Photovoltaics
Now supports PylonTech LITHIUM Batteries!
MPI Hybrid Series
These hybrid solar inverters combine the features of both grid-tied and off grid
operations, and allow users to operate in 3 main modes:
          ●      Grid-Tied (Feedback)
          ●      Off Grid
          ●      Grid-Tied with Battery Backup
Available in 5KW, 5.5KW (single phase) and 10kw (3 phase), these hybrid systems
offer an excellent all-in-one solution of off-grid inverter + grid-tie inverter +
battery charger. Able to accept PV input voltage up to 900V (5K, 10K only) with
MPPT functionality, the Hybrid family can support up to max PV array sizes of up
to 14.85KW. This enables users great flexibility in running load as well as feeding
extra solar power back to grid. When grid fails, these systems will switch to
battery source like an off-grid inverter and keep load backed up. The bundled
monitoring software, SolarPower, offers powerful features that allow users total
control and access to a wide variety of operations to meet different application
demand. Hybrid models are fully compliant to and certified in VDE (Germany) and
CE standards (AS4777 available on 5.5K and 10K only).
**Optional accessories such as MODBUS card, MODBUS server, and Energy Meter are available upon request
         New Features
                                        HIGH CHARGING                                                                       STACKABLE
                                        Max battery                                                                         Supports parallel
                                        charging current                                                                    operation up to 6
                                        now up to 200A!                                                                     units max!
                                        (10K)                                                                               (4K,5K, 10K only)
                                         EMS PORT                                                                           DUAL AC INPUT
                                         this useful port is                                                                grid + generator.
                                         for emergency                                                                      Genset starter dry
                                         light load, 230V/5A                                                                contact available
                                         (4K, 5K only)                                                                      (4K, 5K only)
*Product specifications are subject to change without prior notice. MPP Solar is a registered trademark of MPP Solar Inc.
         Operation Modes
                                                                                                                   In this operation mode, users can program unit to
                                                                                                                   ● Feedback PV power to utility
                                                                                                                   ● Provide PV power to load
                                                                                                                   ● Charge battery by PV
    SOLAR                                                                                     UTILITY              Different priority settings are available in this mode.
                                                                                                                   Charging source may be selected from PV and grid
                                                                                                                   as default, PV only, or none (when     charging not
                                                                                                                   intended). All programming conditions can be done
                                                                                                                   in the CD-bundled software.
              BATTERY                                                         HOUSE LOAD
                                                                                                                   In this operation mode, the inverter will only
                                                                                                                   behave like a pure grid-tie inverter where it only
                                                                                                                   feeds back electricity to grid from PV source.
   SOLAR                                                                                      UTILITY
                                                                                                                   There is no priority setting available when this
                                                                                                                   mode is selected.
               BATTERY                                                        HOUSE LOAD
                                                                                                                  In this operation mode, grid feedback to utility is
                                                                                                                  disabled. Users can only program unit to:
                                                                                                                  ● Provide PV power to load
                                                                                                                  ● Charge battery by PV
   SOLAR                                                                                      UTILITY             Different priority settings are also available, and
                                                                                                                  grid relay may be connected to inverter to provide
                                                                                                                  support when load > 3kw. Charging source may be
                                                                                                                  selected from PV and grid, PV only, or none
                                                                                                                  (charging not intended). All programming can be
               BATTERY                                                       HOUSE LOAD                           done in the CD-bundled software.
*Product specifications are subject to change without prior notice. MPP Solar is a registered trademark of MPP Solar Inc.
  Specifications
MPI HYBRID SERIES                                                       5K                                 5.5K                                    10K
MAIN SPECS
Continuous Output                                                   5,000W                                5,500W                                10,000W
Parallel-Ready                                                Yes, up to 6 units                             No                             Yes, up to 6 units
PV INPUT RATING (GRID-TIED)
Max PV Input Power                                                  10,000W                               6,500W                                14,850W
Max PV Input Voltage                                                 900Vdc                               500Vdc                                 900Vdc
Start-up / Initial Feeding Voltage                              250 / 300 Vdc                         116 / 150Vdc                            320 / 350 Vdc
PV MPPT Range                                                   250 - 850 Vdc                         120 - 450Vdc                            350 - 850 Vdc
Max PV Input Current                                                 10A x 2                              13A x 2                                18A x 2
MPPT Tracker                                                             2                                    2                                     2
Max DC/AC Conversion Efficiency                                                                                         >96%
AC INPUT SPECS
Start-up / Auto Restart Voltage                                                                    120 - 140Vac / 180Vac (per phase)
Input Voltage Range                                                                                       170 - 280Vac (per phase)
Nominal Frequency                                                                                                    50 / 60 Hz
Max AC Input Current                                                   40A                                  40A                                    25A
AC OUTPUT SPECS
Nominal AC Output Voltage                                          208/220/230/240Vac, Single Phase                                          400Vac, 3-Phase
Output Voltage Range                                                               184 - 265Vac                                   184 - 265Vac (P-N) / 318 - 460Vac (P-P)
Output Frequency (GRID-TIE)                                                                            47.5 - 51.5Hz / 59.3 - 60.5 Hz
Output Frequency (OFF-GRID)                                                                                50 / 60Hz, auto-sensing
Output Waveform                                                                                                   Pure Sine Wave
Max Output Power (via grid relay)                                   7,000W                                6,500W                                16,000W
Max Output Power (battery)                                          5,000W                                5,500W                                10,000W
Max Efficiency                                                                          >93%                                                      >91%
BATTERY CHARGER
Nominal DC Voltage                                                                                                      48Vdc
Max Charging Current                                                  100A                                  60A                                   200A
ENVIRONMENTAL / COMMUNICATION
Communication Port                                                                                 RS232 / USB, Intelligent Slot (card)
                                                                             EN62109-1, EN62109-2, EN62040-1 / CE, VDE4105, VDE0126-1-1,
Certifications
                                                                                            AS4777/3100 (5.5K, 10K only)
Operating Temp.                                                    -10 - 50°C                             0 - 40°C                              -10 - 50°C
Operating Humidity                                                                                      0 - 90% RH (No condensing)
Dimension                                                    600*460*200mm                         450*445*110mm                            622*500*167mm
Net Weight                                                            29Kg                                  16Kg                                   45Kg
*Product specifications are subject to change without prior notice. MPP Solar is a registered trademark of MPP Solar Inc.