MPS microgrid series
MPS microgrid
                                                                             hybrid inverter
Key strengths
  Internal integration PV interfaces, battery               Easy expansion, support PV flexible configuration.
  interfaces, load interfaces and grid interfaces
                                                           DC-coupled solution with 2% higher system efficiency.
  Support single-phase and three-phase load power
                                                           Control power AC and DC redundant power supply,
  supply at the same time.
                                                           the system is more secure and reliable.
Applications
    Off-grid mine                Off-grid island    Nomadic farm               Villages without electricity
 MPS0030/MPS0050                  MPS0100/MPS0150          MPS0250                          MPS0500
MPS microgrid series
AC(on-grid)
Model                                         MPS0030               MPS0050               MPS0100                  MPS0150            MPS0250             MPS0500
Max output power (kVA)                            33                     55                   110                    165                 275                  550
Rate output power (kW)                            30                     50                  100                     150                 250                  500
Rated voltage(V)                                                                            208/220/380/400/415
Voltage range (V)                                                                                     320~460
Rated current (A)                                 43                     72                  144                     216                 361                  722
Rated frequency (Hz)                                                                                   50/60
Frequency range (Hz)                                                                                45~55/55~65
THDi                                                                                                       <3%
Power factor                                                                           1lagging-1leading(Settable)
AC connection                                                                                        3W+N+PE
Transformer ratio                              100/400               200/400              270/400                  270/400            270/400              315/400
AC(off-grid)
Max output power (kVA)                            33                     55                   110                    165                 275                  550
Rated power (kW)                                  30                     50                  100                     150                 250                  500
Rated voltage (V)                                                                           208/220/380/400/415
Rated current (A)                                 43                     72                  144                     216                 361                  722
THDu                                                                                   ≤1% linear; or≤5% nonlinear
Rated frequency (Hz)                                                                                   50/60
Overload capacity                                                                        110% long-term, 120% 1min
PV input
Max.PV input voltage (V)                                                                                1,000
Max.PV power (kW)                               36/72                 60/120            120/180/240               120/180/240         300/360           600/660/720
MPPT module quantity                              1/2                    1/2                2/3/4                    2/3/4               5/6               10/11/12
MPPT voltage range (V)                                                                                250-850
MPPT voltage range@full load (V)                                                                      450-850
Battery
Battery voltage range (V)                      250~850               320~850              420~850                  420~850            420~850              500~850
Max. charging power (kW)                        36/72                 60/120            120/180/240               120/180/240         300/360           600/660/720
General data
                                                                                                                                  (600*720*2,050)*1+   (600*720*2,050)*2+
Dimension W*D*H (mm)                        800*800*1,900         800*800*1,900       1,200*800*2,050         1,200*800*2,050
                                                                                                                                   1,200*800*2,050      1,600*1050*2,050
Net weight (kg)                                576/607                720/750          1,120/1,150/1,180      1,250/1,280/1,310      1,980/2,010       3,265/3,295/3,325
Operation temperature (℃)                                                                         -30 ~ 55
Relative humidity                                                                          0 ~95% non-condensing
Ingress protection                                                                                         IP20
Noise emission (dB)                                                                                <70
Operating altitude                                                                        <5000m(>3,000 Derating)
Cooling                                                                                              Air Cooling
Display and communication
Display                                                                                        LCD touch-screen
BMS communication                                                                                   RS485, CAN
EMS communication                                                                                   RS485, TCP/IP
                                                     EN62109-1/-2, EN62477-1, EN61000-6-2, EN61000-6-4, South Africa NRS097-2-1:2017,
Certificates
                                                                               Pakistan & India IEC61727, IEC62116, IEC 61683
    MPS PV and battery configuration principles:
> Boost mode configuration principle - open voltage at low temperature at the limit of PV installation * number of PV panels in series ≤ the lowest voltage of the battery;
> Buck mode configuration principle - the maximum power operating voltage at the extreme high temperature of PV installation≥ the highest voltage of the battery;
> The PV and battery configurations of MPS must comply with the above configuration principles.