My IT Report
My IT Report
1.0 INTRODUCTION
The Students Industrial Experience Scheme (SIWES) was initiated by Industrial Training
Fund (ITF) in the year 1973 as a means of blending theory and practical experience which
was missing in our educational system. The scheme was therefore a school training
orientation program designed to expose and prepare students on work they would meet in
post-graduation endeavors.
As a federal parastatal. ITF was established by decree 47 of 1991 and charged with
view to generate a pool of indigenous trained man power sufficient to meet the needs of
the economy. A clause was invented by the fund in 1978 in its policy statement No_1
dealing with the issue of practical skills among locally trained professionals, section15
of the policy states interlaid great emphasis will be placed on certain products of post-
The fund will seek to work out co-operative machineries with industries whereby
students will be trained in industry on technics in line with their area of studies. The
fund will support such mind careers attachment by contributing to the allowance etc.
payable to the students. The scheme was therefore assigned to provide the much needed
practical experience for the students undergoing all courses that demand exposure in
1. To provide the means for students in the institutions to acquire industrial skills and
acquired in school.
Since its inception, the scope of the scheme has widened considerably. The number of
institutions grew up with its corresponding increase in the number of student’s population.
During its early years of existence, its operations were not heavy. The students’ population
could easily be managed because the industrial facilities were adequate and many multi-
nationals were expanding their industrial bases in Nigeria. The period witnessed a steady
increase in students’ population as the years went by and this meant a corresponding
The Students Industrial Work Scheme (SIWES) in physics is an exercise designed to give
undergraduates. As an important part of the core and total requirements for the award of
B.Tech. (Hons) degree in consonance with the specifications contained in the minimum
                                              2
academic standards for physics SIWES training accounts for eight (8) credit unit which
                                             3
                                    CHAPTER TWO
The Jos transmission sub-station was built in the mid 70’s (1975/1976) and was
from
330/132/33kV Kaduna sub-station for the consumption by Plateau, Bauchi and Gombe
states.
The Jos transmission sub-station switchyard is sectioned into three (3); the330kV, 132kV,
33Kv sections. This switchyard comprises of various power and switching devices with the
In the year 1981, the supply was upgraded to 330kV, and the sub-station transmits 330kV of
electricity to Gombe,132Kv to Bauchi, and 33Kv to NNPC Zaria road, Toro, Anglo Jos,
Dogon Dutse, JUTH and Rukuba road feeders in Plateau state. Currently, the station
To attain a transmission company with a solid reputation for delivering reliable, cost
effective electric power to the end users in Nigeria and western Sub-region.
                                             4
To cost effectively provide, operate and maintain the required equipment and transmission
grid network for evacuating and dispatching high quality and reliable electricity with
                                           5
2.1.4 VARIOUS DEPARTMENTS AND THEIR FUNCTIONS
The organizational structure being operated by the center currently has evolved after careful
initially analysis and matching of its mandate, objectives and strategies and also taking into
various times and at various stages either by government for such a purpose before arriving
at the current structure summarized as follows with the function carried out by the
constituent division and unit. Here we have legal service units, protocol and public relations
internal audit and under the principal managers there are seven (7) departments.
The department human relationship ensures the mutual understanding between the
employee and the management. This department is of great value in any working
need and fostering a work place culture by resolving conflicts between different
 Account Department
Payable and receivable inventory, payroll, fixed asset and all other financial element are
handle in this department. This department review the record of each department to
determine the financial position of the company and any changes requires to run the
                                             6
       Protection Control and Metering Department; The department protection and
metering is one responsible for providing protection to the installed equipment such
others using different types of relay and other metering devices. This department is
also responsible for pre commissioning test and termination of newly installed
mechanisms. This department also carried out maintenance of station battery banks
This department deals with the maintenance of the grid patrol of 330/132Kv towers,
replacement of conductors, clamps, broken insulator and routine patrol of the grid.
This is a department responsible for the interconnection of stations for monitoring of the
overhead cables and for communication between stations. Communication is vital in the
management of all control and protection systems in the switchyard and in inter relation to
other substations.
This is a department responsible for the operations and monitoring of installed switch gears
in the switchyard. This department also issue work and test permit and station guarantee to
                                             7
2.1.6 SUBSTATIONS
transform voltage from high to low or the reverse. Between the generating station and the
consumer, electric power may flow through several station at different voltage level. It may
include transformers and other power equipment installed to change the voltage level from
any station where the power equipment are installed for voltage transformation. A
covered with gravels to function as an insulator from the bare ground because of its ability
to drain water and reduce water-logged areas thus reducing the risk of electric shocks. The
switchyard consists of transformers, circuit breakers, bus-bars, line isolator, feeders, wave-
                                              8
                    Fig. 1 A section of the switchyard at Jos work center
CHAPTER THREE
3.1.0 INTRODUCTION
During the twelve month SIWES attachment, the SIWES was observed in four (4) various
The protection control and metering department is the first department where the SIWES
was observed. It is the department responsible for the protection of switchgears such as
power transformers among others using various protectives relays and the instrument
transformers. This department also carried out the pre commissioning test and termination
                                             9
A relay is an electrically operated switch which is use in a situation needed to control a
circuit by low power signal with complete isolation between control and controlled circuits
or where several circuits must be controlled by one signal. In other word, a relay can be
described as an automatic device which contained two or more open and close contact that
characteristics and sometimes multiple operating coils are used to protect electrical circuits
from faults. In modern electrical power systems, these function are performed by digital
instruments called protective relays. This relays are classified base on their characteristic,
As mentioned above, relays are basically classified base on the below four (4) criteria;
1. Operating mechanism
2. Logic operation
3. Characteristic operation
4. Actuating parameters
1 Operating mechanism;
In this classification, relay can either be electromagnetic relay, mechanical or static relay.
In an electromagnetic relay, the opening and closing of relay contacts are done by
electromagnetic action of a solenoid. As for mechanical relay, the opening and closing of
the contacts are done by mechanical displacement of different gear level system. Static relay
is one in which the opening and closing are done by semiconductor switches like thyristor
2 Logic operation;
                                             10
Example of this relay are the differential relay and distance protection relay. A
differential relay is one protecting the power transformer and the bus-bar while a distance
3 Characteristic operation
Base on characteristics operation relay are categorized as; definite time relay and inverse
4 Actuating parameters
Base on actuating parameters, relay can be categorized as; current relay, voltage relay
among others.
Transformer fault post great danger to people around, reduce the output supply of the station
and the environs at large. This fault may lead to the loss of transformer. As a preventive
measure, relays are set at different location to protect the power equipment most especially
the power transformer. Some of the functions of relay among others in power system
include;
1 Mechanical Protection; Mechanical fault are detected by buchholz relay. This relay is
designed for conservator tank and it detect gas as it rises from the insulating oil due to
2 Over-Current Protection; As the name indicate, the relay trips when the current flowing
in the transformer is above the rated currents of the transformers, the setting of this relay
takes care of the marginal increases and switching surge and operate on substantial changes
                                                11
in the currents only. It is normally located on the HV side since current handled are lower
3 Restricted Earth Fault Protection; This restricted earth fault relay is provided at the
neutral point of the transformer but before earthling. It differs from the normal earth fault
relay to the extent that (EFR) pick-up even line fault whereas, the (REFR) pick-up only the
transformer faults. A fault inside the transformer occurring on one or two phase result in
flow of high current in the neutral. The relay is said to act instantaneously.
4 Differential Protection; this relay keeps a watch on the incoming and outgoing current of
a transformer as long as the current in the CT’s match (taking into consideration the
transformation ratios) the relay remain inactive as long as there is a long balance.
Whenever the balance changes which is possible if there is a fault in the zone between the
two CT’s the differential relay acts tripping off power supply to the transformer.
Since protective relaying, comes into action at the time of equipment distress, a certain
safeguard is necessary in the unlikely event of its failure to act at the time of need. Hence,
 Primary protection
 Back-up protection
Primary protection is the first line of defense, whereas back-up protection follows if the
In power system, protective relays are very expedient in protecting and monitoring the
                                              12
because it improved their efficiency as a protective devices and also increase the life span of
the power equipment. For that maintenance of relay is carried out twice or thrice monthly
mainly to have a better functioning relays and thus increase their efficiency. The major
maintenances culture of this relays are; secondary injection test and primary injection
test
 Secondary injection test; this is done on the relay panel in the control room
to test the relay in order to see whether it will relate with the current
transformer and the circuit breaker to operate in the case of fault. In this test,
it requires the simulation of fault at different current value to the relay using
 Primary injection test; this is done in the switch yard on the current
transformer to see whether the relay will react to the injected current on the
current transformer to operate the circuit breaker in the case of fault using
CPC 100.
Below is a sample reading for the secondary and primary injection test.
 As met setting
EF PS=0.2 TMS=0.06
A Pick up values
                                              13
              Red; Ipk=0.83A      t0=0.81sec
B Relay calibration
RED 1 6.19 10
BLUE 1 7.72 10
CENTER
11 SEPTEMBER,2018
CT RATIO:400/1
                                               14
 R           PS=1                  94          E/F TRIP          OPENED       OKAY
TMS=0.15
TMS=0.2
TMS=0.15
Electrical equipment of high voltage can’t be connected directly to the relay or the control
panel for safety purpose. For that, the current and voltage transformer are needed for
connecting the power equipment to the relay and the control panel. These transformers
reduce the voltage and current level from higher value to low value for measurement by the
relays.
 Current transformer; this is a transformer that transform current from high current
value to low current value for measurement by the conventional instrument like the
relay. In this transformer, the primary winding carries the current which is to be
                                                 15
measured while the secondary winding is connected to the relay. The range of the
transformers are of two type; the wound type and the core type in term of
construction
                                    16
      Potential or Voltage transformer; this is an instrument transformer that transform
voltage from high value to low value for measurement by the relay. The voltage
This is the second department where SIWES was observed and is the department
responsible for maintenances, repairs and installations of all electrical and non-electrical
department also deals with the maintenance of power transformers, circuit breakers,
reactors, isolators, and their operating mechanisms. It also responsible for the
3.2.1 TRANSFORMER
A transformer is a static equipment that enables the transfer of electrical energy from a
system of one voltage level to a system of another. To accomplish this, two or three
windings wound over a magnetic core are needed. The windings are electrically separated
but inter-linked magnetically. The energy transfer is by induction most of the times but
widely used in power systems to transmit power at an economical transmission voltage and
                                            17
3.2.2 BASIC PRINCIPLE OF A TRANSFORMER
Transformer working is based on mutual electromotive force induction between two coils,
which are magnetically coupled. When an AC voltage is applied to one of the windings
(referred to as the primary), it produces alternating magnetic flux in the core made of a
magnetic material (usually some form of steel). The flux is produced by a small
magnetizing current which flows through the windings. The alternating magnetic flux
induces an electromotive force (EMF) in the secondary winding magnetically linked with
the same core and appears as a voltage across the terminals of these windings. Cold rolled
grain oriented steel (CRGO) is used as the core material to provide a low reluctance, low
loss flux path. The steel is in the form of varnished laminations to reduce eddy current flow
primary and secondary are wound. The primary winding is supplied with an AC source of
supply voltage V1. The current flowing in the primary winding produces flux, which varies
                                            18
with time. The flux links with both the windings and produces induced electromagnetic
forces. The electromagnetic force produced in the primary winding is equal and opposite of
the applied voltage (neglecting losses). The electromagnetic force is also induced in the
secondary winding due to mutual flux. The magnitude of the induced electromagnetic force
depends on the number of turns in the primary and secondary windings of the transformer.
 POTENTIAL-INDUCED
The ratio of the primary potential to the secondary potential is the ratio of the number of
N1/N2=V1/V2 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2.1
The concept of step-up and down transformers functions on similar relation. A step up
transformer increases the output voltage by taking N 2>N1 and a step-down transformer
 CURRENT-INDUCED
When the transformer is loaded, the current is inversely proportional to the voltages and is
represented as follows;
V1/V2=I2/I1=N1/N2- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2.2
1 Before their invention and use, power generation and supply was as direct current only,
that is in small quantities. Change of voltages here is not normally possible. Their invention
brought in alternating current production and distribution with voltage change at will, to suit
                                                        19
2 They instituted large scale production and distribution of electrical energy (Increases by
billions of times).
3 They contributed to transporting bulk power through long distances (by increasing to very
high voltages) very economically and reduced high power loss in transmission.
4 Power supply from its generation point to its utilization site, normally passes through 4-6
transformers in all.
The Transmission Company of Nigeria Jos work center comprise of two type of transformer
namely;
1. Power transformer
2. Earthling transformer
Earthling transformer is one of the most important power equipment among the switchgear
in the switchyard. It is mainly for protecting the power transformer against earth fault and
                                            20
                               Fig 4: An Earthling transformer
Since earth is everywhere, grounding ensures keeping the neutral at ground potential at all
places in the country thereby ensuring constancy of phase to neutral voltage of all
similar(voltage) rating transformers. Then all electrical gadgets (say 220volts) can be
worked anywhere in the country. If the neutral is not earthed it would assume its own
potential. This would result to potential difference between the neutral and phase which
would be different in different transformers and all electrical gadgets would not work
                                              21
      Easy path to protective circuit of the transformer;
All earth faults protections and transformers are wired through the earth, and grounding.
The neutral ensures easy path for fault current flow. The moment the currents exceed certain
pre-determined values power supply to the transformer is cut off thereby preventing further
 Neutral floating;
An improperly grounded neutral would cause electrical floating. This would cause the phase
to neutral voltage to be different for the 3phases of the same transformer (when the 3phases
In Figure 5 (not to any scale) the thin lines of the sides of the triangle represent the primary
voltages and the bold lines of the represented the secondary voltages (with unearthed
neutral).
                                              22
Fig.6: Delta Star Diagram of Flow of Voltage
In the case of the figure above, these secondary phase to neutral voltages are equal, as the
In the case of the second figure, the secondary phase to neutral voltages is unequal. The
floating neutral has shifted so that the phase that has the highest load is provided with the
highest voltage named CN. Then the consumers of the phase AN and BN experience low
voltage(Narayana,2007).
The Transmission Company of Nigeria Jos work center switchyard contains transformers of
MAKE: BKS-75000/330
TYPE: IEC60289
STANDARD: HV330,000V
                                             23
1. RATED AMPERS: ONAN: 139.96 839.786
2. FREQUENCY 50Hz
3. VECTORGROUP: Yd11
5. PHASES: 3/3HV/LV
Tap position 01 to 17
6. IMPEDENCE VOLTS%: 1 5 17
                                             24
14. ACTIVE PART WEIGHT:                   51900Kg
      Vector group
      Cooling method
      Maximum ambient temperature
      Top-oil rise temperature
      Winding temperature rise
 Insulation level
 VECTOR GROUPING;
Vector grouping is an indication of the nature of the primary and the secondary connection
between the three phases of a transformer, along with the phase shift (if any) of the
secondary with respect to the primary. For example, a transformer having Dyn11 group; The
11: is the phase shifting, which indicates that LV winding leads the HV by 30˚.
                                              25
      TYPE OF COOLING: ONAN/ONAF.
The capacity of fans is to create adequate breeze and cooling so that we can draw
100% full load currents. ONAN is an acronym for Oil Natural and Air Natural
indicates the mode of cooling the transformer. The heat generated in the winding is
medium. Convection currents are set up due to oil portions getting heated up to
different temperature and thus acquiring different specific gravities. During the
circulation process the heat is conveyed to the tank/radiators and later dissipated to
the atmosphere. Thus the oil circulation and air movement is left to the nature and
we don’t do anything about it. As regards the arrangements of this ONAN cooling,
the 150MVA are provided with radiators or oil coolers permanently welded to the
body. The radiators are designed for maximum surface area for a given internal
volume so that heat dissipation into the atmosphere is maximum. In USA it is called
In the case of ONAF, certain high speed fans are fitted to the radiators. Here the cooling is
ONAN basis up to certain level of loads. After words, the fans are switched on either
automatically (by temperature controlled relays) or manually to create a breeze through the
can be installed and operated in places where the ambient temperature does not
                                              26
        and below in case the atmospheric temperature rises above45°C. Since all the other
temperatures like that of oil windings etc. are relative to this ambient temperature,
hourly basis.
loaded to such extent as to allow a temperature rise up to 45°Cover and above the
ambient temperature. For example, if the atmospheric temperature is 30°C, then the
30°C+45°C=75°C.
The words TOP-OIL is in view of the fact that inside a transformer, only the top most
portion of oil attains the maximum temperature when compared to middle/ lower or bottom
A thermometer is provided to measure this top oil temperature for the purpose normally a
metallic pocket is welded to the top plate so that it protrudes into the oil tank. The pocket is
filled with oil so that it attains the same temperature as the top oil inside the transformer.
The thermometer is provided with a relay setting for alarm and trip, for marginal rise and
                                              27
                                    Fig. 7: Thermometer
Temperature can increase to 55°Cover and above the atmospheric temperature. Here
again we can allow a temperature rise in the windings up to100°C, which is a sum of 55°C
(the latter figure is the maximum allowable ambient temperature). 40years ago, they put a
normal thermometer with its probe along with that of the scale so graduated that the reading
is 10°C above that of the top oil. But practices over further periods showed that the winding
temperature is directly proportional to the current. So, the manufacturers put a CT in one of
the HV bushings and put a thermometer temperature scale for the indicator needle, which
actually moves in proportion to the HV current. In the case of the winding temperature rise
thermometer, relay settings are made for radiators fans “ON” actuation, alarm and tripping,
for marginal and abnormal rise in the winding temperature respectively. This procedure a
gain has been improved upon. A thermometer which combines both the actual effects of oil
temperature and winding temperatures called the hot spot temperature indicator has been
developed. This meter is normally set to actuate radiator fans at 70°C, alarm at 90°C and
trips at 100°C (these settings are in the case of a power transformer under discussion which
is designed providing for a winding temperature rise of 55°C and vary for other). The hot
spot temperature indicator is located in control panel/alarm panel box. An accessory of the
                                            28
                                 Fig.7: Temperature Indicator
 INSULATION LEVEL: The manufacturer is informing the buyers that though the
operating voltages of this transformer are 330KV (HV side) and 132KV (LV side),
laid out in I.S from the safety factor point of view and everybody follows this
conditions.
This is a separate rectangular box mounted at the transformer tank, housing as the name
indicates, all alarms circuit of the transformer. The box also houses pot temperature
indicator, fans-on and fans-off switches for local control of radiator fans.
                                              29
3.2.7 TRANSFORMER LOSES;
These losses are converted into heat which raises the temperature of the interior parts. This
arises the necessity of a cooling medium which is the transit oil. It is a liquid, non-organic
In maintenance work, the quality of the transformer oil indicates the status of the
transformer.
In Transmission Company of Nigeria Jos work center, the following test are performed on a
test includes;
1. Continuity tests
                                                30
    5. Open circuit test.
 B.D.V TEST
Break-down voltage test is a measure of the ability of the transit oil to withstand electric
 D.G.A TEST
Dissolved gas analysis is a measure of the various gases present in the transformer oil. The
various gases present in the transit oil are a measure of deterioration of some solid dielectric
material or transformer oil decomposition due to internal arcing etc. By studying the gases
and to what extent these gases are present, one can arrive at some of the happenings inside
the transformer for example, if there is high level of hydrogen it is an indication of partial
 TAN-TEST
In the tan-test or tan-delta test the power factor(PF) or dissipation factor(DF) of the
number between zero and one PF and DF indicates the dryness of an insulating material.
Their values are almost same in the case of an insulating material. When the insulation
systems get contaminated with moisture and other impurities or pollutant, the power factor
or dissipation factor becomes more. The PF/DF is measured by imposing a voltage across
                                              31
      Winding failure due to mechanical stress.
 Transformer bushing due to general aging, cracking, and internal moisture. Core
electrical circuit from damage caused by overload or short circuit. Its basic function is to
isolate the unhealthy part of the system from the healthy part. Unlike a fuse, which operates
once and then must be replaced, a circuit breaker can be reset (either manually or
automatically) to resume normal operation. Circuit breakers are made in varying sizes, from
designed to protect high voltage circuits feeding an entire city. Its trips off when it senses
overload or a fault on the line and its subjected to hard conditions in the switchyard. The
circuit breaker can be opened manually or automatically. When the circuit breaker senses
any fault, the motor acts on the spring and it breaks the supply or trips off and it then opens
the isolators but there is a spark in the breaker capable of causing a fire outbreak but due to
the arc quenching media in the breaker, it extinguishes the fire. There are various types of
                                             32
Basically circuit breakers are named base on the quenching media provided in the breaker to
reduce the great arcing that occur in the process of opening the breaker. The various types
of breaker include;
In Transmission Company of Nigeria, air blast circuit breaker is not use due to the great
In this type of breaker Mineral oil is used as quenching medium due to its property as a
better insulating material than air. In oil circuit breaker, the fixed contact and moving
contact are immerged inside the insulating oil. Whenever there is a separation of current
carrying contacts in the oil, the arc is initialized at the moment of separation of contacts, and
due to this arc the oil is vaporized and decomposed in mostly hydrogen gas and ultimately
creates a hydrogen bubble around the arc. This highly compressed gas bubble around the arc
prevents re striking of the arc after current reaches zero crossing of the cycle. The Oil
A vacuum circuit breaker is such kind of circuit breaker where the arc quenching
takes place in vacuum. The technology is suitable for mainly medium voltage
                                              33
       application. For higher voltage Vacuum technology has been developed but not
contacts and associated arc interruption take place in a vacuum chamber in the
steel arc chamber in the center symmetrically arranged ceramic insulators. The
A gas circuit breaker is such kind of a circuit breaker that protect the power station by
interrupting electric currents, when tripped by a protective relay. In this type of breaker
Sulphur hexafluoride gas are use as quenching medium in the course of opening the breaker.
                                           34
This breaker has low operating noise with no emission of hot gases and relatively low
maintenance.
In transmission company of Nigeria Jos work center, the normal maintenance of the circuit
breaker includes;
                                               35
    3.3.3   BATTERY BAND/BATTERY BAND MAINTENACE
 DC Supply/Battery band
power to the station in case of power failure as well as supplies power for protection and
metering panels in the control room. The battery bank has two sides, the 50v DC side
and the 110v DC side. The 50v DC side is used for communication and alarm. While the
110v DC side is used for protection. To guarantee or ensure a better efficiency or proper
functioning of the battery banks, proper maintenance is carried out every month which
also involves isolating the battery bank AC supply. The overall voltage of the batteries
of 250v and the voltage of each battery is measured using a multi meter. A hydrometer
is used for the measurement of the specific gravity. The batteries with low electrolytes
                                         36
Fig.10; showing battery band during maintenance
 Battery charger
The battery charger converts the primary AC supply to a regulated DC voltage which
charges the batteries and powers the protection and metering equipment in the station.
When the battery charger is taken off, the batteries supply power without switching or
                                          37
                                 Fig. 11; Battery charger
Shunt Reactors are inductive loads that are used to absorb reactive power to reduce the
inductive load consumes reactive versus a capacitive load generate a reactive power. A
transformer as a shunt reactor, a heavy loaded power line, and an under magnetized
synchronous machine are examples of inductive loads. Shunt reactors are mainly used in
lines under low load conditions and thereby, stabilize the system voltage. Shunt reactors
are normally connected to substation bus bar, but also quite often directly to the
overhead lines. Alternatively, they may also be connected to tertiary winding of power
transformers. The shunt reactors may have grounded or reactor neutral. This transformer
was observed. It deals with the maintenance of the grid patrol of 330/132Kv
                                         38
            towers, replacement of conductors, clamps, broken disk insulator and
3.3.6 TOWERS
Transmission towers have to carry the heavy transmission conductor at a sufficient safe
height from ground. Main parts of a transmission tower. A power transmission tower
 Peak of transmission tower: The portion above the top cross arm is called peak of
transmission tower. Generally, earth shield wire connected to the tip of this peak.
 Cross Arm of transmission tower: Cross arms of transmission tower hold the
                                            39
    transmission voltage, configuration and minimum forming angle for stress
distribution.
 Cage of transmission tower: The portion between tower body and peak is known as
cage of transmission tower. This portion of the tower holds the cross arms.
 Transmission tower body: The portion from bottom cross arms up to the ground
level is called transmission tower body. This portion of the tower plays a vital role
transmission line.
                                         40
Fig 12: Tower Dimension.
          41
3.3.7 TYPES OF TRANSMISSION TOWER
There are different types of transmission towers. The transmission line goes as per available
corridors. Due to unavailability of shortest distance straight corridor transmission line has to
deviate from its straightway when obstruction comes. In total length of along transmission
According to the angle of deviation there are four types of transmission tower;
With regard to the force applied by the conductor on the cross arms, the transmission towers
is where the conductors are simply suspended from the tower, the mechanical
tension being equal or same on both each sides. It is a tower that carries a down
ward force and lateral force. These also have for each conductor an insulator
string hanging down from the tower or two strings making a ‘V’ shape. These
are towers used where a transmission line continuous in a straight line or turns
 Angle tower or tension tower or sometime it is called section tower. All B, C and
located between every three or four suspension towers to pull the conductors
which are re-tied in tension tower insulators. This type of tower that carries a
                                              42
           longitudinal force and is mostly used in road crossing and deviation in
transmission line.
 TOWER SPANS; The Tower Spans is the distance between two towers, for 330KV
From Jos work center to Makeri Sub-station 132KV Double circuit line;
Distance from jos work center to Makeri Sub-station, Terminal Towers ;28km.
The sky wire is connected to earth after certain number of towers and serves as a lightening
conductor or lightening arrestor which is connected at the apex or tip of the towers. It
collects or receives all the discharged current by lightening from the tip of the towers and
drains it down to the ground by earthling. Every lightening that strikes adds a minimum of
This is the last department where SIWES was observed. It is the department responsible for
the operations and monitoring of installed switch gears in the switchyard. This department
also issue work and test permit and station guarantee to the other technical department in the
organization.
                                             43
3.4.0 THE CONTROL PANEL/BOARDS
This is a board/panel which provides operators with information about power flow,
conditions, efficiency of equipment and working principles of the circuits i.e. current
reading the three (3) phases. Voltage reading of the three (3) phases, transformer winding
temperature, oil temperature, switching equipment alarms and trips, frequency of the main
supply to the equipment e.g. transformers, 33kv feeders Rukuba, Dogon Dutse, NNPC,
Anglo-Jos, Toro, JUTH, Zaria road feeders. The operators also give permits and the isolate
Fig. 13: 33Kv relay Panel Board showing different relay protecting the feeders
                                           44
                             CHAPTER FOUR
department libraries.
 The welfare of the students should be looked out for, and ITF should try and
pay students before going for the training so that it can ease the stress of
transport fare.
 Safety wears should be made available for every student when the need arises.
 The libraries and internet connections should be made available for research.
section.
                                             45
4.1.3 RECOMMENDATION
 The welfare of the students should be looked out for and ITF should try and pay
students before going for the training so that it can ease the stress of transport
fare.
organization.
 Provision of Safety wears should be made available for every student when the
4.1.4 CONCLUSION
knowledge and skills learnt. It also provides student with industrial work experience which
                                               46
                              4.1.5 REFERENCES
maintenance. A first edition printed and published by the Author: Press by terrain
47