Facp: Located at Secqurity Room: Ground Level Premises Connection Cable Passing Through Overhead Tray
Facp: Located at Secqurity Room: Ground Level Premises Connection Cable Passing Through Overhead Tray
1'-2"
1'-2"
SD = SMOKE DETECTOR
3'-1" 11'-5" 6'-1" 9'-8" 9'-7" 10'-2" 10'-5" 10'-9" 11'-0" 11'-0" 11'-4" 10'-8" 10'-11" 8'-2" 8'-6" 10'-2" 10'-2" 9'-4" 9'-4" 11'-3" 11'-3" 10'-1" 10'-10" HD = HEAT DETECTOR
MD = MULTI CRITERIA DETECTOR
11'-4"
11'-4"
F = MANUAL PULL STATION
OM = OUTPUT MODULE
IM = INPUT MODULE
HS = HORN WITH STROBE
H = HORN
62'-5" (SECTION A-A) FD = FIRE DOOR
B
EX = EXHAUST FAN
2'-0"
7'-0"
P1:L4:SD:17 NACP = NOTIFICATION APPLIANCE CIRCUIT
POWER EXTENDER
7'-10"
33'-7"
11'-6"
P1:L4:SD:21 P1:L4:SD:19 P1:L4:SD:18 N0:HS:00
10'-2"
P1:L4:SD:14 DEVICE SERIAL
6'-3"
M.TOILET
DEVICE TYPE
10'-3" 21'-5" 17'-6" 5'-5" ELECTRICAL 47'-3"
F.TOILET
P1:L2:MD/SD/HD/F/OM/IM: 000
12'-11"
4'-9"
P1:L4:SD:20 39'-2"
SLC:4 Out To Roof Floor DEVICE SERIAL
7'-4"
UP
SLC:4 (Start) (FACP-1) (FACP-1) (Riser 1) DEVICE TYPE
5'-0"
P1:L4:SD:22 P1:L4:SD:24 P1:L4:SD:25 P1:L4:SD:26 P1:L4:SD:27 P1:L4:SD:10 P1:L4:SD:09 P1:L4:SD:08 In From FACP Room(Riser 1) LOOP NUMBER
74'-3"
F.TOILET
STAIR P1:L4:SD:05 PANEL NUMBER
P1:L4:SD:07
OFFICE
P1:L4:SD:23
LOCKER P1:L4:SD:06
UP
ADDRESSABLE OUTPUT MODULE
LEGEND: ADDRESSABLE FIRE DETECTION & ALARM SYSTEM
genitor
F STAIR
EX:N2:HS:03 6'-3"
OFFICE
Symbol Description Brand Model QTY.
P1:L4:OM:11 OM
8'-9"
EX:N2:HS:02
7'-1"
DN
F
7'-7"
7'-7"
TOILET
OM P1:L4:SD:41
P1:L4:OM:29
LIFT Heat Detector Cooper UCAH330 00
1'-8"
13'-7"
12'-1''x12'-1''
19'-8"
LOBBY R/F
P1:L4:OM:03
TOILET
FIRE CURTAIN
Multi Sensor Detector Cooper UCAPT340 00
19'-8"
15'-7"
OM
OM R/F
P1:L4:OM:106
5'-5"
1" OM
'-1
1'-0"
P1:L4:OM:32 P1:L4:SD:50 P1:L4:SD:49 P1:L4:SD:48 P1:L4:SD:47 P1:L4:SD:46 P1:L4:SD:45 P1:L4:SD:44 P1:L4:SD:43 P1:L4:SD:42
OM
12
P1:L4:SD:105 P1:L4:SD:89
9'-3" 21'-5" 22'-10" 23'-9" 23'-7" 20'-10" 20'-4" 21'-2" 22'-3" 22'-11" 12'-10"
IM Input Module Cooper UMCIM 00
5'-5"
P1:L4:SD:52 P1:L4:SD:51
A A Horn With Strobe Cooper HSR 07
137'-5"
TIANJIE 20131121-E464899
22'-3"
22'-3"
22'-3"
Circuit Pathway Class A
17'-0"
111'-8"
P1:L4:SD:53 P1:L4:SD:54 P1:L4:SD:55 P1:L4:SD:56 P1:L4:SD:57 P1:L4:SD:58 P1:L4:SD:59 P1:L4:SD:60 P1:L4:SD:61 P1:L4:SD:62 P1:L4:SD:63 P1:L4:SD:88 P1:L4:SD:90 2 hr. Fire Rated Door
22'-3"
22'-3"
22'-3"
22'-3"
EX-N2 END
EOLR
10'-1"
P1:L4:SD:91
As per NFPA-72, Table-17.7.6.3.3.2 (V-2013)
14'-3" 21'-5" 21'-5" 22'-10" 23'-9" 23'-7" 20'-10" 20'-4" 21'-2" 22'-3" 22'-11" 12'-10"
10'-2"
19'-0"
19'-0"
19'-0"
1'-8"
P1:L4:SD:75 P1:L4:SD:76 P1:L4:SD:77 P1:L4:SD:78 P1:L4:SD:79 P1:L4:SD:80 P1:L4:SD:81 P1:L4:SD:82 P1:L4:SD:83 P1:L4:SD:84 P1:L4:SD:85 P1:L4:SD:86 P1:L4:SD:92 Detector Spacing Reduction Based on Ceiling Height
'-3
EX:N2:HS:06 "
11'-1"
11'-1"
11'-1"
11'-1"
Detector Type Heat & Multi Sensor
P1:L4:SD:104 P1:L4:SD:103 P1:L4:SD:102 P1:L4:SD:101 P1:L4:SD:100 P1:L4:SD:99 P1:L4:SD:98 P1:L4:SD:97 P1:L4:SD:96 P1:L4:SD:95 P1:L4:SD:94 P1:L4:SD:93 Detector
Multiply Listed Spacing by 0.91
B
7'-0"
253'-10"
Floor Height 11'-4"
5TH FLOOR PLAN (BUILDING-1) 01. Fire Door, Exhaust Fans, Fire Pumps are Interfaced with FACP: LOCATED AT SECQURITY ROOM Floor Area 30,589 SFT.
8"
SCALE : 1: 100
CONCRETE
SLAB Fire Alarm Control Panel
Max. Coverage Area 900sft
01'2' 4' 10' 20'
02 . Panel Capacity: This Panel Capacity up to 200 Addressable Devices GROUND LEVEL PREMISES CONNECTION
14"
SCA E ( A IC SCA E)