SmartPro LCD 120V 1500VA 900W Line- Highlights
Interactive UPS, AVR, 2U Rack/Tower, LCD, USB, ● Supports a half-load (450W) up
DB9 Serial, 8 Outlets to 11.8 min. during power
outage
MODEL NUMBER: SMART1500LCD ● Supports a full load (900W) up
to 4.4 min. during power outage
● High 98% efficiency in line
power mode
● Features 8 protected NEMA 5-
15R outlets
● Offers automatic voltage
regulation (AVR)
● LCD screen reports real-time
UPS and power status
Package Includes
● SMART1500LCD UPS
Provides reliable 1500VA/900W power protection for your desktop computer, network workstation, ● USB cable
audio/video components or media center. Protects against surges, line noise, blackouts and brownouts. ● DB9 serial cable
● Telephone cable
Description
● Mounting hardware
The SMART1500LCD SmartPro LCD 120V, 1500VA/900W Line-Interactive Uninterruptible Power Supply
provides battery backup and AC power protection against blackouts, brownouts, power surges and line ● Owner’s Manual
noise that can damage electronics or destroy data. Ideal for backing up your desktop computer or
audio/visual components, this line-interactive UPS switches to battery backup mode in milliseconds to
keep your connected equipment running long enough to save files and shut down safely with no data loss.
Eight NEMA 5-15R outlets protect against surges, as well as provide up to 11.8 minutes of UPS battery
support at half load (450W) and 4.4 minutes of support at full load (900W). Automatic voltage regulation
(AVR) corrects severe undervoltages as low as 75V and overvoltages as high as 147V without using any
battery power. EMI/RFI noise filtering improves your equipment’s performance and prevents damage. A
870-joule surge suppression rating protects your equipment from harmful power surges.
NEMA 5-15P plug with 6-foot cord connects to any NEMA 5-15R socket. Large rotatable LCD screen with
dimmer shows real-time input voltage, overload, AVR and battery statuses at a glance. Alarm sounds to
indicate power loss or low battery. With Tripp Lite’s free PowerAlert software (available via free
download), the SMART1500LCD enables safe unattended system shutdown and file saves in case of a
prolonged power failure.
Features
Reliable Battery Backup
● Provides 1500VA/900W high-performance power protection for desktop computers, audio/video
components, media centers and other electronics
1/6
● Supports 50% load (450W) up to 11.8 minutes and full load (900W) up to 4.4 minutes
● Audible alarm indicates loss of utility power or low battery
● Battery access door enables hot-swappable, user-replaceable internal batteries
Optimized Outlets
● 8 NEMA 5-15R outlets provide battery backup and protect against surges or spikes that can harm
equipment or data
Automatic Voltage Regulation (AVR)
● Corrects undervoltages as low as 75V and overvoltages as high as 147V without drawing battery
backup power
Rotatable LCD Status Screen
● Large LCD screen offers real-time status information regarding operating mode, voltage, load level,
battery charge percentage and estimated runtime in minutes
● UPS configuration options via front panel LCD include battery self-test, external battery pack
configuration, alarm on/off status and LCD brightness
● Rotates for easy viewing in both horizontal and vertical installations
AC Line, Tel/DSL and Ethernet Surge Suppression
● Surge suppression rating of 870 joules protects connected equipment and data from harmful power
surges
● Built-in RJ-45 jacks protect single-line tel/DSL or network Ethernet connection
EMI/RFI Line Noise Filtering
● Removes electromagnetic and radio frequency interference that can disrupt or damage your
equipment’s performance
USB and DB9 Communication Ports and Free PowerAlert Software
● HID-compliant USB port integrates with built-in power management and auto-shutdown of Windows and
Mac OS X
● USB & Serial ports enable data-saving unattended shutdown when used with Tripp Lite's PowerAlert
software, available via FREE download from www.tripplite.com/poweralert
● DB9 port also supports contact closure messaging for AC Present and AC Fail status
Flexible Installation Options
● NEMA 5-15P plug with 6-foot cord connects to any NEMA 5-15R socket
● Adapts to vertical or horizontal installation with included mounting hardware
● Includes 2U brackets for rack-mount installation in 2 or 4 post racks
2/6
Specifications
OVERVIEW
UPC Code 037332126146
UPS Type Line-Interactive
INPUT
Rated input current (Maximum Load) 8.6A
Nominal Input Voltage(s) Supported 120V AC
UPS Input Connection Type 5-15P; Right-Angled
Input Circuit Breakers 10A
UPS Input Cord Length (ft.) 6
UPS Input Cord Length (m) 1.8
Recommended Electrical Service 15A 120V
Input Phase Single-Phase
OUTPUT
Output Volt Amp Capacity (VA) 1500
Output kVA Capacity (kVA) 1.5
Output Watt Capacity (Watts) 900
Nominal Voltage Details 115v nominal output in battery mode
Frequency Compatibility 60 Hz
Output Voltage Regulation (Line -18%, +8%
Mode)
Output Voltage Regulation (Battery 115V (+/- 5%)
Mode)
Output AC Waveform (AC Mode) Sine wave
Output AC Waveform (Battery PWM sine wave
Mode)
Nominal Output Voltage(s) 110V; 115V; 120V
Supported
Output Receptacles (8) 5-15R
Individually Controllable Load Banks No
BATTERY
Full Load Runtime (min.) 4.4 min. (900w)
Half Load Runtime (min.) 11.8 min. (450w)
DC System Voltage (VDC) 24
3/6
Battery Recharge Rate (Included Less than 4.5 hours from 10% to 90%
Batteries)
Internal UPS Replacement Battery IMPORTANT BATTERY REPLACEMENT INFORMATION > If your SMART1500LCD UPS has no battery
Cartridge replacement door, please contact a local electronics repair technician to source and install a matching replacement
battery; If your SMART1500LCD UPS is equipped with a battery access door, please order Tripp Lite <a
class="productLink" href="//www.tripplite.com/ups-battery-replacement-for-smart1200lcd-smart1500lcd-
smart1500lcdxl-smx1500lcd~RBC1500">RBC1500</a> (quantity 1) replacement battery
Expandable Runtime No
VOLTAGE REGULATION
Voltage Regulation Description Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 75 to 147
Overvoltage Correction Input voltages between 128 and 147 are reduced by 12%
Undervoltage Correction Input voltages between 93 and 107 are boosted by 14%
Severe Undervoltage Correction Input voltages between 75 and 92 are boosted by 30%
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display Backlighted LCD screen offers detailed UPS status information, configuration options and Error message reporting;
STATUS INFORMATION includes Input Voltage, Output Voltage, Estimated Runtime (minutes), Output Load
Percentage, Output Load Wattage, Battery Charge Percentage, Graphical 5-Bar Battery Charge Level and UPS
Operating Mode Display / CONFIGURATION OPTIONS include Power Sensitivity, LCD Status Information Scrolling,
Alarm Disable, LCD Brightness and Self Test / REPORTED ERROR MESSAGES include Replace-Battery and
Overload conditions; LCD Screen rotates for vertical or horizontal UPS placement
Switches ON/OFF/MODE button provides UPS on/off power control (long-press) and advances the LCD screen display (short
tap); MUTE/ENTER button provides temporary alarm cancel, plus selection and confirmation of on-screen
configuration options
Alarm Cancel Operation Press the MUTE/ENTER button during a power failure to silence the alarm; Once silenced, alarm will re-sound to
indicate low-battery status
Audible Alarm Audible alarm indicates power-failure and low-battery status; Alarm can be disabled entirely via front panel LCD
interface (see manual)
LED Indicators Front panel LCD display
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating 870
UPS AC Suppression Response Instantaneous
Time
UPS Dataline Suppression 1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet
UPS Dataline Suppression Details 168 joules; Compatible with POE applications
EMI / RFI AC Noise Suppression Yes
PHYSICAL
Cooling Method Fan
Included Mounting Accessory Included mounting brackets enable installation in 2 and 4 post racks, plus upright tower configurations; Set of 4
Description rubber-feet enable no-slip horizontal desktop placement
Installation Form Factors Supported 2 post 19 inch rackmount; 2 post front mount; 4 post 19 inch rackmount; Tower
with Included Accessories
Minimum Required Rack Depth (cm) 34.29
4/6
Minimum Required Rack Depth 13.5
(inches)
Primary Form Factor Rackmount
Primary UPS Depth (mm) 267
Primary UPS Height (mm) 89
Primary UPS Width (mm) 438
Rack Height 2U
Shipping Dimensions (hwd / cm) 19.81 x 38.81 x 55.30
Shipping Dimensions (hwd / in.) 7.80 x 15.28 x 21.77
Shipping Weight (kg) 13.83
Shipping Weight (lbs.) 30.50
UPS Housing Material ABS
UPS Power Module Dimensions 8.89 x 43.82 x 26.67
(hwd, cm)
UPS Power Module Dimensions 3.5 x 17.25 x 10.5
(hwd, in.)
UPS Power Module Weight (kg) 13.61
UPS Power Module Weight (lbs.) 30
ENVIRONMENTAL
Operating Temperature Range +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature Range +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity Up to 95%, non-condensing
AC Mode BTU / Hr. (Full Load) 78
AC Mode Efficiency Rating (100% 98%
Load)
COMMUNICATIONS
Network Monitoring Port Description Supports detailed monitoring of UPS and site power conditions; DB9 provides contact-closure notification of AC
Present (pins 1,9 connected) and AC Fail (pins 1,8 connected)
PowerAlert Software For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at
http://www.tripplite.com/poweralert
Communications Cable USB and DB9 Serial cabling included
WatchDog Compatibility Supports Watchdog application, OS and hard-reboot restart options for remote applications
Communications Interface Contact closure; DB9 Serial; USB (HID enabled)
LINE / BATTERY TRANSFER
Transfer Time 4 milliseconds (AC to battery mode); 1 millisecond (Battery to AC mode)
Low Voltage Transfer to Battery 75
Power (Setpoint)
5/6
High Voltage Transfer to Battery 147
Power (Setpoint)
SPECIAL FEATURES
Cold Start (Startup in Battery Mode Cold-start operation supported
During a Power Failure)
Green Energy-Saving Features Greater than 95% efficiency - GREEN UPS
STANDARDS & COMPLIANCE
UPS Certifications Meets FCC Part 15 Category B (EMI); Tested to CSA (Canada); Tested to NOM (Mexico); Tested to UL1778 (USA)
UPS Certification Details UL1778: 2014 R8.15 5TH EDITION; CSA-C22.2 NO. 107.3-14 3RD EDITION; FCC Part 68 Certification Number
5WSWP00B001; Industry Canada Certification Number 3449-001, REN: 0.1
WARRANTY
Product Warranty Period (U.S. & 3-year limited warranty
Canada)
Product Warranty Period (Latin 3-year limited warranty
America)
Product Warranty Period 2-year limited warranty
(International)
Product Warranty Period (Mexico) 3-year limited warranty
Connected Equipment Insurance $250,000 <a class="insuranceLink" href="//www.tripplite.com/support/insurance-policy">Ultimate Lifetime
(U.S., Canada & Puerto Rico) Insurance</a>
© 2020 Tripp Lite. All rights reserved. All product and company names are trademarks or registered trademarks of their respective holders. Use of them does
not imply any affiliation with or endorsement by them. Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice.
Tripp Lite uses primary and third-party agencies to test its products for compliance with standards. See a list of Tripp Lite's testing agencies:
https://www.tripplite.com/products/product-certification-agencies
6/6