Revision 2017-09-11
TTUA
Humidity and temperature transmitter
for room mounting
Wall mounted room transmitters for measuring
humidity and temperature in indoor environments. • Output signal 0…10 V or Modbus
• With or without display
• Good long-term stability
• Humidity range 0…100 RH%
• Temperature range 0…50 °C
SUPPLY VOLTAGE
Function
The transmitter uses a supply voltage of max. 24 V AC
The sensor is mounted in the cover-part of the casing. The
±10 % / 15...35 V DC.
cover is easy to detach from the back by means of snap-in
grips and detachable terminals which makes mounting
easy. Furthermore, no cables have to be disconnected, Appearance
simplifying service and replacement. The transmitter comes in a discreet white housing. The
TEMPERATURE version …-D has a LCD display showing temperature and
humidity in an alternating series.
The transmitter has a built in temperature sensor, which
gives output signal 0...10 V and has a temperature range
of 0...50 °C. In the versions ... -M the output will result Installation
in a Modbus signal. The transmitter should be mounted in a location with
good air circulation where it can be expected to give a
REL ATIVE HUMIDIT Y
representative reading. It can be mounted on a wall box or
The transmitters have a capacitive thin-film element
directly on the wall.
which gives a signal that is proportional to the relative
humidity. The measuring signal is converted by the built-
in electronics to output signal 0...10 V (corresponding to
0…100 % RH). The sensor element has rapid response to
changes in humidity, and excellent long-term stability. The
element also has good durability in contaminated environ-
ments.
MAIN OFFICE BRESSANONE TTUA
I-39042 Bressanone (BZ) tel: +39 0472 830626
via Julius-Durst-Str. 70 fax: +39 0472 831840
VAT No. IT02748450216 www.industrietechnik.it -1-
Technical data
Supply voltage 24 V AC ± 10 % / 15…35 V DC
Power consumption <1W
Transformer power >=2 VA
Working range, temperature 0…50 °C
Working range, humidity 0…100 % RH
Ambient temperature 0…50 °C
Ambient humidity 10…90 % RH (non-condensing)
Accuracy, humidity ±3 % RH at 20°C
Protection class IP30
Isolation class III
Models
Article Description Display Output signal Accuracy, temperature
TTUA RH + °C - 0…10 V + 0…10 V ± 0.4 °C
TTUA-PT100 RH + PT100, 100 Ohm (0 °C) - 0…10 V + ohm ± 0.3 °C
TTUA-PT1000 RH + PT1000, 1000 Ohm (0 °C) - 0…10 V + ohm ± 0.3 °C
TTUA-NTC1.8 RH + NTC 1.8, 1800 Ohm / 25 °C - 0…10 V + ohm ± 0.5 °C
TTUA-NTC2.2 RH + NTC 2.2, 2252 Ohm / 25 °C - 0…10 V + ohm ± 0.2 °C
TTUA-NTC10-01 RH + NTC 10, 10 kOhm / 25 °C - 0…10 V + ohm ± 0.2 °C
TTUA-NTC10-02 RH + NTC 10, 10 kOhm / 25 °C - 0…10 V + ohm ± 0.3 °C
TTUA-NTC10-03 RH + NTC 10, 10 kOhm / 25 °C - 0…10 V + ohm ± 0.25 °C
TTUA-NTC20 RH + NTC 20, 20 kOhm / 25 °C - 0…10 V + ohm ± 0.2 °C
TTUA-NI1000-01 RH + Ni1000, 1000 Ohm / 0 °C - 0…10 V + ohm ± 0.5 °C
TTUA-NI1000-02 RH + Ni1000, 1000 Ohm / 0 °C - 0…10 V + ohm ± 0.5 °C
TTUA-M RH + °C - Modbus ± 0.2 °C
TTUA-D RH + °C x 0…10 V + 0…10 V ± 0.4 °C
TTUA-D-PT100 RH + PT100, 100 Ohm (0 °C) x 0…10 V + ohm ± 0.3 °C
TTUA-D-PT1000 RH + PT1000, 1000 Ohm (0 °C) x 0…10 V + ohm ± 0.3 °C
TTUA-D-NTC1.8 RH + NTC 1.8, 1800 Ohm / 25 °C x 0…10 V + ohm ± 0.5 °C
TTUA-D-NTC2.2 RH + NTC 2.2, 2252 Ohm / 25 °C x 0…10 V + ohm ± 0.2 °C
TTUA-D-NTC10-01 RH + NTC 10, 10 kOhm / 25 °C x 0…10 V + ohm ± 0.2 °C
TTUA-D-NTC10-02 RH + NTC 10, 10 kOhm / 25 °C x 0…10 V + ohm ± 0.3 °C
TTUA-D-NTC10-03 RH + NTC 10, 10 kOhm / 25 °C x 0…10 V + ohm ± 0.25 °C
TTUA-D-NTC20 RH + NTC 20, 20 kOhm / 25 °C x 0…10 V + ohm ± 0.2 °C
TTUA-D-NI1000-01 RH + Ni1000, 1000 Ohm / 0 °C x 0…10 V + ohm ± 0.5 °C
TTUA-D-NI1000-02 RH + Ni1000, 1000 Ohm / 0 °C x 0…10 V + ohm ± 0.5 °C
TTUA-D-M RH + °C x Modbus ± 0.2 °C
CE
Low Voltage Directive (LVD) standards: This product conforms to the requirements of the European Low Voltage Directive
(LVD) 2014/35/EU through product standards EN 60730-1/A16
EMC emissions & immunity standards: This product conforms to the requirements of the EMC Directive 2014/30/EU
through product standards EN 61000-6-1 and 61000-6-3.
RoHS: This product conforms to the Directive 2011/65/EU of the European Parliament and of the Council through
standard 50581:2012.
MAIN OFFICE BRESSANONE TTUA
I-39042 Bressanone (BZ) tel: +39 0472 830626
via Julius-Durst-Str. 70 fax: +39 0472 831840
VAT No. IT02748450216 www.industrietechnik.it -2-
Revision 2017-09-11
Dimensions
85
100
30.5
Wiring
Output 0…10V + 0…10V Output 0…10V + ohm Output Modbus
Product documentation
Document Description
Instruction TTUA Instruction for installation and commissioning
The product documentation can be downloaded from www.industrietechnik.it
MAIN OFFICE BRESSANONE TTUA
I-39042 Bressanone (BZ) tel: +39 0472 830626
via Julius-Durst-Str. 70 fax: +39 0472 831840
VAT No. IT02748450216 www.industrietechnik.it -3-