MANUAL
AIR CONDITIONER
Please read this installation manual completely before installing the product.
Installation work must be performed in accordance with the national wiring standards by authorize
Please retain this installation manual for future reference after reading it thoroughly..
MFL69312302
Rev.13_061620
ENGLISH
FRANÇAIS
ITALIANO
DEUTSCH
ESPAÑOL
РУССКИЙ ЯЗЫК
POLSKI
PORTUGUÊS
ed personnel only.
中文
ČEŠTINA
www.lg.com
Copyright © 2016 - 2020 LG Electronics Inc. All Rights Reserved.
2 TIPS FOR SAVING ENERGY
Model number :
Serial number :
Dealer’s name :
Date of purchase :
! WARNING
This symbol indicates potentially hazardous situation which, if not avoided could result in death or
serious injury.
! CAUTION
This symbol indicates a potentially hazardous situation which, if not avoided, may result in minor
or moderate injury.
IMPORTANT SAFETY INSTRUCTIONS 3
ENGLISH
! WARNING
Installation
• For electrical work, contact the dealer, seller, a qualified electrician, or an authorized service Center.
- Do not disassemble or repair the product. There is risk of fire, electric shock, explosion, equipment
malfunction, or injury.
• Request to the service center or installation specialty store when reinstalling the installed product.
- There is risk of fire, electric shock, explosion, equipment malfunction, or injury.
• Do not disassemble, fix, and modify products randomly.
- There is risk of fire, electric shock, explosion, equipment malfunction, or injury.
• The product shall be installed according to the national standards and local code.
• Apply totally enclosed noncombustible conduit in case of local building code requiring plenum.
• Use appropriate unit mounting procedures.
• Avoid direct sunlight.
• Avoid moist areas.
In-Use
• Do not place flammable objects close to the product.
- There is risk of fire, electric shock, explosion, equipment malfunction or injury.
• Do not allow product to get wet.
- There is risk of fire, electric shock, explosion, equipment malfunction or injury.
• Avoid dropping the product.
- There is risk of fire, electric shock, explosion, equipment malfunction or injury.
• If product gets wet, contact your dealer or authorized service center.
- There is risk of fire, electric shock, explosion, equipment malfunction, or injury. If the instructions are
not followed, it may cause death or severe injury of the user.
• Do not use sharp or pointed objects on product.
- There is risk of fire, electric shock, explosion, equipment malfunction or injury.
• Do not touch or pull the lead wire with wet hands.
- There is risk of product breakdown or electric shock.
! CAUTION
Installation
• If anyone other than a licensed professional installs, repairs, or alters LG Electronics air conditioning
products, the warranty is voided.
- All costs associated with repair are then the full responsibility of the owner.
• Do not install the unit in potentially explosive atmospheres.
In-use
• Do not clean using powerful detergents like solvent but use soft cloths.
- There is risk of fire, electric shock, explosion, equipment malfunction or deformation.
• Do not press the screen using powerful pressure.
- There is risk of product break-down or malfunction.
4 TABLE OF CONTENTS
TABLE OF CONTENTS
2 TIPS FOR SAVING ENERGY 25 HOLD SETTING
25 Hold
2 IMPORTANT SAFETY
26 ADDITIONAL OPERATION –
INSTRUCTIONS
VENTILATION
7 DESCRIPTION 26 Additional operation
ENGLISH
45 Sleep timer 84 Human detection mode setting
46 Turn-off Reservation 85 Discharge direction
47 Turn-on Reservation 86 CO2 Fan Control(general ventilator)
86 Economizer setting
48 SCHEDULE SETTING
48 How to enter schedule 87 USER SETTING
49 Daily Schedule 87 How to enter user setting
50 Schedules & Edit 87 User Setting
51 Schedules & Edit – Add schedule 88 Language setting
52 Exception day 89 Setpoint Type Setting
90 Temperature unit setting
53 ENERGY (air conditioner / 91 Screen saver timer setting
DX ventilator) 91 LCD brightness in idle setting
92 External device setting
53 How to enter energy
92 External device use
54 Instantaneous power check
93 External device types
55 Energy consumption
94 On condition / Off condition
57 Energy saving - Temperature Setback Timer
95 Date setting
58 Energy saving - Time Limit Control
96 Time setting
59 Energy setting - outdoor unit capacity
setting 97 Summer time setting
60 Energy setting - target instantaneous power 98 Password setting
setting 99 Schedule initialization
61 Energy setting - target power consumption 100 Theme setting
62 Energy setting - target operation time 100 Humidity display
63 Energy setting - Alarm Popup Setting 101 System restart
64 Energy setting – Usage data initialization 102 Indoor unit display light brightness setting
ENGLISH
DESCRIPTION
NEW STANDARD REMOTE CONTROLLER
Operation display
window
Up/Down/Left/Right OK Button
Button
Accessories
< Air conditioner main screen> <General Ventilation main <Dx Ventilation main screen>
screen>
Menu screen
In the main screen, press [<, >(left/right)] button to select the menu and press [OK] button to
move to menu screen.
In the menu screen, press [<, >(left/right)] button to select the category to set, and press [OK]
button to move to the detail screen.
DESCRIPTION OF THE OPERATION 9
ENGLISH
Setting screen
Select the category to set using [∧,∨(up/down)] button.
In each detail screen of the menu, as in the box in the left figure,
when “<,>” icons are displayed at the same time, you can im-
mediately apply the setting value by pressing [<, >(left/right)]
button.
※ For the values that can be set in each category, refer to the
detail manual for each function.
In each detail screen of the menu, as in the box in the left figure,
if only “>” icon is displayed, you can move to the detail setting
screen by pressing [>(right) or OK] button.
※ For the values that can be set in each category, refer to the
detail manual for each function.
Popup screen
The toast message is the message displayed at the bottom of the screen when an operation is
turned On/Off or if a function is set / cancelled.
The popup message is mainly displayed when an error occurred in the product.
ENGLISH
Interface screen
Select the product (air conditioner or ventilation) to set using [<, >(left/right)] button.
When you control the air conditioner and the ventilation product
with one remote controller, the screen is displayed as in the side
figure. You can set the air conditioner by pressing [<(left)] but-
ton and pressing [OK] button to move to the air conditioner
screen.
When you control the air conditioner and the ventilation product
with one remote controller, the screen is displayed as in the side
figure. You can set the ventilation by pressing [>(right)] button
and pressing [OK] button to move to the ventilation screen.
OPERATION SETTING
On / Off
Air conditioner and ventilator will be turned on or off.
Press the remote controller’s (On/Off) button.
- If the product is in operation, On/Off button will be illuminated.
If the product is in off, On/Off button backlight will be off.
Operation mode
You can easily control the desired operation mode.
In the main screen, press [<,>(left/right)] button to select the operation mode or home leave or
hold category, and press [∧,∨(up/down)] button to set the operation mode.
※Some products may not support some operation modes.
Mode Description
Cool Cool the room to the desired temperature.
Dry It removes the moisture with cooling.
Heat Heats the room to the desired room temperature.
The product automatically provides the appropriate fan speed based on
AI / Auto
the temperature of the room.
Fan Fan only operation, no cooling or heating.
Power Cool It provides strong cooling in short time.
Power heating Power heating increases indoor temperature quickly.
OPERATION SETTING 13
ENGLISH
Cooling Operation
Cooling operation’s minimum setting temperature is 18°C (16°C).
For some types of the indoor units, the desired temperature can be controlled in the units of 1°C
or 0.5°C.
! NOTE
The compressor starts after 3 minutes and the cold wind comes out.
In the cooling operation, you can select the desired temperature in the range of 18°C ~ 30°C
(16°C ~ 30°C).
The favorable temperature difference between the indoor temperature and the outdoor
temperature is 5°C.
For some types of the indoor units, you can select the desired temperature in the range of
16°C ~ 30°C.
14 OPERATION SETTING
Heating Operation
The heating operation’s minimum setting temperature is 16°C.
For some types of the indoor units, the desired temperature can be controlled in the units of 1°C
or 0.5°C.
! NOTE
In the heating operation, you can select the desired temperature in the range of 16°C ~ 30°C.
Heating operation is operated only in cooling/heating model. The heating is not operated in
cooling exclusive model.
OPERATION SETTING 15
ENGLISH
Dry Operation
Dry operation’s initial fan speed is “Low”.
Dry operation does not have a separate desired temperature.
- If you unit is operating in dehumidification mode and you press the [On/Off] button the dehu-
midification operation will shut off.
! NOTE
If you use it in the rainy season, or when the humidity is high, you can have both the
effective dehumidification and cooling operation at the same time.
16 OPERATION SETTING
- If you unit is operating in fan only mode and you press the [On/Off] button the the unit will stop.
! NOTE
It provides the Fan only operation without temperature control, with recirculation of indoor
air.
OPERATION SETTING 17
ENGLISH
AI / Auto operation
Auto operation’s initial desired temperature is 25°C.
The cooling exclusive model’s initial desired temperature is “It’s Fine”.
Cooling/heating model’s desired temperature can be controlled in the units of 1°C or 0.5°C.
For cooling exclusive model, the value can be controlled from “hot” stage to “cold” stage.
- Hot
- A little hot
- It’s fine
- A little cold
- Cold
- If you unit is operating in ai/auto mode and you press the [On/Off] button the ai/auto operation
will shut off.
! NOTE
If the product is a cooling/heating model, in the auto operation, the desired temperature can
be selected in the range of 18°C ~ 30°C.
If it does not operate as you wish, select another operation mode.
18 OPERATION SETTING
! NOTE
• Auto heating function only operates on cooling and heating models.
• Auto heating function doesn’t operate on cooling only models.
• When remote controller has a connection with indoor unit that does not support 'dual
setpoint', thermal operation function of indoor unit is replaced with ON/Off control from the
wired remote, when the user sets target temperatures in the below ranges.
- cooling target temp. range : 87~99 °F (30.5~37.5 °C)
- heating target temp. range : 40~59 °F (4~15.5 °C).
OPERATION SETTING 19
ENGLISH
Power Cool Operation
Power cooling quickly lowers the indoor temperature.
Desired temperature: 18°C
Fan speed : Power fan speed
Fan direction: Current fan direction
- During the power cooling, if fan speed or desired temperature is changed, the power cooling is
cleared, and it operates in the cooling operation mode.
- During the power cooling, if you press [On/Off] button, the power cooling operation stops, and
when you press [On/Off] button again, it operates in the cooling operation mode.
In the main screen, press [<,>(left/right)] button to select the operation mode category, and press
[∧,∨(up/down)] button to set the operation mode.
※The direct cooling type ventilation’s air conditioner operation mode is composed separately
from the ventilation operation mode.
TEMPERATURE SETTING 21
ENGLISH
TEMPERATURE SETTING
Controlling Desired Temperature
You can easily control to the desired temperature.
• In the main screen, press [<,>(left/right)] button to select the desired temperature category,
and press [∧,∨(up/down)] button to set the desired temperature.
- In the cooling, heating, and AI/auto mode, the desired temperature control is possible.
Mode Description
If the desired temperature is higher than the indoor temperature, the
cooling is not performed.
Cool
Set the desired temperature lower than the indoor temperature.
You can select in the range of 18°C ~ 30°C (16°C ~ 30°C).
If the desired temperature is lower than the indoor temperature, the heat-
ing is not performed.
Heat
Set the desired temperature higher than the indoor temperature.
You can select in the range of 16°C ~ 30°C.
For cooling/heating product, you can select in the range of 18°C ~ 30°C.
AI / Auto For cooling exclusive product, you can select Hot, A little hot, Adequate,
A little Cold, and Cold.
! NOTE
The favorable temperature difference between the indoor temperature and the outdoor
temperature is 5°C.
22 TEMPERATURE SETTING
! NOTE
The temperature distribution in the remote controller installation space is not uniform, so
there can be a little difference between the temperature you actually feel and the remote
controller’s room temperature display
According to Control type setting value
• Single setpoint
Fahrenheit: 52~99 °F
- below 52 °F: display ‘LO’
- over 99 °F: display ‘HI’
Celsius: 10.5~39.5 °C
- below 10.5 °C: display ‘LO’
- over 39.5 °C: display ‘HI’
• Dual setpoints
Fahrenheit: 34~99 °F
- below 34 °F: display ‘LO’
- over 99 °F: display ‘HI’
Celsius: 0.5~39.5 °C
- below 0.5 °C: display ‘LO’
- over 39.5 °C: display ‘HI’
- For indoor temperature below 50 °F (10 °C), the value perceived by the Thermostat(with
cable) is displayed.
• Because of location of Temperature sensing, the real room temperature and the this
displayed value can be different.
WIND SETTING 23
ENGLISH
WIND SETTING
Fan speed control
From the main screen, press [<,>(left/right)] button to select the fan speed category, and press
[∧,∨(up/down)] button to set the fan speed control the desired fan speed.
- It circulates in the order of Slow ↔ Low ↔ Medium ↔ High ↔ Power ↔ Auto.
※The auto Fan can be used only when the air contamination (CO2) sensor is installed.
※For some product some air flow settings may not be available.
24 HOME LEAVE SETTING
! NOTE
User can not change indoor unit status with wired remote controller while set 'home leave
mode' except for 'home leave mode' release control.
• Home leave mode will be released if indoor unit operation was changed by commands of
other controllers(central controller, drycontact and wireless remote controller).
• When occupied schedule event occurs while operate a home leave mode, home leave
mode will be released and indoor unit status follow the occupied schedule event.
• Indoor unit operation change as below when the home leave mode is released.
- The setpoints and operation mode values are reflected in the control events of the
scheduled events that are currently applied.
- If there are no schedule events, the setpoint shall be applied as last setpoints before the
home leave operation.
- If there are no setpoints before the 'home leave' operation(dehumidification or fan mode),
default values will be applied to the setpoints.
- Default values : dual setpoint auto , heat 60 °F(16 °C), cool 86 °F(30 °C)
HOLD SETTING 25
ENGLISH
HOLD SETTING
Hold
User can use this function when they want to manage indoor unit as home leave control mode
only.
! NOTE
Can not change indoor unit status with wired remote controller while set ‘hold mode' except
for ‘hold mode' release control.
• Hold mode will be released if indoor unit operation was changed by commands of other
controllers(central controller, drycontact and wireless remote controller).
• A scheduled event is not applied to the indoor unit during a hold mode, even if a scheduled
event is set.
26 ADDITIONAL OPERATION –VENTILATION
Energy saving It performs the energy saving function while ventilating efficiently.
! NOTE
The general ventilation and the direct cooling type ventilation’s additional operation are the
same.
The ventilation product’s additional functions (air cleaning / heater / humidification / fan auto)
setting methods are the same as the air conditioner.
EXTERNAL EQUIPMENT CONTROL SETTING 27
ENGLISH
EXTERNAL EQUIPMENT CONTROL SETTING
External equipment control
It is the function to set the contact point output of the external equipment control mode.
• In the main screen, press [<,>(left/right)] button to select the external equipment control cate-
gory, and press [∧,∨(up/down)] button to set the contact point output.
Mode Description
On When it is set to “On”, it always performs the contact point output.
When you set it to “Off”, it does not perform the contact point output in
Off
any case.
When it is set to “auto”, the contact point output is decided according to
Auto
the user setting’s external equipment logic setting value.
! NOTE
Please use the corresponding function when the external equipment is actually connected.
When the external equipment is not set, please maintain “Off” status.
For the detail external equipment control condition setting, refer to the user setting - external
equipment logic setting.
28 PLASMA PURIFICATION SETTING
In case of plasma purification single operation, it operates in fan mode / automatic wind state,
and the wind direction operated before the plasma purification single operation is turned off.
! NOTE
• If mode is changed during plasma purification single operation, it is switched to the air
cleaning additional operation.
• Air cleaning operation may not be displayed or performed in some products.
OVERRIDE CONTROL SETTING 29
ENGLISH
OVERRIDE CONTROL SETTING
Override control
In dual setpoint setting, wired remote controller can manages indoor unit status based on pro-
grammed control events which have occupancy option.
Override control function switches between ‘occupied’ and ‘unoccupied’, and vice-versa.
User can set timer option which can return to original schedule event in override function menu.
OK
! NOTE
• If there are no 'occupied' schedule event when operate 'override' control, wired remote
controller change indoor unit operation as below default setting value.
- operation mode : Auto
- target temperature : 86 °F(30 °C)(cool), 60 °F(16 °C)(heat)
• If there are no ‘unoccupied' schedule event when operate 'override' control, wired remote
controller change indoor unit operation as 'home leave' mode default value.
- operation mode : Auto
- target temperature: 'home leave' target temperature.
• If wired remote controller received command from other controller, ‘Override’ operation will
be released.
• When schedule event occurs while operating an override mode, override mode will be re-
leased and indoor unit status follow the schedule event.
30 MONITORING SCREEN
MONITORING SCREEN
How to enter fine dust status screen
• In the main screen, press [Back] button to move to monitoring/additional functions screen, and
press [<, > (left/right)] button to move to fine dust status screen. (Method 1)
• In the menu screen, press [<, > (left/right)] button to select the fine dust screen category, and
press [OK] button to move to the fine dust status screen. (Method 2)
MONITORING SCREEN 31
ENGLISH
Fine dusts status
It is the function to monitor dust value measured by the dust sensor mounted inside the air con-
ditioner.
• In the fine dust status screen, you can check fine dust, ultra fine dust, and super ultra fine dust
concentration values.
• The overall index displays the worst dust status value among the three dust status values.
! NOTE
• The fine dust status may not be displayed in some products.
• Fine dust status can be checked only when the product is in operation.
32 SUB FUNCTION SETTING
ENGLISH
Energy Saving Setting
The energy saving cooling function is the function to control the desired temperature during the
cooling operation to improve the comfort of the user and to improve the power saving perform-
ance.
! NOTE
The energy saving function is an additional function, and it may not be displayed/operated in
some products.
The energy saving function is possible only when the product is in the cooling operation.
34 SUB FUNCTION SETTING
! NOTE
The air cleaning function is an additional function, and it may not be displayed/operated in
some products.
The air cleaning function is possible only when the product is in operation.
If you want air cleaning single operation, set air cleaning in the wind only operation.
SUB FUNCTION SETTING 35
ENGLISH
Fan Auto Setting
Select fan operation after performing thermal control of indoor units.
If set to 'ON', fan operation keeps on after thermal operation of indoor units.
! NOTE
The fan auto function is an additional function, and it may not be displayed/operated in some
products.
36 SUB FUNCTION SETTING
Humidification setting
It is the function to activate the humidifier installed in the product when the indoor air is dry.
! NOTE
The humidification function is an additional function, and it may not be displayed/operated in
some products.
SUB FUNCTION SETTING 37
ENGLISH
Electric Heater Setting
It is the function to reinforce the heating capability by turning on the electric heater during the
heating operation.
! NOTE
It can be set only in the heating operation.
The heater function is an additional function, and it may not be displayed/operated in some
products.
38 SUB FUNCTION SETTING
! NOTE
It can be set 30 seconds after the operation stopped.
The robot cleaning function is an additional function, and it may not be displayed/operated in
some products.
SUB FUNCTION SETTING 39
ENGLISH
Ventilation kit Setting
Function enables operation of an optional ventilation kit with indoor units
! NOTE
The ventilation kit function is an additional function, and it may not be displayed/operated in
some products.
40 SUB FUNCTION SETTING
! NOTE
The comfort cooling function is an additional function, and it may not be displayed/operated in
some products.
The comfort cooling function is only possible when the product is in the cooling operation.
ZONE CONTROL SETTING 41
ENGLISH
ZONE CONTROL SETTING
Zone Control
A function to control zone with duct type indoor units.
Wired Remote controller can control maximum 8 zones.
OK
! NOTE
According to installation setting value
• If no function is supported this entry can not function.
• Old type
- Zone control is currently only available to monitor.
• New type(4zone or 8Zone)
- Any number of zones is installed is displayed on the screen can be controlled.
42 LOCK SETTING
LOCK SETTING
How to enter lock setting
• In the menu screen, press [<,>(left/right)] button to select “lock setting” category, and press
[OK] button to move to the lock setting list screen.
• In the lock setting list, if you press [∧ ,∨(up/down)] button, you can turn on/off the correspon-
ding lock function.
OK
Lock Description
All lock It locks all button operation of the remote controller.
On/Off lock It locks the On/Off button operation of the remote controller.
Mode lock It locks the operation mode button operation of the remote controller.
It is the function that can limit the range of the desired temperature that
can be set in the wired remote controller.
Temperature range - Single: Lower limit : 16~30 °C (60~86 °F)
lock Upper limit : 16/18~30 °C (60/64~86 °F)
- Dual : Cooling : 50~99 °F (10~37.5 °C)
Heating : 40~90 °F (4~32 °C)
! NOTE
In the central controller, when the central control temperature range lock is set, the wired
remote controller’s temperature lock setting is cleared.
The temperature change by external equipment is reflected regardless of the remote
controller temperature range lock.
TIMER SETTING 43
ENGLISH
TIMER SETTING
Timer entrance and setting method
• In the menu screen, press [<,>(left/right)] button to select the timer category, and press [OK]
button to move to the timer setting list screen.
• In the timer setting list screen, press [∧,∨(up/down)] button to select the timer to set, and
press [OK] button to move to the detail screen.
• After setting the value, when you press [OK] button, the timer is activated.
• After setting the value, if you press [Back] button, the changed value will not be applied.
OK
44 TIMER SETTING
Simple timer
You can easily set the timer in the range of 1~7 hours in the units of 1 hour.
OK
! NOTE
If the product operation is On, the easy timer turns off the operation after the corresponding
time.
If the product operation is Off, the easy timer turns on the operation after the corresponding
time.
If the easy timer operation is turned On/Off before the timer operation, the set timer will be
cleared.
TIMER SETTING 45
ENGLISH
Sleep timer
Sleep timer is the function to operate the air conditioner in sleep mode before going to sleep for
certain hours and stop the operation.
OK
! NOTE
You can set the sleep timer while the product is in operation.
If the sleep timer operation is turned On before the timer operation, the set timer will be
cleared.
46 TIMER SETTING
Turn-off Reservation
The product is automatically turned Off at the set timer time.
OK
! NOTE
Even if the Turn-off Reservation operation is turned On/Off after the setting and before the
timer operation, the set timer is not cleared.
TIMER SETTING 47
ENGLISH
Turn-on Reservation
The product is automatically turned On at the set timer time.
OK
! NOTE
Even if the Turn-on Reservation operation is turned On/Off after the setting and before the
timer operation, the set timer is not cleared.
48 SCHEDULE SETTING
SCHEDULE SETTING
How to enter schedule
• In the menu screen, press [<,>(left/right)] button so select the schedule category, and press
[OK] button to move to the schedule setting list screen.
• In the schedule setting list screen, press [∧,∨(up/down)] button to select the menu to set, and
press [OK] button to move to the detail screen.
OK
SCHEDULE SETTING 49
ENGLISH
Daily Schedule
It is the function that can check the status of the timer (schedule) saved in the remote controller.
• In the schedule list, select the daily schedule status category, and press [OK] button to move to
the detail daily schedule status screen.
• You can use the remote controller’s [<,>(left/right)] button to check the timer information of
other dates.
• You can use the remote controller’s [∧,∨(up/down)] button to check the corresponding date’s
other timer information.
• Select the timer information, and press [OK] button to move to the corresponding timer’s edit
screen.
! NOTE
In the daily schedule status screen, even if the timer (schedule) is set, if the corresponding
date is designated as an exception date, the schedule will not be performed.
Less than 5 schedules per day is recommended.
50 SCHEDULE SETTING
• Select the timer information, and press [OK] button to move to the corresponding timer’s edit
screen.
ENGLISH
Schedules & Edit – Add schedule
Description of each stage in Add schedule
When stages 1~4 are completed, along with the message of ‘schedule is added’, it moves to
View and edit schedule screen.
52 SCHEDULE SETTING
Exception day
It is the function to automatically stop the operation on the set timer day.
• In the schedule list, select the exception day category, and press [OK] button to move to the
Exception day designation detail screen.
• In the exception day, you can check, and add/change/delete the exception day information
saved in the remote controller.
- To add an exception day, in the Exception day registration detail screen, designate
year/month/day, and press [OK] button to save the Exception day.
- Select the Exception day to edit using [∧,∨(up/down)] button, and press [OK] button to move
to the edit screen.
- In the exception day edit screen, you can check, delete/change the corresponding exception
day’s setting contents.
- When you change the exception day information, you need to save it after the change.
ENERGY 53
ENGLISH
ENERGY (air conditioner / DX ventilator)
How to enter energy
• In the menu screen, press [<,>(left/right)] button to select the energy category, and press [OK]
button to move to the energy list.
OK
54 ENERGY
OK
• The target and the value of all can be set in the energy setting.
• The usage ratio compared to the target is the value expressed in current/target * 100.
※For how to set the energy, refer to the energy setting.
! NOTE
Instantaneous power: It is the power currently used in the product.
ENERGY 55
ENGLISH
Energy consumption
You can check the energy consumption (operation time, power consumption).
※There may be some error with the actual consumption, so use it only for reference.
• In the energy list, select the “energy consumption” category, and press [OK] button to move to
the detail screen.
OK
• In the detail screen, press [<,>(left/right)] button to move to the power consumption and opera-
tion time screen.
<, >
56 ENERGY
• Operation time unit is time (hr.), and power consumption unit is kWh.
• The power consumption display can be checked when it is connected to the indoor unit that
supports the power consumption information display function.
Description
List
Power consumption Operation time
You can see the power consump- You can see the operation time
Year On Year Usage tion compared to the same month compared to the same month of
of the previous year. the previous year.
It displays the daily power con- It displays the daily operation time
Weekly usage
sumption of the current month. of the current month.
ENGLISH
Energy saving - Temperature Setback Timer
It is the function to return to the desired temperature after the set time after the product opera-
tion for energy saving.
• In the energy list, select “Energy saving” category, and press [OK] button to move to the en-
ergy saving screen.
• In the energy saving list, select “Temperature Setback Timer” category, and press [OK] button
to move to the Temperature Setback Timer setting screen.
OK
OK
• When it is set to On, you can set the time (10 minutes ~ 120 minutes, 10 minutes unit) and the
temperature (18°C ~ 30°C), and after the setting, when you press [OK] button, the set value is
saved.
• When the desired temperature setback timer setting is set to “On”, after the set time, the de-
sired temperature is recovered to the set temperature.
! NOTE
When it is set at the same time with the remote controller desired temperature range lock or
the central control temperature range lock, it may not return to the desired temperature.
58 ENERGY
OK
OK
• In the detail screen, you can select “On/Off” to turn on and off the time limit control function.
When it is set to On, you can set the time (30 minutes ~ 540 minutes, 30 minutes unit), and
after the setting, if you press [OK] button, the set value is saved.
If you do not press [OK] button but press [Back] button, it moves to the list screen without sav-
ing the set value.
• If the time limit control is set to “On”, the operation stops after the set time.
! NOTE
If it is set at the same time with the remote controller operation lock, the time limit control
will not be performed.
ENERGY 59
ENGLISH
Energy setting - outdoor unit capacity setting
It is the function that can set the outdoor unit capacity.
• In the energy list, select “energy setting” category, and press [OK] button to move to the en-
ergy setting screen.
• In the energy setting list, select “outdoor unit capacity setting” category, and press [OK] button
to move to the outdoor unit capacity setting screen.
OK
OK
• In the detail screen, you can select “On/Off” to set the outdoor unit capacity. If it is set to On,
you can set the outdoor unit capacity (minimum 1kW), and after the setting, if you press [OK]
button, the set value is saved. If you do not press [OK] button but press “Back’ button, it
moves to the list screen without saving the set value.
• If the capacity setting is set to “On”, in the Instantaneous power screen, it is displayed as “all”
capacity.
• For the outdoor unit capacity, refer to the label of the outdoor unit product.
- For Single product and Multi product, the first 3 digits of the model name is the outdoor unit
capacity.
ex) For ABC1019…, it is 10.1kW
- For Multi-V product, the first 2 digits of the model name < 0.75 is the outdoor unit capacity.
ex) For ABCD101.…, it is 10 * 0.75 = 7.5kW
• For TMS users, refer to the all capacity displayed on TMS.
! NOTE
According to the user input, there may be difference to the actual product capacity.
60 ENERGY
OK
OK
• In the detail screen, you can select “On/Off” to set the target Instantaneous power.
If it is set to On, you can set the target Instantaneous power (minimum 1kW), and after the
setting, if you press [OK] button, the set value is saved.
- If the outdoor unit capacity is set, the maximum value is the outdoor unit capacity
- If the outdoor unit capacity is not set, the maximum value is 9999kW
If you do not press [OK] button but press “Back’ button, it moves to the list screen without
saving the set value.
• When the target Instantaneous power setting is set to “On”, in the Instantaneous power
screen, it is displayed as “all” capacity.
ENERGY 61
ENGLISH
Energy setting - target power consumption
It is the function to set the target power consumption per hour.
• In the energy setting list, select “target power consumption” setting category, and press [OK]
button to move to the target power consumption setting screen.
OK
OK
• In the detail screen, you can select “On/Off” to set the target power consumption.
When it is set to On, you can set the target power consumption (minimum 1kWh, maximum
100kWh), and after the setting, if you press [OK] button, the set value is saved.
If you do not press [OK] button but press “Back’ button, it moves to the list screen without
saving the set value.
• If the target power consumption setting is set to “On”, it is displayed as the energy
consumption’s power consumption target value.
- Daily target consumption: Weekly usage’s daily target
- Weekly target consumption: Monthly usage’s weekly target (daily target * 7)
- Monthly target consumption: Yearly usage’s monthly target (daily target * 31)
62 ENERGY
OK
OK
• In the detail screen, you can select “On/Off” to set the target operation time.
When it is set to On, you can set the target operation time (minimum 1hr. and maximum 24hr.),
and after the setting, if you press [OK] button, the set value is saved.
If you do not press [OK] button but press “Back’ button, it moves to the list screen without
saving the set value.
• If the target operation time setting is set to “On”, it is displayed as the energy consumption’s
operation time target value.
- Daily target : Weekly usage’s daily target
- Weekly target : Monthly usage’s weekly target (daily target * 7)
- Monthly target : Yearly usage’s monthly target (daily target * 31)
ENERGY 63
ENGLISH
Energy setting - Alarm Popup Setting
It is the function to set whether to use the target power consumption and the target operation
time notice popup window.
• In the energy setting list, select “target operation time” category, and press [OK] button to
move to the target operation time setting screen.
• In the notice popup list, select “target power consumption notice or target operation time no-
tice” category, and press [OK] button to move to the detail setting screen.
OK
OK
OK
! NOTE
The popup message appears once every hour.
64 ENERGY
OK
OK
OK
• In the initialization popup screen, if you press “check” button, all previously saved power con-
sumption and operation time are deleted.
FUNCTION SETTING 65
ENGLISH
FUNCTION SETTING
How to enter function setting
To enter the menu displayed at the bottom, you need to enter the function setting menu as fol-
lows.
• In the menu screen, press [<,>(left/right)] button to select the setting category, and press [OK]
button to move to the setting list.
• In the setting list, select the function setting category, and press [OK] button to move to the
function setting list.
OK
66 FUNCTION SETTING
Function Setting
Menu Description
Vane angle control setting You can control the wind blowing angle.
Elevation grill setting It is the function to operate the Elevation grill for the indoor unit filter cleaning.
Robot cleaning function is the function to automatically perform the filter
cleaning with the cleaner of the product when the air conditioner is used for
Robot cleaning setting
certain time period. It sets the manual or automatic operation of the robot
cleaning. You can set it 30 seconds after the stopping of the operation.
Auto dry function is the function to remove mold and moisture by drying the inside
Auto dry setting
of the indoor unit after the cooling operation and when the product is turned off.
Filter sign check and When it becomes the time for the indoor unit filter cleaning, the filter
initialization cleaning display appears, and it is the function to remove the display.
Change Temperature is the function to set the temperature for the
Change Temperature
automatic conversion between cooling and heating according to the
setting
temperature in AI operation mode.
When heating and cooling desired temperatures have been changed,
Dead Band the set value will maintain a difference between the heating and
cooling desired temperature.
It is the function to perform the pairing function of the Wi-Fi module
Wi-Fi pairing
connected to the indoor.
Zone Name setting Zone name settings allow you to select zone name.
Override set time setting When timed override is used, the set time will be a default value.
Home leave set When customer operate as home leave mode, this setting
temperature setting temperature value will be applied.
Comfort cooling setting It is the function to set the outdoor unit Comfort saving operation stage value.
ODU Refrigerant Noise It is the function to set the outdoor unit’s refrigerant noise reduction
Reduction setting function.
Defrost Mode setting It is the function to set the outdoor unit’s defrost mode operation.
It is the function to set the outdoor unit’s smart load control stage value.
Smart load control
(Smart load control is the function to calculate the necessary performance
setting
with the indoor and outdoor air temperature and humidity and operate.)
Low noise mode time It is the function to set the start and end time of the outdoor unit’s
setting low noise mode operation.
Advanced fan speed “Auto” It is the function to set the indoor unit’s fan auto by temperature.
Delay time setting It is the function to set the ventilation operation to start after the delay
(exclusive for ventilation) time.
Midnight air cooling It is the function to discharge indoor air and supply cool outdoor air
(ventilation interface) into the indoor during summer nights to save energy.
Human detection mode It is the function to set the operation of human detection mode.
This is a function to set the usage of the upper and lower vanes when
Discharge direction
operating the product.
A function that controls the fan when the product is turned ON/OFF,
CO2 fan control
based on the CO2 concentration in the ventilation product.
Provides outside air to a room to save energy and improve the air
Economizer setting
quality indoors.
FUNCTION SETTING 67
ENGLISH
Vane angle control setting
You can control the wind blowing angle.
- In the function setting list screen, press [∧,∨(up/down)] button to select the vane angle control
category, and press [OK] button to move to the up/down vane angle detail screen.
OK
• In the detail screen, press [∧,∨(up/down)] button to select “individual control, overall control,
standard”.
• Use [<,>(left/right)] button to select the vane.
- The selected vane is moving. Check the moving vane.
• Press [∧,∨ (up/down)] button to select the desired wind angle, and press [OK] button to save
the setting.
- The wind angle’s setting range can be changed to 5 stages or 6 stages according to the prod-
uct.
※If you do not press [OK] button, the selected wind angle will not be reflected.
Control Description
Each It sets the vane angle individually.
All It sets the vane angle of all the vanes of the product at once.
Standard It sets the vane angle to the factory initialization state.
! NOTE
For some product types, there are products with only 1 or 2 vanes.
68 FUNCTION SETTING
Value Description
Up Raises the Elevation grill toward the product
Stop Stops the movement of the Elevation grill
Down Lowers the Elevation grill toward the floor
! NOTE
The Elevation grill setting function may not work in some products.
FUNCTION SETTING 69
ENGLISH
Robot cleaning setting
Robot cleaning function is the function to perform the automatic filter cleaning with the cleaner
of the product when the conditioner is used for certain period of time. It sets the manual or auto-
matic operation of the robot cleaning.
- It can be set 30 seconds after the operation stop.
• You can use [<,>(left/right)] button to set the following setting values as follows.
Value Description
It automatically performs the robot cleaning when the accumulated in-
Auto
door unit operation time passes 30 hours
Manual It manually performs the robot cleaning.
! NOTE
The robot cleaning setting function may not work in some products.
Value Description
Use Use auto dry function
Not Use Not use auto dry function
! NOTE
Auto dry setting function may not work in some products.
70 FUNCTION SETTING
OK
! NOTE
• Some products have a Filter Time Remaining function that can be accessed with Filter Sign
check.
• Dirty filters will increase the cost to cool or heat the conditioned space.
• The filter check message is cleared after certain time without a separate clearing.
FUNCTION SETTING 71
ENGLISH
Change temperature setting
Change Temperature is the function to set the automatic Change Temperature between cooling
and heating operation according to the temperature in AI operation mode.
• In the function setting list, select the Change Temperature category, and press [OK] button to
move to the detail screen.
OK
Value
1~7°C(Default : 2°C)
It is the function that can be used only in cooling/heating product.
19ഒ
ڹ
! NOTE
The Change Temperature setting function may not work in some products.
72 FUNCTION SETTING
Dead Band
Dead Band function is used with a dual setpoint mode.
When heating and cooling desired temperatures have been changed, the set value will maintain a
difference between the heating and cooling desired temperature.
• In the function setting list, select the dead band category, and press [OK] button to move to the
detail screen.
OK
! NOTE
Dead Band function only can use in dual setpoint mode.
• When changing the desired cooling temperature, in case of that the difference with the
heating temperature becomes lesser than its minimal value of difference, it lowers the
desired heating temperature automatically.
• When changing the desired heating temperature, in case of that the difference with the
heating temperature becomes lesser than its minimal value of difference, it raises the
desired cooling temperature automatically.
FUNCTION SETTING 73
ENGLISH
Wi-Fi pairing setting
It is the function to perform the pairing function of the Wi-Fi module connected to the indoor unit.
• In the function setting list, select the Wi-Fi pairing category, and press [OK] button to move to
the detail screen.
- After selecting “Apply”, if you press [OK] button, the Wi-Fi pairing popup window is created,
select “check” and press [OK] button to request the Wi-Fi pairing.
OK
! NOTE
The Wi-Fi setting function may not work in some products.
74 FUNCTION SETTING
OK
OK
! NOTE
Zone name setting function may not work in some indoor unit products.
FUNCTION SETTING 75
ENGLISH
Override Set Time Setting
Override Set Time function can only be used in Dual Setpoint Control mode.
When timed override is used, the set time will be a default value.
OK
! NOTE
Override Set Time function can only be used in a dual setpoint control mode.
76 FUNCTION SETTING
OK
! NOTE
Home Leave Set Temperature function can only be used in a dual setpoint control mode.
FUNCTION SETTING 77
ENGLISH
Comfort cooling setting
It is the function to set the outdoor unit Comfort saving operation value.
• You can set the following values using [<,>(left/right)] button.
Value
Step 1
Step 2
Step 3
! NOTE
The Comfort cooling function does not work in the group control.
Comfort cooling setting function is only available in some products.
Value Description
Step 0 Not use
Step 1 Outdoor unit noise mode 1
Step 2 Outdoor unit noise mode 2
! NOTE
The ODU Refrigerant Noise Reduction function can be set only when the installer setting’s
outdoor unit function M/S setting is set to “Master”.
ODU Refrigerant Noise Reduction function is only available in some products.
78 FUNCTION SETTING
! NOTE
The Defrost mode setting function can be set only when the installer setting’s outdoor unit
function M/S setting is set to “Master”.
Defrost mode setting function is only available in some products.
FUNCTION SETTING 79
ENGLISH
Smart load control(SLC) setting
Change the outdoor unit’s Smart Load Control stage value.
(Smart load control is the function to calculate the indoor air temperature, outdoor air tempera-
ture, and humidity to operate effectively.)
• In the function setting list, select the Smart load control category, and press [OK] button to
move to the detail screen.
OK
Off Step 0
Step 1
Value Step 2
On
Step 3
Step 4
- When SLC is Operating, on the expanded screen’s monitoring information, ‘In Smart load con-
trol’ is displayed.
! NOTE
Smart load control function can be set only when the installer setting’s outdoor unit function
M/S setting is set to “Master”.
Smart load control function is only available in some products.
Step4 settings may not be available on some indoor unit products.
80 FUNCTION SETTING
OK
! NOTE
Low noise mode time setting function can be set only when the installer setting’s outdoor
unit function M/S setting is set to “Master”.
Low noise mode time setting function is only available in some products.
! CAUTION
If the function is not used, please set it to Off.
When you enter the low noise operation, the cooling capacity may be degraded.
FUNCTION SETTING 81
ENGLISH
Advanced fan speed “Auto” setting
It is the function to set the indoor unit’s temperature based auto fan usage.
It is the function to automatically change the fan speed according to the difference between the
indoor temperature and the desired temperature.
• You can set the following setting values using [<,>(left/right)] button.
Value Description
Set Change the fan speed automatically
Clear Do not change the fan speed automatically
! NOTE
Advanced fan speed “Auto” setting function is only available in some products.
82 FUNCTION SETTING
OK
Value
0 ~ 60 Minutes
FUNCTION SETTING 83
ENGLISH
Midnight air cooling (ventilation interface)
It is the function to discharge indoor air and supply cool outdoor air into the indoor during sum-
mer nights to save energy.
• In the function setting list, if you select midnight outdoor air cooling category and press [OK]
button, it moves to the detail screen.
- When you set the start and end time and press [OK] button, it saves and moves to the upper
level list.
OK
! NOTE
Whether to run the midnight air cooling is decided only when both air conditioner and
ventilation are stopped.
• Even if it is the set midnight air cooling time, it enters the midnight air cooling only when
the outdoor temperature conditions is met.
• During the midnight air cooling operation, “in midnight outdoor air cooling” message is
displayed on the monitoring screen.
• Midnight air cooling function may not work in some products.
! CAUTION
If you do not use the function, please set it as off.
84 FUNCTION SETTING
OK
After selecting human detection power saving mode category, if you press [OK] button, it moves
to the detail screen.
You can select OFF ← → On/Off Power saving ← → Temperature power saving for mode value.
You can set the time value when you select On/Off power saving or Temperature power saving.
FUNCTION SETTING 85
ENGLISH
After selecting human detection wind direction category, you can set the following setting values
using [<,> (left/right)] button.
Value Description
OFF Do not use human detection wind direction control
Direct Human detection direct wind operation
Indirect Human detection indirect wind operation
! NOTE
Human detection operation setting function may not work in some products.
Discharge direction
This is a function to set the usage of the upper and lower vanes when operating the product.
You can set the following setting values using [<,>(left/right)] button.
Concurrency (whole)
Discharge
Top
direction
Bottom
! NOTE
Discharge direction setting function may not be available on some products.
86 FUNCTION SETTING
OK
Condition 1 Condition 2
Off
Operation on Low
Periodic
Off
Operation off
Periodic
Economizer setting
Provides outside air to a room to save energy and improve the air quality indoors.
Value Description
Off Disable the economizer function to keep the outside air damper closed.
If the outside air temperature is lower than the air temperature indoors when
Auto
cooling is being operated, outside air is supplied to the room to save energy.
Opens the outside air damper opening by one stage to improve the indoor
Step 1
air quality by introducing fresh air into the room.
Opens the outside air damper opening by two stages to improve the indoor
Step 2
air quality by introducing fresh air into the room.
! NOTE
Economizer setting function may not be available on some products.
USER SETTING 87
ENGLISH
USER SETTING
How to enter user setting
To enter the menu displayed at the bottom, you need to enter the user setting menu as follows.
• Select the setting category, and press [OK] button to move to the setting list.
• Select the user setting category, and press [OK] button to move to the user setting list.
OK
User Setting
• You can set the product user functions.
• Some functions may not be available in some product types.
Menu Description
Language setting Set the language to be displayed on the remote controller.
Setpoint Type Setting It is the function to set GUI type on the remote controller.
Temperature unit setting Set the temperature unit displayed on the remote controller.
Screen saver timer setting Adjust the screen Off time of the remote controller.
LCD brightness in idle setting Adjust the remote controller’s screen brightness.
External device setting Set the name of external equipment and equipment logic setting
Date setting Set the date displayed on the remote controller.
Time setting Set the time displayed on the remote controller.
Summer time setting Set the summer time in the remote controller.
Password setting Set the password to prevent unauthorized change to remote controller settings.
Schedule initialization Initialize all timer settings in the remote controller.
Theme setting Set the theme of the remote controller screen.
It is the function to decide whether to display humidity on the main
Humidity display
screen and additional information screen.
System reboot Restart the remote controller.
Indoor unit display light
This function adjusts the brightness of the indoor unit display light.
brightness
88 USER SETTING
Language setting
Set the language to be displayed on the remote controller.
• In the user setting list, select the language category, and press [OK] button to move to the de-
tail screen.
• After the setting, if you press [OK] button, the setting is saved and moves to the previous
screen.
OK
Language
한국어 English Français
Deutsche Italiano Español
Русский Polski Português
中文 Čeština
USER SETTING 89
ENGLISH
Setpoint Type Setting
It is the function to set GUI type on the remote controller.
* Dual setpoint type is a function that makes it possible to set the cooling and heating target tem-
perature simultaneously. It is recommended for customers accustomed to using North Ameri-
can thermostats.
We recommend that you use it only in the region (North America).
If select dual setpoint option, target temperature ranges will be expanded and activated over-
ride, home leave, hold mode and occupancy information based schedule.
OK
1°C
Celsius
Value 0.5°C
Fahrenheit
! CAUTION
The temperature unit function may not work or work differently in some products.
You cannot set the temperature unit in the slave wired remote controller.
USER SETTING 91
ENGLISH
Screen saver timer setting
Adjust the screen Off time of the remote controller.
• Select the following setting values using [<,>(left/right)] button.
Value
15sec 30sec (default) 1min
! CAUTION
Selecting longer stand by screen will decrease LCD lifespan.
Value
0% 10% (default) 20% 30% Auto
! CAUTION
Selecting brighter stand by screen will decrease LCD lifespan.
※ "Auto" setting is only available in the indoor units that is equipped with the human detection
sensor.
※ When set to Auto, wired remote standby screen brightness (0%, 10%, 20%, 30%) will auto-
matically adjust according to the illuminance detected by the human detection sensor.
92 USER SETTING
OK
Value
Not use Use
USER SETTING 93
ENGLISH
External device types
It is the function to set the name of the External device attached to the remote controller.
• You can set the following setting values using [<,>(left/right)] button.
Value
OK
ENGLISH
Date setting
Set the date displayed on the remote controller.
• In the user setting list, select the date category, and press [OK] button to move to the detail
screen.
• After the setting, if you press [OK] button, the setting is saved and moves to the previous
screen.
OK
96 USER SETTING
Time setting
Set the time displayed on the remote controller.
• In the user setting list, select the time category, and press [OK] button to move to the detail
screen.
• After the setting, if you press [OK] button, the setting is saved and moves to the previous
screen.
OK
USER SETTING 97
ENGLISH
Summer time setting
Set the daylight savings time dates in the remote controller.
• In the user setting list, select the summer time setting category, and press [OK] button to
move to the detail screen.
- Summer time: The system to advance the time by 1 hour from the spring when the day is
longer and return back in the fall when the day gets shorter.
- When it becomes AM 02:00 on the DST start date, the current time changes to AM 03:00,
and when it becomes AM 02:00 of the DST end date, the current time changes to AM 01:00.
OK
98 USER SETTING
Password setting
Set the password to prevent unauthorized change to remote controller settings.
• Select the user password setting category, and press [OK] button to move to the detail screen.
- If the password is set, when you enter “menu – setting”, you need to input password to
enter the setting list.
- When you forgot the password, you can initialize the password using the installer setting’s
“password initialization”.
The initialized password is “0000”.
OK
USER SETTING 99
ENGLISH
Schedule initialization
Initialize all timer settings in the remote controller.
• In the user setting list, select the schedule initialization setting category, and press [OK] button
to move to the detail screen.
- Press the check button to initialize the sleep/simple timer, on/off timer, schedule and excep-
tion date in the remote controller.
OK
100 USER SETTING
Theme setting
Set the theme of the remote controller screen.
• Select either white or black using [<,>(left/right)] button.
Humidity display
It is the function to decide whether to display humidity on the main screen and additional infor-
mation screen.
You can use [<, > (left/right)] button to set the setting values (On or Off).
ON Display humidity.
Setting value
OFF Do not display humidity.
! NOTE
If humidity display is `ON`, the displayed humidity is different according to the humidity
detection location setting (installer setting).
• Remote controller: remote controller humidity display.
• Indoor unit: If it receives indoor unit humidity, it displays the indoor unit humidity, and if it
does not receive indoor unit humidity, it does not display humidity.
USER SETTING 101
ENGLISH
System restart
Restart the remote controller.
• In the user setting list, select the system restart setting category, and press [OK] button to
move to the detail screen.
- In the detail screen, when you press [OK] button, a popup message is displayed, press the
check button, to restart the system.
- For forced reset, press down [On/Off + Back] button for 5 seconds to restart the system.
OK
102 USER SETTING
Value
On Off Auto
※ "Auto" setting is only available in the indoor units that is equipped with the human detection
sensor.
※ When set to Auto, the indoor unit display light brightness will automatically adjust according to
the illuminance detected by the human detection sensor.
※ "Off" setting is only available in the indoor units that have brightness control function.
SERVICE SETTING 103
ENGLISH
SERVICE SETTING
How to enter service setting
To enter the menu displayed at the bottom, you need to enter the service setting menu as fol-
lows.
• In the menu screen, press [<,>(left/right)] button to select the setting category, and press [OK]
button to move to the setting list.
• In the setting list, select the service setting category, and press [OK] button to move to the
service setting list.
OK
Service setting
• You can set the product service functions.
• Some functions may not be displayed/operated in some product types.
Menu Description
Check and input the service center phone number that you can call
Service contact
when there is service issue.
Check the indoor/outdoor product group and capacity information to
Model Information
which the remote controller is connected.
RMC Version Information Check the remote controller model name and software version.
Error History View the connected indoor unit’s error history.
Open Source License View the remote controller’s open source license.
104 SERVICE SETTING
Service contact
Check and input the service center phone number that you can call when there is service issue.
• In the service setting list, select the service contact point and press [OK] button to move to the
detail screen.
• While “edit” button is selected, press [OK] button to move to the edit screen, change it, and
press [OK] button to change the service contact point.
OK
OK
SERVICE SETTING 105
ENGLISH
Model information
Check the indoor/outdoor product group and capacity information to which the remote controller
is connected.
• In the service setting list, select the indoor/outdoor model information category, and press [OK]
button to move to the detail screen.
• Indoor unit capacity
- 1kWh = 1kBtu * 0.29307
kWh is the result calculated based on Btu, There may be a small difference between calcu-
lated and actual capacity.
Ex) If the indoor unit capacity is 18kBtu, it is displayed as 5kWh.
OK
106 SERVICE SETTING
OK
SERVICE SETTING 107
ENGLISH
Error history
View the connected indoor unit’s error history.
• In the service setting list, select ‘check error history’ category, and press [OK] button to move
to the detail screen.
- You can view up to 20 error instances sorted by date occurred.
OK
108 SERVICE SETTING
OK
INSTALLATION 109
ENGLISH
INSTALLATION
Installation of Remote Controller
• After fixing the remote controller installation plate on the desired location, fix it firmly with the
provided screws.
- If the installation plate is not flat on the surface, it may result in the controller being twisted
and cause a defect.
- If there is a mounting box, install the remote controller installation plate using the fixings holes
which suit, as in the below diagrams.
- Do not leave a gap with the wall or product loose after the installation.
• The wired remote controller cable can be installed in 4 directions. Install to the suitable
direction according to the installation environment.
- Installation direction: Rear entry, top side, right side, left side.
- When you install the remote controller cable at the top, right and left side, remove the remote
controller cable guide hole before the installation.
※ Use a long nose pliers to remove the guide hole.
• After removing the hole, trim the cut surface neatly.
• When installing the remote control cable on the left side, be sure to install it in the following guide.
1. Make the cable to "ㄱ" shape as shown below.
2. Fit the bent "ㄱ" cable into the upper center piece of case.
3. Tighten the installation plate with preventing interference with the surrounding guide structure.
※ If the cable is assembled in a shape other than "ㄱ", it may not be fastened to the installation
plate due to interference with the structure of case.
Reference. the bent cable shape The Upper center boss for fixing the bent cable
110 INSTALLATION
• After fixing the remote controller top side on the installation plate attached to the wall as in the
following figure, press the bottom side to combine with the installation plate.
- Do not leave a gap in the top, bottom, left, and right side of the remote controller and the in-
stallation plate after combining them.
- Before combining with the installation plate, arrange the cables to avoid interference with the
circuit parts.
<Order of Combining>
Wall Wall
• When you remove the remote controller from the installation plate, insert a small flat head screw-
driver into the bottom side separation hole and turn clockwise to separate the remote controller.
- There are 2 separation holes at the bottom part. Slowly separate one by one.
- Be careful not to damage the internal parts during the removal.
<Order of Separation>
Wall Side
• Use the connection cables to connect the indoor unit with the remote controller.
DC 12 V Red
Please check if connector is normally connected.
Signal Yellow
Indoor
GND Black OK
Unit side
Connecting cable
• For the following cases, separately purchase and use the cables suitable for the situation.
- Do not install the cable over 50 m. (It may cause communication issues.)
- If the distance between the wired remote controller and the indoor unit is 10 m or more : 10
m extension cable (model name: PZCWRC1)
- If you control several indoor unit products with one wired remote controller : Group control
cable (model name: PZCWRCG3)
! NOTE
During the wired remote controller installation, do not bury it in the wall. (It may cause
temperature sensor failure.)
Do not install the cable over 50 m. (It may cause communication defect.)
When you install the extension cable, carefully check the direction of the connectors on the
remote controller side and the product side before the installation.
Specification of extension cable: AWG 24, 3 conductor or above.
INSTALLATION 111
ENGLISH
Group control
• It connects and controls 2 or more air conditioner indoor units(Maximum number of IDU : 16ea)
to one wired remote controller.
※Connect using the group control cable.
Indoor unit Main PCB
Indoor unit 1 Indoor unit 2 Indoor unit 3
Master Slave Slave
RED(12V)
YELLOW(SIG) YELLOW(SIG) YELLOW(SIG)
BLACK(GND) BLACK(GND) BLACK(GND)
OK
① Group control cable (PZCWRCG3): Connect to indoor unit’s wired remote controller connector
② Extension cable (PZCWRC1): Connect to No. ① cable and slave indoor unit’s wired remote
controller connector
While No. ① cable is connected, connect No. ② cable.
1 2
! NOTE
• Connect only GND and signal cable to the indoor unit set as slave. (If power cable is also
connected, it may cause loss of communication)
• Inquiries related to the purchase of the cable shall be directed to the specialized company
and the service center.
• After checking the existence of the event communication in the product manual, change
master/slave of the remote controller.
※For details, refer to ‘remote controller master/slave’ contents.
• Change master/slave of the indoor unit.
- For ceiling cassette and duct product group, change the setting with the indoor unit PCB
switch.
Master Slave Slave
GND
Signal cable No. 3 switch OFF: master (factory ship-out based)
12V
Yellow
Black Red
- For the details on the wireless remote controller master/slave setting changes, refer to the
wireless remote controller manual.
- After completing the master/slave setting in the indoor unit product, turn Off the power of the
indoor unit product, and turn On the power after 1 minute.
! NOTE
• During the group control, set only 1 indoor unit as master.
• During the group control, some functions other than the basic operation setting, fan speed
Low/Med/High, remote controller lock setting, and time setting may be limited.
• During the individual control, if the master indoor unit Dip switch is set to slave, malfunction
may occur.
INSTALLATION METHOD TO USE EXTERNAL DEVICE 113
ENGLISH
INSTALLATION METHOD TO USE EXTERNAL
DEVICE
Cable connection method to use external device
1) Wired remote controller-cable connection method.
- In the wired remote controller, connect the part marked in the following figure (J02C, DO-
Port) to the cable.
- According to the installation environment, there are 3 directions (Rear entry, top side, and
right side) for the installation.
2) Cable extension connection method
- Among the cables connected to the wired remote controller, cut the remaining connectors
on the other side, and then extend and connect the cables
- Extension cable specification: 24~26AWG.
! CAUTION
For the External device connection, use the cable insulated with sheath for the extension connec-
tion.
Before combining with the installation plate, arrange the cables to avoid interference with the in-
ternal parts.
RMC
DO-Port 30cm
• Output specification
2 (GND_Black) - Voltage : DC 11~12V
3 (DC 12 V_Red)
- Current : 30mA
Remote
controller Field connection
product
composition
114 AIR CONDITIONER AND VENTILATION INTERFACE
General General
ventilation Air conditioner ventilation
General indoor unit
ventilation
WIRED WIRED
REMOTE REMOTE
CONTROLLER
OK
CONTROLLER
OK
General General
Direct ventilation Air conditioner ventilation
indoor unit
ventilation
WIRED WIRED
REMOTE REMOTE
OK
CONTROLLER
OK
CONTROLLER
※The wiring method is the same as the air conditioner user manual. (Refer to the remote con-
troller manual group control page contents)
※Ventilation product means general ventilation product and direct cooling type ventilation prod-
uct.
INSTALLER SETTING 115
ENGLISH
INSTALLER SETTING
How to enter installer setting
! CAUTION
The installer setting mode is the mode to set the remote controller’s detail function. If the in-
staller setting mode is incorrectly set, it may cause product failure, user’s injury, or property dam-
age. It must be set by the installation specialist with the installation license, and if it is installed or
changed without installation license, all problems caused will be the responsibility of the installer,
and may void the LG warranty.
• In the menu screen, press [<,>(left/right)] button to select the setting category, and press
[∧(up)] button for 3 seconds to enter the password input screen for the installer setting.
• Input the password and press [OK] button to move to the installer setting list.
OK OK
! NOTE
Some categories of the installer setting menu may not be available depending on the
product function or the menu name may be different.
116 INSTALLER SETTING
ENGLISH
Menu Description
It is a function that sets the minimum running time of outdoor unit
Guard timer cycle mode when switching from cooling mode to heating mode and
vice versa during Auto Operation mode.
Fan speed in Cooling thermal It is a function that sets the indoor unit fan movement, in cooling
off mode, when thermal is off.
It is the function to set the heater usage to have higher priority over
Primary heater setting
the outdoor unit cycle during the indoor unit heating operation.
Air conditioner Fan operation It is the function to set whether to operate the air conditioner fan dur-
interlocked with ventilation ing the interface operation of the air conditioner and the ventilation
setting product.
Indoor unit Auto-Start It is a function that sets whether to restore the indoor unit operation
by resuming the previous power-on state or as power-off state in the
setting power failure compensation.
Occupancy duration time It is the function to set the occupied decision maintaining time among
setting the occupied sensor values.
It is the function to set whether to install (use) Dry Contact.
CN_CC setting (It is not a function for Dry Contact installation, but it is a function to
set the usage of the indoor unit’s CN_CC port.)
It is the function to set the indoor unit’s Dry Contact Port to control ex-
ternal input and output according to DI/DO set by the customer. (It is
CN_EXT setting
the function to decide the usage of the contact point port (CN_EXT)
mounted in the indoor unit PCB.)
ODU function master setting It is the function to set the outdoor unit’s function Master / Slave.
It is the function to set the indoor unit’s continued Fan function usage.
Fan continuous operation It is the function to maximize the cooling/heating efficiency by the out-
setting door unit operating the indoor unit fan operation longer than the previ-
ous operation method.
It is the function to set the main agent of the low noise mode control.
Low noise mode priority
(It is the function to set only one of the outdoor unit / remote con-
setting
troller can control the low noise operation.)
Human detection sensor set- It is the function to set whether to install human detection sensor and
ting operation standard value.
Humidity sensing position It is the function to set the location to detect humidity.
ODU cycle priority This function can select standby mode or priority cooling.
Outdoor temp. for heating This function can select outdoor temperature values for use reference
stages point of heater and heating mode operation.
Estimated energy display This function can set to display energy data which ODU estimated.
CN_PTC setting This is a function to set PTC Port of indoor unit.
It is the function to initialize (0000) the password when you forgot the
Password initialization
password set in the remote controller.
This function automatically sets the rotation speed of the fans
Auto ESP
corresponding to each step of rated airflow for easy installation.
Dust step color setting This function is to set the dust step color.
118 INSTALLER SETTING
Test run setting DX(Direct Exchanger) Type It is the function to set the trial operation at the initial product installation.
It is the function to set the central control address of the indoor unit during
Central control address Setting General
the central controller connection.
It is the function to set the fan speed value corresponding to the air supply
Air supply ESP
side fan speed.
General/DX Type
It is the function to set the fan speed value corresponding to the air dis-
Air discharge ESP
charge side fan speed.
It is the function to select the temperature sensor that will decide the indoor
Temperature sensor setting DX Type
temperature.
Product direction General It is the function to set the ventilation indoor unit’s installation direction.
It is the function to set the priority of the air supply and discharge during the
Express ventilation priority
General/DX Type express ventilation operation.
RMC master/slave setting It is the function to set group control or 2-remote controller control.
The operation master / slave selection function is to avoid other mode oper-
Override master/slave setting DX Type ations, and it is the function to prevent the selection of the opposite mode
of the indoor unit set as master by the indoor units set as slaves.
Dry contact function is the function that can be used only when the dry con-
Dry contact mode setting DX Type
tact devices is separately purchased and installed.
Fixed fan speed setting DX Type It is the function to set the indoor unit’s fan speed option to variable or fixed.
Hum. Of Stand-alone Vent. It is the function to set whether to use the humidification function in the di-
General/DX Type
Mode rect cooling type ventilation’s ventilation single operation.
Hum. Of Vent. With Heating It is the function to set the direct cooling type ventilation’s heating humidifi-
DX Type
Oper. cation function as auto or manual.
It is the function to increase/decrease ventilation’s standard fan speed from
Vent. Fan Speed Alignment General
the current status according to the field environment.
This function allows you to check the address of the indoor unit designated
Indoor unit address verification DX Type
by the outdoor unit.
It is a function that sets whether to restore the indoor unit operation by re-
Indoor unit Auto-Start setting DX Type suming the previous power-on state or as power-off state in the power fail-
ure compensation.
It is the function to set the indoor unit’s Dry Contact Port to control external input
CN_EXT setting DX Type and output according to DI/DO set by the customer. (It is the function to decide the
usage of the contact point port (CN_EXT) mounted in the indoor unit PCB.)
ODU function master setting DX Type It is the function to set the outdoor unit’s function Master / Slave.
It is the function to set the main agent of the low noise mode control. (It is
Low noise mode priority setting DX Type the function to set only one of the outdoor unit / remote controller can con-
trol the low noise operation.)
Filter check alarm General This function sets the filter check alarm of the ventilation product.
INSTALLER SETTING 119
ENGLISH
Test run setting (air conditioner / DX ventilator)
After product installation, the Test run must be performed. For Test run related details, refer to
the product manual.
• In the installer setting list, select the Test run setting category, and press [OK] button to move
to the detail screen.
- You can select ‘cooling Test run / heating Test run’
- During the Test run, if you start the following functions, the Test run stops.
☞ Operation mode, desired temperature, fan speed, wind direction, start/stop
OK
120 INSTALLER SETTING
OK
INSTALLER SETTING 121
ENGLISH
ESP setting (air conditioner / general, DX ventilator)
It is the function to set the fan speed value corresponding to each fan speed for easy installation.
OK
! NOTE
If ESP is incorrectly set, the air conditioner may malfunction.
This function must be set by the installation specialist that holds an installation license.
For ventilation products, separate ESP values are used for the supply and exhaust fans.
• In the installer setting list, select the ESP setting category, and press [OK] button to move to
the detail screen.
! NOTE
Be especially careful not to switch ESP values corresponding to each fan speed.
Engineering manuals have ESP setting tables that reference air flow and corresponding
value setting to achieve the flow.
The ESP values that can be set may be different for each product and capacity.
122 INSTALLER SETTING
ENGLISH
Ceiling height setting (air conditioner)
It is the function to control the fan speed stage according to the ceiling height in the ceiling type
product.
• You can set the following setting values using [<,>(left/right)] button.
! NOTE
When group control is enabled some functions are limited depending on product type.
124 INSTALLER SETTING
Description
Static pressure
Variable / Fixed ESP default value
Variable high static pressure V-H Variable High static pressure(High)
Fixed high static pressure F-H Fixed High static pressure(High)
Variable low static pressure V-L Variable Low static pressure(Low)
Fixed low static pressure F-L Fixed Low static pressure(Low)
ENGLISH
Remote controller master / slave setting
(air conditioner / General, DX ventilator)
This function sets configuration for the master/slave setting through the remote controller.
• Change setting values using [<,>(left/right)] button.
M/S Description
Using group control, the indoor units are operated based on the re-
Master (default)
mote controller.
Using group control, all remote controllers except 1 master remote
Slave
controller are set as slaves.
M/S Description
Master Using group control, this master sets the mode of slave IDU’s.
For the indoor unit set as slave, it can only select the some operation
mode of the master indoor unit cycle.
Ex) Master is in cooling cycle, Slave can select cooling, dehumidifica-
Slave
tion, auto, and wind only
Master is in heating cycle, Slave can select auto, heating, and wind
only
! NOTE
Override M/S setting function is only available in some products.
INSTALLER SETTING 127
ENGLISH
Dry contact mode setting (air conditioner / DX ventilator)
Dry contact function is the function that can be used only when the dry contact devices is sepa-
rately purchased and installed.
• Change setting values using [<,>(left/right)] button.
Value
Auto
manual
! NOTE
For dry contact mode related detail functions, refer to the individual dry contact manual.
What is dry contact?
It means the contact point signal input when the hotel card key, human body detection
sensor, etc. are interfacing with the air conditioner.
Added system functionality by using external inputs (dry contacts and wet contacts).
128 INSTALLER SETTING
ENGLISH
Zone Type Setting(air conditioner)
This function is only available on some products.
This function select a type of zone control type which indoor unit support as 'new type' or 'old
type'.
Value
Old
New(4 Zone)
New(8 Zone)
Value
New(4 zone) : 2~4
New(8 zone) : 2~8
130 INSTALLER SETTING
OK
! NOTE
This function setting must be carried out by a certified-technician.
INSTALLER SETTING 131
ENGLISH
Function control during group Control setting (air conditioner)
This function enables the control of the common functions or some functions based on the mas-
ter indoor unit during the group control.
• Change setting values using [<,>(left/right)] button.
Value Description
Not use Common function,
Use expanded function which
Use
is based on master indoor unit
! NOTE
Common functions and some indoor unit master standard setting shall be set only during
the group control with the same type indoor units.
During the group control with different indoor unit types, set it as ‘000’ to use the existing
group control method.
132 INSTALLER SETTING
Function Value
Plasma purification
Heater
Humidifier
Elevation grill Not install / Install
Ventilation Kit
Aux Heater
Refrigerant leakage detection sensor
INSTALLER SETTING 133
ENGLISH
Expand of Temperature Range (air conditioner)
This function using in dual setpoint control mode.
This function is used for select setting temperature range option.
Value
Clear : 60~86 °F / 16~30 °C (default)
Set : 40~99 °F / 4~37.5 °C
! NOTE
When the set values are changed, the items below will be initialized.
- Target temperature (default: Cooling: 86 °F(30 °C)/ Heating: 60 °F(16 °C))
'home leave' temperature (default: Cooling: 86 °F(30 °C)/ Heating: 60 °F(16 °C))
In case of the setting expanded temperature range (set), please note that the setting of the
wired remote controller can be altered under below circumstances.
- In case of cooling at 30~37.5 °C(64~99 °F), it is changed to cooling at 86 °F(30 °C).
- In case of heating at 4~15.5 °C(40~86 °F), it is changed to heating at 60 °F(16 °C).
- If set on dual setpoint, it is changed to the current operation mode(cooling or heating) of
the indoor unit.
Situation where changes in the setting occur
a. Operates the Auto address work and pipe search in situations such as product installment
and service.
b. Occurrence of errors and deactivation.
c. Command generated by the central control, outdoor unit, Dry contact, Remote controller,
indoor unit switch.
134 INSTALLER SETTING
OK
INSTALLER SETTING 135
ENGLISH
Static pressure step setting (air conditioner)
It is the function to subdivide and set the product’s Static pressure to 11 stages.
• Change setting values using [<,>(left/right)] button.
Value
Step 0 ~ Step 11
! NOTE
If Static pressure step setting is used, the Static pressure setting is not used.
For the Static pressure step value for each stage, refer to the indoor unit product manual
136 INSTALLER SETTING
Step Value
0 0 minute
1 15 minutes
2 30 minutes
3 45 minutes
4 60 minutes
INSTALLER SETTING 137
ENGLISH
Fan speed in Cooling thermal off (air conditioner)
Indoor unit fan, in cooling mode, during thermal off condition.
• Select value using [<,>(left/right)] button.
Value
Low Fan speed low
Off Fan off
Setting fan speed setting value
138 INSTALLER SETTING
Value Description
Not use During the heating, heater is set to be used as secondary
Use During the heating, heater is set to be used as main
INSTALLER SETTING 139
ENGLISH
Air conditioner Fan operation interlocked with ventilation setting
(air conditioner)
It is the function to set the air conditioner fan operation if the ventilation is operated while the air
conditioner operation is stopped when the air conditioner and the ventilation are installed to inter-
face with each other.
• You can set the following setting values using [<,>(left/right)] button.
Value Description
Off The air conditioner indoor unit Fan is Off during the ventilation interface
The air conditioner indoor unit operates in very weak wind during the ventila-
On
tion interface
- When the air conditioner operation is Off, if the ventilation product is in operation, the air condi-
tioner fan shall be operated, and when the fan is in operation, dust may fall, so it is the function
to set the air conditioner fan operation status in case of ventilation interface through the setting.
140 INSTALLER SETTING
Value Description
Use Use indoor unit auto restart
Not use Not use indoor unit auto restart
INSTALLER SETTING 141
ENGLISH
Occupancy duration time setting(air conditioner)
It is a function that sets the light-on/occupancy duration after motion is detected when installing
an occupancy sensor.
• You can set the following setting values using [<,>(left/right)] button.
Value
0 Minute
10 Minutes
30 Minutes
60 Minutes
142 INSTALLER SETTING
OK
Value Description
When power is applied to the product, indoor unit when the contact
DC auto install
point is on in Dry Contact installed state recognizes Dry Contact installa-
(default)
tion
DC manual not install Do not use (install) Dry Contact
DC manual install Use (install) Dry Contact
Programmable DI/DO Use as Programmable DI/DO (Simple On/Off)
! NOTE
CN_CC is the device connected to the indoor unit to recognize and control the external
contact point.
INSTALLER SETTING 143
ENGLISH
CN_EXT setting (air conditioner / DX ventilator)
It is the function to set to control the external input and output according to DI/DO set by the
customer using the indoor unit’s Dry Contact Port. (It is the function to decide the usage of the
contact point port (CN_EXT) mounted in the indoor unit PCB.)
• In the installer setting list, select CN_EXT setting category, and press [OK] button to move to
the detail screen.
OK
Value Description
Not use (default) Use installer code No. 41 setting value (simple Dry Contact setting value)
Simple operation
Simple operation On/Off
control
Single emergency stop Indoor unit single emergency stop
Occupied / Unoccupied Occupied / Unoccupied
Indoor unit all emergency stop
All emergency stop
※It can be set only when there is indoor unit emergency stop function.
Window contact
Window contact
※ It can be set only when there is window contact function.
Window contact with lock
Window contact lock
※ It can be set only when there is window contact lock function.
144 INSTALLER SETTING
Value Description
Cannot enter the Smart load control function setting
Cannot enter the low noise operation time setting
Slave
Cannot enter the refrigerant noise reduction setting
Cannot enter the defrost mode setting
! CAUTION
※When you change the outdoor unit function master setting from master to slave, check the op-
eration status of the outdoor unit function (outdoor unit low noise operation, smart load control)
and make sure to stop the outdoor unit function before the change.
INSTALLER SETTING 145
ENGLISH
Fan continuous operation setting (air conditioner)
It is the function to set the indoor unit’s continued fan function usage. (It is the function to maxi-
mize the cooling/heating efficiency by the outdoor unit operating the indoor unit fan operation
longer than the previous operation method.)
• You can set the following setting values using [<,>(left/right)] button.
Value Description
Clear Do not use continued fan usage
Set Use continued fan usage
146 INSTALLER SETTING
Value Description
Ignore the outdoor unit PCB’s low noise operation Switch Setting value
RMC - Function setting – remote controller low noise operation time menu de-
activation
ENGLISH
Human detection sensor (air conditioner)
It is the function to set whether to install human detection sensor and operation standard value.
• In the installer setting list, after selecting human detection sensor setting category, if you press
[OK] button, it moves to the detail screen.
• You can set the following setting values for each category using [<,> (left/right)] button.
Value Description
Installation status Not installed, basic installation, 90º rotation installation
Detection result sending cycle 5 s, 30 s, 1 min., 3 min.
Sensitivity setting Standard, low sensitivity, high sensitivity
Step 0 : Keeps the product running and uses the tem-
perature power saving function.
Temperature control option
Step 1 : The operation of indoor units is stopped by
using the temperature power saving function.
Detection Area Setting Indoor floor area detection, 6X6, 12X6
148 INSTALLER SETTING
Value Description
Remote controller (default value) Humidity sensor of the remote controller itself
Indoor unit Humidity received from indoor unit
INSTALLER SETTING 149
ENGLISH
ODU cycle priority (air conditioner)
This function can set cycle priority of outdoor unit.
Multi V Heat Pump system does not support mixed mode therefore wired remote controller can
not show opposite operation mode for select option while ODU operate cooling or heating cycle.
Set this function user can select opposite operation mode with wired remote controller and in-
door units enter to ‘standby’ status or outdoor unit can support cooling first and operate heating
with heater.
OK
150 INSTALLER SETTING
Option Description
Does not support opposite cycle operation using wired remote controller
- When ODU operate as cooling cycle selectable operation modes with
Not use wired remote controller are cool, auto, dehumidification and fan.
- When ODU operate as heating cycle selectable operation modes with
wired remote controller are heat, auto and fan
When user set opposite operation mode using wired remote controller in-
Standby
door unit stop thermal operation and fan.
h When user select cooling option, additional setting menu will be activated.
The additional timer setting menu is for setting minimum cooling operation period.
Once outdoor unit change over to cooling by cooling priority, outdoor unit can change over to
heating after set time.
ENGLISH
Outdoor temp. for heating stages (air conditioner)
It is a function that sets outdoor temperature values for two stage heating.
if user set outdoor temperature T1 and T2, Indoor unit will select heating stage between Indoor
unit operation and heater operation.
OK
※ Even if the remote control version is 2.09.0a or more, Features may not be supported.
152 INSTALLER SETTING
ENGLISH
Password initialization (air conditioner / general, DX ventilator)
It is the function to initialize (0000) when you forgot the password set in the remote controller.
• In the installer setting list, select the password initialization setting category, and press [OK]
button to move to the detail screen.
• When you press “initialization” button, a popup screen appears, and when you press “check”
button, password initialization starts, and the user password is changed to 0000.
OK
154 INSTALLER SETTING
OK
After selecting the voltage setting, the product will automatically operate and automatically set
the rotation speed for each fan speed - High, Medium, and Low.
Check the product type and select “Auto” for a Single product and “Manual” for a Multi V prod-
uct.
Value Description
Off Not in use
Auto Automatically selects the voltage
Selects the voltage (190V-270V)
Manual
* Only for Multi V products
INSTALLER SETTING 155
ENGLISH
While setting, a pop-up is displayed. This means that Auto ESP is being set.
(It takes approximately 3 to 8 minutes.)
! NOTE
If Auto ESP is incorrectly set, the air conditioner may malfunction.
This function must be set by an installation specialist with an installation license.
156 INSTALLER SETTING
Value Step
Type 1 4Step(for Korea)
Type 2 4Step(for Global)
Type 3 6Step(for China)
Value
Normal Reverse
INSTALLER SETTING 157
ENGLISH
Express ventilation priority (general , DX ventilator)
It is the function to set the priority of the air supply and air discharge during the express ventila-
tion operation.
• Select value using [<,>(left/right)] button.
Value
Priority in air supply Priority in air discharge
158 INSTALLER SETTING
Value
Not use Use
INSTALLER SETTING 159
ENGLISH
Humidification of ventilation with heating operation
(DX ventilator)
It is the function to set the heating humidification function of the direct ventilation to be auto-
matic or manual.
• Select value using [<,>(left/right)] button.
Value
Not use Use
160 INSTALLER SETTING
Value
Default value 10% increase 10% decrease 20% decrease
Value
Step 0 - 5
GUIDE TO DIFFERENT MODE OPERATION/OPEN SOURCE SOFTWARE 161
ENGLISH
GUIDE TO DIFFERENT MODE
OPERATION/OPEN SOURCE SOFTWARE
Different mode operation
Different mode operation is the case when the indoor units’ operation modes are different when
multiple indoor units are installed to one outdoor unit. (Different mode operation doesn’t happen
in the cooling exclusive model.)