LAND KEY :

GENERAL NOTES
ABBREVIATION DESCRIPTION SYMBOLS LEGEND SUPPLY SLOT LINEAR DIFUSER
.1 ALL MECHANICAL DRAWINGS SHALL BE READ IN CONJUNCTION WITH GENERAL NOTES,
44
HVAC HEATING,VENTILATING&AIR CONDITIONING SPECIFICATIONS AND MISCELLANEOUS DETAILS.
°C CELISUZ DEGREE
DOOR UNDER CUT .2 PROVIDE ACCESS PANELS (WHERE REQUIRED) IN THE CEILING TO ALL FIRE DAMPERS,
L/S LITER PER SECOND
VOLUME DAMPERS (WHERE REQUIRED) AND OTHER CONCEALED
DB DRY BULB TEMPRATURE RETURN SLOT LINEAR DIFUSER EQUIPMENT. CONTRACTOR SHALL COORDINATE NO EXTRA COST WITH ARCHITECT THE 46
DUCT SIZE: FINAL LOCATION OF ACCESS PANELS TO SUIT THE SELECTED EQUIPMENT.
WB WET BULB TEMPRATURE
350X200 FIRST FIGURE - SIDE SHOWN
TR TONS OF REFRIGERATION SECOND FIGURE - SIDE NOT SHOWN .3 UNLESS OTHERWISE SPECIFIED, ALL DUCT SIZES AND OTHER DIMENSIONS ARE IN
MILLIMETERS. GENERAL NOTES :
KW KILOWATT
1. ALL DIMENSIONS ARE IN MILLIMETERS AND ALL LEVELS ARE IN METERS
NC NOISE CRITERIA .4 ALL DUCT SIZES MENTIONED ON PLANS ARE CLEAR SIZES, EXCLUDING THE THICKNESS
UNLESS OTHERWISE NOTED.
OF INSULATION, AND OTHER DUCT LINING. 2. DO NOT SCALE FROM THIS DRAWING.
PS POWER SUPPLY
SUPPLY DUCT IN SECTION 3. FOLLOW THE WRITTEN DIMENSIONS
PH PHASE .5 PROVIDE 6mm SQUARE MESH SCREEN ON ALL DUCT AND WALL OPENINGS IN CEILING 4. CONTRACTOR TO CHECK SITE CONDITIONS AND BUILDER PLANS PRIOR
SUPPLY SQUARE CEILING DIFUSER SPACE. TO COMMENCE CONSTRUCTION WORKS.
HZ HERTZ
5. ACCESS PANELS SHALL BE LOCATED AS PER RCP DRAWINGS (REFLECTED
SAD SUPPLY AIR DUCT .6 FLEXIBLE DUCT CONNECTION TO ANY AIR OUTLET SHALL NOT EXCEED A LENGTH OF 1.5 CEILING COORDINATION PLANS).
RETURN AIR DUCT IN SECTION
RAD RETURN AIR DUCT METERS AND SHOULD BE STRAIGHTENED AS MUCH AS POSSIBLE TO ACHIEVE MINIMUM
EAD EXHAUST AIR DUCT RESISTANCE TO AIR FLOW.
ESP EXTERNAL STATIC PRESSURE DUCTWORK, FITTINGS, HANGERS AND ACCESSORIES SHALL BE AS PER SMACNA
.7 00 ADM SUBMISSION 17/01/2019
EXHAUST DUCT IN SECTION
EAF EXHAUST AIR FAN RECOMMENDATIONS.
K.EAF KITCHEN EXHAUST AIR FAN
.8 WALL AND ROOF OPENINGS SHALL BE 13mm LARGER ALL AROUND THAN DUCT OR FIRE
K.MAF KITCHEN MAKEUP AIR FAN DAMPER SLEEVE PASSING THROUGH WALL OR SLAB AND THE VOID WILL BE FILLED WITH REV. NO. DESCRIPTION Date

NON-COMBUSTIBLE MATERIAL. MASTER DEVELOPER :


VRF VARIABLE REFRIGERANT FLOW RETURN SQUARE CEILING DIFUSER
AHU AIR HANDLING UNIT VRF AIR COOLED CONDENSING UNIT COORDINATE GRILLES, DIFFUSERS AND REGISTERS WITH REFLECTED CEILING PLANS AND
.9
FAHU FRESH AIR HANDLING UNIT LIGHTING PLANS.
OWNER:

SRAC SPLIT ROOM AIR CONDITIONING .10 REFER TO ARCHITECTURAL DRAWINGS FOR DOOR GRILLES AND DOOR UNDERCUT SIZES
AND DETAILS.
CASS. CASSETTE UNIT
.11 FAN SYSTEM RESISTANCE STATED IN THE SCHEDULES ARE DESIGN
CU CONDENSING UNIT HAMAD MUBARAK SALEM AL SHAMSI
DX CONDENSING UNIT APPROXIMATIONS ONLY AND SHALL BE CHECKED BY THE MECHANICAL SERVICES
IU INDOOR CONCEALED DUCTED SPLIT UNIT CONTRACTOR PRIOR TO THE FINAL ORDERING OF EQUIPMENT.
SLD SUPPLY LINEAR SLOT DIFFUSER CONSULTANT :
.12 PIPE ALL CONDENSATE DRAIN LINES TO THE NEAREST DRAIN POINT PROVIDED UNDER
RLD RETURN LINEAR SLOT DIFFUSER SUPPLY ROUND DIFUSER PLUMBING WORKS UNLESS OTHERWISE SHOWN ON THE DRAWING.
EG EXHAUST GRILLE
.13 WHERE SHOWN ON PLANS THE ROOM THERMOSTATS SHALL BE MOUNTED ON THE WALL
FAL FRESH AIR LOUVER
1.5m. ABOVE FLOOR AND COORDINATE WITH INTERIOR DESIGN.
TYP. TYPICAL
N.T.S NOT TO SCALE AIR HANDLING UNIT .14 EXPOSED EQUIPMENT TO BE TROPICALIZED AND WEATHERPROOFED. CONTRACTOR
QTY QUANTITY SHALL COORDINATE WITH ARCHITECTS TO MAKE SURE THAT THE EQUIPMENT IS
CONCEALED BEHIND PARAPET WALLS. PROJECT NAME :
UC DOOR UNDERCUT
.15 VIBRATING EQUIPMENT SHALL BE PROVIDED WITH ISOLATORS TO PREVENT VIBRATION
VD VOLUME DAMPER TRANSMISSION.
PRIVATE RESIDINTIAL VILLA
W.M.S WIRE MESH SCREEN SPLIT ROOM AIR CONDITIONING .16 INSTALL EXHAUST FANS , AIR CONDITIONING UNITS ON CONCRETE
RETURN ROUND DIFUSER
BASE / CURB AS DETAILED ON STRUCTURAL DRAWINGS.
B.M. BELLMOUTH ZONE :
.17 INSTALL ALL EQUIPMENT AS PER MANUFACTURER'S RECOMMENDATIONS.
C/W COMPLETE WITH ABU DHABI - AL MAQTA
.18 INSTALL VOLUME DAMPERS ON ALL DUCT BRANCHES AND BRANCH TAKE-OFFS AND
INDOOR CONCEALED DUCTED SPLIT UNIT SECTOR NO : PLOT NO :
WHEREVER REQUIRED FOR PROPER BALANCING OF AIR.
MQ12 45
.19 IN CASE OF ANY CONFLICTION BETWEEN THE HVAC DRAWINGS , B.O.Q
AND SPECIFICATIONS (IF EXISTED) , REFER TO THE ENGINEER. PROJECT DESCRIPTION :
PRIVATE RESIDENTIAL VILLA CONSIST OF THE FOLLOWING:
THE CONTRACTOR IS RESPONSIBLE TO ACHIEVE THE REQUIRED SOUND LEVEL IN ALL
* THE MAIN VILLA CONSIST OF GROUND, FIRST, ROOF & TOP ROOF FLOOR.
SPACES, SO THAT THE MAX. ACCEPTABLE NOISE CRITERIA IS .35
OUTDOOR UNIT - GROUND FLOOR CONTAINING RECEPTION & DINING SPACES, LIVING
SUPPLY SQUARE CEILING DIFUSER AREAS, SERVICES & GUEST ROOMS.
.20 PIPING SHALL BE SIZED BY CONTRACTOR BASED ON ACTUAL PIPE LENGTH ACCORDING
- FIRST FLOOR CONTAINING FAMILY LIVING ROOM WITH 5 BEDROOMS.
TO THE LOCATION OF INDOOR AND OUTDOOR UNITS AND THE DISTANCE BETWEEN THEM. - ROOF FLOOR CONTAINING SERVICES & PRIVATE SUITE.
* SERVICE & ELECTRICAL ROOM ON THE BOUNDARY WALL.

.21 THE DUCT EXTERNAL STATIC PRESSURE IS A ROUGHLY ESTIMATE, CONTRACTOR IS RESPONSIBLE
TO CALCULATE THE ACTUAL STATIC PRESSURE BASED ON THE FINAL DUCT ROUTES AND THE DRAWING TITLE :
INLINE EXHAUST AIR FAN
ACTUAL MATERIAL SUBMITTALS.
HVAC LEGEND,SYMBOLS
&
FRISH AIR FAN SECTION
GENERAL NOTES
RETURN SQUARE CELINIG DIFUSER DRAWING NO : REVISION NO:

MV-MH-0-00-00-00 00

CEILING EXHAUST FAN SUBMISSION DATE : SCALE :

16/01/2019 1:100
PROJECT ID : DRAWING SIZE :

XX XXXX A1
ROOF TOP EXHAUST FAN SUPPLY SIDE GRILLE
OFFICIAL USE ONLY :

OFFICIAL USE ONLY :

RETURN SIDE GRILLE


ROOF TOP FRESH AIR FAN
LAND KEY :

A B C D E F G H I J K

44

46

BALCONY
018 GENERAL NOTES :
1. ALL DIMENSIONS ARE IN MILLIMETERS AND ALL LEVELS ARE IN METERS

1 1 UNLESS OTHERWISE NOTED.


2. DO NOT SCALE FROM THIS DRAWING.
3. FOLLOW THE WRITTEN DIMENSIONS
4. CONTRACTOR TO CHECK SITE CONDITIONS AND BUILDER PLANS PRIOR
TO COMMENCE CONSTRUCTION WORKS.
MASTER BR. BATH 5. ACCESS PANELS SHALL BE LOCATED AS PER RCP DRAWINGS (REFLECTED

2 016 2 CEILING COORDINATION PLANS).

DRESS 00 ADM SUBMISSION 17/01/2019


017
MASTER BEDROOM
019 REV. NO. DESCRIPTION Date

MASTER BR. DRESSING MASTER DEVELOPER :

015

OWNER:

3 3
MASTER BR. HAMAD MUBARAK SALEM AL SHAMSI
BEDROOM-01 ENTRANCE DRESS BEDROOM-04
023 021 013 014 CONSULTANT :

LOBBY
024

4 OPEN BELOW STAIR 4


STORAGE BATH
020
005 012
PROJECT NAME :
5 DRESS 5
MAIN HALL +5.25
025 1ST. F.F.L. LOBBY
022 PRIVATE RESIDINTIAL VILLA
011
LOBBY
010
ZONE :

6 BATH 6 ABU DHABI - AL MAQTA


026 LIFT
003 DRESS BEDROOM-03 SECTOR NO : PLOT NO :

008 009 MQ12 45

7 7 PROJECT DESCRIPTION :
PRIVATE RESIDENTIAL VILLA CONSIST OF THE FOLLOWING:
LOBBY KITCHENETTE
* THE MAIN VILLA CONSIST OF GROUND, FIRST, ROOF & TOP ROOF FLOOR.
027 002 - GROUND FLOOR CONTAINING RECEPTION & DINING SPACES, LIVING
AREAS, SERVICES & GUEST ROOMS.
- FIRST FLOOR CONTAINING FAMILY LIVING ROOM WITH 5 BEDROOMS.

8 8 - ROOF FLOOR CONTAINING SERVICES & PRIVATE SUITE.


* SERVICE & ELECTRICAL ROOM ON THE BOUNDARY WALL.
DRESS STORAGE ELEC. ROOM
FAMILY LIVING
028 004 006 DRAWING TITLE :
BEDROOM-02 001
030 OPEN BELOW
FIRST FLOOR PLAN -
HVAC SYSTEM

9 BATH 9 DRAWING NO : REVISION NO:


+3.50
007 MV-MH-1-01-00-00
S.S.L 00

10 10 SUBMISSION DATE : SCALE :

OPEN BELOW
16/01/2019 1:100
BATH PROJECT ID : DRAWING SIZE :
11 029 11
XX XXXX A1
OFFICIAL USE ONLY :

+3.50
S.S.L OFFICIAL USE ONLY :

A B C D E F G H I J K
LAND KEY :

A B C D E F G H I J K

44

46
FAF-02 EAF-04

FAD 250x250 EAD 250x250


GENERAL NOTES :
1. ALL DIMENSIONS ARE IN MILLIMETERS AND ALL LEVELS ARE IN METERS

1 1 UNLESS OTHERWISE NOTED.


VERANDA 2. DO NOT SCALE FROM THIS DRAWING.
3. FOLLOW THE WRITTEN DIMENSIONS
015
4. CONTRACTOR TO CHECK SITE CONDITIONS AND BUILDER PLANS PRIOR
TO COMMENCE CONSTRUCTION WORKS.
5. ACCESS PANELS SHALL BE LOCATED AS PER RCP DRAWINGS (REFLECTED
2 2 CEILING COORDINATION PLANS).

00 ADM SUBMISSION 17/01/2019


FAMILY DINNING
013
FAMILY SITTING
REV. NO. DESCRIPTION Date
014 MASTER DEVELOPER :

OWNER:

3 3
MAIN HALL HAMAD MUBARAK SALEM AL SHAMSI
017 FAMILY
PANTRY
CONSULTANT :
012
STAIR
GUEST BEDROOM 016 TOILET
018 WASH 010
011

4 4
TOILET
PROJECT NAME :
5 019 DRESSING KITCHEN 5
020 007 BATH
009 PRIVATE RESIDINTIAL VILLA

ZONE :
GUEST TOILET
6 022 LIFT 6 ABU DHABI - AL MAQTA
005
SECTOR NO : PLOT NO :

LOBBY MQ12 45
002
7 SERVICE 7 PROJECT DESCRIPTION :

004 PRIVATE RESIDENTIAL VILLA CONSIST OF THE FOLLOWING:


STORE DRIVER * THE MAIN VILLA CONSIST OF GROUND, FIRST, ROOF & TOP ROOF FLOOR.
- GROUND FLOOR CONTAINING RECEPTION & DINING SPACES, LIVING
MAJLIS 006 008
AREAS, SERVICES & GUEST ROOMS.

023 - FIRST FLOOR CONTAINING FAMILY LIVING ROOM WITH 5 BEDROOMS.


8 8 - ROOF FLOOR CONTAINING SERVICES & PRIVATE SUITE.

DINNING HALL * SERVICE & ELECTRICAL ROOM ON THE BOUNDARY WALL.

003
GUEST WASH DRAWING TITLE :

021
GROUND FLOOR PLAN
-
HVAC SYSTEM
9 ENTRANCE 9 DRAWING NO : REVISION NO:

001 MV-MH-1-GR-00-00 00

10 10 SUBMISSION DATE : SCALE :

16/01/2019 1:100
PROJECT ID : DRAWING SIZE :
11 11
XX XXXX A1
OU-01 OU-01

OFFICIAL USE ONLY :

OFFICIAL USE ONLY :


ELEC. ROOM GARBAGE
025 COLLECTION
024

A B C D E F G H I J K
LAND KEY :

A B C D E F G H I J K

44

Below
Balcony
46

GENERAL NOTES :
1. ALL DIMENSIONS ARE IN MILLIMETERS AND ALL LEVELS ARE IN METERS
MASTER BR. BATH UNLESS OTHERWISE NOTED.
012 1 2. DO NOT SCALE FROM THIS DRAWING.
3. FOLLOW THE WRITTEN DIMENSIONS
4. CONTRACTOR TO CHECK SITE CONDITIONS AND BUILDER PLANS PRIOR
TO COMMENCE CONSTRUCTION WORKS.
5. ACCESS PANELS SHALL BE LOCATED AS PER RCP DRAWINGS (REFLECTED
CEILING COORDINATION PLANS).

00 ADM SUBMISSION 17/01/2019


DRESS
SUITE
010
011 REV. NO. DESCRIPTION Date
MASTER DEVELOPER :

MASTER BR. DRESS


009
OWNER:

3 HAMAD MUBARAK SALEM AL SHAMSI

CONSULTANT :

MAIDS ROOM
008

BATH
007 4
PROJECT NAME :

LOBBY 5
003 PRIVATE RESIDINTIAL VILLA

ZONE :

ABU DHABI - AL MAQTA


IRON 6
TERRACE LAUNDRY SECTOR NO : PLOT NO :
005
001 006 MQ12 45

PROJECT DESCRIPTION :
7 PRIVATE RESIDENTIAL VILLA CONSIST OF THE FOLLOWING:
* THE MAIN VILLA CONSIST OF GROUND, FIRST, ROOF & TOP ROOF FLOOR.
STORE LIFT ELEC. ROOM - GROUND FLOOR CONTAINING RECEPTION & DINING SPACES, LIVING
AREAS, SERVICES & GUEST ROOMS.
001 002 004
- FIRST FLOOR CONTAINING FAMILY LIVING ROOM WITH 5 BEDROOMS.
- ROOF FLOOR CONTAINING SERVICES & PRIVATE SUITE.

8 * SERVICE & ELECTRICAL ROOM ON THE BOUNDARY WALL.

DRAWING TITLE :

ROOF PLAN - HVAC SYSTEM

DRAWING NO : REVISION NO:


9
MV-MH-1-RF-00-00 00

SUBMISSION DATE : SCALE :


10
16/01/2019 1:100
PROJECT ID : DRAWING SIZE :

11 XX XXXX A1
OFFICIAL USE ONLY :

OFFICIAL USE ONLY :

A B C D E F G H I J K
LAND KEY :

A B C D E F G H I J K

44

46

GENERAL NOTES :
1. ALL DIMENSIONS ARE IN MILLIMETERS AND ALL LEVELS ARE IN METERS

1 1 UNLESS OTHERWISE NOTED.


2. DO NOT SCALE FROM THIS DRAWING.
3. FOLLOW THE WRITTEN DIMENSIONS
4. CONTRACTOR TO CHECK SITE CONDITIONS AND BUILDER PLANS PRIOR
TO COMMENCE CONSTRUCTION WORKS.
5. ACCESS PANELS SHALL BE LOCATED AS PER RCP DRAWINGS (REFLECTED

2 2 CEILING COORDINATION PLANS).

00 ADM SUBMISSION 17/01/2019

REV. NO. DESCRIPTION Date


MASTER DEVELOPER :

OWNER:

3 3
HAMAD MUBARAK SALEM AL SHAMSI

CONSULTANT :

4 4

PROJECT NAME :
5 5
PRIVATE RESIDINTIAL VILLA

ZONE :

6 6 ABU DHABI - AL MAQTA

SECTOR NO : PLOT NO :

MQ12 45

7 7 PROJECT DESCRIPTION :
PRIVATE RESIDENTIAL VILLA CONSIST OF THE FOLLOWING:
* THE MAIN VILLA CONSIST OF GROUND, FIRST, ROOF & TOP ROOF FLOOR.
- GROUND FLOOR CONTAINING RECEPTION & DINING SPACES, LIVING
AREAS, SERVICES & GUEST ROOMS.
- FIRST FLOOR CONTAINING FAMILY LIVING ROOM WITH 5 BEDROOMS.

8 8 - ROOF FLOOR CONTAINING SERVICES & PRIVATE SUITE.


* SERVICE & ELECTRICAL ROOM ON THE BOUNDARY WALL.

DRAWING TITLE :

UPPER ROOF PLAN - HVAC SYSTEM

9 9 DRAWING NO : REVISION NO:

MV-MH-1-UR-00-00 00

10 10 SUBMISSION DATE : SCALE :

16/01/2019 1:100
PROJECT ID : DRAWING SIZE :
11 11
XX XXXX A1
OFFICIAL USE ONLY :

OFFICIAL USE ONLY :

A B C D E F G H I J K
LAND KEY :

44

46

GENERAL NOTES :
1. ALL DIMENSIONS ARE IN MILLIMETERS AND ALL LEVELS ARE IN METERS
UNLESS OTHERWISE NOTED.
2. DO NOT SCALE FROM THIS DRAWING.
3. FOLLOW THE WRITTEN DIMENSIONS
4. CONTRACTOR TO CHECK SITE CONDITIONS AND BUILDER PLANS PRIOR
TO COMMENCE CONSTRUCTION WORKS.
5. ACCESS PANELS SHALL BE LOCATED AS PER RCP DRAWINGS (REFLECTED
CEILING COORDINATION PLANS).

00 ADM SUBMISSION 17/01/2019

REV. NO. DESCRIPTION Date


MASTER DEVELOPER :

OWNER:

HAMAD MUBARAK SALEM AL SHAMSI

CONSULTANT :

PROJECT NAME :

PRIVATE RESIDINTIAL VILLA

ZONE :

ABU DHABI - AL MAQTA

SECTOR NO : PLOT NO :

MQ12 45

PROJECT DESCRIPTION :
PRIVATE RESIDENTIAL VILLA CONSIST OF THE FOLLOWING:
* THE MAIN VILLA CONSIST OF GROUND, FIRST, ROOF & TOP ROOF FLOOR.
- GROUND FLOOR CONTAINING RECEPTION & DINING SPACES, LIVING
AREAS, SERVICES & GUEST ROOMS.
- FIRST FLOOR CONTAINING FAMILY LIVING ROOM WITH 5 BEDROOMS.
- ROOF FLOOR CONTAINING SERVICES & PRIVATE SUITE.
* SERVICE & ELECTRICAL ROOM ON THE BOUNDARY WALL.

DRAWING TITLE :

HVAC GENERAL DETAILS 1/1

DRAWING NO : REVISION NO:

MV-MH-4-00-00-00 00

SUBMISSION DATE : SCALE :

16/01/2019 1:100
PROJECT ID : DRAWING SIZE :

XX XXXX A1
OFFICIAL USE ONLY :

OFFICIAL USE ONLY :


LAND KEY :

44

46

GENERAL NOTES :
1. ALL DIMENSIONS ARE IN MILLIMETERS AND ALL LEVELS ARE IN METERS
UNLESS OTHERWISE NOTED.
2. DO NOT SCALE FROM THIS DRAWING.
3. FOLLOW THE WRITTEN DIMENSIONS
4. CONTRACTOR TO CHECK SITE CONDITIONS AND BUILDER PLANS PRIOR
TO COMMENCE CONSTRUCTION WORKS.

BUTT HINGE 25mm 25mm OR PIANO HINGE


5. ACCESS PANELS SHALL BE LOCATED AS PER RCP DRAWINGS (REFLECTED

AIR FLOW
CEILING COORDINATION PLANS).
AIR FLOW

L
WHERE L=1/3 W (MIN.)
+D SLOPE 1" IN 7" STRAIGHTENING
D1
D HEEL RADIUS VANES

GRILLE

GAGE 26
THROAT RADIUS
ALUMINIUM CLADDING
(FOR OUTDOOR LOCATION)
00 ADM SUBMISSION 17/01/2019

W
VIEW PORT

TYPICAL TAKEOFFS
CELLULAR GLASS


VOLUME DAMPER PIPE INSULATION
VOLUME DAMPER WITH FACTORY
APPLIED VAPOR
BARRIER

"L" MAY BE ZERO STRAIGHTENING VANES


REV. NO. DESCRIPTION Date
60° MINIMUM
REDUCER SQUARE TO ROUND MASTER DEVELOPER :
HINGE POSITION JOINT SEALER
CLOSE OPENING
ELEVATION ELEVATION AT CORNERS
THIS ARRANGEMENT USED ON LARGE DIFFUSERS THIS ARRANGEMENT USED ON SMALL DIFFUSERS. NO. NO. GAGE
15" DIAM. NECK AND ABOVE. ALTERNATE ON LARGE DIFFUSERS WITH APPROVAL OF ENGINEER. MAX DIM.
HINGES HANDLES DOOR BACK FRAME
NOTES :
12 X 12 2 1 26 26 24 PIPE NON-FERROUS BAND
1- INSTALL STRAIGHTENING VANES WHEN "L" IS LESS THAN 4 "D"
16 X 20 2 2 24 26 22
2- PREFERABLY "X" NOT LESS THAN "D" MINIMUM "X" = 1/2 "D"
45 DEGREE ENTRY 0 = 45°
3- "Y" VARIES (UNIMPORTANT) 24 X 24 3 2 22 26 22 OVERLAP
OWNER:
4- WITH STRAIGHTENING VANES "L" MAY BE ZERO
THIS ACCESS PANEL MAY BE DUCT GAGE
DIFFUSERS IN LATERAL TAKEOFF DOOR
WITH SCREWS AT"8"MAXIMUM SPACING

SUPPLY DUCT RETURN AND EXHAUST DUCT


NOTES:-
BONDING ADHESIVE
AIR FLOW AIR FLOW 1. FIRE DAMPERS AND ACCESS DOORS PROVISION AND INSTALLATION BETWEEN PIPE AND
ON HVAC DUCTS SHALL BE STRICTLY IN ACCORDANCE WITH NFPA CODES. INSULATION
BRANCH CONNECTION DETAIL
2. FIRE DAMPER PROVISION, INSTALLATION ACCESS DOORS AND IDENTIFICATION
DESIRABLE SLOPE 1 IN 7 MIN. SLOPE 1 IN 7
ALLOWABLE 1 IN 4 SHALL BE STRICTLY IN ACCORDANCE WITH NFPA CODES.
DUCT REDUCER
HAMAD MUBARAK SALEM AL SHAMSI
TYPICAL DUCT TAKEOFFS DUCT ACCESS DOOR REFRIGERANT PIPING INSULATION DETAIL

DETAIL No 01 DETAIL No 02 DETAIL No 03 DETAIL No 04 DETAIL No 05 DETAIL No 06 CONSULTANT :

REFRIGERANT PIPES

#24 GAUGE ALUMINUM


3 SHEET METAL CLADDING
MASTIC SEALANT ALL AROUND
DU
FOR EXPOSED TO CT
VIEW DUCT ONLY WID
GALVANIZED STEEL FLAASHING
4 DUCT HANGER (TYP.) TH
BEDDED IN MASTIC AND TIMBER LINING
SECURED WITH GALVANIZED 18mm THICK WALL
STEEL CLAMPING RING 1

DUCT HEIGHT
INSULATION AS
SPECIFIED
SUCTION PIPE

CONDENSING UNIT
2
300 MIN.
LIQUID PIPE
REFRIGERANT PIPE DUCT WORK END TABS OR FLAPS FOR JOINTS FORMED BY
STRIPPING FROM THE VAPOR BARRIER SEAL DUCT
CONCRETE SUPPORT (TYP.)
OVER LAPS WITH A QUICK TACKING ADHESIVE
BASE
GALVANIZED FRAME PROJECT NAME :
ANGLE UNDERCUT WITH NEOPRENE GASKET
CAST IN PIPE SLEEVE
GALV. SHEAR BLADE
FLAME RESISTANT QUICKTACKING
ADHESIVE TO BE COATED
100% OF DUCT SURFACE AREA 51 x 51 x 102MM U.S.G #20 EXTENDED SHAFT
GALVANIZED SHEET METAL
RC ROOF SLAB
A.EXPOSED TO VIEW #18 GAUGE TIE WIRE CORNER BEADING

NEOPRENE REFRIGERANT PIPE 1. CLOSED CELL TUBE 1NSULATION 18mm. THICKNESS SPACE AT 305MM
OR APPROVED EQUAL
DUCTWORK
DUCT INSULATION
PRIVATE RESIDINTIAL VILLA
PADS SUCTION & LIQUID 2. ADHESIVE FOSTER 85-20 OR EQUIVALENT
TO FCU
3. 4 OZ. CORA CLOTH BONDED ON THE INSULATION WITH
50
2 LAYERS OF ATLAS FOSTER 30-36 OR EQUIVALENT
NOTES: 4. 2 COATS OF VINYL BASED VAPORS 1.DUCT INSDE THE MECHANICAL ROOM SHALL BE INSULATED ZONE :
1. FOR ROOF CONSTRUCTION AND FLASHING & COUNTER FLASHING WITH 25MM THICK RIGID BOARD
BARRIER FOSTER 30-35 OR EQUIVALENT
DETAIL,REFER TO ARCHITECTURAL DRAWING.
INSULATION AND WRAPPED WITH CANVAS AND PAINTED
WITH POSTER PAINT.
ABU DHABI - AL MAQTA
(INSTEAD OF METAL CLADDING)
DUCT THROUGH WALL

INSTALLATION OF SPLIT A/C UNIT REFRIGERANT PIPES THRU ROOF INSTALLATION OF REFRIGERANT MAIN DUCT VOLUME DAMPER SECTOR NO : PLOT NO :
( CONDENSING UNIT) EXPOSED PIPES INSTALLATION DETAIL

MQ12 45
DETAIL No 07 DETAIL No 08 DETAIL No 09 DETAIL No 10 DETAIL No 11 DETAIL No 12 DETAIL No 13

PROJECT DESCRIPTION :
WALL

PRIVATE RESIDENTIAL VILLA CONSIST OF THE FOLLOWING:


INSULATION
* THE MAIN VILLA CONSIST OF GROUND, FIRST, ROOF & TOP ROOF FLOOR.
DUCT

AIR OUTLET
SUPPORT FROM ROOF STEEL
IN AN APPROVED MANNER
- GROUND FLOOR CONTAINING RECEPTION & DINING SPACES, LIVING
AIR INTAKE
AREAS, SERVICES & GUEST ROOMS.
PIPE INSULATION INSULATION
ANCHOR AIR FLOW DUCT
COPPER PIPE
- FIRST FLOOR CONTAINING FAMILY LIVING ROOM WITH 5 BEDROOMS.
DUCT
4 THREADED OUTDOOR
RODS (TYP).

MASTIC SEALANT
EACH O 8mm
AIR EXTRACTOR CONDENSING ROD - ROOF FLOOR CONTAINING SERVICES & PRIVATE SUITE.
DX INDOOR CONCEALED UNIT WEATHERPROOF SLEEVES Ø3/8"
UNIT
FOR REFRIGERANT PIPING
WORM GEAR OR
PIN & HINGE OPTIONAL
OPTIONAL CONTROL
* SERVICE & ELECTRICAL ROOM ON THE BOUNDARY WALL.
FIG. A
ESCUTCHEON PLATE IRON ANGLE WELD
2 ANGLE FRAMES FOR EXPOSED WALL ONLY AT ALL POINTS OF
EACH 50x50mm STEEL DRAIN PIPE CONTACT
RUBBER VIBRATION ISOLATOR AIR INTAKE IRON ANGLE LOCKING NUT
DUCT INTERCONNECTING TYPICAL MASONRY 2 1/2"x2 1/2"x1/4"
AIR FLOW SUPPORT NUT
ALUM.WIRE MESH EXPANSION BOLT
PIPING AND WIRING
CONCEALLED IN WALL DRAWING TITLE :
INDOOR
TO DRAIN TRAP
FLOW

30mm WOOD BLOCKING WALL SUPPORT TRAPEZE SUPPORT


AIR

ALL AROUND FAN COIL


AIR EXTRACTOR
STRAIGHTENING GRID UNIT
(WHEN REQUIRED)
(WHEN REQUIRED)

ADJUSTABLE
AIR FILTER
WALL DAMPER

AIR OUTLET
WALL

NOTE:-
REGISTER CONTAINS VOLUME
CONTROL AT GRILLE. GRILLE
FIG. B
SUPPLY REGISTER
GRILLE FLANGES MUST
THERMOSTAT
HVAC GENERAL DETAILS 1/2
HAS NO VOLUME CONTROL. COVER DUCT FLANGES.

CONDENSATE DRAIN
PIPE TO NEAREST
FLOOR DRAIN DUCTWORK SUPPORT DETAIL
DRAWING NO : REVISION NO:

EXHAUST AIR LOUVER SPLIT ROOM AIR CONDITIONER


INSTALLATION DETAIL
GRILLE & REGISTER CONNECTIONS INSTALLATION DETAIL FOR DX SPLIT UNIT
MV-MH-4-00-01-00 00

SUBMISSION DATE : SCALE :


DETAIL No 14 DETAIL No 15 DETAIL No 16 DETAIL No 17 DETAIL No 18 DETAIL No 19 DETAIL No 20
16/01/2019 1:100
PROJECT ID : DRAWING SIZE :

XX XXXX A1
OFFICIAL USE ONLY :

OFFICIAL USE ONLY :


LAND KEY :

SCHEDULE No1. SCHEDULE No5.

VRF AIR COOLED CONDENSING UNIT VRF AIR HANDLING UNITS SCHEDULE
44
AIR QUANTITY FAN DATA COOLING COIL DATA
MOTOR DATA ACTUAL CAPACITY AIR DATA
COOLING CAP. POWER INPUT POWER SUPPLY COMPRESSOR WEIGHT REFRIGERANT
UNIT NO. UNIT NO. SERVICE LOCATION EXT. ENT. TEMP. LVG. TEMP. FACE
(KW) (KW) (∅/V/Hz) (Kg) TYPE FAN TOTAL SENS.
TYPE TOTAL MIN. MOTOR ELECTRIC
SPEED STATIC SERVICE
COOLING COOLING DRY WET DRY WET VEL.
46
(L/S)
RPM PRESS. MOTOR SPEED LOAD LOAD BULB BULB BULB BULB (M/S)
PA KW RPM (V/PH/H) KW KW °C °C °C °C
VRF O.U 186.6 61.55 3/380/50 SCROLL 1135 R 410A
AHU-01 LOBBY UPPER ROOF 850 1200 500 1.15 1450 380/3/50 15.8 10.5 27 17.8 13.6 12.7 2.5

GENERAL NOTES :
* UNIT SELECTION SHALL BE BASED ON THE OUTSIDE WEATHER CONDITION 46(C DB 25& C WB) AHU-02 FAMILY DINNING,SITTING UPPER ROOF 1130 1200 500 2.25 1450 380/3/50 21.1 19 25.9 17.9 13.7 13 2.5 1. ALL DIMENSIONS ARE IN MILLIMETERS AND ALL LEVELS ARE IN METERS
UNLESS OTHERWISE NOTED.
2. DO NOT SCALE FROM THIS DRAWING.
3. FOLLOW THE WRITTEN DIMENSIONS
* UNIT SELECTION SHALL BE BASED ON THE OUTSIDE WEATHER CONDITION 46(C DB 25& C WB)
4. CONTRACTOR TO CHECK SITE CONDITIONS AND BUILDER PLANS PRIOR
TO COMMENCE CONSTRUCTION WORKS.
5. ACCESS PANELS SHALL BE LOCATED AS PER RCP DRAWINGS (REFLECTED
CEILING COORDINATION PLANS).

SCHEDULE No2.
SCHEDULE No6.
HI-WALL SPLIT AIR CONDITIONING UNITS
FRESH AIR HANDLING UNITS SCHEDULE 00 ADM SUBMISSION 17/01/2019
ELECTRICAL DATA
UNIT NO. TYPE SERVED AREA COOLING CAP.
POWER AIR QUANTITY FAN DATA COOLING COIL DATA
(KW) VOLTS PHASE HERTZ
(K.W) MOTOR DATA REV. NO. DESCRIPTION Date
ACTUAL CAPACITY AIR DATA
VRF-SRAC-01
MASTER DEVELOPER :
HI-WALL-VRF SPLIT UNIT ELEC.ROOM
. & STORE 2.2 220 1 50 0.025
UNIT NO. SERVICE LOCATION EXT. ENT. TEMP. LVG. TEMP. FACE
FAN TOTAL SENS.
TOTAL MIN. MOTOR ELECTRIC
SPEED STATIC SERVICE
COOLING COOLING DRY WET DRY WET VEL.
(L/S) MOTOR SPEED LOAD
VRF-SRAC-02 0.03 RPM PRESS. LOAD BULB BULB BULB BULB (M/S)
HI-WALL-VRF SPLIT UNIT DRIVER ROOM 3.6 220 1 50 PA KW RPM (V/PH/H) KW KW °C °C °C °C
OWNER:
FAHU-01 ALL FLOORS UPPER ROOF 470 1200 400 0.9 1450 380/3/50 13 13 43.9 23.3 17.5 15 2.5
* UNIT SELECTION SHALL BE BASED ON THE OUTSIDE WEATHER CONDITION 46 C DB 25& C WB)
* UNIT SELECTION SHALL BE BASED ON MEDIUM SPEED.
* UNIT SELECTION SHALL BE BASED ON THE OUTSIDE WEATHER CONDITION 46(C DB 25& C WB)
HAMAD MUBARAK SALEM AL SHAMSI

CONSULTANT :

SCHEDULE No7.
SCHEDULE No3. CONDENSING UNITS SCHEDULE
INDOOR AIR CONDITIONING UNITS PROJECT NAME :
COMPRESSOR DATA CONDENSER FAN DATA

ELECTRICAL DATA
COOLING CAP. AIR FLOW EXTERNAL STATIC ACTUAL PRIVATE RESIDINTIAL VILLA
UNIT NO. TYPE FAN
(KW) (L/S) PRESSURE (Pa) POWER CAPACITY TYPE REFRIGERANT MIN. ELECTRIC TYPE QTY. BREAK
VOLTS PHASE HERTZ UNIT NO. SERVICE LOCATION SPEED
(K.W) (KW) MOTOR SERVICE RPM KW
KW ZONE :
VRF-CONCEALED TYPE 5.6 216 150 220 1 50 0.13 (V/PH/H)
IU-01

CU-01 FAHU-01 UPPER ROOF 13 SCROLL R-134a 13.5 380/3/50 PROPELLER 2 1100 0.33 ABU DHABI - AL MAQTA
IU-02 VRF-CONCEALED TYPE 7.10 283 150 220 1 50 0.19

SECTOR NO : PLOT NO :
IU-03 VRF-CONCEALED TYPE 9 300 150 220 1 50 0.24
MQ12 45
* UNIT SELECTION SHALL BE BASED ON THE OUTSIDE WEATHER CONDITION 46(C DB 25& C WB)
IU-04 VRF-CONCEALED TYPE 11.20 416 150 220 1 50 0.26
PROJECT DESCRIPTION :

IU-05 PRIVATE RESIDENTIAL VILLA CONSIST OF THE FOLLOWING:


VRF-CONCEALED TYPE 12.80 500 150 220 1 50 0.37
* THE MAIN VILLA CONSIST OF GROUND, FIRST, ROOF & TOP ROOF FLOOR.
- GROUND FLOOR CONTAINING RECEPTION & DINING SPACES, LIVING
AREAS, SERVICES & GUEST ROOMS.
* UNIT SELECTION TO BE BASED ON MEDIUM FAN SPEED TO MEET SPECIFIED ABOVE PERFORMANCE.
- FIRST FLOOR CONTAINING FAMILY LIVING ROOM WITH 5 BEDROOMS.

* TOTAL STATIC PRESSURE IS TO BE VERIFIED BY CONTRACTOR UPON SELECTION OF ACTUAL UNIT, AND FINAL DUCT ROUTING . - ROOF FLOOR CONTAINING SERVICES & PRIVATE SUITE.
* SERVICE & ELECTRICAL ROOM ON THE BOUNDARY WALL.

SCHEDULE No8.
DRAWING TITLE :

FANS
HVAC EQUIPMENT SCHEDULE
SCHEDULE No.4 ELECTRICAL DATA
CAPACITY EXTERNAL STATIC POWER
UNIT NO. FLOOR SERVED SYSTEM SERVED TYPE DRIVE
(L/S) PRESSURE (Pa) (KW) VOLTS PHASE HERTZ
DX-SPLT HIGH WALL
EAF-01 GR,1ST,RF TOILET,PANTRY CEILING MOUNTED 50 DIRECT 75 0.1 220 1 50
DRAWING NO : REVISION NO:
EAF-02 MASTER BATHROOM 175 DIRECT 0.15 220 1 50
1ST,RF AXIAL INLINE 75
MV-MH-6-00-00-00 00
EAF-03 UPPER ROOF KITCHEN HOOD AXIAL INLINE 665 BELT DRIVE 150 0.3 220 1 50
SUBMISSION DATE : SCALE :
EAF-04 GROUND FLOOR PUMP ROOM ROOF TOP 120 DIRECT 50 220 1 50
0.15

FAF-01 UPPER ROOF KITCHEN HOOD FAN SECTION 530 DIRECT 150 0.25 220 1 50
16/01/2019 1:100
FAF-02 GROUND ROOF PMP ROOM ROOF TOP 100 DIRECT 50 0.15 220 1 50 PROJECT ID : DRAWING SIZE :

XX XXXX A1
* FINAL STATIC PRESSURE TO BE VERIFIED BY CONTRACTOR UPON SELECTION OF ACTUAL EQUIPMENT AND OFFICIAL USE ONLY :

FINAL DUCT ROUTING .

* UNIT SELECTION TO BE BASED ON MEDIUM FAN SPEED TO MEET SPECIFIED ABOVE PERFORMANCE. OFFICIAL USE ONLY :