Ap 3002013
Ap 3002013
TABLE OF CONTENTS
Discharge
Level Control Line
hose connection
Discharge
Check Valve
(inside) Inlet Check
Valve
Pumping Action: The inlet check swings open to allow fluid in. Air inside the pump chamber
exits through an airline in the top (either pulled out under vacuum or pushed out by liquid filling
the chamber; these two modes are described in the next section).
Once the chamber is full, it is pressurized with compressed air and the inlet valve is pushed
closed. With the chamber pressurized, the liquid is forced out the discharge check valve. This
pressurization occurs for a set number of seconds, enough to clear the pump chamber, and then
the chamber is depressurized and the cycle starts over.
When the level control line is submerged in 2” of water, the control panel will begin a fill
stroke followed by a discharge stroke. This makes for one complete pumping cycle. After one
complete cycle, the panel checks for the presence of liquid; if there is liquid it will immediately
cycle again, if there isn’t the panel will wait however long it takes for enough liquid to enter the
sump and reach the 2” level again.
**This means your pump may not cycle steadily. It will cycle to match the inflow feeding the
sump.
Dual pumping systems run exactly as described above except a second pump is filling when
the first is discharging and visa versa.
F
PANEL LAYOUT
Important: All variations of the AP300 control panels share the same control box/logic
and vary by the size and capacity of the air valves/filtration/flow inducers mounted below the
box. The function of each component is identical, only the size and capacity vary.
C J
G F
H
L
AP300 Flow
Induced Panel
* The flow inducer is a form of vacuum pump that uses compressed air to generate
vacuum. Its purpose is to suck air out of the pump chamber, which pulls liquid in.
Once the fill stroke is complete (usually 3-6 seconds; see pg.14 start-up chart for factory settings)
the panel switches to the discharge stroke by closing the exhaust valve (to trap pressure in the
pump) and also cuts off air to the flow inducer while opening the discharge pressure regulator.
This discharge stroke feeds regulated, compressed air down the main airline and into the pump to
push its contents downstream.
The exhaust and vacuum generator valves are operated by piloting air valves in the control logic
located inside the control panel enclosure.
A couple of important notes; the cycling will only occur when there is enough liquid to fill the
pump chamber- the pump will not cycle (run dry) if no liquid is present unless in the ‘MANUAL
OVERRIDE’ mode. The MANUAL OVERRIDE forces the panel to cycle even if it is out of
liquid.
The cycling of the pump is relatively slow; anywhere from zero to 10 times per minute so don’t
expect the pump to ‘hammer away’. If it is cycling rapidly, it is probably has had the stroke
settings messed up and is putting out less flow than it should.
Component Identification:
The dual control panel uses the same components as the single control panel show on pg 4 with
the addition of duplicates of the REP50 discharge regulator, EXVS75 exhaust valve, flow
inducer, and FV200 flow inducer supply valve.
A- EXVS75exhaust valves
B- Flow inducers
C- FV200 flow inducer supply valves
D- REP50 discharge regulator
A
C
Discharge Piping
Try to match the discharge piping to the size of the outlet port. Avoid reducing more
than one pipe size unless imperative. The reasons and trade-offs are as follows,
1- for an average flow rate of 50 gpm, the PITBULL® will be discharging liquid at 100+
gpm in discreet bursts so friction losses need to be based on the burst flow, not the
averaged flow over time. Our pipe sizes are oversized for the average flow but
appropriate for the flow in bursts.
2- The PITBULL® will pass large solids. Watch out for pumping bigger stuff than your
piping can take.
**Note: If you are reducing the piping and have potential for large solids, consider adding a
strainer to the pump inlet. CIPC offers threaded inlet adapter (see parts section for numbers)
with big-ported strainers as an option. Or improvise your own.
Install an isolation
valve somewhere
near the discharge
outlet.
Important- when the proper line size is not possible, adding an air reservoir/receiver close to the
control panel will dampen the air supply and let the pump put out more flow rate and keep the
supply pressure to the panel steadier (for better control function).
The pump consumes air in ‘bursts’. Your airline may be able to deliver the averaged out air
flow, but can’t keep up during the ‘burst’, which causes the pressure to fall way off while the
pump is trying to discharge. A 30-120 gallon receiver (size per pump) is often the low cost cure
for this, without requiring an increased supply line.
3” 9” 4”
AP300F3 shown
11”
17”
7.5” max
depth
Mounting
holes (4)
3/4” NPT
inlet
11”
3/4” NPT x 3/4”
hose outlet to
pump
16”
Page 10 of 30 Aug
2013
Connecting the Panel to the Pump
There are two connections to make, the main airline and the control airline. Both airlines
are provided with your system and come as 15’ lengths standard.
1) Run the main airline from the hose barb on the panel under the exhaust valve to the hose
barb on the top of the tank.
2) Run the level control airline from the bottom right side of the panel to the level control
airline hose barb on the side of the pump (or other equal elevation).
Main airline
Control Box
A- Control pressure regulator (set at 70 psi) and filter B
B- *Discharge pressure regulator adjustment A
F- Fill stroke time adjustment and pop-up indicator
D- Discharge stroke time adjustment and pop-up F
indicator
E- Discharge pilot valve adjustable delay
CL- Control logic module
* Discharge pressure regulator (adjustable to 70 psi
max; to go higher than 70psi the control pressure D
must be raised first. Max is 100 psi, and will
shorten maximum stroke time)
CL
E
Page 11 of 30 Aug
2013
START-UP SETTINGS
The control panel is preset for fill (F) and discharge (D) strokes. The discharge pressure
is preset for 40 psi using the discharge pressure adjustment. When initially starting up the pump,
do not change the fill (F) and discharge (D) stroke settings and only adjust the discharge pressure
(see ‘B’ in photo above) if needed. Please see the section on adjusting settings if you have (1) a
very long pipe run, >300’ or (2) a reduction of two more pipe sizes in the discharge piping. In
those cases you will need to increase the discharge stroke.
Setting the discharge pressure. Try to determine the total dynamic head required for the
application. In simple terms, take the vertical height that the pump must push the liquid and
convert it to psi (there are 2.31 ft per 1 psi), and then add in your calculated or 'guesstimated'
friction loss (guess high if the liquid is viscous) in psi, and finally add 15 psi for a safety margin.
This total should be enough to push the liquid out of the pump at a good flow rate. Note: too
little discharge pressure will cause little (or none) fluid to exit the pump (the pump is essentially
deadheaded). Too much pressure and compressed air is wasted.
Example: The pump is in a sump 6' deep, and must pump to an elevated tank 40' above grade,
TIP: If your discharge piping size is the same as the PITBULL® the velocity will be low
enough that friction loss is negligible on shorter runs with watery fluids.
Finally, from a friction loss chart you find that the loss for 40 gpm of water flowing
through 200' of 2" pipe is 3.6 ft/100', or a total of 7.2' (3.1psi). So set the discharge regulator for
20 + 3.1 + 15 = 38.1 psi.;40 is close enough. (Note that the friction loss was small)
Page 12 of 30 Aug
2013
FACTORY SET STROKE ADJUSTMENTS
Pump Model Fill/Discharge Fill/Discharge Fill/Discharge
Flow Induced Suction lift Gravity filled
S2C/S2S 3.0 sec /2.5 sec 3.5* sec/2.5 sec 4.0 sec/2.5 sec
S3C/S3S 3.5 sec /3.0 sec 4.5* sec/3.0 sec 5.0 sec/3.0 sec
S4C/S4S 4.5 sec /4.0 sec 6* sec/4.0 sec 6.0 sec/4.0 sec
SH4C/SH4S 7.0 sec /5.0 sec 8* sec/5.0 sec 8.0 sec/5.0 sec
S6x4C/S6x4S 5.5 sec /5.0 sec 7* sec/5.0 sec 7.0 sec/5.0 sec
S6C/S6S 8.0 sec /6.0 sec 9* sec/6.0 sec 9.0 sec /6.0 sec
S8C/S8S 9.0 sec /7.0 sec 10* sec/7.0 sec 10.0 sec/7.0 sec
*suction lift times will likely go longer for lifts greater than 4 ft.
To re-set the discharge time.( Most submersed pumps will not require adjustment, and are
factory pre-set) With the pump cycling (level control line flooded) use a small blade screw
driver in the slot adjustment knob to make changes in the fill and discharge strokes. USE
YOUR WATCH WHEN FINE TUNING THE STROKES. Clockwise is longer, CCW
is shorter, the entire range is .5-8 seconds.
Discharge stroke adjustment- align
arrow with approximate time number.
Pop-up indicator *time and set with a watch to set
(above adjuster) accurately- these are not clocks and
pops out during the numbers are not accurate.
the fill stroke Pop-up indicator (below adjuster)
pops out during the discharge stroke.
If the discharge pipe run is long or restricted/reduced in size, it is likely you will need to add 20-
50% more time to the discharge stroke. *You may also need to increase the discharge pressure.
Page 13 of 30 Aug
2013
FACTORY SET STROKE ADJUSTMENTS FOR DUAL PUMP SYSTEMS
(flow induced as standard)
The settings above are based on the dual pump system running in the flow induced mode
(the liquid is pulled into the pump instead or running in by gravity. This gives a shorter, more
consistent fill stroke duration).
The time setting for the discharge stroke may be slightly long, and some compressed air
is blown down the line after the pump is emptied. In this case it is best to throttle back the
discharge line (it won’t take much) to create enough back pressure to slow the discharge stroke
down until no more air goes into the line. If that is not an option consult the factory for
additional air throttling valves to slow the discharge rate. *Also check that the discharge
pressure setting is not too high (see previous section) which would push the liquid out faster than
needed.
Page 14 of 30 Aug
2013
SETTINGS AND ADJUSTMENTS CONTINUED
Fine tuning pressure and discharge strokes (typically not needed): The settings most likely to
need adjustment are the pressure and discharge stroke duration. If inadequate pressure is used
for the conditions, then the pump will push little if any liquid downstream during the discharge
stroke.
Step One- Establish the fill time under your field conditions.
Set the discharge stroke to an excessive time. Check the chart on pg 13 for your pump and then
add another 3 seconds to the discharge setting. This excess time will insure you are starting with
an empty pump on each fill stroke.
Step Two- Find the amount of time needed to refill an empty pump.
Start the fill stroke off at least 1 second short of the recommended fill time (pg 13 again). You
can hear the tone of the flow inducer change once the pump is full (goes up in pitch).
Incrementally increase the fill stroke until you hear this pitch change, or, until liquid starts
coming out the exhaust. At this point the fill time is barely too long; shorten it by about ½
second until the spray goes away and/or the tone doesn’t change. Now the pump is getting full
but not over filled and you can go on to step three.
Step Three- Correct the discharge stroke to match the full fill stroke.
From the previous step the pump is now full at the beginning of each discharge stroke, but we
still have the discharge set intentionally too long. Start shortening the discharge stroke a little at
a time until the same flow inducer tone change and/or exhaust spray occur. At this point the
stroke length is too short to push out all of the liquid but the fill stroke allows for refilling all of
the liquid, so the pump overfills. Lengthen the stroke about ½ second to just make these
symptoms go away.
Page 15 of 30 Aug
2013
AP300XH High Flow Panel Variation
This version of the AP300 control panel is designed for very high flow applications and has the
following differences from the AP300 standard;
1) The piloted discharge regulator is replaced by a 1-1/2” or larger pilot operated regulator
that has much higher flow capacity.
2) The exhaust valve is enlarged to >2” piping, and a double acting operated ball valve or
butterfly valve replaces the EXV200.
3) Inside the control box, NRE125 regulator provides the discharge pressure control.
Please note that all basic functioning of the high flow panel is the same as the standard when it
comes to level control, stroke settings and troubleshooting.
Page 16 of 30 Aug
2013
TROUBLESHOOTING THE PUMP
THE MOST COMMON PROBLEMS DURING START-UP
If you are having difficulty with the operation of your pump please review the following
list of pump problems. This list contains the most common problems we get calls on and also
represents a group of avoidable conditions
1) Rust, scale, water slugs in the air supply fouling the filter-autodrain/valving because of not
blowing down the air supply until clear, prior to connection. For excessively wet conditions
or corroded piping, a knock-out pot (air receiver or other tank near the panel will help
immensely).
2) Exhaust splatter and fouling due to the pump being deadheaded or close to it.
3) Cycling problems due to improper layout of the airlines, with crimps, undersized airlines
substituted for the hoses supplied, restrictive quick couplings and fittings or excessive
lengths.
4) Erratic cycling due to a small diameter air supply that can't deliver the volume while
maintaining pressure. 'Control' pressure gauge falls below 40 psi during discharge stroke.
5) Pump fails to fill up and discharges a low volume per stroke because of a restriction in the
exhaust path (muffler, looped line etc.).
6) Poor setting of the discharge pressure and/or discharge time for the conditions. Stroke and/or
pressure are way off, usually from being played with unnecessarily. These conditions are all
covered in the installation and start-up of the pump. If you are having one of these problems,
and particularly if you have recently installed the pump, please review the earlier portions of
the manual for correcting the condition.
Given that the preceding section does not address your pump's condition, we suggest the
following process of test/evaluation/elimination to arrive at the source of the problem with the
least amount of servicing.
Page 17 of 30 Aug
2013
COMMON CHECK VALVE AND PIPING PROBLEMS
Page 18 of 30 July2013
CONTROL PANEL COMPONENT IDENTIFICATION
EXVS75
exhaust valve
Level control
airline connection
Flow inducer
F50/AD supply
air filter with
FV200 auto-drain. ½”
Isolation ball flow
valve ¾” inducer
REP50 supply
½” discharge valve
regulator
Quick Relief
Valve
AP300F6 panel
Flow Inducer
F100/AD supply
air filter with
auto-drain. 1”
REP100
1” discharge
Isolation ball regulator
Page 19 valve
of 302” Aug
2013
INNER CONTROL PANEL COMPONENT IDENTIFICATION
PG1.5S
NRE125 Discharge
Discharge piloting pressure gage
regulator
NREFC125AD
Control filter,
regulator, gage and
auto-drain
AP300L
complete logic PG1.0
module Control
pressure gage
FTD
Fill stroke timer
DTD
Discharge FEPC
stroke timer Dual coalescing
filter element
PB-IND
Pop-out stroke
indicators (2)
NAD125
Autodrain
CV1032
Relief valve MBR.01 R333
Orifice (2) with Discharge
cleanout wire tool piloting valve
Page 20 of 30 Aug
2013
CONTROL PANEL TROUBLESHOOTING
Start this section only after you have evaluated the pump using pages 11 to 12. This logic
sequence only makes sense if you have already eliminated the standard problems like
deadheading, low air pressure, plugged inlet already discussed. Without doing that first you may
well be wasting your time.
START
Inspect REP50/REP100
Confirm that #FV200 supply Call factory for
discharge regulators for
valve for the flow inducer is walk-thru
torn/leaking diaphragms.
outputting an air flow when disassembly of
If they are getting piloted
piloted. If not, inspect, level control
and not opening, they
clean/repair/lube or replace. components.
need repair.
Page 21 of 30 Aug
2013
TROUBLESHOOTING CONTINUED
G
B
EXV200 Exhaust valve
Page 22 of 30 H Aug
2013
FLOW INDUCER TROUBLESHOOTING AND REPAIR
Flow Inducers with side vacuum port
This style flow inducer has the air supply in the side and
pulls vacuum in the top and exhaust out the bottom. There
are (3) sections, suction, supply and exhaust.
Suction
First inspect the flow path by looking through from the
suction out the exhaust. If all clear, then there is either an
air supply problem or an adjustment problem (this is
assuming there is nothing connected to the exhaust; remove
any muffler or tubing before troubleshooting).
Compressed air
supply section Air supply- remove the supply hose from the hose barb and
confirm there is plenty of air flow and pressure (need 60 psi
or more).
Page 23 of 30 Aug
2013
REP50, REP100 and REP150 Regulators
Poppet seat
Page 24 of 30 Aug
2013
AP300 CONTROL PANEL SPARE PARTS AND COMPONENTS
Note: all panels share the enclosure and internal logic components. The differences are in the
size of discharge regulators and exhaust valves. All other parts are interchangeable.
Part # Description
****** Complete control panel with all valving and filtration
(All Models: AP300G2–G8, and AP300F2L–F8L)
AP300L Control logic module
MBR.01 Bubbler orifice (orifices (2) and clean-out tool)
NREFC125AD Combination coalescing control filter, regulator and auto-drain
FEPC Control filter element, dual particulate and coalescing.
FTD Fill stroke timer
DTD Discharge stroke timer.
PB-IND Pop-out logic indicator (F or D)
NRE125 Discharge piloting regulator
NAD125 Control filter auto-drain.
PG1.5S Discharge pressure gage.
PG1.0 Control supply pressure gage.
CV1032 Level control line relief valve.
R333 Discharge piloting valve time delay
EXVS75 Complete 3/4" stainless exhaust valve, viton seat, nitrile seal.
EXVS75IN Complete drop in replacement internal assembly
EXVS75S 3/4" SS exhaust valve seat, and seal rebuild kit
EXV200 2" exhaust valve.
EXV200K 2" exhaust valve rebuild kit
REP50 1/2" piloted discharge regulator.
REP50K 1/2" piloted discharge regulator repair kit.
REP100 1" piloted discharge regulator.
REP100K 1" piloted discharge regulator repair kit.
REP150 1-1/2" piloted discharge regulator.
REP150K 1-1/2" discharge regulator (pilot operated) repair kit.
FLOW INDUCERS
F2L Flow inducers for 2" pumps
F3L Flow inducers for 3" pumps
F4L Flow inducers for 4" pumps
F6L Flow inducers for SH4, 6x4 and 6” pumps
F8L Flow inducers for 8” and larger pumps
* Flow inducers should be exhausted into large diameter, rubber hose or approved mufflers.
Page 25 of 30 Aug
2013
MUFFLERS
ST-6B Muffler for F2–F3 flow inducers
ST-12C Muffler for F4–F8 flow inducers
Adder for threaded inlet adapter plate (same adapter as on inlet of transfer pumps).
Includes: plate with male threaded end, valve plate gasket, extra length bolts for check valve flapper posts(sealing
bolts). Pump is capable of dry-piping inlet with this adapter. Note size and construction of pump.
Page 26 of 30 Aug
2013
CIPC CHECK VALVES
CIPC recommends that customer’s stock inlet and discharge check valve internals, and in cases of
expected high wear such as abrasive slurries we recommend entire spare check valves. Following
is a list of CIPC check valve part numbers and descriptions.
Part # Size Description
2CVP/C(_) 2" CIPC steel swing check, plate style,
full port, complete assembly for S2C pumps. (Fig 20A)
2CVP/S(_) 2" CIPC 316SS swing check, plate style,
full port, complete assembly for S2S pumps. (Fig 20A)
2CVF/(_) 2" Flapper (316SS) (Fig 20B, 20D exploded )
Seat adders for check valve flappers
** (3) gaskets required for submersible (1 spare) & (4) required for transfer pumps
** CIPC strongly recommends that new gaskets be installed whenever reassembling check valves.
Page 27 of 30 July2013
CIPC CHECK VALVES CONTINUED
3CVP/C(_) 3" CIPC steel swing check, plate style,
full port, complete assembly for S3C pumps. (Fig 20A)
3CVP/S(_) 3" CIPC 316SS swing check, plate style,
full port, complete assembly for S3S pumps. (Fig 20A)
3CVF/(_) 3" Flapper (316SS) (Fig 20B, 20D exploded )
Seat adders for check valve flappers
** (3) gaskets required for submersible (1 spare) & (4) required for transfer pumps
** CIPC strongly recommends that new gaskets be installed whenever reassembling check valves.
Nitrile Good all-purpose elastomer. Medium chemical, oil and solvent resistance, good
strength, temperatures up to 170°F.
Viton Excellent resistance to oxidizers and solvents. Medium strength, temperatures up to
250°F.
Teflon Best chemical resistance of all. Inert to acid bases and solvents. Lower cycle life,
non-elastomeric, temperatures up to 300°F.
Urethane HD Best resistance to abrasion. Toughest of the elastomers, with mild chemical
resistance, temperatures up to 150°F.
EPDM Good heat and acid/base resistance. Tougher than Viton but poor solvent resistance,
temperatures up to 300°F.
** (3) gaskets required for submersible (1 spare) & (4) required for transfer pumps
** CIPC strongly recommends that new gaskets be installed whenever reassembling check valves.
4SICV 4" CIPC side inlet internal swing check, stainless steel,
for 4” high flow side inlet pumps
4SICV-DT 4” CIPC side inlet internal swing check, stainless steel, with low level
downtube, for 4” high flow side inlet pumps
6SICV 6" CIPC side inlet internal swing check, stainless steel,
for 6x4, 6” side inlet pumps
6SICV-DT 6” CIPC side inlet internal swing check, stainless steel, with low level
downtube, for 6x4, 6” side inlet pumps
8SICV 8" CIPC side inlet internal swing check, stainless steel,
for 8” side inlet pumps
8SICV-DT 8” CIPC side inlet internal swing check, stainless steel, with low level
downtube, for 8” side inlet pumps
Contact CIPC with your pump serial number for current available products
for your pump.