LDU11
LDU11
UL recognized
FM approved
                            Features
                               •   Performs leak test of the gas shut-off valves before start-up and/or immediately
                                   after burner shut-down
                               •   No inlet gas pressure limitations
                               •   Easy-to-read dial indicates progress of test program
                               •   Ability to eliminate or leak test the vent valve
                               •   Cost effective control improves system safety
                               •   Globally Approved – cULus, FM, CE
Application
               The LDU11... control detects leakage of the shut-off valves on gas trains with two safety shutoff
               valves. During each burner cycle, the LDU control unit automatically sequences, and if a leak is
               detected, initiates a lockout and prevents the burner from starting up.
Function
              The LDU11 (or control unit) is used in a gas-fired combustion system with or without a vent valve in the gas
              train.
              Installed with one or two pressure switches mounted between the gas valves, the LDU automatically initiates
              gas valve proving either
                   • prior to burner start-up
                   • immediately after the controlled shutdown, or
                   • both prior to burner start-up and immediately after shutdown
              If the leak detect switch signals excessive gas pressure increase during the first test phase «Test1», or
              decrease during the second test phase «Test2», the LDU control will lockout and prevent burner start-up.
              The indicator dial on the front of the unit indicates the progress of the leak test. When a fault occurs, the
              indicator dial stops at the time of lockout, and indicates which of the valves is leaking. In the event of a
              lockout, the reset button on the front of the control will light orange to indicate a fault.
              Pushing the clear window in front of the indicator dial once will reset the LDU control. DO NOT hold in the
              reset button. The LDU may also be reset with a remote button (see wiring diagram).
  Ordering
Warning Notes
                     • All regulations and standards applicable to the particular application must be observed!
                     • Qualified personnel must always carry out installation and commissioning work!
                     • The electrical wiring must be made in compliance with national and local standards and
                     regulations!
                     • The LDU... must be completely isolated from the mains before performing any wiring!
                     • Secure the LDU to the base plate to ensure from protection against electric shock!
                     • Check wiring and all safety functions.
                     • Do not open or modify the control.
                     • Fall or shock can adversely affect the control. Do not put such units into operation, even if
                     they do not exhibit any damage.
Mounting notes
                     The LDU control must be mounted in an enclosure, typically in the control panel containing the flame
                     safeguard. There are no distance restrictions from the gas train. The LDU control is not adversely
                     affected by electromagnetic resonance caused by items such as ignition transformers.
                     One or two automatic reset single-pole, double-throw pressure switches must be mounted in
                     between the gas safety shutoff valves. Manual reset switches are not permitted to be the leak
                     detection switch. No additional piping modifications are required to the gas train.
Page 2/11
Mechanical design
                The front dial provides information about the program sequence, the type of fault and the point in time the
                fault occurred, using easy-to-remember symbols.
Technical data
                                                                                                              Page 3/11
Function
            The LDU monitors the automatic reset, leak detect pressure switch between the gas valves. During the first test phase,
            called «Test1», the downstream gas valve is powered for 4 seconds, providing atmospheric pressure between the
            valves being tested. If the upstream gas valve is leaking, causing the pressure to rise above the set point of the leak
            detect switch, the LDU will initiate a lockout and trigger an alarm (optional). The program indicator then stops at
            «Test1» to indicate the upstream gas valve is leaking. If no leak is detected in the upstream gas valve, the LDU control
            continues its program with the second test phase.
            During the final test phase, «test 2», the upstream gas valve is powered for 4 seconds, pressurizing the area between
            the gas valves. During this test, the pressure between the gas valves may not decrease below the set point of the
            pressure switch. If pressure falls below the set point, the LDU control will initiate lockout and prevent the burner from
            starting up. The program indicator on the front dial then stops at «Test2» to indicate the downstream gas valve is
            leaking.
            On successful completion of the second test phase, the control unit closes dual internal relays to complete the internal
            control loop between terminals 3 and 6. The LDU recycles to the start position for the next test. During these steps,
            the positions of the control contacts remain unchanged. If a lockout occurs, terminal 13 is powered and may be wired
            to an external alarm.
                                          Start position
                                none
                                          Internal diagnostic test
                                        T e rm in a l 1 5 p ro v id e s
                                        p o w e r th ro u g h th e le a k
                 Test1      15-16       sw itc h to te rm in a l 1 6 .
                                        If a le a k is d e te c te d ,
                                        te rm in a l 1 7 is p o w e re d
                                        a n d lo c k o u t o c c u rs.
                                       U p stre a m S O V o p e n s ,
                                11     p re s su riz in g c h a m b e r
                                       b e tw e e n g a s v a lv e s.
                                       T e r m in a l 1 5 p r o v i d e s
                                       p o w e r th ro u g h th e lea k
                                       s w i tc h to t e r m i n a l 1 7 .
                Test2      15-17       I f a le a k i s d e t e c te d ,
                                       term in a l 1 6 is p o w ered
                                       an d lo c k o u t o ccu rs.
                                       Upon successful
                                       com pletion of the test 2,
                            3-6        the LD U closes dual
                                       internal relays to complete
                                       the terminal 3 to 6 circuit.
                                       T e rm in a l 6 is p o w e re d
                                       c o n tin u o u sly s ig n a lin g a
                  III       6          su c e ssfu l te st. P ro g ra m
                                       d ia l re tu rn s to sta rt
                                       p o sitio n fo r n e x t te s t.
                                          Tim e (Seconds) 0 2          6                  24 26 30                     52 54      72
                                          from start of test
                                          LDU requires 54 seconds to complete a successful test.
                                          From original start, 72 seconds required to return to start for next test.
Page 4/11
Program and lockout indicator
                                In the event of lockout, the LDU control stops and the position indicator on the front of the
                                unit lights bright orange. The symbol that stops above the reading mark indicates the test
                                phase during which lockout occurred and also gives the number of programming steps com-
                                pleted from the start of this test phase (1 step = 2.5 seconds). In the event of lockout, all
                                terminals receiving voltage from the control unit will be deenergized, except terminal 13,
                                which is used for lockout indication. The clear window in front of the indicator dial is the
                                reset button. Push once to reset the unit. After a reset, the programming mechanism auto-
                                matically returns to its start position to immediately program a new valve leak test.
Note Do not press and hold the reset button for more than 10 seconds.
(P I -Pset ) x x
                            V
                                Leak =     Patm     x       t Test
Pset PSI Gas pressure setting on pressure switch I (normally set to 50 % of PI)
                        Patm              PSI               Atmospheric Pressure downstream of gas valves. Typically 14.7 PSI.
                                            3
                        V                 ft / hr           Volume between the gas valves to be tested. See table (1).
Ttest seconds Fixed at 22.5 seconds for test 1, and 27.5 seconds for test 2.
                        Example leak detection calculations can be found in the following section under single and dual
                        switches.
                                                                                                                             Page 5/11
Wiring and setting of LDU… Single Leak Detection Pressure Switch:
                                                                                             LDU11
                                                                                             14
15
                                                                                 NC          16
                                                                             C
                                                                                 NO          17
                                                                         Pressure Switch I
                                   During Test 1, power is on Terminal 15. After the area between the gas valves has been
                                   evacuated of pressure, the switch should have power through terminal 15 to terminal 16. If the
                                   main gas valve is leaking, the area between the gas valves fills with gas, leak detection pressure
                                   switch I trips, sending power to terminal 17, causing a lockout.
                                   During Test 2, Terminal 15 is powered, and with pressure between the gas valves, terminal 17
                                   will also be powered. If the blocking gas valve is leaking, the area between the gas valves losses
                                   pressure. Leak detection pressure switch I trips, power is sent to terminal 16, resulting in a
                                   lockout.
                                   Leak detection pressure switch should be set at 50% of the gas pressure upstream of the
                                   main shut-off valve.
(P I -Pset ) x x
                                    V
                                        Leak =     Patm     x       t Test
        Ttest = 22.5 s (test 1)                          In this example, if the 1st gas valve is leaking at a rate of 0.07 ft3/hr or
                                                         greater, the LDU will lockout during test 1. If the 2nd gas valve is leak-
               = 27.5 s (test 2)
                                                         ing at a rate of 0.06 ft3/hr or greater, the LDU will lockout during test 2.
                                   If the maximum permissible gas leakage rate (Vleak) exceeds the desired leakage testing
               Note                rate, use dual leak detection pressure switches.
Page 6/11
Wiring and setting of LDU… Dual Leak Detection Pressure Switches:
                                                                                              LDU11
                                                                                              14
15
                                                                             NC               16
                                                                      C
                                                                             NO
                                                                     Pressure Switch G
                                                                             NC
                                                                      C
                                                                             NO                17
                                                                     Pressure Switch A
                                 During Test 1, Terminal 15 is powered. After the area between the gas valves has been
                                 evaluated of pressure, pressure G switch should have power through terminal 15 to terminal 16.
                                 If the main gas valve is leaking, the area between the gas valves fills with gas, pressure switch A
                                 trips, sending power to terminal 17, causing a lockout.
                                 Switch A needs to be set up to a maximum of 50% of the available gas pressure through the
                                 valves. The lower the pressure switch is set, the smaller of a leak will be detected through the
                                 blocking (downstream) gas valve. Setting the switch at or near atmospheric pressure may cause
                                 nuisance lockouts.
                                 During Test 2, Terminal 15 is powered. With pressure between the gas valves, terminal 17 will
                                 also have power through pressure switch A. If the blocking gas valve is leaking, the area
                                 between the gas valves losses pressure, and pressure switch G trips, power is sent to terminal
                                 16, causing a lockout.
                                 Pressure Switch G need to be set at a minimum of 50%, up to 90%, of the inlet gas pressure
                                 through the valves. The higher this switch is set, the smaller a leak will be detected through the
                                 main (upstream) gas valve. Setting the pressure switch G at or near the inlet pressure may
                                 cause nuisance lockouts due to regulator fluctuations.
Example                          Using Siemens 1-1/2” VGD gas valves with an inlet gas pressure of .5 PSI, calculate the ex-
                                 pected leakage rate which will cause the LDU11 to lockout with two LDU pressure switches, Pa
                                 set at .1 PSI, and Pg set at .4 PSI:
                                                                                                                          Page 7/11
Trouble Shooting
                   In the event of a lockout, the following steps need to be performed to determine the cause.
                   1) Check the leak detection switch to ensure it is an automatic reset switch.
                   2) Determine at which point in the leak test sequence the lockout occurred, by viewing the
                   front dial of the LDU control.
                   3) If the lockout occurs during Test 1, manually leak test the upstream gas valve as rec-
                   ommended by NFPA 86. If the main valve is leaking, lockout the appliance and replace the
                   valve.
                   5) Determine the set-point of the leak test pressure switch. Check the inlet pressure in the
                   gas train and the set point of the leak detection switch. Use the guidelines on the previous
                   pages. Re-adjusting the leak detect pressure switch and reset the LDU.
                   6) Check the wiring and functionality of the leak test pressure switch. If faulty, replace
                   and/or rewire.
                   7) Manually leak test the downstream valve as recommended by NFPA 86. If found to be
                   leaking, lockout the appliance and replace the valve.
8) Reset the LDU by pushing the clear window in front of the indicator dial (do not hold in).
Page 8/11
Connection examples for leak test before burner start-up:
                   The LDU control may be wired in many different manners, depending upon application, burner
                   control version and sequence of operations. Below is the generic wiring diagram for performing the
                   test before burner start-up. Contact Siemens with questions or for assistance.
LDU11...
                                   Optional
          Line Voltage             Remote
                                   Reset
                                   Button
                                                       18
                                                                                                        N
                        Burner                          1         2
                       Operating
                        Control                                                   Downstream
                       (ON/OFF)                         3         9              (Blocking) SOV
                                                                                 Upstream
                                                        4        11             (Main) SOV
                                                                                 External Alarm
                                                        5      13                  (Optional)
                                                               14                 Vent Valve
                                                                                  (Optional)
                      Flame Safeguard                           15
                         Terminals
                                                       10                          NC
                                                                16
                       Terminal which
                       Powers Main
                                                                                                  C
                       Gas Valves                      12
                                                                17
                                                                                   NO
                                                                                    Automatic Reset
                       Terminal which                                               Pressure Switch
                       Powers Flame                     6                             (See Options)
                       Safeguard
                                                                                                      Page 9/11
Connection examples for leak test before burner start-up and after shut down with LFL burner control:
                        Below is the wiring diagram using a LFL flame safeguard performing the leak test before burner
                        start-up and after a controlled shut-down. This diagram only depicts the wires that are con-
                        nected to the LDU control. Please consult Siemens manual 7451 for further wiring instructions
                        for the LFL burner control.
                                                                      LDU11...
               LFL Flame                            Optional Remote
               Safeguard                            Reset Button                                                      N
               Terminals                                              18       2
                                                                                              Downstream
                      4                                               1        9            (Blocking) SOV
                                                                                              Upstream
                      9                                               3      11              (Main) SOV
                   10                                                        13              External Alarm
                                                                      4                       (Optional)
                      8                                               5     14
                    11           Proof-of-Closure                     20    15
                                   Switch(es)
                                                                                                  NC
                    19                                                21    16
                                                                                                                   C
                      7                                               23    17
                                                                                                  NO
                      6                                               24                          Automatic Reset
                                                                                                  Pressure Switch
                                                                      8                               (See Options)
                                                                      6
                                     Burner Operating
                                     Control (On/Off)
                                                                      12     10
                                                                      22     19
             The base plates of the LDU and LFL controls are the same dimensions. Each is keyed during production in
             order that the controls may not be installed into the incorrect base plate.
Page 10/11
                                                                                  Dimensions
                        Dimensions in inches
                                                                                                                 5
                                          1                    1
                                                          7/16
                            18,9
5/8
1 1/16 1 1/16
1 3/8
                                                                                                             4
                                                                                                 1/4
                                          13   14   15   16   17   18   19   20   21   22   23    24
                                     12
                                                                                                  18,9
                        2            11
10
                                     8
                                                    31
                                     7
                                                                                                       4,4
                                     6
                        2            4
                                                                    N
                                     3
                                                                             32
                                     2
AGM11