BASIC ENGINATOR SPECIFICATIONS
AIR CLEANER – Two stage, dry panel type with rain shield and service indicator. Engine mounted.
BARRING DEVICE – Manual.
VGF24GL/GLD
BASE – Engine, generator and radiator or heat exchanger are mounted and aligned on a welded steel,
wide flange base, designed for solid mounting on an inertia block, with standard through-base holes
for lifting.
BREATHER – Closed system.
CONNECTING RODS – Drop forged alloy steel, angle split, serrated joint, oil jet piston pin lubrication.
COOLING SYSTEM – Choice of mounted radiator with pusher fan, core guard and duct adaptor, heat
VGF Series Gas Enginator
exchanger with mounted surge tank or flanged connections for remote radiator cooling. Generating System
CRANKCASE – Alloy cast iron, fully ribbed, integral with cylinder frame.
295 - 425 kW
CRANKSHAFT – Drop forged alloy steel with induction hardened journals, dynamically balanced and
fully counterweighted. Viscous vibration dampener.
CYLINDER HEADS – Individual, interchangeable valve-in-head type with deep section
alloy casting. Two hard-faced intake and two hard-faced exhaust valves per cylinder.
Replaceable intake and exhaust valve seats. Mechanical valve lifters with pivoted roller
followers.
CYLINDERS – Removable wet type liners of centrifugally cast alloy iron.
ENGINE PROTECTION SHUTDOWN CONTACTS – High water temperature, low oil
pressure, and overspeed.
EXHAUST – Water-cooled, cast iron exhaust manifold. Single vertical flexible stainless
steel exhaust connection with ANSI 125# 8″ oulet flange.
FUEL SYSTEM – Natural gas carburetor, gas pressure regulator, and 24V DC gas solenoid
valve (shipped loose). Pressure required: GL models, 25 – 50 psig; GLD models, 8″ – 20″
W.C.
GENERATOR – Open, drip-proof, direct connected, synchronous, fan cooled, AC revolving field type, 2/
3 pitch, single bearing generator with PMG brushless exciter for 300% short circuit sustain
(250% for 50 Hz) and motor starting. TIF and Deviation Factor within NEMA MG–1.22. Voltage: 480/
277, 3 phase, 12 wire Wye, 60 Hz, and 400/230, 3 phase, 12 wire Wye, 50 Hz. Temperature rise
Enginator shown with options.
within NEMA 105° C for continuous duty, within NEMA 130° C for standby duty. Voltage regulation is
± 0.5%. All generators are rated at 0.8 power factor, are mounted on the engine flywheel housing,
and have multiple steel disc flexible coupling drive. All continuous power gensets have 10% overload Model VGF24GL/GLD
capability. Turbocharged and Intercooled, Lean Combus-
tion Gas Fueled Enginator
GOVERNOR – Woodward model EG3P electric acuator (mounted) and magnetic pickup (mounted).
IGNITION – Waukesha Custom Engine Control electronic ignition system with coils, cables, hall effect
pickup and spark plugs. Non-shielded. 24 V DC power required.
INTERCOOLER – Air-to-water.
INSTRUMENT PANEL – Engine mounted, includes water temperature, oil pressure, intake manifold SPECIFICATIONS
temperature and intake manifold pressure gauges, and emergency stop pushbutton.
JUNCTION BOXES – Separate AC & DC junction boxes for engine wiring and external connections. Waukesha Engine Jacket Water
KNOCK DETECTION MODULE (KDM) – Electronic detonation protection system. Includes engine H24GL/GLD Capacity
mounted sensors, wiring and KDM. Meets CSA Class I, Division 2, Group D hazardous location Cylinders 20 gal.
requirements. Standard on GL and GLD engines with 11:1 compression ratio. Inline 8 (75 L)
LUBRICATION SYSTEM – Gear type pump, full flow spin-on filters and industrial type oil pan. Piston Displacement Starting System
Engine mounted plate type oil cooler. 24V DC Electric
1462 cu. in.
PAINT – Oilfield orange. (24 L) Fuel LHV
PISTONS – Aluminum alloy, three ring, with combustion bowl. Oil jet cooled with full floating piston pin. 900 Btu/ft3
Bore & Stroke
11:1 compression ratio. (33.5 J/cm3)
5.98″ x 6.5″
STARTING SYSTEM – 24 V DC starting motor. Crank termination switch, (shipped loose).
(152 x 165 mm) Lube Oil Capacity
TURBOCHARGER – Dry-type with wastegate. 56 gal.
Compression Ratio
VOLTAGE REGULATOR – Automatic type. (212 L)
11:1
WATER CIRCULATING SYSTEM
Auxiliary Circuit – Gear driven pump for intercooler and oil cooler. Inlet temperature of 130° F (54°
C) for all models.
Jacket Water Circuit – 180° – 190° F (82° – 88° C) thermostatic temperature regulation.
Gear-driven pump.
PERFORMANCE DATA: VGF24GL/GLD GAS ENGINATOR GENERATING SYSTEM
CONTINUOUS POWER* STANDBY POWER
HEAT EXCHANGER COOLING 1800 rpm 1500 rpm 1800 rpm 1500 rpm
Intercooler Water: 130°F (54°C)
60 Hz 50 Hz 60 Hz 50 Hz
kW RATING 375 310 425 355
Fuel Consumption x 1000 Btu/h (kW) 3752 (1100) 3057 (896) 4235 (1241) 3455 (1013)
Jacket Water x 1000 Btu/h (kW) 931 (273) 784 (230) 1013 (297) 858 (251)
Intercooler x 1000 Btu/h (kW) 201 (59) 130 (38) 252 (74) 177 (52)
Lube Oil x 1000 Btu/h (kW) 155 (45) 124 (36) 160 (47) 128 (38)
Heat Radiated x 1000 Btu/h (kW) 144 (42) 140 (41) 188 (55) 139 (41)
Exhaust Heat** x 1000 Btu/h (kW) 1042 (305) 821 (241) 1172 (343) 942 (276)
Exhaust Flow lb/h (kg/h) 4835 (2193) 3935 (1785) 5420 (2459) 4410 (2000)
Exhaust Temperature °F (°C) 857 (458) 825 (441) 845 (452) 828 (442)
Induction Air Flow scfm (m3/min) 1080 (31) 885 (25) 1215 (34) 990 (28)
CONTINUOUS POWER* STANDBY POWER
WATER CONNECTION COOLING 1800 rpm 1500 rpm 1800 rpm 1500 rpm
Intercooler Water: 130°F (54°C)
60 Hz 50 Hz 60 Hz 50 Hz
kW RATING 375 310 425 355
Fuel Consumption x 1000 Btu/h (kW) 3752 (1100) 3057 (896) 4235 (1241) 3455 (1013)
Jacket Water x 1000 Btu/h (kW) 931 (273) 784 (230) 1013 (297) 858 (251)
Intercooler x 1000 Btu/h (kW) 201 (59) 130 (38) 252 (74) 177 (52)
Lube Oil x 1000 Btu/h (kW) 155 (45) 124 (36) 160 (47) 128 (38)
Heat Radiated x 1000 Btu/h (kW) 144 (42) 140 (41) 188 (55) 139 (41)
Exhaust Heat** x 1000 Btu/h (kW) 1042 (305) 821 (241) 1172 (343) 942 (276)
Exhaust Flow lb/h (kg/h) 4835 (2193) 3935 (1785) 5420 (2459) 4410 (2000)
Exhaust Temperature °F (°C) 857 (458) 825 (441) 845 (452) 828 (442)
Induction Air Flow scfm (m3/min) 1080 (31) 885 (25) 1215 (34) 990 (28)
CONTINUOUS POWER* STANDBY POWER
RADIATOR COOLING - MOUNTED 1800 rpm 1500 rpm 1800 rpm 1500 rpm
Intercooler Water: 130°F (54°C)
60 Hz 50 Hz 60 Hz 50 Hz
kW RATING 350 295 405 345
Fuel Consumption x 1000 Btu/h (kW) 3752 (1100) 3057 (896) 4235 (1241) 3455 (1013)
Jacket Water x 1000 Btu/h (kW) 931 (273) 784 (230) 1013 (297) 858 (251)
Intercooler x 1000 Btu/h (kW) 201 (59) 130 (38) 252 (74) 177 (52)
Lube Oil x 1000 Btu/h (kW) 155 (45) 124 (36) 160 (47) 128 (38)
Heat Radiated x 1000 Btu/h (kW) 165 (48) 153 (45) 193 (56) 135 (39)
Exhaust Heat** x 1000 Btu/h (kW) 1042 (305) 821 (241) 1172 (343) 942 (276)
Exhaust Flow lb/h (kg/h) 4835 (2193) 3935 (1785) 5420 (2359) 4410 (2000)
Exhaust Temperature °F (°C) 857 (458) 825 (441) 845 (452) 828 (442)
Induction Air Flow scfm (m3/min) 1080 (31) 885 (25) 1215 (34) 990 (28)
Radiator Air Flow scfm (m3/min) 48000 (1359) 40000 (1133) 48000 (1359) 40000 (1133)
Typical heat balance data is shown. Consult factory for guaranteed data.
*Continuous Power Rating: The highest electrical power output of the Enginator available for an unlimited number of hours per year, less maintenance. It is permissible to operate the
Enginator with up to 10% overload for two hours in each 24 hour period.
Standby Power Rating: This rating applies to those systems used as a secondary source of electrical power. This rating is the electrical power output of the Enginator (no overload) 24
hours a day, for the duration of the primary power source outage.
Rating Standard: The Waukesha Enginator power rating descriptions are in accordance to ISO 8528, DIN6271 and BS5514. It is also valid for ISO 3046/1-1986 with an engine mechanical
efficiency of 90% and auxiliary water temperature Tcra (clause 10.0) is limited to ± 10° F (5° C).
**Heat rejection based on cooling exhaust gas to 85° F (29° C).
Cooling
Equipment L in (mm) W in (mm) H in (mm) Avg. Wt. lb (kg)
Heat Exchanger 142 (3610) 54 (1370) 79 (2000) 11100 (5030)
Water Cooler 132 (3350) 54 (1370) 79 (2000) 10600 (4810)
Radiator 176 (4470) 78 (1981) 100 (2540) 12300 (5580)
WAUKESHA POWER SYSTEMS Consult your local Waukesha Distributor for system
WAUKESHA ENGINE application assistance. The manufacturer reserves the right
to change or modify without notice, the design or equipment
DRESSER, INC.
specifications as herein set forth without incurring any
1101 West St. Paul Avenue obligation either with respect to equipment previously sold or
Waukesha, WI 53188-4999 in the process of construction except where otherwise
Phone: (262) 547-3311 Fax: (262) 549-2795 specifically guaranteed by the manufacturer.
waukeshaengine.dresser.com
Bulletin 8068 0506
Waukesha, VGF and Enginator are trademarks/registered trademarks of Waukesha Engine, Dresser, Inc.