                                TECHNICAL SPECIFICATIONS
                                                          FOR
                           11kV, XLPE, AERIAL BUNCHED CABLES
    Prepared by                Checked by                 Checked by                Checked by            Approved by
Er. Aamina Kirmani (AEE    Er. Manzoor Ahmad Dar    Er. Muzaffar Mukhtar Shah,   Er. Bashir Ahmad Dar,   Techno Economic
     Procurement)            (Executive Engineer)    Superintending Engineer,        Chief Engineer,      Committee vide
Er. Shazia Basharat (AE)       Purchase Officer,        Procurement Circle.            Planning &               No.
  Er. Bhavna Koul (JE)      Procurement Division.                                Procurement, KPDCL,      MD/KPDCL/TS-
                                                                                        Srinagar.           1/1920-26
                                                                                                         Dated:12/08/2022
             Specification No.
                                                              Date of Issue: 12/08/2022                       Rev 0
    CE/P&P/SPEC/2022/ABCable/11kV/007
   AB Cable (11kV)                                                                             page 1 of 12
         This is a Tender Specification for
         procurement       of    “CROSS      LINKED
         POLYETHYLENE       INSULATED    AND    PVC
         SHEATHED AERIAL BUNCHED CABLES WITH
         NEUTRAL CUM MESSENGER CONDUCTOR
         (11kV)”, subject to the modification by the
         Purchaser as per actual field requirement.
         Supplier to submit the Guaranteed Technical
         Particulars (GTP) and Drawings, after the
         award of the Contract, for approval of the
         Purchaser.
AB Cable (11kV)                                 page 2 of 12
                                           SECTION A
        TECHNICAL SPECIFICATIONS FOR CROSS LINKED POLYETHYLENE INSULATED AND PVC
                          SHEATHED 11kV AERIAL BUNCHED CABLES
       1. SCOPE:
         1.1 This specification covers design, manufacture, testing at manufacturer’s works
             before dispatch, transportation, supply and delivery of 11 kV grade XLPE
             insulated, screened all Aluminium conductor and PVC sheathed Power Cables, HT
             Aerial Bunched Cables for overhead lines.
         1.2 It is not the intent to specify completely herein all details of the design and
             construction of the equipment. However, the equipment shall conform in all
             respects to high standards of engineering, design and workmanship and shall be
             capable of performing in continuous commercial operation up to the bidder’s
             guarantee in a manner acceptable to the purchaser, will interpret the meanings
             of drawings and specifications and shall have the discretion to reject any work or
             material which, in his judgment, is not in accordance there with.
             The Cables shall be suitable for Climatic conditions as listed in Section -B.
       2. COMPOSITION OF THE CABLE:
       The composite cable shall compose of three single-core cables twisted around a
       bare aluminium alloy messenger wire, which will carry the weight of the cable.
       3. RATED VOLTAGE:
       The rated voltage of the cables shall be 11kV and the maximum operating
       voltage shall be 12kV.
       4. APPLICABLE STANDARDS:
       Unless otherwise stipulated in this specification, the following standard with up to
       date amendment shall be applicable.
         S.NO      Indian Standards        Title                                      International
                                                                                      standards
        1          IS-8130/1984            Specification for conductors for insulated        -
                                           cables
        2          IS-398 (PART-IV)        Specification for aluminium alloy                 -
                                           conductor
        3          IS -7098 (PART-         Specification for cross linked                     -
                   II)/1979                Polyethylene insulated PVC Sheathed
                                           cables
AB Cable (11kV)                                                                   page 3 of 12
       5. DETAILS OF SINGLE CORE CABLE
       5.1        The cable conductors shall be H 4 grade class 2 Aluminium Conductors complying
                  with the requirements as specified in IS-8130-1984 with latest amendments.
                  The cable conductors shall be of round, stranded and compacted aluminium
                  of nominal cross sectional area 35mm2,50mm2,70mm2,,95 mm2,120 mm2 ,150
                  mm2 and 185 mm2.Conductor shall be clean & reasonably uniform in size and
                  shape and its surface shall be free from sharp edges. Corresponding number of
                  wires in the conductor shall be as given in the table below:
           Nominal       Maximum D.C           Minimum no.     Nominal           Max short circuit
           cross         resistance at 20      of strands      thickness of      current for 1 sec
           sectional     degree Celsius                        insulation        (KA)
           area of Al.                                         (mm)
           conductor
           35            0.868                 6               3.6               3.4
           50            0.641                 6               3.6               4.72
           70            0.443                 12              3.6               6.7
           95            0.32                  15              3.6               8.96
           120           0.253                 15              3.6               11.32
           150           0.206                 15              3.6               14.16
           185           0.164                 30              3.6               17.39
     5.2       Conductor Screen
                The conductors screen shall be of extruded semi-conducting cross linked
                polyethylene compound of thickness not less than 0.5 mm.
     5.3        Insulation
               The insulation shall be of extruded cross linked polyethylene (XLPE) ,Dry gas
               cured/wet cured process of nominal insulation thickness 3.6 mm conforming to
               the physical, electrical and ageing properties of IS: 7098 (Part-II)-2011.
               The XLPE conductor shall be suitable for use where the combination of ambient
               temperature and temperature rise due to load, including temperature on
               exposure to direct sunlight results in conductor temperature not exceeding the
               following:
               Normal continuous operation             Short circuit operation
                             90°C                                    250°C
AB Cable (11kV)                                                                    page 4 of 12
     5.4 Insulation screen
       The insulation screening shall consist of two parts; namely metallic & non metallic. Non
       metallic part shall consist of a layer of extruded semi-conducting compound and shall
       be applied directly over the insulation of each core. Thickness of non-metallic part
       should be 0.6 mm.
       The metallic part shall be non magnetic and shall be applied over the non-metallic part
       of insulation screening of individual core. Metallic screening material shall be annealed
       Copper tape. Thickness of Copper tape should be minimum 0.06 mm.
     5.5 Outer –Sheath :-
       Over the metallic screen the Cable shall be provided with extruded PVC outer sheath.
       The composition of the PVC compound for outer sheath shall be Type ST2 of IS-5831-
       1984 with latest amendments. The colour of the outer sheath shall be black. The
       nominal & minimum thickness of the sheath shall not be less than the standard values
       specified in the table No. 7 of IS-7098(Part-II)/2011. Outer surface of the Cable shall be
       ultra-violet Ray resistant.
6.     MESSENGER (NEUTRAL CONDUCTOR)
     6.1     The bare messenger wire shall consist of aluminium alloy wires, generally
             conforming to IS:398 (Part IV)– 1979.Messasnger conductor shall be stranded,
             compacted ,circular and shall have smooth round surface to avoid damage to
             the outer insulating sheath of single-core phase cables twisted around the
             messenger.
     6.2     There shall be no joints in any wire of the stranded messenger conductor
             except thosemade in the base rod or wire before finally drawing.
     6.3     The technical characteristics of messenger wire shall be as follows:
                                       Messenger Conductor (Stranded Al Alloy IS 398 Part-4)
        Nominal Cross sectional
                                   Nominal Area of      No. of Strand of          Maximum DC
       Areaof Phase Conductor
                                  Aluminium Alloy in    Aluminium Alloy         resistance at20oC
       (sq. mm)
                                  Messenger Wire (sq.                               (ohm/km)
                                        mm)
                  35                     70                      7                   0.493
                  50                      70                     7                   0.493
                  70                      70                     7                   0.493
AB Cable (11kV)                                                                     page 5 of 12
                    95                       70                         7              0.493
                    120                      95                     19                 0.351
                    150                     120                     19                 0.283
                    185                     150                     19                 0.229
       6. TESTS
       The cables offered should have been fully type tested as per the relevant standards
       at any NABL accredited laboratory of National repute. The bidder shall furnish the
       type test reports along with the bid, which shall not be more than ten years prior to
       the date of publication of tender.
      The following tests shall be carried out on the single-core cables as per IS-7098 (Part-II).
         7.1      Type Tests
               a)      Tests on conductor:
                     i) Tensile test
                     ii) Wrapping test
                     iii) Resistance test
               b)        Tests for thickness of insulation and sheath
               c)        Physical tests for insulation:
                         i)   Tensile strength and elongation at break
                         ii)  Agency in air oven
                         iii) Degree of cross linking
                         iv) Hot set test
                         v)   Shrinkage test
                         vi) Water absorption test ( gravimetric)
               d)        Physical tests for outer sheath:
                         i) Tensile strength and elongation at break
                         ii) Ageing in air oven
                         iii) Shrinkage test
                         iv) Hot deformation
                         v) Loss of mass in air oven
                         vi) Heat shock.
                         vii) Thermal stability
                         viii) Carbon black content of polythene sheath
               e)        Partial discharge test
AB Cable (11kV)                                                                      page 6 of 12
               f)          Test on extruded semi-conducting screens
                             i) Test for strippability of semiconducting strippable insulation screen(when
                                 applicable)
                             ii) Volume resistivity
               g)           Thermal ageing test for complete cable
               h)           Bending test
               i)           Dielectric Power factor test:
                            i) As a function of voltage
                            ii) As a function of temperature
               j)           Insulation resistance (volume resistivity ) test
               k)           Heat cycle test
               l)           High voltage test
               m)           Flammability test for PVC Sheathed cables
       7.2           Acceptance Test
                      a.    Tensile Test
                      b.    Wrapping Test
                      c.    Conductor resistance test
                      d.    Test for thickness of insulation and sheath
                      e.    Hot set test for insulation
                      f.    Tensile strength and elongation at break test for insulation and sheath
                      g.    Partial discharge test (for screened cables only)
                      h.    High voltage test
                      i.    Insulation resistance (volume resistivity) test
                      j.    Tests for cross linking for extruded semi conducting screen
       7.3          Routine Tests
                      a. Conductor resistance test
                      b. Partial Discharge Test
                      c. High voltage test
         7.4        The following tests shall be carried out on the bare messenger wire in
               accordance with IS: 398 (Part-IV).
                    Type Tests/Acceptance Test
                         a) Breaking Load Test (on finished wire)
                         b) Elongation Test
                         c) Resistance Test
AB Cable (11kV)                                                                           page 7 of 12
  7.5 CHALLENGE CLAUSE:
      Purchase reserves the right to have the material, received after the inspection by
      the authorized inspecting officer, again tested for any parameter(s) from
      approved/NABL Accredited testing house/in house technique of the Purchaser. The
      results if found deviating/unacceptable or in non-compliance with the approved
      GTP’s, the lot shall be rejected and bidder shall arrange to replace the rejected LOT
      within thirty (30) days of such detection at his cost including to and fro
      transportation.
   8. GUARANTEED TECHNICAL PARTICULARS:
         The manufacturer shall furnish the guaranteed technical particulars of the cable
         offered in the GTP format provided in section C.
    9.    CABLE IDENTIFICATION
         The Cable shall be identified throughout its length by the following information by
         means of a printed tape as per IS-7098(part-II) Identification shall be given on any
         one of the insulated conductor of cables.
                i.      Manufacturer’s name or trade mark.
                ii.     Voltage grade.
                iii.    Year of manufacture
                iv.     Name of Purchaser
         The Cables shall also be marked with the Standard Mark (BIS/ISI Mark). The
         requisite BIS license corresponding to IS -7098(part-II) shall also be furnished along
         with the bid without which the bid shall be treated as non-responsive.
         The identification shall repeat after every 1000 mm along the length of the cable.
 10.     PACKING
         The cables, as per specified delivery lengths, shall be securely wound /packed in
         non- returnable wooden drums, capable of withstanding rough handling during
         transport by Rail, Road, etc. The packing should withstand storage conditions in
         open yards. The cable drums shall conform to IS-10418:1982. The dimensional
         drawings of wooden drums shall be furnished after Purchase order both as hard
         copy and soft copy (PDF format and AutoCAD format). The drum shall be provided
         with circumferential lagging of strong wooden planks. The end of the cable shall be
         sealed with good quality heat shrink sealing caps. The sufficiently required
         additional sealing caps shall be supplied for use of testing during laying and jointing
AB Cable (11kV)                                                                      page 8 of 12
       at site and to seal spare lengths of cable. The packing should be able to withstand
       the rigorous of transport. Wood preservative shall be applied to the entire drum.
       Each drum shall have the following information in bold letters in English stenciled
       on it.
                  a.   Ref: IS-7098(part-II)
                  b.   Name & Address of the manufacturer, Trade name/Trade mark/Brand
                  c.   ISI Marking
                  d.   Type of Cable & Voltage Grade
                  e.   Nominal Cross Section area of phase conductor
                  f.   Length of Cable on drum (Meters)
                  g.   Number of lengths on the drum (if more than one)
                  h.   Direction of rotation of drum (by means of an arrow)
                  i.   Gross weight (in Kg)
                  j.   Country of Manufacture
                  k.   Year of Manufacture
                  l.   Owners purchase order reference.
 11.   CABLE LENGTHS:
       The cables shall be supplied in continuous lengths of 500 m with +5% tolerance.
       Where the ordered quantity is not multiple of 500 m and the incremental quantity is
       very small, the same may be included in one of the drums. Otherwise, an additional
       length for the incremental quantity will be supplied.
 12.   INSPECTION AND QUALITY CONTROL:
       The Manufacturer shall furnish a complete and detailed quality plan for the
       manufacturing process of the cable. All raw materials shall conform to relevant
       applicable standards and tested for compliance to quality and requirement. During
       the manufacturing process, at all stages, inspections shall be made to check the
       physical and dimensional parameters, for verification to compliance to the
       standards. The Manufacturer shall arrange, for inspection by the purchaser, during
       manufacture with one month advance notice for verifying the various stage
       inspections as specified in the quality assurance plan enclosed to verify the quality
       control            process               of           the            Manufacturer.
AB Cable (11kV)                                                                   page 9 of 12
                                              SECTION -B
                              CLIMATIC AND ISOCERAUNIC CONDITIONS (CIC)
  1. The climatic and isoceraunic conditions at the site of work are approximately given
     as under:
S.No.                           Description                                  Values
   i.    Max. temp of air in shade                                          30.60C
  ii.    Min. temp of air in shade                                           -200C
  iii.   Max. temp of air in sun                                              450C
  iv.    Height above sea level (Approx.)                                   1600 m
  v.     Max. relative humidity                                               90%
  vi.    Min. relative humidity                                               15%
 vii.    Average no. of thunder storm days per year                            54
 viii.   Average rainfall                                                    80 cm
  ix.    Wind Zone                                                          WZ – 3
   x.    Average number of rainy days per year                                106
  xi.    Seismic Zone                                                        SZ – 5
 xii.    Area of installation                                                 HSZ
                                                                     HSZ = Heavy Snow Zone, LSZ = Light Snow Zone
                2.     Communication and Transport
The nearest railway station is Jammu/Udhampur on the broad gauge line and is connected to the
Divisional Stores by a metal road. The equipment is required to pass en-route through various
Tunnels on NH-44. The weights and maximum dimension of the packages suitable for transportation
through tunnel route are as follows:
          i.         Length                                       7.0m
          ii.        Width                                        3.0m
         iii.        Height                                       4.55m
         iv.         Weight                                       40 Ton (Metric)
The supplier shall get the permissible weight and dimensions confirmed from the Highway
Authorities before proceeding with the manufacture of the equipment. It will be the responsibility of
the supplier to ensure timely and proper delivery of the equipment on door delivery at Srinagar,
through road transport. The supplier shall also ensure that the weights and dimensions of the
packages which are suitable to be carried by road transport up to Srinagar.
AB Cable (11kV)                                                                   page 10 of 12
                                              SECTION –C
                   Guaranteed Technical Particulars for 11 kV, Aerial Bunched Cable
                             (To be filled in by the tenderer/bidder)
                                                                                        Tenderer
S.No                       Description
                                                                                        Response
        Manufacturer’s Name
        Class of Power Cable
  1      Name of the Manufacturer and country of origin
  2      Country of Manufacture
  3      Type of cable/ cable code
  4      Applicable standard
         Voltage
  5     a) Rated Nominal voltage
        b) Rated Maximum voltage
         Suitability for:
  6
         Earthed system
         Phase Conductor
        a) Nominal cross section(sq.mm)
        b) Material
  7     c) Shape
        d) Diameter of conductor(mm)
        e) Number of wires per conductor(Nos.)
        f) Nominal diameter of wire in conductor(mm)
        g) Weight of Phase Conductor per kilometer(Kg/km)
         Messenger Conductor
        a) Nominal cross section(sq.mm)
        b) Material
  8     c) Shape
        d) Diameter of conductor(mm)
        e) Number of wires per conductor(Nos.)
        f) Nominal diameter of wire in conductor(mm)
        g) Weight of Messenger Conductor per kilometer(Kg/km)
         Insulation XLPE
         a) Curing process
         b) Material/Composition
 9       c) Minimum average XLPE Insulation thickness for AB Cable
         i) 35 mm2 (mm)
        ii) 50 mm2 (mm)
        iii) 70 mm2 (mm)
 AB Cable (11kV)                                                                 page 11 of 12
       iv) 95 mm2 (mm)
       v) 120 mm2 (mm)
       vi) 150 mm2 (mm)
      vii)185 mm2 (mm)
 10    Conductor screening
      a) Material
      b) Minimum thickness
      c) Method of application
 11    Insulation screen
 A     Non metallic part
       a) Material
       b) Minimum thickness
       c) Method of application
 B     Metallic part
      a) Material
      b) Minimum thickness
 12    Outer sheath
      a) Material
      b) Minimum thickness
      c) Method of application
      d) Colour
 13    Volume resistivity of insulation
      a) At 27 degree Celsius (ohm-cm)
      b) At 90 degree Celsius(ohm-cm)
 14    Tensile strength of insulation and sheath (N/mm2)
 15    Elongation at break of insulation and sheath (%)
16     Completed cable
      a) Approx overall dia
      b) Approx weight (Kg/KM)
17     Cable drums
       a) Drum size and material
      (as per IS -10418/1982)
       b) Standard drum length and tolerance of each drum
       c) Dimensions of drum
AB Cable (11kV)                                             page 12 of 12