EE3036 Notes
EE3036 Notes
HV INSULATION SYSTEM
UNIT-I
SUSTAINABLE AND ENVIRONMENTAL ENERGY AND PRODUCTS
Introduction:
Sustainable and Environmental
Sustainable:
Involving the use of natural products and energy in a way that does not harm the
environment.
Causing, or made in a way that causes, little or no damage to the environment and
therefore able to continue for a long time.
Environmental Friendly:
The production system must be economically and socially acceptable, and also nature-
and environment-friendly.
The primary function of high voltage insulators is to insulate, i.e., prevent the flow of
electric current and to keep oppositely charges conductors mechanically separated
during all service conditions.
This means that the insulation of a power apparatus is designed to withstand any
electrical, thermal, and mechanical stress likely to occur during manufacturing,
testing, and the long-expected service lifetime of 30 years or more.
CARBON PRINT:
A carbon footprint (or greenhouse gas footprint) is a calculated value or index that
makes it possible to compare the total amount of greenhouse gases that an activity,
product, company or country adds to the atmosphere. Carbon footprints are usually
reported in tonnes of emissions (CO2-equivalent) per unit of comparison. Such units
can be for example tonnes CO2-eq per year, per kilogram of protein for
consumption, per kilometre travelled, per piece of clothing and so forth. A product's
carbon footprint includes the emissions for the entire life cycle. These run from the
production along the supply chain to its final consumption and disposal.
The carbon footprint concept makes comparisons between the climate impacts of
individuals, products, companies and countries. A carbon footprint label on products
could enable consumers to choose products with a lower carbon footprint if they want
to help limit climate change.
Greenhouse gases (GHGs) warm the Earth by absorbing energy and slowing
the rate at which the energy escapes to space; they act like a blanket insulating the
Earth. Different GHGs can have different effects on the Earth's warming. Two key
ways in which these gases differ from each other are their ability to absorb energy
(their "radiative efficiency"), and how long they stay in the atmosphere (also known
as their "lifetime").
The Global Warming Potential (GWP) was developed to allow comparisons of the global
warming impacts of different gases. Specifically, it is a measure of how much energy the
emissions of 1 ton of a gas will absorb over a given period of time, relative to the
emissions of 1 ton of carbon dioxide (CO2). The larger the GWP, the more that a given
gas warms the Earth compared to CO2 over that time period. The time period usually used
for GWPs is 100 years. GWPs provide a common unit of measure, which allows analysts
to add up emissions estimates of different gases (e.g., to compile a national GHG
inventory), and allows policymakers to compare emissions reduction opportunities across
sectors and gases.
CO2, by definition, has a GWP of 1 regardless of the time period used, because it is
the gas being used as the reference. CO2 remains in the climate system for a very long
time: CO2 emissions cause increases in atmospheric concentrations of CO2 that will
last thousands of years.
Methane (CH4) is estimated to have a GWP of 27-30 over 100 years. CH4 emitted
today lasts about a decade on average, which is much less time than CO2. But
CH4 also absorbs much more energy than CO2. The net effect of the shorter lifetime
and higher energy absorption is reflected in the GWP. The CH4 GWP also accounts
for some indirect effects, such as the fact that CH4 is a precursor to ozone, and ozone
is itself a GHG.
Nitrous Oxide (N2O) has a GWP 273 times that of CO2 for a 100-year timescale. N2O
emitted today remains in the atmosphere for more than 100 years, on average.
Chlorofluorocarbons (CFCs), hydrofluorocarbons (HFCs), hydrochlorofluorocarbons
(HCFCs), perfluorocarbons (PFCs), and sulfur hexafluoride (SF6) are sometimes
called high-GWP gases because, for a given amount of mass, they trap substantially
more heat than CO2. (The GWPs for these gases can be in the thousands or tens of
thousands.)
Global Warming Potential Example:
For example, the GWP100 for nitrous oxide (N2O) is 273. This means that 1 tonne of N2O
causes the same amount of warming as 273 tonnes of CO2 (in this case over 100 years).
Burning fossil fuels, cutting down forests and farming livestock are increasingly influencing
the climate and the earth's temperature. This adds enormous amounts of greenhouse gases to
those naturally occurring in the atmosphere, increasing the greenhouse effect and global
warming.
Introduction:
Two governing factors have been normally considered in a conventional design of electrical
systems, these are low cost and reliable performance.
Since the environmental issue becomes increasingly important, the associated design
guidelines and legislations have been proposed and implemented in more and more countries.
Material selection:
For instance (example), the Montreal and Tokyo agreement, European standard on
environment, a standard specifically for electrical equipment known as WEEE (Waste
from Electrical and Electronic Equipment), and most importantly ISO 14000.
It is a potent greenhouse gas with a high global warming potential, and its
concentration in the earth atmosphere is rapidly increasing.
During its working cycle, SF6 decomposes under electrical stress, forming toxic by-
products that are a health threat for working personnel in the event of exposure.
During its working cycle, SF6 decomposes under electrical stress, forming toxic by-
products that are a health threat for working personnel in the event of exposure.
In its normal state it is chemically inert, non-toxic and non-flammable. Because of its
inertness and non-toxic characteristics it has been treated as an environmentally safe
and acceptably non-toxic material, in the sense that it does not react unfavourably
with the biomass.
Much effort has been spent in identifying the species, the generation rates, and some
of their properties, under laboratory or practical operating conditions in GIS power
systems.
The possible formation of SF4, SF2, S2F10, SO2, SOF2 SOF4, SO2F2, SOF10,
S2O2F10, HF, and H2S during degradation of SF6 is now well documented and
widely accepted by workers in this field.
The compounds formed include not only gaseous sulfur fluorides and sulfur
oxyfluorides but also metal fluorides formed by the reactions with electrode materials
and spacers.
Recent experimental work has established that the production yield of some of the
contaminants (i.e., S2F10) may be affected by the presence of water, oxygen, or even
surface reactions originating by the presence of organic insulates, for example poly
tetra fluoro ethylene [PTFE], under corona, spark, and arc discharges).
In addition, high energy photons and high energy X-rays lead to decomposition
of gaseous SF6 forming corrosive oxyfluoride by-products comparable to the ones
obtained during corona discharge occurrence.
Table 2 provides typical net production yields for several SF6 decomposition products
formed during electrical discharges.
sustainable solution has not been found- until now, that is—because of the numerous,
low GWP;
ALTERNATE GASES:
Grid Solutions, a GE and Alstom joint venture, has identified a fluoronitrile based gas
mixture dubbed ‘g3—green gas for grid’ that is such a alternative.
Environmental considerations are increasingly taking a front seat in all arenas of our
daily lives— political, industrial and societal.
Not least among the major concerns are global warming and the greenhouse gases that
contribute to it, as their concentration in the air reaches new heights.
Hence the power industry’s focus on sulfur hexafluoride (SF6) and the need to find a
suitable alternative for it in industrial applications.
Grid Solutions, a GE and Alstom joint venture, has identified a fluoronitrile based
gas mixture dubbed ‘g3—green gas for grid’ that is such a alternative.
Currently the first SF6-free high voltage equipment are available offering the same
performances and footprints that SF6 insulated equipment provide at similar and
affordable economic conditions. GE’s Grid Solutions business fluoronitrile based gas
mixture dubbed ‘g3— green gas for grid’ has been proven as a suitable replacement
for SF6.
g3—Green Gas for Grid:
Pure 3M™ Novec™ 4710 Dielectric Fluid has liquefaction at a low temperature
which means that it cannot alone replace SF6.
On further investigation, it was found that the best solution was to mix it with CO 2—
for the latter’s arc quenching capability—to create a gas mixture suitable for
disconnector and circuit breaker applications.
The resulting mixture was dubbed ‘g3—green gas for grid’. Depending on minimum
operating temperature and maximum filling pressure, g3 can be based on 4%vol,
6%vol or 10%vol Novec™ 4710 fluid.
These three mixtures allow covering the majority of the specification for indoor and
outdoor application.
Like the heptafluoro-iso-butyronitrile itself, the toxicity of g3 was also compared to the EU
1272/2008 CLP regulation dealing with Classification, Labelling and Packaging of chemicals
and the European Agreement concerning the International Carriage of Dangerous Good by
Road (ADR)—where the toxicity of a gas mixture (LC50) is calculated by taking into
account the toxicity (LC50i) and the mole fraction or volume fraction ( fi) of each substance:
LC50 (mixture) = 1/(Rfi/LC50i).
Then the LC50 of g3 can be derived from the previous formula and goes from approximately
100,000 ppmv to 190,000 ppmv for 10% to 4% Fluoronitrile respectively. These figures were
confirmed by tests performed by independent and accredited toxicological lab. Additional
toxicity measurements made after current interruption test demonstrate that used g3 is
basically slightly less toxic than used SF6.
The heat dissipation capability of g3 was determined by temperature rise tests on a 420 kV
busbar arrangement filled with the gas mixture at 5.5 bar for a minimum operating
temperature of –25°C. The results were then compared to a system filled with SF6 at 5.5 bar
as a reference. The test setup was equipped with temperature sensors to monitor the
temperature rise.
Considering that the heat dissipation within a GIS arrangement is mainly driven by
convection, Vermeer’s constant was determined. Vermeer’s constant is linked to the gas’s
physical properties, such as density t, thermal conductivity m, specific heat capacity Cp and
dynamic viscosity h using the following formula:
and was found to be equal to 13.8 for heptafluoro-iso-butyronitrile. This means that the pure
gas has a higher heat dissipation capability than SF6. Then the convection constant of g3 can
be derived from the gas mixture formula Cmix = C1(x1)0.75 + C2(x2)0.75, where Ci and xi
stand for the convection coefficient and volume fraction of gas i. The heat dissipation of g3 is
a little lower than pure SF6 but still higher than CO2.
It was ascertained that with g3 the Global Warming Potential can be brought down by over
98% compared with SF6 depending on the application. The GWP of g3 was calculated
according to the F-gas regulation4 where the total Global Warming Potential of a mixture that
contains fluorinated greenhouse gas is calculated as a weight average, derived from the sum
of the weight fractions of the individual substances multiplied by their GWP. For an example,
the gas mixture used in the 420 kV GIB present a GWP of about 330 which is less than 1.5%
the GWP of an equivalent SF6i insulated GIB.
Testing on Equipment:
Under application conditions, the dielectric performance of different g3 gas mixtures were tested on a
typical 145 kV SF6 GIS arrangement with a disconnector/earthing switch connected to a
cable end box. The performance of the mixtures was compared to SF6 under lightning
impulse and power frequency. Table 1 shows the insulation performance relative to SF6
assuming a 50% probability of flashover in negative polarity—which is the worst polarity for
both SF6 and the alternative gas mixtures. The dielectric performance of the tested mixtures
at pressures of 6.7 to 8.2 barabs is between 87 %–96% of that of pure SF6 at 5.5 barabs.
It should be noted that the standard deviation measured on the gas mixtures is essentially the
same as for SF6, or even lower. The small difference in dielectric performance can be
compensated by design adjustments or with a dielectric coating in high stress electrodes. For
power frequency tests, all the mixtures withstood 300 kV for one minute.
Temperature rise tests were performed on a fully equipped three-phase encapsulated 145 kV
GIS bay containing a circuit breaker, a current transformer, two busbar disconnectors/
earthing switches, a line disconnector/earthing switch and a cable end box. The conductors
were equipped with about 200 temperature sensors to monitor temperature rise
for different gas formulations.
The disconnector was filled with a g3 mixture for a minimum operating temperature of –
25°C at a total pressure of 5.5 bar. Arcing time proved to be stable over the 100 operations
with average arcing time comparable to those that are typical for SF6.
This means that the gas mixture tested is eminently capable of switching bus-transfer current
and can be used as a substitute to SF6 for this application. Arcing contacts presented
electrical wear similar to SF6.
g3 in Action:
All these exhaustive laboratory and equipment tests provided conclusive evidence that g3 is
an effective and highperforming substitute for SF6. This meant that it is now Possible to
deliver switchgear that responds to the demand for more environmentally sustainable high-
voltage electrical equipment.
A third, a 145 kV circuit breaker, is in the final stages of development and will soon be ready
for the market.
Circuit Breaker
GE Grid Solutions business decided to adapt their last generation of 145 kV GIS to g3
technology. This involved testing the GIS bay in its entirety including the circuit breaker.
With a customer interested in a pilot project for a 145 kV GIS using g3.
Currently the first SF6-free high voltage equipment are available offering the same
performances and footprints that SF6 insulated equipment provide at similar and affordable
economic conditions. GE’s Grid Solutions business fluoronitrile based gas mixture dubbed
‘g3— green gas for grid’ has been proven as a suitable replacement
for SF6.
The first applications will be commissioned soon and the extension of Grid Solutions g3
portfolio is underway. As environmental concerns become an increasing focus of
governments, regulators and consumers, the development of g3 adds momentum to the on-
going quest for a more sustainable high-voltage switchgear equipment solution. By adopting
g3 solutions for their new assets final users of high voltage equipment may anticipate and
protect themselves from possible increasing regulatory and customer pressure to reduce their
environmental footprint. The advent of g3, as a ground-breaking step towards a greener
industry, will help them satisfy that requirement.
UNIT III
ALTERNATE GREEN LIQUID INSULATORS
Green insulating liquids Vegetable insulating liquids are a potential alternative to mineral
insulating oil for application in HV apparatus, but they also fulfil environmental and health
demands, for instance, nontoxicity, biodegradability, recyclability, and non-hazardousness.
Undoubtedly, VOs are abundantly available as a natural resource and thought to be green and
reasonable insulator.
The liquid insulation system is applied both as an insulator and a coolant in several elements
of the HV network comprising cables, switchgear and transformers.
Mineral oil (MO)- Mineral transformer oil is exposed to mechanical and electrical stresses
when transformers are running and the oil is stable at higher temperature, but it exhibited low
thermal conductivity. As the time passes by, the oil gets contaminated with impurities and
properties of the oil are degraded and so it is discarded as a waste. The impurities present in
waste transformer oil such as polychlorinated biphenyls (PCBs), polycyclic aromatic
hydrocarbons (PAHs), harmful gases and heavy metals etc. contaminate the environment and
has hazardous impact on land, water, air and on living beings
Mineral transformer oil spills occur in the environment when a power transformer is
damaged.
The pollutants present in waste transformer oil are polychlorinated biphenyls (PCBs), heavy
metals, polycyclic aromatic hydrocarbons and hazardous gases etc. which makes the oil more
toxic and adversely affect the environment and living beings.
The transformer oil during use gets contaminated with PCBs and becomes hazardous and
hence it is discharged. During the discharge of this waste transformer oil the environment is
the recipient. It goes into the environment through incineration of PCBs containing wastes,
leakage of oil from old electrical equipment, through runoff, improper disposal of waste oils,
volatilization
transformer oils and found that mineral transformer oil are hazardous to environment having
low biodegradability, contaminate the waterways and soil if spilled or leakage occurs and
transformer mineral oils consists of complex mixture of hydrocarbons and PCBs components.
Since the base fluid of transformer oil is the mineral oil hence some of the toxic effects are
listed below in Table.
The transformer oil impacted soil contaminated with heavy metals is due to anthropogenic
activities and it has adverse effect on human health if the significant amount of its daily
dosage occurs with long term exposure. Since it also contains persistent organic pollutants
(POP) which are hazardous substances can cause serious environmental effects. As compared
to adults’ children are more vulnerable to contaminated environmental pollution.
Hence mineral oil, silicon liquids are classified as hazardous and will damage the
environment.
Alternate Sources of Environmental Friendly Liquid Such as
Ester Oil, Vegetable Oils Dielectric and its Properties.
Natural ester liquids indicated adequate dielectric traits, superior chemical stability and lower
pour point. They manifested outstanding properties as compared with MO, for instance,
higher fire and flashpoint temperatures and superior biodegradability conduct.
These also have a smaller pour point, high humidity tolerant and enhanced operation at
elevated temperature, and these are toxic-free and freely decomposable.
VOs also termed as NEs or bio-based liquids are commonly extracted from contemporary
entities and derived from plants yields usually sunflower, rapeseed and soybean.
The first transformer prototype with VOs as an insulating medium was developed in 1996;
however standard fabrication of transformer immersed with VOs initiated in 1999.
Timeline events in the development and applications of NEs insulating liquids are given in
Figure.
Figure: Timeline of proceedings in the development and application of natural-ester insulating fluids.
Natural esters are obtained from different plant-based seed oils. Their physical and chemical
traits rely on their sources of origin, chemical configuration and saturation/unsaturation
proportion of fatty acids.
The contaminants (moisture, particles, gases) existing in the oil highly impact dielectric
strength, which results in the trend to compare them with traditional MOs by observing the
contamination level.
Water absorption of natural esters and MOs makes a huge deference among them in terms of
humidity-absorbing ability; NEs possess more excellent moisture-absorbing capability (20–
30 times more) in comparison to MOs which affects the impact of moisture on BDV.
On the subject of security, environmental concerns and thermal characteristics, natural esters
ensure better features in comparison to MO. They are categorized as extraordinary fire point
liquids with self-quenching traits and appropriate for several industrialized applications.
Thermal features and relationship with cellulose insulation contribute toward extended
insulation lifetime and permit greater or prolonged overloads, over a longer period without
unusual failure of dielectric structures.
Natural esters are deliberated as the suitable substitute of MOs in the applications where fire
protection, ecological vulnerabilities or better insulation qualities are necessary. Fire safety is
one of the main concerns of today’s research community due to the applications of insulating
fluids in some sensitive areas for instance, subway channels, ships, offices, shops,
workplaces, etc.
There are multiple examples of equipment explosion leading to exterior fires that are very
hard to quench and may cause the extension to atmospheres due to the seepage of oil. Typical
characteristics of natural ester and MO are given in Table.
Electrical Properties:
The dielectric constant of natural ester influences the dielectric constant of paper insulation
impregnated with ester liquids that are superior to that of MOs.
Because of the closer permittivity values of natural esters and impregnated paper insulation, a
greater stress is undergone on paper insulation in the case of natural esters liquids than MOs.
The dielectric features of various sorts of insulating fluids are presented in Table.
The dielectric strength (DS) of insulating material is a measure of its capability to endure
electrical stress without collapse. The BDVs of an insulating structure (liquid and solid
insulation) is one of the key factors for the electrical structure of HV equipment. It may be
defined as the lowest voltages at which there occurs electric conduction that leads to a
dielectric rupture. BDV is also termed dielectric strength or striking voltage.
The insulation system provides insulation up to a specific voltage extent beyond which
insulation BD happens. The voltage at which BD happens is called BDV or DS of insulation.
This BDV signifies the electrical insulation competency of the insulation system; thus, a
small value manifests that the insulation system is not a good insulation system.
All the insulation systems for HV equipment must fulfil AC withstand voltage, lightning
impulse (LI) and switching impulse test standards. Numerous investigations have been
conducted by multiple researchers to observe the BDV, discharge properties of various
insulation systems.
The impulse strength of the insulation system specifies its capability to endure HV transients
of a very short period, for instance, those it may be exposed to through lightning strikes.
The standard lightning impulse (LI) specifies simulating lightning shots and usually uses
1.2μs surge for a wave to achieve a 90% amplitude and decline down to 50% amplitude after
50 μs. The LI BDV is generally examined by IEC 60897 standard.
Physical Properties:
Vegetable oil:
Vegetable oils and their esters are being investigated as potential substitutes for mineral
insulating oils used in medium-voltage electrical equipment like transformers, due to their
environmental advantages like biodegradability and renewability.
Properties like breakdown voltage, pour point, and viscosity were measured for several
seed oils and their esters and compared against IEC standards for mineral oils and synthetic
esters.
Some seed oils like rapeseed oil and their esters were found to meet or exceed the dielectric,
viscosity and pour point requirements after chemical modifications like esterification.
Vegetable oil-based dielectrics also showed advantages like higher flash/fire points, better
thermal properties like heat capacity and conductivity, and lower expansion coefficients
compared to mineral oils.
In summary, the promising initial results for vegetable oil-based dielectric coolants as greener
substitutes for traditional mineral oils in distribution transformer.
Properties Measured:
Breakdown voltage (IEC 60156)
Pour point (ISO 3016)
Viscosity at 40°C (ISO 3104)
Key Results:
Untreated seed oils and esters showed breakdown voltages up to 70-99 kV, meeting IEC
requirements after accounting for higher moisture saturation limits.
Untreated seed oil viscosities (41-261 mm2/s at 40°C) exceeded IEC limits, but esterification
reduced viscosities to 5-16 mm2/s, meeting requirements.
Untreated seed oil pour points (-15 to -27°C) didn’t meet the -40°C limit, but esters from
larger alcohols had pour points < -38°C, meeting the limit.
Flash points 315-328°C and fire points 350-360°C, higher than mineral oils (100-185°C).
Volume expansion coefficients 5.5-5.9 x 10^-4 K^-1, lower than mineral oils (7-9 x 10^-4
K^-1).
Biodegradability & Aging:
Vegetable oils are inherently biodegradable unlike mineral oils.
Oxidation inhibitors and metal passivators may be needed as additives to improve
oxidative stability.
Sealed transformer designs limit air exposure to slow oxidation:
Esterification Process:
To improve properties like viscosity, the authors performed esterification on the vegetable
oils. This involves breaking down the triglyceride molecules into three separate fatty acid
esters by reacting with an alcohol like methanol or isopropanol.
This reduces the molecular size/weight, lowering the viscosity
Breakdown Voltage:
While untreated vegetable oils had high moisture contents (150-200 ppm), their high
saturation limits mean this absolute moisture corresponded to relatively low relative
humidities of ~27%. This is comparable to typical mineral oil moisture levels after
dehydration treatment, explaining why the vegetable oils could still achieve the required
breakdown voltage performance.
Environmental Benefits:
Being bio-derived and biodegradable are the key environmental advantages of vegetable oils
over mineral oils. Their renewability from crops and lack of toxicity are also beneficial.
However, oxidative aging remains a challenge that may require food-grade antioxidant
additives.
Technical Benefits:
1. High Fire Safety – Vegetable oils exhibited much higher flash points (315-328°C) and
fire points (350-360°C) compared to mineral oils, making them more fire-resistant.
2. Good Thermal Properties – Vegetable oils had similar or better thermal
conductivities, heat capacities and lower volume expansion coefficients beneficial
for heat transfer performance.
3. Vegetable oil-based dielectric fluids provide an environmentally-friendly alternative to
mineral oils while also offering technical performance benefits like higher fire safety
and potential economic benefits, making them promising candidates for transformer
application.
Mineral oil and Natural ester (Rice bran oil and Sunflower oil) are analysed and from the
analysis, it is concluded that vegetable oils have better breakdown voltage, flash point, fire
point, Density of oil, than the mineral oil.
UNIT IV
SOLID INSULATORS:
Solid insulator means the insulating coating of wiring harnesses, provided in order to
cover and prevent the high voltage live parts from any direct contact.
Solid insulation
Insulating paper
Plant fiber paper includes cable paper, capacitor paper, winding paper, etc.
Solid dielectrics vary widely in their origin and properties. They may be natural
organic substances, such as paper, cloth, rubber, etc.
Some key environmental effects on the dynamics and life-time of ceramic and
polymeric insulators. That high pollution levels are non-uniformly distributed and are
correlated with, for example, industrial and marine regions. In these regions, the
pollution, aging and degradation of insulator materials is accelerated compared to
relatively unpolluted regions, where the degradation is more predictable over time.
The rate of the environmental pollution of HV insulators depends on the weather
conditions, surface roughness wettability, and insulator geometry. The mechanism of
pollution of HV insulators is mainly governed by the gravity, wind forces,
electrostatic forces, humidity, particle size and mass, and chemical properties of the
insulators. The analyses indicate that the presence of pollutants on insulator surfaces
leads to different types of electrical discharge such as corona, partial discharge and
dry band arching which result in the accelerated degradation of insulators and the
surrounding infrastructure and ultimately can cause flashover and blackouts. Although
multiple methods were devised to improve the material surface of insulators, the
surface pollution associated with aerial deposits and electromagnetic radiation cannot
be totally avoided.
In the electricity sector, this is acknowledged that the lifespan of the HV apparatus is
primarily based upon used insulation arrangement (usually liquid and solid insulating
materials) status. This arrangement forms the main insulating constituent of the
insulation system executing the threefold operation of the electric barrier, mechanical
backing and heat outflow route.
The major insulating media for HV equipment generally comprises of greatly solid
insulation.
The BDVs of an insulating structure (liquid and solid insulation) is one of the key
factors for the electrical structure of HV equipment. It may be defined as the lowest
voltages at which there occurs electric conduction that leads to a dielectric rupture.
BDV is also termed dielectric strength or striking voltage. The insulation system
provides insulation up to a specific voltage extent beyond which insulation BD
happens. The voltage at which BD happens is called BDV or DS of insulation. This
BDV signifies the electrical insulation competency of the insulation system; thus, a
small value manifests that the insulation system is not a good insulation system. The
DBV is influenced by the physicochemical properties of materials used, and it is
sensitive to humidity and particulate content.
The oxidation of liquid insulation is a critical matter since it leads to the development
of derivatives, e.g., acids and sludge, which in turn originate issues in the apparatus
by decreasing dielectric features of solid insulating material.
Thermosets are widely used for insulation protection of electrical equipment and play
notable roles in advanced electrical systems for their excellent electrical properties,
thermal stability and mechanical properties. Conventional electrical insulating
thermosets are processed complicatedly and unfriendly to environment during
manufacture, operation, and maintenance and recycling. The advancement of green
power grids and the promotion of sustainable development have spurred considerable
interest in environmental-friendly electrical insulating thermosets. Green synthesis
technology and design of recyclable molecular structure are emerging technologies
for preparing environmental-friendly electrical insulating thermosets. Environmental-
friendly electrical insulating thermosets and mainly introduced bio-based electrical
insulating.
The development of new catalysts is not only It can improve catalytic efficiency and
insulation material. Use organic catalysts instead of gold Catalysts are an important
means to achieve green catalysts. Solvent is often as reaction medium and diluent, its
and improve air quality, etc. Use water as a solvent It is the main development of
materials.
UNIT V
As power systems continue to evolve and demand for electricity increases, power
system equipment faces higher operating demands. One critical aspect of power
system equipment is insulation, which plays a crucial role in ensuring the safe and
efficient operation of electrical infrastructure.
Higher operating demands in power systems result from factors such as increased
power consumption, renewable energy integration, and the electrification of various
sectors. These demands put additional stress on power system equipment, including
transformers, cables, and switchgear. Traditional insulation materials may struggle to
withstand the increased temperatures, electrical stresses, and environmental
conditions associated with these higher operating demands.
Higher operating demands also require improved electrical insulation to ensure the
safe and reliable operation of power system equipment. Insulation materials with
higher dielectric strength and lower dielectric losses have been developed to minimize
electrical stress and prevent breakdowns. Additionally, advancements in
nanotechnology have led to the development of nanocomposite insulation materials,
which offer superior electrical insulation properties and enhanced resistance to partial
discharges.
Environmental Considerations
Higher operating demands necessitate insulation materials that can withstand harsh
environmental conditions and prolonged service life. Manufacturers are incorporating
additives and modifiers into insulation materials to enhance their durability and
resistance to aging. Additionally, advanced testing and monitoring techniques, such as
partial discharge measurements and thermal imaging, are being employed to assess
the condition of insulation in real-time, allowing for proactive maintenance and
replacement strategies.
The standards suggest the use of the previous insulation system as a reference in the
qualification process of a new insulation wall.
Many standards exist and provide procedures and test methods for estimating the
lifetime of an insulating system submitted to thermal stress (Ul-746, UL-1446, IEC-
60216, IS-11182, etc.). Many other factors cannot be well-quantified and should be
studied later. For example, the customer does not always know how many times his
machine will operate under overvoltage or overload conditions as well as their
duration. Studies periodically confirm that thermal aging is responsible for the
greatest number of outages and subsequently, a good method to initiate the design of
electrical insulation is to first deal with the effect of thermal aging. Thermal aging
does not apply to all elements of an insulation system. All the elements or materials
used do not have the same behavior in front of this constraint. Hence, it may be
possible to increase the expected lifespan of an insulation system by modifying only
one of its components: the weakest one. The constitution of insulation wall must be
examined, and, in particular, the arrangement of the insulation layers in machines
which should have a high service life. These machines are essentially high voltage
machines.
The standards, IEC and IEEE, request that turn insulation must be able to withstand a
surge pulse. In observing the IEC standard, the test voltage is 0.65 times the surge
voltage (4 Un + 5 kV) and the rise time is around 0.2 μs. The surge test also takes into
account the main insulation; it must be able to withstand a surge (4 Un + 5 kV) rise
time 1.2 μs.
The standards provide any indication about the combination of constraints. However,
the standards do not provide any indication about the combination of constraints.
Moreover, many stresses are out of the scope: mechanical stress, moisture, starting
conditions, etc. Manufacturers are aware of these limits and believe that existing
standards need to be improved.
During the standard ageing test, the coils are not powered and are not submitted to
mechanical stresses. Moreover, the standards suggest that any added mechanical
stress or electrical stress, should not introduce any significant additional aging during
the thermal aging test.
The dielectric, mechanical, and thermal properties of some biobased materials and
their possible applications are introduced in following paragraphs.
Bio-based thermoplastic polymers in polymeric insulation. PLA, which is derived
from corn, sorghum, and plant roots, is a bio-based material with good electrical
performance. To assess the feasibility of PLA as a dielectric insulation, the volume
resistivity, relative permittivity, and dielectric loss tanδ of PLA are measured.
The volume resistivity (4.9–5.5 × 1017 Ω·cm), dielectric constant (3–3.8), and tanδ
(0.02–0.022) of polylactic acid (PLA) are slightly greater than those of cross-linked
polyethylene (XLPE).