TF - Protection - Compatibility Mode
TF - Protection - Compatibility Mode
                                                                       Over-current Protection
      During a fault , the secondary current(s) of the C.T. increases and if the C.T. sec. current increase beyond the setting of the relay , the relay will operates wit
      hin a time (as per the fault current)
Generally IDMTL(Inverse Minimum Definite Time Lag) relays are used in HVPNL for protection of primary & secondary side as well as feeder p
rotection of the power transformer. An IDMTL Over current/Earth fault relay has a Aluminum Disc and will take a time to trip after occurrenc
e a fault. The tripping time of the relay is inversely proportional to the fault current.
If fault current is high , operating time is less and if fault current is less , relay will take a long time to operate.
The main drawback of IDMTL relay is to take some minimum operation time even for extreme high fault currents, say as high as 8-10 times the
rating of transformer.
If relay take even a small time to isolate (trip) such heavy fault currents , the power transformer may be in trouble during heavy faults.
So , we need a method by which the IDML relay allow to operate for fault currents below say 5x (5 times the capacity of transformer) and if faul
t current goes beyond 5x then plain over-current relay (non-IDMTL) will trip the transformer instantaneously.
This Non-IDMTL Over-current relay is called High-set or Instantaneous Relay.
Highset relay is always connected in series with the IDMTL relay so that it can see the same current as seen by IDMTL relay as show in picture belo
w.
Highset relays are never connected in incomers i.e. 132KV I/c,66KV I/c,33KV I/c & 11KV I/c and always provided on outgoing circuits i.e. 11KV Out
going feeders , 33KV Outgoings feeders etc so that for heavy outgoing feeder fault , the incomer should not trip and disturb other healthy feeders
connected to it.
In LV side of power transformer , all outgoing feeders are equipped with highset relay to trip the feeder instantaneously during a heavy fault. As al
ready indicated , no highset relay is provided on the LV Incomer panel/VCB of the power transformer. As the LV bus is fed by LV Incomer so if there
is some heavy/serious fault in the LV bus i.e. 11KV bus for a 66/11 or 132/11KV TF , 11KV Incomer panel’s relay will take some time to trip being ID
MTL relay and as bus fault is very nearer to T/F , such delay in tripping can’t be tolerated. So there is a provision of providing the Highset on HV si
de of TF to trip the transformer for LV bus faults.
In a Power Transformer , Restricted Earth Fault (R.E.F.) protection is provided on both H.V. and L.V. side if transformer is of Yy0 type. If primary is D
elta connected (if T/F is Delta-Star type) , no need of R.E.F. on Delta (HV) side. All the Earth Faults on outgoing feeders are looked by their relays. E
arth fault in bus zone will be seen by E/f relay on LV incomer.
Suppose
•an earth fault in a 11KV Incomer cable
•puncture of 11KV or 33KV L.A. of power transformer
•Damage of TF CT on HV side or LV side with a flash with ground
•Damage of LV cable box (LV incomer Indoor/Outdoor)
•Damage of HV or LV winding of transformer after shortening with core/earth
•Bird-age on transformer of HV/LV jack buses etc
Such faults are very nearer to transformer and transformer should be isolated from fault to avoid any mis-happening. We need a relay which will auto
matically sense the zone between HV C.T.s to HV winding/core (for HV R.E.F.) and between LV Winding/core to LV incomer C.Ts (for LV R.E.F.).
This relay needs to sense and isolate the earth faults in the above said zones so called Restricted Earth Fault Relay.As we need immediate tripping
, so these are non IDMTL relays i.e. don’t have a rotating disk e.g. CAG14 (Alstom) etc.So following may be cloncluded.
•A H.V. R.E.F. relay will sense any earth fault in H.V. C.Ts , HV Jack Bus, H.V. L.As , TF H.V. Bushing/core and winding.
Similarly
•A L.V. R.E.F. relay will sense any earth fault in L.V.Core/Winding/Bushing of the transformer , LV Jack bus (11KV Incomer cables in case of 132/11 or 6
6/11KV T/F) , LV L.As & L.V. C.T.s ( 33KV I/c C.Ts in case of 132/33KV T/f & 11KV Incomer C.Ts in case of 132/11KV T/F.
                                        Path of Current during Earth Fault on any outgoing feeder
For an Earth fault , the fault current have to return to neutral bushing of the source transformer through NCT as shown above whatever be the distance of l
ocation of Earth fault from source transformer
                                                 REF relay during Normal Loading condition
During normal condition , the phase currents in all phases will be approx. same and so Ict=0 (as vector sum of three phases currents 120deg apart will b
e zero.The current in NCT secondary will also be zero due to no Earth fault & no current in NCT primary i.e. in normal condition , there won’t be any curr
ent through neutral circuit of Power transformer.
So in normal situation , no current will flow through REF relay and it will not operate.
                                              REF relay during External Earth Fault Condition
During External Earth Fault condition, the fault current will flow through the NCT as well as through the REF core of the faulty phase CT.As direction of
                         both the currents are in opposition so nullify both the currents in relay and REF relay won’t operate.
                                   SO, THE REF RELAY WON’T OPERATE FOR A OUT-OF-ZONE EARTH FAULT
                                              REF relay during In-zone Earth Fault Condition
During In-zone Earth Fault condition, the fault current will only flow through the NCT & no t from the REF core of Incomer CT being fault before Income
           r panel.The current from NCT goes to REF relay and trips it being no counter current from REF cores of Incomers CTs to oppose it.
                                      SO, THE REF RELAY SHOULD OPERATE FOR A IN-ZONE EARTH FAULT
                                                                Differential Protection
Differential Protection is most sensitive & fast acting protection of the power transformer. It sense the difference in the currents received from the HV si
de & LV side CT’s differential cores. It covers the area from the differential core of HV CTs to the differential core of LV CT’s including Las , HV/LV jack bu
ses , TF winding , cores & bushings etc
A Buchholz relay is a gas and oil operated device installed in the pipe work between the top of the transformer main tank and the conservat
or. A second relay is sometimes used for the tap changer selector chamber. The function of the relay is to detect an abnormal condition
within the tank and send an alarm or trip signal. Under normal conditions the relay is completely full of oil. Operation occurs when floats
are displaced by an accumulation of gas, or a flap is moved by a surge of oil. Almost all large oil-filled transformers are equipped with a Buch
holz relay, first developed by Max Buchholz in 1921.
PRESSURE RELIEF DEVICE
The pressure relief device (PRD) is designed to open and close automatically when the pressure reaches the operating pressur
e of the PRD.
The pressure relief device will open and remain open until the pressure falls to the reseal pressure. The pressure relief device r
eseals at a positive pressure.
 Magnetic Oil Level Gauges ( Indicator )are most commonly fitted on conservator of Power/ Distribution Transfor
mers. These Gauges give visual indication of oil level and provide Alarm facility at desired level. Float movement d
ue to rise and fall of oil level gives rotary movement to indicating pointer through bevel gears and magnets.
               THANK YOU !!
               Er.Sandeep Yadav
                 Executive Engineer,
              Protection Division,HVPNL
                  Gurgaon (Haryana)
Certified Energy Auditor from Bureau of Energy Efficiency
                      Govt. of INDIA
                   +919310404372
                  https://www.facebook.com/sanrwr
                   sandeep.hvpnl@gmail.com
                   xenmpccggn@hvpn.gov.in
Percentage Impedance:
The percentage impedance of a transformer is the volt
drop on full load due to the winding resistance and
leakage reactance expressed as a percentage of the
rated voltage.
It is also the percentage of the normal terminal voltage
required to circulate full-load current under short circuit
conditions. The impedance is measured by means of a
short circuit test. With one winding shorted, a voltage at
the rated frequency is applied to the other winding
sufficient to circulate full load current. The method of
testing will be discussed later.
   The maximum primary and secondary fault currents
can be calculated from 160MVA.
   e.g. Consider a transformer of 16MVA , 66/11kV with
%age impedance of 10%.Calculate the maximum fault
current that will flow during dead short circuit on its LV
bushings.
   Fault MVA = 16x10/100=160MVA
   Max. HV side fault current = 160x10^6/√3x66x10^3 =
1400A against rated current of 140A
   Max. LV side fault current = 160x10^6/√3x11x10^3 =
8400A against rated current of 840A
    A transformer with lower impedance will lead to a
higher fault level (and vice versa)
In practice, the actual fault level will be reduced by the
source impedance, the impedance of cables and
overhead lines between the transformer and the fault,
and the fault impedance itself.
 Size MVA                           Voltage rating in kV
   MVA      12kV    33kV   72,5kV       148kV              250kV   300kV   420kV
   0.5      4.75%   5.0%   5.5%
Dd0
Delta connected HV winding, delta connected LV
winding, no phase shift between HV and LV.
Dyn11
Delta connected HV winding, star connected LV
winding with neutral brought out, LV is leading HV
with 30°
Group I   - (0 o'clock, 0°) - delta/delta, star/star
Group II - (6 o'clock, 180°) - delta/delta, star/star
Group III - (1 o'clock, -30°) - star/delta, delta/star
Group IV - (11 o'clock, +30°) - star/delta, delta/star
1. The voltage ratio must be same.
2. The percentage impedance of the transformers should
   be same.(not essential but recommended)
3. The MVA rating of the transformers should be same.
   (not essential but recommended)
4. To avoid the circulating currents during parallel
   operation, the polarity of the transformers should be
   same
5. Phase sequence or phase rotation of the transformers
   should be same or we can say that vector group of the
   transformers should be same.
 Sr.No.   Group         Clock          Winding Configuration
                        Number/Angle
PHASE-EARTH FAULT
The flow of the earth fault current depends upon the flow of zero
sequence component of the current. The AT (ampere-turn) balance
between primary & secondary windings should be maintained. The
magnitude of the earth fault current is depends upon the method of
the earthing , the impedance of the winding and the transformer
configuration (Start-star , Delta-Star etc).It also depends upon the
position of fault in the winding.
Solidly earthed transformer windings have only their winding
impedance to limit the earth fault currents.
We can use earthing transformers & resistors to add further
impedance to the path of zero sequence currents.
FAULTS FACED BY A TRANSFORMER
INTER-TURN FAULTS
Degradation of the winding insulation is the major
cause of inter-turn faults. Such faults cause localized
over heating & formation of hotspots as the faulted
current carry more currents.
Inter-turn faults may cause very heavy currents to
flow within the shorted turns. Such heavy inter-turn
fault current in the shorted turns when referred to
primary side will reflect a very small amount of
current, which may be quite less to initiate any
protective device.
Resistance of faulted turns = 1mΩ (assume)
Voltage drop across faulty turns = 4V (assume)
Fault current = 4/0.001=4000A
Ib + Ic + Id = Ia
  Factors affecting Differential Protection Relay
            Tap    Vp       Vs        Ip       Is      Ratio
             1    138600   33000   66.65134 279.9356   4.200
             5    132000   33000   69.9839 279.936     4.000
            17    112200   33000    82.334 279.9356    3.400
TRANSFORMATION RATIO VARIATION