P43 Service Manual
P43 Service Manual
of network parameters
               P43
user’s manual
                    1
2
Contents
 1. Application ....................................................................... 5
 2. Transducer Set .................................................................. 6
 3. Basic Requirements and Operational Safety ............................... 6
 4. Installation ....................................................................... 7
 5. Service ........................................................................... 14
 6. Archive - Power Profile ....................................................... 32
 7. Software updating ............................................................. 33
 8. Error Codes ...................................................................... 35
 9. Serial Interfaces ................................................................ 53
10. Examples of P43 Transducer Programming ............................... 57
11. Technical Data .................................................................. 61
12. Execution Codes ................................................................ 62
                                                                                        3
4
1. APPLICATION
The P43 transducer is a programmable digital instrument destined for
the measurement and parameter conversion of 3 or 4-wire three-phase
power networks, in balanced and unbalanced systems.
It ensures the measurement and conversion of measured values into
standard analog current signals. Relay outputs signal the overflow of
selected quantities, and the pulse output can be used for the consump-
tion monitoring of the 3-phase active energy.
Quantities measured and calculated by the transducer:
 l phase voltages....................................................... U , U , U
                                                                               1       2     3
 l phase–to-phase voltages ...................................... U , U , U
                                                                               12       23      31
 l 3-phase mean voltage ........................................... U
 l frequency .............................................................. f			
 l energy consumption - power guard....................... P
                                                                               ord
                                                                                                    5
The transducer possesses an archive, in which 9000 last mean power
values, with time marker, suitably synchronized with the clock (15, 30
or 60 minutes) are stored.
Maximal and minimal values are measured for all quantities. Additional-
ly, there is the possibility to accommodate the transducer to external
measuring transducers. The transducer has a detection and signaling
of incorrect phase sequence. The actualization time of all accessible
quantities does not exceed 1 second. All quantities and configuration
parameters are accessible through the RS-485 interface and the USB
interface.
Transducer output signals are galvanically isolated from the input
signals and the supply. Outside the transducer, there are socket-plug
screw terminal strips, to which a conductor with maximal diameter
2,5mm2 can be connected.
2. Transducer Set
The set of the P43 transducer is composed of:
- P43 transducer                     1 pc
- user’s manual                      1 pc
- guarantee card                     1 pc
- CD disc                            1 pc
When unpacking the transducer, please check whether the type
and execution code on the data plate correspond to the order.
6
l   Before switching the transducer on, one must check the
    correctness of connections to the network.
l   The removal of the transducer housing during the guarantee
    contract period may cause its cancellation.
l   The P43 transducer is destined to be installed and used in
    industrial electromagnetic environment conditions.
l   One must remember that in the building installation, a switch or a
    circuit-breaker should be installed. This switch should be located
    near the device, easy accessible by the operator, and suitably
    marked.
4. INSTALLATION
4.1. Fitting
The P43 transducer is adapted to be mounted on a 35 mm rail acc. to EN 60715.
The overall drawing and the fitting way are presented on the fig.1.
                                                                           7
4.2. External Connection Diagrams
8
Direct measurement in a four-wire network.
                                             9
     Measurement with the use of current transformers in
                  a four-wire network.
10
       Indirect measurement with the use of
     3 current transformers and 2 or 3 voltage
        transformers in a four-wire network.
11
       Direct measurement in a three- wire network.
12
       Indirect measurement with the use of
     2 current transformers and 2 or 3 voltage
       transformers in a three-wire network.
13
5. SERVICE
                                                       Transducer
                                                       state diode
                                                       Diode of data
                                                       transmission through
                                                       RS-485
                                                       Diodes of AL1
                                                       - AL4 alarms
14
naled by a pulsing of the Tx diode.
The switching of the relay 1 - 4 on causes the lighting of the AL1 - AL4
diode (fig. 4).
                                                                       15
After closing the creator, the system detect immediately the succes-
sive device – USB Serial Port (fig. 6.). The creator for detection a new
hardware will start again.
After the successful ending of the installation, the system will inform
about the installation of a new device (fig. 7.). Two new devices ap-
pear in the device manager – Transducer P43 and Port COM named:
Transducer P43, acc. to the fig. 8.
16
                                      6
Fig. 8. View of the device manager window together with the installed
         P43 transducer, which the port COM6 is assigned to.
After the connection configuration, one must choose from the Device ->
Transducers -> P43v2 menu, and next click the Readout icon in order
to read out all parameters. One can also read out parameters indivi-
dually in each group, clicking the Refresh button. In order to change
parameters, one must write the new value in the parameter window and
click the Apply button.
18
5.4.1 Setting of Transmission Parameters
After choosing the group – transmission parameters, it is possible to
configure following elements:
         a) address – address for the communication with the P43
              transducer through the RS-485 interface from the range
              1...247. The value 1 is normally set up by the manufacturer.
         b) baud rate – the communication rate through the RS-485
              interface from the range (4800, 9600, 19200, 38400 bit/sec.)
              The value 9600 is set up by the manufacturer.
         c) transmission mode – The transmission mode through the
              RS485 interface from the range (RTU 8N2, RTU 8E1,
              RTU 8O1, RTU 8N1). The transmission mode is normally
              set up on RTU 8N2 by the manufacturer.
                                                                       19
5.4.2 Setting of Measurement Parameters
After choosing the group: ratios, power synchronization, time, follo-
wing elements can be configured (fig. 11.):
       a) current transformer ratio. The multiplier is used to
            recalculate the current in the transformer primary
            side. It is set up on 1 by the manufacturer.
       b) voltage transformer ratio. The multiplier is used to
            recalculate the voltage in the transformer primary
            side. It is set up on 1 by the manufacturer.
       c) way to synchronize the mean power:
            - 15 minutes’ walking window – mean power PAV
            will be recalculated for the last 15 minutes, actualized
            every 15 seconds, i.e. walking window,
       - measurement synchronized with the clock every 15, 30
            or 60 minutes - mean power PAV will be actualized every
            15, 30 or 60 minutes synchronized with the external real
            clock (fig. 12).
       It is set up on the walking window by the manufacturer.
20
Fig. 12. Measurement of the 15 minutes’ active mean power synchro-
                           nized with the clock.
       d) ordered power. Ordered power in percentage of rated power
       (see chapter 9, example 2).
       e) pulse ratio for the pulse output (for active energy).
       f) 3-phase measurement mode. 3- and 4-wire measurement.
22
     06        Coefficient of active power of phase L1                 1
     07        Coefficient tgj of phase L1                             1
     08        Voltage of phase L2                                 Un [V] *
     09        Current in the wire of phase L2                      In [A] *
     10        Active power of phase L2                    Un x In x cos(0°) [W] *
     11        Reactive power of phase L2                 Un x In x sin(90°) [var] *
     12        Apparent power of phase L2                       Un x In [VA] *
     13        Coefficient of active power of phase L2                 1
     14        Coefficient tgj of phase L2                             1
     15        Voltage of phase 3                                  Un [V] *
     16        Current in the wire of phase L3                      In [A] *
     17        Active power of phase L3                    Un x In x cos(0°) [W] *
     18        Reactive power of phase L3                 Un x In x sin(90°) [var] *
     19        Apparent power of phase L3                       Un x In [VA] *
     20        Coefficient of active power of phase L3                 1
     21        Coefficient tgj of phase L3                             1
     22        3-phase mean voltage                                Un [V] *
     23        3-phase mean current                                 In [A] *
     24        3-phase active power                      3 x Un x In x cos(0°) [W] *
     25        3-phase reactive power                    3 x Un x In x sin(90°) [var] *
     26        3-phase reactive power                         3 x Un x In [VA] *
     27        Power factor of 3-phase active power                    1
     28        3-phase coefficient tgj                                 1
     29        Frequency                                           100 [Hz]
     30        Phase-to-phase voltage L1-L2                        3 Un [V] *
     31        Phase-to-phase voltage L2-L3                        3 Un [V] *
     32        Phase-to-phase voltage L3-L1                        3 Un [V] *
     33        Phase-to-phase mean voltage                         3 Un [V] *
     34        mean active power                         3 x Un x In x cos(0°) [W] *
                used active ordered power
      35                                                           100 [%]
                (used energy)
* Un, In – Rated values of transducer voltage and current
                                                                                     23
     b) kind of the alarm output operation – choose one from 10 modes
        n-on, n-off, on, off, h-on and h-off, A3non, A3nof, A3_on, A3_of.
        Working modes have been presented on the fig. 14,
     c) lower value of alarm switching – percentage value of the state
        change of the chosen signal,
     d) upper value of alarm switching – percentage value of the state
        change of the chosen signal,
     e) switching delay of the alarm. Delay time in seconds when
        switching the alarm state,
     f) switching off delay of the alarm. Delay time in seconds when
        switching off the alarm state,
     g) deadlock of alarm re-switching. Time, after which the alarm 		
        can be switched on again.
Caution! The setup of the value Aoff ³ Aon causes the alarm switching off.
b) n-off
24
c) on
d) off
Other alarm types: h-on – always switched on; h-off – always switched off.
  –– A3non – when the “n-on” alarm type occurs on any of the phases
      - the relay switches on . When all alarms fade away, the relay
      switches off.
  –– A3nof – when the “n-of” alarm type occurs on any of the phases
      - the relay switches on . When all alarms fade away, the relay
      switches off.
  –– A3_on – when the “on” alarm type occurs on any of the phases
      - the relay switches on . When all alarms fade away, the relay
      switches off
  –– A3_of – when the “off” alarm type occurs on any of the phases
      - the relay switches on . When all alarms fade away, the relay
      switches off
In the “A3” alarm series, the alarm value must range from 0-7. They work
with equal Aoff and Aon hysteresis thresholds for all of the phases.
                                                                        25
5.4.6 Setup of analog output parameters
After choosing the group: output 1-4, it is possible to configure following
output parameters:
      a) assignment of the parameter to the analog output. Kind of
          signal, on which the output has to react acc. to the table 1,
      b) lower value of the input range. Percentage value of the
          chosen signal,
      c) upper value of the input range. Percentage value of the
          chosen signal,
      d) lower value of the output range. Output signal value in mA,
      e) upper value of the output range. Output signal value in mA,
      f)  working mode of the analog output. Following modes are
          accessible: normal work lower value, upper value. Both
          alarms are set up in the normal mode by the manufacturer.
     g)    value on the output by false input parameter value (1e20) in mA.
5.4.7 Clock
After choosing the group: clock it is possible to set up time and date and
synchronize the clock with the time on the PC computer.
                                                                       Table 2
                                                                   Manufac-
 Parameter description               Range/value
                                                                  turer value
   Ratio of the current
                                       1...10000                       1
       transformer
   Ratio of the voltage
                                        1...4000                      1.0
       transformer
                           - 15 minutes’ walking window
                             (recording in the archive every
  Synchronization of the                                            walking
                             15 minutes); measurement
   active mean power:                                               window
                             synchronized with the clock
                             every 15, 30 or 60 minutes
                                                                   0 - without
   The way of min. and
                                           0,1                        errors
   max. value storage
                                                                  -1e20, 1e20
                                                                  0 - inductive
   The way of passive
                                           0,1                   and capacitive
   energy calculation
                                                                     energy
     Ordered power                    0...144,0 %                  100,0 %
  Quantity on the alarm
                              0...35 (acc. to the table 1)            24
   output No 1, 2, 3, 4
   Output type of the       n-on; n-off; on; off; h-on; h-off;
                                                                     n-on
     alarm 1, 2, 3, 4        A3non, A3nof, A3_on, A3_of
                                                                              27
                                                                  Table 2
 Lower value of the alarm
                                   -144.0...144.0 %            99,0 %
   1, 2, 3, 4 switching
 Upper value of the alarm
                                   -144.0...144.0 %           101,0 %
      1, 2, 3, 4 switching
   Switching-on delay of
                                   0...900 seconds               0
     the alarm 1, 2, 3, 4
   Switching-off delay of
                                   0...900 seconds               0
     the alarm 1, 2, 3, 4
      Deadlock of alarm
                                   0...900 seconds               0
    1,2,3,4 re-switching
    Quantity on the con-
    tinuous output No 1,      0...35 (acc. to the table 1)       24
             2, 3, 4
      Lower value of the
  input range in % of the
                                   -144.0...144.0 %             0.0%
 rated range of the input
         No 1, 2, 3, 4
    Upper value of the
  input range in % of the
                                   -144.0...144.0 %            100.0%
 rated range of the input
       No 1, 2, 3, 4
 Lower value of the out-
 put range of the output          -20.00...20.00 mA           0.00 mA
       No 1, 2, 3, 4
    Upper value of the
    output range of the            0.01...20.00 mA            20.00 mA
        output No 1
                                      normal work,
   Manual switching of       the lower value of the output
 the analog output 1, 2,            range is set up,         normal work
        3, 4 on:             the upper value of the output
                                    range is set up.
 Pulse quantity for pulse
                                    5000 - 20000                5000
         output
      Address in the
                                       1... 247                  1
     MODBUS network
     Transmission mode            8n2, 8e1, 8o1, 8n1            8n2
         Baud rate            4800, 9600, 19200, 38400          9600
28
5.4.9 Measured Values
After choosing the group: - measured values, all parameters measured
by the transducer are displayed in the form of a list (fig. 16.).
                                                                 29
5.4.10 Minimal and Maximal Values
After choosing the group: - minimal and maximal values, minimal and
maximal values of individual parameters measured by the transducer
in the form of a list are displayed (fig. 17.).
Fig. 17. View of the window of the min. and max. value group
30
   Fig. 18. View of the window of the power profile archive group
Fig. 19. View of the window of the information about the device group
                                                                      31
6. Archive – Power Profile
The P43 transducer is equipped with an archive allowing to store up to
1000 measurements of averaged active power. The averaged active
power PAV can be archived with time intervals 15, 30, 60 minutes (syn-
chronized with the internal time clock) according to synchronization
type in register 4005.
In case of work in the walking window mode, the arichiving follows in full
quarters of an hour, despite the fact, that the step of the walking window
lasts 15 seconds and the walking window function can be activated any
moment (fig. 12). Direct access to the archive is for 15 records including
date, time and value located in the range of addresses 1000 - 1077.
In register 1000 is placed the position of the first (the oldest one) archived
sample, and in register 1001 is the position of the last archived sample
(the latest one).
In register 1002 is placed the first record of the fifteen available records
located in registers 1003 - 1077. After writing the first read record (1
- 9000), the data of 15 records for read-out are updated.
Values 1e20 are in registers, in which samples are not written yet.
The archive is organized in a shape of a circular buffer. After writing the
nine thousandth value, the next value overwrites the oldest value with the
number 0, and successively the next with the number 1, etc. If the value
of the register 1000 is higher than 1001, it means, that the buffer at least
once was overflowed. For example value 15 in the register 1000 and 14
in register 1001 means, that there was more than nine thousand of sam-
ples and the oldest samples are from the record 15 to 9000, next from the
record 1 to the latest record with the number 14.
Erasing of average power or change of the average time do not erase the
archive. Automatic erasing of the archive and average power is made
after current or voltage transformer ratio is changed.
32
7. SOFTWARE UPDATING
The P43 transducer (from the version 2.50) comes with the implemented
function that allows for updating the software from a PC with LPCon sof-
tware. Free LPCon program and the updating files are available on our
website www.lumel.com.pl. Either RS485 port and USB port can be used
to carry out the updating process.
                                               b)
a)
Note! After updating the software the manufacturer’s settings for the
transducer ought to be set, therefore it is advisable to store the transdu-
cer parameters before its updating using LPCon software.
After LPCon has been started, one ought to set serial port, baut rate, mode
and the transducer address in Options. Then choose the P43 transducer
from the menu Devices and click the icon Read in order to read all set
parameters (necessary for their later restoration). After selecting from the
menu Updating the option Device software updating, the Lumel Updater
(LU) window opens – Fig. 20 b. Press Connect. The information window
Messages contains information on the updating process. At the correctly
opened port, the message Port opened displays.
                                                                        33
Entering the updating mode in the transducer is carried out remotely by
LU program (based on the settings in LPCon - adres, mode, baud rate,
port Com) either through RS485 or USB. Pulsating of the transducer
state diode in green signals readiness for updating, whereas the LU
program displays the message Device found and the name and version
of the program of the conneted device. One should press the button ...
and indicate the transducer updating file. At the correctly opened file,
the information File opened displays. One should press Send button.
After updating being successfully completed the transducer switches
to normal work, whereas the information window displays Done and the
duration time of the updating. After the LU window closure, one should
go to the parameters group Restoring manufacturer’s settings, mark the
option and press Apply button. Then press the icon Save in order to save
readout initially set parameters. The up-to-date software version can also
be checked via reading About P41 transducer from LPCon program.
Note! Switching the supply off during the software updating process may result
in permenent damage of the transducer!
Note! If an error occurs during the upgrade, re-upgrade can be performed only
by a USB port.
34
8. Error Codes
After connecting the transducer to the network, messages about errors can
appear. Causes of errors are presented below:
- the state diode pulsates in red – lack of calibration or the non-volatile
  memory is damaged. One must return the transducer to the manu-
  facturer,
- the state diode lights in red – inappropriate work parameters; one
  must configure the transducer again.
- the state diode pulsate alternately in red and green - error of phase
  connection sequence; one must interchange the connection of phase
  L2 with the phase L3.
9. Serial Interfaces
                                                                        35
9.2. USB Interface – Set of Parameters
l identifier                        0xC6 (198)
l transducer address                1
l baud rate                         9.6 kbit/s
l working mode                      Modbus RTU
l information unit                  8N2
l maximal response time             400 ms
l maximal number of bytes
  during the readout/write:         - 56 registers - 4 bytes
		                                  - 109 registers - 2 bytes
l implemented functions             03, 04, 06,16, 17
  - 03, 04 readout of registers,
  - 06 write of one register,
  - 16 write of n registers,
  - 17 device identifying.
36
                                                                 Table 3
 Range of      Type of
                                            Description
addresses       value
                                                                       37
                                                                     Table 4
     Register   Ope-
     address      ra-                     Description
      16 bits   tions
       1000        R    Position of the oldest archived mean power
      1001       R      Position of the youngest archived mean power
      1002      R/W     First available record - NrBL (range 1...9000)
                        Year of archived mean power with the number
      1003       R
                        NrBL + 0
                        Month* 100 + archived day of mean power with the
      1004       R
                        number NrBL + 0
                        Hour* 100 + archived minute of mean power with
      1005       R
                        the number NrBL + 0
      1006       R      Archived value of mean power with the number
      1007       R      NrBL + 0 of float type - 4 bytes in order 3-2-1-0
                        Archived year of mean power with the number
      1008       R
                        NrBL + 1
                        Archived month, day of mean power with the num-
      1009       R
                        ber NrBL + 1
                        Archived hour, minute of mean power with the
      1010       R
                        number NrBL + 1
      1011       R      Archived value of mean power with the number
      1012       R      NrBL + 0 of float type - 4 bytes in order 3-2-1-0
38
                                                                  Table 5
Regi-
        Ope-                                                        By
 ster
          ra-    Range                Description                   de-
 ad-
        tions                                                      fault
dress
4000    RW         0                    Reserved                     0
4001    RW           0                 Reserved                      0
4002    RW           0                 Reserved                      0
4003    RW      1...10000      Current transformer ratio             1
4004    RW      1...40000    Voltage transformer ratio x 10         10
                            Synchronization of mean active
                            power:
                            0 –15 minutes’ walking window
                                (recording synchronized
                                every 15 min with the clock.)
4005    RW        0...3     1 – measurement synchronized             0
                                every 15 min with the clock.
                            2 – measurement synchronized
                                every 30 min with the clock.
                            3 – measurement synchronized
                                every 60 min with the clock.
4006    RW         0                    Reserved                     0
                            The way of minimal and maximal
4007    RW        0.1                value recording                 0
                             0 -without errors, 1 - with errors
4008    RW        0.1                   Reserved                     0
                               The way of reactive energy
4009    RW      0...2359               calculation                   0
                             0 -without errors, 1 - with errors
4010    RW      0...1440             Ordered power                 1000
                                Erasing of energy counter:
                              0 - without changes, 1 - erase
4011    RW        0..3                                               0
                             active energy, 2 - erase passive
                               energy, 3 - erase all energy
4012    RW        0.1       Erasing of mean active power PAV         0
                              Erasing of mean active power
4013    RW         0.1                                               0
                                      PAV archive
4014    RW         0.1          Erasing of min. and max.             0
                                                                         39
                                 Alarm output 1 - quantity on the
 4015   RW       0.1...35                                                0
                                    output (code acc. to table 6)
                                 Alarm output 1 - type: 0 – n-on,
                                        1– n-oFF, 2 – on, 3 - oFF,
 4016   RW         0..9                                                  0
                                    4 – h-on, 5 – h-oFF, 6 - A3non,
                                     7 - A3nof, 8 - A3_on, 9 - A3_of
             -1440...0...1440   Alarm output 1 - lower alarm switch-
 4017   RW                                                              990
                  [o/oo]          ing value of the rated input range
             -1440...0...1440   Alarm output 1 - upper alarm switch-
 4018   RW                                                              1010
                  [o/oo]           ing value of the rated input range
 4019   RW      0...900 s       Alarm output 1 - switching-on delay      0
                                Alarm output 1 - alarm switching-off
                                 delay (for ordered power quantity
 4020   RW      0...900 s                                                0
                                [register 4015 = 35] this parameter
                                               is excluded
                                      Alarm output 1 - deadlock
 4021   RW      0...900 s                    of re-switching
                                                                         0
 4022   RW         0.1                          Reserved                 0
                                  Alarm output 2 -quantity on the
 4023   RW       0.1...35                                                24
                                 output (code acc.to the table 6)
                                  Alarm output 2 - type: 0 – n-on,
                                        1– n-oFF, 2 – on, 3 - oFF,
 4024   RW        0...9                                                  3
                                    4 – h-on, 5 – h-oFF, 6 - A3non,
                                     7 - A3nof, 8 - A3_on, 9 - A3_of
             -1440...0...1440   Alarm output 2 - lower alarm switch-
 4025   RW                       ing value of the rated input range     990
                  [o/oo]
             -1440...0...1440   Alarm output 2 - upper alarm switch-
 4026   RW                                                              1010
                  [o/oo]         ing value of the rated input range
                                Alarm output 2 - alarm switching-on
 4027   RW      0...900 s                                                0
                                               delay
                                  Alarm output 2 - alarm switch-
                                 ing-off delay (for ordered power
 4028   RW      0...900 s                                                0
                                 quantity [register 4023 = 35] this
                                      parameter is excluded)
                                    Alarm output 2 - deadlock
 4029   RW      0...900 s                                                0
                                          of re-switching
 4030   RW         0,1                       Reserved                    0
                                Alarm output 3 - quantity on the
 4031   RW       0,1...35                                                24
                                    output (code acc. to table 6)
                                 Alarm output 3 - type: 0 – n-on,
                                     1– n-oFF, 2 – on, 3 - oFF,
 4032   RW        0...9                 4 – h-on, 5 – h-oFF,             0
                                       6 - A3non, 7 - A3nof,
                                        8 - A3_on, 9 - A3_of
40
            -1440...0...1440   Alarm output 3 - lower alarm switch-
4033   RW                                                               990
                 [o/oo]         ing value of the rated input range
            -1440...0...1440   Alarm output 3 - upper alarm switch-
4034   RW                                                               1010
                 [o/oo]         ing value of the rated input range
                               Alarm output 3 - alarm switching-on
4035   RW      0...900 s                                                 0
                                               delay
                                 Alarm output 3 - alarm switch-
                                ing-off delay (for ordered power
4036   RW      0...900 s                                                 0
                                quantity [register 4023 = 35] this
                                    parameter is excluded)
                                   Alarm output 3 - deadlock
4037   RW      0...900 s                                                 0
                                         of re-switching
4038   RW         0,1                       Reserved                     0
                               Alarm output 4 - quantity on the
4039   RW       0,1...35                                                 24
                                   output (code acc. to table 6)
                                Alarm output 4 - type: 0 – n-on,
                                    1– n-off, 2 – on, 3 - oFF,
4040   RW        0...9                 4 – h-on, 5 – h-oFF,              0
                                      6 - A3non, 7 - A3nof,
                                       8 - A3_on, 9 - A3_of
            -1440...0...1440   Alarm output 4 - lower alarm switch-
4041   RW                                                               990
                 [o/oo]         ing value of the rated input range
            -1440...0...1440   Alarm output 4 - upper alarm switch-
4042   RW                                                               1010
                 [o/oo]         ing value of the rated input range
                               Alarm output 4 - alarm switching-on
4043   RW      0...900 s                                                 0
                                               delay
                                 Alarm output 4 - alarm switch-
                                ing-off delay (for ordered power
4044   RW      0...900 s                                                 0
                                quantity [register 4039 = 35] this
                                     parameter is excluded)
                                  Alarm output 3 - deadlock of
4045   RW      0...900 s                                                 0
                                           re-switching
4046   RW         0,1                       Reserved                     0
                               Continuous output 1 - quantity on
4047   RW      0...15258                                                 24
                               the output (code acc. to table 6)
                                 Continuous output 1 - type: 0
4048   RW      0...65535        - (0 ...20) mA; 1 - (4...20) mA; 2       2
                                          - (-20...20) mA
                               Continuous output 1 - lower value of
            -1440...0...1440
4049   RW                      the input range in [o/oo] of the rated    0
                 [o/oo]
                                            input range
                                                                              41
                                Continuous output 1 - upper value of
             -1440...0...1440
 4050   RW                      the input range in [o/oo] of the rated   1000
                  [o/oo]
                                            input range
             -2400...0...2400   Continuous output 1 - lower value of
 4051   RW                                                                0
                 [10 mA]          the current output range [10 mA]
                                Continuous output 1 - upper value of
 4052   RW   1...2400 [10 mA]                                            2000
                                 the current output range [10 mA]
                                Continuous output 1 - manual switch-
                                        ing on: 0 - normal work,
 4053   RW        0...2                                                   0
                                  1- value set from the register 4051,
                                2 - value made from the register 4052
                                 Continuous output 1 - value on the
 4054   RW    -24...24 [mA]                                               24
                                            output by error
                                Continuous output 2 - quantity on the
 4055   RW       0,1...35                                                 24
                                    output (code acc. to the tab.6)
                                     Continuous output 2 - type:
 4056   RW        0...2          0 - (0 ...20) mA; 1 - (4...20) mA;       2
                                           2 - (-20...20) mA
                                Continuous output 2 - lower value of
             -1440...0...1440
 4057   RW                      the input range in [o/oo] of the rated    0
                  [o/oo]
                                              input range
                                Continuous output 2 - upper value of
             -1440...0...1440
 4058   RW                      the input range in [o/oo] of the rated   1000
                  [o/oo]
                                              input range
             -2400...0...2400   Continuous output 2 - lower value of
 4059   RW                                                                0
                 [10 mA]          the current output range [10 mA]
                                Continuous output 2 - upper value of
 4060   RW   1...2400 [10 mA]                                            2000
                                  the current output range [10 mA]
                                Continuous output 1 - manual switch-
                                        ing on: 0 - normal work,
 4061   RW        0...2                                                   0
                                  1- value set from the register 4059,
                                2 - value made from the register 4060
                                 Continuous output 2 - value on the
 4062   RW    -24...24 [mA]                                               24
                                            output by error
                                Continuous output 3 - quantity on the
 4063   RW       0,1...35                                                 24
                                    output (code acc. to the tab.6)
                                    Continuous output 3 - type:
 4064   RW        0...2          0 - (0 ...20) mA; 1 - (4...20) mA;       2
                                           2 - (-20...20) mA
                                Continuous output 3 - lower value of
             -1440...0...1440
 4065   RW                      the input range in [o/oo] of the rated    0
                  [o/oo]
                                              input range
42
                               Continuous output 3 - upper value of
            -1440...0...1440
4066   RW                      the input range in [o/oo] of the rated   1000
                 [o/oo]
                                           input range
            -2400...0...2400   Continuous output 3 - lower value of
4067   RW                                                                0
                [10 mA]          the current output range [10 mA]
                               Continuous output 3 - lower value of
4068   RW   1..2400 [10 mA]                                             2000
                                the current output range [10 mA]
                               Continuous output 1 - manual switch-
                                       ing on: 0 - normal work,
4069   RW        0...2                                                   0
                                 1- value set from the register 4067,
                               2 - value made from the register 4068
                                Continuous output 3 - value on the
4070   RW    -24...24 [mA]                                               24
                                           output by error
                               Continuous output 4 - quantity on the
4071   RW       0,1...35                                                 24
                                   output (code acc. to the tab.6)
                                   Continuous output 4 - type:
4072   RW        0...2          0 - (0 ...20) mA; 1 - (4...20) mA;       2
                                          2 - (-20...20) mA
                               Continuous output 4 - lower value of
            -1440...0...1440
4073   RW                      the input range in [o/oo] of the rated    0
                 [o/oo]
                                             input range
                               Continuous output 4 - upper value of
            -1440...0...1440
4074   RW                      the input range in [o/oo] of the rated   1000
                 [o/oo]
                                             input range
            -2400...0...2400   Continuous output 4 - lower value of
4075   RW                                                                0
                [10 mA]          the current output range [10 mA]
                               Continuous output 4 - lower value of
4076   RW   1..2400 [10 mA]                                             2000
                                 the current output range [10 mA]
                               Continuous output 1 - manual switch-
                                       ing on: 0 - normal work,
4077   RW        0...2                                                   0
                                 1- value set from the register 4075,
                               2 - value made from the register 4076
                                Continuous output 1 - value on the
4078   RW    -24...24 [mA]                                               24
                                           output by error
4079   RW    5000...20000        Pulse quantity for pulse output        5000
4080   RW       1...247        Address in the MODBUS network             1
                                Transmission mode: 0 -> 8n2, 1
4081   RW        0...3                                                   0
                                   -> 8e1, 2 -> 8o1, 3 -> 8n1
                               Baud rate: 0 -> 4800, 1 -> 9600,
4082   RW        0...3                                                   1
                                    2 -> 19200, 3 -> 38400
                                Update the change of transmis-
4083   RW         0,1                                                    0
                                        sion parameters
                                                                              43
 4084   RW     0...59                    seconds                      0
 4085   RW    0...2359            Hour*100 + minutes                  0
 4086   RW   101...1231           Month*100 + minutes                1201
 4087   RW   2009...2100                    Year                     2010
                            Record of standard parameters
 4088   RW       0,1        (with zero adjustment of energy,          0
                              min, max and mean power)
                              Active input energy, two most
 4089   R     0...15258                                               0
                                     significant bytes
                           Active input energy, two least signifi-
 4090   R     0...65535                                               0
                                         cant bytes
                              Active output energy, two most
 4091   R     0...15258                                               0
                                     significant bytes
                             Active output energy, two least
 4092   R     0...65535                                               0
                                     significant bytes
                            Reactive inductive energy, two
 4093   R     0...15258                                               0
                                   most significant bytes
                             Reactive inductive energy, two
 4094   R     0...65535                                               0
                                 least significant bytes
                            Reactive capacitive energy, two
 4095   R     0...15258                                               0
                                   most significant bytes
                            Reactive capacitive energy, two
 4096   R     0...65535                                               0
                                 least significant bytes
 4097   R          0                     Reserved                     0
 4098   R          0                     Reserved                     0
 4099   R          0                     Reserved                     0
 4100   R          0                     Reserved                     0
 4101   R    0... 65535    Status register 1 - description below      -
 4102   R    0... 65535    Status register 2 - description below      -
 4103   R    0... 65535      Serial number, two older bytes           -
 4104   R    0... 65535    Serial number, two younger bytes           -
 4105   R    0... 65535         Program version (x 100)              100
 4106   R    0..65535                    reserved                     0
 4107   R    0..65535                    reserved                    104
                            Measurement mode: 0 -3Ph4W,
 4108   RW       0,1                                                  0
                                         1- 3Ph3W
44
In parenthesis [ ]: resolution or unit is suitably placed.
                                                                  45
Bit 7 – reserved                        Bit 3 – „1” – alarm output 4 switched on
Bit 6 – reserved                        Bit 2 – „1” – alarm output 3 switched on
Bit 5 – reserved                        Bit 1 – „1” – alarm output 2 switched on
Bit 4 – reserved                        Bit 0 – „1” – alarm output 1 switched on
Rejestr Statusu 3 (rejestr 4109):
Bity 15-12 – „1” - zarezerwowany
Bit 11 – „1” – wystąpienia alarmu 4 typu A3xxx w fazie L3
Bit 10 – „1” – wystąpienia alarmu 4 typu A3xxx w fazie L2
Bit 9 – „1” – wystąpienia alarmu 4 typu A3xxx w fazie L1
Bit 8 – „1” – wystąpienia alarmu 3 typu A3xxx w fazie L1
Bit 7 – „1” – wystąpienia alarmu 3 typu A3xxx w fazie L2
Bit 6 – „1” – wystąpienia alarmu 3 typu A3xxx w fazie L1
Bit 5 – „1” – wystąpienia alarmu 2 typu A3xxx w fazie L3
Bit 4 – „1” – wystąpienia alarmu 2 typu A3xxx w fazie L2
Bit 3 – „1” – wystąpienia alarmu 2 typu A3xxx w fazie L1
Bit 2 – „1” – wystąpienia alarmu 1 typu A3xxx w fazie L3
Bit 1 – „1” – wystąpienia alarmu 1 typu A3xxx w fazie L2
Bit 0 – „1” – wystąpienia alarmu 1 typu A3xxx w fazie L1
                                                                            Table 6
               Ad-
                      Operations
              dress
 Address
3Ph /4W
                                                                                      3Ph /3W
              of 32
                                                                     Unit
  of 16 bit                                  Description
               bit
 registers
              regi-
              sters
6000/7000     7500      R          Voltage of phase L1               V       √         x
6002/7002     7501      R          Current of phase L1               A       √         √
6004/7004     7502      R          Active power of phase L1          W       √         x
6006/7006     7503      R          Reactive power of phase L1        Var     √         x
6008/7008     7504      R          Apparent power of phase L1        VA      √         x
6010/7010     7505      R          Active power factor of phase L1    -      √         x
                                   Reactive power to active power
6012/7012     7506      R          ratio of phase L1                  -      √         x
6014/7014     7507      R          Voltage of phase L2               V       √         x
6016/7016     7508      R          Current of phase L2               A       √         √
6018/7018     7509      R          Active power of phase L2          W       √         x
6020/7020     7510      R          Reactive power of phase L2        Var     √         x
6022/7022     7511      R          Apparent power of phase L2        VA      √         x
6024/7024     7512      R          Active power factor of phase L2    -      √         x
46
                       Reactive power to active power
6026/7026   7513   R   ratio of phase L2                   -    √   x
6028/7028   7514   R   Voltage of phase L3                V     √   x
6030/7030   7515   R   Current of phase L3                A     √   √
6032/7032   7516   R   Active power of phase L3           W     √   x
6034/7034   7517   R   Reactive power of phase L3         Var   √   x
6036/7036   7518   R   Apparent power of phase L3         VA    √   x
6038/7038   7519   R   Active power factor of phase L3     -    √   x
                       Reactive power to active power
6040/7040   7520   R   ratio of phase L3                   -    √   x
6042/7042   7521   R   Mean 3-phase voltage               V     √   x
6044/7044   7522   R   Mean 3-phase current               A     √   √
6046/7046   7523   R   3-phase active power               W     √   √
6048/7048   7524   R   3-phase reactive power             Var   √   √
6050/7050   7525   R   3-phase apparent power             VA    √   √
6052/7052   7526   R   Mean active power factor            -    √   √
                       Mean ratio of reactive power
6054/7054   7527   R   to active power                     -    √   √
6056/7056   7528   R   Frequency                          Hz    √   √
6058/7058   7529   R   Phase-to-phase voltage L1-L2       V     √   √
6060/7060   7530   R   Phase-to-phase voltage L2-L3       V     √   √
6062/7062   7531   R   Phase-to-phase voltage L3-L1       V     √   √
6064/7064   7532   R   Mean phase-to-phase voltage        V     √   √
                       15, 30, 60 minutes’ 3-phase act.
6066/7066   7533   R   power (P1+P2+P3)                   W     √   √
6068/7068   7534   R   THD U1                             %     √   x
6070/7070   7535   R   THD U2                             %     √   x
6072/7072   7536   R   THD U3                             %     √   x
6074/7074   7537   R   THD I1                             %     √   x
6076/7076   7538   R   THD I2                             %     √   x
6078/7078   7539   R   THD I3                             %     √   x
6080/7080   7540   R   cosinus angle between U1 and I1     -    √   x
6082/7082   7541   R   cosinus angle between U2 and I2     -    √   x
6084/7084   7542   R   cosinus angle between U3 and I3     -    √   x
                                                                    47
6086/7086   7543   R   mean 3-phase cosinus                    -     √   √
                                                               o
6088/7088   7544   R   angle between U1 and I1                       √   x
                                                               o
6090/7090   7545   R   angle between U2 and I2                       √   x
6092/7092   7546   R   angle between U3 and I3                 o
                                                                     √   x
                       Current in neutral lead (evalueted
6094/7094   7547   R                                          A      √   x
                       from vectors)
                       3-phase active input energy
                       (number of register 7549 overfills,   100
6096/7096   7548   R                                                 √   √
                       setting to zero after exceeding       MWh
                       99999999.9 kWh)
                       3-phase active input energy (watt-
6098/7098   7549   R                                         kWh     √   √
                       hour meter counting to 99999.9 kWh)
                       3-phase active output energy
                       (number of register 7551 overfills,   100
6100/7100   7550   R                                                 √   √
                       setting to zero after exceeding       MWh
                       99999999.9 kWh)
                       3-phase active output energy
6102/7102   7551   R   (watt-hour meter counting to          kWh     √   √
                       99999.9 kWh)
                       3-phase reactive inductive energy
                       (number of register 7553 overfills,    100
6104/7104   7552   R                                                 √   √
                       setting to zero after exceeding       MVarh
                       99999999.9 kVarh)
                       3-phase reactive inductive energy
6106/7106   7553   R   (watt-hour meter counting to          kVarh   √   √
                       99999.9 kWh)
                       3-phase active output energy
                       (number of register 7555 overfills,    100
6108/7108   7554   R                                                 √   √
                       setting to zero after exceeding       MVarh
                       99999999.9 kVarh)
                       3-phase reactive capacitive
6110/7110   7555   R   energy (watt-hour meter counting      kVarh   √   √
                       to 99999.9 kWh)
6112/7112   7556   R   Reserved                                      √   √
6114/7114   7557   R   Reserved                                      √   √
6116/7116   7558   R   Reserved                                      √   √
6118/7118   7559   R   Reserved                                      √   √
6120/7120   7560   R   Time - seconds                        sec     √   √
6122/7122   7561   R   Time - hours, minutes                   -     √   √
48
6124/7124   7562   R   Date - month, day                       -    √    √
6126/7126   7563   R   Date - year                             -    √    √
6128/7128   7564   R   Stering up the analog output 1         mA    √    √
6130/7130   7565   R   Stering up the analog output 2         mA    √    √
6132/7132   7566   R   Stering up the analog output 3         mA    √    √
6134/7134   7567   R   Stering up the analog output 4         mA    √    √
                       Energy consumption in percentages in
6136/7136   7568   R                                          %     √    √
                       “power guard” modus
6138/7138   7569   R   Status 3                                -    √    √
6140/7140   7570   R   Status 1                                -    √    √
6142/7142   7571   R   Status 2                                -    √    √
6144/7144   7572   R   Voltage L1 min                         V     √    x
6146/7146   7573   R   Voltage L1 max                         V     √    x
6148/7148   7574   R   Voltage L2 min                         V     √    x
6150/7150   7575   R   Voltage L2 max                         V     √    x
6152/7152   7576   R   Voltage L3 min                         V     √    x
6154/7154   7577   R   Voltage L3 max                         V     √    x
6156/7156   7578   R   Current L1 min                         A     √    √
6158/7158   7579   R   Current L1 max                         A     √    √
6160/7160   7580   R   Current L2 min                         A     √    √
6162/7162   7581   R   Current L2 max                         A     √    √
6164/7164   7582   R   Current L3 min                         A     √    √
6166/7166   7583   R   Current L3 max                         A     √    √
6168/7168   7584   R   Active power L1 min                    W     √    x
6170/7170   7585   R   Active power L1 max                    W     √    x
6172/7172   7586   R   Active power L2 min                    W     √    x
6174/7174   7587   R   Active power L2 max                    W     √    x
6176/7176   7588   R   Active power L3 min                    W     √    x
6178/7178   7589   R   Active power L3 max                    W     √    x
6180/7180   7590   R   Reactive power L1 min                  var   √    x
6182/7182   7591   R   Reactive power L1 max                  var   √    x
6184/7184   7592   R   Reactive power L2 min                  var   √    x
6186/7186   7593   R   Reactive power L2 max                  var   √    x
6188/7188   7594   R   Reactive power L3 min                  var   √    x
                                                                        49
6190/7190   7595   R   Reactive power L3 max                    var   √   x
6192/7192   7596   R   Apparent power L1 min                    VA    √   x
6192/7194   7697   R   Apparent power L1 max                    VA    √   x
6196/7196   7698   R   Apparent power L2 min                    VA    √   x
6198/7198   7699   R   Apparent power L2 max                    VA    √   x
6200/7200   7600   R   Apparent power L3 min                    VA    √   x
6202/7202   7601   R   Apparent power L3 max                    VA    √   x
6204/7204   7602   R   Power factor (PF) L1 min                  -    √   x
6206/7206   7603   R   Power factor (PF) L1 max                  -    √   x
6208/7208   7604   R   Power factor (PF) L2 min                  -    √   x
6210/7210   7605   R   Power factor (PF) L2 max                  -    √   x
6212/7212   7606   R   Power factor (PF) L3 min                  -    √   x
6214/7214   7607   R   Power factor (PF) L3 max                  -    √   x
6216/7216   7608   R   Reactive and active power ratio L1 min    -    √   x
6218/7218   7609   R   Reactive and active power ratio L1 max    -    √   x
6220/7220   7610   R   Reactive and active power ratio L2 min    -    √   x
6222/7222   7611   R   Reactive and active power ratio L2 max    -    √   x
6224/7224   7612   R   Reactive and active power ratio L3 min    -    √   x
6226/7226   7613   R   Reactive and active power ratio L3 max    -    √   x
6228/7228   7614   R   Phase to phase voltage L1-2 min          V     √   √
6230/7230   7615   R   Phase to phase voltage L1-2 max          V     √   √
6232/7232   7616   R   Phase to phase voltage L2-3 min          V     √   √
6234/7234   7617   R   Phase to phase voltage L2-3 max          V     √   √
6236/7236   7618   R   Phase to phase voltage L3-1 min          V     √   √
6238/7238   7619   R   Phase to phase voltage L3-1 max          V     √   √
6240/7240   7620   R   3-phase mean voltage min                 V     √   √
6242/7242   7621   R   3-phase mean voltage max                 V     √   √
6244/7244   7622   R   3-phase mean current min                 A     √   √
6246/7246   7623   R   3-phase mean current max                 A     √   √
6248/7248   7624   R   3-phase active power min                 W     √   √
6250/7250   7625   R   3-phase active power max                 W     √   √
6252/7252   7626   R   3-phase reactive power min               var   √   √
6254/7254   7627   R   3-phase reactive power max               var   √   √
50
6256/7256   7628   R   3-phase apparent power min                         VA   √    √
6258/7258   7629   R   3-phase apparent power max                         VA   √    √
6260/7260   7630   R   Power factor (PF) min                               -   √    √
6262/7262   7631   R   Power factor (PF) max                               -   √    √
6264/7264   7632   R   min 3-phase mean reactive and active power ratio    -   √    √
6266/7266   7633   R   max 3-phase mean reactive and active power ratio    -   √    √
6268/7268   7634   R   Frequency min                                      Hz   √    √
6270/7270   7635   R   Frequency max                                      Hz   √    √
6272/7272   7636   R   Phase to phase mean volatge min                     V   √    √
6274/7274   7637   R   Phase to phase mean volatge max                     V   √    √
6276/7276   7638   R   15,30,60 minutes 3-phase active power min          W    √    √
6278/7278   7639   R   15,30,60 minutes 3-phase active power max          W    √    √
6280/7280   7640   R   THD U1 min                                         %    √    x
6282/7282   7641   R   THD U1 max                                         %    √    x
6284/7284   7642   R   THD U2 min                                         %    √    x
6286/7286   7643   R   THD U2 max                                         %    √    x
6288/7288   7644   R   THD U3 min                                         %    √    x
6290/7290   7645   R   THD U3 max                                         %    √    x
6292/7292   7646   R   THD I1 min                                         %    √    x
6294/7294   7647   R   THD I1 max                                         %    √    x
6296/7296   7648   R   THD I2 min                                         %    √    x
6298/7298   7649   R   THD I2 max                                         %    √    x
6300/7300   7650   R   THD I3 min                                         %    √    x
6302/7302   7651   R   THD I3 max                                         %    √    x
6304/7304   7652   R   Cosine angle between U1 and I1 min                 -    √    x
6306/7306   7653   R   Cosine angle between U1 and I1 max                 -    √    x
6308/7308   7654   R   Cosine angle between U2 and I2 min                 -    √    x
6310/7310   7655   R   Cosine angle between U2 and I2 max                 -    √    x
6312/7312   7656   R   Cosine angle between U3 and I3 min                 -    √    x
6314/7314   7657   R   Cosine angle between U3 and I3 max                 -    √    x
6316/7316   7658   R   Mean 3-phase cosine min                            -    √    √
6318/7318   7659   R   Mean 3-phase cosine max                            -    √    √
                                                                          o
6320/7320   7660   R   Angle between U1 and I1 min                             √    x
                                                                          o
6322/7322   7661   R   Angle between U1 and I1 max                             √    x
                                                                                   51
                                                                 o
6324/7324   7662   R   Angle between U2 and I2 min                   √    x
                                                                 o
6326/7326   7663   R   Angle between U2 and I2 max                   √    x
                                                                 o
6328/7328   7664   R   Angle between U3 and I3 min                   √    x
63307330    7665   R   Angle between U3 and I3 max               o
                                                                     √    x
6332/7332   7666   R   Current in neutral lead min               A   √    x
6334/7334   7667   R   Current in neutral lead max               A   √    x
In case of a lower overflow, the value –1e20 is written in, however in case
of an upper overflow or if an error occurs, the value 1e20 is written in.
52
10. Examples of P43 Transducer Programming
Example 1 – Programming an Alarm 1 with Hysteresis
Program the operation of the alarm 1 in such a way, that at the value
250 V of the phase 1 voltage, the alarm will be switched on, however
switched off at the value 210 V.
For the rated Un = 230 V execution, one must set up values from the
table 7.
                                                              Table 7
 Regi-
          Value                            Meaning
 ster
 4015        1     1 – voltage of phase 1 (U1)
 4016        0     0 – n-on mode
                   913 – 91.3% (percentage value with one place after the
                   decimal point multiplied by 10) of the rated voltage of
  4017     913
                   phase 1 – alarm switched off,
                   (210 V/230 V) x 1000 = 913
                   1087 – 108.7 % (percentage value with one place after
                   the decimal point multiplied by 10) of the rated voltage of
  4018     1087
                   phase 1 – alarm switched on,
                   (250 V/230 V) x 1000 = 1087
  4019       0     0 – 0 second delay in the alarm switching
  4020       0     0 – 0 second delay in the alarm switching off
  4021       0     0 – 0 second deadlock for the alarm re-switching
                                                                            53
Work optimization of power limit function (alarm switch on delay):
delay time of the alarm to= 10% * [1 MW * 900 s/ 1.5 MW] = 60 s (register 4019).
Figure 20 presents how to take advantage of the parameter showing
used ordered power to activate alarm. The alarm delay is switched off
(set to 0 sec.) - register 4019.
In the example for the remaining 10% of ordered power under maxi-
mal power consumption the devices could work yet 60 seconds without
exposing the consumer to penalties. If the delay was set to 60 seconds
the alarm would not be activated (register 4019).
54
                                                                       Table 8
 Regi-
          Value                             Meaning
 ster
                   579 – 57.9 % (percentage value with one place after the
  4010     579     decimal point multiplied by 10) percentage value of ordered
                   power in relation to the rated power
  4015     35      35 – alarm set to the percentage of used active power
                                                                             55
                   400 – 4.00 mA (value in mA with two places after the decimal
  4051     400     point multiplied by 100) lower value of the output current
                   (4,00 mA x 100) = 400
                   2000 – 20.00 mA (value in mA with two places after
                   the decimal point multiplied by 100) upper value of the
  4052     2000
                   output current.
                   (20.00 mA x 100) = 2000
  4053      0      0 – normal mode of the continuous output 1
  4054      24     24 – 24 mA on continuous output 1 if the error (-1e20 or 1e20)
56
11. TECHNICAL DATA
Measuring Ranges and Admissible Basic Errors
                                                                               Table 11
     Measured                                                                    Basic
                              Measuring range               L1   L2   L3   S
      quantity                                                                   error
  Current 1 A ~                 0.002 ... 1.2 A~
                                                            l    l    l          ±0.2%
            5 A~                  0.01 ... 6 A~
Voltage L-N 57,7 V~             2.80 ...70.0 V~
                                                            l    l    l          ±0.2%
            230 V~              10.0 ... 276 V~
Voltage L-L 100 V~                5 ... 120 V~
                                                            l    l    l          ±0.5%
            400 V~               20 ... 480 V~
     Frequency                   47.0...63.0 Hz             l    l    l          ±0.2%
    Active power          -1.65 kW...1.4 W...1.65 kW        l    l    l    l     ±0.5%
  Reactive power         -1.65 kvar...1.4 var...1.65 kvar   l    l    l    l     ±0.5%
 Apparent power                1.4 VA...1.65 kVA            l    l    l    l     ±0.5%
    PF factor                       -1...0...1              l    l    l    l     ±0.5%
   Tangens j                      -1.2...0...1.2            l    l    l    l      ±1%
    Cosinus j                         -1...1                l    l    l    l      ±1%
 Angle between U
                                 -180o... 180o              l    l    l          ±0.5%
      and I
 Input active energy         0...99 999 999.9 kWh                          l     ±0.5%
 Developed active
                            0...99 999 999.9 kvarh                         l     ±0.5%
      energy
Reactive inductive
                             0...99 999 999.9 kWh                          l     ±0.5%
      energy
Reactive capacitive
                            0...99 999 999.9 kvarh                         l     ±0.5%
      energy
  THD in the range
   10...120% U,I;                   0...100%                l    l    l    l      ±5%
 48...52 Hz; 58..62 Hz
Caution! For correct current measurement, the presence of voltage
with the value higher than 0.05 Un is required at least on one phase.
Power Consumption:
- in supply circuit                         10 VA
- in voltage circuit                        0.05 VA
- in current circuit                        0.05 VA
                                                                                    57
Analog Outputs:                0, 2 or 4 programmable outputs:
                               - 20...0...+20 mA, Rload: 0..250 W		
                               basic error 0,2% 			
                               output response time < 2 s
Relay Outputs:                 0, 2 or 4 relays, voltageless NO contacts
                               load capacity 0.5 A/250 V a.c.
Serial Interface:              RS-485: address 1...247;
                               mode: 8N2, 8E1, 8O1, 8N1;
                               baud rate: 4.8, 9.6, 19.2, 38.4 kbit/s,
                               USB: 1.1 / 2.0, address 1;
                               mode 8N2; baud rate 9.6 kbit/s,
Transmission Protocol:         Modbus RTU
Response time:                 500 ms
Energy Pulse Output:           output of OC type, passive
                               acc. to EN 62053-31
Pulse Constant
of OC Type Output:             5000 -20000 imp./kWh, independently
                               on settings ratios Ku, Ki
Ratio of the Voltage
Transformer Ku:                0.1... 4000.0
Ratio of the Current
Transformer Ki:                1...10000
Protection Degree:
- for the housing              IP 40
- from terminals (rear side)   IP 10
Weight:                        0.3 kg
Dimensions:                    90 x 120 x 100 mm
Fixing Way:                    on a 35 mm DIN rail
Reference and Rated Operating
Conditions:
- supply voltage              85...253 V a.c. 40...400 Hz; 		
58
                                   90...320 V d.c.
                                   or 20...40 V a.c. 40...400 Hz; 		
                                   20...60 V d.c.
- input signal                     0...0.002...1.2 In; 0...0.05...1.2 Un
                                   for current, voltage
                                   0...0.002...1.2 In; 0...0.1...1.2 Un
                                   for power factors Pf i ,tj i
                                   frequency 47...63 Hz
                                   sinusoidal (THD £ 8%)
- power factor                     -1...0...1
- analog outputs                   -24...-20...0...+20...24 mA
- ambient temperature              -10...23...+55°C
- storage temperature              -30...+70°C
- relative humidity                25...95% (inadmissible condensation)
- admissible peak factor:
    - current                      2
    - voltage                      2
- external magnetic field          0..40...400 A/m
- short duration overload 5 sec.
    - voltage inputs               2Un (max.1000 V)
    - current inputs               10 In
- work position                    any
- preheating time                  5 min.
Additional errors:
in percentage of the basic error:
- from frequency of input signals < 50%
- from ambient temperature
changes                           < 50%/10oC
- for THD > 8%                    < 100%
60
12. ORDERING CODES
                                                                       Table 12
Code           Description
P43 211300M0   3-phase transducer of power network parameters P43, input I 5A(X/5);
               input U 3 x 57,7/100V; supply 85-253Vac, 90-320Vdc;
               4 x analog output, without relays; documentation and descrip-
               tions in Polish and English, test certificate
P43 221300M0   3-phase transducer of power network parameters P43 input I 5A(X/5);
               input U 3 x 230/400V; supply 85-253Vac, 90-320Vdc;
               4 x analog output, without relays; documentation and descrip-
               tions in Polish and English, test certificate
P43 221100M0   3-phase transducer of power network parameters P43, input I 5A(X/5);
               input U 3 x 230/400V; supply 85-253Vac, 90-320Vdc; 4 x relay,
               without analog outputs; documentation and descriptions in
               Polish and English, test certificate
P43 111300M0   3-phase transducer of power network parameters P43, input I 1A(X/1);
               input U 3 x 57,7/100V; supply 85-253Vac, 90-320Vdc;
               4 x analog output, without relays; documentation and descrip-
               tions in Polish and English, test certificate
P43 121300M0   3-phase transducer of power network parameters P43, input I 1A(X/1);
               input U 3 x 230/400V; supply 85-253Vac, 90-320Vdc;
               4 x analog output, without relays; documentation and
               descriptions in Polish and English, test certificate
P43 121100M0   3-phase transducer of power network parameters P43, input I 1A(X/5);
               input U 3 x 230/400V; supply 85-253Vac, 90-320Vdc; 4 x relay,
               without analog outputs; documentation and descriptions in
               Polish and English, test certificate
P43 111100M0   3-phase transducer of power network parameters P43, input I 1A(X/1);
               input U 3 x 57,7/100V; supply 85-253Vac, 90-320Vdc; 4 x relay,
               without analog outputs; documentation and descriptions in
               Polish and English, test certificate
                                                                                61
     LUMEL S.A.
     ul. Słubicka 4, 65-127 Zielona Góra, Poland
     tel.: +48 68 45 75 100, fax +48 68 45 75 508
     www.lumel.com.pl
     Technical support:
     tel.: (+48 68) 45 75 143, 45 75 141, 45 75 144, 45 75 140
     e-mail: export@lumel.com.pl
     Export department:
     tel.: (+48 68) 45 75 130, 45 75 132
                                                                 P43-09H_R1
     e-mail: export@lumel.com.pl
     Calibration & Attestation:
     e-mail: laboratorium@lumel.com.pl
62