Ele 578 Power System Protection Course Outline
Ele 578 Power System Protection Course Outline
Course outline
Faults and concept of protection in power systems, symmetrical and unsymmetrical fault
analysis, fuses, circuit breakers, basic principles of relay design, construction, characteristics
and applications, protective relays: distance relay, differential relay, etc, protection of
Power system protection is the art and science of detecting faults (problems) with power
system components and isolating these components. The protection of the power system
ensures that any part of a system is quickly detected and isolated so that the rest of the
system/equipment and personnel are safe and the remaining system operates satisfactorily.
ii. be absolutely reliable in operation, the simpler and more robust the design the better
iii. be able to discriminate between currents fed to the fault points within the protected
The detection of a fault and disconnection of a faulty section or apparatus can be achieved
by using fuses or relays in conjunction with circuit breakers. However, for high-voltage
circuits, a combination of relays and circuit breakers are employed to serve the desired
Protective relays
A protective relay is a device that detects the fault and initiates the operation of the circuit
breaker o isolate the defective element from the rest of the system. Figure shows a typical
1
The relay detects the abnormal conditions in the electrical circuits by constantly measuring
the electrical quantities such as voltage, current, frequency and phase angle, which are
different under normal and fault conditions. The faults signal their presence, type and location
to the protective relays through the changes in one or more of these quantities. Having
detected the fault, the relay operates to close the trip circuit of the breaker. This results in the
When a short circuit occurs at point F on the transmission line, the current flowing in the line
increases to an enormous value. This results in a heavy current flow through the relay coil,
causing the relay to operate by closing its contacts. Consequently, it closes the trip circuit of
the breaker, making the circuit breaker open and isolating the faulty section from the rest of
the system. Thus, the relay ensures the safety of the circuit equipment from damage and the
Every protective system which isolates a faulty element is required to satisfy the following
essential requirements:
2
(i) Selectivity and discrimination (ii) speed of operation (iii) sensitivity (iv) reliability
(v) simplicity
Selectivity is the ability of the protective system to select correctly that part of the system
in trouble and disconnect the faulty part without disturbing the rest of the system. The
protective system must be able to discriminate between those conditions for which prompt
operation is required and those from which no operation or time-delay operation is required.
Speed of operation
The relay system should disconnect the faulty section as quickly as possible. This is desirable
for many reasons, such as reducing the damage incurred. Improvement in power system
stability results in less annoyance to consumers and a decrease in power outage time, a
decrease in the likelihood of the development of one type of fault into a more severe type,
permits the use of rapid reclosure of circuit breakers to restore service to the consumer.
Sensitivity
A protective system must be sufficiently sensitive to operate reliably when required under
the condition that produces the least operating tendency. The sensitivity of a relay is a
function of the volt-amperes input to the relay's coil necessary to cause its operation. The
smaller the volt-ampere input required to cause relay operation, the more sensitive is the
relay.
Reliability
Reliability is the ability of the relay system to operate under pre-determined conditions.
Without reliability, the protection would be rendered largely ineffective and could even
become a liability.
3
Simplicity. The relaying system should be simple so that it can be easily maintained.
Reliability is closely related to simplicity. The simpler the protection scheme, the greater will
be its reliability.
In a symmetrical fault, the fault currents in the three lines are equal in magnitude and
displaced 120º electrical from one another. Due to the balanced nature of symmetrical faults,
it is sufficient to consider only one phase in calculations since the conditions in the other two
However, most common faults on the power system are unsymmetrical in nature and when
such fault occurs, it gives rise to unsymmetrical currents (the magnitude of fault currents in
the three lines are different having unequal phase displacement). The calculation procedure
known as method of symmetrical components is used to determine the currents and voltages
Those faults on the power system which give rise to unsymmetrical fault currents are known
three lines become unequal and so is the phase displacement among them. Note: the term
‘unsymmetry’ applies only to the fault itself and the resulting line currents and the system
impedances and the source voltages which are always symmetrical through its main elements
There are three ways in which unsymmetrical faults may occur in a power system
4
R R
Y Y
B B
L-G Fault
L-L-Fault
B
L-L-G-Fault
any unbalanced system of 3-phase currents (or voltages) may be regarded as three separate
namely: (i) a balanced system of 3-phase currents having positive (or normal) phase sequence.
(ii) a balanced system of 3-phase currents having the opposite or negative phase sequence.
(iii) a system of three currents equal in magnitude and having zero phase displacement. These
The positive, negative and zero phase sequence components (denoted with subscripts 1, 2 and
unbalanced system.
Suppose an unsymmetrical fault occurs on a 3-phase system having phase sequence abc.
be resolved into :
sequence (abc) as shown in Fig. 18.3 (i). These are the positive phase sequence
components
5
(ii) a balanced system of 3-phase currents I a 2 , I b 2 and I c 2 having negative phase
sequence
(acb) as shown in Fig. 18.3. These are the negative phase sequence components.
(iii) a system of three currents I a 0 , I b 0 and I c 0 equal in magnitude with zero phase
displacement
from each other as shown in Fig. 18.3 (iii). These are the zero phase sequence
components.
I a = I a1 + I a 2 + I a 0
I b = I b1 + I b 2 + I b 0
I c = I c1 + I c 2 + I c 0
The positive phase sequence currents ( I a1 , I b1 and I c1 ), negative phase sequence currents
balanced system of currents. Hence, they are called symmetrical components of the
unbalanced system.
(ii) The symmetrical component theory applies equally to 3-phase currents and voltages both
(iii) The symmetrical components do not have separate existence. They are only mathematical
components of unbalanced currents (or voltages) which actually flow in the system.
(iv) In a balanced 3-phase system, negative and zero phase sequence currents are zero.
I c1 I a1 Ib2
Ia2
120o 120 o
Ia0
240 o 240 o
Ib0
Ic0
I b1 Ic2
6
Operator ‘a’
As the symmetrical component theory involves the concept of 120º displacement in the
positive
sequence set and negative sequence set, therefore, it is desirable to evolve some operator
which
should cause 120º rotation. For this purpose, operator ‘a’ is used. It is defined as under
a = −0.5 + j 0.886
a2 = −0.5 − j 0.886
a3 = 1
1 + a + a2 = 0
The unbalanced phase currents in a 3-phase system can be expressed in terms of symmetrical
components
as under
I a = I a1 + I a 2 + I a 0
I b = I b1 + I b 2 + I b 0
I c = I c1 + I c 2 + I c 0
7
Ib = a2 I a1 + aI a 2 + I a 0
Ic = aI a1 + a2 I a 2 + I a 0
I a + Ib + I c = I a1 (1 + a2 + a) + I a 2 (1 + a + a 2 ) + 3I a 0
= I a1 (0) + I a 2 (0) + 3I a 0 = 3I a 0
since (1 + a + a = 0)
2
1
I a0 = ( I a + Ib + Ic )
3
1
I0 = (I a + Ib + Ic )
3
I a + aIb + a2 I c = I a1 (1 + a3 + a3 ) + I a 2 (1 + a 2 + a 4 ) + I a 0 (1 + a + a 2 )
= 3I a1 + I a 2 (0) + I a 0 (0) = 3I a1
1
I a1 = ( I a + aI b + a 2 I c )
3
1
I1 = ( I a + aI b + a 2 I c )
3
I a + a2 Ib + aI c = I a1 (1 + a 4 + a 2 ) + I a 2 (1 + a3 + a3 ) + I a 0 (1 + a 2 + a)
1
I a 2 = ( I a + a 2 I b + aI c )
3
1
I 2 = ( I a + a 2 I b + aI c )
3
8
b
aI
120o
I
120o a
120o
a2I
c
Ib2 = a I a 2 Ia2
I c1 = a I a1 I a1
o
120
120o Ia0
120o Ib0
120o 120o
120o
Ic0
I b1 = a 2 I a1
Ic2 = a 2 Ia2
Sequence Impedance
The sequence impedance of the network describes the behaviour of the system under
unsymmetrical fault conditions. All component on power system such as the generators,
transformers and transmission lines, has three values of impedance namely positive sequence
symmetrical value of current. The concept of impedances of various elements of power system
unsymmetrical fault calculations, each piece of equipment will have three values of
positive
9
sequence impedance Z1 . Similarly, impedances offered by any circuit or equipment to
negative and zero sequence currents are respectively called negative sequence impedance Z 2
(ii) No current flows in the network other than due to fault i.e. load currents are neglected.
In each case of unsymmetrical fault, e.m.f.s’ per phase are denoted by E a , Eb and E c and the
Consider a 3-phase system with an earthed neutral. Let a single line-to-ground fault occur on
the red phase as shown in Fig. 18.13. It is clear from this figure that
I a = I 0 + I1 + I 2 = 3I 0
a
Ea
N
Eb Va
Ec Ib = 0
c
b
Ic = 0 Vb
Vc
10
1 1
I0 = ( I a + Ib + Ic ) = I a
3 3
1 1
I1 = ( I a + aI b + a 2 I c ) = I a
3 3
1 1
I 2 = ( I a + a 2 I b + aI c ) = I a
3 3
1
I 0 = I1 = I 2 = I a
3
Fault current
Let Z1 , Z 2 and Z 0 Consider the closed loop NREN. As the sequence currents produce voltage
Ia
Z1
3Ea
Z2
Z0
Ea = I1Z1 + I 2 Z 2 + I 0 Z 0 + Va
Va = 0 I = I = I
1 2 0
Ea = I 0 ( Z1 + Z 2 + Z 0 )
Ea
I0 =
Z1 + Z 2 + Z 0
3 Ea
Fault current, I a = 3I 0 = (i)
Z1 + Z 2 + Z 0
11
the equivalent circuit of (i) is shown in fig and the fault current can calculated using the by
connecting the phase sequence impedances in series across an imaginary generator of voltage
3Ea
however, it is assumed is that the fault impedance is zero. Otherwise if the fault impedance is
3Ea
I a = 3I 0 =
Z1 + Z 2 + Z 0 + 3Z f
Note; if the neutral is not grounded, then zero sequence impedance will be infinite and the
fault current is zero. This is expected because now no path exists for the flow of fault current.
For phase voltage at fault, the generated e.m.f. system is of positive sequence only, the
sequence
Z2 + Z0
V1 = Ea
Z1 + Z 2 + Z 0
−Z2
V2 = 0 − Z 2 I 2 = Ea
Z1 + Z 2 + Z 0
−Z2
V0 = 0 − Z 0 I 0 = Ea
Z1 + Z 2 + Z 0
ground.
12
Vb = V0 + a 2V1 + aV2
Vc = V0 + aV1 + a 2V2
3 Ea
I a = fault current = 3I 0 = ; Ib = 0 ; Ic = 0
Z1 + Z 2 + Z 0
Line–to–Line Fault
Consider a line-to-line fault between lines c and b lines as shown in Fig. 18.15. The
Vb = Vc ; I a = 0; I b + I c =0
Vc = Vb
V1 (a 2 − a) = V2 (a 2 − a)
V1 = V2
(i)
13
Ia = 0
a
Ea
N
Eb
Ec Ib = 0
c
b
Ic = 0
I b + I c =0
Also,
( I 0 + a2 I1 + aI 2 ) + ( I 0 + aI1 + a 2 I 2 ) = 0
I1 + I 2 = 0 (ii)
Ea − Ea
Fault current, I b = I 0 + a 2 I1 + aI 2 = 0 + a 2 + a
Z1 + Z 2 Z1 + Z 2
Ea − j 3Ea
I b = (a 2 − a) = = − Ic
Z1 + Z 2 Z1 + Z 2
Phase voltages. Since the generated e.m.f. system is of positive phase sequence only, the
sequence
E0 = 0; E2 = 0; E1 = Ea
14
The sequence voltages at the fault for R-phase are
Ea Z1
V1 = Ea − I1Z1 = Ea −
Z1 + Z 2
Z 2 Ea
V1 =
Z1 + Z 2
Z2
V2 = 0 − Z 2 I 2 = Ea
Z1 + Z 2
V0 = 0 − Z 0 I 0 = 0
2 Z 2 Ea
Va =
Z1 + Z 2
Z E Z E
Vb = V0 + a 2V1 + aV2 = 0 + a 2 2 a + a 2 a
Z1 + Z 2 Z1 + Z 2
Z E
= (a 2 + a) 2 a
Z1 + Z 2
Z 2 Ea
Vb = −
Z1 + Z 2
Z E Z E
Vc = V0 + aV1 + a 2V2 = 0 + a 2 a + a 2 2 a
Z1 + Z 2 Z1 + Z 2
Z E
= (a 2 + a) 2 a
Z1 + Z 2
Z 2 Ea
Vc = −
Z1 + Z 2
− j 3 Ea
I a = 0; I b = − I c =
Z1 + Z 2
15
Z 2 Ea
Vb = Vc = −
Z1 + Z 2
2 Z 2 Ea
Va =
Z1 + Z 2
I1
I2
V1 Z1 Z2 V2
Ea
Consider the double line-to-ground fault involving Y–B lines and earth as shown in Fig. 18.17.
(ii)
16
Ia = 0
a
Ea
N
Eb
Ec Ib = 0
c
b
Ic = 0 Fault current
= Ib + I c
Vb = Vc = 0
1
V1 = V2 = V0 = Va
3 (i)
Also, I a = I1 + I 2 + I 0 = 0 (ii)
Ea
I1 =
Z Z
Z1 + 2 0
Z2 + Z0
Z0
I 2 = − I1
Z2 + Z0
Z2
I 0 = − I1
Z2 + Z0
Z2
Fault current, I f = I b + I c = 3I 0 = 3 − I1
Z2 + Z0
3Z 2 Ea 3Z 2 Ea
= =
Z2 + Z0 Z2 Z0 Z 0 Z1 + Z 0 Z 2 + Z1Z 2
Z1 +
Z2 + Z0
17
V1 = Ea − I1Z1; V2 = 0 − I 2 Z 2 ; V0 = 0 − I 0 Z 0
1
V1 = V2 = V0 = Va
3
Va = V1 + V2 + V0 = 3V2
= 0 V2 = 0
( a 2 + a + 1 = 0)
I1
I2 I0
Z1 V1 Z2 V2 Z0 V0
Ea
and makes the analysis easy and interesting. In fact, this method if the made in arriving at
exp. (i) permits to bring any unsymmetrical fault into a simple circuit of
the secondary current with a reduced value or level. That is, the primary current is
proportional to the secondary current. It reduces high voltage currents to a much lower value
and provides a convenient way of safely monitoring the actual electrical current flowing in
18
.
the range of the rated normal current of the CT and has specified errors at the operating
value. A protection CT on the other hand operates over a range of currents many times the
rating of the circuit the CT is protecting and it is very often subjected to conditions greatly
exceeding these to which a measuring CT is subjected. The corresponding flux density leads
to the saturation of the core and the transient period of the short circuit current is usually very
The design of CTs is the same as in power or distribution transformers in which the emf
equation is given as
= BAc Ac = w l
19
The CT Knee Point
The accuracy of the CT's measurement depends on its linearity, which is the degree to which
the secondary current is proportional to the primary current. Ideally, a CT would provide a
linear output for any primary current, but in practice, CTs have a limit to their linearity,
known as the knee point. The knee point is the point at which the CT core begins to saturate
due to the magnetic flux density becoming too high. As the core saturates, the output of the
CT becomes non-linear, which means that the ratio of primary current to secondary current
is no longer linear. This can result in inaccurate measurements and can lead to errors in the
so, in design, once the core saturation has been fixed, then the flux density is also limited to
the knee point value of about 1.5 wb/m2 or Tesla. The normal design criterion is to limit the
20
For instance, consider a CT ratio of 400/1 with a core section of l= 40mm and w = 30mm then
In this design, if the CT is used to protect a 150 kVA transformer of 11/0.415 kV at the
150 10 3
= = 208.7 Amps.
3 0.415
Accordingly, this CT can be used to protect this transformer and the secondary current of the
208.7
= 1 = 0.522 Amps.
400
Burden of a Current Transformer.
The burden of a current transformer is the value of the impedance/load (largely resistive)
connected across the secondary winding of the transformer. It is expressed as the output in
volt-amperes (VA). For a 5 VA burden on a 1 Amp CT, the impedance will be 5 Ω. Burdens
are usually and always connected in series with the CT and the increase in the impedance
The bar primary CTs for which the primary is a centrally situated straight conductor,
extending some distance on both sides of the CT which is a component of the power system.
In all cases, the primary is simply one primary turn. The secondary on the other hand is
wound uniformly over the whole periphery of the core, which is usually of the ring type (or
annular rings of steel). In this design, the leakage flux of both the primary and secondary are
negligible.
21
The primary wound types: the primary of this type consists of one or more turns; and because
of the small number of turns, they cannot be distributed uniformly over the whole core. These
types, therefore, tend to have high leakage flux, and are usually built with cores of E, T, I or
The error of a protective CT is specified at the rated current and the accuracy limit current.
ratio error
A common error in current transformers is the ratio error. It emerges when the transformer
fails to convert current precisely according to a predefined ratio. Often, the non-linear
characteristics of the core and changes in coil impedance contribute to this error.
It can be best understood going back to the equivalent and phasor diagram figures
22
Ip I s' Is
Rp Xp I Xs Ib
Rs
Io Im Rb
Vs
Ep Es
Xb
Ns
turn ratio , a =
Np
That is
nominal ratio-actual ratio
Current ratio error = (5)
actual ratio
a − at
= 100%
at
where
Ip
Transformation Ratio ( at ) at = (6)
Is
23
To evaluate I p , we extend the line of aI s from a to b and trace to c from Figure
looking at obc
I p2 = ob2 + bc 2 (7)
2 2
= aI s + I cos(90 − ( + )) + I sin(90 − ( + )) (8)
2 2
= aI s + I sin ( + ) + I cos ( + )
= a 2 I s2 + 2aI s I sin ( + ) + I 2
1
In design I aI s thus, if I sin ( + ) used instead of I the value of at is not affected. Then
we can write
1
s s (
a2 I 2 + 2aI I sin( + ) + I sin( + ) 2 2
)
at =
Is
aI s + I sin ( + )
at
Is
I
at a+ sin( + ) (10)
Is
I m sin + I o cos
at a+ (11)
Is
If = 0; cos = 1; sin = 0
24
Io
at a+ (12)
Is
Phase Angle Error – In an ideal current transformer the vector angle between the primary
and reversed secondary current is zero. But in an actual current transformer, there is a phase
difference between the primary and the secondary current because the primary current has to
supply core loss and magnetizing components of the CT for which its losses some phase angle.
Thus, the difference between the two phases is termed phase angle error . The phase angle
ac I cos( + )
tan = = (13)
ob aI s + I sin( + )
I cos − I o sin
= radian
aI s
(15)
Under normal operating conditions, the secondary winding of a CT is connected to its burden,
and it is always closed. When the current flows through the primary windings, it always flows
through secondary windings and the amperes turns of each winding are subsequently equal
and opposite. The secondary turns will be 1% and 2% less than the primary turns and the
difference being used in the magnetising core. Thus, if the secondary winding is opened and
the current flows through the primary windings, then there will be no demagnetizing flux
25
Due to the absence of the counter ampere-turns of the secondary, the unopposed primary
MMF will set up an abnormally high flux in the core. This flux will produce core loss with
subsequent heating, and a high voltage will be induced across the secondary terminal.
This voltage caused the breakdown of the insulation and also the loss of accuracy in the future
may occur because the excessive MMF leaves the residual magnetism in the core. Thus, the
secondary of CT may never be open when the primary is carrying the current.
Specific Items of CT
CTs are designed to have rated secondary current of 0.5 A, 1.0A or 5A. the burden should
have a definite VA at the rated CT current value. Since Z = VA I 2 that is the impedance varies
inversely to the rated CT current. Many CT burdens are situated at some distance from the
CT. Accordingly, the connected leads resistances do introduce an additional burden on the
CT; and the higher the current rating, the more the burden introduced by the leads. Consider
that the lead resistance is 2 ohms and at 1A rating the lead burden is 2 VA, but at 5 A rating,
the VA will be (2 5) 5 = 50 A. Therefore, in all cases where the leads burden is appreciable,
there is a great advantage in using lower rated CTs. For this reason, modern practice tends
Primary windings
It is necessary to achieve a satisfactory voltage output from a current transformer. The basic
Hence, for cases of I p = 80 A and below and N1 = 1 , the core size sectional area, Ac will be large.
It is therefore more economical to increase the number of primary turns Np to two or more in
26
certain designs. The number of secondary turns will also increase thereby increasing the knee-
point voltage for a given cross-section Ac. Figure 2.10. the transformer may be specially
constructed or bypass the primary and secondary turns through the ring-type CT design and
construction.
To limit the secondary winding losses, because of the secondary winding current as a result
of the CT resistance, it is best to reduce the winding resistance value. in this way, copper losses
and temperature rise are reduced. In core design using ring-type CT, there are no leakage
the current transformers. The effect may not be much in overcurrent relays but it does have
an effect on the overall setting of the earth-fault relay; and sometimes a profound effect on the
differential protection system. This effect is particularly so when a large number of current
transformers are connected as in the case of busbar zone protection. The error arises from the
fact that the primary operating current (POC) of a protection system = sum of relay setting
currents and magnetizing currents of all the connected current transformers at the voltage
A voltage or potential transformer fulfils one requirement, that the secondary voltage must
be an accurate replica of the primary voltage in both magnitude and phase. To achieve this
requirement, they are designed to operate at fairly low flux densities so that the magnetizing
current and hence the turn ratio and phase angle errors are small if any. The core area for a
given output is therefore larger than that of a power transformer. Therefore, the overall size
27
of a comparison unit is large. The stringent performance characteristics call for five limbs
design of the cores, figure to avoid magnetic interference between phases. For protection
the voltage is suppressed. Therefore, a VT for protection must meet the extended range of
requirements over a range of 5% to 80% of rated voltages, and for certain applications, the
Protection of VT
VTs are usually protected on the primary side of HRC fuses while other types of fused or
miniature circuit breakers are used on the secondary side. Since they are designed to operate
at low flux densities, their impedances are low and so the secondary side short circuit will
produce a fault current of many times the rated current of its normal burden.
Residual connection
Correct voltage magnitude and phase angle must be presented to directional earth fault relays
the earth fault elements of impedance relays. But an earth fault can occur on any of the three
phases of the system, and it is therefore not possible to derive a voltage conventionally. The
28
Under balanced conditions, the three winding voltages sum up to zero. But if one voltage is
absent or reduced because of an earth fault on a phase, then the difference between that
voltage and the normal voltage is delivered to the relay and hence it trips the appropriate
circuit.
At a voltage of 132kV and more, the cost of an electromagnetic voltage transformer is high.
Essentially this is a capacitor voltage divided into a turning inductance and an auxiliary
Any simple voltage divider system causes wide voltage variations and this affects the burden.
But by turning c2 with L the burden can be varied over a wide range with very low regulation.
The capacitors connected in series act like potential dividers provided the current taken by
the burden is negligible compared with the current passing through the series-connected
capacitors. However, the burden current becomes relatively larger and ratio error and also
The reactor connected in series with the burden is adjusted to such a value that at supply
frequency it resonates with the sum of two capacitors. This eliminates the error.
29
Fuses
A fuse is a safety device that protects electrical circuits from the effects of excessive currents.
It interrupts a circuit whenever that circuit carries a current larger than that for which it is
intended. Figure shows a typical fuse consisting of a low-resistance metallic wire (element)
low melting point, high conductivity and least deterioration due to oxidation. Under normal
operating conditions, the element is at a temperature below its melting point and carries the
normal current without overheating. However, when a fault occurs, the current through the
fuse increases beyond its rated value thereby raises the temperature and the fuse element
melts (or blows out), thus, disconnecting the protected circuit. In this way, a fuse protects the
Advantages
iii. Its operation is inherently completely automatic unlike a circuit breaker which requires
an
v. The smaller sizes of fuse elements impose a current limiting effect under short-circuit
conditions.
30
vi. The inverse time-current characteristic of a fuse makes it suitable for overcurrent
protection.
vii. The minimum time of operation can be made much shorter than with the circuit
breakers.
Disadvantages
ii. On heavy short circuits, discrimination between fuses in series cannot be obtained
unless
iii. The current-time characteristic of a fuse cannot always be co-related with that of the
protected apparatus.
Important Terms
i. Current rating of fuse elements. It is the current that the fuse element can normally
carry
without overheating or melting. It depends upon the temperature rise of the contacts of the
ii. Fusing current. It is the minimum current at which the fuse element melts and thus
disconnects
the circuit protected by it. For a round wire, the approximate relationship between fusing
iii. Fusing factor. It is the ratio of the minimum fusing current to the current rating of the
fuse element.
Minimum fusing current
Fusing factor=
Current rating of fuse
31
iv. Prospective Current. It is the r.m.s. value of the first loop of the fault current obtained
v. Cut-off current. It is the maximum value of fault current reached before the fuse
melts.
vi. Pre-arcing time. It is the time between the commencement of fault and the instant
vii. Arcing time. This is the time between the end of pre-arcing time and the instant when
viii. Total operating time. It is the sum of pre-arcing and arcing times.
ix. Breaking capacity. It is the r.m.s. value of a.c. component of maximum prospective
Types of Fuses
It is a usual practice to provide isolating switches in series with fuses where it is necessary to
Low voltage fuses can be subdivided into two classes viz: (i) semi-enclosed rewireable fuse
i. Semi-enclosed rewireable fuse is used where low values of fault current are to be
interrupted. It consists of (i) a base and (ii) a fuse carrier. The base is of porcelain and
carries the fixed contacts to which the incoming and outgoing phase wires are
connected. The fuse carrier is also of porcelain and holds the fuse element between its
terminals. The fuse carrier can be inserted in or taken out of the base when desired.
Advantages.
32
(i) the detachable fuse carrier permits the replacement of fuse elements without any
Disadvantages
(i) There is a possibility of renewal by the fuse wire of the wrong size or by improper
material.
(ii) It has a low-breaking capacity and hence cannot be used in circuits of high fault levels.
(iii) The fuse element is subjected to deterioration due to oxidation through the
continuous heating up of the element. Therefore, after some time, the current rating of
conditions.
(v) Accurate calibration of the fuse wire is not possible because the fusing current very
Figure shows a typical H.R.C. cartridge fuse. It consists of a heat resisting ceramic body
having metal end-caps to which is welded silver current-carrying element. The space within
the body surrounding the element is completely packed with a filling powder which may be
chalk, plaster of paris, quartz or marble dust and acts as an arc quenching and cooling
medium. Under normal load conditions, the fuse element carries the normal current without
overheating. When a fault occurs, the current increases and the fuse element melts before the
fault current reaches its first peak. The heat produced in the process vapourises the melted
silver element. The chemical reaction between the silver vapour and the filling powder results
in the formation of a high resistance substance which helps in quenching the arc.
33
Advantages
(i) They are capable of clearing high as well as low fault currents.
(vi) They are cheaper than other circuit interrupting devices of equal breaking capacity.
Disadvantages
(ii) Heat produced by the arc may affect the associated switches.
High-voltage fuses are used in high-voltage circuits. Some of the high-voltage fuses are:
(i) Cartridge type. This is similar in general construction to the low-voltage cartridge type
except that special design features are incorporated. Some designs employ fuse elements
wound in the form of a helix to avoid corona effects at higher voltages. In some designs, there
are two fuse elements in parallel; one of low resistance (silver wire) and the other of high
resistance (tungsten wire). Under normal load conditions, the low-resistance element carries
34
the normal current. When a fault occurs, the low-resistance element is blown out and the high-
resistance
element reduces the short-circuit current and finally breaks the circuit. High voltage cartridge
fuses are used upto 33 kV with a breaking capacity of about 8700 A at that voltage.
(ii) Liquid type. These fuses are filled with carbon tetrachloride and have the widest range of
applications to h.v. systems. They may be used for circuits up to about 100 A rated current on
systems up to 132 kV and may have breaking capacities of the order of 6100 A. Fig. 20.5 shows
the essential parts of the liquid fuse. It consists of a glass tube filled with carbon tetrachloride
solution and sealed at both ends with brass caps. The fuse wire is sealed at one end of the tube
and the other end of the wire is held by a strong phosphor bronze spiral spring fixed at the
other end of the glass tube. When the current exceeds the prescribed limit, the fuse wire is
blown out. As the fuse melts, the spring retracts part of it through a baffle (or liquid director)
and draws it well into the liquid. The small quantity of gas generated at the point of fusion
forces some part of the liquid into the passage through the baffle and there it effectively
(iii) Metal clad fuses. Metal clad oil-immersed fuses have been developed with the object of
providing a substitute for the oil circuit breaker. Such fuses can be used for very high voltage
circuits and operate most satisfactorily under short-circuit conditions approaching their rated
capacity.
The current carrying capacity of a fuse element mainly depends on the metal used and the
cross-sectional area. It is also affected by the length, the state of the surface and the
35