HT APFC Relay
HT APFC Relay
MODEL- GB-VI-3L-12
-1-
IMPORTANT
Read the manual carefully before the device is installed.
Connect the C.T. when the relay is in OFF condition. Use suitable size cable for the C.T.
-2-
Contents
Features 04
Specifications
Connector Details 06
Installation Scheme 07
Display 12
EDIT PARAMTERS
Edit Parameters General and IO 17
Edit Parameters System 19
Edit Parameters Fault 21
Edit Parameters Step 27
Edit Parameters Communication 31
Edit Utilization Counter 32
Auto Operation 33
Manual Operation 34
Installation Scheme 07
Fault Finding Guidelines 38
-3-
FEATURES:
-4-
SPECIFICATIONS:
Humidity: 0 to 98%.
Terminal and Connector arrangement is at the Back and Bottom side of the instrument. Terminals provided are plug in
type connectors. While installation/dismantling the unit, the terminals should be removed by plugging them out.
-5-
CONNECTOR DETAILS:
L1 L2 Fuse
0.5 A
b
com B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 B11 B12
-6-
INSTALLATION SCHEMES:
HT SIDE
SCEME 1
T/F
LT SIDE
LOAD
CT
LOAD
CAP APFC
CT
This scheme is considered for the LT consumers of electricity where the metering is carried out on LT side.
This is more beneficial when the user is interested in maintaining the Power Factor on the secondary side of
the transformer.
As per this scheme the Voltage feedback is taken from the LT bus & C.T. sense is taken from output of
Transformer in such a way that the C.T. senses the Load as well as Capacitor Current.
Capacitor current feedback is taken from all the capacitor banks that are controlled by i.e. the
GB-VI-3L-12 capacitor feedback C.T. senses the overall current of the capacitor banks in the circuit.
-7-
Scheme-2: C.T. & P.T. Sense from HT side.
HT SIDE SCEME 2
LOAD
CT
PT
T/F
LT SIDE
LOAD
CAP APFC
CT
This scheme is considered for LT consumers of electricity, where the metering is carried out on HT side.
In this scheme, the compensation is also against magnetizing current of the transformer (i.e. No Load
Compensation of Transformer). Hence the consumer will get the results with more accuracy.
In this scheme, the load sensing of C.T. and the voltage feedback of P.T. is taken from the primary side of
the transformer (i.e. HT Side).
Capacitor current feedback is taken from all the capacitor banks that are controlled by i.e. the
GB-VI-3L-12 capacitor feedback C.T. senses the overall current of the capacitor banks in the circuit.
-8-
Scheme-3: Usage with Mains/Generator changeover system & P.T. Sense from LT side
Figure.1 Figure.2
LT SIDE LT SIDE
LOAD CT
SUMMATION
CT
LOAD LOAD
APFC APFC
CAP CAP
CT CT
In case of system with dual sources of supply, i.e. Supply grid and Generator. Under such case, the system
can be shifted between the two sources. For every source there may be different requirements of maximum
loading on sources as well as requirements of different P.F. target settings.
In this scheme, a summation C.T. is used as shown in Figure.1 or C.T. must be used at common bus of
Mains and Generator supply as shown in Figure.2. The changeover between the two sources is indicated to
through its GB-VI-3L-12 Auxiliary Input port.
Using this scheme, user has an advantage of using single P.F. improvement system with either of source in
operation.
Capacitor current feedback is taken from all the capacitor banks that are controlled by i.e. the
GB-VI-3L-12 capacitor feedback C.T. senses the overall current of the capacitor banks in the circuit.
-9-
CONTROL WIRING DIAGRAM:
- 10 -
COMMUNICATION PORT DIAGRAM:
5 4 3 2 1
6 7 8 9
1 NC
2 RXD TXD
3 TXD RXD
4
5 GND GND
6
7
8
9 NC
Communication Terminals: GB-VI-3L-08 has one serial communication port that is on front D type
connector. The default is RS-232.
- 11 -
RS-485 serial communication 9 pin D-Connector:
5 4 3 2 1
6 7 8 9
1 GND VCC
2 NC -
3 NC +
4 - 485 GND
5 + 485
6
7
8
9 NC
- 12 -
DISPLAY:
The first line of LCD Display (Default) condition shows ‘’ PF = ‘’ i.e. Power factor sensed from the load
sensing CT i.e. the Transformer / Supply grid. Further, screen also shows “IND” for Inductive Power Factor
& “CAP” for Capacitive Power Factor. Controller works with two set points. One group of set points is for
Transformer/Supply grid and other group of set points is for generator operation. Transformer/Supply grid
operation is indicated by “↑” and generator operation is indicated by “↓”.Then it shows the operation mode
i.e. “A “ for auto mode and “M” for Manual mode. Last digit of first line shows “OK” (blinking) indicates status
of the system, healthy or faulty.
The bottom line of the LCD display shows capacitor bank status which is also shown by LEDs for each step
= This symbol indicates that bank is declared as fixed bank and is ON.
= This symbol indicates that output is in discharging mode (blinking red LED).
There are number of options on screen that shows various parameters that are measured or derived. These
various options can be used to display parameters by pressing the Scroll UP and DOWN keys.
To observing other system related parameters Scroll up/down keys and then pressing ENT key. To exit from
a sub-menu press MODE. Following is the sequence of the parameters displayed on LCD screen.
1. Display Overall Values: Overall values give overall system parameters are as follows:
2. Display Per-Phase RMS: Per Phase RMS values for the instantaneous parameters like:
- 13 -
3. Display Power: It gives per phase values of parameters like:
5. Display Harmonics: This gives per phase Voltage, Current, Neutral current & Capacitor per phase
current THD as well as odd harmonics coefficients up-to 15th.
1) Vr-THD-F 6) Ib-THD-F
000.0% 000.0%
2) Vy-THD-F 7) CCr-THD-F
000.0% 000.0%
3) Vb-THD-F 8) CCy-THD-F
000.0% 000.0%
4) Ir-THD-F 9) CCb-THD-F
000.0% 000.0%
5) Iy-THD-F
000.0%
6. Display Step KVAR: It gives the values of KVAR that is measured for every output step.
1) Step[01] KVAr
0300
2) Step[02] KVAr
0600
UPTO
12) Step[12] KVAr
0600
- 14 -
7. Display Aux-Function: It displays auxiliary functions like internal and external temperature.
8. Time: 02:02:08: It displays Date and Time that is set on internal RTC.
Date: 10/10/18
Harmonic data of various current & voltage parameters can be viewed by pressing ENT on the respective
parameter screen of the Harmonics menu. Following are the sub-menus giving the harmonic data of voltage, current
& capacitor current for each phase.
V-Harmonics:
1) Vr harmonics 7) Vr harmonics 13) Vy harmonics 19) Vb harmonics
03rd: 00.0% 15th: 00.0% 13th: 00.0% 11th: 00.0%
2) Vr harmonics 8) Vy harmonics 14) Vy harmonics 20) Vb harmonics
05th: 00.0% 03rd: 00.0% 15th: 00.0% 13th: 00.0%
3) Vr harmonics 9) Vy harmonics 15) Vb harmonics 21) Vb harmonics
07th: 00.0% 05th: 00.0% 03rd: 00.0% 15th: 00.0%
4) Vr harmonics 10) Vy harmonics 16) Vb harmonics
09th: 00.0% 07th: 00.0% 05th: 00.0%
5) Vr harmonics 11) Vy harmonics 17) Vb harmonics
11th: 00.0% 09th: 00.0% 07th: 00.0%
6) Vr harmonics 12) Vy harmonics 18) Vb harmonics
13th: 00.0% 11th: 00.0% 09th: 00.0%
I-Harmonics:
1) Ir harmonics 8) Iy harmonics 15) Ib harmonics
03rd: 00.0% 03rd: 00.0% 03rd: 00.0%
2) Ir harmonics 9) Iy harmonics 16) Ib harmonics
05th: 00.0% 05th: 00.0% 05th: 00.0%
3) Ir harmonics 10) Iy harmonics 17) Ib harmonics
07th: 00.0% 07th: 00.0% 07th: 00.0%
4) Ir harmonics 11) Iy harmonics 18) Ib harmonics
09th: 00.0% 09th: 00.0% 09th: 00.0%
5) Ir harmonics 12) Iy harmonics 19) Ib harmonics
11th: 00.0% 11th: 00.0% 11th: 00.0%
6) Ir harmonics 13) Iy harmonics 20) Ib harmonics
13th: 00.0% 13th: 00.0% 13th: 00.0%
7) Ir harmonics 14) Iy harmonics 21) Ib harmonics
15th: 00.0% 15th: 00.0% 15th: 00.0%
- 15 -
CC-Harmonics:
EDIT PARAMETERS
AUTO OPERATION
MANUAL OPERATION
(During commissioning edit the required parameters by setting in the EDIT PARAMETER mode, then follow
the AUTO or MANUAL mode selection).
EDIT PARAMETERS:
Select
1.EDIT
PARAMETERS
The Editing of various system parameter settings can be carried out by using UP and DOWN keys & also by
selecting various options, which can be edited as per the requirement. For saving/Setting the editing
parameters choose one of the options and press ENT to sub menus of the specific types. The details of sub
menus are given below. Coming out of menu/sub-menu press MODE key once.
- 16 -
To store edited parameters permanently, press SAVE when either in EDIT Parameter type or submenu areas.
To come out of EDIT Parameters without saving the changes, press MODE key again.
(Note: During Editing if the key is not pressed within a minute time span (60 sec) then default screen will
appear and the changes done will get discarded.)
Password
Disable: 0
Password
Enable: 1
2. Change Password: The 3 digit number that can act like a password can be changed by changing the value
in this parameter.
2. Load Default: There are number of parameters that are already set during the manufacturing
process. The settings can be changed as the customer’s requirement and for retrieval
the factory settings the load default can be set to “Yes” and then by pressing the
“SAVE” command.
Load Default
No: 0
Load Default
Yes: 1
4. THD To Display: It can be helpful for selecting the type of THD to be displayed for Voltage, Current
and Capacitor Current. R-THD means RMS values & F-THD means Fundamental values.
THD TO DISPLAY
R-THD: 0
THD TO DISPLAY
F-THD: 1
RESET ENERGY
No: 0
RESET ENERGY
Yes: 1
- 17 -
RESET DATA?
No : 0
RESET DATA?
Yes : 1
2. External P.T. Ratio: For rated system voltages other than 110 Volts, a external P.T. can be used. The P.T.
ratio of secondary to primary has to be edited. Without external P.T. the ratio is 0001.0:1, e.g. With 11kV
system with 110V secondary P.T., this ratio is “100.00”.
EXT-PT Ratio
0100.0:1
3. Current C.T. Primary Mains: GB-VI-3L-12 Relay displays the primary current rating of the connected load
side C.T.
CUR CT Primary
Mains: 800
5. Capacitor Current C.T. Primary Mains: This parameter will define the capacitor current feedback
. C.T primary ratings in terms of Amperes.
7. P.F. Upper Limit: Mains : Upper target P.F. setting. The limit setting can be selected as
Inductive by setting ‘1’ or Capacitive by setting ‘0’.
PF Up Lim : Mains
[Cap :0] : 0. 999
PF Up Lim : Mains
Cap 0 : [0. 999]
8. P.F. Lower Limit: Mains : Lower target P.F. setting. The limit setting can be selected as
Inductive by setting ‘1’ or Capacitive by setting ‘0’.
- 18 -
PF Up Lim : Mains
[Cap :0] : 0. 999
PF Up Lim : Mains
Cap 0 : [0. 999]
9. P.F. Upper Limit : GEN : Upper target P.F. setting. The limit setting can be selected as
Inductive by setting ‘1’ or Capacitive by setting ‘0’.
PF Up Lim :GEN
[Cap :0] : 0. 820
PF Up Lim : GEN
Cap 0 : [0. 820]
10. P.F. Lower Limit: GEN : Lower target P.F. setting. The limit setting can be selected as Inductive
by setting ‘1’ or Capacitive by setting ‘0’.
PF Up Lim :GEN
[Cap :0] : 0. 820
PF Up Lim : GEN
Cap 0 : [0. 820]
Mains Generator
Mains: 0
Mains Generator
Generator: 1
- 19 -
EDIT PARAMETERS FAULT:
1. Over Voltage Fault: During Over Voltage conditions, the action taken by is indicated GB-VI-3L-12 as
follows. The options displayed on the screen are
Over Vol Fault
Disable: 0
Over Vol Fault
Indicate: 1
Over Vol Fault
Off Step: 2
Over Vol Fault
Off Fix: 3
0: Disable: Display screen will not indicate the fault nor action will be taken by
the relay.
1: Indicate: Only the Fault will be displayed by the Relay.
2: Off Step: In this option, Variable Banks will be switched OFF step by step with
1sec step delay by the relay.
3: Off Fix: The fixed banks will be switched OFF along with Variable Banks, if the
fixed banks are controlled by GB-VI-3L-12
4: Fast Off: Variable and Fixed banks are turned Off simultaneously.
2. Over Voltage Limit (%): The parameter defines the level of over voltage at which fault would be detected.
Over Voltage Limit (%): 115
3. Over Voltage Resume (%): The parameter defines the level of over voltage at which fault would be reset
and GB-VI-3L-08 operation will resume.
4. Under Voltage Fault: During Under Voltage conditions, the action taken by GB-VI-3L-12 is indicated as
follows. The options displayed on the screen are
- 20 -
0: Disable: Display screen will not indicate the fault nor action will be taken by
the relay.
1: Indicate: Only the Fault will be displayed by the Relay.
2: Off Step: In this option, Variable Banks will be switched OFF step by step with
1sec step delay by the relay.
3: Off Fix: The fixed banks will be switched OFF along with Variable Banks, if the
fixed banks are controlled by GB-VI-3L-12.
4: Fast Off: Variable and Fixed banks are turned Off simultaneously.
5. Under Voltage Limit (%): The parameter defines the level of under voltage at which fault would be
detected.
Under Voltage Limit (%): 115
6. Under Voltage Resume (%) : The parameter defines the level of under voltage at which fault would be reset
and operation GB-VI-3L-12 will resume
7. Over Load Fault: During Over load conditions, the action taken by is indicated GB-VI-3L-12 as
follows. The options displayed on the screen are
Over Load Fault
Disable: 0
Over Load Fault
Indicate :1
Over Load Fault
Off Step :2
Over Load Fault
Off Fix :3
Over Load Fault
Fast Off: 4
0: Disable: Display screen will not indicate the fault nor action will be taken by
the relay.
1: Indicate: Only the Fault will be displayed by the Relay.
2: Off Step: In this option, Variable Banks will be switched OFF step by step with 1sec
step delay by the relay.
3: Off Fix: The fixed banks will be switched OFF along with Variable Banks,
if the fixed banks are controlled by GB-VI-3L-12.
4: Fast Off: Variable and Fixed banks are turned Off simultaneously.
8. Over Load Cur Limit (%): The parameter defines the level of Over load at which fault would be
detected.
Over Load Limit (%): 115
9. Over Load Resume (%): The parameter defines the level of Over Load at which fault would be reset and
GB-VI-3L-12 operation will resume.
10. Under Load Fault: During Under load conditions, the action taken by is indicated GB-VI-3L-12 as follows.
The options displayed on the screen are
- 21 -
Under Load Fault
Disable: 0
0: Disable: Display screen will not indicate the fault nor action will be taken by
the relay.
1: Indicate: Only the Fault will be displayed by the Relay.
2: Off Step: In this option, Variable Banks will be switched OFF step by step with
1 sec step delay by the relay.
3: Off Fix: The fixed banks will be switched OFF along with Variable Banks, if the
fixed banks are controlled by GB-VI-3L-12
4: Fast Off: Variable and Fixed banks are turned Off simultaneously.
11. Under Load Cur Limit (%): The parameter defines the level of Under load at which fault would be
detected.
Under Load Limit (%): 115
12. Under Load CUR Resume (%): The parameter defines the level of Under Load at which fault would be
reset and GB-VI-3L-12 operations will resume.
13. Load Unbalance Fault: The limits defined here are in % of maximum of the three phase source
current compared with the minimum of three phase source current.
Load Unbalance
Resume (%) : 040
16. Over Capacitor Current Fault: This fault is capacitor Over current for the given KVAR connected.
17. Over Capacitor Current Limit (%): The parameter defines the level of Over Capacitor Current at
which fault would be detected.
18. Over Capacitor Current Resume (%):The parameter defines the level of Over Capacitor Current at
which fault would be reset and GB-VI-3L-08 operation will resume.
- 23 -
21. Temperature Fault: GB-VI-3L-12 is capable of sensing the temperature inside its own cabinet. In case of
excessive limit of the temperature, the unit can be used to disable all the
output commands to the capacitor banks. Upper limit is for tripping and lower
limit is for normal operation.
Temperature Flt
Disable: 0
Temperature Flt
Indicate :1
Temperature Flt
Off Step :2
Temperature Flt
Off Fix: 3
Temperature Flt
Fast Off: 4
0: Disable: Display screen will not indicate the fault nor action will be taken by
the relay.
1: Indicate: Only the Fault will be displayed by the Relay.
2: Off Step: In this option, Variable Banks will be switched OFF step by step
with 1sec step delay by the relay.
3: Off Fix: The fixed banks will be switched OFF along with Variable Banks, if
the fixed banks are controlled by GB-VI-3L-12
4: Fast Off: Variable and Fixed banks are turned Off simultaneously.
Temperature Deg C
L .Limit: 50
Temperature Deg C
U.Limit: 60
Temperature
U .Limit : 060 To 100 Deg C
24. Capacitor Current THD Fault: The controller can sense the THD value of the capacitor current
and in case of THD exceeding can give this fault.
27. Step Health Check: GB-VI-3L-12 carries out on line monitoring of the KVAr values of every step when the
step is put in the circuit. In case the tolerance limit defined here is exceeded, that
specific bank is declared faulty.
29. Out Of Banks Fault: In case GB-VI-3L-12 after switching on all the possible capacitor banks finds,
that for next two consecutive correction cycles, P.F. is lower than the P.F. lower limit, then this fault is indicated if
enable option is selected. But this fault does not switch off capacitor banks
Steps Connected: 12
2. Default Mode: US-HT-5004can be used in Auto or Manual mode of operation. Usually it is Auto mode but
in case, it is operated in manual mode as normal default, the setting ‘1’ here will do the same. In case of
power failure and again power is resumed the operation mode will be selected before the failure.
- 25 -
3. Compensation . Method
Fine : 1
Fair : 2
Max : 3
R - ph : 4
Y - ph : 5
B - ph : 6
Mean : 7
4. Compensation KVAR: In auto mode, the KVAR to be inserted in the system can be calculated by
two methods.
Compensation KVAR
Instant: 0
Compensation KVAR
Mean: 1
5. Capacitor Bank Voltage: Line to line value of Capacitor bank voltage is defined here. i.e. it defines the
Voltage value at the defined KVAR.
6. Correction Time: Correction time is the time during which there is total inactivity (except
measurement) as far as capacitor switching is concerned
i.e. it is the time period between the two successive KVAR compensations.
Correction Time
Seconds: 010
7. Discharge Time: Time defined here is the time for discharge of the capacitors to a level, so that they
can be turned ON again. Discharge time should be always kept at 1 minute.
Discharge Time
Seconds: 060
8. Step Response: Step Response defines the time after which the KVAR of any step should be measured
when the step turns on.
Step Response
Cycles: 00045
9. Fix-Bank Setting: By using the keys “ENT”, “UP” and “DOWN”, the fixed banks can be defined for
specific output of GB-VI-3L-12. Fixed banks are the banks that are kept ON at minimum loading or for
no-load compensation of transformer.
1) UNEQUAL : If the capacitor banks does not having a definite ratio. Un-Equal banks
option to be selected.
Correction Type
Un-Equal : 1
11. Ext-Fixed Bank KVAR: In case APFC system uses some capacitor bank as fixed step and not
controlled by GB-VI-3L-12, then it should be specified here
Ext Fix Bank
KVAr: 010
1) UNIT ID: Value of Unit ID can be 0000 to 9999. This ID is used for serial communication on RS-232
protocol.
UNIT ID: 0000
TIME
14: 47:57
5) Initialization of RTC: It initializes the real time clock by defining ‘Yes’. Press SAVE button after
setting this parameter
Initialize RTC
- 27 -
No: 0
Initialize RTC
Yes:1
6) COM2 Function:
Disable : 0
ASCII : 1
RTU : 2
1. Utilization Bank Counter: The value on the screen indicates the total switching of a single step capacitor
bank. These counters are used for equal utilization for the Banks of same
KVAR value. This improves the life of switch and capacitor.
For the Banks with the same KVAR value, this value is used for FIFO
operation. The counter values are for indication purpose only and are not
editable.
Utilization Cntr
Bank [1] : 000006
Utilization Cntr
2. Clear Bank Counter: In case of APFC system, if a capacitor bank or the associated equipment’s
(Contactors etc) are replaced, then the corresponding step utilization counter value can be set to zero so that the
replaced bank can be operational in the system. If GB-VI-3L-12 is replaced with some other new system, these
counters can all be reset to zero by setting Yes option here.
Clr Bank [1] Cntr
No : 0
Clr Bank [1] Cntr
Yes : 1
.
.
Clr Bank [8] Cntr
No : 0
Clr Bank [8] Cntr
Yes: 1
AUTO OPERATION:
Select
2.Auto Operation
Press “ENT” button on the screen that will operate the GB-VI-3L-12 in Auto mode. The set mode will continue
till alternate operation mode is selected or unit is put to Power down condition.
In auto mode operations, the GB-VI-3L-12 will switch the capacitor bank ON/OFF as per the load requirement.
Here GB-VI-3L-12 calculates the KVAR compensation value and selects the closest equivalent capacitor
combination and the same are activated in the system so that the P.F. is maintained at the desired level.
Relay calculates internally C/K ratio for correct compensation. On the default display, the status of capacitor
bank is seen as activated by GB-VI-3L-12.
While performing the compensation, GB-VI-3L-12 can even calculate the KVAR of every step that operates in
the system. This enables on line Health-monitoring of every capacitor bank operating in the circuit. assumes
that during the switching of contactor, spikes currents are generated. Hence to avoid a major spike current,
the banks are switched ON after a safe time delay. Switching time is inbuilt in the relay.
MANUAL OPERATION:
Select
3.Manual Operation
Press “ENT” button on the screen that will operate the GB-VI-3L-12 in Manual mode. The set mode will
continue unless it is purposely changed or Power is down.
- 29 -
For Testing banks with manual ON / OFF commands:
Press “ENT”, the cursor will start blinking. Use LEFT & RIGHT keys to select the specific bank. Use UP key to
turn On and DOWN key to turn Off the capacitor banks. After pressing UP key, symbol will appear with cursor
blinking status and when DOWN key is pressed symbol will disappear. To come out of Manual On/Off edit
mode, press “ENT” key so that cursor stops blinking.
Ensure that there are no loose connections and the wiring is as per the wiring diagram.
Ensure that the power cables are connected properly from source to the Panel incomer and then to
the feeder incomer. Refer the schemes given in earlier part of this manual for C.T. and P.T.
connection.
Ensure that the Bus Bars and/or Lugs are Clean, Dust free, No Corrosion or Oxidation on the
contact sides so that it does not disrupt electrical connection. Use proper lugs/connectors to get
maximum contact area.
Ensure that the load feedback C.T. connections are proper and the C.T. is connected in proper
phase as per the wiring diagram and check polarity. Also ensure that there is provision for
shorting the C.T.
C.T. connections to be done carefully so as to ensure that the wires do not remain open and no
loose connection.
Loose connections or open C.T. secondary can result to very high voltages developed in the
circuit that can damage the C.T. and also risk of noise in the system. GB-VI-3L-08 relay is
provided with three terminals for each phase of C.T. secondary so that 1 Ampere and 5 Ampere
can be selectable. For 1A secondary C.T. connections, connect C.T. of R-Phase, Y-Phase and
B-Phase to RS - RS1, YS -YS1 and BS - BS1 terminals of controller respectively. For 5A
secondary C.T. connections, connect C.T. of R-Phase, Y-Phase and B-Phase to RS - RS5, YS
- YS5 and BS - BS5 terminals of controller respectively
Ensure that the neutral and earth connections are proper. The Panel should not be powered before
confirmation.
The controller and the control sections should not be powered before the Neutral and Earth connections
are proper, to avoid permanent damage to the controller, contactor coils, fans and other equipment’s in the
panel. The Power connections are done, to source side, in such a way that, the wires are not accidentally
disconnected. If required, use proper labels on the wires to identify them.
2. Turn On the supply to the panel and set Date/time and various other parameters as per the panel
configuration. It is important to understand the meaning of every parameter from the instructions
given before and then put the appropriate values in them. Wrong values entered can give the
wrong performance of the panel.
3. Once the setting of parameters is complete, put the GB-VI-3L-12 in Manual mode to check every
bank command is transmitted to the switch. This can be observed by switching the contactors ON &
OFF.
4. Once all the contactors get the correct commands, switch OFF the supply and place all the fuses
(or turn on MCB’s/MCCB’s if they are provided instead of fuses).Turn on the panel.
5. Put GB-VI-3L-12 back in Manual mode and turn ON/Off the individual steps. Use Current Clamp (AC
current measurement) to check the current in all the three phase of the corresponding banks.
6. Keep all the banks in off mode. Remove the short-link of Load feedback C.T. In case KW value is
seen as negative, reverse the C.T. polarity.
7. Switch OFF all the banks manually and put the GB-VI-3L-12 in Automatic mode. Observe the panel
performance for a period of about 2hrs after the commissioning.
- 31 -
FAULT FINDING GUIDELINES:
- 32 -