1672 Us Datasheet
1672 Us Datasheet
Full-color touch screen and tactile rotary knob for fast navigation
Navigate through
the display using the
Toggle between
measure mode and rotary dial, or tap your
form mode. finger on the display
screen to make a selection
Save
measurements
Fluke Connect
transfers data to
your smart device
Simplified User Interface and Testing Setup
The 1670 Series takes data management to the next level
streamlining test set up and preparation with an advanced
bidirectional user interface. When setting up your project, the
hierarchical tree topology for clients, sites, distribution boards,
Faster installation testing circuits, and test points can be easily customized using the
high-resolution colour touchscreen, a smart device, or by PC.
and documentation in
Edit, add, delete, or modify information directly on the tool as
three easy steps you test to ensure accurate data, or transfer updates to your
tester via the Fluke Connect™ mobile app or TruTest™ desktop
1. Setup software. Easy-to-read test tables help you quickly see that
you are capturing the right measurement data at the right test
Use the simplified bidirectional user
interface to quickly and easily setup
point, every time. Now you can spend less time setting up your
your tester using the color touchscreen, tester and organising data, giving you more time to perform
a smart device, or by PC. valuable testing.
Additional Capabilities
• Field updatable — you can apply any changes to • Unique zero adapter for fast, reliable, and accurate
regulations or enhancements to the tester in the test lead and mains cord compensation.
field. • Simultaneous readings of voltage measurements
• Compact and lightweight (less than 1.6 kg), with a between L-N, L-PE, and N-PE using the mains cord. No
padded neck strap to free your hands. need to change measurement connections.
• Full-color touch screen and tactile rotary knob for • RCD trip current and trip time measurement in
fast navigation, with no complex multi-level menus. parallel (RCD type AC, A, B, F and GFCI).
• Rechargeable 2,500 mAh Li-ion battery to cover a • PEFC or PSC and loop impedance measurement in
full day of testing. parallel, displays them together on the dual display.
• Standard USB-C charging Port with fast charging • Ring testing lets you select the required input
support for convenient on-the-go charging. sockets without exchanging test leads.
• Newly designed professional hard case for • Continuity test with low test current (10 mA) to
transporting and protecting your installation tester measure motor windings.
and accessories. • Earth Volt Touchpad detects raised earth voltages >
• Additional high current loop mode for faster 50 V, indicating potentially dangerous situations.
measurements than loop tests with non-trip mode
for RCD protected circuits.
• Insulation Monitoring Devices (IMD) tests.
• Surge Protection Device (SPD) functional test.
• Voltage drop measurement function.
• Z Max memory for loop tests to support easy
evaluation of the highest loop test value.
Earth resistance • •
Insulation resistance • • •
Other features
Illuminated display • • •
Memory, interface
Z Max memory • •
Memory • • •
Surge Protection Device (SPD) Insulation RAMP Test (Varistor Test) IEC 61643-11
Test Voltage Voltage Ranges Resolution Test Current Accuracy
500 V Step Ramp 0 V to 500 V 1V 1 mA ± (1.5 % + 3 digits)
100 kΩ to 3 MΩ 100 kΩ
No Trip mode: ± (3 %)
200 Ω 0.1 Ω
Hi Current mode: ± (2 %)
2000 Ω 1Ω ± 6 % [3]
[1] Valid for resistance of neutral circuit < 20 Ω and up to a system phase angle of 30°. Test leads must be zeroed before testing.
[2] Fluke Connect™ 1674 FC model only.
[3] Valid for mains voltage > 200 V.
Prospective Earth Fault Current (PEFC) Prospective Short Circuit Current (PSC)
Range Range Resolution
IK < 1000 A 1A
0 kA to 50 kA
IK ≥ 1000 A 0.1 kA
Computation: Prospective Earth Fault Current (PEFC/IK) or prospective short circuit current (psc/IK) determined by dividing measured mains voltage by
measured loop (L-PE) resistance or line (L-N) resistance, respectively.
A, F S • • •
[7]
B, B+ G • •
B, B+ S • •
[8]
RDC-DD, RCD A/EV, RCD B/Mi • •
GFCI • • •
[1] RCD test inhibited for V > 265 AC [6] A – Responds to AC and pulsed signal
[2] RCD tests permitted only if the selected current, [7] F – responds to AC, pulsed and high frequency
multiplied by earthing resistance, is < 50 V. [8] B, B+ – Responds to AC, pulsed, high frequency,
[3] AC – Responds to AC and smooth DC
[4] G – General, no delay [9] RDC-DD – Responds to residual currents of 6 mA DC
[5] S – Time delay
x 5
• • •
Ramp • • • • • • •
Auto • • •
Mains voltage 50 V – 265 V ac, 45/66 Hz
[1] Type B RCDs require mains voltage range of 195 V to 265 V.
[2] Type AC RCDs only.
[3] Type A RCDs are limited to 700 mA, not available for Type B RCDs.
30 % to 110 % of
10 % of I ΔN [2] 300 ms/step 500 ms/step ±5%
RCD-rated current[1]
[1] Specified trip current ranges (IEC 61008-1): 35 % to 140 % for Type A (> 10 mA)
30 % to 150 % for Type A IΔ N > 10 mA 35 % to 200 % for Type A (≤ 10 mA)
30 % to 210 % for Type A IΔ N = 10 mA 50 % to 200 % for Type B
20 % to 210 % for Type B [2] 5 % for Type B
50 % to 100 % for Type AC
Software updates
Expedited shipping
Included accessories
Heavy duty mains cord with single input connector, hard case,
USB-C power adapter for charging, remote control probe,
hanging strap, zero adapter, test leads and probes, alligator
clips, Li-Ion battery.
Additional options
The Fluke 1672 can be purchased as a standalone model or as a
kit with Fluke TruTest Software.