CHAPTER 9 -FIRE PROTECTION SYSTEMS
4. The minimum positive pressure of 25 Pa of          470 liters per second per door, or that specified by a
         water and a maximum positive pressure of 67        registered design professional to meet the
         Pa of water with respect to occupied floors        requirements of a designed pressurization system.
         are not required at the floor of recall with the
         doors open.
                                                            909.21.5       Standby        power .       The
                                                            pressurization system shall be provided with
   909.21.1.1       Use of ventilation systems.             standby power in accordance with Section 2702.
   Ventilation systems, other than hoistway supply air
   systems, are permitted to be used to exhaust air from
   adjacent spaces on the fire floor, two floors            909.21.6         Activation of pr essur ization
   immediately below and one floor immediately              system. The elevator pressurization system shall be
   above the fire floor to the building’s exterior where    activated upon activation of either the building fire
   necessary to maintain positive pressure                  alarm system or the elevator lobby smoke detectors.
   relationships as required in Section 909.21.1 during     Where both a building fire alarm system and
   operation of the elevator shaft pressurization           elevator lobby smoke detectors are present, each
   system.                                                  shall be independently capable of activating the
                                                            pressurization system.
   909.21.2        Rational analysis. A rational
   analysis complying with Section 909.4 shall be           909.21.7        Testing. Testing for performance
   submitted with the construction documents.               shall be required in accordance with Section
                                                            909.18.8. System acceptance shall be in accordance
                                                            with Section 909.19.
   909.21.3         Ducts for system. Any duct
   system that is part of the pressurization system shall
   be protected with the same fire-resistance rating as     909.21.8       Mar king and identification.
   required for the elevator shaft enclosure.               Detection and control systems shall be marked in
                                                            accordance with Section 909.14.
   909.21.4        Fan system. The fan system
   provided for the pressurization system shall be as       909.21.9        Control   diagr ams.  Control
   required by Sections 909.21.4.1 through 909.21.4.4.      diagrams shall be provided in accordance with
                                                            Section 909.15.
   909.21.4.1       Fire resistance. Where located
   within the building, the fan system that provides the    909.21.10      Control panel. A control panel
   pressurization shall be protected with the same fire-    complying with Section 909.16 shall be provided.
   resistance rating required for the elevator shaft
   enclosure.
                                                            909.21.11        System response time. Hoistway
                                                            pressurization systems shall comply with the
   909.21.4.2      Smoke detection. The fan system          requirements for smoke control system response
   shall be equipped with a smoke detector that will        time in Section 909.17.
   automatically shut down the fan system when
   smoke is detected within the system.
                                                            SECTION 910 SMOKE AND HEAT
                                                                 REMOVAL
   909.21.4.3      Separate systems. A separate fan
   system shall be used for each elevator hoistway.         910.1 General. Where required by this code,
                                                            smoke and heat vents or mechanical smoke removal
                                                            systems shall conform to the requirements of this
   909.21.4.4       Fan capacity. The supply fan shall      section.
   be either adjustable with a capacity of not less than
                                                   SBC 201-CR-18                                             359
CHAPTER 9 -FIRE PROTECTION SYSTEMS
   910.2 Where required. Smoke and heat vents or            surface of the story is not a roof assembly, a
   a mechanical smoke removal system shall be               mechanical smoke removal system in accordance
   installed as required by Sections 910.2.1 and            with Section 910.4 shall be installed.
   910.2.2.
                                                            910.3 Smoke and heat vents. The design and
   Exceptions:                                              installation of smoke and heat vents shall be in
                                                            accordance with Sections 910.3.1 through 910.3.3.
      1. Frozen food warehouses used solely for
         storage of Class I and II commodities where
         protected by an approved automatic sprinkler
                                                            910.3.1 Listing and labeling. Smoke and heat
         system.
                                                            vents shall be listed and labeled to indicate
      2. Smoke and heat removal shall not be required       compliance with UL 793 or FM 4430.
         in areas of buildings equipped with early
         suppression fast-response (ESFR) sprinklers.
      3. Smoke and heat removal shall not be required       910.3.2 Smoke and heat vent locations. Smoke
         in areas of buildings equipped with control        and heat vents shall be located 6 m or more from
         mode special application sprinklers with a         adjacent lot lines and fire walls and 3 m or more
         response time index of 50 (m · s)½ or less         from fire barriers. Vents shall be uniformly located
         that are listed to control a fire in stored        within the roof in the areas of the building where
         commodities with 12 or fewer sprinklers.           the vents are required to be installed by Section
                                                            910.2 with consideration given to roof pitch,
                                                            sprinkler location and structural members.
   910.2.1 Gr oup F-1 or S-1. Smoke and heat vents
   installed in accordance with Section 910.3 or a
   mechanical smoke removal system installed in             910.3.3 Smoke and heat vents area. The required
   accordance with Section 910.4 shall be installed in      aggregate area of smoke and heat vents shall be
   buildings and portions thereof used as a Group F-1       calculated as follows:
   or S-1 occupancy having more than 4645 m2 of
   undivided area. In occupied portions of a building       For buildings equipped throughout with an
   equipped throughout with an automatic sprinkler          automatic sprinkler system in accordance with
   system in accordance with Section 903.3.1.1 where        Section 903.3.1.1:
   the upper surface of the story is not a roof assembly,
   a mechanical smoke removal system in accordance                       ܣோ  ൌ ܸȀʹͶͷ                9-3
   with Section 910.4 shall be installed.
                                                            where:
                                                            AVR      =        The required aggregate vent area
   Exception: Group S-1 aircraft repair hangars.            (m2).
                                                            V       =       Volume (m3) of the area that
   910.2.2 High-piled combustible storage. Smoke            requires smoke removal.
   and heat removal required by Table 3206.2 of the
   SBC 801 for buildings and portions thereof
   containing highpiled combustible storage shall be        For unsprinklered buildings:
   installed in accordance with Section 910.3 in                ܣோ  ൌ  ܣி ȀͷͲ                 9-4
   unsprinklered buildings. In buildings and portions
   thereof containing high-piled combustible storage        where:
   equipped throughout with an automatic sprinkler
   system in accordance with Section 903.3.1.1, a           AVR      =        The required aggregate vent area
   smoke and heat removal system shall be installed in      (m2).
   accordance with Section 910.3 or 910.4. In               AFA     =       The area of the floor in the area that
   occupied portions of a building equipped                 requires smoke removal.
   throughout with an automatic sprinkler system in
   accordance with Section 903.3.1.1, where the upper
                                                   SBC 201-CR-18                                              360
CHAPTER 9 -FIRE PROTECTION SYSTEMS
                                                           interior fire exposure to temperatures in excess of
                                                           538°C for a period of not less than 15 minutes.
   910.4 Mechanical smoke removal systems.
   Mechanical smoke removal systems shall be
   designed and installed in accordance with Sections
                                                           910.4.7 Controls. Where building air-handling and
   910.4.1 through 910.4.7.
                                                           mechanical smoke removal systems are combined
                                                           or where independent building air-handling systems
                                                           are provided, fans shall automatically shut down in
   910.4.1 Automatic spr inklers required. The             accordance with SBC 501. The manual controls
   building shall be equipped throughout with an           provided for the smoke removal system shall have
   approved automatic sprinkler system in accordance       the capability to override the automatic shutdown of
   with Section 903.3.1.1.                                 fans that are part of the smoke removal system.
   910.4.2 Exhaust fan constr uction. Exhaust fans         910.5 Maintenance. Smoke and heat vents and
   that are part of a mechanical smoke removal system      mechanical smoke removal systems shall be
   shall be rated for operation at 105°C. Exhaust fan      maintained in accordance with the SBC 801.
   motors shall be located outside of the exhaust fan
   air stream.
                                                           SECTION 911 FIRE COMMAND
   910.4.3 System design criteria. The mechanical
                                                                CENTER
   smoke removal system shall be sized to exhaust
   the building at a minimum rate of two air               911.1 General. Where required by other sections
   changes per hour based upon the volume of the           of this code and in buildings classified as high-rise
   building or portion thereof without contents.           buildings by this code, a fire command center for
   The capacity of each exhaust fan shall not              civil defense operations shall be provided and shall
                                                           comply with Sections 911.1.1 through 911.1.6.
   exceed 14150 liters per second .
   910.4.3.1         Makeup air. Makeup air openings
   shall be provided within 1.8 m of the floor level.      911.1.1 Location and access. The location and
   Operation of makeup air openings shall be manual        accessibility of the fire command center shall be
   or automatic. The minimum gross area of makeup          approved by the fire chief.
   air inlets shall be 0.74 m2 per 470 liters per second
   of smoke exhaust.
                                                           911.1.2 Separ ation. The fire command center shall
                                                           be separated from the remainder of the building by
   910.4.4 Activation. The mechanical smoke                not less than a 1-hour fire barrier constructed in
   removal system shall be activated by manual             accordance with Section 707 or horizontal assembly
   controls only.                                          constructed in accordance with Section 711, or
                                                           both.
   910.4.5 Manual contr ol location. Manual controls
   shall be located so as to be accessible to the fire     911.1.3 Size. The room shall be not less than 19 m2
   service from an exterior door of the building and       with a minimum dimension of 3 m.
   protected against interior fire exposure by not less
   than 1-hour fire barriers constructed in accordance
   with Section 707 or horizontal assemblies               911.1.4 Layout appr oval. A layout of the fire
   constructed in accordance with Section 711, or both.    command center and all features required by this
                                                           section to be contained therein shall be submitted
                                                           for approval prior to installation.
   910.4.6 Control wiring. Wiring for operation and
   control of mechanical smoke removal systems shall
   be connected ahead of the main disconnect in            911.1.5 Stor age. Storage unrelated to operation of
   accordance with SBC 401 and be protected against        the fire command center shall be prohibited.
                                                  SBC 201-CR-18                                            361