C(1)(2) of the 2005 National
Electrical Code.
(B) Connector wire ranges and cavities are established in
conjunction with Table 6.1.4.2.1 of UL 489 standards.
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-143
Revised on 05/31/18
Lug Information
Aluminum Body Lugs for Copper or Aluminum Wire Selection
ND6, 2TA4P8500 bc
NXD6, SND6-B, 250–500 kcmil (Cu or Al)
3TA4P8500 bd
HND6, HNXD6, 800–1200 1–4
MOLDED CASE
CIRCUIT BREAKERS
a Use
TA2K500 or TA3K500 only. c Contains 2 connectors plus 1 NDTS end barrier.
b Used
for 100% rated MD/ND frame breakers. d Contains 3 connectors plus 1 NDTS end barrier.
Rated for 90° C cable.
7-144 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
Revised on 11/30/19
Lug information
Optional Mechanical Lugs Selection
Compression Lugs
Ampere Lugs
For Circuit Breaker Types Rating Poles Per Kit Lug Wire Size Catalog Number
Lugs (contains indicated number of lugs and necessary hardware per kit)
ED2, ED4, ED6, HED4, HHED6, CED6 15–125 1, 2, 3 1 #2/0 AWG Cu/Al CCE125
QR2, QR2H, HQR2, HQR2H 100-250 2-3 1 #6 - 350kcmil Al/Cu CCQ250
F(X)D6-A, HF(X)D6, HHF(X)D6, CFD6 125–250 2, 3 1 350 kcmil CCF250
JXD2-A, J(X)D6-A, HJ(X)D6-A, HHJ(X)D6-A, CJD6, SJD6-B, SHJD6-B,
200–600 2, 3 1 500 kcmil CCL600
SCJD6-B, L(X)D6-A, HL(X)D6-A, CLD6, SLD6-B, SHLD6-B, SCLD6-B
Kits (contain lugs and hardware for complete line or load end of 2 or 3-pole breaker)
2 6 CCM800K2
M(X)D6, HM(X)D6, CMD6, SMD6-B, SHMD6-B, SCMD6-B 500–800
3 9 CCM800K3
500 kcmil
2 8 CCN1200K2
7
N(X)D6, HN(X)D6, CND6, SND6-B, SHND6-B, SCND6-B 900–1200
3 12 CCN1200K3
CIRCUIT BREAKERS
MOLDED CASE
Distribution Lugs
Ampere Lugs Wires
For Circuit Breaker Types Rating Poles Per kit Per Lug Lug Wire Size Catalog Number
#6-#4 AL
NGG, HGG, LGG 15-125 1,2,3 1 6 TA6GG04
#14-#4 Cu
#14-#4 AWG Cu
ED2, ED4, ED6, HED4, HHED6, CED6 15-125 1,2,3 1 6 TA6ED06
#6-#4 AWG Al
#14-#4 AWG Cu
F(X)D6-A, HF(X)D6, HHF(X)D6, CFD6 70-250 2,3 1 6 TA6FD04
#6-#4 AWG Al
s Built to order. Allow 6–8 weeks for delivery. a Used for 100% rated JD/LD frame circuit breakers.
Special purpose wire connectors, not for general use.
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-145
Revised on 10/31/18
A variety of internal and external 50°C Ambient Calibration — Not UL listed and not available for solid state, 100% rated breakers
accessories, as well as modifications, or 400HZ calibrated breakers.
are available to adapt Siemens circuit or BL Type Circuit Breakers
F
breakers to special installation — Add suffix ‘M’ to catalog number
(Example: B120M).....................................................................................No Charge
requirements. UL listed internal
accessories for 100 through 2000A For BQ and ED Frame Circuit Breakers
— Replace ‘B’ in catalog number with ‘M’..................................................No Charge
circuit breakers are field-addable. (Example: BQ3M060, ED63M060)
Internal accessories fine tune an For FD, JD, LD, LMD, MD, ND, PD, and RD Frame Circuit Breakers
electrical distribution system, Non-Interchangeable Trip (3–pole only).................................................No Charge
allowing control of the circuit breakers to — Replace ‘B’ in catalog number with ‘M’
(Example: FXD63M225, JXD63M400)
meet special application requirements.
400 HZ Calibration
For example, emergency situations may
dictate tripping critically placed circuit UL Listed (5KA IR)
breakers quickly. Shunt trips accomplish for BQ & BL Type Circuit Breakers (200A max.)............................................Add 25% to list price
— Add suffix ‘Y’ to catalog number
this conveniently and efficiently.
Or, when voltage drops are a concern, Not UL Listed
for all other Circuit Breakers, see derating tables on page 7-157 and order standard circuit breakers.
undervoltage trips automatically open
Fungus Proofing
the circuit breaker at a predetermined
voltage level. All BQD, CQD, GB, GG, ED, FD, JD, LD, LMD, MD, ND, PD, RD, DG, FG, JG, LG, MG, NG, and PG
Frame Circuit Breakers are inherently fungus resistant and do not require special treatment.
A wide range of external operating and For BL, and BQ Type Circuit Breakers.............................................................Add $10.00 net per pole
mounting accessories is also available. — Consult Sales Office for Availability
For example, face, shallow, and back For all other Circuit Breaker Types..................................................................Add $160.00 net per device
mounting plates are ideal for tailoring BQ — Consult Sales Office for Availability
circuit breakers to OEM applications. Certificate of Compliance with Test Report (catalog number CERT OF COMP.) Add $210.00 net
A complete line of operating handles Certificate of compliance testing must be performed on the actual device being shipped.
and handle-blocking devices meet The certificate cannot be provided after initial shipment. Order for devices with COC requirement
must be placed directly with the factory by the sales office and shipped directly to the end user.
switchboard, enclosure and safety
needs. Plug-in mounting assemblies,
which simplify switchboard mounting of
circuit breakers and permit breaker
removal without disconnecting bus or
cable connections, are available.
Feature Combinations
The available feature combinations are shown in the chart below. For applications requiring combinations
of features not listed in this chart, consult the sales office for availability.
7
CIRCUIT BREAKERS
MOLDED CASE
S01FD60 S01FD60
For ED Frames For FD Frames For JD and LD Frames
Padlocking Device
For locking breaker in “OFF” position. Note “ON” position does not affect breaker fuctionally
ECPLD1 Type QP, BL, QAF2, QPF2, QE, QT-Duplex, BQ, BQXD 1P 3 Pieces
ECPLD1R Type QP, BL, QAF2, QPF, QE, QT-Duplex, BQ, BQXD 1P 3 Pieces
(Red Color)
ECPLD2 Type QP, BL, QAF2, QPF, QE, QT-Triplex & Quadplex, BQ, 2P 3 Pieces
BQXD
ECPLD2R Type QP, BL, QAF2, QPF, QE, QT-Triplex & Quadplex, BQ, 2P 3 Pieces
BQXD (Red Color)
ECPLD3 Type QP, BL, QAF2, QPF, QE, BQ 3P 1 Piece
US2:ECPLD3R Type QP, BL, QAF2, QPF, QE, BQ (Red Color) 3P 1 Piece
ECQLD3 Type QP, BL, BQ, BQXD 1P 10 Pieces
ECQLD4 Type QT-Duplex QT-Duplex Breakers 10 Pieces
ECQLN3 150-225 MBKA, QN, QNR n/a 1 Piece
ECQTH4 Type QP, BL, BQH Designed for (3) 1P Breakers 1 Piece
Handle Tie
Provide simultaneous swiching of 2 adjacent handles.
ECQTH2 Type QT Duplex Designed for (2) QT Duplex Breakers 25 Pieces
ECQTH3 Type QP, BL 2P 50 Pieces
Mechanical Interlock
ECQML12 Type QP, BL, BQ Interlock Bracket Designed for 1” Breaker 10 Pieces
Mounting Accessories
7
Replacement Lugs
TA1Q1 Type BQ, NGG 100A Al Cu LGS n/a 6 Pieces
TC1Q1 Type BQ, NGG 40A Al Cu LUGS n/a 6 Pieces
Finger Shield
BQFS1K Type BQXD Finger Shield (Bulk Pack) n/a 1000 Pieces
BQFS2 Type BQXD Finger Shield n/a 2 Pieces
Filler Plate
ECQF3 1” Filler Plate n/a 5 Pieces
For a complete list of standby power mechanical QP Type includes QPH, HQP QAF2 Type includes QAFH2, BAF2, BAFH2, QFGA2,
interlock kits, see page 1-25 BLType includes BLH, HBL QFGAH2, BFGA2, BFGAH2
For use with Ultimate Load Center Main Breakers BQ Type includes BQH, HBQ QPF Type includes QPHF, BLF, BLHF
Not suitable for use on 15-50A, 10 AIC Type QP Circuit QE Type includes QEH, BLE, BLEH
Breakers
Padlocking Device
ECPLD1 ECQLD3
ECQL1
ECBX231M
ECQTH2 ECQTH3
7
CIRCUIT BREAKERS
MOLDED CASE
ECMBR1 ECMBR2 ECQML12
Mounting Accessories
FP9508
FP9556
Padlocking Devices
For locking breaker in “OFF” position.
All QR HPLQR 1 1
⁄4
All BQD, CQD, NGB, HGB, LGB BQDPLD 01 1
⁄8
NGG, HGG, LGG HPLG 01 1
⁄4
FD Padlocking
All ED ED2HPL 01 1
⁄4 Device
All FD FD6PL1 01 1
⁄4 FD6PLI
All JD, LD, LMD JD6HPL 01 1
⁄4
All MD, ND, PD, RD MN6PLD 01 1
⁄4
All ED E2HBL 01 ⁄4
1
All FD FD6HB1 01 ⁄2
1
Terminal Shields
Catalog Standard
Breaker Type Poles Number Package
HGG, LGG, NGG 3 TSSG3A 1
JD, LD 3 JDTERMSHIELD 1
MD, ND, PD, RD 3 MDTERMSHIELD 1
Handle
Extension
EX11
7-150 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
Revised on 02/28/19
7
All JD, LD MI5413 d — 1 1
All LMD MI5406 dn — 1 1
CIRCUIT BREAKERS
MOLDED CASE
All MD MI5404 en — 1 3
All ND MI5404 en — 1 3
All PD, RD MI5405es — — —
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-151
Revised on 02/28/19
n Built to order. Allow 2–3 weeks for delivery. b Meets the requirements of NFPA 79, section 5.3.3.1 d For
extended shaft support order catalog number
for locking external operator disconnecting devices. RHONSB2.
s Built to order. Allow 6–8 weeks for delivery. c For e Lengthof shaft is 300mm (11.8 inches).
3 or 3R, order shaft and breaker operator as shown,
a For
use on 3-pole ED frame only. and handle RHOH. For 4 & 4X, order handle RHOH4.
Consult sales office for additional EG operator shaft
lengths.
7-152 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
Revised on 02/28/19
Max-Flex™ handles are available with solid black handles instead of the customary “red for on” flange handle. These are
preferred for use in IECmarkets, where red handles have specific meaning. Order components separately, appending the
letter “i” to the catalog number (e.g. FHOHI).
7
FHOFC036
Handle Auxiliary Switch
CIRCUIT BREAKERS
MOLDED CASE
For use with Max-Flex and Rotary Door operators (FHOH and RHOH). 1 NO and 1 NC contact (Form C).
For Use With Catalog Number
ED, FD, JD, LD, LMD, ND, PD, RD, SD, Max Flex HAS1
FDFBFR
Fixed Depth Flange Mounting
Minimum Left Hand Mount Right Hand Mount
Enclosure NEMA
Frames Depth Type Catalog Number Catalog Number
1, 3R, 12 FDFBELs FDFBERs
ED 6.44
4, 4X FDFBEL4s FDFBER4s
1, 3R, 12 FDFBFLs FDFBFRs
FD 6.44
4, 4X FDFBFL4s FDFBFR4s
Max-Flex™ handles are available with solid black handles instead of the customary “Red for On” flange handle. These are
preferred for use in IECmarkets, where red handles have specific meaning. Order components separately, appending the
letter “i” to the catalog number (e.g. FHOHI).
s Built to order. Allow 6–8 weeks for delivery. b48inch cable is standard length for M through R frame dConsult sales office for additional cable lengths for EG
aFor Max-Flex operators. Flex Shaft Operators. For 3-Pole only.
1- or 2-pole breaker order FHOED036 complete kit or cMeets requirements of NFPA 79, section 5.3.3.1 for 3-Pole ED only.
FHOEDBO breaker operator only. Use MFHM3R handle.
locking external operator disconnecting devices
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-153
Molded Case Circuit Breakers
External Accessories Selection/Dimensions
Dimensions
Frame A B C D E F
ED 7.04 4.31 — 4.31 13.84 8.84
FD 9.50 4.55 1.60 6.84 9.70 7.58
JD, LD, LMD 11.00 7.50 0.79 8.34 9.85 7.74
MD, ND, PD, RD 16.00 9.00 — 9.83 13.13 10.13
Operating Currents
On Off
Catalog In-Rush Running Time In-Rush Running Time Reset
Number (Amps) (Amps) (msec) (Amps) (Amps) (msec) (Amps)
7
Bottom View
7-154 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
Revised on 02/28/19
All ND PL9699
3 PC5666 c PC5666 c
7
Rear-Connecting Studs Circuit Breaker
CIRCUIT BREAKERS
MOLDED CASE
With Rear-Connecting Studs
For Use Extension
With Behind Line Side Load Side
Breaker Ampere Breaker
Frames Rating Description (inches) Catalog Number d Catalog Number d
100 Line Side (Short) 2.38 RS2643 s e
—
100 Load Side (Short) 2.38 — RS2644es
All ED
100 Line Side (Long) 4.88 RS2641es —
100 Load Side (Long) 4.88 — RS2642es
250 Short 3.12 RS4756es RS4756es
All FD
250 Long 7.06 RS4755es RS4755es
400 Short 5.85 RS5774s RS5774s
All JD
400 Long 11.20 RS5773s RS5773s
600 Short 5.85 RS5784s RS5784s
All LD
600 Long 11.20 RS5783s RS5783s
CJD, SCJD
Add required shield kit. CLRSJL3
CLD, SCLD
LM(X)D6, Short 5.85 RS5788s RS5788s
800
HLM(X)D6 Long 11.20 RS5787s RS5787s
All MD, 1200 Short 5.50 RS5786s RS5786s
ND 1200 Long 8.00 RS5785s RS5785s
s Built to order. Allow 6–8 weeks for delivery. c For vertical bus mounting — for horizontal, substitute e For proper electrical clearance, studs must alternate
aMust PC5665 for PC5664 and PC5667 for PC5666. between short and long stud lengths on circuit breaker
be ordered separately with other plug-in d Price includes one current stud, insulating tube, stud poles (e.g. SLSLSL or LSLSLS).
assemblies.
bEach piece catalog number consists of (1) mounting nuts and terminal shields, when required. f Plug-in assembly for EG breakers include line and load
side in one assembly.
block assembly and required tulip assemblies (2) for
2-pole, (3) for 3-pole
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-155
Revised on 05/31/18
Note: The information provided on this and the next page is intended for reference and recommendation only. Because several
variables can act on a circuit breaker’s performance at the same time, the data below is based less on controlled testing,
than on experience and engineering judgment. Contact Siemens for further information on special conditions and treatment.
High Ambient Temperatures Table 1 — Temperature Derating Data for Thermal-Magnetic Breakers
Because thermal-magnetic trip breakers Reference
are temperature sensitive and calibrated Ampere Rating at:
Ampere
for a specific ambient of 40° C (104° F) Rating at 50°C 60°C
(average enclosure temperature), a 40°C (104°F) (122°F) (140°F) Siemens Breaker Frames
higher ambient will cause the breaker to 15 13 11
trip at lower current than its nameplate 20 18 16
rating, in other words, causing the 25 23 21 BQ,
breaker to “derate” (see Table 1). 30 28 26 BL,
Similarly, the current carrying capacity 35 30 28 BQD,
of a circuit conductor is based upon a 40 37 34
certain ambient temperature, a higher 50 46 42
CQD,
ambient will reduce its current carrying 60 56 52 GG,
capacity, causing it to “derate.” Thus, 70 65 60 GB,
with a fluctuating temperature, a 90 84 78
thermal-magnetic breaker will derate ED
100 94 87
nearly parallel with its connected circuit
125 114 100
conductors and maintain close circuit
150 136 120 FD
protection. If the application temperature
exceeds 40° C (104° F) and is known, 175 159 140 QR
either a breaker specially calibrated for 200 182 160
the higher ambient or one oversized 225 205 180
according to Table 1 may be selected. 250 235 220
JD
In a case such as this, the circuit 300 276 252
conductors should be oversized as well. 350 325 301
LD
400 372 340
Siemens Sensitrip® IV and Type SB
500 468 435
Encased Systems Breakers are
insensitive to temperature changes. 600 564 525
MD
However, they do include circuitry to 700 658 613
protect the components from 800 754 704
abnormally high temperatures. 900 828 749
ND
1000 900 825
Moisture — Corrosion
1200 1090 1000
For atmospheres having high moisture 1400 1304 1148 PD
content and / or where fungus growth is 1600 1500 1320
prevalent, a special preventive treatment
7
6,000 (1,800)
400 Hz Systems a
Siemens molded case circuit breakers ambient temperature exceeds 40° C are usually the hottest terminals with a
can be applied for overcurrent protection (104° F). balanced load. A maximum temperature
on 400Hz systems, commonly used to Cable and Bus Sizing of 75° C (35° C over a maximum ambient
power computer installations, aircraft, of 40° C) would verify the particular
military and other specialty equipment. The cable and bus sizes to be utilized application. Temperature profiles taken
Below are basic guidelines. at 400Hz are not based on standard on these breakers can be correlated to
National Electric Codes tables for 60Hz ensure that the hottest points within
Circuit Breaker Derating Required application. Larger cross sections are the breaker are within the required
This table lists the maximum continuous necessary at 400Hz. All bus bars temperature limits.
current carrying capacity for Siemens specified are based upon mounting
breakers at 400Hz. Due to the increased the bars in the vertical plane to allow Factory Configuration
resistance of the copper sections maximum air flow. All bus bars are When required, molded case circuit
resulting from the skin effect produced spaced at a minimum of 0.25 in. (6 mm) breakers may be factory calibrated for
by eddy currents at these frequencies, apart. Mounting of bus bars in the 400Hz application. These breakers are
circuit breakers in many cases require horizontal plane will necessitate specially labeled for 400Hz usage and
derating. The thermal derating on these additional drafting. Edgewise orientation their nameplate current rating will
devices is based upon 100%, of the bus may change the maximum include the necessary derating factory.
three phase application in open air in a ratings indicated. If additional information The highest “Maximum Continuous
maximum of 40° C (104° F) with 48 in. is required for other connections of cable Amperes” rating at 400Hz, found in the
(1219 mm) of the specified cable or bus or bus, contact Siemens for information. table below approximates the highest
at the line and load side. Additional Application Recommendations specially calibrated 400Hz nameplate
derating of not less than 20% will be ampere rating available for a given
required if the circuit breaker is to be It is recommended that temperatures be
measured on the line and load terminals frame size. Contact Siemens for
utilized in an enclosure. Further derating ordering information on other
may be required if the enclosure or T-connectors of the center pole. These
breakers applied in 400Hz systems.
400Hz Breakers
Maximum Continuous Ampere Rating 75°C (167° F) Maximum Continuous Ampere Rating 75° C (167° F)
At 40°C (104°F) b Copper At 40° C (104° F) b Copper
Siemens 60HZ 400HZ Cable per Pole Siemens 60HZ 400/415HZ Cable per Pole
Breaker Enclosed No of Wire Breaker Enclosed No of Wire
Type Open Air Open Air c After Derating Pieces Size Type Open Air Open Air c After Derating Pieces Size
015 015 012 1 #14 0250 0210 168 1 250 kcmil
020 020 016 1 #12 0300 0240 192 1 350 kcmil
025 025 020 1 #10 LD6, LXD6, 0350 0260 208 1 500 kcmil
HLD6, HLXD6,
030 030 024 1 #10 HHLD6, 0400 0300 240 2 #3/0
035 035 028 1 #10 HHLXD6, 0450 0340 272 2 #4/0
CLD6
040 040 032 1 #8 0500 0375 300 2 250 kcmil
ED2, ED4, ED6, 045 043 034 1 #8 0600 0420 336 2 350 kcmil
BQD, HED4, 050 048 038 1 #8 0250 0210 210 1 250 kcmil
HED6, CED6, 060 057 046 1 #6 0300 0240 240 1 350 kcmil
7
GG, GB
070 067 054 1 #4 0350 0260 260 1 500 kcmil
LD6, LXD6,
080 076 061 1 #4 HLD6, HLXD6, 0400 0300 300 2 #3/0
100% Rated
CIRCUIT BREAKERS
MOLDED CASE
090 086 069 1 #3 0450 0340 340 2 #4/0
100 095 076 1 #3 0500 0375 375 2 250 kcmil
110 105 084 1 #2 0600 0420 420 2 350 kcmil
125 119 095 1 #1 0500 0400 320 2 250 kcmil
070 063 050 1 #4 MD6, MXD6, 0600 0430 360 2 350 kcmil
HMD6,
080 072 058 1 #4 HMXD6, CMD6 0700 0500 400 3 250 kcmil
090 080 064 1 #3 0800 0560 448 3 300 kcmil
QR2, QR2H, 100 090 072 1 #3 0500 0400 400 2 250 kcmil
MD6, MXD6,
HQR2, HQR2H, 110 095 075 1 #2 HMD6, 0600 0430 430 2 350 kcmil
FD6, FXF6, 125 105 084 1 #1 HMXD6, CMD6 0700 0500 500 3 250 kcmil
HFD6, HFXD6, 100% Rated
CFD6 150 125 100 1 #1/0 0800 0560 560 3 300 kcmil
175 140 112 1 #2/0 0800 0560 448 3 300 kcmil
200 160 128 1 #3/0 ND6, NXD6 0900 0600 480 3 350 kcmil
HND6, HNXD6,
225 180 144 1 #4/0 CND6 1000 0650 520 3 400 kcmil
250 200 160 1 250 kcmil 1200 0780 624 4 350 kcmil
200 170 136 1 #3/0 ND6, NXD6 0900 0600 600 3 350 kcmil
225 190 152 1 #4/0 HND6, HNXD6, 1000 0650 650 3 400 kcmil
JXD2, JD6, CND6
JXD6, HJD6, 250 210 168 1 250 kcmil 100% Rated 1200 0780 780 4 350 kcmil
HJXD6, HHJD6, 300 240 192 1 350 kcmil 1200 0780 624 4 400 kcmil
HHJXD6, CJD6 350 PD6, PXD6,
260 208 1 500 kcmil HPD6, HPXD6, 1400 0850 680 4 500 kcmil
400 300 240 2 #3/0 CPD6, 1600 0960 768 5 500 kcmil
200 170 170 2 #3/0 PD6, PXD6, 1200 0780 780 4 400 kcmil
225 190 190 2 #4/0 HPD6, HPXD6, 1400 0850 850 4 500 kcmil
JD6, JXD6, CPD6
HJD6, HJXD6 250 210 210 1 250 kcmil 100% Rated 1600 0960 960 5 500 kcmil
100% Rated 300 240 240 1 350 kcmil RD6, RXD6, 1600 0960 768 5 500 kcmil
350 260 260 1 500 kcmil HRD6, HRXD6 1800 1080 864 5 500 kcmil
400 300 300 2 #3/0 80% Rated 2000 1200 960 6 500 kcmil
aThe information provided on this page is intended for controlled testing, than on experience and engineering temperature is greater than 40°C (104°F).
reference and recommendation only. Because several judgment. Contact Siemens for further information on cCalculatedafter derating to compensate for the heating
variables can act on a circuit breaker’s performance at special conditions and treatment. of the copper conductor, caused by the skin effect
the same time, the data above is based less on bAdditional derating may be required if the ambient generated by eddy currents produced at 400/415HZ.
Interrupting Class
N — Normal
H — High
L — Very High
C — Trip Unit Only
Frame Family
D — Type DG L — Type LG P — Type PG
F — Type FG M — Type MG
J — Type JG N — Type NG
Breaker Type
E — Global DG, FG Frame Only R —
Molded Case Switch
600 Y/347 V (DG, FG, LG-frame)
G — Global interchangeable (UL, S — Molded Case Switch
IEC, CE, CSA, NOM, CCC) T — Trip Unit Only
J — 240V rated JG frame, V — Thermal Magnetic, standard 40°C
Non-interchangeable only ambient, 600VAC 25kA, UL/CSA
K — Global, Non-interchangeable (LG frame)
(DG, FG, LG-frame) W — 100% rated, Non-interchangeable
M — Motor Circuit Protector (DG, LG-frame)
P — Motor Circuit Protector X — Global Non-interchangeable
(DG, FG Only) Y — 100% rated, Non-interchangeable
Number of Poles
2, 3
Trip Unit
F — Frame only, without trip unit S — Molded Case Switch
B — Thermal Magnetic, standard 40° C ambient A — Electronic w/ LCD, LSI or 3P (neutral protected)
L — Magnetic Only, Motor Circuit Protector - Low G — Electronic w/ LCD, LSIG, 3P/4W (selectable residual or
instantaneous range return type ground fault protection)
J — Magnetic Only, Motor Circuit Protector - Low K — Electronic with LCD, LSI and GF alarm only, 3P/4W
instantaneous range (LG-frame) (selectable residual or return type ground fault alarm)
M — Magnetic Only, Motor Circuit Protector - Standard R — Electronic LI or 3P (neutral protected)
instantaneous range T — Electronic LSI or 3P (neutral protected)
Y — Magnetic Only, Motor Circuit Protector - Standard V — Electronic, LSIG or 3P/4W, residual ground fault protection
instantaneous range (LG-frame) W— Electronic, LIG or 3P/4W, residual ground fault protection
H — Magnetic Only, Motor Circuit Protector - High
instantaneous range
Continuous Current Rating
For DG use 050, 060, 070, 080, 090, 100, 110, 125, 150
For FG use 100, 110, 125, 150, 175, 200, 225, 250
7
For JG use 250, 300, 350, 400
For LG use 400, 500, 600
For MG use 600, 700, 800
CIRCUIT BREAKERS
MOLDED CASE
For NG use 800, 900, 100 (1000A), 120 (1200A)
For PG use 120 (1200A), 140 (1400A), 160 (1600A)
Terminations
B — Load End Standard (cu/al) Lugs
L — Line & Load Standard (cu/al) Lugs
X — No Lugs (use only if accessory suffixes are to follow)
Accessories
Auxiliary and Alarm Switch Combinations
Suffix Description
A1 — 1 Alarm (includes 1NO & 1NC switch with a 2 Aux./1 Alarm Base, for frames DG to LG) Note: A1 and A3 include 1NO and 1NC switch for
A2 — 2 Aux (1NO & 1NC switch with a 3 Aux. Base, for frames DG to LG) alarm purposes, only one of these switches may
A3 — 2 Aux + 1 Alarm (2NO & 2NC switches with a 2 Aux./1 Alarm Base, for frames DG to LG) be used as there is only one space for an alarm.
A3 — 2 Aux + 2 Alarm (2NO & 2NC switches with a 2 Aux./2 Alarm Base, for frames MG to PG)
A4 — 4 Aux (2NO & 2NC switches with a 4 Aux. Base, for frames MG to PG)
Shunt Trips
RB — 24 VDC RM — 48-60 VAC
RC — 48-60 VDC RN — 110-127 VAC
RD — 110-127 VDC RS — 208-277 VAC LCD = Liquid Crystal Display
RE — 250 VDC RV — 380-600 VAC LI = Long Delay & Instantaneous trip functions
LSI = Long Delay, Short Delay, & Instantaneous trip functions
Under Voltage Releases LSIG = Long Delay, Short Delay, Instantaneous, & Ground Fault trip functions
UA — 12 VDC UN — 110-127 VAC GF = Ground Fault
UB — 24 VDC UP — 208 VAC 3P = 3-pole
UC — 48 VDC UR — 220-250 VAC 4W = 4-wire
UD — 110-127 VDC US — 277 VAC
UE — 220-250 VDC UT — 380-415 VAC
UG — 60 VDC UU — 440-480 VAC
UK — 24 VAC
Select Frames
If ordering factory-installed accessories or special modifications, you must order a 15-digit catalog number. See the examples
below for a detailed explanation. The 15 digit number is achieved by placing X’s in positions not being occupied by an
accessory/modification. Contact Siemens for circuit breakers configured with accessories.
HFG3B200L A2 XXXX
Standard 9-digit Aux. Switch Completes Cat #
HFG3B200L XX UN XX
Standard 9-digit UVR
Completes Cat #
HFG3B200L A2 RN XX
Standard 9-digit Aux. Shunt Completes
Switch Trip Cat #
HFX3B200L
Standard 9-digit
7 MOLDED CASE
CIRCUIT BREAKERS
Frame Family DG FG JG
7
600Vac 18 18 25
240Vac 100/75 100/75 100/75
IEC 415Vac 70/70 70/70 70/70
CIRCUIT BREAKERS
MOLDED CASE
(lCU /lCS)
690Vac 12/6 12/6 15/8
DC Voltages – Interrupting Rating (kA)d
250Vdc - 2p 30 30 30
500Vdc - 3pc 18 25 35
600Vdc - 3p 42 42 65
Type L – Very High Interrupting Ratinga, RMS Symmetrical Amperes (kA)
240Vac 200 200 200
UL 480Vac 100 100 100
600Vac 18 18 25
240Vac 200/150 200/150 200/150
IEC 415Vac 100/75 100/75 100/75
(lCU /lCS)
690Vac 12/6 12/6 15/8
DC Voltages – Interrupting Rating (kA)d
250Vdc - 2p 30 30 30
500Vdc - 3pc 18 30 35
Continuous Ampere Range 150 to 600A 200 to 800A 300 to 1200A 400 to 1600A
Number of Poles 2, 3 2, 3 2, 3 3
Maximum Voltage Rating 600V 600V 600V 600V
Type of Protection
Thermal-Magnetic u u u u
Electronic u u u u
Electronic with LCD u u u u
Motor Circuit Protector u u u —
Molded Case Switch u u u u
100% Rated 400/500 Amp u u u
Interchangeable Trip Unit — u u u
W In.(mm) 5.5 (139) 7.5 (190) 9 (229)
H 11 (279) 16 (406) 16 (406)
D 4.2 (102) 4.7 (114) 6.2 (157)
D1 5.4 (138) 5.9 (151) 8.1 (207)
Type N – Normal Interrupting Ratinga, RMS Symmetrical Amperes (kA)
240Vac 65 65 65 65
UL 480Vac 35 35 35 35
600Vac 18 25 25 25
240Vac 65/65 65/65 65/65 65/65
IEC 415Vac 45/45 50/50 50/25 50/25
(lCU /lCS)
690Vac 12/6 20/10 20/10 20/10
DC Voltages – Interrupting Rating (kA)d
250Vdc - 2p 30 22 22 22
500Vdc - 3pc 25 35 35 35
Type H – High Interrupting Ratinga, RMS Symmetrical Amperes (kA)
240Vac 100 100 100 100
UL 480Vac 65 65 65 65
7
600Vac 18 35 35 35
240Vac 100/75 100/75 100/75 100/50
IEC 415Vac 70/70 70/70 70/35 70/35
MOLDED CASE
CIRCUIT BREAKERS
(lCU /lCS)
690Vac 15/8 30/15 30/15 30/15
DC Voltages – Interrupting Rating (kA)d
250Vdc - 2p 30 25 25 25
500Vdc - 3pc 35 50 50 50
600Vdc - 3pe 65 65 65 65
Type L – Very High Interrupting Ratinga, RMS Symmetrical Amperes (kA)
240Vac 200 200 200 200
UL 480Vac 100 100 100 100
600Vac 18 50 65 65
240Vac 200/150 200/150 200/150 200/150
IEC 415Vac 100/75 100/75 100/75 100/75
(lCU /lCS)
690Vac 15/8 35/17 35/17 35/17
DC Voltages – Interrupting Rating (kA)d
250Vdc - 2p 30 42 42 42
500Vdc - 3pc 35 65 65 65
The interchangeability of the VL circuit mation menus. With precise control factory for each frame and do not
breaker trip units allow for easy conver- over the circuit beaker functions and overlap with the settings on the other
sion from any of 3 types of protection. access to system status, diagnostics, frames. Therefore, when VL breakers
They are thermal-magnetic, electronic, and information, these trip units allow are used together in a system the GF
or electronic with a built-in LCD. The for unsurpassed flexibility in circuit protection is automatically coordinated.
thermal-magnetic trip unit features an coordination. The user also has the ability to program
adjustable magnetic trip setting. The a custom coordination scheme with
electronic trip units are microprocessor An example of coordination is the out adjustable settings on both the 555 and
based true RMS sensing devices and of the box Ground Fault function on the 586 trip units.
are available with a variety of adjustable Model 555 trip units. The pick-up and
trip settings, configurations, and infor- time delay settings are set at the
VL Trip Units
Trip Unit Functions Model 525 Model 555 Model 586
Electronic Electronic Electronic
Thermal- Electronic Electronic Electronic Electronic with LCD with LCD with LCD
magnetic LI LIG LSI LSIG LSI LSIG LSI + G alarm only
Continuous Current Setting (Ir) Fixed u u u u u u u
Long Time Delay (tr) h u u u u u u u
Instantaneous Function l l l l l (ON/OFF) (ON/OFF) (ON/OFF)
Instantaneous Pickup (Ii) u u u u u u u u
Short Time Function h h h l l (ON/OFF) (ON/OFF) (ON/OFF)
Short Time Pick-up (Isd) h h h u u u u u
Short Time Delay (tsd) h h h u u u u u
Ground Fault Pick-up (Ig) h h u h u h u h
Ground Fault Delay (tg) h h u h u h u h
Ground Fault Alarm Pick-up h h h h h h u u
Ground Fault Alarm Delay h h h h h h u u
Alarm & Status Indicator h l l l l l l l
Built-in Display (LCD) h h h h h l l l
Pre-Trip Alarma h l l l l l l l
Last Trip Information h la la la la l l l
Zone Selectivea h l l l l l l l
Communicationsa h l l l l l l l
u Adjustable setting
7
l This feature is included
h Feature is not included.
CIRCUIT BREAKERS
MOLDED CASE
a Requires a COMPRO20 or COMMOD21 module in a communication system.
Continuous Amps Rating (Ir) override function to ensure self protec- Ground Fault Pick-Up (Ig)
This setting is the continuous current tion of circuit breaker. This setting controls the level of ground
that the breaker will carry without trip- fault current that will cause the breaker
ping. It can be set up to 100% of the trip Short Time Pick-Up (lsd) to trip. Model 555 Electronic Trip Units
unit’s nominal rating (In). This function controls the level of fault act on the residual current to sense
current the breaker will carry for a short ground current. The Model 586
Long Time Delay (tr) time without tripping, thus allowing Electronic Trip Unit is programmable
Sometimes referred to as the “overload” downstream devices to clear short cir- and allows the user to select either
position, this function controls the break- cuits ahead of up-stream protection. the residual current method or direct
er‘s “pause-in-tripping” time. It allows It may be defeated (turned-off) on detection (via a separate current trans-
low level, temporary inrush currents Model 586 trip units. former) to detect ground current.
such as those encountered when start-
ing a motor to pass without tripping. The Short Time Delay (tsd) Ground Fault Time Delay (tg)
time delay begins when the current This controls the interval of time the
This controls the interval of time the
reaches 6 x Ir. breaker will remain closed after a ground
breaker will remain closed against a fault
(at the Short Time Pick-up current level) fault is detected (at the Ground Fault
Instantaneous Pick-up (Ii) without tripping. The time delay may be Pick-up current level) without tripping.
This function sets the breaker to trip set at fixed points or at short time inter-
instantaneously during high fault condi- vals based on l2t curves. This function is
tions. This function may be turned off on used with the Short Time Pick-up to
Model 586 trip units. Turning this func- achieve selectivity and better system
tion off will enable an instantaneous trip coordination.
Thermal-Magnetic trip units, Model 525, combine the inverse time element design for low level overloads, and instantaneous
magnetic action for short circuit protection. The standard unit has preset overload protection and an adjustable instantaneous trip
setting, with 6 set points. Thermal-Magnetic trip units are available throughout the VL family, from 50 to 1600A.
Ordering Information
Complete Assembled Breaker
A complete factory assembled DG breaker includes the frame, trip unit, and
standard line and load connectors, all factory installed and shipped as a com-
plete breaker. Assembled breakers are only available with standard
connectors.
For DC applications, use thermal magnetic trip unit only.
Breakers are suitable for reverse feed applications.
For special applications, refer to page 7-212.
Mounting hardware is included with each frame or complete breaker.
For 100% rated breakers with a non-interchangeable trip unit, change the 3rd
character of the catalog number to “W”. Available in electronic and electronic
with LCD only.
HACR rated.
Interrupting Ratings
RMS Symmetrical Amperes (KA)
UL 489 IEC 60947-2
Volts AC (50/60 Hz) Volts DC Volts AC (50/60 Hz) Dimensions, inches (mm)
Interrupting Breaker 600Y 220/240 380/415 690 Number To Handle
Class Type 240 480 /347 250 500 ICU ICS ICU ICS ICU ICS of Poles Width Length Depth D1
N NDGB 65 35 18 30 18 65 65 40 40 12 6 2, 3 4.1 (105) 6.9 (175) 3.4 (81) 4.2(107)
H HDGB 100 65 18 30 18 100 75 70 70 12 6
L LDGB 200 100 18 30 18 200 150 100 75 12 6
7
Copper 30-150 #6–3/0 Cu 1 3TC1DG30b
Distribution Lugs
CIRCUIT BREAKERS
MOLDED CASE
30-150 #14–#2 Al/Cu (3pcs. Max) 3 3TA3DG02b
30-150 #14–#4 Cu, #14–#6 Al 6 3TA6DG04b
Compression Lugs
30-150 #14–2/0 kcmil Al/Cu – 2CLD20c
30-150 #14–2/0 kcmil Al/Cu – 3CLD20b
a Standard connector supplied with complete breakers.
b Kit consists of 3 terminal connectors.
c 2 Lugs for 2-pole breakers.
d Required for 100% rated DG breakers. Requires 90°C Cu cable sized at 75°C ampacity
DG Thermal-Magnetic, Instantaneous
Trip Adjustment Range
Instantaneous
Trip Unit Continuous Overcurrent Setting (Ii)
Amp Rating (In) Min. Max.
50 450 600
60 450 600
70 450 700
80 450 800
90 500 1000
100 500 1000
110 550 1100
125 625 1250
150 800 1600
Note: Each breaker has 6 trip settings in this range. External Accessories pages 7-195 through 7-207
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-165
VL Circuit Breakers
DG 150A Thermal-Magnetic Trip Unit Selection
AMPS I n =150A
1120 1280 40? C
TM ~
960 1440
7-166 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
VL Circuit Breakers
DG 150A Electronic Trip Units Selection
7
CIRCUIT BREAKERS
MOLDED CASE
Model 586 Trip Unit
DG 150A Frame 3-Pole Electronic LCD Trip Unit a
COMPLETE FACTORY ASSEMBLED CIRCUIT BREAKER
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-167
VL Circuit Breakers
Internal Accessories for DG 150A and FG 250A Frames Selection
Shunt Trips
Description Mounting Pocket Catalog Number
24 VDC STRLB24DC
48-60 VDC STRLC60DC
110-127 VDC STRLD125DC
220-250 VDC Right Pocket Only STRLE250DC
48-60 VAC STRLM60
110-127 VAC STRLN120
208-277 VAC STRLS277
380-600 VAC
7
STRLV600
Undervoltage Release
MOLDED CASE
CIRCUIT BREAKERS
a efer to the “Accessory Locations” chart on page 7-208 for guidelines and limitations about which pockets may be used for
R
accessory combinations.
b These kits include two bases, one for mounting switches in the left pocket and another for mounting in the right.
c Includes 1A and 1B contact for alarm purposes, only one of which may be installed at any time.
‘A’ refers to a normally open contact (open when the breaker contacts are open). External Accessories pages 7-195 through 7-207
‘B’ refers to a normally closed contact (closed when the breaker contacts are open).
7-168 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
VL Circuit Breakers
FG 250A Frame, VL Series Selection/Dimensions
Ordering Information
Complete Assembled Breaker
A complete factory assembled FG breaker includes the frame, trip unit,
and standard line and load connectors, all factory installed and shipped as
a complete breaker. Assembled breakers are available only with standard
connectors.
For DC applications, use thermal magnetic trip unit only.
Breakers are suitable for reverse feed applications.
For special applications, refer to page 7-212.
Mounting hardware is included with each frame or complete breaker.
HACR rated.
7
Kitconsists of 3 terminal connectors.
2 Lugs for 2-pole breakers.
3 Lugs for 3-pole breakers.
CIRCUIT BREAKERS
MOLDED CASE
FG Thermal-Magnetic,
Instantaneous Trip
Adjustment Range
Instantaneous
Trip Unit Continuous Overcurrent Setting (Ii)
Amp Rating (In) Min. Max.
100 625 1250
110 800 1600
125 800 1600
150 800 1600
175 1000 2000
200 1000 2000
225 1250 2500
250 1250 2500
Note: Each breaker has 6 trip settings in this range.
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-169
VL Circuit Breakers
FG 250A Thermal-Magnetic Trip Unit Selection
AMPS I n =250A
1750 2000 40? C
TM ~
1500 2250
225
250 NFK3B250L HFK3B250L LFK3B250L
0
7-170 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
VL Circuit Breakers
FG 250A Electronic Trip Units Selection
7
CIRCUIT BREAKERS
MOLDED CASE
Model 586 Trip Unit
FG 250A Frame 3-Pole Electronic LCD Trip Unita
COMPLETE FACTORY ASSEMBLED CIRCUIT BREAKER
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-171
VL Circuit Breakers
Internal Accessories for DG 150A and FG 250A Frames Selection
Shunt Trips
Description Mounting Pocket Catalog Number
24 VDC STRLB24DC
48-60 VDC STRLC60DC
110-127 VDC STRLD125DC
220-250 VDC Right Pocket Only STRLE250DC
48-60 VAC STRLM60
110-127 VAC STRLN120
208-277 VAC STRLS277
7
Undervoltage Release
Description Mounting Pocket Catalog Number
12 VDC UVRLA12DC
24 VDC UVRLB24DC
48 VDC UVRLC48DC UVRLN120
60 VDC UVRLG60DC
110-127 VDC UVRLD125DC
220-250 VDC UVRLE250DC
24 VAC Right Pocket Only UVRLL24
110-127 VAC UVRLN120
220-240 VAC UVRLR240
208 VAC UVRLP208
277 VAC UVRLS277
380-415 VAC UVRLT415
440-480 VAC UVRLU480
a Refer to the “Accessory Locations” chart on page 7-208 for guidelines and limitations about which pockets may be
used for accessory combinations.
b These kits include two bases, one for mounting switches in the left pocket and another for mounting in the right.
c Includes 1A and 1B contact for alarm purposes, only one of which may be installed at any time.
‘A’ refers to a normally open contact (open when the breaker contacts are open). External Accessories pages 7-195 through 7-207
‘B’ refers to a normally closed contact (closed when the breaker contacts are open).
7-172 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
VL Circuit Breakers
JG 400A Frame, VL Series Selection/Dimensions
Ordering Information
Complete Assembled Breaker
A complete factory assembled JG breaker includes the frame, trip unit,
and standard line and load connectors, all factory installed and shipped
as a complete breaker. Assembled breakers are available only with
standard connectors.
For any other configuration, order the frame, trip unit, and terminals as
separate items.
For DC applications, use thermal magnetic trip unit only.
For reverse feed applications, select non-interchangeable trip breakers only.
For non-interchangeable trip breakers, change the third digit of the catalog
number to “X” for standard breakers.
For 100% rated breakers with a non-interchangeable trip unit, change the 3rd
character of the catalog number to ”Y“ (3-pole only).
For special applications, refer to page 7-212.
Mounting hardware is included with each frame or complete breaker. Dimensions, inches (mm)
HACR rated. Number To Handle
of Poles Width Length Depth D1
7
Aluminum 70-400 3/0–250 kcmil Al/Cu 2 3TA2JG250ab
Aluminum 70-400 250–750 kcmil Al 1 3TA1JG750b
Aluminum 70-400 3/0–600 kcmil Cu 1 3TA1JG750b
CIRCUIT BREAKERS
MOLDED CASE
Copper 70-400 3/0–600 kcmil Cu 1 TC1JG750
Copper 70-400 3/0–250 kcmil Cu 2 TC2JG250
Distribution Lugs
70-400 #14–4 Cu 12 3TA12JG04b
70-400 #14–2/0 Al/Cu 6 3TA6JG20b
Compression Lugs
70-400 #6–350 kcmil — 3CLJ350b
70-400 250-600 kcmil — 3CLJ600b
a Standard construction supplied for each breaker.
b Kit consists of 3 terminal connectors.
c Required for 100% rated JG breakers. Requires 90°C Cu
cable sized at 75°C ampacity.
JG Thermal-Magnetic,
Instantaneous
Trip Adjustment Range
Instantaneous
Trip Unit Continuous Overcurrent Setting (Ii)
Amp Rating (In) Min. Max.
250 1250 2500
300 1500 3000
350 1750 3500
400 2000 4000
External Accessories pages 7-195 through 7-207
Note: Each breaker has 6 trip settings in this range.
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-173
VL Circuit Breakers
JG 400A Thermal-Magnetic Trip Unit Selection
N-Interrupting Class
7-174 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
VL Circuit Breakers
JG 400A Electronic Trip Units Selection
7
CIRCUIT BREAKERS
MOLDED CASE
Model 586 Trip Unit
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-175
VL Circuit Breakers
Internal Accessories for JG 400A and LG 600A Frames Selection
Shunt Trips
Description Mounting Pocket Catalog Number
24 VDC STRLB24DC
48-60 VDC STRLC60DC
110-127 VDC STRLD125DC
220-250 VDC Right Pocket Only STRLE250DC
48-60 VAC STRLM60
110-127 VAC STRLN120
208-277 VAC STRLS277
380-600 VAC STRLV600
7
Undervoltage Release
MOLDED CASE
CIRCUIT BREAKERS
a Refer to the “Accessory Locations” chart on page 7-208 for guidelines and limitations about which
pockets may be used for accessory combinations.
b Includes 1A and 1B contact for alarm purposes, only one of which may be installed at any time.
‘A’ refers to a normally open contact (open when the breaker contacts are open).
‘B’ refers to a normally closed contact (closed when the breaker contacts are open). External Accessories pages 7-195 through 7-207
7-176 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
VL Circuit Breakers
LG 600A Frame, VL Series Selection/Dimensions
Ordering Information
Complete Assembled Breaker
A complete factory assembled LG breaker includes the frame, trip unit, and
standard line and load lugs, all factory installed and shipped as a complete
breaker. Assembled breakers are available only with standard connectors.
For DC applications, use thermal magnetic trip unit only.
Breakers are suitable for reverse feed applications.
For special applications, refer to page 7-212.
Mounting hardware is included with each breaker.
For 100% rated breakers, change the 3rd character of the catalog number to
“W”. Available on 400/500 Amp only (3-pole only).
HACR rated.
Interrupting Ratings
RMS Symmetrical Amperes (KA) Dimensions, inches (mm)
UL 489 IEC 60947-2 Number To Handle
Volts AC (50/60 Hz) Volts DC Volts AC (50/60 Hz) of Poles Width Length Depth D1
Interrupting Breaker 220/240 380/415 690
2, 3 5.5 (139) 11 (279) 4.2 (102) 5.4 (138)
Class Type 240 480 600 250 500 ICU ICS ICU ICS ICU ICS
Ext. 13.6
N NLGB 65 35 18 30 25 65 65 45 45 12 6
Shield (345.5)
H HLGB 100 65 18 30 35 100 75 70 70 15 8
L LLGB 200 100 18 30 35 200 150 100 75 15 8
Special 600Vac 25kA thermal-magnetic version (Type HLGC) available, see page 7-178.
7
150-600 250-600 kcmil Al/Cu — 6CLL600
Standard construction supplied for each breaker.
CIRCUIT BREAKERS
MOLDED CASE
Kit consists of 3 terminal connectors.
Kit consists of 6 lugs for Line or Load end.
Required for 100% rated LG breakers. Requires 90°C Cu cable sized at 75°C ampacity.
LG Thermal-Magnetic,
Instantaneous
Trip Adjustment Range
Instantaneous
Trip Unit Continuous Overcurrent Setting (Ii)
Amp Rating (In) Min. Max.
400 2000 4000
500 2500 5000
600 2750 5500
Note: Each breaker has 6 trip settings.
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-177
VL Circuit Breakers
LG 600A Thermal-Magnetic Trip Unit Selection
Type HLGC 600A Frame 2-Pole with Thermal-Magnetic Trip Unit , 600Vac 25kA only
N-Interrupting Class H-Interrupting Class L-Interrupting Class
7
400 — HLV2B400L —
500 — HLV2B500L —
600 — HLV2B600L —
Type HLGC 600A Frame 3-Pole with Thermal-Magnetic Trip Unit , 600Vac 25kA only
N-Interrupting Class H-Interrupting Class L-Interrupting Class
For
100% rated 400A or 500A versions, change the third Consult sales office for availability.
character of the catalog number to “Z”.
7-178 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
VL Circuit Breakers
LG 600A Electronic Trip Units Selection
7
CIRCUIT BREAKERS
MOLDED CASE
Model 586 Trip Unit
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-179
VL Circuit Breakers
Internal Accessories for JG 400A and LG 600A Frames Selection
Shunt Trips
Description Mounting Pocket Catalog Number
24 VDC STRLB24DC
48-60 VDC STRLC60DC
110-127 VDC STRLD125DC
220-250 VDC Right Pocket Only STRLE250DC
48-60 VAC STRLM60
110-127 VAC STRLN120
208-277 VAC STRLS277
380-600 VAC STRLV600
7
Undervoltage Release
MOLDED CASE
CIRCUIT BREAKERS
a efer to the “Accessory Locations” chart on page 7-208 for guidelines and limitations about which pock-
R
ets may be used for accessory combinations.
b Includes 1A and 1B contact for alarm purposes, only one of which may be installed at any time.
‘A’ refers to a normally open contact (open when the breaker contacts are open).
‘B’ refers to a normally closed contact (closed when the breaker contacts are open). External Accessories pages 7-195 through 7-207
7-180 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
VL Circuit Breakers
MG 800A Frame, VL Series Selection/Dimensions
Ordering Information
Complete Assembled Breaker
A complete factory assembled MG breaker includes the frame, trip unit, and
standard line and load lugs, all factory installed and shipped as a complete
breaker. Assembled breakers are available only with standard
connectors.
For any other configuration, order the frame, trip unit, and terminals as
separate items.
For DC applications, use thermal magnetic trip unit only.
For reverse feed applications, select non-interchangeable trip breakers only. For
non-interchangeable trip breakers, change the third digit of the catalog number
to “X” for standard breakers.
For 100% rated breakers with a non-interchangeable trip unit, change the 3rd
character of the catalog number to ”Y“.
For special applications, refer to page 7-212.
Mounting hardware is included with each frame or complete breaker. Dimensions, inches (mm)
HACR rated. Number To Handle
of Poles Width Length Depth D1
7
Copper 200-800A 1/0–500 kcmil Cu 3 TC3MG500e
Aluminum 200-800A #2–600 kcmil Al/Cu 3 3TA3MG600bd
CIRCUIT BREAKERS
MOLDED CASE
a Standard connector supplied with complete breakers.
b Kit consists of 3 terminal connectors.
c Consists of one terminal.
d Includes extended terminal cover.
e Required for 100% rated MG breakers. Requires 90°C Cu cable sized at 75°C ampacity.
MG Thermal-Magnetic,
Instantaneous
Trip Adjustment Range
Instantaneous
Trip Unit Continuous Overcurrent Setting (Ii)
Amp Rating (In) Min. Max.
600 3000 6000
700 3250 6500
800 3250 6500
Note: Each breaker has 6 trip settings.
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-181
VL Circuit Breakers
MG 800A Thermal-Magnetic Trip Unit Selection
7-182 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
VL Circuit Breakers
MG 800A Electronic Trip Units Selection
7
MG 800A Frame 3-Pole Electronic LCD Trip Unit
CIRCUIT BREAKERS
MOLDED CASE
N-Interrupting Class H-Interrupting Class L-Interrupting Class
Catalog Number Catalog Number Catalog Number Catalog Number
FRAME ONLY
Continuous NMG3F800 HMG3F800 LMG3F800
Ampere Rating COMPLETE FACTORY ASSEMBLED CIRCUIT BREAKER TRIP UNIT ONLY
LCD ELECTRONIC LSI TRIP
600 NMG3A600L HMG3A600L LMG3A600L CMT3A600
800 NMG3A800L HMG3A800L LMG3A800L CMT3A800
LCD ELECTRONIC LSIG TRIP
600 NMG3G600L HMG3G600L LMG3G600L CMT3G600
800 NMG3G800L HMG3G800L LMG3G800L CMT3G800
LCD ELECTRONIC LSI TRIP + GF ALARM ONLY
600 NMG3K600L HMG3K600L LMG3K600L CMT3K600
800 NMG3K800L HMG3K800L LMG3K800L CMT3K800
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-183
VL Circuit Breakers
Internal Accessories for MG 800A, NG 1200A and PG 1600A Frames Selection
Shunt Trips
Description Mounting Pocket Catalog Number
24 VDC STRPB24DC
48-60 VDC STRPC60DC
110-127 VDC STRPD125DC
220-250 VDC Right Pocket Only STRPE250DC
48-60 VAC STRPM60 AMBP2
110-127 VAC STRPN120
208-277 VAC STRPS277
380-600 VAC STRPV600
Undervoltage Release
Description Mounting Pocket Catalog Number
12 VDC UVRPA12DC
24 VDC
7
UVRPB24DC
48 VDC UVRPC48DC
60 VDC UVRPG60DC
MOLDED CASE
CIRCUIT BREAKERS
UVRPN120
7-184 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
VL Circuit Breakers
NG 1200A Frame, VL Series Selection/Dimensions
Ordering Information
Complete Assembled Breaker with Lugs
A complete factory assembled NG breaker includes the frame, trip unit,
and standard line and load lugs, all factory installed and shipped as a complete
breaker. Assembled breakers are available only with standard connectors.
For any other configuration, order the frame, trip unit, and terminals as
separate items.
For DC applications, use thermal magnetic trip unit only.
For reverse feed applications, select non-interchangeable trip breakers only. For
non-interchangeable trip breakers, change the third digit of the catalog number
to “X” for standard breakers.
For 100% rated breakers with a non-interchangeable trip unit, change the 3rd
character of the catalog number to ”Y“.
For special applications, refer to page 7-212.
Mounting hardware is included with each frame or complete breaker.
A Toggle Handle Extension is included with each frame or complete breaker. Dimensions, inches (mm)
HACR rated. Number To Handle
of Poles W L D D1
2, 3 9 (229) 16 (406) 6 (152) 8.1 (207)
Interrupting Ratings
RMS Symmetrical Amperes (KA)
UL 489 IEC 60947-2 Shipping Weight, lbs. (kg)
Volts AC (50/60 Hz) Volts DC Volts AC (50/60 Hz)
Complete
Interrupting Breaker 220/240 380/415 690 Poles Frame Trip Unit Breaker
Class Type 240 480 600 250 500 ICU ICS ICU ICS ICU ICS 2, 3 46.3 (21.0) 8.8 (4.0) 55.1 (25.0)
N NNG 65 35 25 22 35 65 35 50 25 20 10
H HNG 100 65 35 25 50 100 50 70 35 30 15
L LNG 200 100 65 42 65 200 100 100 50 35 17
7
Aluminum 300-1200A 500-750 kcmil Al/Cu 3 3TA3NG750d
Copper 300-1200A 1/0–500 kcmil Cu 4 3TC4NG500bd
Aluminum 300-1200A 1/0–500 kcmil Al/Cu 4 3TA4NG500Hbd
CIRCUIT BREAKERS
MOLDED CASE
Compression Lugs
300-1200A 1/0-500 kcmil Al/Cu — 12CLN500
a Total of 12 connectors (4 per phase Line or Load).
b For 100% rated NG breakers. Requires 90°C Cu cable sized at 75°C ampacity.
c Standard connector provided with complete breakers.
d Kit consists of 3 terminal connectors.
NG Thermal-Magnetic,
Instantaneous
Trip Adjustment Range
Instantaneous
Trip Unit Continuous Overcurrent Setting (Ii)
Amp Rating (In) Min. Max.
800 4000 8000
900 5000 10000
1000 5000 10000
1200 7000 12000
Note: Each breaker has 6 trip settings.
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-185
VL Circuit Breakers
NG 1200A Thermal-Magnetic Trip Unit Selection
Ii I n = 1200A Ii Ii
AMPS AMPS AMPS
40 C
9000 10000 9000 10000 9000 10000
8000
TM ~ 8000 8000
11000 11000 11000
7-186 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
VL Circuit Breakers
NG 1200A Electronic Trip Units Selection
7
CIRCUIT BREAKERS
MOLDED CASE
Model 586 Trip Unit
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-187
VL Circuit Breakers
Internal Accessories for MG 800A, NG 1200A, and PG 1600A Frames Selection
Shunt Trips
Description Mounting Pocket Catalog Number
24 VDC STRPB24DC
48-60 VDC STRPC60DC
110-127 VDC STRPD125DC
220-250 VDC Right Pocket Only STRPE250DC
48-60 VAC STRPM60
AMBP2
110-127 VAC STRPN120
208-277 VAC STRPS277
380-600 VAC STRPV600
Undervoltage Release
Description Mounting Pocket Catalog Number
12 VDC UVRPA12DC
7
24 VDC UVRPB24DC
48 VDC UVRPC48DC
MOLDED CASE
CIRCUIT BREAKERS
60 VDC UVRPG60DC
110-127 VDC UVRPD125DC
220-250 VDC UVRPE250DC
110-127 VAC Right Pocket Only UVRPN120
220-240 VAC UVRPR240
208 VAC UVRPP208
277 VAC UVRPS277
380-415 VAC UVRPT415
440-480 VAC UVRPU480 STRPN120
a Refer to the “Accessory Locations” chart on page 7-208 for guidelines and limitations about which
pockets may be used for accessory combinations.
‘A’ refers to a normally open contact (open when the breaker contacts are open).
‘B’ refers to a normally closed contact (closed when the breaker contacts are open).
UVRPN120
7-188 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
VL Circuit Breakers
PG 1600A Frame, VL Series & Thermal-Magnetic Trip Unit Selection/Dimensions
Ordering Information
A complete factory assembled PG breaker includes the frame and trip unit only.
The connectors must be ordered as separate items.
PG thermal-magnetic breakers sold as non-interchangeable only.
For any other configuration, order the frame, trip unit, and connectors as
separate items.
Connectors require a Breaker Lug Mounting Assembly or Breaker Mounting
Base and must be ordered as a seperate item.
For DC applications, use Thermal magnetic trip unit only.
For reverse feed applications select non-interchangeable trip breakers only.
Change the third digit of the catalog number to “X” for non-interchangeable trip
breakers.
For 100% rated breakers with a non-interchangeable trip unit, change the 3rd
character of the catalog number to ”Y“.
For special applications, refer to page 7-212.
Mounting hardware is included with each frame or complete breaker. Dimensions, inches (mm)
A Toggle Handle Extension is included with each frame or complete breaker. Number To Handle
of Poles W L D D1
2, 3 9 (229) 16 (406) 6 (152) 8.1 (207)
Interrupting Ratings
RMS Symmetrical Amperes (KA)
UL 489 IEC 60947-2 (ETU only) Shipping Weight, lbs. (kg)
Volts AC (50/60 Hz) Volts DC Volts AC (50/60 Hz) Complete
220/240 380/415 690 Poles Frame Trip Unit Breaker
Interrupting Breaker
Class Type 240 480 600 250 500 ICU ICS ICU ICS ICU ICS 2, 3 60.2 (27.3) 8.8 (4.0) 69.0 (31.3)
N NPG 65 35 25 22 35 65 35 50 25 20 10
H HPG 100 65 35 25 50 100 50 70 35 30 15
L LPG 200 100 65 42 65 200 100 100 50 35 17 PG Thermal-Magnetic,
Instantaneous
Connectors for 75°C Wire Trip Adjustment Range
Ampere Wire No. of cables Instantaneous
Construction Rating Range per phase Catalog Number Trip Unit Continuous Overcurrent Setting (Ii)
Amp Rating (In) Min. Max.
7
Aluminum 1200-1600A 1/0–750 kcmil Al/Cu 6 3TA6PG750ac
Aluminum 1200-1600A 300–600 kcmil Al/Cu 5 TA5P600bd 1200 7000 12000
Aluminum 1200-1600A 600–750 kcmil Al/Cu 4 TA4P750bd
1400 7000 12000
CIRCUIT BREAKERS
MOLDED CASE
Aluminum 1200-1600A 300–600 kcmil Al/Cu 6 TA6R600bd
Copper 1200-1600A 300–600 kcmil Cu 5 TC5R600bde 1600 7000 12000
Note: Each breaker has 6 trip settings in this range.
Mounting Arrangement
Ii I n = 1600A Ii Ii
10000
40º C
9000
AMPS
10000 9000
AMPS
10000
TM ~
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-189
VL Circuit Breakers
PG 1600A Electronic Trip Units Selection
N-Interrupting Class H-Interrupting Class L-Interrupting Class
MOLDED CASE
CIRCUIT BREAKERS
Catalog Number Catalog Number Catalog Number Catalog Number
FRAME ONLY
Continuous NPG3F160 HPG3F160 LPG3F160
Ampere Rating COMPLETE FACTORY ASSEMBLED CIRCUIT BREAKER TRIP UNIT ONLY
LCD ELECTRONIC LSI TRIP
1200 NPG3A120 HPG3A120 LPG3A120 CPT3A120
1600 NPG3A160 HPG3A160 LPG3A160 CPT3A160
LCD ELECTRONIC LSIG TRIP
1200 NPG3G120 HPG3G120 LPG3G120 CPT3G120
1600 NPG3G160 HPG3G160 LPG3G160 CPT3G160
LCD ELECTRONIC LSI TRIP + GF ALARM ONLY
1200 NPG3K120 HPG3K120 LPG3K120 CPT3K120
1600 NPG3K160 HPG3K160 LPG3K160 CPT3K160
7-190 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
VL Circuit Breakers
Internal Accessories for MG 800A, NG 1200A, and PG 1600A Frames Selection
Shunt Trips
Description Mounting Pocket Catalog Number
24 VDC STRPB24DC
48-60 VDC STRPC60DC
110-127 VDC STRPD125DC
220-250 VDC Right Pocket Only STRPE250DC
AMBP2
48-60 VAC STRPM60
110-127 VAC STRPN120
208-277 VAC STRPS277
380-600 VAC STRPV600
Undervoltage Release
Description Mounting Pocket Catalog Number
7
12 VDC UVRPA12DC
24 VDC UVRPB24DC
CIRCUIT BREAKERS
MOLDED CASE
48 VDC UVRPC48DC
60 VDC UVRPG60DC
110-127 VDC UVRPD125DC
220-250 VDC UVRPE250DC
110-127 VAC Right Pocket Only UVRPN120
220-240 VAC UVRPR240
208 VAC UVRPP208
277 VAC UVRPS277
380-415 VAC UVRPT415 STRPN120
440-480 VAC UVRPU480
a Refer to the “Accessory Locations” chart on page 7-208 for guidelines and limitations about which
pockets may be used for accessory combinations.
‘A’ refers to a normally open contact (open when the breaker contacts are open).
‘B’ refers to a normally closed contact (closed when the breaker contacts are open).
UVRPN120
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-191
VL Circuit Breakers
Molded Case Switch Selection
General switch has a fixed instantaneous self- the molded case switch. Also, the
Typically a molded case switch is used protecting trip element which may short-circuit current rating of the
when a compact load-break switch is open the switch under high fault condi- switch is limited to the interrupting rat-
needed for disconnect purposes. The tions. ing of the upstream protective device
VL line of molded case switches from or the ratings in the table below,
Application Note whichever is less.
Siemens is made of the same materi-
als and components as the VL circuit Overcurrent protection must be provid-
breakers but do not provide overcur- ed by an appropriate overcurrent pro-
rent protection. Each molded case tective device located upstream from
Ordering Information
Each type VL molded case switch accepts the same terminals and accessories as the equivalent VL circuit breakers.
All type VL molded case switches are suitable for reverse feed applications.
Mounting hardware and standard line and load terminals are included on ratings through 250A. For 400 – 1600A ratings,
order the lugs separately.
All ratings are UL listed and CSA certified.
7-192 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
VL Circuit Breakers
Motor Circuit Protectors Selection
General
Protection of Motor Circuits
Molded case circuit breakers are used in motor circuits as a disconnecting means and for short-circuit protection. They should be
used in conjunction with motor-running, over-current protection devices, and should permit the motor to start without nuisance trip-
ping from motor-inrush current. The circuit breaker should have a continuous current rating of not less than 115% of the motor full-
load current.
The recommended motor circuit protectors listed have continuous-current ratings of at least 115% of motor full-load currents. The
trip setting positions are approximately 11 times motor full-load current. The suggested trip settings may need to be adjusted
upward to no higher than 1300% of full-load current for non-design E type motors, and no greater than 1700% of full-load current
for design E motors, to allow for motor startup due to in-rush current.
Important: The information below does not apply to all motor applications: it is recommended that the user refer to the National
Electrical Code (NEC) for specific needs.
7
92-133 1200 246-356 3200
104-150 1350 277-400 3600
115-150b 1500 308-400b 4000
CIRCUIT BREAKERS
MOLDED CASE
96-139 1250 154-222 2000
115-150b 1500 185-267 2400
135-150b 1750 HDP3H150L 215-311 2800 HLM3J600
135-150b 2000 246-356 3200
135-150b 2250 277-400 3600
135-150b 2500 308-444 4000
46-67 600 212-306 2750
55-80 720 254-367 3300
65-93 840 HFP3L250L 296-428 3850 HLM3Y600
74-107 960 338-489 4400
83-120 1080 381-550 4950
92-133 1200 423-600 5500
77-111 1000 250-361 3250
92-133 1200 292-422 3800
108-156 1400 HFP3M250L 335-483 4350 HMM3M800
123-178 1600 385-556 5000
138-200 1800 442-638 5740
154-222 2000 500-722 6500
135-194 1750 385-556 5000
162-210 2100 462-667 6000
188-220 2450 HFP3H250L 538-778 7000 HNM3M120
215-241 2800 615-889 8000
242-250b 3150 692-1000 9000
242-250b 3500 769-1111 10,000
a M
otor circuit protectors rated 150A and 250A are supplied with line and load lugs b T
hese settings are provided for starting currents greater than 11X but not to exceed
installed. If lugs are required on 400A to 1200A motor circuit breakers, order required 17X. Full Load Amps ( FLA ) not to exceed ampere rating of MCP.
lugs separately.
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-193
Revised on 10/31/18
VL Circuit Breakers
600 Volt DC Circuit Breakers Selection
General the table. This family of circuit breakers interruption level, it is necessary to
Siemens UL Listed non-interchangeable is rated from 100 to 1600 Amperes. connect the terminals of the 3 pole
trip DC Thermal/magnetic Molded Case Types HFGD through HPGD circuit break- circuit breaker in a series configuration
Circuit Breakers shown below are for use ers are provided with an adjustable as shown in the diagram below.
in grounded & ungrounded general DC magnetic over-current function located Types HFGD through HPGD use the
circuits and ungrounded battery supply on the face of the circuit breaker. same internal and external accessories
circuits of UPS systems. These breakers Contact Siemens for specific magnetic as the standard FG through PG frames
are rated at 600Vdc closed circuit and over-current values. and associated types. Consult the
feature rated interruption levels from To properly use these UL Listed circuit individual frame section for accessory
42,000 to 65,000 amperes as indicated in breakers at 600Vdc and the indicated information.
Catalog Short-Circuit
Continuous Number Current Rating + –
Frame Type Ampere Rating (3-pole)a 600VDCb
100 HFC3B100 42K
150 HFC3B150 42K
FG HFGD 175 HFC3B175 42K
200 HFC3B200 42K
250 HFC3B250 42K
250 HJC3B250 65K
300 HJC3B300 65K
JG HJGD
350 HJC3B350 65K
LOAD
400 HJC3B400 65K
400 HLC3B400 65K
LG HLGD 500 HLC3B500 65K
600 HLC3B600 65K
600 HMC3B600 65K
MG HMGD 700 HMC3B700 65K
800 HMC3B800 65K
800 HNC3B800 65K
7
a T
erminal connectors must be ordered separately; see page 7-202.
b S
tandard VL breakers DG - PG feature DC ratings up to 500V for ungrounded UPS
applications. Consult the individual frame section for more information.
7
CIRCUIT BREAKERS
MOLDED CASE
1 Base for Plug-In or Draw-Out 9 Cover Frame for Door Cutout 17 Thermal Magnetic Trip Unit (525)
2 Interphase Barriers 10 Stored Energy Operator 18 Electronic Trip Unit (555)
3 Rear Terminals – Flat and Round 11 Rotary Handle Operator 19 Elec. Trip Unit with LCD (586)
4 Bus Extensions 12 Variable Depth Rotary Operator 20 Communication Module with ZSI
5 Terminal Connectors 13 Max Flex Operator 21 Electronic Trip Unit Tester and
6 Plug-In Terminal Blades 14 Circuit Breaker LCD Power Supply
7 Extended Terminal Shield 15 Shunt Trip or Undervoltage Releases
8 Standard Terminal Shield 16 Auxiliary/Alarm Switches
RHVM12H
a During manual operation, Early Break auxiliary switch contacts open before the breaker opens.
7-196 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
For MG Frame For NG to PG Frame
800 A 1200 to 1600 A
Description Catalog Number Catalog Number
Through-Door Rotary Handle Operator Kit
Fixed depth, breaker mounted.
For direct fitting to the circuit breaker.
Lockable with up to 3 padlocks.
NEMA 1, 12 — — — —
Red Handle version
with red knob, yellow indicator plate
NEMA 1, 12 — — — —
Door-Mounted Rotary Handle Operator Kit
Variable depth, door mounted handle.
Includes knob with masking frame,
indicator plate, detachable door coupling,
12” shaft, and breaker mounted rotary
operator. Lockable knob (for up to 3
padlocks).
NEMA 1, 12 RHVM12 — —
7
NFPA-79 Handle Kit
CIRCUIT BREAKERS
MOLDED CASE
Intermediate handle for NFPA-79 compliance
with door-mounted rotary operator RHVM79H RHVP79H
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-197
External Accessories
Operating Mechanisms
a Max-Flex™ handles are available with solid gray or black handles instead of the customary “Red for On” flange handle.
The black handle is preferred for IEC markets, where red handles have a specific meaning.
b During manual operation, Early Break aux. contacts open before the breaker opens.
7-198 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
For MG Frame For NG Frame For PG Frame
800 A 1200 A 1600 A
7
1 Aux. switch MFSPA1 MFSPA1 MFSPA1
2 Aux. switch MFSPA2 MFSPA2 MFSPA2
CIRCUIT BREAKERS
MOLDED CASE
a Max-Flex™ handles are available with solid gray or black handles instead of the customary “Red for On” flange handle.
The black handle is preferred for IEC markets, where red handles have a specific meaning.
b During manual operation, Early Break aux. contacts open before the breaker opens.
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-199
Revised on 11/30/19
External Accessories
Operating Mechanisms
For DG to FG Frame
150 to 250 A
Description Catalog Number
Stored Energy and Motor Operators
Lockable with up to 3 padlocks.
AC Voltage DC Voltage Stored Energy Type
— 24 SEAFB
42-48 42-48 SEAFM
60 60 SEAFY
110–127 110–127 SEAFN
220–250 220–250 SEAFR
Cylinder Locks for Field Installation CLKF
Connections
Terminal Shields
MOLDED CASE
CIRCUIT BREAKERS
Interphase Barriers
Set of 2 barriers IPBF IPBF
Also fits plug-in and draw-out bases.
Terminal Shields
Lug Mounting Assy. — —
IPBF
7-200 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
Revised on 11/30/19
For JG Frame For LG Frame For MG Frame For NG Frame For PG Frame
400 A 600 A 800 A 1200 A 1600 A
Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number
FBCJ3 FBCL3 FBCM3
— — — SSBP SSBP
SSBPH SSBPH
CIRCUIT BREAKERS
MOLDED CASE
TSSL3 — TSSM3 TSSP3 TSSP3
TSLL3 — TSLM3 TSLP3 TSLP3
— — — — LMAP1600b
— — — — MBPG1600
— — — — MBPG1601
a Not for use with standard Al terminals. Use Standard b Kit includes connection for one side of breaker only.
Shield for rear connection and Extended Shield for bus- Order quantity 2 if connecting line and load side.
bar connection.
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-201
External Accessories
Connections
TNKD3
Mechanical Lugs
Steel Wrap Around Body (Cu Wire Only)
Cable Size; (cables per phase) #8-1/0; 1-hole #4-350 kcmil; 1-hole
Single Lug TW1DG20 TW1FG350
Kit of 3 3TW1DG20 3TW1FG350
Aluminum Body (Al or Cu Wire)
Cable Size; (cables per phase) #6-3/0; 1-hole #4-350 kcmil; 1-hole
Single Lug TA1DG30 TAW1FG350
Kit of 2 — —
Kit of 3 3TA1DG30 3TAW1FG350
Single Lug — —
3TA4NG500
MOLDED CASE
CIRCUIT BREAKERS
Compression Lugs
Cable Size; (cables per phase) #14-2/0; 1-cable #4-350 kcmil; 1-cable
Kit of 2 2CLD20 —
Kit of 3 3CLD20 3CLF350
7-202 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
For JG Frame For LG Frame For MG Frame For NG Frame For PG Frame
400 A 600 A 800 A 1200 A 1600 A
Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number
1/0-600 kcmil; 1-hole — — — —
TW1JG600 — — — —
3TW1JG600 — — — —
3/0-250 kcmil; 2-hole #2-600 kcmil; 2-hole 1/0-500 kcmil, 3-hole 1/0-500 kcmil; 4-hole 1/0-750 kcmil; 6-hole
TA2JG250 — TA3MG500 — —
— — 3TA3MG500 2TA4NG500 —
—
3TA2JG250 3TA2LG600LDa 3TA4NG500 3TA6PG750e
3TA2LG600LNb 3TA4NG500Hc
7
TC1JG750 — — — TC5R600f
CIRCUIT BREAKERS
MOLDED CASE
#6-350 kcmil; 1-cable #6-350 kcmil; 2-cable 1/0-500 kcmil; 4-cable —
— — — — —
3CLJ350 6CLL350 (kit of 6) — 12CLN500 (kit of 12) —
TA2JG250PT — TA3MG500PT — —
— 3TA2LG600LNPT — 3TA4NG500PT —
All lug kits include the nut keepers. c Required for 100% rated breakers. Requires 90°C cable e Used only with LMAP1600 mounting base.
a Mounted on Load Side Only. sized at 75°C ampacity. f Used only with MBPG1600 or MBPG1601 mounting
b Mounted on Line Side Only. d Requires extended modified shield. base.
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-203
Revised on 11/30/19
External Accessories
General
7-204 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
Revised on 11/30/19
For JG Frame For LG Frame For MG Frame For NG Frame For PG Frame
400 A 600 A 800 A 1200 A 1600 A
Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number
HPLL HPLL HPLM HPLP HPLP
— — — — —
CBCM36 CBCM36 CBCM36 — —
CBCP54 CBCP54 CBCP54 CBCP54 CBCP54
— — — — —
MSKL4 MSKL4 MSKM4 MSKP4 MSKP4
7
CIRCUIT BREAKERS
MOLDED CASE
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-205
Revised on 10/31/18
External Accessories
Ground Sensors & Electronic Accessories
Com20 Profibus
& Com21 Modbus
Communications
MOLDED CASE
CIRCUIT BREAKERS
Module
THEP
7-206 Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog Product Category MCCB
Revised on 11/30/19
For JG Frame For LG Frame For MG Frame For NG Frame For PG Frame
400 A 600 A 800 A 1200 A 1600 A
Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number
— — — — —
— — — — —
— — — — —
NGSJ250 — — — —
NGSL400 NGSL400 — — —
— NGSM600 NGSM600 — —
— — NGSN800 NGSN800 —
— — — NGSP120 NGSP120
— — — — NGSP160
7
CIRCUIT BREAKERS
MOLDED CASE
BZLL3 BZLL3 BZLM3 BZLP3 BZLP3
BZLLBDC BZLLBDC
Product Category MCCB Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 7-207
VL Circuit Breakers
Accessory Locations Selection
Up to 4 Auxiliary Switches Shunt Trip or UVR or up to 4 Auxiliary Switches
MG, NG, PG
800 to 1600A
Up to 2 Auxiliary Switches + 2 Alarm Swiches Shunt Trip or UVR or up to 4 Auxiliary Switches
* Except DG and FG breakers with Electronic Trip Units. Due to the location of the Magnetic Latch, the Left Pocket is not available for accessories.
7
Suffix for factory mounted Undervoltage Releases
Then add Device
CIRCUIT BREAKERS
MOLDED CASE
If the frame is: And you need these functions: this suffix: Catalog Number
12V DC UA UVRLA12DC
24V DC UB UVRLB24DC
48V DC UC UVRLC48DC
60V DC UG UVRLG60DC
110-127V DC UD UVRLD125DC
220-250V DC UE UVRLE250DC
DG, FG, JG or LG 24V AC UK UVRLL24
110-127V AC UN UVRLN120
220-240V AC UR UVRLR240
208V AC UP UVRLP208
277V AC US UVRLS277
380-415V AC UT UVRLT415
440-480V AC UU UVRLU480
12V DC UA UVRPA12DC
24V DC UB UVRPB24DC
48V DC UC UVRPC48DC
60V DC UG UVRPG60DC
110-127V DC UD UVRPD125DC
220-250V DC UE UVRPE250DC
MG, NG or PG 110-127V AC UN UVRPN120
220-240V AC UR UVRPR240
208V AC UP UVRPP208
277V AC US UVRPS277
380-415V AC UT UVRPT415
440-480V AC UU UVRPU480
DG FG JG LG MG NG PG
Max rated continuous current 150 250 400 600 800 1200 1600
Rated operational voltage
NEMA V AC 600 600 600 600 600 600 600
IEC V AC 690 690 690 690 690 690 690
Rated Impulse Withstand Voltage
Main conducting paths kV 8 8 8 8 8 8 8
Auxiliary circuits kV 4 4 4 4 4 4 4
Ambient Temperature Range ºC -25 to +75 -25 to +75 -25 to +75 -25 to +75 -25 to +75 -25 to +75 -25 to +75
High Ambient Derating (thermal-mag.) 50ºC 93% 93% 93% 93% 95% 95% 95%
60ºC 86% 86% 86% 86% 86% 86% 80%
70ºC 80% 80% 80% 80% 80% 80% 74%
Operating Cycles 20,000 20,000 20,000 10,000 5,000 3,000 3,000
Max switching rate (per hour) 120 120 120 60 60 30 30
Power loss (at max. rated current)
Thermal-magnetic W 15 – 48 32 – 80 60 – 175 85 – 230 170 – 250 150 – 220 200 – 260
Electronic trip unit W 40 60 90 160 250 210 260
IEC 1
Time constant t = 10 ms
1 current path 2 current paths 3 current paths
in series in series
Up to 250V DC 440V DC 600V DC — — — — — — —
NEMA
Time constant t = 8 ms
2 poles switching 1 current path
250V DC Max. 2 30 30 30 30 42 42 42
3 poles switching 2 current paths in series
500V DC Max. 2 18 25 35 35 65 65 65
Accessories
Auxiliary/ Alarm Switch
Current rating (1 or 2 switches) 10 10 10 10 10 10 10
Current rating (3 or 4 same switch) A 5 5 5 5 5 5 5
Shunt Trip
Pick-up voltage V 0.7 – 1.1 0.7 – 1.1 0.7 – 1.1 0.7 – 1.1 0.7 – 1.1 0.7 – 1.1 0.7 – 1.1
7
110 – 127 V AC VA 424 – 489 424 – 489 424 – 489 424 – 489 424 – 489 424 – 489 424 – 489
208 – 277 V AC VA 533 – 736 533 – 736 533 – 736 533 – 736 533 – 736 533 – 736 533 – 736
380 – 600 V AC VA 408 – 645 408 – 645 408 – 645 408 – 645 408 – 645 408 – 645 408 – 645
24 V DC W 594 594 594 594 594 594 594
48 – 60 V DC W 740 – 925 740 – 925 740 – 925 740 – 925 740 – 925 740 – 925 740 – 925
110 –127 V DC W 559 – 648 559 – 648 559 – 648 559 – 648 559 – 648 559 – 648 559 – 648
220 – 250 V DC W 722 – 820 722 – 820 722 – 820 722 – 820 722 – 820 722 – 820 722 – 820
Max. Operating time ms 50 50 50 50 50 50 50
1 Consult Siemens for short circuit values.
2 Review individual frame and type values.
Technical Data
DG FG JG LG MG NG PG
Undervoltage Trip
Drop voltage (percentage) V 35% – 70% 35% – 70% 35% – 70% 35% – 70% 35% – 70% 35% – 70% 35% – 70%
Pick-up voltage (percentage) V 70% – 85% 70% – 85% 70% – 85% 70% – 85% 70% – 85% 70% – 85% 70% – 85%
Power consumption (continuous) at:
110 – 127 V AC VA 1 1 1 1 1.1 1.1 1.1
220 – 250 V AC VA 2.1 2.1 2.1 2.1 2.1 2.1 2.1
208 V AC VA 1.2 1.2 1.2 1.2 1.2 1.2 1.2
277 V AC VA 1.4 1.4 1.4 1.4 1.4 1.4 1.4
380 – 415 V AC VA 1.9 1.9 1.9 1.9 1.9 1.9 1.9
440 – 480 V AC VA 2.2 2.2 2.2 2.2 2.2 2.2 2.2
500 – 525 V AC VA 2.5 2.5 2.5 2.5 2.5 2.5 2.5
600 V AC VA 2.8 2.8 2.8 2.8 2.8 2.8 2.8
Max. opening time ms 50 50 50 50 50 50 50
Motorized Operating Mechanism
Motor with stored energy mechanism
(synchronizable) X X X X
Motor Operator X X X
Max. switching rate (per hour) 120 120 120 60 60 30 30
Command duration ms 20 – 50 20 – 50 20 – 50 20 – 50 20 – 50 — —
Closing time ms <100 <100 <100 <100 <100 <5,000 <5,000
Charging time s <5 <5 <5 <5 <5 <5 <5
Break time s <5 <5 <5 <5 <5 <5 <5
Power consumption VA/W <100 <100 <200 <250 <250
Inrush (A)
Control Voltages 110 – 127 V AC
220 – 250 V AC
24 V DC
48 V DC
60 V DC
Operating Range 85 – 110% of rated control voltage
7
CIRCUIT BREAKERS
MOLDED CASE
Technical Data
Unusual Operating Conditions Reference
Note: The information provided on Table 1 – Temperature derating data for thermal-magnetic breakers
this and the next page is intended for
Reference Ampere Ampere Rating at:
reference and recommendation only.
Rating at 50°C 60° C
Because several variables can act on 40° C (104° F) (122° F) (140° F) Siemens Breaker Frames
a circuit breaker’s performance at the 50 46 42
same time, the data below is based less 60 56 52
on controlled testing, than on experi- 70 65 60
ence and engineering judgment. Contact 90 84 78 DG
Siemens for further information on 100 94 87
special conditions and treatment. 125 114 100
150 136 120
High Ambient Temperatures 175 159 140 FG
Because thermal-magnetic trip breakers 200 182 160
225 205 180
are temperature sensitive and calibrated
250 235 220
for a specific ambient of 40° C (104°
300 276 252 JG
F) (average enclosure temperature), a 350 325 301
higher ambient will cause the breaker 400 372 340
to trip at lower current than its name- 500 468 435 LG
plate rating, in other words, causing 600 564 525
the breaker to “derate” (see Table 1). 700 658 613 MG
Similarly, the current carrying capacity 800 754 704
of a circuit conductor is based upon a 900 828 749
NG
certain ambient temperature, a higher 1000 900 825
ambient will reduce its current carrying 1200 1090 1000
capacity, causing it to “derate.” Thus, 1400 1304 1148 PG
with a fluctuating temperature, a ther- 1600 1500 1320
mal-magnetic breaker will derate nearly
parallel with its connected circuit con-
ductors and maintain close circuit pro-
tection. If the application temperature
exceeds 40° C (104° F) and is known,
either a breaker specially calibrated for
the higher ambient or one oversized
7
Altitude
Reduced air density at altitudes greater
than 6600 ft. (2000 meters) affects the
ability of a molded case circuit breaker
to transfer heat and interrupt faults.
Therefore, circuit breakers applied at
these altitudes should have interrupt-
ing, insulation and continuous currents
derated as indicated in Figure 1.
Maximum continuous ampere rating 75°C (167F) Maximum continuous ampere rating 75°C (167F)
at 40°C (104°F) Copper at 40°C (104°F) Copper
60HZ 400HZ cable per pole 60HZ 400HZ cable per pole
Breaker Enclosed after No of Breaker Enclosed after No of
type Open air Open air derating pieces Wire size type Open air Open air derating pieces Wire size
50 48 38 1 #8 400 300 240 2 #3/0
60 57 46 1 #6 LG 500 375 300 2 250 kcmil
70 63 50 1 #4 600 420 336 2 350 kcmil
80 72 58 1 #4 600 430 360 2 350 kcmil
DG 90 80 64 1 #3 MG 700 500 400 3 250 kcmil
100 90 72 1 #3 800 560 448 3 300 kcmil
600 430 430 2 350 kcmil
7
110 95 75 1 #2 MG
125 105 84 1 #1 100% 700 500 500 3 250 kcmil
150 125 100 1 #1/0 Rated 800 560 560 3 300 kcmil
CIRCUIT BREAKERS
MOLDED CASE
100 90 72 1 #3 800 560 448 3 300 kcmil
110 95 75 1 #2 900 600 480 3 350 kcmil
NG
125 105 84 1 #1 1000 650 520 3 400 kcmil
150 125 100 1 #1/0 1200 780 624 4 350 kcmil
FG 900 600 600 3 350 kcmil
175 140 112 1 #2/0 NG
200 160 128 1 #3/0 1000 650 650 3 400 kcmil
100%
1200 780 780 4 350 kcmil
225 180 144 1 #4/0 Rated
1200 780 624 4 400 kcmil
250 200 160 1 250 kcmil
1400 850 680 4 500 kcmil
250 210 168 1 250 kcmil
PG 1600 960 768 5 500 kcmil
300 240 192 1 350 kcmil
JG 1200 780 780 4 400 kcmil
350 260 208 1 500 kcmil
400 300 240 2 #2/0 PG 100% 1400 850 850 4 500 kcmil
JG 250 210 210 1 250 kcmil Rated 1600 960 960 5 500 kcmil
100% 300 240 240 1 350 kcmil
Rated 350 260 260 1 500 kcmil
400 300 300 2 #3/0
400 300 240 2 #3/0
LG 500 375 300 2 250 kcmil
600 420 336 2 350 kcmil
The information provided on this page is intended for judgment.Contact Siemens for further information on Calculated after derating to compensate for the heating
reference and recommendation only. Because several special conditions and treatment. of the copper conductor, caused by the skin effect
variables can act on a circuit breaker’s performance at Additional derating may be required if the ambient generated by eddy currents produced at 400/415HZ.
the same time, the data above is based less on con- temperature is greater than 40°C (104°F).
trolled testing, than on experience and engineering
The term “Series Connected Short This is permitted as long as the series No substitutions are permitted. All com-
Circuit Rating” refers to the application of combination has been tested and certi- binations shown have been tested and
series circuit breakers in a combination fied by UL. are UL Listed. This information is provid-
that allows downstream breakers to have The tables on these pages list specific ed as a reference tool only. For verifica-
lower individual interrupting ratings than main and branch breaker combinations tion of specific combination ratings
the available fault current. that may be used for the short circuit consult the UL Recognized
interrupting ratings shown. Components Directory.
65000 BFGAH2
BAF, QAF 2 120/240 15-20 (cont.) BAF, QAF, QAFH, BAFH 2 120/240 15-20
QPP 2 120/240 125-200
QT 1, 2 120 15-40
QT 1, 2 120/240 15-40
MOLDED CASE
CIRCUIT BREAKERS
240V Breaker Series Ratings (continued) 240V Breaker Series Ratings (continued)
Series Main Breaker Branch Breaker Series Main Breaker Branch Breaker
Rating Max. Number Rating Max. Number
kAIR Type Amperes Type of Poles Voltage Amperes kAIR Type Amperes Type of Poles Voltage Amperes
QFGAH2, BFGAH2, QAFH2, 1 120/240 15-70
1 120 15-20
BAFH2, QAFH, BAFH QPH, BQH, BLH 2 120/240 15-125
QAFH, BAFH 2 120/240 15-20 3 240 15-100
QPHF, BLHF, QPHF2, QAF2, BAF2, QAFH2,
HQR2 250 1 120 15-30
BLHF2, QEH, BLEH NMG, BAFH2, QFGA2, BFGA2, 1 120 15-20
(cont.) (2P, 3P)
QEH, BLEH, QPHF, BLHF 2 120/240 15-60 HMG QFGAH2, BFGAH2
QN, QNH, QNR, QNRH 2 120/240 150-200 QPF2, BLF2, QPHF2, BLHF2 1 120 15-30
QS, QSH, QSHH 2 120/240 100-225 QR2, QRH2 2,3 240 100-250
QR2, QRH2 2,3 240 100-250 QN, QNH 2 120/240 150-200
1 120/240 15-70 QNR, QNRH 2 120/240 150-200
QPH, BQH, BLH 2 120/240 15-125 1 120/240 15-70
3 240 15-100 QPH, BQH, BLH 2 120/240 15-125
800
JXD2-A, QAF2, BAF2, QAFH2, 3 240 15-100
(2P, 3P)
JD6-A BAFH2, QFGA2, BFGA2, 1 120 15-20 SMD6 QAF2, BAF2, QAFH2,
(cont.)
JXD6-A QFGAH2, BFGAH2 SMD6-B BAFH2, QFGA2, BFGA2, 1 120 15-20
QPF2, BLF2, QPHF2, BLHF2 1 120 15-30 QFGAH2, BFGAH2
QR2, QRH2 2,3 240 100-250 QPF2, BLF2, QPHF2, BLHF2 1 120 15-30
QJ2H, QJH2 2,3 240 60-225 QR2, QRH2 2,3 240 100-250
1 120/240 15-70 1 120/240 15-70
QPH, BQH, BLH 2 120/240 15-125 QPH 2 120/240 15-125
NJGA/ 3 240 15-100 3 240 15-100
NJJA QR2, QRH2 2,3 240 100-250 HMXD6 QAF2, BAF2, QAFH2,
QN, QNH 2 120/240 150-200 HMD6 BAFH2, QFGA2, BFGA2, 1 120 15-20
400 QNR, QNRH 2 120/240 150-200 QFGAH2, BFGAH2
(2P, 3P) 1 120/240 15-70 QPF2, BLF2, QPHF2,
1 120 15-30
QPH, BQH, BLH 2 120/240 15-125 BLHF2
3 240 15-100 1 120/240 15-70
SJD6-A QAF2, BAF2, QAFH2, QPH, BQH, BLH 2 120/240 15-125
SJD6-B BAFH2, QFGA2, BFGA2, 1 120 15-20 3 240 15-100
QFGAH2, BFGAH2 QAF2, BAF2, QAFH2,
QPF2, BLF2, QPHF2, BLHF2 1 120 15-30 ND6, NXD BAFH2, QFGA2, BFGA2, 1 120 15-20
QR2, QRH2 2,3 240 100-250 QFGAH2, BFGAH2
1 120/240 15-70 QPF2, BLF2, QPHF2,
1 120 15-30
QPH 2 120/240 15-125 BLHF2
3 240 15-100 QR2, QRH2 2,3 240 100-250
HJD6-A, 1 120/240 15-70
QAF2, BAF2, QAFH2,
HJXD6 QPH, BQH, BLH 2 120/240 15-125
BAFH2, QFGA2, BFGA2, 1 120 15-20
QFGAH2, BFGAH2 3 240 15-100
QPF2, BLF2, QPHF2, BLHF2 1 120 15-30 QAF2, BAF2, QAFH2,
1 120/240 15-70 BAFH2, QFGA2, BFGA2, 1 120 15-20
QPH, BQH, BLH 2 120/240 15-125 NNG, HNG QFGAH2, BFGAH2
65000 3 240 15-100 65000 QPF2, BLF2, QPHF2,
1 120 15-30
(cont.) QR2, QRH2 2,3 240 100-250 (cont.) BLHF2
LD6-A QR2, QRH2 2,3 240 100-250
QAF2, BAF2, QAFH2, 1200
LXD6-A QN, QNH 2 120/240 150-200
BAFH2, QFGA2, BFGA2, 1 120 15-20 (2P, 3P)
QFGAH2, BFGAH2 QNR, QNRH 2 120/240 150-200
1 120/240 15-70
7
QPF2, BLF2, QPHF2, BLHF2 1 120 15-30
QJ2H, QJH2 2,3 240 60-225 QPH, BQH, BLH 2 120/240 15-125
1 120/240 15-70 3 240 15-100
QPH, BQH, BLH 2 120/240 15-125 QAF2, BAF2, QAFH2,
CIRCUIT BREAKERS
MOLDED CASE
SND6
3 240 15-100 BAFH2, QFGA2, BFGA2, 1 120 15-20
SND6-B
QR2, QRH2 2,3 240 100-250 QFGAH2, BFGAH2
NLGA, QAF2, BAF2, QAFH2, QPF2, BLF2, QPHF2,
1 120 15-30
NLGB BAFH2, QFGA2, BFGA2, 1 120 15-20 BLHF2
QFGAH2, BFGAH2 QR2, QRH2 2,3 240 100-250
QPF2, BLF2, QPHF2, BLHF2 1 120 15-30 1 120/240 15-70
QN, QNH 2 120/240 150-200 QPH 2 120/240 15-125
600 3 240 15-100
QNR, QNRH 2 120/240 150-200
(2P, 3P) HND6, QAF2, BAF2, QAFH2,
1 120/240 15-70
QPH, BQH, BLH 2 120/240 15-125 HNXD6 BAFH2, QFGA2, BFGA2, 1 120 15-20
3 240 15-100 QFGAH2, BFGAH2
QAF2, BAF2, QAFH2, QPF2, BLF2, QPHF2,
SLD6-A 1 120 15-30
BAFH2, QFGA2, BFGA2, 1 120 15-20 BLHF2
SLD6-B 1 120/240 15-70
QFGAH2, BFGAH2 SPD6,
QPF2, BLF2, QPHF2, QPH, BQH, BLH 2 120/240 15-125
1 120 15-30 SPD6-B,
BLHF2 3 240 15-100
PD6, PXD6
QR2, QRH2 2,3 240 100-250 QR2, QRH2 2,3 240 100-250
1 120/240 15-70 1 120/240 15-70
QPH 2 120/240 15-125 QPH, BQH, BLH 2 120/240 15-125
1600
3 240 15-100 3 240 15-100
NPG (2P, 3P)
QR2, QRH2 2,3 240 100-250
HLD6-A, QN, QNH 2 120/240 150-200
HLXD6-A QNR, QNRH 2 120/240 150-200
QAF2, BAF2, QAFH2,
BAFH2, QFGA2, BFGA2, 1 120 15-20 1 120/240 15-70
HPD6,
QFGAH2, BFGAH2 QPH 2 120/240 15-125
HPXD6
QPF2, BLF2, QPHF2, BLHF2 1 120 15-30 3 240 15-100
1 120/240 15-70 1 120/240 15-70
HRD6,
QPH, BQH, BLH 2 120/240 15-125 QPH 2 120/240 15-125
HRXD6
3 240 15-100 3 240 15-100
MD6, 800 QAF2, BAF2, QAFH2, 2000 QR2, QRH2 2,3 240 100-250
MXD6 (2P, 3P) BAFH2, QFGA2, BFGA2, 1 120 15-20 (2P, 3P)
1 120/240 15-70
QFGAH2, BFGAH2 RD6, RXD6
QPH, BQH, BLH 2 120/240 15-125
QPF2, BLF2, QPHF2, BLHF2 1 120 15-30 3 240 15-100
QR2, QRH2 2,3 240 100-250
240V Breaker Series Ratings (continued) 240V Breaker Series Ratings (continued)
Series Main Breaker Branch Breaker Main Breaker Branch Breaker
Series
Rating Max. Number Rating Max. Number
kAIR Type Amperes Type of Poles Voltage Amperes kAIR Type Amperes Type of Poles Voltage Amperes
HED4 100 (1P) ED2, ED4 1 120 15-100 QP, BQ, BL, 1 120/240 15-70
QP, BQ, BL, 1 120/240 15-70 QPH, BQH, BLH, 2 120/240 15-125
QPH, BQH, BLH, 2 240 15-125 HQP, HBQ, HBL 3 240 15-100
HQP, HBQ, HBL, 3 240 15-100 QAF2, BAF2, QAF, BQAF,
QAF2, BAF2, QAF, BQAF, BAF, QAFH2, BAFH2,
BAF, QAFH2, BAFH2, HQAF2, HBAF2, QAFH,
HQAF2, HBAF2, QAFH, 1 120 15-20
1 120 15-20 BQAFH, BAFH, QFGA2,
BQAFH, BAFH, QFGA2, BFGA2 HQFGA2, HBF-
BFGA2 HQFGA2, HBF- GA2, QFGAH2, BFGAH2
GA2, QFGAH2, BFGAH2 QAF, BAF, QAFH, BAFH 2 120/240 15-20
QAF, BAF, QAFH, BAFH 2 120/240 15-20 QE, BE, BLE, QPHF,
HED4,
QEH,BLEH, QE, BE, BQHF, BLHF, QPF, BQF,
HED6
QPHF,BQHF, BLHF, QPF, HFD6, BLF, QEH, BLEH, QPF2, 1 120 15-30
BLF, BQF, BLE, QPF2, 1 120 15-30 HFXD6 BLF2, HQPF2, HBLF2,
BLF2, QPHF2, BLHF2, QPHF2, BLHF2
HQPF2, HBLF2 QPF, BLF, BLE, BLEH,
QEH, BLEH, QPHF, QE, 2 120/240 15-60
125 2 120/240 15-60 QPHF, BLHF, QEH, QE
BLHF,QPF,BLF, BLE ED4 1 120 15-100
(2P, 3P)
ED2 1,2,3 120/240 15-100 ED4, ED6 2,3 240 15-125
ED4 1 120 15-100 FD6-A, FXD6-A 2,3 240 70-250
ED4, ED6 2,3 240 15-125 QJ2, QJH2, QJ2H 2,3 240 60-225
QT 1,2 120/240 15-40 HQPP, QPPH, QPP 2 120/240 125-225
QAF2, QAFH2, QAF, QR2, QRH2, HQR2 2,3 240 100-250
BQAF, BAF, BAFH2, QT 1,2 120/240 15-40
HQAF2, HBAF2, QAFH, NDGA, NDGB 2, 3 240 50-150
1 120 15-20
BQAFH, BAFH, QFGA2, NFGA, NFGB 2, 3 240 70-250
BFGA2 HQFGA2, HBF- ED4, ED6 1 240 15-100
NGB, GA2, QFGAH2, BFGAH2
HGB, ED4, ED6 2,3 240 15-125
QAF, BAF, QAFH, BAFH 2 120/240 15-20
LBG NFGA, NFGB 2, 3 240 70-250
QPF,BQF,BLF, QPHF,
QAF2, BAF2, QAFH2,
BQHF, BLHF, QPF2, BLF2,
1 120 15-30 BAFH2, HQAF2, HBAF2,
QPHF2, BLHF2, HQPF2,
QFGA2, BFGA2 HQFGA2, 1 120 15-20
HBLF2 HFGA,
250 HBFGA2, QFGAH2,
QPF, BLF 2 120/240 15-60 HFGB
(2P, 3P) BFGAH2
NGB, 1 120 15-70 QPF2, BLF2, HQPF2,
QP, BQ, BL, QPH, BQH, 1 120 15-30
HGB, 2 120/240 15-125 HBLF2, QPHF2, BLHF2
BLH, HQP, HBQ,HBL
LBG 3 240 15-100
QR2, QRH2, HQR2 2,3 240 100-250
ED4, ED6 1 240 15-100
HDGA, 150 FD6, FXD6 2, 3 240 70-250
ED4, ED6 2,3 240 15-125
HDGB (2P, 3P) FD6-A, FXD6-A 2, 3 240 70-250
NDGA, NDGB 2,3 240 50-150
1 120/240 15-70
QP, BQ, BL, QPH, BQH, 1 120/240 15-70 QP, BQ, BL 2 120/240 15-125
100000
100000 BLH, HQP, HBQ, HBL 2 120/240 15-125
(cont.) 3 240 15-100
HQPP, QPPH, QPP 2 120/240 125-225 QT 1,2 120/240 15-50
QAF2, BAF2, QAF, BQAF, QFGA2, BFGA2, QAF2,
BAF, QAFH2, BAFH2, 1 120 15-20
BAF2, QAF, BAF
HQAF2, HBAF2, QAFH,
1 120 15-20 QAF, BAF 2 120/240 15-20
BQAFH, BAFH, QFGA2,
QPF2, BLF2, QPF, BQF,
BFGA2 HQFGA2, HBF- 1 120 15-30
BLF, QE, BLE, BE
GA2, QFGAH2, BFGAH2
7
3 240 15-100
BQF, BLF, BLE, QPF2, 1 120 15-30
HQR2H QFGAH2, BFGAH2,
BLF2, QPFH2, BLHF2,
QAFH2, BAFH2, HQFGA2,
HQPF2, HBLF2 1 120 15-20
HBFGA2, HQAF2, HBAF2,
QE, QEH, BLEH,
2 120/240 15-60 QAFH, BAFH
QPHF,BLHF,QPF,BLF,BLE
QAFH, BAFH 2 120/240 15-20
QR2, QRH2, HQR2 2 120/240 100-225
QPHF, BLHF, QPHF2,
QT 1,2 120/240 15-40
BLHF2, QEH, BLEH, 1 120 15-30
15-25
QP, BP, QL 1 120/240 HQPF2, HBLF2
35-70
QEH, BLEH, QPHF, BLHF 2 120/240 15-60
15-25
2 120/240 1 120/240 15-70
35-125
HQP, HBQ, HBL 2 120/240 15-125
3 240 15-100
3 240 15-100
QR2, QRH2, HQR2 2,3 240 100-225
QS, QSH, QSHH, HQS 2 120/240 100-225
1 120/240 15-70
QPH, BQH, BLH, HQP, QR2, QRH2, HQR2 2,3 240 100-250
2 120/240 15-125
HBQ ,HBL ED4 1 120 15-100
3 240 15-100
ED4, ED6 2, 3 240 15-125
QAF2, BAF2, QAF, BQAF,
QAF2, BAF2, QAFH2,
BAF, QAFH2, BAFH2,
225 BAFH2, HQAF2, HBAF2,
HQAF2, HBAF2, QAFH,
HQJ2H 1 120 15-20 QFGA2, BFGA2 HQFGA2, 1 120 15-20
(2P, 3P) BQAFH, BAFH, QFGA2,
HBFGA2, QFGAH2,
BFGA2 HQFGA2, HBF-
BFGAH2
GA2, QFGAH2, BFGAH2
HJD6-A, 400 QPF2, BLF2, HQPF2,
QAF, BAF, QAFH, QAFH 2 120/240 15-20 1 120 15-30
HJXD6-A (2P, 3P) HBLF2, QPHF2, BLHF2
QEH, BLEH, QE, BE,
QR2, QRH2, HQR2 2,3 240 100-250
QPHF, BQHF, BLHF, QPF,
BQF, BLF, BLE, QPF2, 1 120 15-30 FD6-A, FXD6-A 2, 3 240 70-250
BLF2, HQPF2, HBLF2, JD6-A, JXD6-A
2, 3 240 200-400
QPHF2, BLHF2 JXD2-A, SJD6-A
QEH, BLEH, QPHF, BLE, NDGA, NDGB 2, 3 240 50-150
2 120/240 15-60 NFGA, NFGB 2, 3 240 70-250
BLHF, QE, QPF, BLF
QT 1 120/240 15-50 NJGA, NJJA 2, 3 240 200-400
240V Breaker Series Ratings (continued) 240V Breaker Series Ratings (continued)
Series Main Breaker Branch Breaker Main Breaker Branch Breaker
Series
Rating Max. Number Rating Max. Number
kAIR Type Amperes Type of Poles Voltage Amperes kAIR Type Amperes Type of Poles Voltage Amperes
ED4, ED6 1 240 15-100 QR2, QRH2, HQR2 2,3 240 100-250
ED4, ED6 2,3 240 15-125 SHLD6,
600 NDGA, NDGB 2, 3 240 50-150
QAF2, BAF2, QAFH2, SHLD6-A
(3P) NFGA, NFGB 2, 3 240 70-250
BAFH2, HQAF2, HBAF2, SHLD6-B
(cont.) NJGA, NJJA 2, 3 240 200-400
QFGA2, BFGA2 HQFGA2, 1 120 15-20 (cont.)
NLGA, NLGB 2, 3 240 400-600
HBFGA2, QFGAH2, ED4, ED6 1 240 15-100
BFGAH2 ED4, ED6 2,3 240 15-125
400 QPF2, BLF2, HQPF2, NFGA, NFGB 2, 3 240 70-250
HJGA 1 120 15-30
(2P, 3P) HBLF2, QPHF2, BLHF2 FD6, FXD6 2, 3 240 70-250
NFGA, NFGB 2, 3 240 70-250 FD6-A, FXD6-A 2, 3 240 70-250
FD6, FXD6 2, 3 240 70-250 NJGA, NJJA 2, 3 240 200-400
FD6-A, FXD6-A 2, 3 240 70-250 JD6, JXD6 2, 3 240 200-400
QR2, QRH2, HQR2 2,3 240 100-250 JD6-A, JXD6-A 2, 3 240 200-400
NJGA, NJJA 2, 3 240 200-400 NLGA, NLGB 2, 3 240 400-600
JD6, JXD6 2, 3 240 200-400 LD6, LD6-A 2, 3 240 200-600
JD6-A, JXD6-A 2, 3 240 200-400 LXD6, LXD6-A 2, 3 240 450-600
ED4 1 120 15-100 HMG
NMG 2, 3 240 600-800
ED4, ED6 2, 3 240 15-125 QAF2, BAF2, QAFH2,
FD6-A, FXD6-A 2, 3 240 70-250 BAFH2, HQAF2, HBAF2,
JD6-A, JXD6-A QFGA2, BFGA2 HQFGA2, 1 120 15-20
2, 3 240 200-400
JXD2-A, SJD6-A, SJD6-B HBFGA2, QFGAH2,
QAF2, BAF2, QAFH2, BFGAH2
BAFH2, HQAF2, HBAF2, QPF2, BLF2, HQPF2,
SHJD6, 1 120 15-30
QFGA2, BFGA2 HQFGA2, 1 120 15-20 HBLF2, QPHF2, BLHF2
SHJD6-A, 400 (3P)
HBFGA2, QFGAH2, QR2, QRH2, HQR2 2,3 240 100-250
SHJD6-B
BFGAH2 LMD6, LMXD6 2, 3 240 600-800
QPF2, BLF2, HQPF2, MD6, MXD6 2, 3 240 400-800
1 120 15-30 800
HBLF2, QPHF2, BLHF2 NDGA, NDGB 2, 3 240 50-150
QR2, QRH2, HQR2 2,3 240 100-250 (2P, 3P)
NFGA, NFGB 2, 3 240 70-250
NDGA, NDGB 2, 3 240 50-150 NJGA, NJJA 2, 3 240 200-400
NFGA, NFGB 2, 3 240 70-250 NLGA, NLGB 2, 3 240 400-600
NJGA, NJJA 2, 3 240 200-400 NMG 2, 3 240 600-800
ED4 1 120 15-100 ED4 1 120 15-100
ED4, ED6 2,3 240 15-125 ED4, ED6 2,3 240 15-125
QAF2, BAF2, QAFH2, FD6-A, FXD6-A 2,3 240 70-250
BAFH2, HQAF2, HBAF2, JD6-A, JXD6-A,
QFGA2, BFGA2 HQFGA2, 1 120 15-20 2,3 240 200-400
JXD2-A, SJD6-A
HBFGA2, QFGAH2, LD6-A 2,3 240 200-600
BFGAH2 HMD6,
HMXD6 LXD6-A 2,3 240 450-600
QPF2, BLF2, HQPF2, QAF2, BAF2, QAFH2,
1 120 15-30
HBLF2, QPHF2, BLHF2 BAFH2, HQAF2, HBAF2,
HLD6-A, FD6-A, FXD6-A 2,3 240 70-250 QFGA2, BFGA2 HQFGA2, 1 120 15-20
100000 HLXD6-A JD6-A, JXD6-A, JXD2-A, HBFGA2, QFGAH2,
2,3 240 200-400 100000
(cont.) SJD6-A, SJD6-B BFGAH2
(cont.)
LD6-A 2,3 240 200-600 QPF2, BLF2, HQPF2,
LXD6-A 2,3 240 450-600 1 120 15-30
HBLF2, QPHF2, BLHF2
SLD6-A, SLD6-B 3 240 300-600 QR2, QRH2, HQR2 2,3 240 100-250
QR2, QRH2, HQR2 2,3 240 100-250 SLD6-A, SLD6-B 3 240 300-600
7
NDGA, NDGB 2, 3 240 50-150 MD6, MXD6 2,3 240 500-800
NFGA, NFGB 2, 3 240 70-250 SMD6, SMD6-B 3 240 600-800
NJGA, NJJA 2, 3 240 200-400 NDGA, NDGB 2, 3 240 50-150
600
CIRCUIT BREAKERS
MOLDED CASE
NLGA, NLGB 2, 3 240 400-600 NFGA, NFGB 2, 3 240 70-250
(2P, 3P)
ED4, ED6 1 240 15-100 NJGA, NJJA 2, 3 240 200-400
ED4, ED6 2,3 240 15-125 NLGA, NLGB 2, 3 240 400-600
NFGA, NFGB 2, 3 240 70-250 NMG 2, 3 240 600-800
FD6, FXD6 2, 3 240 70-250 ED4 1 120 15-100
FD6-A, FXD6-A 2, 3 240 70-250 ED4, ED6 2,3 240 15-125
NJGA, NJJA 2, 3 240 200-400 FD6-A, FXD6-A 2,3 240 70-250
JD6, JXD6 2, 3 240 200-400 JD6-A, JXD6-A,
JD6-A, JXD6-A 2, 3 240 200-400 2,3 240 200-400
JXD2-A
HLGA, NLGA, NLGB 2, 3 240 400-600 SJD6-A, SJD6-B 2,3 240 200-400
HLGB QAF2, BAF2, QAFH2, SHMD6, 800 LD6-A 2,3 240 200-600
BAFH2, HQAF2, HBAF2, SHMD6-B (3P) LXD6-A 2,3 240 450-600
QFGA2, BFGA2 HQFGA2, 1 120 15-20 QAF2, BAF2, QAFH2,
HBFGA2, QFGAH2, BAFH2, HQAF2, HBAF2,
BFGAH2 QFGA2, BFGA2 HQFGA2, 1 120 15-20
QPF2, BLF2, HQPF2, HBFGA2, QFGAH2,
1 120 15-30
HBLF2, QPHF2, BLHF2 BFGAH2
QR2, QRH2, HQR2 2,3 240 100-250 QPF2, BLF2, HQPF2,
LD6, LD6-A 2, 3 240 200-600 1 120 15-30
HBLF2, QPHF2, BLHF2
LXD6, LXD6-A 2, 3 240 450-600 QR2, QRH2, HQR2 2,3 240 100-250
ED4 1 120 15-100
SLD6-A, SLD6-B 3 240 300-600
ED4, ED6 2,3 240 15-125
MD6, MXD6, SMD6,
FD6-A, FXD6-A 2,3 240 70-250 2,3 240 500-800
SMD6-B
JD6-A, JXD6-A, JXD2-A,
2,3 240 200-400 ED4, ED6 1 240 15-100
SJD6-A, SJD6-B
ED4, ED6 2,3 240 15-125
LD6-A 2,3 240 200-600
NFGA, NFGB 2, 3 240 70-250
SHLD6, LXD6-A 2,3 240 450-600
600 FD6, FXD6 2, 3 240 70-250
SHLD6-A, SLD6-A, SLD6-B 3 240 300-600
(3P) FD6-A, FXD6-A 2, 3 240 70-250
SHLD6-B 1200
QAF2, BAF2, QAFH2, HNG NJGA, NJJA 2, 3 240 200-400
BAFH2, HQAF2, HBAF2, (2P, 3P)
QFGA2, BFGA2 HQFGA2, 1 120 15-20 JD6, JXD6 2, 3 240 200-400
HBFGA2, QFGAH2, JD6-A, JXD6-A 2, 3 240 200-400
BFGAH2 NLGA, NLGB 2, 3 240 400-600
QPF2, BLF2, HQPF2, LD6, LD6-A 2, 3 240 200-600
1 120 15-30
HBLF2, QPHF2, BLHF2 LXD6, LXD6-A 2, 3 240 450-600
240V Breaker Series Ratings (continued) 240V Breaker Series Ratings (continued)
Series Main Breaker Branch Breaker Series Main Breaker Branch Breaker
Rating Max. Number Rating Max. Number
kAIR Type Amperes Type of Poles Voltage Amperes kAIR Type Amperes Type of Poles Voltage Amperes
QAF2, BAF2, QAFH2, ED4 1 240 15-100
BAFH2, HQAF2, HBAF2, ED4, ED6 2,3 240 15-125
QFGA2, BFGA2 HQFGA2, 1 120 15-20 JD6-A, JXD6-A
HBFGA2, QFGAH2, 2,3 240 200-400
JXD2-A
BFGAH2 SJD6-A, SJD6-B 3 240 200-400
HNG QPF2, BLF2, HQPF2, LD6-A 2,3 240 200-600
1 120 15-30
(cont.) HBLF2, QPHF2, BLHF2 LXD6-A 2,3 240 450-600
QR2, QRH2, HQR2 2,3 240 100-250 SLD6-A, SLD6-B 3 240 300-600
NMG 2, 3 240 600-800 MD6, MXD6, 2,3 240 500-800
LMD6, LMXD6 2, 3 240 600-800 HPD6, SMD6, SMD6-B 3 240 600-800
NNG 2, 3 240 800-1200 HPXD6, ND6, NXD6,
ND6, NXD6 2,3 240 600-1200 2,3 240 500-1200
SHPD6 SND6, SND6-B
ED4 1 240 15-100 SHPD6-B PD6, PXD6 2,3 240 1200-1600
ED4, ED6 2,3 240 15-125 SPD6, SPD6-B 3 240 1400-1600
FD6-A, FXD6-A 2,3 240 70-250 QR2, QRH2, HQR2 2,3 240 100-250
JD6-A, JXD6-A, NDGA, NDGB 2, 3 240 50-150
2,3 240 200-400
JXD2-A, SJD6-A NFGA, NFGB 2, 3 240 70-250
LD6-A 2,3 240 200-600 NJGA, NJJA 2, 3 240 200-400
1200 LXD6-A 2,3 240 450-600 NLGA, NLGB 2, 3 240 400-600
(2P, 3P) SLD6-A, SLD6-B 3 240 300-600
NMG 2, 3 240 600-800
MD6, MXD6,
2,3 240 500-800 NNG 2, 3 240 800-1200
SMD6 1600 NPG 2, 3 240 1200-1600
ND6, NXD6, (3P)
2,3 240 500-1200 ED4 1 240 15-100
SND6, SND6-B
HND6, QAF2, BAF2, QAFH2, ED4, ED6 2,3 240 15-125
HNXD6 BAFH2, HQAF2, HBAF2, FD6-A, FXD6-A 2,3 240 70-250
QFGA2, BFGA2 HQFGA2, 1 120 15-20 JD6-A, JXD6-A, JXD2-A 2,3 240 200-400
HBFGA2, QFGAH2, SJD6-A, SJD6-B 3 240 200-400
BFGAH2 LD6-A 2,3 240 200-600
QPF2, BLF2, HQPF2, LXD6-A 2,3 240 450-600
1 120 15-30
HBLF2, QPHF2, BLHF2 SLD6-A, SLD6-B 3 240 300-600
QR2, QRH2, HQR2 2,3 240 100-250 MD6, MXD6, 2,3 240 500-800
NDGA, NDGB 2, 3 240 50-150 SMD6, SMD6-B 3 240 500-800
NFGA, NFGB 2, 3 240 70-250 100000 SHPD6, ND6, NXD6 2,3 240 500-1200
NJGA, NJJA 2, 3 240 200-400 (cont.) SHPD6-B SND6, SND6-B 3 240 500-1200
NLGA, NLGB 2, 3 240 400-600 NPG, PD6, PXD6 2,3 240 1200-1600
NMG 2, 3 240 600-800 SPD6, SPD6-B 3 240 1400-1600
NNG 2, 3 240 800-1200 NDGA, NDGB 2, 3 240 50-150
ED4 1 240 15-100 NFGA, NFGB 2, 3 240 70-250
ED4, ED6 2,3 240 15-125 NJGA, NJJA 2, 3 240 200-400
FD6-A, FXD6-A 2,3 240 70-250 NLGA 2, 3 240 400-600
JD6-A, JXD6-A, NMG 2, 3 240 600-800
2,3 240 200-400
JXD2-A, SJD6-A NNG 2, 3 240 800-1200
100000 LD6-A 2,3 240 200-600
(cont.) NPG 2, 3 240 1200-1600
LXD6-A 2,3 240 450-600 ED4 1 240 15-100
SLD6-A, SLD6-B 3 240 300-600
ED4, ED6 2,3 240 15-125
MD6, MXD6,
2,3 240 500-800 JD6-A, JXD6-A, JXD2-A 2,3 240 200-400
SMD6, SMD6-B
7
240V Breaker Series Ratings (continued) 240V Breaker Series Ratings (continued)
Series Main Breaker Branch Breaker Series Main Breaker Branch Breaker
Rating Max. Number Rating Max. Number
kAIR Type Amperes Type of Poles Voltage Amperes kAIR Type Amperes Type of Poles Voltage Amperes
NGB,HGB,LBG 1,2,3 240 15-125 LXD6-A, HJXD6-A 2,3 240 450-600
LDGA, 150
NDGA, NDGB, HDGA, QT 1,2 120/240 15-30
LDGB (2P, 3P) 2, 3 240 50-150
HDGB NGB,HGB,LBG 1,2,3 240 15-125
1 120/240 15-70 NDGA, NDGB, HDGA,
QP, BQ, BL, QPH, BQH, 2-3 240 50-150
2 120/240 15-125 CLD6-A HDGB
BLH, HQP, HBQ, HBL
3 240 15-100 (cont.) NFGA, NFGB, HFGA,
QAF2, BAF2, QAF, BQAF, 240 70-250
HFGB
BAF, QAFH2, BAFH2,
NJGA, HJGA, NJJA 240 200-400
HQAF2, HBAF2, QAFH,
1 120 15-20 NLGA, HLGA, NLGB,
BQAFH, BAFH, HQFGA2, 600 240 400-600
HLGB
HBFGA2, QFGA2, QF- (2P, 3P
GAH2, BFGAH2 NGB,HGB,LBG 1,2,3 240 15-125
BAF, QAF, BAFH, QAFH 2 120/240 15-20 NDGA, NDGB, HDGA,
2, 3 240 50-150
QPHF, BQHF, BLHF, QE, HDGB
BE, BLE, QPF, BQF, BLF, 1 120 15-30 NFGA, NFGB, HFGA,
LLGA, 240 70-250
QEH, BLEH, QAF, BAF HFGB
LLGB
QPHF, BLHF, QE, BLE, HFD6, HFXD6 240 70-250
QPF, BLF, QEH, BLEH, 2 120/240 15-60 NJGA, HJGA, NJJA 240 200-400
CFD6 QAF, BAF NLGA, HLGA, NLGB,
240 400-600
ED2 1,2,3 120/240 15-100 HLGB
250 HED4, ED4 1 120 15-100 ED4 1 240 15
(2P, 3P) ED4, ED6, ED4, ED6,
2,3 240 15-125 2,3 240 15-125
HED4, HED6 HED4, HED6
FD6-A, FXD6-A FD6-A, FXD6-A,
2,3 240 70-250 2,3 240 70-250
HFD6, HFXD6 HFD6, HFXD6
QJ2H, QJH2, QJ2 2,3 240 60-225 JXD2-A, JD6-A,
QPPH, QPP 2 120/240 125-225 JXD6-A, HJD6-A 2,3 240 200-400
QT 1,2 120/240 15-40 HJXD6-A
NGB,HGB,LBG 1,2,3 240 15-125 LD6-A, HLD6-A 2,3 240 200-600
NDGA, NDGB, HDGA, LXD6-A, HLXD6-A 2,3 240 450-600
2, 3 240 50-150 CMD6
HDGB MD6, MXD6,
NFGA, NFGB, HFGA, 2,3 240 500-800
2, 3 240 70-250 HMD6, HMXD6
HFGB NDGA, NDGB, HDGA,
NGB,HGB,LBG 1,2,3 240 15-125 2,3 240 50-150
HDGB
NDGA, NDGB, HDGA, NFGA, NFGB, HFGA,
2, 3 240 50-150 2,3 240 70-250
LFGA, HDGB 800 HFGB
LFGB NFGA, NFGB, HFGA, (2P, 3P
240 70-250 NJGA, HJGA, NJJA 2,3 240 200-400
HFGB
NLGA, HLGA, NLGB,
HFD6, HFXD6 240 70-250 2,3 240 400-600
HLGB
QPH, BQH, BLH, 2 120/240 100-125
NMG, HMG 2,3 240 600-800
HQP, HBQ, HBL 3 240 100
HFD6, HFXD6 2,3 240 70-250
ED4, ED6 2,3 240 15-125
200000 200000 MD6, MXD6 2,3 240 400-800
FD6-A, FXD6-A
(cont.) 2,3 240 70-250 (cont.) HMD6, HMXD6 2,3 240 400-800
HFD6, HFXD6
JXD2-A, JD6-A, NDGA, NDGB, HDGA,
2,3 240 50-150
JXD6-A, HJD6-A, 2,3 240 200-400 HDGB
CJD6-A HJXD6-A LMG NFGA, NFGB, HFGA,
2,3 240 70-250
QT 1,2 120/240 15-30 HFGB
7
NGB,HGB,LBG 1,2,3 240 15-125 NJGA, HJGA, NJJA 2,3 240 200-400
NDGA, NDGB, HDGA, NLGA, HLGA, NLGB,
2, 3 240 50-150 2,3 240 400-600
HDGB HLGB
CIRCUIT BREAKERS
MOLDED CASE
NFGA, NFGB, HFGA, NMG, HMG 2,3 240 600-800
240 70-250
HFGB MD6, MXD6,
400 2,3 240 500-800
NJGA, HJGA, NJJA 240 200-400 HMD6, HMXD6
(2P, 3P)
NGB,HGB,LBG 1,2,3 240 15-125 NDGA, NDGB, HDGA,
2,3 240 50-150
NDGA, NDGB, HDGA, HDGB
2, 3 240 50-150 SCMD6,
HDGB NFGA, NFGB, HFGA,
LJGA NFGA, NFGB, HFGA, SCMD6-A 800 (3P) 2,3 240 70-250
240 70-250 HFGB
HFGB SCMD6-B
NJGA, HJGA, NJJA 2,3 240 200-400
HFD6, HFXD6 240 70-250 NLGA, HLGA, NLGB,
NJGA, HJGA, NJJA 240 200-400 2,3 240 400-600
HLGB
FD6-A, FXD6-A 2 NMG, HMG 2,3 240 600-800
240 70-250
HFD6, HFXD6 3 ED4, ED6 1 240 15
NDGA, NDGB, HDGA, ED4, ED6,
HHJD6, 2, 3 240 50-150 2,3 240 15-125
HDGB HED4, HED6
HHJXD6
NFGA, NFGB, HFGA,
240 70-250 FD6-A, FXD6-A,
HFGB 2,3 240 70-250
HFD6, HFXD6
NJGA, HJGA, NJJA 240 200-400
JXD2-A, JD6-A,
FD6-A, FXD6-A
2, 3 240 70-250 JXD6-A, HJD6-A, 2,3 240 200-400
HFD6, HFXD6
HJXD6-A
NDGA, NDGB, HDGA,
2, 3 240 50-150 LD6-A, HLD6-A 2,3 240 200-600
HDGB
HHLD6, LXD6-A, HLXD6-A 2,3 240 450-600
NFGA, NFGB, HFGA,
HHLXD6 240 70-250 1200 MD6, MXD6,
HFGB CND6-A 2,3 240 500-800
NJGA, HJGA, NJJA 240 200-400 (2P, 3P) HMD6, HMXD6
NLGA, HLGA, NLGB, ND6, NXD6, SHND6,
600 240 400-600 2,3 240 500-1200
HLGB HND6,HNXD6
(2P, 3P) NDGA, NDGB, HDGA,
QPH, BQH, BLH 2 120/240 100-125 2,3 240 50-150
HQP, HBQ, HBL 3 240 100 HDGB
ED4, ED6 2,3 240 15-125 NFGA, NFGB, HFGA,
2,3 240 70-250
FD6-A, FXD6-A HFD6, HFGB
CLD6-A 2,3 240 70-250 NJGA, HJGA, NJJA 2,3 240 200-400
HFXD6
JXD2-A, JD6-A, JXD6-A, NLGA, HLGA, NLGB,
2,3 240 200-400 2,3 240 400-600
HJD6-A, HJXD6-A HLGB
LD6-A, HLD6-A 2,3 240 200-600 NMG, HMG 2,3 240 600-800
480V Breaker Series Ratings (continued) 480V Breaker Series Ratings (continued)
Series Main Breaker Branch Breaker Main Breaker Branch Breaker
Series
Rating Max. Number Rating Max. Number
kAIR Type Amperes Type of Poles Voltage Amperes kAIR Type Amperes Type of Poles Voltage Amperes
FD6-A, FXD6-A 2,3 480 70-250 LMD6,LMXD6 2,3 480 600-800
JD6-A, JXD6-A 2,3 480 200-400 MD6,MXD6 2,3 480 400-800
SJD6-A 3 480 200-400 SMD6, SMD6-B 3 480 500-800
LD6-A 2,3 480 200-600 800 NDGA, NDGB,
LXD6-A 2,3 480 450-600 2,3 480 50-150
HMG (2P & 3P) NDGB
SLD6-A, SLD6-B 3 480 400-600 (cont.) NFGA, NFGB 2,3 480 70-250
1600
PD6, PXD6 NDGA, NDGB 2,3 480 50-150 NJGA 2,3 480 250-400
(3P)
NFGA, NFGB 2,3 480 70-250 NLGA, NLGB 2,3 480 400-600
NJGA 2,3 480 250-400 NMG 2,3 480 600-800
NLGA, NLGB 2,3 480 400-600 FD6-A, FXD6-A 2,3 480 70-250
NMG 2,3 480 600-800 JD6-A, JXD6-A 2,3 480 200-400
NNG 2,3 480 800-1200 LD6-A 2,3 480 200-600
50,000 NPG 2,3 480 1200-1600 LXD6-A 2,3 480 450-600
(cont.) FD6-A, FXD6-A 2,3 480 70-250 MD6, MXD6 2,3 480 500-800
JD6-A, JXD6-A 2,3 480 200-400 SMD6, SMD6-B 3 480 500-800
SJD6-A, SJD6-B 3 480 200-400 HND6, LMD6, LMXD6 2,3 480 600-800
LD6-A 2,3 480 200-600 HNXD6 NDGA, NDGB,
LXD6-A 2,3 480 450-600 2,3 480 50-150
NDGB
SLD6-A, SLD6-B 3 480 400-600 NFGA, NFGB 2,3 480 70-250
18-2000
RD6, RXD6 NDGA, NDGB 2,3 480 50-150 NJGA 2,3 480 250-400
(3P)
NFGA, NFGB 2,3 480 70-250 1200 NLGA, NLGB 2,3 480 400-600
NJGA 2,3 480 250-400 (2P & 3P) NMG 2,3 480 600-800
NLGA, NLGB 2,3 480 400-600 NNG 2,3 480 800-1200
NMG 2,3 480 600-800 LMD6,LMXD6 2,3 480 600-800
NNG 2,3 480 800-1200 MD6, MXD6 2,3 480 400-800
NPG 2,3 480 1200-1600 ND6,NXD6 2,3 480 800-1200
HDGA, 150 NDGA, NDGB,
NDGA, NDGB 2,3 480 50-150 2,3 480 50-150
HDGB (2P & 3P) NDGB
BQD, CQD 1,2,3 277/480 15-100 HNG
NFGA, NFGB 2,3 480 70-250
ED4, HED4 1 277 15-100 NJGA 2,3 480 250-400
HFD6,
ED4, ED6, HED4, NLGA, NLGB 2,3 480 400-600
HFXD6 2,3 480 15-125
250 HED6 NMG 2,3 480 600-800
(2P & 3P) NDGA, NDGB 480 50-150 65,000 NNG 2,3 480 800-1200
2,3
NFGA, NFGB 480 70-250 (cont.) FD6-A, FXD6-A 2,3 480 70-250
HFGA, NDGA, NDGB 480 50-150 NDGA, NDGB,
2,3 2,3 480 50-150
HFGB NFGA, NFGB 480 70-250 NDGB
HED4, ED4 1 277 15-100 NFGA, NFGB 2,3 480 70-250
FD6-A, FXD6-A 2,3 480 70-250 HPD6, 1600 NJGA 2,3 480 250-400
HJD6-A, JD6-A, JXD6-A 2,3 480 200-400 HPXD6 (3P)
NLGA, NLGB 2,3 480 400-600
HJXD6-A NDGA, NDGB 2,3 480 50-150
NFGA, NFGB 2,3 480 70-250 NMG 2,3 480 600-800
NJGA 2,3 480 250-400 NNG 2,3 480 800-1200
NDGA, NDGB 2,3 480 50-150 NPG 2,3 480 1200-1600
400
NFGA, NFGB 2,3 480 70-250 LMD6,LMXD6 2,3 480 600-800
(2P & 3P)
NJGA 2,3 480 250-400 MD6, MXD6 2,3 480 400-800
HJGA
1 277 15-125 ND6,NXD6 2,3 480 800-1200
NGB,HGB,LBG 2 277/480 15-125 NDGA, NDGB 2,3 480 50-150
3 277/480 15-125 NFGA, NFGB 2,3 480 70-250
1600
7
1 277 15-125* HPG
HHJD6, (2P & 3P) NJGA 2,3 480 250-400
NGB,HGB,LBG 2 277/480 15-125*
HHJXD6 NLGA, NLGB 2,3 480 400-600
3 277/480 15-125*
NMG 2,3 480 600-800
CIRCUIT BREAKERS
MOLDED CASE
ED4, HED4 1 277 15-100
FD6-A, FXD6-A 2,3 480 70-250 NNG 2,3 480 800-1200
JD6-A, JXD6-A 2,3 480 200-400 NPG 2,3 480 1200-1600
65,000
LD6-A 2,3 480 200-600 FD6-A, FXD6-A 2,3 480 70-250
HLD6-A,
LXD6-A 2,3 480 450-600 JD6-A, JXD6-A 2,3 480 200-400
HLXD6-A
NDGA, NDGB 2,3 480 50-150 LD6-A 2,3 480 200-600
NFGA, NFGB 2,3 480 70-250 LXD6-A 2,3 480 450-600
NJGA 2,3 480 250-400
NDGA, NDGB 2,3 480 50-150
NLGA, NLGB 2,3 480 400-600 HRD6, 18-2000
600 NFGA, NFGB 2,3 480 70-250
(2P & 3P) 1 277 15-125 HRXD6 (3P)
HHLD6, NJGA 2,3 480 250-400
NGB,HGB,LBG 2 277/480 15-125
HHLXD6 NLGA, NLGB 2,3 480 400-600
3 277/480 15-125
1 277 15-125* NMG 2,3 480 600-800
NGB,HGB,LBG 2 277/480 15-125* NNG 2,3 480 800-1200
3 277/480 15-125* NPG 2,3 480 1200-1600
HLGA,
NDGA, NDGB 2,3 480 50-150 1 277 15-125*
HLGB LDGA, 150
NFGA, NFGB 2,3 480 70-250 NGB,HGB,LBG 2 277/480 15-125*
NJGA 2,3 480 250-400 LDGB (2P & 3P)
3 277/480 15-125*
NLGA, NLGB 2,3 480 400-600 1 277/480 15-100
FD6-A, FXD6-A 2,3 480 70-250 CFD6 BQD, CQD
2,3 277/480 15-30
JD6-A, JXD6-A 2,3 480 200-400 1 277 15-125*
LD6-A 2,3 480 200-600 NGB,HGB,LBG 2 277/480 15-125*
LXD6-A 2,3 480 450-600 3 277/480 15-125*
LMD6, LMXD6 2,3 480 600-800 100,000
LFGA, NDGA, NDGB,
250 2,3 480 50-150
HMD6, 800 MD6, MXD6 2,3 480 400-800 LFGB HDGA, HDGB
HMXD6 (2P & 3P) (2P & 3P)
NDGA, NDGB, NFGA, NFGB,
2,3 480 50-150 2,3 480 70-250
NDGB HFGA, HFGB
NFGA, NFGB 2,3 480 70-250 HFD6, HFXD6 2, 3 480 70-250
NJGA 2,3 480 250-400 HHFD6, 1 277 15-125*
NLGA, NLGB 2,3 480 400-600 HHFXD6 NGB,HGB,LBG 2 277/480 15-125*
NMG 2,3 480 600-800 3 277/480 15-125*
480V Breaker Series Ratings (continued) 480V Breaker Series Ratings (continued)
Series Main Breaker Branch Breaker Series Main Breaker Branch Breaker
Rating Max. Number Rating Max. Number
kAIR Type Amperes Type of Poles Voltage Amperes kAIR Type Amperes Type of Poles Voltage Amperes
ED4, ED6, HED4, FD6-A, FXD6-A 2,3 480 70-250
1 277 15-100
HED6
HFD6-A, HFXD6-A 2,3 480 70-250
HFD6, HFXD6,
2,3 480 70-250 JD6-A, HJD6-A
FXD6-A, FD6-A 2,3 480 200-400
HHJXD6, JXD6-A, HJXD6-A
NDGA, NDGB,
HHJD6, 2,3 480 50-150 LD6-A, HLD6-A 2,3 480 200-600
HDGA, HDGB
NFGA, NFGB, LXD6-A, HLXD6-A 2,3 480 450-600
2,3 480 70-250
HFGA, HFGB MD6, MXD6
400 2,3 480 500-800
NJGA, HJGA 2,3 480 200-400 HMD6, HMXD6
(2P, 3P) CND6 1200 (3P)
1 277 15-125* ND6, NXD6
CJD6-A NGB,HGB,LBG 2 277/480 15-125* 2,3 480 500-1200
HND6, HNXD6
3 277/480 15-125* NDGA, NDGB,
NDGA, NDGB, 480 50-150
2,3 480 50-150 HDGA, HDGB
HDGA, HDGB NFGA, NFGB,
LJGA NFGA, NFGB, 480 70-250
2,3 480 70-250 HFGA, HFGB 2-3
HFGA, HFGB NJGA, HJGA 480 200-400
HFD6, HFXD6 2,3 480 70-250
NLGA, HLGA,
ED4, ED6, HED4, 480 400-600
1 277 15-100 NLGB, HLGB
HED6
FD6-A, FXD6-A
HFD6, HFXD6, 2,3 480 70-250
2,3 480 70-250 HFD6-A, HFXD6-A
FXD6-A, FD6-A 100,000
HHLD6, NDGA, NDGB,
NDGA, NDGB, (cont.) 2,3 480 50-150
HHLXD6 2,3 480 50-150 HDGA, HDGB
HDGA, HDGB
NFGA, NFGB, CPD6 1600 (3P) NFGA, NFGB,
2,3 480 70-250 2,3 480 70-250
600 HFGA, HFGB
HFGA, HFGB
(2P, 3P) NJGA, HJGA 2,3 480 200-400
NJGA, HJGA 2,3 480 200-400
NDGA, NDGB, NLGA, HLGA,
2,3 480 50-150 2,3 480 400-600
HDGA, HDGB NLGB, HLGB
LLGA, NFGA, NFGB, NDGA, NDGB,
2,3 480 70-250 2,3 480 50-150
LLGB HFGA, HFGB HDGA, HDGB
HFD6, HFXD6 2,3 480 70-250 NFGA, NFGB,
2,3 480 70-250
NJGA , HJGA 2,3 480 200-400 HFGA, HFGB
FD6-A, FXD6-A HFD6, HFXD6 2,3 480 70-250
2,3 480 70-250
HFD6-A, HFXD6-A NJGA, HJGA 2,3 480 200-400
JD6-A, HJD6-A, 1600 NLGA, NLGB,
2,3 480 200-400 LPG (2,3P) 2,3 480 400-600
JXD6-A, HJXD6-A (2P, 3P) HLGA, HLGB
100,000
LD6-A, HLD6-A 2,3 480 200-600 MD6, MXD6, HMD6,
(cont.) 2,3 480 500-800
LXD6-A, HLXD6-A 2,3 480 450-600 HMXD6
MD6, MXD6, HMD6, ND6, NXD6, HND6
800 2,3 480 500-800 2,3 480 500-1200
CMD6 HMXD6 HNXD6
(3P)
NDGA, NDGB, PD6,PXD6, HPD6
2,3 480 50-150 2,3 480 1200-1600
HDGA, HDGB HPXD6
NFGA, NFGB, ED4 1 277 15-100
2,3 480 70-250
HFGA, HFGB
400 HFD6, HFXD6 2,3 480 70-250
NJGA, HJGA 2,3 480 200-400 CJD6-A
(2P, 3P) JD6-A, HJD6-A,
NLGA, HLGA, 2,3 480 200-400
2,3 480 400-600 JXD6-A, HJXD6-A
NLGB, HLGB
NDGA, NDGB, 150,000 ED4 1 277 15-100
2,3 480 50-150 HFD6, HFXD6 2,3 480 70-250
HDGA, HDGB
7
7
ED4, ED6, HED4, HED6 2,3
FD6-A, FXD6-A 2,3 70-250
JD6-A, JXD6-A, JXD2-A 2,3 200-400
SJD6-A, SJD6-B 3 200-400
CIRCUIT BREAKERS
MOLDED CASE
601-6000 LD6-A 2,3 200-600
L
(2,3P) LXD6-A 2,3 450-600
SLD6-A, SLD6-B 3 300-600
SMD6, SMD6-B 3 500-800
SND6, SND6-B 3 500-1200
PD6, PXD6, SPD6 3 1200-1600
RD6, RXD6 3 1600-2000
7
CIRCUIT BREAKERS
MOLDED CASE
General Specifications
Molded case circuit breakers shall provide circuit overcurrent protection with
inverse time and instantaneous tripping characteristics and shall be Siemens
Sentron, Sensitrip or approved equal.
display breaker status, a max log, and a trip log. The trip
for motor short circuit protection. The magnetic trips shall be adjustable and log will retain and display date, time and type of trip
accessible from the front of all circuit breakers frames. The continuous current (overload, short circuit or ground fault) for the most
MOLDED CASE
CIRCUIT BREAKERS
rating shall be between 1 and 800 Amperes as indicated on the drawing. recent 5 trip events.
Connection Accessories
Unless otherwise noted, Mechanical lugs shall be provided with all Molded Case
Breakers. Where indicated on the drawings, compression lugs shall be provided on
1200 Ampere frame and below circuit breakers. All compression lugs shall be
supplied by the Circuit Breaker Manufacturer. Where indicated on the drawings,
UL listed plug-in or rear connectors shall be supplied.
7
FXD63B070-FXD63B250 f a
FJ63B070-FJ63B250 b
FJ3B070-FJ3B225
FXD63S250A a
FJ63S250 b
FJ3S225
CIRCUIT BREAKERS
MOLDED CASE
HED41B015-HED41B100 a
HE41B015-HE41B100
HED42B015-HED42B125 a
HE42B015-HE42B100
HED43B015-HED43B125 a
HE43B015-HE43B100
HED61B015-HED61B100 a
HE61B015-HE61B100
b
HE2B015-HE2B100
HED63B015-HED63B125 a
HE63B015-HE63B100 b
HE3B015-HE3B100
HFD62B070-HFD62B250 a
HF62B070-HF62B250
HFD63B070-HFD63B250 a
HF63B070-HF63B250
HHED63B015-HHED63B125 a
HED63B015-HED63B125
HJD63B200-HJD63B400 a
HJ63B200-HJ63B400 b
HJ3B125-HJ3B400
HLD63B250-HLD63B600 a
HL63B450-HL63B600 b
HL3B450-HL3B600
HMD63B500-HMD63B800 b
HN3B500-HN3B800
HND63B100-HND63B120 b
HK3B100-HK3B120
HPD63B120-HPD63B160 b
HP3B120-HP3B160
HRD63B160-HRD63B200 b
HR3B160-HR3B200
a Mechanically and electrically interchangeable. d Electricallyinterchangeable only if the system interrupting f Effective1994 — The FD6 and FXD6 types have been
b Electrically interchangeable only, refer to sales office for capacity is less than or equal to: replaced by FD6-A and FXD6-A type thermal / magnetic
further details. 200 kA at 240V AC circuit breakers — mechanically and electrically
c Electrically interchangeable only if the system interrupting 150 kA at 480V AC interchangeable with the exception that FXD6-A and FD6-A
capacity is less than or equal to: 100 kA at 600V AC have 22kA at 600V AC ratings versus 18kA at 600V AC for
200 kA at 240V AC e Refer to local sales office for replacement information. types FXD6 and FD6.
200 kA at 480V AC
100 kA at 600V AC
7
SHPD6B140LIG-SHPD6B160LIG a SPD69140G-SPD69160G b SHPF3B120G-SHPF3B160G
SHPD6B140LSIG-SHPD6B160LSIG a SPD69140NGT-SPD69160NGT b SHPF3N120-SHPF3N160G
CIRCUIT BREAKERS
MOLDED CASE
SHPD6B140LSI-SHPD6B160LSI a SPD69140NT-SPD69160NT b SHPF3N120G-SHPF3N160G
— — d BQCC1B015-BQC1B030
— — d CC1B015-CC1B030
— — d CC2B015-CC2B030
— — d CC3B015-CC3B030
— — d EF2A003, EF2H050, EF2L050, EF2A100
— — d EF2H150, EF2L150
— — d EH1B015-EH1B100
— — d EH2B015-EH2B100
— — d EH3B015-EH3B100
— — c HE2A003, HE2H050, HE2L050-HE2A100
— — c HE3A003, HE3H050, HE3L050-HE3A100
— — c HE3B015-HE3B100