www.mgeups.

com

“THE MGE CHALLENGE”

Galaxy 3000
NOW PARALLEL READY !!!!!!

w Scalable and ready to grow with


your upcoming power demands.
Why a UPS?

w Power is not a certainty


w 35% of business equipment is power
sensitive
w Most business will experience 14
power quality events per year

Actual study of US Power Quality. SOURCE: EPRI


Galaxy 3000

w Galaxy 3000 combines leading-edge power


electronics technologies to deliver superior
capacity, performance and data protection.
w Single modules in 10kVA, 15kVA, 20kVA and
30kVA.
w Parallel ready up to 4 modules to achieve
90kVA with redundancy.
w Comprehensive remote monitoring and
network integration.
w Standard features include: fault tolerance
and high availability.
w Scalable to meet your future expansion
needs.
w UL-924 Battery Systems
Galaxy 3000
Unique Features and Benefits

Feature Benefit
Quiet Operation limits noise disturbances

Remote Monitoring and Alert


easily check on UPS status and immediately be alterted to any problems
Management

Voltage Stabliziation Technology


manages surges from server start-ups without any voltage deviations
for IT equipment start up surges

no requirement for costly generator oversizing to ensure UPS/generator


Generator Frienly Technology
compatability

Fault tolerant architecture UPS can safely manage and clear faults on the output

True On-Line Doble Conversion


true isolation from hazzards of the raw utility power
Technology

Low Cost of Ownership the ultimate combination of overall cost and reliability

Protected by over 120 Field Service


local factory help is close by if ever needed
Engineers

Digital Power Quality Management digitally regulates output voltage for lab grade power
Contractor Friendly Power
fast, easy and economical installation
Terminals
Galaxy 3000 offers 10 features that really matter to
customers

1. Lower cost of ownership


2. Parallel Ready
3. Scalable and ready to grow with your upcoming power demands.
4. A incredible reliability track record and large installation base
5. Easy interfacing with networks and monitoring systems
6. Clean utility power – no reflected distortion
7. Fault tolerant circuitry
8. Load surge management technology
9. Generator compatibility and smaller generator sizing
10.Backed by close by Factory Field Engineers
Power Range

w Single Modules Parallel Modules


w 10 kVA (8 kW) 20kVA (16kW)
w *15 kVA (12 kW) 30kVA (24kW)
w 20 kVA (16 kW)
w 30 kVA (24 kW)

* micro cabinet and standard cabinet UPS provides 30 kVA


208 V input / 208 V output standard (60 Hz) 0.8 PF Output 26 kVA
220 / 480 / 600 input or output available
50 Hz models available (different offering)

Output Typical UPS


UPS provides
Power operating range
0-70% load
unity PF Output
kW = kVA

0 kVA
Technical Specifications
Single Module Standard cabinet
18” 18” 33” 33”

Wall
Mounted MBP

42 Pole External 62.5”


Auxiliary UPS Module
Distribution Battery
Cabinet 208 V in
Cabinet Cabinet
(optional) 208 V out q Wall mounted external
(optional) (optional)
Maintenance Bypass also
available (2 or 3 CB)

36”

q Optional for long backup up times.


No battery inside UPS cab when
q 42 pole distribution this option used.

Can contain one or all of the


following options
q External Maintenance Bypass (2 or 3 q Includes UPS module with internal
CB) batteries

q 24 pole distribution q Optional input isolation or input


voltage conversion transformer (208,
q Output voltage conversion transformer 220, 480 or 600 V)
(208, 220, 480 or 600 V)
Technical Specifications
micro cabinet

6” 23”

w A smaller form factor –offer is


limited to:
> 10-15 kVA
Wall
Mounted MBP > 208/208
49”
Top Entry
UPS Module
> with internal battery
Cabinet
w Not available with any auxiliary
cabinets
q Wall mounted external
Maintenance Bypass 30”
also available (2 or 3 CB)

q Top entry
cabinet

q UPS Module with internal batteries


Technical Specifications
Parallel Module Standard cabinet
33” 33”
18” 18”
33”

External
UPS Module 62.5”
Battery
208 V in System Bypass 62.5”
Cabinet 42 Pole 42 Pole
208 V out Cabinet
(optional)

36” 36”

q Optional for long backup up q Optional up to 2 x 42


times. No battery inside UPS pole distribution
cab when this option used.

q 2CB or 3CB Version


q 60kVA or 90kVA Capacity
q Includes UPS module with q Accepts up to 4 UPS parallel
internal batteries module outputs.
q 208V/208V 60Hz
Galaxy 3000 Auxiliary Cabinet

w Galaxy 3000 has a single auxiliary


cabinet that can be ordered with:
> External Maintenance Bypass
(MBP)
> 24 pole Distribution
– 42 pole distribution requires a
separate aux cabinet
> Output Transformer Output
Transformer

*standard cabinet only


MBP

Distribution

18”
Technical Specifications
Batteries

w Batteries
– not included in the base cost of the
UPS module (adder)
– internal to the UPS module for
shorter autonomies
– external battery cabinets for longer
autonomies (never both internal
and external)
– call TSG for quotes on longer run
times – may require an external
battery charger (also see Power
Battery Matrix in on-line pricing
section)
– Battery life estimated at five years
plus depending on how many
times they discharge
Technical Specifications
Options

w Distribution: provides 24 or 42 poles for circuit breakers


> Benefit: eliminating the need for a power
distribution panel board; allows the
customer to feed smaller branch circuits
directly from the UPS
w Communications Cards: UPS module is standard
with one card that have five dry; communication card port
accepts three additional cards – see communications
section.

w Seismic Bracket: brackets that secure cabinets to the


floor so it will be safe for installation in a seismic zone four
environment (i.e Southern California) per UBC 97

The distribution hosts 24 or 42


circuits that can then branch out to
feed smaller loads
Galaxy 3000 Topology

4 Port Communications Interface IGBT Power Factor Corrected


Rectifier

Microcontroller Management
System

IGBT PWM Inverter


Internal Maintenance Bypass

Battery Breaker
Power Cable Connections

4 Color Graphical User Interface


Bottom Entry Conduit
Plate Internal Sealed Low Maintenance
Battery Bank

Front Access Slide Out Battery


Trays
Galaxy 3000

Parallel Features:
208V
3PH
w Up to 4 parallel modules with MGE System Bypass
Cabinet (SBC)
> Parallel for capacity
– 1+0, 2+0, 3+0 CB
> Parallel for redundancy
– 1+1, 2+1, 3+1
CB

w Parallel up to 2 modules without a MGE System


Bypass Cabinet
> 1+1 Redundancy

w 2CB or 3CB System Bypass Cabinet 208V


> 60kVA 3PH
> 90kVA

w Up to Two - 42 Pole Distribution on SBC


w Remote Alarm Status Panel
w Secondary UPS Isolation (up to 4 Breakers)
w Field Upgrade Kits (Unitary to Parallel)
Applications

w Small to medium businesses can use Galaxy 3000


as their central UPS for power consolidation
purposes
> Simple to manage
> Network-wide communication
> Reduced TCO (Total Cost of
Ownership)

w Medium to large enterprises can use Galaxy 3000


for department or branch office needs
> Scalable architecture
> High Availability
> Easy to maintain
Typical Usage

400W 2kW 4kW 8kW


PC Rack Rack Rack
Single UPS
10kVA 20 4 2 1
15kVA 30 6 3 1.5
20kVA 40 8 4 2
30kVA 60 12 6 3

Parallel UPS
3 x 20kVA 120 24 12 6
3 x 30kVA 180 36 18 9

4th module for N+1 redundancy


Galaxy 3000 Parallel
w Pay as you grow:
> Fit the budget you have today
> Meet the future needs of your organization
> Low upfront cost adder
w Simply add a new module when you need more power
> Up to 3 times the initial capacity (up to 90kVA)
> 4th module for N+1 redundancy

30 kVA 60 kVA 90 kVA 90 kVA


N+1
Example: 2 CB Parallel System
Example: 3CB Parallel System
Example: Parallel N+1 w/No MGE System
Bypass Cab.

Customer Gear
Galaxy 3000 Single Line
True On-Line Double Conversion Topology

Double Conversion Advantages


w True isolation between the input and output
w Independence of the input and output voltages and frequency
w No-break transfer to battery or bypass power
w No reliance on batteries for frequency stabilization

Double Conversion True On-Line


Technology Line Interactive Technology
Fault Tolerant Circuitry
Manages faults without compromising the UPS

w Output faults are relatively common over the life of any electrical system –
will your UPS be able to handle them?
w No matter what the overload capacity of the inverter (i.e. 150% or 300% it’s
not enough to handle output faults which range from around 600% to infinite
current.
w Only the utility has enough power to clear most output faults safely (usually
will have 100 times + the fault clearing current of the UPS module).
w The Galaxy 3000’s inverter’s fast current limiting response protects it from
damage while safely allowing the utility to safely clear the fault via the robust
Galaxy 3000 with 150% rated
static bypass switch
fast current limiting inverter and
> (no matter how much overload fully rated transfer switch.

w Other UPS may suffer fatally from output shorts as the inverter may self
destruct if it can not current and transfer to bypass safely
inverter
fault
Brand
A

Brand A with 300% rated inverter


and slower transfer switch.
Fault Tolerant Circuitry
How fault tolerant circuitry works

w Fault tolerant circuitry relies on two critical features


> Inverter is fast enough to current limit (switch off) and
avoid being overloaded by excessive fault currents

> Static transfer switch can sustain enough current to


clear the fault with out damage
DPQ [Digital Power Quality]
The heart of MGEs performance advantage

w Output created from hundreds of variable width


pulses (Pulse Width Modulation)
w Control Loop compares output to a references
sine wave and makes adjustments or correction
pulses to maintain a “power quality envelope”

Power
Output Up to 8
Quality
Voltage cycles per
Envelo
pe mS (132 /
Feature Benefit (<1% cycle)
Variable Switching Frequency Stable and high efficiency V)
Tolerates output faults by stopping
Sub Cycle Control of Output
inverter quickly
Active cancellation of harmonics on
Error Correction Pulses
critical bus
Real Time Reference Sine Wave Precision voltage regulation
Fast Switching Frequency Superior step load performance
DPQ Advantages
Load Surge Management

w Step loads or load surges common in just about all applications


Devices with high start-up surges
> i.e. starting distribution transformers, starting banks of
servers, starting motor loads (chillers), medical imaging
equipment w IT equipment (switch mode power
> UPSs not capable of sustaining stable voltage during supplies)
step loads can compromise the load by decaying the
voltage under quick load changes w Medical imaging equipment
> Most manufacturers quote <5% on specifications but w Distribution transformers
some may not be true . w Motor loads
w Fluorescent Lighting

IT FACT: starting up one bank of


servers can cause power surges
equal to the rating of a 30 kVA UPS
and may decay your UPS voltage.
DPQ Advantages
Active Harmonic Cancellation

w Harmonics are reflected by most loads


(especially IT loads) and pollute the
critical bus
w MGEs inverter technology recognizes the
harmonics and produces correction
pulses at a high enough resolution to
cancel harmonics
w The result is that the critical bus THD is
limited to 3.5% avoiding problems
associated with high THD

reflected
UPS Output
harmonics
Clean Distortion Free Input Power
IGBT Rectifier Advantages
w Eliminates harmful distortion that is reflected back onto the utility from the UPS from disturbing sensitive
equipment sharing the utility power

UPS w/
Input Filter

UPS w/o
Input Filter

Galaxy 3000 w/
IGBT Rectifier

UPS Input
Distortion reflected back from UPS UPS Output
input onto other devices sharing (utility power)
utility power
Input Power Factor Correction
IGBT Rectifier Advantages

Input PFC (Power-factor correction) is achieved by


using a three-phase IGBT rectifier that draws a
sinusoidal input current, in phase with the voltage.
THDI < 3% (current total harmonic distortion, input
side)
w PF > 0.99 (power factor)
w No special installation precautions (i.e. oversized
neutral cables)
w No risk of harmonic problems for existing
installations (harmonics from UPS will not disturb
other loads sharing utility power)
w No bulky, expensive input filters required
w Total compatibility with an generators, even for
low loads
w Current consumption reduced by up to 20%,
allowing smaller upstream breakers, transformers
and cables
Generator Friendly Technology
IGBT Rectifier Advantages
w The Galaxy incorporates all the essential features for perfect
generator UPS compatibility

> Super wide frequency and voltage input range (<25%)


– Generator voltage often drops when first loaded; the wide
input range means the UPS won’t transfer to battery

> No leading power factor


– Generators can be forced off-line if the load (i.e. the UPS)
power factor becomes too leading

> Ultra low input THD


– Generator run cooler when distortion is lower
Less generator over sizing
> Smallest UPS to generator ratio in the industry
– Generators typically have to be oversized (often two or means significant cost
three times that of the UPS rating) to safely operate with a savings!
UPS – The Galaxy 3000 does not require significant
oversizing

> No reliance on battery battery power to regulate frequency


like Delta Conversion® technology!
– The Galaxy 3000 does not have to rely on battery power
(which reduces battery life) to maintain frequency
regulation when on generator power
Graphical User Interface

Safe, easy operation…


w Operator error is the number one reason UPS
reliability is compromised!
w Galaxy 3000’s operator interface simplifies
operation so much, even first time users can
proceed with confidence
w Displays include:

- alarm / event logs


- battery usage history
- animated power flow diagrams
- phase balancing
- operator instructions
- power graphs
Graphical User Interface
user friendly operation

Main Menu Mimic Diagram Graphs

User Instructions Detailed Measurements Load Balancing


Batteries that last…
Better managed batteries for a more reliable UPS

w Intermittent Charging Technology (only MGE)


> Uses intermittent cycles to maintain battery charge vs. a constant float
charge
> Avoids the constant strain and deterioration caused by constant float
charging
> Dramatically reduces premature battery failures that are the leading
cause UPS reliability issues
> Increases life of batteries by up to 50% (huge cost savings)
Network Integration

w 3 slots for management cards


> SNMP, Web, ModBus, etc.
Linux
» Compatible with any NMS or BMS
> Unicenter TNG, Tivoli, HP OpenView
> Insight Manager 7
IBM AIX
> MGE Enterprise Power Manager
» Fully secured web-based management
> SSL encription
Novell
> XML format

» Network-wide shutdown capabilities


> Up to 50 servers supported by Sun Solaris
management card
> Smart management of redundant
power supplies, virtualization and HP/UX
more. MacOS X
MGE Remote PowerMonitoring™

w RemotePowerMonitoring™ service provides:


> Remote monitoring and diagnostics service
> 7x24x365 monitoring by MGE’s Customer Care Center
> Customizable email alert messages sent to pager, email, or fax
> Integrated watchdog alarm assures continuous connectivity

The power of knowing you're on-line


Factory Trained Field Engineers ready to
support you on-site.

w MGE has 720 factory Field Engineers (150 North American) through the world
dedicated exclusive to MGE UPSs systems
w State of the art Customer Care Center oversees service and maintenance to
guarantee a timely and quality response
w <4 hour response in most areas w/ local parts depots
w Preventative maintenance and immediate expert response means you will be on-
line and stay on-line!

MGE Customer Care Center in 720 Factory trained Field


Automated computer diagnostics
Costa Mesa, CA Engineers world wide and
near you!
Automated Computer Aided Diagnostics

> UPS continuously runs automated


self diagnostics on all components
and alerts users as to any
abnormalities

> Field Engineers can perform more


than 300 tests instantly - isolates
potential problems to expedite
maintenance

> 100% solid state (no potentiometers


anywhere) permits computerized
adjustment of any parameter
Instant analysis of all PCBA’s – no
risk of manual calibration errors
Maintainability
simple to maintain

w Galaxy 3000 requires no maintenance for normal operation


> preventative maintenance (available through MGE Service) is suggested
on any item as a means pro-actively mitigating any potential problems and
increasing reliability
> Just like on any electronic assembly – it is suggested that over the life of
the unit the following items should be replaced to assure reliable
performance
– Batteries (suggested every five years)
– Capacitors (every 7-10 years)
– Fans (every (5-10 years)

w Full front access facilities easy service and thermal scanning (all
electromechanical connections can be scanned through the front of the UPS)
w Self calibrating boards (no trim pots or thermal drift)
w Digital diagnostics port interfaces with PC and accesses all PCBs and system
status

Full front access


Made in the USA with Pride

w Made in the USA


w The Galaxy 3000 is manufactured in a dedicated building in
the MGE campus in Costa Mesa CA.

w Prior to shipment each Galaxy 3000


is tested by automatic test stations
under the supervision of MGE test
technicians
w Every UPS function is tested and
over 100 measurements are
documented electronically.
Easy to Install

w Contractors and installer like


the Galaxy 3000’s ease of
installation
w All cable connections are easy
to access at the front on the
UPS
Galaxy 3000 Applications
Medical imaging
w Superior Step Load Performance
> Doesn’t rob from battery on step loads
– Competition cycles battery during step loads
– greatly reducing life span
– MGE has enough reserve in charger /
rectifier to supply even 100% step load
without a battery present while maintaining
precise voltage regulation
– Won’t decay voltage
> Critical for medical imaging applications which The Galaxy 3000 and Comet are a
step loads battery hundreds of times per day perfect solution for the 7500 MRI systems
in the USA
> Baggage scanning systems also utilize similar
technology (step load when imaging)
Galaxy 3000
Motor and industrial loads
w Galaxy 3000 will power these loads perfectly but must size
correctly for the application

w Motor loads
> May have up to six times the rated name plate current
when starting (check locked rotor current)
Variable
> May require an output isolation transformer in some Frequency Drives
applications to prevent “regenerative” current from being (VFDs)
fed back onto UPS

w Variable Frequency Drives (VFDs)


> Commonly used on motors to control speed and torque
> May have high in-rush conditions Electric Motors
Here are just a few of the thousands of businesses that
depend on the Galaxy 3000

There are close to 10,000 Galaxy 3000 UPS modules protecting


critical power around the world.

You might also like