Mitsubishi GOT User's Manual
Mitsubishi GOT User's Manual
A970GOT-TBA/TBD(-B)
A970GOT-SBA/SBD
A970GOT-LBA/LBD
A960GOT-EBA/EBD
User’s Manual
(Hardware)
Prior to use, please read both this manual and detailed manual
thoroughly and familiarize yourself with the product.
MODEL A900GOT-U-JE
MODEL
1DM100
CODE
IB(NA)-80032-H(0512)MEE
When using this equipment, thoroughly read this manual. Also pay careful
attention to safety and handle the module properly.
These precautions apply only to this equipment.
Refer to the user’s manual of the CPU module to use for a description of the
PLC system safety precautions.
These "Safety Precautions" classify the safety precautions into two categories:
"DANGER" and "CAUTION".
[DESIGN PRECAUTIONS]
DANGER
z Some failures of the GOT main unit, communication module,
communication board or cable may keep the outputs on or off.
An external monitoring circuit should be provided to check for output
signals which may lead to a serious accident.
Not doing so can cause an accident due to false output or malfunction.
z If a communication fault (including cable disconnection) occurs during
monitoring on the GOT, communication between the GOT and PLC CPU is
suspended and the GOT becomes inoperative.
For bus connection: The CPU becomes faulty and the GOT inoperative.
For other than bus connection: The GOT becomes inoperative.
A system where the GOT is used should be configured to perform any
significant operation to the system by using the switches of a device other
than the GOT on the assumption that a GOT communication fault will
occur.
Not doing so can cause an accident due to false output or malfunction.
A-1
[DESIGN PRECAUTIONS]
DANGER
z Do not use the GOT as the warning device that may cause a serious
accident.
An independent and redundant hardware or mechanical interlock is required
to configure the device that displays and outputs serious warning.
Failure to observe this instruction may result in an accident due to incorrect
output or malfunction.
z Incorrect operation of the touch switch(s) may lead to a serious accident if
the GOT backlight is gone out.
When the GOT backlight goes out, the display section turns black and
causes the monitor screen to appear blank, while the input of the touch
switch(s) still remains active.
This may confuse an operator in thinking that the GOT is in “screensaver”
mode, who then tries to release the GOT from this mode by touching the
display section, which may cause a touch switch to operate.
Note that the following occurs on the GOT when the backlight goes out.
• The monitor screen disappears even when the screensaver is not set.
• The monitor screen will not come back on by touching the display section,
even if the screensaver is set.
CAUTION
z Do not bundle the control and communication cables with main-circuit,
power or other wiring.
Run the above cables separately from such wiring and keep them a
minimum of 100mm apart.
Not doing so noise can cause a malfunction.
[MOUNTING PRECAUTIONS]
DANGER
z Before installing or removing the GOT main unit to or from an enclosure,
always switch off the GOT power externally in all phases.
Not doing so can cause a module failure or malfunction.
z Before loading or unloading the communication board, communication
module, External I/O module or memory board to or from the GOT, always
switch off the GOT power externally in all phases.
Not doing so can cause a module failure or malfunction.
A-2
[MOUNTING PRECAUTIONS]
CAUTION
z The GOT should be used in the environment given in the general
specifications of this user's manual.
Not doing so can cause an electric shock, fire, malfunction or product
damage or deterioration.
z When mounting the GOT main unit to an enclosure, tighten the mounting
screws in the specified torque range.
Undertightening can cause a drop, short circuit or malfunction.
Overtightening can cause a drop, short circuit or malfunction due to the
damage of the screws or module.
z When loading the communication board, communication module or
External I/O module to the GOT main unit, fit it to the connection interface
of the GOT and tighten the mounting screws in the specified torque range.
Undertightening can cause a drop, failure or malfunction.
Overtightening can cause a drop, failure or malfunction due to the damage
of the screws or module.
z When loading the memory board into the GOT main unit, load it into its
corresponding GOT slot and tighten the mounting screws in the specified
torque range.
Undertightening can cause a malfunction due to a contact fault.
Overtightening can cause a malfunction due to the damage of the screws
or module.
z When loading the PC card into the GOT main unit, insert and push it into
its corresponding GOT slot until the PC card eject button comes up.
Not doing so can cause a malfunction due to a contact fault.
z Before loading or unloading the PC card to or from the GOT, set the
memory card access switch to the OFF position.
Not doing so can cause the PC card data to be corrupted.
z Be sure to support the PC card with your hand when removing it.
Otherwise, the PC card may drop, resulting in a failure or damage.
[WIRING PRECAUTIONS]
DANGER
z Before starting wiring, always switch off the GOT power externally in all
phases.
Not doing so may cause an electric shock, product damage or malfunction.
A-3
[WIRING PRECAUTIONS]
CAUTION
z Please make sure to ground FG terminal, LG terminal, and protective
ground terminal of the GOT power supply unit by applying Class D
Grounding (Class 3 Grounding Method) or higher which is used exclusively
for the GOT.
Not doing so may cause an electric shock or malfunction.
z Correctly wire the power supply module on the GOT after confirming the
rated voltage and terminal arrangement of the product.
Not doing so can cause a fire or failure.
z Tighten the terminal screws of the GOT power supply section in the
specified torque range.
Undertightening can cause a short circuit or malfunction.
Overtightening can cause a short circuit or malfunction due to the damage
of the screws or module.
z Exercise care to avoid foreign matter such as chips and wire offcuts
entering the module.
Not doing so can cause a fire, failure or malfunction.
z Plug the bus connection cable by inserting it into the connector of the
connected module until it "clicks".
After plugging, check that it has been inserted snugly.
Not doing so can cause a malfunction due to a contact fault.
z Plug the communication cable into the connector of the connected module
and tighten the mounting and terminal screws in the specified torque
range.
Undertightening can cause a short circuit or malfunction.
Overtightening can cause a short circuit or malfunction due to the damage
of the screws or module.
A-4
[STARTUP/MAINTENANCE PRECAUTIONS]
DANGER
z When power is on, do not touch the terminals.
Doing so can cause an electric shock or malfunction.
z Before starting cleaning or terminal screw retightening, always switch off
the power externally in all phases.
Not switching the power off in all phases can cause a module failure or
malfunction.
Undertightening can cause a short circuit or malfunction.
Overtightening can cause a short circuit or malfunction due to the damage
of the screws or module.
CAUTION
z Do not disassemble or modify the module.
Doing so can cause a failure, malfunction, injury or fire.
z Do not touch the conductive and electronic parts of the module
directly.
Doing so can cause a module malfunction or failure.
z The cables connected to the module must be run in ducts or clamped.
Not doing so can cause the module or cable to be damaged due to the
dangling, motion or accidental pulling of the cables or can cause a
malfunction due to a cable connection fault.
z When unplugging the cable connected to the module, do not hold and pull
the cable portion.
Doing so can cause the module or cable to be damaged or can cause a
malfunction due to a cable connection fault.
A-5
[BACKLIGHT CHANGING PRECAUTIONS]
DANGER
z Before changing the backlight, always switch off the GOT power externally
in all phases (when the GOT is connected to the bus, the PLC CPU power
must also be switched off externally in all phases) and remove the GOT
main unit from the enclosure.
Not switching the power off in all phases may cause an electric shock.
Not removing the unit from the enclosure can cause injury due to a drop.
CAUTION
z While changing the backlight, do not touch the circuit boards and electronic
parts of the GOT.
Doing so can cause a failure or malfunction.
z When changing the backlight, always note the following.
(1) Wear gloves or fingerstalls before starting the replacement of the
backlight.
Not doing so can cause injury.
(2) Start changing the backlight more than 5 minutes after switching the
GOT power off.
Not doing so can cause a burn due to the heat of the backlight.
[DISPOSAL PRECAUTIONS]
DANGER
z When disposing of the product, handle it as industrial waste.
A-6
Revisions
*The manual number is given on the bottom right of the top cover.
Print Date *Manual Number Revision
Jan., 1999 IB(NA)-80032-A First edition
Jun., 1999 IB(NA)-80032-B
Partial correction
Section 5.1
Partial addition
Section 3.2, Section 3.3, Section 5.2
Addition
A970GOT-LBA/LBD
Jun., 2001 IB(NA)-80032-C
Partial correction
Chapter 2, Section 5.1, Section 5.2, Section 5.3
Addition
Appendix 2
Feb., 2002 IB(NA)-80032-D
Partial correction
SAFETY PRECAUTIONS
Jan., 2004 IB(NA)-80032-E
Partial correction
Chapter 1, Section 3.2
Addition
Section 5.4
Mar., 2004 IB(NA)-80032-F
Partial correction
Section 5.4
MODEL CODE change
Changed from 13JN45 to 1DM100.
Aug., 2004 IB(NA)-80032-G
Addition
Section 5.4, 5.5, 5.6
Partial correction
Section 5.7 corresponds to the former Section 5.4.
About Manuals, Section 3.3, Appendix 1
Dec., 2005 IB(NA)-80032-H
Partial correction
Section 3.2
This manual does not warrant or license any industrial property rights and other rights.
Under no circumstances will Mitsubishi Electric be liable or responsible for any
consequential problems involving the industrial property rights which may arise as a
result of the use of this equipment described in this manual.
© 1999 MITSUBISHI ELECTRIC CORPORATION
A-7
CONTENTS
1. Overview .......................................................................................................1
1.1 Packing List ..............................................................................................1
2. System Configuration ....................................................................................2
3. Specifications ................................................................................................3
3.1 General Specifications..............................................................................3
3.2 Performance specifications.......................................................................4
3.3 Power supply specifications......................................................................6
4. Name of the Parts ..........................................................................................7
5. Handling .......................................................................................................8
5.1 Handling instructions ................................................................................8
5.2 Installation method ...................................................................................8
5.3 Wiring diagram .......................................................................................11
5.4 The precautions on the wiring.................................................................12
5.5 Connecting to the GOT Power Section...................................................15
5.6 Connection Cable Wiring ........................................................................16
5.7 Precautions for back light replacement...................................................17
Appendices ....................................................................................................18
Appendix 1 Outline dimension drawing.........................................................18
Appendix 2 Depth dimension for when mounting each type of module.........19
About Manuals
Detailed Manual
Manual No.
Manual name
(Model code)
A985GOT/A975GOT/A970GOT/A960GOT
SH-4005
User’s Manual
(1DM099)
(Available as an Option)
Relevant Manuals
For relevant manuals, refer to the PDF manual stored within the drawing
software.
A-8
1. Overview
This user's manual describes the system configuration, specifications, part
names, handling and outline dimensions of the A975GOT/A970GOT/A960GOT
Graphic operation terminal (Referred to as GOT, hereafter).
*2: If the protective sheet needs to be replaced, please obtain the one that is to
be purchased separately.
1
2. System Configuration
The overall configuration of the GOT is shown below.
Others
Audio output device (Commercially available)
Printer (Commercially available) *1
Barcode reader (Commercially available) *1
*1: For details of the system configuration, refer to the GOT-A900 Series User’s
Manual (Connection System Manual).
2
3. Specifications
3.1 General specifications
Item Specifications
Operating Display section 0 to 40°C *1
ambient
Other than display section 0 to 55°C
temperature
Storage ambient
-20 to 60°C
temperature
Operating
10 to 90%RH, non-condensing
ambient humidity
Storage ambient
10 to 90%RH, non-condensing
humidity
Frequency Acceleration Amplitude Sweep Count
Conforms In case of 10 to 57Hz ⎯ 0.075mm 10 times in
to JIS intermittent 57 to each of X, Y
Vibration 9.8m/s2 ⎯
B3502 vibration 150Hz and Z
resistance
and IEC In case of 10 to 57Hz ⎯ 0.035mm directions
61131-2. continuous 57 to (for 80
4.9m/s2 ⎯ minutes)
vibration 150Hz
Conforms to JIS B3502 and IEC 61131-2
Shock resistance
(147m/s2, 3 times in each of X, Y and Z directions)
Operating
No corrosive gas
atmosphere
Operating
2000m max.
altitude*4
Installation site Inside control box
Overvoltage
II or less
category *2
Contamination
2 or less
level *3
*1: For A975GOT-TBA/TBD (-B) and A970GOT-TBA/TBD (-B), it becomes 0 to
55°C.
*2: Indicates the element in the distribution system between the public
electricity grid and the mechanical equipment inside the premises that the
relevant device is assumed to be connected to.
Category II applies to devices such as those that draw their power supply
from fixed installations.
The surge voltage withstand capability of devices with ratings up to 300V is
2,500V.
*3: This index gives a measure of the incidence of conductive materials in the
environment in which the device is used.
A contamination level of 2 indicates an environment in which there is only
contamination by non-conducting materials, but due to occasional
condensation, conductivity may occur.
*4: Please do not use or store GOT in an environment with atmospheric
pressure greater than the atmospheric pressure at sea level (0m).
There is a possibility errors may occur if this point is not observed.
3
3.2 Performance specifications
Specifications
A975GOT- A970GOT- A970GOT-
Item TBA(-B) TBA(-B) SBA A970GOT-LBA A960GOT-EBA
A975GOT- A970GOT- A970GOT- A970GOT-LBD A960GOT-EBD
TBD(-B) TBD(-B) SBD
STN
D-STN color
Type TFT color liquid crystal monochrome EL
liquid crystal
liquid crystal
Resolution 640 × 480 dots 640 × 400 dots
Display 192 (7.57) × 120 (4.73)
211 (8.31) × 158 (6.23) mm (inch)
size mm (inch)
Display Display 2 color 2 color
256 color 16 color 8 color
section color (monochrome) (yellow orange, black)
TBA/TBD:250 cd/m2 2
250 cd/m
Intensity TBA/TBD-B:380 cd/m2 ⎯
(LCD only)
(LCD only)
TBA/TBD:80 degrees 50 degrees(right and left),
Display
TBA/TBD-B:85 degrees 45 degrees(up), ⎯
angle
(right, left, up and down) 40 degrees(down)
Cold cathode fluorescent tube backlight
Backlight ⎯
(Backlight OFF/screen saving time setting allowed)
TBA/TBD:41,000h
50,000h 30,000h
Display TBA/TBD-B:43,000h
(Operating ambient (Initial luminance
section*2*3 (Operating ambient
temperature: 25) 70%,25°C)
temperature: 25)
TBA/TBD:40,000h
40,000h
Life*1 TBA/TBD-B:43,000h
Backlight ⎯
(Time when display luminance reaches 50% at the
operating ambient temperature of 25°C)
Touch key 1 million times or more (operating force 100g max.)
Built-in
Number of write times: 100,000 times
memory
Environmental
Front section: Equivalent to IP67/NEMA4
protective
Panel inside: IP2X
structure*5
268 (10.56) (W) ×
297 (11.7) (W) × 208 (8.2) (H) × 46 (1.81) (D) 192 (7.56) (H) ×
Outline dimensions
mm (inch) 49 (1.93) (D)
mm (inch)
258 (10.17) (W) ×
Panel cutting 289 (11.38) (W) × 200 (7.88) (H)
183 (7.21) (H)
dimensions mm (inch)
mm (inch)
Weight 1.8 (3.96) kg (lb) 1.9 (4.18) kg (lb) 1.6 (3.52) kg (lb)
SW0D5C-GTWORKS-E SW0D5C- SW0D5C- SW0D5C-
Version A or later, GTWORKS-E GTWORKS-E GTWORKS-E
SW1D5C-GOTRE-PACK Version A or Version A or Version A or
Version A or later later, later, later,
Compatible
(The 8-step brightness SW1D5C- SW1D5C- SW1D5C-
software package*4
adjustment of the high GOTRE- GOTRE- GOTRE-
luminance model is PACK PACK PACK
complied to with Version Version A or Version J or Version A or
C and above.) later later later
*1: When parts must be changed, consult your sales representative.
*2: The screen save and back light OFF functions of the GOT and operator detect sensor
function are used to prevent the display of the screen from being printed and prolong the
service life of the back light.
*3: Bright dots (always lit) and dark dots (unlit) may appear on a liquid crystal display panel. It
is impossible to completely avoid this symptom, as the liquid crystal display comprises of
a great number of display elements.
Please note that these dots appear due to its characteristic and are not caused by
product detect.
4
*4: GT Works2 and GT Designer2, are supported from the first version (Version1.00A).
*5: The specifications differ depending on the version of GOT (hardware version, function
version).
5
3.3 Power supply specifications
Specifications
A975GOT-TBA(-B) A975GOT-TBD(-B)
A970GOT-TBA(-B) A970GOT-TBD(-B)
Item
A970GOT-SBA A970GOT-SBD
A970GOT-LBA A970GOT-LBD
A960GOT-EBA A960GOT-EBD
Input power supply
100AC to 240V (+10%,-15%) 24VDC(+25%,-20%)
voltage
Input frequency [Hz] 50/60 ± 3 -
Using 100VAC
Communication board loaded:
50VA or less
Communication module loaded:
Input max. apparent 60VA or less *1
-
power Using 200VAC
Communication board loaded:
63VA or less
Communication module loaded:
75VA or less *1
Input max. power - 40W
40Ap max. 61Ap max.
Inrush current
(264VAC, max. load) (30VDC, max. load)
Permissible
instantaneous power 20ms (100VAC or more) 1ms (19.2VDC or more)
failure time
By noise simulator of
By noise simulator of 1,500Vp-p
500Vp-p noise voltage,
Noise immunity noise voltage, 1μs noise width and
1μs noise width and 25 to
25 to 60Hz noise frequency
60Hz noise frequency
500VAC for 1 minute
Dielectric withstand 1500VAC for 1 minute across AC
across DC external
voltage external terminals and earth
terminals and earth
Insulation resistance 10MΩ or larger by insulation resistance tester
Applicable wire size 0.75 to 2mm2
Applicable solderless
RAV1.25–3, V2–S3.3, V2-N3A, FV2-N3A
terminal
Applicable tightening
torque (Terminal block 59 to 88Nycm
terminal screw)
External output Refer to *2
*1: When the communication module for bus connection (A9GT-BUSSU/A9GT-
BUS2SU/A9GT-QBUS2SU) is loaded, this value is equivalent to the input
max. apparent power value when the communication board is loaded.
*2: For external outputs please refer to the A985GOT/A975GOT/A970GOT/
A960GOT User’s Manual that is to be purchased separately.
Remarks
Note that the power is reset if an instantaneous power failure occurs.
However, if the instantaneous power failure is within 20ms when using 100
to 240VAC, or within 1ms when using 24VDC, the operation will be normal.
6
4. Name of the Parts
17) 17)
1) 18) 2) 3) 4) 5) 6) 7)
15)
When 9) is removed 13) 12)11) 10) 9) 8)
17) 17)
14) 16)
7
5. Handling
5.1 Handling instructions
When mounting the main unit to a control box or the like, set the display section
as shown below.
When the temperature inside the enclosure is 40 to 55°C or less, the mounting
angle should be in the range 60 to 105 degrees.
GOT
Display 105°
section 60°
Enclosure, etc.
The GOT will be deteriorated earlier if it is used at the mounting angle other
than the above. Therefore, the temperature inside the enclosure should be
within 40°C.
A960GOT
[+1.0(0.04), −0(0)] [+1.0(0.04), −0(0)]
8
(2) Mounting position
When mounting the GOT, the following clearances must be left from the
other device.
Plate thickness
within 2mm to 4mm (0.08inch to 0.16inch)
Part A size: As the GOT connection cable is led out downward, the
following clearance must be provided in consideration of the
bending radius.
Item A [mm] (inch)
A97*GOT + Communication board 130 (5.12) or more
A960GOT + Communication board 140 (5.51) or more
A97*GOT + A9GT-BUSSU/BUS2SU 15 (0.59) or more
A960GOT + A9GT-BUSSU/BUS2SU 30 (1.18) or more
When using a cable prepared by user, please consider the
connector cover to be used and the bending radius of the
cable.
When using a bar code reader, please consider the
dimensions of the connector to be used and the bending
radius of the cable.
Part B size: When using a PC card or an audio output device (for a
connected cable connector and a wire), a clearance of 100
mm (3.94 inch) or more is required. When removing a PC card
by opening a cover of the memory card interface part, a
clearance of 50 mm (1.97 inch) is required. (A clearance of 50
mm (1.97 inch) or more is required when an audio output
device or a memory card is not used.)
(A clearance of 50mm (1.97 inch) or more is required when
these are not used.)
Part C size: Please allow a gap 80mm (3.15inch) or more from the
structure and other equipment in the upper part of the unit to
often allow good ventilation.
Part D size: When installing a device that generates radiation noise
(contactor, etc.) or a device generating high levels of heat near
the GOT, provide a clearance of 100mm (3.94 inch) behind
the module to avoid the effect of the noise and heat.
9
(3) Mounting method
(a) Put the GOT main unit into the panel opening, with its front face first.
(b) Mount the GOT in the following four locations at its top and bottom.
(Top) (Bottom)
10
5.3 Wiring diagram
(1) 100AC to 240V
L L
+ -
DC12/24V
(2) DC24V
INPUT
24VDC
+ -
L L
+ -
DC12/24V
11
5.4 The Precautions on the Wiring
DANGER
z Completely turn off the externally supplied power used in the system when
installing or placing wiring. Not completely turning off all power could result
in electric shock, damage to the product.
CAUTION
z Be sure to ground the FG terminal and LG terminal of the GOT power
supply section to the protective ground conductor. Not doing so could
result in electric shock or erroneous operation.
z When wiring in the GOT power section, be sure that it is done correctly by
checking the product's rated voltage and the terminal layout. Connecting a
power supply that is different from the rating or incorrectly wiring the
product could result in fire or erroneous operation.
z Tighten the terminal screws of the GOT power supply section within the
specified torque range.
If the terminal screws are loose, it could result in short circuits, erroneous
operation or erroneous operation.
Tightening the terminal screws too far may cause damages to the screws
and/or the module, resulting in fallout, short circuits, or erroneous
operation.
z Be sure there are no foreign substances such as sawdust or wiring debris
inside the modle GOT main unit.
12
(1) Power supply wiring
y Separate the GOT's power supply line from the lines for I/O devices and
power devices as shown below.
When there is much noise, connect an insulation transformer.
200VAC GOT
T1
I/O power supply
I/O equipment
AC GOT
E2
POINT
(1) Separate the ground of the surge absorber for lightening (E1) from
that of the GOT (E2).
(2) Select a surge absorber for lightening whose power supply voltage
does no exceed the maximum allowable circuit voltage even at the
time of maximum power supply voltage elevation.
13
(2) Grounding
y For grounding, perform the following:
Use a dedicated grounding wire as far as possible. (Grounding
resistance of 100 or less.)
y When a dedicated grounding cannot be performed, use (2) Common
Grounding shown below.
Also, be sure to take noise countermeasures other than grounding.
Grounding Grounding
(Class 3 grounding) (Class 3 grounding)
(1) Independent grounding Best (2) Common grounding Good (3) Joint grounding Not allowed
Power equipment
(Servo, etc.)
Connection cable
FG
CN1A CN1B
LG
CN2 CN3
FG FG GOT
LG
14
(b) An example of common grounding
Power equipment
(Servo, etc.)
Connection cable
FG
CN1A CN1B
LG
CN2 CN3
FG
FG GOT
LG
AC GOT
INPUT
100-240VAC
Fuse
LG FG
AC
DC
24VDC
GOT
INPUT
24VDC
LG FG
Grounding wire
Grounding
15
POINT
(1) Use the thickest possible (max. 2 mm2 (14 AWG)) wires for the
100/200 VAC and 24 VDC power cables. Be sure to twist these wires
starting at the connection terminals. To prevent a short-circuit should
any screws loosen, use solderless terminals with insulation sleeves.
(2) When the LG terminals and FG terminals are connected, be sure to
ground the wires. Do not connect the LG terminals and FG terminals
to anything other than ground. If LG terminals and FG terminals are
connected without grounding the wires, the PLC may be susceptible
to noise.
In addition, since the LG terminals have potential, the operator may
receive an electric shock when touching metal parts.
3) (A8GT-C BS)
OUT IN
FG
LG L N LG FG
N (A8GT-EXCNB)
L
16
5.7 Precautions for back light replacement
Use the following back lights for the GOT that includes this manual.
Replacement back
Type Model
light
A975GOT-TBA
(Hardware version D (JAN,1998) or later),
A9GT-70LTTB
A975GOT-TBD
(Hardware version B (JAN,1998) or later)
A975GOT
A975GOT-TBA-B
(Function version B (JAN,2004) or later),
A9GT-70LTTBW
A975GOT-TBD-B
(Function version B (JAN,2004) or later)
A970GOT-TBA
(Hardware version D (JAN,1998) or later),
A9GT-70LTTB
A970GOT-TBD
(Hardware version B (JAN,1998) or later)
A970GOT-TBA-B
A970GOT
(Function version B (JAN,2004) or later),
A9GT-70LTTBW
A970GOT-TBD-B
(Function version B (JAN,2004) or later)
A970GOT-SBA, A970GOT-SBD,
A9GT-70LTS
A970GOT-LBA, A970GOT-LBD
The GOT hardware version and function version can be checked from the
rating plate, which is situated on the backside of the GOT.
The applicable back light differs with the GOT hardware version and function
version.
For more information, refer to A985GOT/A975GOT/A970GOT/A960GOT User’s
Manual.
17
Appendices
Appendix 1 Outline dimension drawing
L C
M
G
B
F
K D
G
A
J
H
I
E
Unit: mm(inch)
Item A B C D E F G H I J K L M
A975GOT, 297 208 235 229 288 199 10 46 40 6 34 31 15.4
A970GOT (11.70) (8.20) (9.26) (9.02) (11.35) (7.84) (0.40) (1.81) (1.58) (0.24) (1.34) (1.22) (0.61)
268 192 204 198 257 182 10 49 43 6 35 32 15.4
A960GOT
(10.56) (7.56) (8.04) (7.80) (10.13) (7.17) (0.40) (1.94) (1.69) (0.24) (1.38) (1.26) (0.61)
18
Appendix 2 Depth dimension for when mounting each type of module
(1) A97*GOT
Installed communication module A [mm] (inch) B [mm] (inch)
Communication
A9GT-QBUSS, A9GT-BUSS 40 (1.57) 85 (3.35)
board loading
A9GT-QBUS2S, A9GT-BUS2S 62 (2.44) 85 (3.35)
A9GT-BUSSU, A9GT-BUS2SU 74 (2.91) 15 (0.59)
A9GT-RS2(T) 40 (1.57) *1
A9GT-RS4 40 (1.57) 115 (4.53)
A7GT-J71AP23, A7GT-J71LP23 74 (2.91) *2
A7GT-J71AR23, A7GT-J71BR13 74 (2.91) *3
A7GT-J71AT23B 96 (3.78) -
B A8GT-J61BT13, A8GT-J61BT15 79 (3.11) -
A A9GT-J71E71-T 70.2 (2.76) -
A9GT-70KBF 82.6 (3.25) -
Communication (2) A960GOT
module/Option Installed communication module A [mm] (inch) B [mm] (inch)
module loading A9GT-QBUSS, A9GT-BUSS 43 (1.69) 100 (3.94)
A9GT-QBUS2S, A9GT-BUS2S 65 (2.56) 100 (3.94)
A9GT-BUSSU, A9GT-BUS2SU 77 (3.03) 30 (1.18)
A9GT-RS2(T) 43 (1.69) *1
A9GT-RS4 43 (1.69) 130 (5.12)
A7GT-J71AP23, A7GT-J71LP23 77 (3.03) *2
A7GT-J71AR23, A7GT-J71BR13 77 (3.03) *3
B
A7GT-J71AT23B 99 (3.90) -
A8GT-J61BT13, A8GT-J61BT15 82 (3.23) -
A
A9GT-J71E71-T 73.2 (2.88) -
A9GT-70KBF 85.6 (3.37) -
*1 Depends on the dimensions of the converter and cable used.
*2 This dimension is between 195mm (7.68) maximum and 80mm (3.15)
minimum depending on the optional fiber cable and connector connected.
*3 This dimension is between 80mm (3.15) maximum and 73mm (2.87)
minimum depending on the coaxial cable connected.
19
MEMO
20
Warranty
Mitsubishi will not be held liable for damage caused by factors found not to be the cause of
Mitsubishi; machine damage or lost profits caused by faults in the Mitsubishi products;
damage, secondary damage, accident compensation caused by special factors
unpredictable by Mitsubishi; damages to products other than Mitsubishi products; and to
other duties.
For safe use
y This product has been manufactured as a general-purpose part for general industries, and
has not been designed or manufactured to be incorporated in a device or system used in
purposes related to human life.
y Before using the product for special purposes such as nuclear power, electric power,
aerospace, medicine or passenger movement vehicles, consult with Mitsubishi.
y This product has been manufactured under strict quality control. However, when installing
the product where major accidents or losses could occur if the product fails, install
appropriate backup or failsafe functions in the system.
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
NAGOYA WORKS : 1-14, YADA-MINAMI 5-CHOME, HIGASHI-KU, NAGOYA, JAPAN
When exported from Japan, this manual does not require application to the Ministry
of Economy, Trade and Industry for service transaction permission.
Specifications subject to change without notice.
Printed in Japan on recycled paper.