UV 80/2 LCD2 Technical Data

GENERAL INFORMATION
Max flow rate 250 l/m
UVC transmittance 99%- 1 cm
UVC dose 400 J/m2
Water Temperature range 5-50° C
Total consumption 177 W
Mounting Vertical or horizontal
Quartz sleeve cleaning system
Manual Availabe – RM version (only SS 316L)

UV REACTOR
Material Stainless Steel 304 (optional 316L)
Connections Thread 1 ½” M
Drain/Air Valve 1/8” ½” M thread
Total Volume 7.9 l
Total weight 6 kg
Max working pressure 10 bars g
Protection class IP 54
Shape Z
Flow direction From bottom to top

UV LAMP
Number 2
Lifespan 9000 hr
Lamp power 80 W
Type HO low pressure type 028124

UV SENSOR (ONLY on PLUS MODELS)


Type UVC selective sensor Mod. UV737S/TF
Sensor Cable Shielded cable 4 meters
Sensor holder material Teflon

CONTROL PANEL LCD (PLUS)


Material and colour Black Polypropylene
Dimensions 215 x 215 x 90 mm
Protection class IP 55 (IP 65 on request)
Ambient temperature range 5 – 45 °C
Power supply 230 V - 50/60 Hz (115V – 50/60 Hz on request)
Lamp cable 1m
Power supply cable 1m
Monitor display LCD SITA
Hour meter Yes for total system life
Resettable hour meter Yes for lamp life control
Lamp function control Yes
Alarm led Yes
Free contact (NO - NC) Yes – general alarm (max 2 A)
230 V output (NO - NC) Yes – general alarm (max 2 A)
Remote ON/OFF contact Yes (settable)
ON/OFF Timer Yes (settable)
Reactor temperature measurement and Yes (°C) – settable value (shut off for high temperature) on PLUS MODELS
alarm
2
UV Irradiance measurement and alarm Yes (% or W/m optional) – settable value on PLUS MODELS
4/20 mA output Optional – for Irradiance and water temperature on PLUS MODELS
Audio alarm Optional
Rev. 02-2021
-

S.I.T.A. srl – Via Rivarolo 61 – 16161 Genova Italy


tel 0039-10-7406848 – fax 0039-10-7406851 – e-mail info@sitauv.com – www.sitauv.com