0% found this document useful (0 votes)
38 views11 pages

LDU11

The LDU11 Automatic Valve Proving Control performs leak tests on gas shut-off valves to enhance safety in gas-fired combustion systems. It operates in two test phases to detect leaks and initiates a lockout if a leak is found, preventing burner startup. The control unit is globally approved and requires specific pressure switches for proper installation and operation.

Uploaded by

mocanudaniel2002
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
38 views11 pages

LDU11

The LDU11 Automatic Valve Proving Control performs leak tests on gas shut-off valves to enhance safety in gas-fired combustion systems. It operates in two test phases to detect leaks and initiates a lockout if a leak is found, preventing burner startup. The control unit is globally approved and requires specific pressure switches for proper installation and operation.

Uploaded by

mocanudaniel2002
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 11

7 696

Automatic Valve Proving Control LDU11


ISO 9001

UL recognized
FM approved
Features
• Performs leak test of the gas shut-off valves before start-up and/or immediately
after burner shut-down
• No inlet gas pressure limitations
• Easy-to-read dial indicates progress of test program
• Ability to eliminate or leak test the vent valve
• Cost effective control improves system safety
• Globally Approved – cULus, FM, CE

Application

The LDU11... control detects leakage of the shut-off valves on gas trains with two safety shutoff
valves. During each burner cycle, the LDU control unit automatically sequences, and if a leak is
detected, initiates a lockout and prevents the burner from starting up.

Function

The LDU11 (or control unit) is used in a gas-fired combustion system with or without a vent valve in the gas
train.

Installed with one or two pressure switches mounted between the gas valves, the LDU automatically initiates
gas valve proving either
• prior to burner start-up
• immediately after the controlled shutdown, or
• both prior to burner start-up and immediately after shutdown

The valve leak test is completed in two stages:


• First test phase «Test1», evacuates the pressure between the gas valves to test the upstream gas
shutoff valve. The pipe between the gas valves is monitored by a leak detect pressure switch for no
increase in pressure.
• Second test phase «Test2», pressurizes the area between the gas valves to test the downstream
safety shutoff valve. The pipe between the gas valves is monitored by the leak detect pressure
switch for no decrease in pressure.

If the leak detect switch signals excessive gas pressure increase during the first test phase «Test1», or
decrease during the second test phase «Test2», the LDU control will lockout and prevent burner start-up.
The indicator dial on the front of the unit indicates the progress of the leak test. When a fault occurs, the
indicator dial stops at the time of lockout, and indicates which of the valves is leaking. In the event of a
lockout, the reset button on the front of the control will light orange to indicate a fault.

Pushing the clear window in front of the indicator dial once will reset the LDU control. DO NOT hold in the
reset button. The LDU may also be reset with a remote button (see wiring diagram).
Ordering

Control unit for gas valve proving, without plug-in base


- For AC 220...240 V, 50...60 Hz LDU11.523A27
- For AC 100...110 V, 50...60 Hz LDU11.523A17

Plug-in base AGM11

The following items must be ordered separately:


• (1) or (2) single-pole, double throw pressure switches. See bulletin 155-292 for
Siemens QP... Series pressure switch selections.

Warning Notes

• All regulations and standards applicable to the particular application must be observed!
• Qualified personnel must always carry out installation and commissioning work!
• The electrical wiring must be made in compliance with national and local standards and
regulations!
• The LDU... must be completely isolated from the mains before performing any wiring!
• Secure the LDU to the base plate to ensure from protection against electric shock!
• Check wiring and all safety functions.
• Do not open or modify the control.
• Fall or shock can adversely affect the control. Do not put such units into operation, even if
they do not exhibit any damage.

Mounting notes

The LDU control must be mounted in an enclosure, typically in the control panel containing the flame
safeguard. There are no distance restrictions from the gas train. The LDU control is not adversely
affected by electromagnetic resonance caused by items such as ignition transformers.

One or two automatic reset single-pole, double-throw pressure switches must be mounted in
between the gas safety shutoff valves. Manual reset switches are not permitted to be the leak
detection switch. No additional piping modifications are required to the gas train.

Page 2/11
Mechanical design

The LDU control includes:


- The synchronous motor with its gear train and step action sequence switch
- The camshaft with its 15 nonadjustable cams
- The program indicator at the head of the camshaft
- One main and one auxiliary relay
- The lockout relay which can be electrically reset from a remote location
- The unit fuse and a spare fuse

The plug-in base carries the following terminals:


- 24 connection terminals
- 3 earth terminals
- 3 neutral terminals, prewired to terminal 2 (neutral input)

The front dial provides information about the program sequence, the type of fault and the point in time the
fault occurred, using easy-to-remember symbols.

Technical data

General unit data Mains voltage


- LDU11.523A17 AC 100 V –15 %...AC 110 V +10 %
- LDU11.523A27 AC 220 V –15 %...AC 240 V +10 %
Mains frequency 50...60 Hz ±6 %
Power consumption
- During the test 3.5 VA
- During operation 2.5 VA
Primary fuse (external) T10 / 500V
Unit fuse T6.3H250V to IEC 127
Perm. input current at terminal 1 5A
Perm. Current rating of control terminals 4A
Required switching capacity
of pressure switch min. 1 A, AC 250 V
Mounting In a panel or control cabinet
Mounting orientation No restrictions
Degree of protection NEMA 1, 2, 5, 12, 13
Weight
- LDU11... 4 lbs
- Plug-in base ½ lb
Environmental Transport
conditions Temperature range -58...+140 °F
Operation
Temperature range -5...+140 °F

Approvals (110 V only):


FM J.I. 1Z2A6.AF Dec 1995
cULus File MH26883
CSA In Progress
Approvals (110 V and 220 V):
CE Electromagnetic compatibility EMC 89 / 336 EEC incl. 92 / 31 EEC
CE Directive for gas appliances 90 / 396 EEC

Page 3/11
Function

The LDU monitors the automatic reset, leak detect pressure switch between the gas valves. During the first test phase,
called «Test1», the downstream gas valve is powered for 4 seconds, providing atmospheric pressure between the
valves being tested. If the upstream gas valve is leaking, causing the pressure to rise above the set point of the leak
detect switch, the LDU will initiate a lockout and trigger an alarm (optional). The program indicator then stops at
«Test1» to indicate the upstream gas valve is leaking. If no leak is detected in the upstream gas valve, the LDU control
continues its program with the second test phase.

During the final test phase, «test 2», the upstream gas valve is powered for 4 seconds, pressurizing the area between
the gas valves. During this test, the pressure between the gas valves may not decrease below the set point of the
pressure switch. If pressure falls below the set point, the LDU control will initiate lockout and prevent the burner from
starting up. The program indicator on the front dial then stops at «Test2» to indicate the downstream gas valve is
leaking.

On successful completion of the second test phase, the control unit closes dual internal relays to complete the internal
control loop between terminals 3 and 6. The LDU recycles to the start position for the next test. During these steps,
the positions of the control contacts remain unchanged. If a lockout occurs, terminal 13 is powered and may be wired
to an external alarm.

LDU Sequence of operations, 60 Hertz


Dial Terminal Operation
Symbol powered Performed
1 Pow er into LDU

Start position
none
Internal diagnostic test

Downstream SOV opens,


9 evacuating pressure
between gas valves.

T e rm in a l 1 5 p ro v id e s
p o w e r th ro u g h th e le a k
Test1 15-16 sw itc h to te rm in a l 1 6 .
If a le a k is d e te c te d ,
te rm in a l 1 7 is p o w e re d
a n d lo c k o u t o c c u rs.

none Internal diagnostic test

U p stre a m S O V o p e n s ,
11 p re s su riz in g c h a m b e r
b e tw e e n g a s v a lv e s.

T e r m in a l 1 5 p r o v i d e s
p o w e r th ro u g h th e lea k
s w i tc h to t e r m i n a l 1 7 .
Test2 15-17 I f a le a k i s d e t e c te d ,
term in a l 1 6 is p o w ered
an d lo c k o u t o ccu rs.
Upon successful
com pletion of the test 2,
3-6 the LD U closes dual
internal relays to complete
the terminal 3 to 6 circuit.

T e rm in a l 6 is p o w e re d
c o n tin u o u sly s ig n a lin g a
III 6 su c e ssfu l te st. P ro g ra m
d ia l re tu rn s to sta rt
p o sitio n fo r n e x t te s t.

Tim e (Seconds) 0 2 6 24 26 30 52 54 72
from start of test
LDU requires 54 seconds to complete a successful test.
From original start, 72 seconds required to return to start for next test.

Page 4/11
Program and lockout indicator

In the event of lockout, the LDU control stops and the position indicator on the front of the
unit lights bright orange. The symbol that stops above the reading mark indicates the test
phase during which lockout occurred and also gives the number of programming steps com-
pleted from the start of this test phase (1 step = 2.5 seconds). In the event of lockout, all
terminals receiving voltage from the control unit will be deenergized, except terminal 13,
which is used for lockout indication. The clear window in front of the indicator dial is the
reset button. Push once to reset the unit. After a reset, the programming mechanism auto-
matically returns to its start position to immediately program a new valve leak test.

Note Do not press and hold the reset button for more than 10 seconds.

Calculating the leakage rate escaping from a length of pipe

(P I -Pset ) x x

V
Leak = Patm x t Test

Legend Symbol Unit Description


3
Vleak ft / hr Valve leakage rate in ft3 per hour

PI PSI Inlet gas pressure. Pressure upstream of both shut-off valves.

Pset PSI Gas pressure setting on pressure switch I (normally set to 50 % of PI)

Patm PSI Atmospheric Pressure downstream of gas valves. Typically 14.7 PSI.
3
V ft / hr Volume between the gas valves to be tested. See table (1).

Ttest seconds Fixed at 22.5 seconds for test 1, and 27.5 seconds for test 2.

Pipe Size Total Gas Volume (cu ft)


" NPT by Pipe Length between valves
Siemens
VGD .5 ft. 1 ft. 1.5 ft. 2 ft. 3.25 ft. 5 ft.
Valves
0.50 0.006 0.008 0.01 0.013
0.75 0.01 0.0125 0.015 0.02
1.00 0.01 0.013 0.016 0.019 0.025 0.034
1.50 0.026 0.022 0.032 0.042 0.052 0.064 0.088
2.00 0.028 0.043 0.055 0.067 0.078 0.102 0.138
2.50 0.046 0.08 0.103 0.13 0.15 0.177 0.247
3.00 0.054 0.17 0.191 0.222 0.242 0.311 0.4
4.00 0.106 0.21 0.3 0.37 0.466 0.508 0.65
Table 1. Volume between gas valves.

Example leak detection calculations can be found in the following section under single and dual
switches.

Page 5/11
Wiring and setting of LDU… Single Leak Detection Pressure Switch:

LDU11
14

15

NC 16
C
NO 17
Pressure Switch I

During Test 1, power is on Terminal 15. After the area between the gas valves has been
evacuated of pressure, the switch should have power through terminal 15 to terminal 16. If the
main gas valve is leaking, the area between the gas valves fills with gas, leak detection pressure
switch I trips, sending power to terminal 17, causing a lockout.

During Test 2, Terminal 15 is powered, and with pressure between the gas valves, terminal 17
will also be powered. If the blocking gas valve is leaking, the area between the gas valves losses
pressure. Leak detection pressure switch I trips, power is sent to terminal 16, resulting in a
lockout.

Leak detection pressure switch should be set at 50% of the gas pressure upstream of the
main shut-off valve.

Example Leakage Rate Calculation


Using Siemens 1-1/2” VGD gas valves with an inlet gas pressure of .5 PSI,
calculate the expected leakage rate which will cause the LDU11 to lockout setting one leak detec-
tion pressure switch at .25 PSI:

(P I -Pset ) x x

V
Leak = Patm x t Test

PI = .5 PSI (.5 - .25) * .026 * 3600 = 0.07 ft3/hr


V
Pset = .25 PSI Leak = 14.7 * 22.5 (test1)
Patm = 14.7 PSI (.5 - .25) * .026 * 3600 = 0.06 ft3/hr
V
V = .026 ft3 (From table 1) Leak = 14.7 * 27.5 (test2)

Ttest = 22.5 s (test 1) In this example, if the 1st gas valve is leaking at a rate of 0.07 ft3/hr or
greater, the LDU will lockout during test 1. If the 2nd gas valve is leak-
= 27.5 s (test 2)
ing at a rate of 0.06 ft3/hr or greater, the LDU will lockout during test 2.

If the maximum permissible gas leakage rate (Vleak) exceeds the desired leakage testing
Note rate, use dual leak detection pressure switches.

Page 6/11
Wiring and setting of LDU… Dual Leak Detection Pressure Switches:

LDU11
14

15

NC 16
C
NO
Pressure Switch G

NC
C
NO 17
Pressure Switch A

During Test 1, Terminal 15 is powered. After the area between the gas valves has been
evaluated of pressure, pressure G switch should have power through terminal 15 to terminal 16.
If the main gas valve is leaking, the area between the gas valves fills with gas, pressure switch A
trips, sending power to terminal 17, causing a lockout.

Switch A needs to be set up to a maximum of 50% of the available gas pressure through the
valves. The lower the pressure switch is set, the smaller of a leak will be detected through the
blocking (downstream) gas valve. Setting the switch at or near atmospheric pressure may cause
nuisance lockouts.

During Test 2, Terminal 15 is powered. With pressure between the gas valves, terminal 17 will
also have power through pressure switch A. If the blocking gas valve is leaking, the area
between the gas valves losses pressure, and pressure switch G trips, power is sent to terminal
16, causing a lockout.

Pressure Switch G need to be set at a minimum of 50%, up to 90%, of the inlet gas pressure
through the valves. The higher this switch is set, the smaller a leak will be detected through the
main (upstream) gas valve. Setting the pressure switch G at or near the inlet pressure may
cause nuisance lockouts due to regulator fluctuations.

Example Using Siemens 1-1/2” VGD gas valves with an inlet gas pressure of .5 PSI, calculate the ex-
pected leakage rate which will cause the LDU11 to lockout with two LDU pressure switches, Pa
set at .1 PSI, and Pg set at .4 PSI:

(Pressure differential* V * 3600


V
Leak = Patm x t Test

PI = .5 PSI (.1) * .026 * 3600 = 0.027 ft3/hr


V
Pa = .1 PSI Leak= 14.7 * 22.5 (test1)
Pg = .4 PSI (.5 - .4) * .026 * 3600 = 0.022 ft3/hr
V
Patm = 14.7 PSI Leak= 14.7 * 27.5 (test2)
V = .026 ft3 (From table 1)
Ttest = 22.5 s (test 1) In this example, if the 1st gas valve is leaking at a rate of 0.027 ft3/hr or greater,
the LDU will lockout during test 1. If the 2nd gas valve is leaking at a rate of
= 27.5 s (test 2)
0.022 ft3/hr or greater, the LDU will lockout during test 2.

Page 7/11
Trouble Shooting

In the event of a lockout, the following steps need to be performed to determine the cause.
1) Check the leak detection switch to ensure it is an automatic reset switch.

2) Determine at which point in the leak test sequence the lockout occurred, by viewing the
front dial of the LDU control.

3) If the lockout occurs during Test 1, manually leak test the upstream gas valve as rec-
ommended by NFPA 86. If the main valve is leaking, lockout the appliance and replace the
valve.

4) If the lockout occurs during Test 2, proceed to step 5.

5) Determine the set-point of the leak test pressure switch. Check the inlet pressure in the
gas train and the set point of the leak detection switch. Use the guidelines on the previous
pages. Re-adjusting the leak detect pressure switch and reset the LDU.

6) Check the wiring and functionality of the leak test pressure switch. If faulty, replace
and/or rewire.

7) Manually leak test the downstream valve as recommended by NFPA 86. If found to be
leaking, lockout the appliance and replace the valve.

8) Reset the LDU by pushing the clear window in front of the indicator dial (do not hold in).

9) Contact local Siemens combustion representative for assistance.

Page 8/11
Connection examples for leak test before burner start-up:

The LDU control may be wired in many different manners, depending upon application, burner
control version and sequence of operations. Below is the generic wiring diagram for performing the
test before burner start-up. Contact Siemens with questions or for assistance.

LDU11...

Optional
Line Voltage Remote
Reset
Button
18
N
Burner 1 2
Operating
Control Downstream
(ON/OFF) 3 9 (Blocking) SOV
Upstream
4 11 (Main) SOV

External Alarm
5 13 (Optional)

14 Vent Valve
(Optional)

Flame Safeguard 15
Terminals
10 NC
16
Terminal which
Powers Main
C
Gas Valves 12
17
NO
Automatic Reset
Terminal which Pressure Switch
Powers Flame 6 (See Options)
Safeguard

Page 9/11
Connection examples for leak test before burner start-up and after shut down with LFL burner control:

Below is the wiring diagram using a LFL flame safeguard performing the leak test before burner
start-up and after a controlled shut-down. This diagram only depicts the wires that are con-
nected to the LDU control. Please consult Siemens manual 7451 for further wiring instructions
for the LFL burner control.

LDU11...
LFL Flame Optional Remote
Safeguard Reset Button N
Terminals 18 2
Downstream
4 1 9 (Blocking) SOV

Upstream
9 3 11 (Main) SOV

10 13 External Alarm
4 (Optional)

8 5 14
11 Proof-of-Closure 20 15
Switch(es)
NC
19 21 16
C
7 23 17
NO
6 24 Automatic Reset
Pressure Switch
8 (See Options)

6
Burner Operating
Control (On/Off)
12 10
22 19

The base plates of the LDU and LFL controls are the same dimensions. Each is keyed during production in
order that the controls may not be installed into the incorrect base plate.

Page 10/11
Dimensions
Dimensions in inches

LDU11... with plug-in


base AGM11

5
1 1
7/16
18,9

5/8

1 1/16 1 1/16

1 3/8

4
1/4

13 14 15 16 17 18 19 20 21 22 23 24
12
18,9
2 11

10

8
31
7
4,4
6

2 4
N
3
32
2

AGM11

Feb 2003 Siemens Building Technologies


Draft - Subject to change Page 11/11

You might also like