0% found this document useful (0 votes)
209 views1 page

Arrestor Calculation

Uploaded by

Dan Street
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
209 views1 page

Arrestor Calculation

Uploaded by

Dan Street
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 1

Surge Arrestors Local To Grid Transformer - Assessment Of Required Position

Instructions
1 Enter appropriate figures in blue cells; see notes.
2 Read off total acceptable length for d+d1+d2+dA; see figures.
Notes
N = No. of lines connected to substation (take account of typical outages) 1 line(s) Typically 1 or 2. Line Type Factor A (kV)
A = Lightning performance voltage for the line voltage/type 4500 kV See Table 1. Transmission Single conductor 4500
Urw = Equipment rated lightning impulse withstand voltage (BIL) 550 kV See EE Spec 1/2. Double conductor bundle (twin) 7000
Upl = Arrester Lightning Impulse Level 311 kV See Table 2 or 3. Four conductor bundle (quad) 11000
Lsp = Span length of first span of overhead line 300 m Distribution Unearthed wood pole 2700
Lf = Overhead line section with outage rate equal to acceptable failure rate 50 Earthed construction wood pole 900
Ra = Acceptable failure rate of protected equipment 1 failure in 1000 years 0.001 failures/year Table 1 (taken from EN 60099-5)
r = Line outage rate for first km out 2 fault(s) per 100 km per year/circuit 0.00002 failures/year/m
Arrestor Type Rated Arrestor Rated Discharge Upl (kV)
Lp = arrester protective zone = Lt = total acceptable length d+d1+d2+dA 13.0 m Voltage (kV) Current
ABB type
d
PEXLIMQ132-WV145 132 10kA 311
d
Bowthorpe type
d1
d1 2P4SR132 132 10kA 333

Arrestor dA Bushing dA Arrestor Bushing


Bowthorpe
Metal-oxide gapless
36
45
10kA
10kA
102
123
d2 Table 2

Turret Arrestor Type Rated Arrestor


Voltage (kV)
Rated Discharge Upl (kV)
Current
Gapped to IEC 99-1 132 10kA Heavy-duty 343.2
d2 36 10kA Heavy-duty 100.8
Metal-oxide gapless 132 10kA 303.6-435.6

Transformer to IEC 99-4 36


45
10kA
10kA
82.8-118.8
103.5-148.5
Transformer Table 3

NB Assumes interconnected earth grid.

Calculation method as per EN 60099-5, IEC 99-5 & IEC 71-2:

Eq 1.0 Lp = N/A((Urw/1.15)-Upl)(Lsp+Lf)

Eq 2.0 Lf = Ra/r

You might also like