Conventional Manual
Call Point   C-9201
                                                                                             Technical Specifications
                                                                                                •   Standard: EN54-part 11
                                                                                                •   Approval: CE
                                                                                                •   Protection rating: IP 40
                                                                                                •   Operating voltage: 24Vdc Loop
                                                                                                •   Operating current:
                                                                                                        Standby current 0.8mA
                                                                                                        Alarm Current 2mA
                                                                                                •   Operating temperature: -10°C to
                                                                                                    +50°C
                                                                                                •   N/O Output contact: 60Vdc, 0.1A
                                                                                                •   Contact resistance: 100mΩ
                                                                                                •   Relative humidity: 95%
                                                                                                •   Application: Indoor use
               Features and Benefits                                                            •   Visual Indicator: LED, Red ( lit
                  1. Re-settable (non-breaking glass)                                               steady when alarm, 3 sec interval
                  2. Additional volt free contact                                                   blinking at normal state)
                  3. Friendly installation and test                                             •   Material and colour: ABS, red
                                                                                                •   Wiring: 1 pair polarized
               Description                                                                      •   Dimensions: 90x122x48.5mm
               Designed for the purpose of raising an alarm
               manually once verification of a fire or                                       Mounting Base
               emergency condition exists, by pressing the                                   The location of manual call point should be
               non breakable glass. Meets the standard                                       installed in compliance with all local codes
               requirement of EN 54 part 11, European                                        and / or NFPA 72 National Fire Alarm Code,
               Standard and approved by Loss Prevention                                      NFPA 70 National Electrical Code. Surface
               Certificate Board (LCPB).                                                     mount and it is installed onto a standard
               The C-9201 constructed of high impact red
               ABS with a modern pleasing appearance. The                                                              I−9201
                                                                                                                                      WALL
               terminating back box enables first fix
               installation and termination leaving the fascia                                                  FIRE
                                                                                                                                         ELECTRICAL
               with integral electronics to be simply plugged                                                                             BACK BOX
               into base at the time of commissioning. Non
               breakable glass that can be reset with the
                                                                                                                       MOUNTING
               GST standard reset sucker.                                                                                BASE
               The C-9201 operated via a micro-switch that
               when pressed a signal will be transmitted                                                      SURFACE MOUNT
               and the volt free contact will be latched.                                    one gang electrical box with a mounting
               Contain integral LED indicator to denote                                      hole that have 52mm~68mm spacing.
               operational mode.
                                                                                             Ordering Information:
               Selection of compatible Control Panels
               Compatible with all GST Conventional panels                                   Part No            Description            Weigh          Pack
                                                                                                                                       t/Kg           Qty
               Wiring and Connection:                                                                                                                  per
               Connect as per the marking on the base.                                                                                                Box
                                                                                             C-9201         Conventional                0.156          120
                                                                                                            Manual Call Point
CONVENTIONAL
               +
   PANEL
                                                                1   2
                                                                                             Note: Specifications are subject to change without notice.
                                    K1 K2
                −
     OR
   ZONE
  MONITOR
                                                                          TO NEXT DETECTOR
  MODULE
                          I+   I−   O− 0+
                                                                4   3             OR
                                                                                 AEOL
                                     C−9202 MANUAL CALL POINT       DETECTOR