Operation Manual
Smart-UPS™
  Uninterruptible Power Supply
   SCL500RMI1UC and SCL500RMI1UNC
        500 VA Short-depth Rack-Mount
              with Lithium-ion batteries
This manual provides product safety and installation information for the SCL500RMI1UC and
SCL500RMI1UNC. The only difference between these two models is in their monitoring and
management options. The SCL500RMI1UC has the “SmartConnect” port, which allows the product to
be monitored remotely. Learn more about the APCTM SmartConnect feature on
www.smartconnect.apc.com. The SCL500RMI1UNC can be managed via traditional methods and APC
softwares, it has an embedded network management card, the AP9537SUM.
Important Safety Messages
    SAVE THESE INSTRUCTIONS - This manual contains important instructions that should be followed during
    installation and maintenance of the UPS and batteries.
    Read these instructions carefully and look at the equipment to become familiar with the device before trying to
    install, operate, service or maintain it. The following special messages may appear throughout this bulletin or on
    the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
                  The addition of this symbol to either a “Danger” or “Warning” safety label indicates that an electrical
                  hazard exists which will result in personal injury if the instructions are not followed.
                  This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all
                  safety messages that follow this symbol to avoid possible injury or death.
                                                      DANGER
 DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
                                                     WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
                                                     CAUTION
 CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
                                                     NOTICE
NOTICE is used to address practices not related to physical injury.
                          Smart-UPS SCL500 230 Vac Short-depth Rack-Mount                                                      1
Safety and General Information
Inspect the package contents upon receipt. Notify the carrier and dealer if there is any damage.
General safety
         • Adhere to all national and local electrical codes.
         • All wiring must be performed by a qualified electrician.
         • Changes and modifications to this unit not expressly approved by APC by Schneider Electric could
           void the warranty.
         • This UPS is intended for indoor use only.
         • Do not operate this unit in direct sunlight, in contact with fluids, or where there is excessive dust or
           humidity.
         • Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation.
         • For a UPS with a factory installed power cord, connect the UPS power cable directly to a wall outlet. Do not
           use surge protectors or extension cords.
         • The equipment is heavy. Always practice safe lifting techniques adequate for the weight of the equipment.
Deenergizing safety
     The UPS contains internal batteries and may present a shock hazard even when disconnected from the branch
     circuit (mains). Before installing or servicing the equipment check that the:
         • Input circuit breaker is in the OFF position.
         • Internal UPS batteries are removed.
Electrical safety
         • Use tools with insulated handles.
         • Do not handle any metallic connector before power has been disconnected.
         • 230 V models only: In order to maintain compliance with the EMC directive for products sold in Europe,
           output cords attached to the UPS must not exceed 10 meters in length.
         • The protective earth conductor for the UPS carries the leakage current from the load devices (computer
           equipment). An insulated ground conductor is to be installed as part of the branch circuit that supplies the
           UPS. The conductor must have the same size and insulation material as the grounded and ungrounded
           branch circuit supply conductors. The conductor will typically be green, with or without a yellow stripe.
         • Leakage current for a pluggable, Type A UPS may exceed 3.5 mA when a separate ground terminal is used.
         • The UPS input ground conductor must be properly bonded to protective earth at the service panel.
         • If the UPS input power is supplied by a separately derived system, the ground conductor must be properly
           bonded at the supply transformer or motor generator set.
2                                 Smart-UPS SCL500 230 Vac Short-depth Rack-Mount
Battery safety
             • The batteries typically last for 10 years and operate between 0 and 40 °C. Environmental factors impact
               battery life. Elevated ambient temperatures, poor quality utility power, and frequent short duration
               discharges will shorten battery life. Due to the long life of the batteries, we recommend replacing the unit
               entirely. For longest battery performance, the ambient temperature should be maintained between 68° and
               77°F (20° and 25°C).
             • This unit uses Lithium Ion (LFP) batteries. Under normal use and handling, there is no contact with the
               internal components of the battery.
             • Servicing of user replaceable batteries should to be performed or supervised by personnel knowledgeable
               about batteries and required precautions. Keep unauthorized personnel away from batteries. When
               replacing batteries, replace with the same type and number of batteries or battery packs. In this case,
               batteries are not user replaceable.
             • Disconnect the charging source prior to connecting or disconnecting battery terminals.
             • CAUTION: Before installing or replacing the batteries, remove conductive jewelry such as chains, wrist
               watches and rings. High energy through conductive materials could cause severe burns.
             • CAUTION: Do not dispose of batteries in a fire. The batteries may explode.
             • CAUTION: Do not open the plastic case of the batteries. Doing so will expose the cell terminals which pose
               an energy hazard.
             • CAUTION: Failed batteries can reach temperatures that exceed the burn thresholds for touchable surfaces.
             • CAUTION: Do not open or mutilate batteries. Released material is harmful to the skin and eyes. It may be
               toxic.
             • CAUTION: A battery can present a risk of electric shock and burns by high short-circuit current. The
               following precautions should be observed when working on batteries:
                 – Disconnect the charging source prior to connecting or disconnecting battery terminals.
                 – Do not wear any metal objects including watches and rings.
                 – Do not lay tools or metal parts on top of batteries.
                 – Use tools with insulated handles.
                 – Wear rubber gloves and boots.
                 – Determine if battery is either intentionally or inadvertently grounded. Contact with any part of
                   a grounded battery can result in electric shock and burns by high short-circuit current. The risk
                   of such hazards can be reduced if grounds are removed during installation and maintenance by
                   a skilled person.
•
                                                        WARNING
    RISK OF CHEMICAL HAZARD AND EXCESSIVE HEAT
    • Recycle the UPS when the UPS battery fault is detected at the end of its service life. Power off the UPS
      and unplug it from the AC input.
    • The battery is not user replaceable. Contact APC by Schneider Electric Worldwide Customer Support if
      there are defects in the product and the product is within warranty.
    Failure to follow these instructions can result in death or serious injury.
General information
             • The model and serial numbers are located on a small, rear panel label. For some models, an additional label
               is located on the chassis under the front bezel.
             • Always recycle used batteries.
             • Recycle the package materials or save them for reuse.
                              Smart-UPS SCL500 230 Vac Short-depth Rack-Mount                                                 3
        SCL500RMI1UC and SCL500RMI1UNC Rack-Mount
Rack-Mounting
                                             
                                  0   76a
                             su 1                                                                    6a
                                                                                                 10 7
                                                                                              su
                                           Two-post rack-mounting: Utilize the bracket holes that
                                            are offset 6.25”.
                                     6a
                                  107
                             su
                                                                                               0   77a
                                                                                           su 1
4               Smart-UPS SCL500 230 Vac Short-depth Rack-Mount
 Secure clip nuts to the rack, and attach brackets with                      
provided screws.
                                                                          a                                                       9a
                                                                      07 8                                                1 07
                                                               s u1                                                     su
                                                                        
                                                                    0b                                                        b
                                                               08                                                      08 1
                                                           su1                                                  s u1
Tower Configuration
      Attention: Connect the battery before tower setup by referring to applicable steps in “Rack-Mounting” .
                                                                                                 b
                                                                                             073
                                                                                      s u1
                            Smart-UPS SCL500 230 Vac Short-depth Rack-Mount                                                            5
Wall Mounting
         Attention: Connect the battery before mounting by referring to applicable steps in “Rack-Mounting” .
         To avoid a hazard, do not mount the unit on the wall with the bezel facing downwards, or with the display panel at
         the bottom.
    
                                                      s u10
                                                              82 b
     Note: Whenever possible, attach two screws into wall studs. If stud mounting is not possible, use an expandable wall
    anchor. Hardware is not included;.25” x 2” lag bolts are recommended. Mount the UPS in either of the displayed positions.
                                                       su1083a
                                                                                 su1084a
6                                      Smart-UPS SCL500 230 Vac Short-depth Rack-Mount
Specifications
    For additional specifications, refer to the APC Web site at www.apc.com.
Environmental specifications
                                       Operating                 0° to 40° C (32° to 104° F)
      Temperature
                                       Storage                   -15° to 40° C (5° to 104° F)
                                       Operating                 24,606.3 ft. (7,500m)
      Maximum Elevation
                                       Storage                   9,842.5 ft. (3,000 m)
      Humidity                                                   0% to 95% relative humidity, non-condensing
      International Protection Code                              IP20
      Pollution Degree                                           2
      Overvoltage Category                                       II
      Applicable power grid power distribution system            TN Power System
      Applicable standard                                        IEC 62040-1
    Note: The recommended recharge interval for this UPS is 12 months.
Product Overview
SCL500RMI1UC & SCL500RMI1UNC Rack-Mount
                                                                                   Battery
                                                                                   Bezel
                                                                                   Battery Door
                                                                                   Display (more information below)
                                                                           b
                                                                       028
                                                                s u1
Front panel display features
                                                                                Online / On Battery indicator
                        SCL500RMI 1UC                                                 ™
                                                                                APC SmartConnect status indicator
          1                                             4                       Network status indicator
                                                                                Event Detected indicator
                                                                                Battery Error indicator
          2                                             5
                       SCL500 RMI 1 UNC
          1                                             4
          3                                             5
                                            su1031c
                         Smart-UPS SCL500 230 Vac Short-depth Rack-Mount                                                7
Rear panel features
         ™
     APC SmartConnect port                     Circuit breaker
     Network port                              Controlled outlet group
     USB port                                  Outlets
                                                    ™
     Chassis ground connection screw           APC SmartConnect Control
     UPS input                                 Modbus TCP Control
           SCL 500RMI 1 UC
           SCL 500 RMI 1 UNC
                                                                                                    su1029b
Dimensions and weights
SCL500RMI1UC and SCL500RMI1UNC Rack-Mount Models
                   su 10
                           3 0b
                            Model             Dimensions (in/mm) H x W x D              Weight (lb / kg)
                 SCL500RMI1UC                                                              8.95 / 4.06
                                      17 x 9.14 x 1.75 in (431.8 x 232.14 x 44.44 mm)
                 SCL500RMI1UNC                                                             9.04 / 4.10
8                                   Smart-UPS SCL500 230 Vac Short-depth Rack-Mount
Installation
     For UPS installation information, refer to the Installation Guide included with the UPS.
Placement
     The UPS is intended for IT environments. Avoid placement where there is excessive dust and humidity. Note that
     temperature in excess of 25o C may have an adverse effect on battery and UPS life. All vents on the side or rear of
     the UPS should be free of obstructions.
     The UPS is heavy. The UPS should be placed near the bottom of the rack.
Connect to equipment and utilities
     Note: The UPS will charge to 98% capacity in the first three hours of normal operation.
     Do not expect full battery runtime capability during this initial charge period.
                                                       CAUTION
RISK OF INJURY OR DAMAGE TO EQUIPMENT
 • Adhere to all local and national electrical codes.
 • Wiring should be performed by qualified electrician.
 • Always connect the UPS to a grounded outlet.
Failure to follow these instructions can result in injury or equipment damage.
     1. Connect equipment to the
        outlets in the rear of the
        UPS. Some models are
        equipped with controlled
        outlet groups. Refer to the
        “Configuration” section
        of this manual for further
        instructions on the use of
        controlled outlet groups.                                                                                su0968l
     2. Connect the APC™                                                    
        SmartConnect port      or
        network port to your
        nearest network switch
        using the cable provided.
        When connecting to APC
        SmartConnect, verify that
        the SmartConnect
        Control Switch near the
        network port is set to             SCL 500 RMI 1 UNC
        either “Enable with
        Control” or “Enable-No
        control”.
     3. To setup and manage via            SCL 500 RMI 1 UC
        network port, download
        the Device IP
        Configuration Utility
        from www.apc.com.
     4. Connect the UPS input to AC power.
        Note: Once power is connected the display will be active.
     5. Press the main power button         on the UPS display to turn on the UPS output.
        Note: The On-line LED         will light green when the output is on.
                            Smart-UPS SCL500 230 Vac Short-depth Rack-Mount                                                9
APCTM SmartConnect
     APCTM SmartConnect allows you to monitor the health and status of your UPS from any device connected to the
     Internet. Visit www.smartconnect.apc.com to learn more.
     Log onto www.smartconnect.apc.com or scan the QR code to launch the registration process. The website includes
     instructions to setup your online account, activate your warranty and begin monitoring your UPS remotely.
     By connecting this product to the Internet using the APCTM SmartConnect port, you are agreeing to APCTM
     SmartConnect Terms of Use, as found at smartconnect.apc.com. Schneider Electric Data Privacy Policy can also be
     found at smartconnect.apc.com.
Device IP configuration utility
     The Device IP Configuration Utility can discover Network Management Cards (NMC 2) that do not have an IP
     address assigned. Once discovered, you can configure the IP address settings for the cards. You can also search for
     devices already on the network by entering an IP range to define the search. The Utility scans the IP addresses in
     the defined range and discovers cards that already have a DHCP-assigned IP address.
     For detailed information on the Utility, see the Knowledge Base on the support page of the www.apc.com website
     and search for FA156064 (the ID of the relevant article).
     Once IP address found, access the Web management interface by this IP address. Enter the user name and password
     to login (by default, use apc and apc to login as the administrator).
Connect and install management software
     Smart-UPS is provided with PowerChute management software for unattended operating system shutdown, UPS
     monitoring, UPS control and energy reporting. The following diagram is a representation of a typical server
     installation.
     1. Connect the USB cable (SCL500RMI1UC) / Network cable (SCL500RMI1UNC) from the rear of the
        UPS       / Network Port   to the protected device such as a server.
     2. For a server or other device with an operating system connected to the SCL500RMI1UC, download and install
        the latest version of the PowerChute Business Edition from www.apc.com/pcbe.
        For network-based, graceful, unattended shutdown of your physical servers and virtual machines connected to
        the SCL500RMI1UNC, install the latest version of PowerChute Network Shutdown from www.apc.com/pcns.
        PowerChute provides for graceful shutdown in the event of an extended power outage and is a powerful
        management interface on the local network.
                                                    SCL 500 R M I 1 U NC
                                                    SCL 500 R M I 1 U C
                                                                           su0969i
                                                           OR
     Download and install the latest version                                     Download and install the latest version
       of PowerChute Network Shutdown                                             of PowerChute Business Edition from
          from http://www.apc.com/pcns                                                  http://www.apc.com/pcbe
10                                Smart-UPS SCL500 230 Vac Short-depth Rack-Mount
Operation
Using the display
   Main on/off
                                   This button is used to turn the UPS output power on and off.
   Quick status LEDs
                                   The online indicator illuminates green when UPS output is turned on and operating on
                                   AC power.
                                   The on-battery battery indicator illuminates orange and the unit will continue to emit a
                                   series of short beeps indicating that the UPS is operating on battery power.
                                   The indicator illuminates red when events occur.
                                   These indicators illuminate green when APCTM SmartConnect connection is okay.
                                   These indicators illuminate red when APCTM SmartConnect connection is cut-off
                                   These indicators illuminate green or orange when Network connection is okay.
                                   The battery error indicator illuminates red when the UPS battery does not pass self test
                                   and requires replacement of the entire UPS.
Configuration
General configuration settings
    Configuration settings may be changed at any time using the PowerChute software or SmartConnect Switch. This
    table provides a brief description of the general settings, for more detailed information on each of these parameters
    consult application note 80 at www.apc.com.
    Function           Factory Default        Options             Description
    High Transfer      253Vac                 253 Vac - 265Vac    To avoid unnecessary battery usage, set the transfer point
                                                                  higher if the AC voltage is chronically high and the
                                                                  connected equipment is known to work under this
                                                                  condition. The Power Quality setting will automatically
                                                                  change this setting.
    Low Transfer       207 Vac                195 Vac - 207 Vac   Set the transfer point lower if the AC voltage is chronically
                                                                  low and the connected equipment can tolerate this
                                                                  condition. This setting may also be adjusted using the
                                                                  power quality setting.
    Sensitivity        Normal                 • Normal            Select the level of sensitivity to power events that the UPS
                                              • Reduced           will tolerate.
                                              • Low                • Normal: The UPS will go on battery power more often to
                                                                     provide the cleanest power supply to the connected
                                                                     equipment.
                                                                   • Reduced: The connected equipment is sensitive to voltage
                                                                     fluctuations.
                                                                   • Low: The UPS will tolerate more fluctuations in power
                                                                     and will go on battery power less often.
                                                                  If the connected load is sensitive to power disturbances, set
                                                                  the sensitivity to Normal.
    Date of Last       Date set at factory.
    Battery
    Replacement
    Audible Alarm      On                     • On                Either the UPS will mute all audible alarms if it is set to Off
                                              • Off               by management software or the UPS will temporary mute
                                                                  audible alarms by pressing the power button less than 2
                                                                  seconds while operating on battery power.
                          Smart-UPS SCL500 230 Vac Short-depth Rack-Mount                                                           11
     Function           Factory Default    Options                Description
     Auto Self Test     On start-up and • Never                    The interval at which the UPS will execute a self-test.
                        every 14 days       • Start-up only
                        since the last test • Frequency of test
                                              (every 7 to 14 days)
     Install FW?        Don’t Install      • Next off (Updates Firmware update: this only appears when new firmware
                                             the UPS Firmware is available in the flash memory of the UPS and is ready
                                             next time that the to be installed
                                             UPS is turned off)
                                           • Now (Updates the
                                             UPS firmware
                                             immediately
                                             without
                                             interrupting
                                             operations)
                                           • Don't Install
     SmartConnect       Enable with        • Enable with control This will permit remote configuration changes.
     Control Switch     control            • Enable no control
                                           • Disable
Outlet group configuration settings
     The Main Outlet Group and the Controlled Outlet Group can be configured to independently turn off, turn on, shut
     down, or reboot connected equipment.
          • Turn off: Disconnect from power immediately and connect only with a manual command.
          • Turn on: Connect to power immediately.
          • Shutdown: Disconnect from power and automatically connect when AC power becomes available.
          • Reboot: Disconnect from power, wait for a specified amount of time, then connect to power.
     In addition, the Main Outlet Group and the Controlled Outlet Group can be configured to do the following:
          • Turn on or off in a specified sequence
          • Automatically turn off or shut down when various conditions occur
     Note: If the Main and Controlled Outlet Groups are not configured, all of the outlets on the unit will still provide
     battery back-up power.
     Note: The Main Outlet Group must be turned on for the Controlled Outlet Group to turn on.
     Function           Factory Default Options                   Description
     Name String        Outlet Groups 1    Edit these names using an external interface, such as the Network Management
     Outlet Group       &2                 Card Web interface.
     UPS Name String UPS Outlets
     Turn On Delay      0 sec              Set the value in       The amount of time the UPS or the Outlet Group will wait
                                           seconds                between receiving the command to turn on and the actual
                                                                  startup.
     Turn Off Delay     • 0 sec (Main      Set the value in       The amount of time the Outlet Group will wait between
                          Outlet Group)    seconds                receiving the command to turn off and the actual shut down.
                        • 90 sec
                          (Controlled
                          Outlet Groups)
     Reboot Duration    8 sec              Set the value in       The amount of time that the Outlet Group must remain off
                                           seconds                before it will restart.
     Minimum Return 0 sec                  Set the value in       The amount of battery runtime that must be available before
     Time                                  seconds                the Outlet Group will turn on.
12                                 Smart-UPS SCL500 230 Vac Short-depth Rack-Mount
Function          Factory Default Options                Description
Load Shed On      Disabled       • Shutdown with         When the unit switches to battery power, the UPS can
Battery                            Delay                 disconnect power to the Controlled Outlet Group to save
                                 • Shutdown              runtime.
                                   immediately           To configure this delay time, use the LOAD SHED TIME
                                 • Turn off              WHEN ON BATTERY setting.
                                   immediately
                                 • Turn off with delay
                                 • Disabled
Load Shed Time    Disabled       Set the value in        The amount of time the UPS will keep the Outlet Group on
when On Battery                  seconds                 when operating on battery.
Load Shed On      Disabled       • Shutdown with         When the battery runtime falls below the specified value,
Runtime                            delay                 the Outlet Group will turn off.
                                 • Shutdown              Configure this time using the LOAD S HED RUNTIME
                                   immediately           REMAINING setting.
                                 • Turn off
                                   immediately
                                 • Turn off with delay
                                 • Disabled
Load Shed On      Disabled       Set the value in        When the remaining runtime reaches this level, the Outlet
Runtime                          seconds                 Group will turn off.
Remaining
Load Shed on      Disabled       • Disabled              In the event of an overload (greater than 100% output
Overload                         • Enabled               power), the Outlet Group will immediately turn off to
                                                         conserve power for essential loads. The Outlet Group will
                                                         only turn on again with a manual command.
                    Smart-UPS SCL500 230 Vac Short-depth Rack-Mount                                                  13
Troubleshooting
     Problem and Possible Cause               Solution
     The UPS will not turn on or there is no output.
     The unit has not been turned on.          Press the ON key once to turn on the UPS.
     The UPS is not connected to AC power. Be sure the power cable is securely connected to the unit and to the AC power
                                           supply.
     The input circuit breaker has tripped.    Reduce the load on the UPS. Disconnect nonessential equipment and reset the
                                               circuit breaker.
     The unit shows very low or no input       Contact a qualified electrician to correct wiring issue.
     AC voltage.
     The battery connector plug is not         Be sure that all battery connections are secure.
     securely connected.
     There is an internal UPS error detected. Do not attempt to use the UPS. Turn off the UPS and unplug it from AC. Contact
                                              APC Customer Care Center for assistance.
     The unit cannot remotely turn on.         When network cable is disconnected with the UPS turned off and AC power
                                               connected the UPS will, after a while, automatically enter power saving mode.
                                               Tap the power button to wake up the UPS and enable its remote control feature.
     The UPS is operating on battery, while connected to input AC power.
     The input circuit breaker has tripped.    Reduce the load on the UPS. Disconnect nonessential equipment and reset the
                                               circuit breaker.
     There is very high, very low, or          Move the UPS to a different outlet on a different circuit. Test the input voltage
     distorted input line voltage.             with the AC voltage display. If acceptable to the connected equipment, reduce the
                                               UPS sensitivity.
     UPS is emitting intermittent beeps.
     The UPS is operating normally.            None. The UPS is helping protect the connected equipment.
     UPS does not provide expected backup time.
     The UPS battery is weak due to a recent Charge the battery. Batteries require recharging after extended outages and wear
     power outage or is near the end of its  out faster when put into service often or when operated at elevated temperatures.
     service life.                           If the battery is near the end of its service life, consider replacing the UPS even if
                                             the battery error indicator has not illuminated.
     The UPS is experiencing an overload       Check the UPS load display. Unplug unnecessary equipment, such as printers.
     condition.
     Display interface LEDs flash sequentially.
     The UPS has been shut down remotely None. The UPS will restart automatically when AC power is restored.
     through software or an optional
     accessory card.
     The Error LED is illuminated. The UPS displays an error message and emits a constant beeping sound.
     Internal UPS error detected.              Do not attempt to use the UPS. Turn the UPS off and contact the Customer Care
                                               Center immediately.
     The Battery Error icon is illuminated and the UPS beeps for one minute every five hours.
     The battery has a weak charge.            Allow the battery to recharge for at least four hours. Then, perform a self-test. If
                                               the problem persists after recharging, replace the entire UPS.
     The Battery Error icon is flashing and the UPS beeps once every 2 seconds.
     The battery is not properly connected.    Be sure that the battery connector is securely connected.
14                               Smart-UPS SCL500 230 Vac Short-depth Rack-Mount
Limited Factory Warranty
  Schneider Electric IT Corporation (SEIT), warrants its products to be free from defects in materials and
  workmanship for a period of five(5) years from the date of purchase. The SEIT obligation under this warranty is
  limited to repairing or replacing, at its own sole option, any such defective products. Repair or replacement of a
  defective product or parts thereof does not extend the original warranty period.
  This warranty applies only to the original purchaser who must have properly registered the product within 10 days
  of purchase. Products may be registered online at warranty.apc.com.
  SEIT shall not be liable under the warranty if its testing and examination disclose that the alleged defect in the
  product does not exist or was caused by end user’s or any third person’s misuse, negligence, improper installation,
  testing, operation or use of the product contrary to SEIT’s recommendations or specifications. Further, SEIT shall
  not be liable for defects resulting from: 1) unauthorized attempts to repair or modify the product, 2) incorrect or
  inadequate electrical voltage or connection, 3) inappropriate on site operation conditions, 4) Acts of God, 5)
  exposure to the elements, or 6) theft. In no event shall SEIT have any liability under this warranty for any product
  where the serial number has been altered, defaced, or removed.
  EXCEPT AS SET FORTH ABOVE, THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY
  OPERATION OF LAW OR OTHERWISE, APPLICABLE TO PRODUCTS SOLD, SERVICED OR
  FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH.
  SEIT DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY, SATISFACTION AND
  FITNESS FOR A PARTICULAR PURPOSE.
  SEIT EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY AND NO
  OBLIGATION OR LIABILITY WILL ARISE OUT OF, SEIT’S RENDERING OF TECHNICAL OR OTHER
  ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS.
  THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER
  WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE CONSTITUTE SEIT’S SOLE
  LIABILITY AND PURCHASER’S EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES.
  SEIT WARRANTIES EXTEND ONLY TO ORIGINAL PURCHASER AND ARE NOT EXTENDED TO ANY
  THIRD PARTIES.
  IN NO EVENT SHALL SEIT, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE LIABLE
  FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT
  OF THE USE, SERVICE OR INSTALLATION OF THE PRODUCTS, WHETHER SUCH DAMAGES ARISE
  IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT LIABILITY OR
  WHETHER SEIT HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH DAMAGES.
  SPECIFICALLY, SEIT IS NOT LIABLE FOR ANY COSTS, SUCH AS LOST PROFITS OR REVENUE,
  WHETHER DIRECT OR INDIRECT, LOSS OF EQUIPMENT, LOSS OF USE OF EQUIPMENT, LOSS OF
  SOFTWARE, LOSS OF DATA, COSTS OF SUBSTITUANTS, CLAIMS BY THIRD PARTIES, OR
  OTHERWISE.
  NOTHING IN THIS LIMITED WARRANTY SHALL SEEK TO EXCLUDE OR LIMIT SEIT’S LIABILITY
  FOR DEATH OR PERSONAL INJURY RESULTING FROM ITS NEGLIGENCE OR ITS FRAUDULENT
  MISREPRESENTATION OF TO THE EXTENT THAT IT CANNOT BE EXCLUDED OR LIMITED BY
  APPLICABLE LAW.
  To obtain service under warranty you must obtain a Returned Material Authorization (RMA) number from
  customer support. Customers with warranty claims issues may access the SEIT worldwide customer support
  network through the SEIT Web site: www.apc.com. Select your country from the country selection drop down
  menu. Open the Support tab at the top of the web page to obtain information for customer support in your region.
  Products must be returned with transportation charges prepaid and must be accompanied by a brief description of
  the problem encountered and proof of date and place of purchase.
                        Smart-UPS SCL500 230 Vac Short-depth Rack-Mount                                                  15
Transport the Unit
     1. Shut down and disconnect all equipment.
     2. Disconnect the unit from utility power.
     3. Disconnect all internal and external batteries (if applicable).
     4. Follow the shipping instructions outlined in the Service section of this manual.
Service
     If the unit requires service, do not return it to the dealer. Follow these steps:
     1. Review the Troubleshooting section of the manual to eliminate common problems.
     2. If the problem persists, contact APC Customer Support through the APC web site, www.apc.com.
                 a. Note the model number and serial number and the date of purchase. The model and serial numbers
                    are located on the rear panel of the unit and are available through the LCD interface on select
                    models.
                 b. Call APC Support and a technician will attempt to solve the problem over the phone. If this is not
                    possible, the technician will issue a Returned Material Authorization Number (RMA#).
                 c. If the unit is under warranty, it will be repaired or replaced at no cost.
                 d. Service procedures and returns may vary internationally. Refer to the APC web site for country
                    specific instructions.
     3. Pack the unit properly to avoid damage in transit. Never use foam beads for packaging. Damage sustained in
        transit is not covered under warranty.
     4. Before shipping, always disconnect all battery modules in a UPS or external battery pack.
     5. Write the RMA# provided by Customer Support on the outside of the package.
     6. Return the unit by insured, prepaid carrier to the address provided by Customer Support.
16                                  Smart-UPS SCL500 230 Vac Short-depth Rack-Mount
                    APC by Schneider Electric
                   Worldwide Customer Support
 Customer support for this or any other APC by Schneider Electric product is available at no charge in any of the
 following ways:
     • Visit the APC by Schneider Electric web site to access documents in the APC by Schneider Electric
       Knowledge Base and to submit customer support requests.
          – www.apc.com (Corporate Headquarters)
            Connect to localized APC by Schneider Electric web sites for specific countries, each of which
            provides customer support information.
          – www.apc.com/support/
            Global support searching APC by Schneider Electric Knowledge Base and using e-support.
     • Contact the APC by Schneider Electric Customer Support Center by telephone or e-mail.
          – Local, country specific centers: go to www.apc.com/support/contact for contact information.
          – For information on how to obtain local customer support, contact the APC by Schneider Electric
            representative or other distributor from whom you purchased your APC by Schneider Electric product.
  © 2022 APC by Schneider Electric. APC, the APC logo, Smart-UPS, SmartConnect and PowerChute are
   owned by Schneider Electric Industries S.A.S. or their affiliated companies. All other trademarks are
                                  property of their respective owners.
EN 990-91308A                                                                                          04/2022