LEC1
LEC1
January 1997
  FM739                                                                               LEC1...
            Control Unit                                                                           Series 02
            Control unit for double or multi-flame supervision of oil, gas or forced draught
            oil/gas burners of any fuel throughput (for continuous or intermittent operation).
Use         The LEC1... control unit is designed for the fully automatic start-up and supervision of
            those forced draught burners with which the flame supervision should or must be carried
            out by separate flame safeguards, e.g. with
            -   Dual supervision (of the main flame or of the pilot and main flame by means of two
                identical or different detectors).
            -   Supervision of forced draught oil/gas burners (with different types of detectors
                according to selected operating mode).
            -   Multi-flame supervision (i.e. central and simultaneous control of the start-up and
                supervision program for several burners, the flames of which, however, must be
                individually supervised by one or two flame safeguards each).
            LAE10... for the supervision of oil burners with active selenium photocell sensor RAR... in
            intermittent operation.
            LFE10... for the supervision by means of ionization field (gas burner) or with UV-
            detectors QRA... (gas, oil or dual fuel burners, with or without ignition spark supervision)
            in intermittent operation.
            LFE50... for the supervision with UV-detectors QRA50.../51... (gas, oil or dual fuel
            burners) in intermittent or continuous operation.
            All devices comply with the relevant European standards for oil, gas and forced draught
            burners of any fuel throughput.
            The LEC1... can control the following burner plant components: fan motor, flue gas fan,
            air damper, ignition transformer, one to three fuel valves, the load controller and an
            external fault signaling device.
                                                                                         Grafikname:
                                                                                         Erstellt in:
CC1N7761E                                                                                Erstellt am:
Construction of the      The control unit LEC1... as well as the flame safeguards LAE10... and LFE10... are of
Control Unit and the     plug-in design and are suitable for the mounting in any position at the burner, on control
                         panels and in control cabinets. The spacious terminal bases and the housings are made
Flame Safeguards
                         of impact proof and heat-resistant plastic. The switching mechanism of the unit driven by
                         a synchronous motor, its relays as well as all other switching, control and adjusting
                         elements are mounted on solid printed circuit boards.
Operation                The following description of the mode of operation refers to the start-up and supervision
                         of one single burner.
                         With multi-flame supervision all of the burners connected to the control unit are put into
                         operation and supervised simultaneously in the same manner. A defect leading to a lock-
                         out at one of the burners therefore results in the shutdown of all burners. The prerequisite
                         for the immediate restart of the non-defective burners is the bridging of the flame
                         safeguard of the defective burner by means of an operating switch. This switch must
                         simultaneously interrupt all control lines to the ignition transformer and the fuel valves. For
                         connection examples please refer to data sheet 7781.
                         Defects in the flame safeguard or in the control unit prevent the start or lead to a lock-out
                         during the start-up.
Important                If the air damper is not controlled by the control unit, terminal 20, 21 and 22 must be
                         interconnected.
Program sequence         First the fan motor is switched on via terminal 3 and the air damper actuator is driven via
during burner start-up   terminal 22. As soon as the air damper has reached its fully open position, the switching
                         mechanism of the unit starts its run - the prepurge time begins. The minimum air pressure
                         set at the air pressure monitor must be reached within 10 s (or 7 s in operation with post-
                         purge) and must be maintained until the controlled shutdown, otherwise lockout occurs. A
                         flame signal during the prepurge time also leads to a lockout. On completion of the set
                         prepurge time the air damper receives the control command to return to the minimum air
                         position. During the air damper’s closing time the switching mechanism remains
                         stationary. As soon as the signal contact for the minimum butterfly position is operated by
                         the air damper actuator, the switching mechanism starts again and now controls the
                         program sequence which can no longer be influenced externally:
                         -   Pre-ignition (3 s)
                         -   Release of the 1st fuel valve via terminal 5 (the fuel valve of a pilot burner which must
                             be closed on completion of the 2nd safety time must, however, be connected to
                             terminal 10)
                         -   Programming of the set safety time. If no flame is established during this time, lockout
                             occurs (always with interlocking of the control unit)
                         -   Following an interval of 11 s after the release of the 1st valve, the 2nd fuel valve is
                             released
                         -   The pilot burner, if connected to terminal 10, is switched off
                         -   The load controller is switched on after a further interval of 12 s. Now the burner has
                             reached its operating position. From now on the load controller controls the burner
                             capacity by either increasing or decreasing the fuel throughput and the air volume
                             depending on the heat demand (fuel/air ratio control). This can be carried out in stages,
                             i.e. by means of thermostats or continuously (modulating) by using a continuous
                             controller.
2                                                                                                         CC1N7761E
Burner start-up with      In principle the program sequence is the same as with burner start-up without ignition
ignition spark            spark supervision. Exceptions:
supervision
                          -   If the flame safeguard does not receive any input signal during the short pre-ignition
                              time (UL2 on position «Short pre-ignition»), lockout occurs before any gas is released,
                              i.e. safety time t2 = 0 s.
                          -   With ignition spark supervision the safety time for the pilot burner can only be adjusted
                              between 0 ... 6 s (in the time diagram of the switching mechanism: t2z).
Control program           Controlled shutdown is carried out as soon as one control or supervision device in the
following a controlled    control loop between terminal 8 and 9 open its contact, i.e. the fuel valves are closed
shutdown                  immediately. The switching mechanism starts again and now programs the post-purge, if
                          necessary. On completion of the post-purge time the switching mechanism has again
                          reached its start position in which it remains until the next switching on command is
                          received.
                          The flame supervision restarts again during the post-purge time; therefore every flame
                          signal during this time leads to a lockout.
Control program           After actuation of the built-in or external reset button the switching mechanism runs
following lockout reset   through to its start position. The only burner plant component which is operated during
                          this time is a fan motor connected to terminal 17. As the limit thermostat or pressurestat
                          normally continues to call for heat, the unit immediately initiates a restart as soon as it has
                          reached its start position.
Program Indicator         The program indicator continuously shows the respective phase of the burner start-up
                          sequence. The letters correspond to those of the switching mechanism diagram next to
                          the viewing window. The figures indicate the remaining pre-purge time. If lockout occurs
                          the switching mechanism and the program indicator stop and by this means determine
                          the operating phase during which the lockout occurred.
CC1N7761E                                                                                                              3
Technical Data
Control unit LEC1
                      Mains voltage         AC 220 V -15%...AC 240 V +10%           Radio interference protection
                                            AC 100 V -15%...AC 110 V +10%                                       N according to VDE0875
                      Mains frequency               50 Hz -6%...60 Hz +6%           Max. permissible load on the control outputs
                      Unit fuse, built-in                       T6,3H250V           − per terminal                                     4A
                      External fuse                        10 A max., slow          − in total                                         5A
                      The control unit is delivered without terminal baseplate. The latter must be ordered
                      separately using the following type reference: AGG41041713 (EC)
                      For flame safeguards LAE10... and LFE10... as well as the appropriate detectors, please
                      refer to data sheet 7781.
4                                                                                                                         CC1N7761E
Basic Diagram LEC1
Attention: When using the UV-detector QRA... terminal 10 must be connected to earth!
CC1N7761E                                                                                                 5
                            AS           Unit fuse                                                               L2     Lockout warning device, external
Legend                      AR           Working relay with contacts «ar...»                                     L3     Signal lamp for the flame indication
for the entire data sheet   BR           Lockout relay with contacts «br...»                                     LK     Air damper actuator with limit or auxiliary
                            BS1          Operating switch                                                               switches
                            BS2          Operating mode selector switch                                                 (see also «Connection examples»)
                            BV...        Fuel valve                                                                     a = actuator runs into position «Open»
                            (BV...)      Fuel valve for a pilot burner which is switched                                (maximum air volume)
                                         off on completion of the 2nd safety time                                       z = actuator runs into position «Closed»
                            c...         Fan contactor with contacts «c...»                                             (minimum air volume)
                            d...         Auxiliary relay with contacts «d...»                                    LP     Air pressure monitor
                            e...         Thermal overload fuse                                                   M...   Fan
                            EK1          Reset button at the unit                                                NTC    High-temperature conductor (delay unit)
                            EK2          Remote reset button                                                     OV... Oil valve
                            FE           Flame detector electrode                                                Q      Temperature or pressure detector
                            FR           Flame relay                                                             QRA... UV-detector
                            FW           Contacts of the flame safeguards LAE10...,                              R...   Thermostat or pressurestat
                                         LFE10... or LFE50...                                                    RAR... Selenium photocell detector
                            GP           Gas pressure monitor                                                    RV     Control valve
                            GV...        Gas valve                                                               SB     Safety limiter
                            H            Main isolator                                                           SM     Synchronous motor of the switching
                            HR1          Auxiliary relay with contacts «hr11 and hr12»                                  mechanism
                            HR2          Auxiliary relay with contact «hr21»                                     SQ... Type reference of air damper actuator
                            HR3          Auxiliary relay for flame detector or flame                             UL1    Operating switch for motor of the switching
                                         simulation test                                                                mechanism
                            L1           Lockout warning device, built-in                                        UL2    Changeover link for
                                                                                                                        «Short/long pre-ignition time»
                                                                                                                 UL3    Changeover link for «STOP» or «Run» of
                                                                                                                        the sequence mechanism after a lockout
                                                                                                                 W      Limit thermostat or pressure monitor
                                                                                                                 Z      Ignition transformer
                                  III
                                                                                            t2z
                                                                                                                                a
                                  IV                                                                                            b
                                                                                      67        t4         t9
                                                                                                                90
                                  V                                                             t3´         t5
                                                                                                                                a
                                  VI                                                                                            b
                                                                                                                  93
                                                                 t3
                                  VII                                                      70
                                                                                                                                a
                                  VIII                                                                                          b
                                           3
                                                                                                                                a
                                  IX                                                                                            b
                                                t7
                                  X       t10   10
                                  XI                                                  66
                                                                                                                                a
                                  XII                                                                                           b
                                                                t1
                                                                                                                                a
                                  XIII                                                                                          b
                                                                                63
                                               t11     7761d01/0696
                                                                                           t12
                                                                       t8                                                t6
                                                                            T
                            T                   120 s                                Running time of the switching mechanism
                            t1                  8...63 s                             Pre-purge time, adjustable
                            t2                  0...9 s                              1st safety time, adjustable (set to 0 s with ignition spark supervision)
                            t2z                 0...6 s                              Safety time for the pilot burner in case of burner start-up with
                                                                                     ignition spark supervision
                            t3                  t11 + t1 + t12 + 7 s                 Pre-ignition time «Long» (during the whole pre-purge)
                            t3’                 3s                                   Pre-ignition time «Short»
                            t4                  11 s                                 Interval between release of the 1st and 2nd fuel valve
                            t5                  12 s                                 Interval between release of the 2nd and 3rd fuel valve or the load
                                                                                     controller
                            t6                  T- (30 + t1)                         Post-purge time
                            t7                  3s                                   Delay time
                            t8                  t1 + 30 + t11 + t12                  Total start-up time
                            t9                  0...9 s                              2nd safety time with interrupted pilot burner
                            t10                 10 s                                 Bridging time (set time for the air pressure control)
                            t11, t12            optional                             Opening or closing time of the air damper
                            Maximum permissible after-burn time
                            (counted as of the beginning of t6)                      7s
                            For the factory setting of the different types, please refer to the type summary.
6                                                                                                                                                   CC1N7761E
Specific Features     The construction, control program and adjustment facilities of the unit allow its almost
                      unlimited use in burner plants of any size and type of construction, be it expanding flame
                      or interrupted pilot burners, permanently operating or any other special burners.
With respect to       -   Optional mounting location and position of the control unit
mounting and          -   Large space for connection in terminal base
installation          -   Additional 4 terminals each for earth and neutral conductors as well as 4 auxiliary
                          terminals
With respect to       -   Continuous indication of the program sequence in the viewing window of the unit cover.
commissioning and         *
trouble shooting      -   The motor of the switching mechanism can be switched off (simplifies burner
                          adjustment)
                      -   Cam shaft can be rotated by hand
                      -   Electric remote lockout reset facility
                      * It is, however, also possible to program the unit by means of a changeover link (UL3) in
                        such a way that the programming mechanism does not stop in case of a lock-out, but
                        that it runs through to the end of the program. The only component that remains under
                        voltage during that time is a fan for the post-purge which is connected to terminal 17.
Warning Notes         • In the area covered by DIN assembly and installation must comply with the
                          requirements of the VDE, especially with the DIN/VDE standards 0100 and 0722!
                      • The electrical wiring must be made in accordance with national and local
                          standards.
                      •   LEC1... is a safety device! The loosening of the securing screws as well as any
                          changing of the factory setting must therefore be carried out by authorized
                          persons only!
                      •   Check wiring carefully before putting the unit into operation!
                      •   The LEC1 must be completely isolated from the mains before performing any
                          work on it!
                      •   Check all safety functions when putting the unit into operation or after having
                          replaced any fuses!
                      •   Ensure protection against contact at the unit and at all electrical connections by
                          appropriate mounting!
                      •   Electromagnetic emissions must be checked from an application point of view!
                      •   Condensation and any influence of humidity must be avoided!
CC1N7761E                                                                                                               7
Adjustment Facilities
at the Unit
General instructions     -   Isolate the unit from the mains prior to any adjustment
                         -   Loosen all 6 retaining screws and only remove the unit cover
                         -   The numbering of the switching cams always starts from the motor
                         -   The cam shaft can be turned into any position by hand (clockwise direction of rotation
                             as seen from the motor)
Adjustment elements      UL1    ON/OFF switch for the motor of the                   N5       Cam 5, adjustable (2nd safety time)
                                switching mechanism                                  N7       Cam 7, fixed
                         N1     Cam 1, fixed                                         N8       Cam 8, adjustable (prepurge time)
                         N2, N3 Cam 2 and 3, adjustable (1st safety time)            PA       Program indicator
                         N4     Cam 4, fixed
Important                LEC1... is a safety device! The loosening of the securing screws as well as any
                         modification of the factory setting may therefore be carried out by authorized
                         persons only!
                         UL2     Changeover link for «Short/long pre-ignition time», in position «Short pre-ignition» locked with varnish
                         UL3     Changeover link for «STOP» of the control sequence following a lockout or «Restart». Only the fan for the
                                 post-purge connected to terminal 17 remains under voltage.
8                                                                                                                          CC1N7761E
Adjustment of the          -   Loosen the securing screw of the red cam 8
prepurge time              -   Turn the cam shaft by hand until the required pre-purge time is indicated next to the
                               index notch on the carrier of the switching mechanism
                           -   Hold the cam shaft firmly and rotate cam 8 until the contact tappet operated by it just
                               jumps out or the cam strikes this tappet
                           -   Carefully tighten the securing screw of the cam and check the adjusted time for
                               accuracy. The set time is also visible in the viewing window, if the unit is in its start
                               position.
                           The adjustments of the mark of the red cam N8 to the graduation marks of the black
                           cam N7 result in the prepurge times given in the following table.
Adjustment of the safety   The safety times are adjusted by setting the red cams of the switching mechanism. Their
times                      time marks serve as setting aid. After the adjustment the securing screws of the cams
                           must be tightened very carefully to make any unintentional readjustment impossible.
CC1N7761E                                                                                                              9
1st safety time t2z   (operation with ignition spark supervision)
2nd safety time t9    -   Loosen the securing screw of cam 5 and align its setting mark to the according time
                          marks of cam 4 (see photo and table, intermediate settings possible).
10                                                                                                CC1N7761E
Connection Examples For connection examples for the flame supervision with DETACTOGYR LFE50... see
and Time Diagrams   data sheet 7783.
Double or multi-flame    Start-up with long pre-ignition (t3) and supervised air damper control. Air pressure
supervision of oil       supervision from the start to the controlled shutdown. No load control. Necessary flame
burners                  safeguards: type LAE10... with selenium photocell detector RAR...
LEC1... UL.2
                                  16                     1        2              13     14     15   12    19   18            8            9     4        3        22            21    20         17       6            5         7                     11
                                                                                                                    *                               *
                                                                                     FW
                                                                                 3        4
                                                                                                                                                                                                     e2                                  d1
                                                   SB                                                                                                                                                                                                   d1
                          EK2
                                                                                              6
                                                H                                                                   c1                                    e1                d1
                                                                                 7        5
                                  M1          M2                                                                                                                                                     c2
                                                                                                                                                                                                                                     OV2
                                  M           M                                    FW 4                                                             c1
                                                                                 3
                                                                                                                                                                  1         2        12 11
                                                                                              6                     LP
                                   c1             c2                                                            P                               T                 a              z
                                                                                 7        5
                                   e1             e2                                                                                                R1                                                                     OV1                OV3
                                                                                      (LAE10...)                                                                        M
                                                                                                                                                T
                                                                                                                                                                       N
                                                                                                                                                                                       LK                     Z
                                                                                                                                                W
                                                                                                     L2
                            P                                N                                                 7761a03/0696
                            (R)                              (Mp)
                                                                                                                                      A                                               B                                C                           D         E
                                                       LK
                                       M
                                                                                                                                 22
                          Luft
                                                                                                                                 21
                          Öl                                                                                                 21/d1
                                                                                                                        18/c1/d1
                                              OV3
                                                                                                                                 20
                                                                                                                             LK"a"
                                                            OV2
                                       7761a04/0696                                                                                                                                                                        7761d03/0696
                                                                                                                          LK"z"
                                                                        OV1
                                                                                                                                          t11            t1           t12                  t11                    tn                 t6                t12
Important                In case of burners without air damper or with an air damper not controlled by the control unit, terminals 20, 21 and
                         22 must be interconnected; the path 18-c1-21 of the circuit, however, must be omitted!
                                                   A                                      B                              C                D     E             F                                  G                H                  I                 K                     L
                                                                       t8                                tn                      t6                                                                                                           t6
                                       M1     Kl.3
                                                                  t7                                                                                                                                                                                         t7
                                       M2      17
                                                       t11    t1        t12                                                                                                                                                                                      t1
                                       LK    22/21
                                                                            t2                                                                                                                                                                                         t2
                                       Z          6
                                                                   t3                                                                                                                                                                                             t3
                                       OV1        5
                                                                            t4                                                                                                                                                                                         t4
                                       OV2        7
                                                                                              t5                                                                                                                                                                        t5
                                       OV3     11
FW 13/14
L2 12
7761d02/0696
CC1N7761E                                                                                                                                                                                                                                                               11
Double or multi-flame       Start-up with short pre-ignition (3 s) and supervised air damper control. No load control.
supervision of gas          Necessary flame safeguards: type LFE10... with UV-detectors QRA... or ionization field.
burners (expanding
flame burner)
                                                                                                     A                             B                  C                  D         E
                                                  LK
                                   M                                                           22
                            Luft
                                                                                               21
                            Gas                                                             21/d1
                                                                                          18/c1/d1
                                          GV3
                                                                                               20
                                                                                            LK"a"
                                                       GV2
                                   7761a06/0696                                                                                                           7761d04/0696
                                                                                            LK"z"
                                                                   GV1
                                                                                                         t11       t1     t12          t11       tn            t6            t12
Important                   In case of burners without air damper or with an air damper not controlled by the control unit, terminals 20, 21 and
                            22 must be interconnected; the path 18-c1-21 of the circuit, however, must be omitted!
                                              A                             B                  C               D    E     F                  G        H             I                  K                    L
                                                                  t8                 tn              t6                                                                      t6
                                   M1      Kl.3
                                                             t7                                                                                                                            t7
                                   M2       17
                                                  t11    t1        t12                                                                                                                      t1
                                   LK     22/21
                                                                       t2                                                                                                                          t2
                                   Z         6
                                                                   t3´                                                                                                                           t3´
                                   GV1       5
                                                                       t4                                                                                                                          t4
                                   GV2       7
                                                                                t5                                                                                                                     t5
                                   GV3      11
FW 13/14
L2 12
7761d05/0696
12                                                                                                                                                                       CC1N7761E
Double or multi-flame      Start-up with short pre-ignition (3 s) and supervised air damper control. Control of the 2nd
supervision of burners     output stage via on/off controller (R2). Necessary flame safeguards: type LFE10... with
for selectable operation   UV-detectors QRA...
with oil or gas
(expanding flame burner)
                                               OV3                    I      Gas
                           Luft     M   LK
                                                                      II     Off
                                                                      III    Oil
GV1
Gas
                                                       7761a09/0696
                                         GV2
GV3
CC1N7761E                                                                                                           13
Double or multi-flame   including supervised air damper control. Necessary flame safeguard:
supervision of          For oil:                  LAE10... with active selenium photocell detectors RAR...
modulating burners      For gas:                  LFE10... with UV-detectors QRA... or ionization field
                        For oil/gas:              LFE10... with UV-detectors QRA...
                        Burners that are designed for continuous adjustment of the burner capacity (modulating
                        burners) require, in addition to the standard burner equipment, the devices of the
                        temperature or pressure control circuit, e.g.
                        1       Continuous controller, e.g. POLYGYR RWF32                 1   Auxiliary relay                                 d1
                        1       Operating switch                           BS              1   Control valve or similar for the adjustment
                        1       Temperature or pressure detector    QA.../QB...                of the fuel volume                              RV
                        1       Actuator for the control of the air                        1   Setting unit for remote setting, if necessary FZA...
                                damper and the fuel throughput
                                (fuel/air ratio control)                 SQ...
                                             18               8            9
Control for semi-
automatic operating
mode                                                                             T
                                        L                                         W
                        N (Mp)
                         7761a07/0696
                                                     I                0
                        This circuit is used when fully automatic operation is not required due to certain reasons
                        (e.g. with industrial burners). The burner is started by actuation of the impulse contact I;
                        the burner is shut down by either pressing the circuit-breaking contact 0 or by operating
                        the limit thermostat.
14                                                                                                                                CC1N7761E
Dimensions          Dimensions in mm
LEC1
Baseplate
AGG 41041713 (EC)
Important:          To remove the control unit from the plug-in baseplate, only the 4 screws A must be loosened.
                    To remove the unit cover the 2 screws B also have to be loosened.
                    C: Elongated holes for fixing the baseplate.
                    EK: Reset button
                    SG: Viewing window