Online Double Conversion UPS
i
UPS - 5 KVA - 200 KVA
Three Phase Input / Single Phase Output
Features & Benefits
• 32 bit floating point DSP controlled UPS
• Advance rectifier
• State of Art IGBT based inverter design
• 128 x 64 Graphics Display True RMS
reading of more than 25 different
parameters of UPS
• Inbuilt isolation transformer
• Internal CAN bus communication
• Multiple interfacing options
• Advanced thermal design and monitoring
• N+1 redundant fans
Falcon 1000i range of SCR/IGBT based rectifier UPS systems are designed for the industrial application. Built for working
reliably in harsh environmental conditions with IP41 and above with high operating temperatures. Falcon 1000i UPS has earth
shielding in the standard input and output transformers to maximize noise attenuation. The commercial units, at best, have only
an output transformer as standard and will add a standard double wound transformer to the input without shielding.
• The transformer and power component design calculations for the industrial products assume maximum
temperature (>400C) with N+1 fan.
• Selection criteria for consumables such as capacitors - Industrial UPS calculated at 400C full load with life >10 years
• Latest designs adapt IGBT rectifier, CAN Bus communication and protocol to suit industrial ecosystem
• On demand Natural cool systems can be designed.
Applications
• Oil and Gas Industry (onshore and offshore)
• Power Industry
• Steel Industry
• Cement Industry
• Water and waste water Industry
• Automotive Industry
• Processing plants
• Pulp and paper Industry
• Railway &Signaling
• Foundries
• Textile Industry
Technical Specification
Falcon 1000i
UPS - 5 to 200 KVA
Three Phase Input / Single Phase Output
Falcon 1000i Options
Input
Nominal Voltage 415 V AC (3 Ph + N), +/- 15% 440V, +10% / -20%
Frequency 50 Hz, +/- 6% 60Hz
Rectifier Bridge Configuration 6 Pulse APFC IGBT / 12 pulse
Power Factor >0.92 >0.98/ 0.96
I THD <30% <5% for IGBT / <15% for 12 pulse
Input Source Selector
Battery
5 to 15 KVA - 240V & 110VDC, 20 KVA - 300V DC
Nominal DC 5 to 75 KVA for 220V DC
& above 25 KVA - 360V DC
Charging Current 10A for 5 - 20 KVA, 15A for 25 - 30KVA, 20A for 35 - 60 kVA As per project requirement for Higher rating.
DC Ripple 1%
Type SMF / Lead acid / Ni Cd / Plante
Configuration Individual / Common Battery Common DC Bus
Battery Temp Compensation
Battery Earth fault / Battery reverse polarity
Output
Nominal Rating (KVA) 5 to 200 KVA
Nominal Power Factor 0.8 0.6 to unity within KVA & KW rating
Voltage 220V/230V/240V AC 110V/115V/120V AC upto 200 kVA
Voltage Stability Steady state +/- 1% 2% for 110V
For 0 to 100% step load change the output
Dynamic Response shallremain within + 5% & recover to 98% within
one cycle.( IEC 62040 – 3, Class 1)
Frequency 50 Hz, +/- 0.1% 60Hz
Voltage distortion at linear load <= 2%
Voltage distortion at non-linear load <= 5% (Ref 62040-3)
Waveform Sinusoidal
Topology IGBT Based DSP Control
Crest Factor 3:1
Overload Capacity from Inverter
110% for 60 min, 125% for 10 min, 150% for 60 sec
at Nominal Voltage
Configuration Stand Alone, Parallel Redundant Hot standby / Dual Redundant
Bypass Transformer / SCVS / Static
Voltage 200V/230V/240VAC 110V/115V/120V AC up to 200 kVA
Input Voltage Variation +/-15%
Frequency Synchronization Range 50 Hz (+/- 0.5 TO 3Hz settable) 60Hz
Sync Mode : No Break
Transfer Time Async Mode : <10 ms
Sync Mode : No Break
Retransfer Time Async Mode : Retransfer Inhibited
Manual Bypass Make Before Break Operation
Environment
Operating Temperature 0 to 50oC
Storage Temperature 0 to 70oC
Relative Humidity Upto 95% RH (Non Condensing)
Maximum Operating Altitude without 1000 m
de-rating
Physical Characteristics
Degree of protection for enclosure IP41 IP42
Ventilation Forced Air Redundant Fan
Cable Entry Bottom Top Cable Entry (Through cable Alley)
Cabinet Finish RAL 7016 Structure Finish RAL 7032/7035 OR as per Project requirement
Cabinet Steel Thickness Frame 2mm, front door 2mm, covers 1.2mm Covers 1.6mm / 2mm
Others
PFC 5 PFC
Utility socket 230V, 5A Space heater
Transducer --- 4-20 mA
UPS monitoring --- UPS MON/ HTTP/SNMP
Connectivity ports RS232 / RS485 / Ethernet Ethernet / Modbus RS 485 / Modbus TCPIP / Profibus
*Specifications are subject to change
Global Presence
Sales Offices - 02
Branch Offices - 02
Sales Offices - 03
Head and Branch
Offices in Japen - 17
Sales Offices - 03
Branch Offices - 02
Product Offerings
• Online UPS (1-800 KVA)
• Servo Controlled Voltage
Stabilizer (Oil Cooled /
Air Cooled)
• Active Harmonic Filter
• Static Transfer Switch
• Isolation Transformer
• Solar Inverter
• Medium Voltage /
Low Voltage VFD
• Instrumentation
• Factory Automation
• Process Automation
(PLC/HMI/SCADA)
Bhiwandi Service Offerings
• Comprehensive Annual
Maintenance
Contracts (CAMC)
• Annual Maintenance Contracts
(Labour - AMC)
• AMC for Third Party Power
FEI/FALCON 1000i /03/2023
Products
• Battery Replacement Services
• Power Audits
• Stabilizer Retrofits
• Rental UPS and Stabilizers
• Stabilizer Oil Replacement
• Remote Monitoring
Fuji Electric India Pvt. Ltd.
(CIN:U31900TN1985PTCO11866)
119, 120, 120A, Electrical and Electronics Industrial Estate,
Perungudi, Chennai - 600 096, Tamil Nadu, India
+91 78100 09955
enquiry.fei@fujielectric.com Scan QR code for