( Reaffirmed 1996 )
Indian Standard
                   SPECIFICATION FOR
            DRY-TYPE POWER TRANSFORMERS
                    Transformers   Sectional    Committee,         ETDC    16
          Chairman                                          Representing
SHRI C. R. VARIER                        Crompton    Greaves Ltd, Bombay
          Members
     SHRI S. V. MANERIKAR ( Alternate to
       Shri C. R. Varier )
SHRI R. S. ARORA                      Directorate     General of Supplies & Disposals
                                           ( Inspection Wing ), New Delhi
    SHRI D. R. CHANDRAN ( Alternate )
 SHRI P. K. BHATTACHARYA              Calcutta     Electric     Supply   Corporation    Ltd,
                                           Calcutta
    SHRI B. C. GHOSII ( Alternate )
 DIRECTOR ( SUBSTATIONS )             Central Electricity Authority, New Delhi
    DEPUTY DIRECTOR ( SUBSTA-
       TIONS ) ( Alternate )
 SARI G. L. DUA                       Rural     Blectrification    Corporation    Ltd,  New
                                           Delhi
     SHRI S. C. KHURANA ( Alternate )
 SHRI A. R. DWAILI(ANATH              Madhya Pradesh Electricity Board, Jabalpur
     SHRI N. N. BHAI~~AVA ( Alternate )
 SHRI S. D. GUPTA                     UP State Electricity Board, Lucknow
     S~nr SATISH KUMAR (Alternate )
 SHRI P. J. INoLB                     Central Power Research Institute, Bangalore
     SENIOI~ DEPUTY DIRECTOR
       ( STDS ) (Alternate )
JOINT DIRECTOR TI ( SUBSTATION ) Research, Designs and Standards Organization,
                                           Lucknow
     DEPUTY       DIRECTOR       STDS
       ( ELEC )-C2 ( Alternate )
 SHRI R. S. KHODE                     Bharat Bijlee Ltd, Bombay
     SERI R. G. PARDH~NANI ( Alternate)
 SHRI D. B. MEHTA                     Tata Hydro-Electric         Power Supply Company
                                           Ltd, Bombay
    SRRI R. C~ANDRAMOULI (Alternate)
 SHRI D. V. NAI~KE                    General      Electric     Company     of   India  Ltd,
                                           Allahabad
     SHRI B. A. SUBRAMANYAM ( Alternate )
                                                                        ( Co&sued on page 2 )
                                     0   Copyright   1985
                        INDIAN     STANDARDS         INSTITUTION
  This publication   is protected under the Indian Copyright Act ( XIV of 1957 ) and
  reproduction in whole or in part by any means except with written permissionof the
  nublisher shall be deemed to be an infringement of copyright under the said Act.
18 : 11171- l!HH
( Continued from puga 1 )
          Members                                      Representing
SERI B. K. PATEL                       Gujarat Electricity Board, Vadodara
    S~<RIC. D. PATEL ( Alternate)
SHRI Y. K. PALVANEAR                  Bombay Electric Supply and Transport Underta-
                                           king, Bombay
    SHRI J. L. RODRI~UES ( Altcrnafc )
DR G. M. P~ADKE                       Indian Electrical Manufacturers’         Association,
                                            Bombay
     SARI P. K. PHILIP ( Alternate )
DR K. V. N. RAO                       Electrical Research and Development Associa-
                                           tion, Bombay
     SHRI N. J. BUCH ( Alternate )
SHRI CBANDRA K. ROHATQI               Pradip Lamp Works, Patna
SHRI P. S. SAWHNEY                    Delhi Electric Supply Undertaking, New Delhi
     SHRI S. P. A~QARWAL ( Alternate )
SHRI R. K. SEH~AL                     Bombay Suburban Electric Supply Ltd, Bombay
     SHRI H. S. NATARAJAN ( Afternate )
SHRI K. G. SHAN~~UKHAPPA               NGEF Ltd, Bangalore
     SHRI MOHAMBIED YOUWJF~ (Alternate )
SUPERINTENDINQ E N Q I N E E B Andhra Pradesh State Electricit                 Department
   TECIXNICAL      ( PROJECTS)             ( Electricity Projects and Boar(r ), Hyderabad
     SUPERINTENDINQ    ENGINEER
       ( GRID OPERATIONS) ( Altcrnats )
SIIRI I. C. TAYAL                      Bharat Heavy Electricals Ltd, New Delhi
     SHRI R. S. SIIAH ( Alternate I )
     SHRI D. P. GUPTA ( Alternate II )
DR VAIUL AHUED                         Directorate General of Technical      Development,
                                           New Delhi
     SHRI S. K. PAIHAN ( Alternate )
SHRI T. V. VIDYARATNA RAJ              Kirloskar Electric Company Ltd, Bangalore
      SHT~I1’. RAN~ARAJAN ( Alternate )
SHRI VISH~AJIT M. ME~TA                Indian Transformer Manufacturers’        Association,
                                           New Delhi
SHRI S. P. SACHDEV,                    Director General, IS1 ( Ex-omo    Mambo )
  Director ( Elec tech )
                                   SHRI K. M. BHATIA
                             Joint Director ( Elec tech ), IS1
                                              2
                                                                     IS:11173 -1985
                                                                                      (
                           Indkzn Standard
                         SPECIFICATION                  FOR
          DRY-TYPE               POWER TRANSFORMERS
                            0.    FOREWORD
0.1 This Indian Standard was adopted by the Indian Standards Institution
on 15 May 1985, after the draft finalized by the Transformers Sectional
Committee had been approved by the Electrotechnical Division Council.
0.2 Supply voltages have been increased in recent years to meet the
growing demand for electricity.   IS : 2026* ( issued in four parts ) covers
every aspect of power transformers including high ratings to keep abreast
of technological progress. Since dry-type power transformers are not made
for such high voltages and ratings as oil-immersed transformers, a large
portion of IS : 2026* serves no purpose to manufacturers and the users of
dry-type transformers.    Thus, for convenience sake, this separate and
concise standard has been prepared to set out specific requirements for dry-
type power transformers.
0.3 This standard is to be read in conjunction with IS : 2026*, since
a reference has been made to the technical data of that standard, where
appropriate.
0.4 With the publication of this standard, the requirements of IS : 2026*,
apply to dry-type transformers only in so far as they are referred to in this
standard.
0.5 This standard is primarily based on IEC Publication 726 ( 1982 ) ‘Dry-
type power transformers’      issued by the International     Electrotechnical
Commission.
0.6 For the purpose of deciding whether a particular requirement of
this standard is complied with, the final value observed or calculated,
expressing the result of a test or analysis, shall be rounded off in accord-
ance with IS : 2-196Ot. The number of significant places retained in the
rounded off value should be the same as that of the specified value in this
standard.
   *Specification for power transformers:
     Part 1 General (jr& r&ion ).
     Part 2 Temperature-rise   ( jirst ret&ion ).
     Part 3 Insulation levels and dielectric tests ( second revision ).
     Part 4 Terminal markings tappings and connections (first r&ion       ).
   tRules for rounding off numerical valuer ( revised ).
                                            3
IS : r1171-    19ii5
                              SECTION          1 GENERAL
1. SCOPE
1.1 This standard applies to dry-type power transformers    ( including auto-
transformers ) having values of highest voltage for equipment ( urrr ) up to
and including 36 kV.
1.2 The following small and special dry-type                 transformers    are not covered
by this standard :
      4   Single-phase    transformers rated at less than            1 kVA       and polyphase
          transformers    rated at less than 5 kVA,
      b) Instrument transformers ( see IS : 2705* and IS                    : 31561_ ),
      Cl Transformers for static convertors,
      4 Starting transformers,
      e) Testing transformers,
      f ) Traction transformers mounted on rolling stock,
      8) Flameproof and mining transformers,
      h) Welding transformers ( see IS : 1851-19751 ),
      j) Voltage regulating transformers, and
      k) Small power transformers in which safety is a                      special     considera-
          tion.
2. TERMINOLOGY
2.0 For the purpose of this standard, the following definitions,                      in addition
to those given in IS : 1885 ( Part 38 )-1977s shall apply.
2.1 DryiTransformers     - A transformer               in which the core and windings
are not immersed in an insulating liquid.
       NOTE - The cooling of a dry-type        transformer     may be natural,        natural/forced
  or forced circulation.
   *Specification for current transformers :
     Part 1 General requirements (first revision ).
     Part 2 Measuring current transformers ( jirst revision ).
     Part 3 Protective current transformers (jfirst revision ).
     Part 4 Protective     current transformers   for special purpose applications    (first
       w&ion ) .
  tSpe.cification for voltage transformers :
     Part 1 General requirements (Jirsl revision ).
     Part 2 Measuring voltage transformers (jirst rruision ).
     Part 3 Protective voltage transformers ( jirst revision ).
     Part 4 Capacitor voltage transformers (Jirst revision ).
  fSpecification for single pperator type are welding transformers ( sccand revision ).
  $Electrotechnical   vocabulary : Part 38 Transformers (first revision ).
                                           4
                                                                             IS:   Ill?1    -1985
  2.1.1 Encapsulated- Winding Dry-Type Transformers - A dry-type transfor-
mer having one or more windings encapsulated with solid insulation.
   2.1.2 Non-Encajsulated- Winding Dry- Tyje Transformer -                         A dry-type
transformer  having none of the windings encapsulated   with                       solid insula-
tion.
2.2 Terms       Relating      to the Containment               of a Dry-Type         Transfer;
mer
   2.2.1 Sealed Dry-Tybe Transformer - An air or gas-immersed       dry-type
transformer   within a sealed protective enclosure so constructed that there
can be no interchange    between its contents and the external atmosphere,
that is, the transformer   is non-breathing.
       NOTE-   Thegas in a gas-immersed       transformer          remains    in a gaseous     state
  throughout the range of transformer operations.
   2.2.2 Totally Enclosed Dry-Type Transformer - An air immersed dry-type
transformer within a protective enclosure so constructed  that the ambient
air does not circulate    to cool the core and windings, but which can
breathe to atmosphere.
   2.2.3 Enclosed Dry-Type    Transformer - A dry-type                transformer within a
protective  enclosure so constructed that the ambient                 air may circulate so
as to cool the core and windings directly.
   2.2.4 Non-Enclosed   Dry- Type  Transformer - A dry-type   transformer
without a protective enclosure in which the core and windings are cooled
by ambient air.
3. SERVICE         CONDITIONS
3.1 Normal ‘Service Conditions      - This standard gives detailed                         require-
ments for transformers for use under the following conditions :
       a)    Altitude -   A height      above mean sea-level        not   exceeding        1 000 m.
       NOTE-      For greater altitudes, see 3.2.
       b) Reference ambient temperature
             1) Maximum           ambient   air temperature                                   50°C
             2) Maximum           daily average     ambient    air temperature                40%
             3) Maximum           yearly weighted    average    ambient      temperature      32°C
             4) Minimum       ambient       air temperature                                  -5°C
       NOTE -     See also 3.2.
       Cl    Wave-shape of supply uoltage - A supply voltage              of which    the wave-
             shape is approximately    sinusoidal.
       4     Symmetry of polyphase supPly voltages - For polyphase transformers,
             supply voltages which are approximately     symmetrical.
                                               5
IS : 11171-     1985
3.2 Provision     for Unusual      Service       Conditions
  3.2.1 The purchaser     shall specify in his enquiry any service conditions
not   covered   by the normal service conditions in 3.1 ( SCGAppendix A ).
    3.2.2 Supplementary    requirements, within defined limits, for the rating
and testing of transformers   designed for other than normal service condi-
tions listed in 3.1, such as high temperature     of cooling air or altitude
above 1 000 m are given in 18.2, 10.3 and 11.2.
   3.2.3 For temperature    conditions outside the limits covered by the sup-
plementary    requirements   and special operating    conditions,   for example
restricted cooling air circulation,   the temperature   rise is to be subject to
agreement between the manufacturer        and the purchaser.
4. TERMINAL            MARKINGS,     TAPPINGS           AND CONNECTIONS
4.1 Relevant   provisions,of IS : 2026 ( Part 4 )-1977*   shall be applicable,
but where tappings are required the preferred. tapping range is + 5 per-
cent in 2-5 percent steps, that is, +5,      +2*5,  -2.5 and -5    percent by
means of off-circuit tap-changing   links or tap switch.
5. ABILITY      TO WITHSTAND           SHORT-CIRCUIT
5.4 The    relevant   provisions of IS : 2026          ( Part   1 )-1977t     apply to the
transformers   covered by this standard.
6. INFORMATION            REQUIRED       WITH ENQUIRY               AND       ORDER
6.1 The  technical information  that the purchaser              is required     to   supply
with enquiry and order is given in Appendix B.
                            SECTION          2    RATING
7. RATING
7.0 General    - The manufacturer     shall assign ratings to the transformer,
which shall be marked on the rating plate (see 8 ). These ratings shall be
such that the transformer     can deliver its rated current under steady
loading conditions without exceeding the limits of temperature-rise       speci-
fied in Section 3, assuming that the applied voltage is equal to the rated
voltage and that the supply is at rated frequency.
7.1 Rated Power ( kVA ) -The          rated kVA assigned shall take into
account service conditions corresponding   to those specified in 3 and shall
be related to the product of rated voltage, rated current and the appro-
priate phase factor given in Table 1.
  *Specification for power transformers : Part 4 Terminal markings, tappings and
connections (Jirst revision).
  $Specilication for power transformers : Part 1 General (first revision).
                                             6
                                 TABLE       1    PHASE     FACTORS
                                                 ( Clause 7.1 )
                    NUMBEE   OF PRASE~                             PHASE FACTOR
                             1
                             3
       NOTE - The       rated power corresponds to continuous duty; nevertheless,     dry-
  type transformers     complying with this standard can be occasionally    overloaded to
  some extent under      certain conditions.  Guidance on overloads will be either added
  in this standard or   provided in a separate standard sometimes later.
7.2 Power      ( kVA ) Ratings           -        Provisions of 4.2 of IS : 2026 ( Part 1 )-
1977* shall apply.
7.3 Rated Frequency -              The standard frequency shall be 50 Hz with a
tolerance of f 3 percent.
       NOTE - Nevertheless,  transformers made for other frequencies shall be conside-
  red to comply with this standard provided they do so in all other relevant respects.
7.4 Operation     at Other than Rated Voltage           and                        Frequency   -
Provisions of 4.3 of IS : 2026 ( Part 1 )-1977” shall apply.
8. RATING          PLATES
8.1 Each   transformer shall be provided with a rating plate of weather-
proof material, fitted in a visible position, showing the items indicated
below. The entries on the plate shall be indelibly marked ( for example,
by etching, engraving or sta&pi,ng ) .
      a>Kind   of transformer ( see definitions given in 2 );
     b)  Number    of this standard, Ref IS : 11171-1985;
     cl  Manufacturer’s    name;
     4   Manufacturer’s    serial number;
     e)  Year  of manufacture;
     f 1 Temperature class of insulation ( Insulation system temperature )
         and maximum permissible temperature rise for all windings, or
         for each individual winding, if applicable ( see 10.1 );
     g> Number of phases;
     h) Rated power ( kVA ) for each kind of cooling;
      3 Rated frequency;
     k) Rated voltages, including tapping voltages, if any;
     ml Rated currents for each kind of cooling;
     4 Connection symbol;
  *Specification    for power transformers         : Part 1 General (jirstrevision ).
                                                     7
IS 011171 - 1985
       P) Impedance     voltage at rated current                    [determined    according     to
           16.4 of IS : 2026 ( Part 1 )-1977*];
        cl) Type of cooling;
        r) Type of filling
                                                            f
        s) Operating   pressure range                        i
        t) Maximum     and minimum absolute                  1
                                                             > applicable only to
           pressures for which the enclosure is
                                                             1 sealed units
           designed
                                                                I
       u) Pressure     and temperature    of filling            1
          medium       at the time of sealing                j
       w) Total mass; and
       x) Insulation levels
        NOTE - The rated withstand voltages for            all windings shall appear on the
   rating plate.   The principles of the standard          notation are illustrated in 3 of
   IS : 2026 ( Part 3 )-1981t.
8.2 Dry-type      power transformers           may also be marked          with   ISI   Certifica-
tion Mark.
        NOTE -The    use of the IS1 Certification       Mark is governed by the provisions of
   the Indian Standards     Institution   ( Certification   Marks)   Act and the Rules and
   Regulations   made thereunder.       The IS1 Mark on products covered by an Indian
   Standard conveys the assurance that they have been produced to comply witb the
   requirements of that standard under a well-defined system of inspection, testing and
   quality control which is devised         and supervised by IS1 and operated by the
   producer. IS1 marked products are also continuously checked by IS1 for conformity
   to that standard as a further safeguard. Details of conditions, under which a licence
   for the use of the IS1 Certification       Mark may be granted to manufacturers         or
   processors, may be obtained from the Indian Standards Institution.
                    SECTION 3 COOLING METHODS                              AND
                           TEMPERATURE-RISE
9. IDENTIFICATION                ACCORDING             TO COOLING            METHOD
9.1 Identification        Symbols      - Transformers    shall be identified actor d-
ing to the cooling method          employed.   Letter symbols for use in connection
with each cooling method           shall be as given in Table 2.
     *Specification   for power transformers     : Part 1 General (Jirsl revision ).
    tSpecilication   for power transformers     : Part 3 Insulation levels and dielectric      tests
( second revision ).
                                                 8
                                                                            Isrlll7l-r98!!
                        TABLE     2 LETTER       SYh¶BOLS
                                     ( Cfausr 9.1 )
                                                                                         .
                 KIND OB COOLINGMEDIUM                             Symbol
                           Air                                        A
                          Gas                                        G
                  KIND OB CIBOULAT~GN
                        Natural                                      N
                        Forced                                        F
9.2 Arrangement      of Symbols - Transformers without protective enclo-
sures or within enclosures through which the cooling air can circulate are
identified by two symbols only for the cooling medium ( air ) which is in
contact with the windings or the surface’ coating of the windings. All other
transformers shall be identified by four symbols for each cooling method
for which a rating is assigned by the manufacturer.
   9.2.1 The order in which the symbols are used shall be as given in
Table 3. Oblique strokes shall be used to separate the group of symbols
for different cooling methods for the same piece of equipment.
                      TABLE   3    ORDER       OF SYMBOLS
 COOSINGMEDIUM IN CONTACTWITH              COOLINGMEDIUM IN CONTACTWITH TEE
        THE WINDINQS                             EXTERNALCOOLINGSYSTEM
    1st Letter          2nd Letter                    3rd Letter                  4th Letter
Kindm;g;ding              Kind of               Kind of cooling                    Kind of
                        circulation                 medium                       circulation
   9.2.2 For example, the cooling method of a transformer without a
protectiveenclosure or within an enclosure through which the cooling air
can circulate and with natural air cooling is designated by :
                                         AN
  9.2.3 For a transformer within a protective enclosure through which the
cooling air cannot circulate, with natural air cooling inside and outside the
enclosure, the designation is :
                                   ANAN
  9.2.4 For a transformer in a sealed enclosure with natural nitrogen
cooling inside and alternatives of natural or forced air cooling outside the
cnchure, the designation is :
                                  GNAN/ GNAF
10. TEMPERATURE-RISE              LIMITS
10.1 Normal Temperature-Rise Limits - The temperature rises of
the windings, core and metal parts of transformers designed for operation
                                           9
Is t’lll7l      - 1985
at altitudes not exceeding those given in 3.1 (a) and with external cooling
air temperature as described in 3.1 (b) shall not exceed the limits specified
in Table 4 when tested in accordance with 17.
           NOTE - Insulating materials may be used separately or in a combination provi-
       ding that, in any application,      each system will not be continuously subjected to a
       temperature in excess of that for which it is suitable when operating under rated
      conditions.  Furthermore,    the electrical and mechanical properties of the insulated
      winding must not be impaired by the application of the hot-spot temperature         per-
      mitted for the specrfic insulation system.
                             TABLE     4     TEMPERATURE-RISE            LIMITS
                                             ( Cluu~cs 10.1 and 10.3 )
 SL                   PART                               TEMPERATURE                 TEMPERATURE-
 No.                                                        CLASS OP                      RISE
                                                         INSOLATION*
 (1)                   (2)                                    (3)                           (4)
                                                                                             YI
 i)        Windings    (Temperature-rise                      A                              50
         ” measured by resistance method )                    E                               65
                                                              B                               70
                                                               I!I                          1::
                                                               C                            140
ii)        Core,    metallic         parts       and                       The temperature shall in
           adjacent materials                                              no case reach a value
                                                                           that   will damage       the
                                                                           core itself, other parts. or
                                                                            adjacent materials
    *In accordance with IS : 1271-1958 ‘ Classification of insulating material for electri-
cal machinery and apparatus in relation t,o their thermal stability in service. ’
10.2 Reduced Temperature-Rises         for Transformers    Designed foti
High Cooling      Air Temperatures       or Special Air Cooling   Con&;
tions - If the transformer is designed for service where the temperature
of the cooling air exceeds one of the maximum values of 3.1 by. no more
than lO”C, .the allowable temperature-rises for the windings shall be
reduced as follows :
          a)   By 5°C if the excess temperature is less than or equal to 5°C; and
      b) By 10°C if the excess temperature is greater than 5°C and less
 -_ .   -,,than or equal.to 10°C.
       Where the excess temperature exceeds one of the values specified
in 3.1 by more than 1O”C, the allowable temperature-rises require an agree-
ment between the manufacturer and the purchaser.
      Any site conditions which may either impose restrictions on the
cooling air or produce high ambient air temperatures should be stated by
the ipurchaser.
                                                       10
                                                                       IS : 11171 - 198!!
19.3~ Reduced Temperature-Rises        for Transformers       Designed for
I&i& Altitudes - Unless otherwise        agreed between    the manufacturer
and.the purchaser, for transformers  designed for operation    at an altitude
greater than 1 000 m but tested at normal altitudes, the limits of tempera-
turerise given in Table 4 are reduced by the following amounts for each
500 m by which the intended working altitude exceeds I 000 m :
         a) Natural-air-cooled         transformers           2-5 percent
         b) Forced-air-cooled          transformers           5 percent
       NOTE - If transformers which are designed for operation below 1 000 m are
  tested at altitudes above 1 000 m, the measured temperature rises are to be reduced
  by the above-mentioned amounts for each 500 m by which the test altitude exceed
  1000 m.
                             SECTION        4   INSULATION   LEVELS
11. INSULATION                 LEVELS
ilk    General - When         transformers  are intended   for general   power
distribution    in public or industrial systems, the insulation levels shall be
asgiven~in Table 5, List 1 or 2. The choice between Lists 1 and 2 should
be made by considering the degree of exposure to lightning and switching
overvoltages,     the type of system neutral earthing and, where applicable,
the type of overvoltage protective device. Guidance may be obtained from
13:.2165-1977*.
       However, for application in particular  systems where the insulation
requirements    are lower than in general and where the transformers are not
required to be tested with lightning impulse withstand voltages, the power
f&quency testvoltage     applied may be below the value specified in Table 5
subject  to agreement     between the manufacturer   and the purchaser.   No
                                                                            ‘I
definite figures are recommended    here.
 .*_     .,
 _..              -Y----~-
                                        ~         ~
            .,    TABLE 5 INSULATION    LEVELS
I&HEST VOLTAUEFOR     RATED SHORTDURATION RATED LI~HTNINU IMPULSE
   EQUIPYENT Um          POWER FREQUENCY       WITHSTAND VOLTAGE
                        WITHSTAND VOLTAQE            kV ( peak )
                                              r----       *_--
   kV ( rms)                 kV ( rms )          List 1        List 2
     <l-l                        3                               -
   _j,    3’6,                                        10          20           40
          7.2                                         20          40            60
         12                                           28          60            75
         17’5                                         38          75            95
         24                                           50          95           125
         36                                           7il        145           170
  *Insulation    coordination     ( second
                                         revision ).
                                                  11
g t 11171-1985
11.2 Transformers for Use at High Altitudes - When the transbb
mers are specified for operation at altitudes between 1 000 m and 3 000 m
above mean sea-level, but tested at normal altitude, the rated short
duration  power    frequency  withstand                 voltage    shall be   increased
by 6.25 percent for each 500 m by which                 the altitude of the installation
exceeds 1 000 m.
       NOTE -     The above does not apply to sealed      dry-type   transformers      but    rpecjal
  consideration    should be given to bushings.
                                SECTION 5 TESTS
12. GENERAL          REQUIREMENTS                  FOR TESTS
12.1 Transformers shall be subjected to tests as specified in 13.
12.2 Tests shall be made at the manufacturer’s works, unless otherwise
agreed to between the manufacturer and the purchaser.
12.3 Dielectric tests in accordance with 14, 15 and 16 shall be made with
the transformer at approximately ambient temperature.
12.4 All external components and fittings that are likely to affect the
performance of the transformer during each test shall be in place.
12.5 Tapped windings shall be connected on their principal tapping,
unless otherwise given in relevant part of IS : 2026* or agreed between
the manufacturer and the purchaser.
12.6 The test basis for all characteristics other than insulation is the rated
condition, unless the test clause states otherwise.
12.7 The reference temperature to which the load loss, impedance voltage
and shorticircuit impedance are to be corrected shall be the maximum
winding temperature-rise as given in Table 4 plus 30°C.
      NOTE- When a trsnsformer has windings of different insulation system temt
  peratures ( class of insulation  ), only one reference temperature        is to be used,   that
  is, the one relating to the winding having the higher inrulation        system   temperature,
13. CLASSIFICATION               OF TESTS
13.1 Type Tests - The following shall constitute the type tests :
     a> Measurement of winding resistance [ 16.2 of IS : 2026 ( Part 1 >-
           1977* 1,
      b) Measurement    of voltage ratio and check of voltage                        vector    rela-
         tionship [ 16.3 of IS : 2026 ( Part 1 )-1977* ] :
   *Specification for power transformers :
     Part 1 General ( jrst revision).
     Part 2 Temperature-rise ( Jirsi r&ion ).
     Part 3 Insulation levels and dielectric tests (s~ond revision).
     Part 4 Terminal markings, tappings and connections (first       rcvition   ),
                                              12
                                                                              IS : 11171- 1983
       4    Measurement of impedance   voltage ( principal tapping ), short-
            circuit impedance and load loss [ 16.4 of IS : 2026 ( Part 1 )-
            1977* 1;
       4    Measurement     of        no-load     loss and         current [ 16.5   of IS : 2026
            ( Part 1 )-1977*];
       4    Separate-source       voltage    withstand       test ( 14 );
       f>   Induced     overvoltage     withstand        test ( 15 );
       d    Lightning     impulse test ( 16 ); and
       h)   Temperature-rise       test ( 17 ).
13.2 Routine      Tests     -    The following           shall constitute   routine tests :
       a)   Measurement         of winding      resistance [ 16.2 of IS : 2026        ( Part 1 )-
            1977* 1;
        b) Measurement     of voltage   ratio               and check      of voltage    vector
           relationship [ 16.3 of IS : 2026 (               Part 1 )-1977* 1;
       ‘c) Measurement     of impedance      of               voltage ( principal    tapping ),
           short-circuit impedence and load                  loss [ 16.4 of IS : 2026 (Part I)-
           197i”] ;
       d) Measurement     of no-load              loss     and. current [ 16.5 of IS : 2026
          ( Part 1 )-1977* ] ;
       e) Separate-source         voltage withstand          test ( 14 ); and
       f)   Induced     overvoltage     withstand        test ( 15 ).
13.3 Special Tests - The following tests may be carried                         out by mutual
agreement between the purchaser and the supplier :
       a) Partial discharge        measurement           ( 18 );
       b)   Measurement         of acoustic sound level ( 19 ); and
       c) Short-circuit     test ( 20 ).
14. SEPARATE-SOURCE                   VOLTAGE             WITHSTAND          TEST
14.1   The provisions      of 10 of IS : 2026 ( Part 3 ) - 1981 t are applicable.
14.2 The test voltage shall be in accordance with Table 5 for the specified
insulation level of the transformer, if no other value has been agreed upon
by the manufacturer and the purchaser.
      The full test voltage shall be applied for 60 s between the winding
under test and all the remaining windings, core, frame and transformer
enclosure, connected to earth.
    *Specification for power transformers       : Part 1 General (Jirsi reuision ).
    +Specification for power transformers        : Part 3 Insulation level and dielectric     tests
( second revision ) .
                                                  13
IS : 11171 - 1985
15. INDUCED          OVERVOLTAGE                WITHSTAND                 TEST
15.1 The test shall be carried               out     in    accordance          with     11.1 and 11.2
of IS : 2026 ( Part 3 ) - 1981*.
15.2 The test voltage shall be twice the value corresponding                              to the rated
voltage across an untapped winding of the transformer.
       The duration of the test at full volage shall be 60 s for                                 any     test
frequency up to and including twice the rated frequency.
       When the test frequency             exceeds        twice     the     rated      frequency,        the
duration of the test shall be:
                               120    x rated frequency           seconds
                                                                             2
                                     test frequency
but not less than      15 s.
16. LIGHTNING      IMPULSE TEST
16.1 The test shall be carried out in accordance                             with      12 of IS : 2026
( Part 3 )-1981*.
16.2 The test voltage    shall be in accordance      with List 1 or                              List 2 of
Table 5 for the specified insulation level of the transformer.
       The    test impulse      shall be a full standard           lightning     impulse:
             l-2    & 30 percent/50        & 20 percent           micro-seconds
       The test voltage shall normally   be of negative polarity. The test
sequence per line terminal   shall be one calibration  impulse at a voltage
between 50 and 75 percent of the full voltage followed by three impulses
at full voltage.
      By agreement between the manufacturer      and the purchaser at the
time of the enquiry, tests may be made with positive polarity, but in this
case sudden changes of polarity have to be avoided.
        NOTE- In dry-type transformers, the lightning impulse test can give rise to
   capacitive partial discharges in the air which do not endanger the insulation. These
   partial discharges lead to changes in the current waveform,       whilst the voltage
   waveform varies only slightly or not at all.
17. TEMPERATURE-RISE                     TEST
17.1 Provisions  of 4.2.1,            4.1~2, 4.1.3,       4.3, 4.9.1,        4.9‘2 and 4.9.3               of
IS : 2026 ( Part 2 )-I9777           are applicable,       in addition       to the following.
17.2 Methods          of Loading    - At the choice of the manufacturer,          any of
the following methods may be applied.
            -
     *Specification for power transformers : Part 3 Insulation level and dielectric tests
( second revision ) .
   tSpecilication   for power transformer3    : Part 2 Temperature-rise             (Jirst rctisioh ).
                                                14
Y
                                                                           IS:11171-     1985
       17.2.1 Direct Loading Method* - One winding,     preferably   the inner
    winding, of the transformer  is excited at rated volatge with the other
    connected   to a suitable load such that rated currents      flow in both
    windings.
      17.2.2 Back-to-Back Method* - This              is the preferred   method,   applicable
    when there are two similar transformers             available.
           Two transformers,   one of which is the transformer   under test, are
    connected in parallel, and preferably    the inner windings are excited at
    the rated voltage    of the transformer   under test. By means of different
    voltage ratios or an injected voltage, the rated current is made to flow in
    the transformer   under test.
            NOTE - In view of the fact that the transtormers will be operated at two differ-
       ent taps the winding temperature-rise   of two transformer  may be slightly different.
       While interpreting the results, appropriate corrections to the temperature-rise should
       be made in accordance with 17.3.
       17.2.3 Simulated Load Method ( By Agreement Between /he Munufacturer and
    Purchaser ) - This method is used for an enclosed or non-enclosed       dry-
    type unit with natural air cooling, when only the transformer under test is
    available, or when there is a similar transformer   available but there are
    limitations on the test equipment.
           Temperature   tests are made by utilizing the rises obtained              on two
    tests, one with no-load loss only, and one with load losses only,                that is,
    short-circuit run.
          The no-load test at rated voltage is continued until stead-state condi-
    tions are obtained;  individual winding temperature    rises, AtI, are then
    measured.
          The short-circuit run with rated current flowing in one winding and
    the other winding short-circuited  is started immediately   following the no-
    load run, and continued until steady-state     conditions are obtained when
    the individual winding temperature    rises, A BO, are measured.
           The total winding rise, no’,, of each winding,            with rated current in
    the winding     and normal    excitation of the core,            is calculated  by the
    following formula:
                        Afo   =   A&[ 1 + ( $$-) lea’]
                                                    0e8
           NOTE -   For other types of transformer,    modifications to the formula may be
       necessary.
        *The duration of the test may be reduced by exciting the core for a period of time
    ( preferably not less than 12 h ) prior to the application of test current to the
    windings.
                                               15
iS : 11171- 1985
17.3 Winding      Temperature-Rise      Correction    for Reduced Curr-
ent - When the input test current It is below the rated value of current
I,, but not less than 90 percent IN, of the temperature   rises, A& of the
windings, shall be measured by the resistance method when steady-state
conditions  have been reached,    and corrected  to rated load conditions,
aeN, by the formula:
                              A& = A4           [$I”
      The value of q shall be taken       as:
      AN transformers       : l-6, and
      AF transformers       : 1.8.
17.4 Determination         of Constant    Temperature    Conditions - .The
ultimate temperature-rise     is reached when the temperature   rise becomes
constant;  this is considered to have been achieved when the temperature-
rise does not vary by more than 2 percent uf the permissible temperature-
rise per hour or 2°C per hour, whichever is the smaller.
      For the purpose of determining     when constant temperature    condi-
tions have been achieved, thermocouples,    thermistors, RTDs or thermome-
ters shall be applied to the following surfaces:
      a) Enclosed and non-enclosed units - Centre of top yoke and as close
         as practicable   to the innermost   low-voltage  winding conductors
         at the top of the winding, the measurement      being on the centre
         leg of a three-phase   unit.
      b) Baled and totally enclosed units -      Centre     of top cover      surface    and
         centre of one side of enclosure        surface.
18. PARTIAL        DISCHARGE         MEASUREMENT
18.1 General - The partial discharge        measurement    is performed    in
accordance    with IS : 6209-1982*   and with Appendix        A of IS : 2026
( Part 3 )-19815_. It may be performed   on all kinds of dry-type transfor-
mers, but is especially   applicable  to transformers   having encapsulated
windings.
18.2 Basic Measuring         Circuit ( Typical Only ) - A basic                 measuring
circuit for the partial discharge test is shown in Fig. 1 and 2.
                        -
     *Methods for partial discharge measurements    ( first revision ).
    tSpecification   for power transformers: Part   3 Insulation levels and dielectric   tests
( secotui revision).
                                          16
                                                                     IS : 11171 - 1985
                   WINDING      WINDING
     FIG.   1   BASIC MEASURING CIRCUIT FOR THE PARTIAL DISCHARGE
                    TEST FOR A SINGLE-PHASETRANSFORMER
            ‘3
            LOW-VOLTAGE
              WINDING         HIGH-VOLTAGE
                             ‘WINDING,  DELTA
                              OR STAR CDNN-
                              FCTED
     FIG. 2     BASIC MEASURING CIRCUIT FOR THE PARTIAL DISCHARGE
                   TEST FOR A THREE-PHASE TRANSFORMER
       In the figures, a partial discharge-free    capacitor, C ( having    a
capacitance value large in comparison with the calibration generator capaci-
tance, C, ) in series with a detection impedance, xm, is connected to each
of the high-voltage   terminals.
18.3 Calibration      of Measuring     Circuit - Attenuation   of the disch-
arge pulses occurs both within the windings and in the measuring circuit.
Calibration   is carried out as described     in Appendix    A of IS: 2026
( Part 3 )-1981*, by injecting simulated discharge pulses from a standard
discharge calibrator at the transformer terminals.  The repetition rate of
calibration  pulses should be of the order of twice the frequency of the                        .
excitation voltage.
    *Specification for power transformer: Part 3 Insulation levels    and   dielectric   test
( second revision ).
I@-rlll7d    l   1985
18.4 Voltage    Application - The partial discharge measurement shall
be carried out after all dielectric tests are completed.   The low-voltage
winding shall be supplied from a three-phase or single-phase source,
depending on whether the transformer itself is three-phase or single-phase.
The voltage shall be as nearly as possible & sinewave form and of a
frequency suitably increased above the rated fr@queircy to avoid excessive
excitation current during the test. The procedure shall be as given
in 18.4.1 or 18.4.2.
       NOTE-    When the operating voltage of a transformer is wall below the voltage
  stated for the highest voltage for equipment, lower values for the pre-stress voltage
  and the measuring voltage may be selected by agreement between the manufacturer
  and the purchaser.
  18.4.1     Three-Phase   Transformers
      a) Windings intended for connection to systems which are solidly
         earthed or earthed through a low impedance:
                                                          1.5 ir,
                  A line-to-earth   pre-stress voltage ofI        shall be indu-
                                                           1/ 3
                  ted for 30 s ( LJ,,, being the highest v&age    for the equip
                  ment ), followed without interruption by a line-to-earth
                  voltage ofK>$           for 3 min,   during   which     the   partial
                  discharge shall be measured.
      b)    Windings intended for connection to systems which are isolated
            or earthed through a considerable impedance (for example, an
            arc-suppression coil ) :
                 A phase-to-phase pre-stress voltage of 1.5 U, shall be indu-
                 ced for 30 s, with one line terminal earthed, followed with-
                 out interruption by a phase-to-phase voltage of 1.1 U,,, for
                 3 min, during which the partial discharge shall be measured.
                 This test shall be repeated with another line terminal
                 earthed.
   18.4.2 Single-Phase Transformers - Single-phase transformers for use on
three-phase systems shall be tested as for three-phase transfomers, bearing
in mind that the highest voltage for equipment, U,, is a phase-to-phase
voltage.
      Furthermore,   in the case of a single-phase           transformer connected
phase-to-neutral and tested according to 18.4.1(b),          repeating the test with
another line terminal earthed does not apply.
18.5 Partial Discharge      Acceptance    Levels - The acceptance     level
for the partial discharge measured as above shall be subject to agreement
between the manufacturer and the purchaser.
                                            18
                                                                      IS :11171-1965
     In cases of dispute, investigational procedures                    as detailed    in
Appendix A of IS : 2026 ( Part 3 )-1981* shall be applied.
19. MEASUREMENT                   OF ACOUSTIC            SOUND LEVEL
19.1 The method of test and criteria for conformity shall be as agreed                 to
between the manufacturer and the purchaser.
20. SHORT-CIRCUIT                 TEST
20.1 This test shall be as specified in IS : 2026 ( Part 1 )-1977t.
      NOTE-        References to gas relays and tanks in IS : 2026 (Part   1 ) - 1977t are
  not applicable    to dry-type    transformers.
21. TOLERANCES
21.1 Tolerances       shall be as specified in Table 7 of IS : 2026 ( Part 1 ) -
1977t.
                          SECTION           6      ENCLOSURES
22. DEGREE OF PROTECTION                           BY ENCLOSURES
22.1 The design of an enclosure is dependent upon the location                        and
environmental conditions in which the transformer is installed.
       NOTE- A separate standard on classification of degree of protection provided
  by enclosures is under preparation. In the meantime, reference may be made to
  IS : 2147-1962$.
                              APPENDIX                        A
                                 ( Clause 3.2.1 )
                      UNUSUAL           SERVICE          CONDITIONS
A-l. In addition to high or low ambient temperature and high altitude,
other environment conditions which may affect design and application can
exist and are not necessarily covered by this standard.
    *Specification    for power transformers:  Part 3 Insulation levels and ‘dielectric
tests ( second revision ).
    tspecification for power transformers: Part 1 General (,&St rsision. )
    #Degree of protection     provided by enclosures for low voltage switchgear     and
controlgear.
                                                    19
t$ : 11171 - 1985
       Examples  of such conditions    are damaging. fumes and                            vapours,
excessive and abrasive dust, steam, salt spray, excessive moisture,                       dripping
water.
       NOTE - The seriousness of the effects of the conditions listed above varies
   widely depending upon which design of dry-type transformer is involved. While
   such conditions may have little or no effect on a sealed, dry-type transformer, they
   may have serious effects on other kinds of dry-type txansfbrmer.
A-2. Enclosed or non-enclosed    non-encapsulated-winding    dry-type trans-
formers are normally    designed for installation  indoors in dry locations.
They will, however, operate successfully where the humidity is high, provil
ded precautions are taken to keep.them dry if they are shut down for long
periods.
                                     APPENDIX                       B
                                        ( Clause 6.1 )
       INFORMATION               REQUIRED            WITH ENQUIRY            AND ORDER
B-l.    RATING         AND GENERAL                  DATA
B-l.1    Normal        -    The following        information      should be given in all cases:
        4     Particulars     of the specifications        to be complied   with;
        b)    Kind     of transformer       ( see definitions     given in 2 );
        4     Single or polyphase          units;
        4     Number        of phases in system;
        e)    Frequency;
        f)    Information        as to whether       an enclosure    is required    or not.
              If it is, the degree of protection of the enclosure ( see 22 ).
              Information    on the gas, if required, to fill the enclosure;
         g)   Method       of cooling;
         h)   Indoor    or outdoor       installation;
         3    Rated    power ( in LVA);
         k)   Rated    voltage    ( for each winding         );
        4     State whether     tappings   are required,    and             if SO, whether     off-
              circuit tap-changers   or links are required;
                                                    20
       4    Highest voltage for equipment,            U,   ( for each winding );
       P) Insulation level, that is, values of test voltage at power frequency
          and, if required, lightning impulse ,for which each winding is to
          be designed [see IS: 2026 ( Part 3 )-1981* 1.
      q) Connection symbol;
      r) Impedance voltage at rated current, if specific value is required;
       s) Neutral terminals, if required ( for each winding );
       t) Method of system earthing             ( for each winding );
       u) Any peculiarities of installation, for example space limitations,
          difficulty of maintenance, storage conditions;
       v) Any other appropriate information, for example site conditions,
          duty for which the transformer is required, system overvoltages;
          and
       w) Details of fittings required and an indication of the side from
          which meters, rating plates, etc, should be readable.
B-l.2 Special         -   The following additional         information       may be required
to be given:
       4    Whether a lightning impulse test is required;
       b) Altitude above           sea level if in excess of 1 000 m ( see 10.3 and
          11.2 );
        c) Temperature of cooling air if above or below values given in
           3.1 ( b ) ( see 10.2 also );
       d) Whether the transformer is to be directly connected                            to other
          apparatus which may affect short-circuit conditions;
       e) Whether          unbalanced      loading    is anticipated         and if so, details
          thereof;
       f)   Details of intended regular cyclic overloading;
       g) Connections required ex-works in the case                          of a    transformer
          having alternative winding connections; and
        h) Which snecial tests ( see Section 5 ) are reouired.                 and for each of
           these te’sts the relevant acceptance conditions                      ( levels, lim;ts,
            etc ).
    *Specification    for power transformers:   Part 3 Insulation   levels    and   dielectric tests
(second revision ).
                                                 21
    B-2. PARALLEL               OPERATION
    B-2.1 If parallel operation with existing transformers is required, this
    should be ‘stated and the following information given concerning the
    existing trnsformers:
            a) Rated power ( kVA );
          ‘b) Rated voltage          ratio;
     .I
     1
           Cl Voltage ratios         corresponding to tappings other than the principal
                     tapping;
I           4        L,oad loss at rated current on the principal     tapping,   corrected to
                     the appropriate,reference   temperature;
                     Impedance voltage at rated current ( on the principal tapping );
    .,t   . e)
          .fi
                     Short-circuit impedances, at least on the extreme tappings, if the
                     tapping. range of the tapped winding exceeds f 5 percent; and
                g)   Diagram    of connections,   or connection   symbol, or both.