2TFH360001A1003
2TFH360001A1003
—
Receiving, handling and storage
1
Receiving and handling
Warning Upon receipt, carefully inspect the trans-
Indicates a hazardous situation that,
if not avoided, could result in death fer switch for damage that may have oc-
or serious injury.
Avertissement: curred during transit. If damage is evi-
Indique une situation dangereuse
qui, si elle n'est pas evitée, pourrait dent, or there is visible indication of
entraîner la mort ou de graves
blessures. rough handling, immediately file a dam-
age claim with the transportation com-
pany, and notify your local ABB sales
office.
HAZARD OF EQUIPMENT
OVERTURNING Do not remove the shipping packaging
When moving with a fork lift, do not until ready to install the switch.
remove the shipping packaging until the
device is in its final location. Storage
If the unit will not be placed into service
Failure to follow this instruction may immediately, store the transfer switch in
result in personal injury or equipment its original package in a clean, dry loca-
damage. tion. To prevent condensation, maintain a
uniform temperature. Store the unit in a
heated building, allowing adequate air cir-
culation and protection from dirt and
moisture. Storing the unit outdoors could
cause harmful condensation inside the
transfer switch enclosure.
4 Z e n i t h Z B T S T- s e r i e s 1 0 0 0 A - 3 0 0 0 A By pass Is o l at i o n AT S
—
Read these safety instructions
carefully before using this product!
—
Operation, maintenance,
and installation
instruction
OPER ATION AND MAINTENANCE
INSTRUCTIONS, Zenith
1
Bypass isolation ZBTS T-Series ATS,
Chapters 1– 8
Automatic transfer
switches, Zenith
ZBTS T-series ATS Install ation instructions,
zenith ZBTS T-Series ATS,
2
Chapters 9 –11
6 Z e n i t h Z B T S T- s e r i e s 1 0 0 0 A - 3 0 0 0 A By pass Is o l at i o n AT S
1
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 7
—
Operation and
maintenance instruction
Bypass isolation
1
Automatic transfer
switches, ZBTS T-series
1. Introduction 11
2. Product overview 15
3. General operation 39
5. Electronic accessories 81
1
5.9 Switch-Test/Auto/Inhibit/Start 118
5.10 Audible Transfer Alarm 119
6. Troubleshooting 121
8. Maintenance 137
9. Installation 139
—
1. Introduction
1
basic operation, and maintenance of the
Zenith ZBTS T-series (1000A-3000A) by-
pass isolation automatic transfer
switches, manufactured by ABB. Installa-
tion for the transfer switch and available
accessories can be found in chapters 9
and 10.
—
1.1 Hazard Categories
The following important highlighted
information appears throughout this Warning
Indicates a hazardous situation that, if not
document to warn of potential hazards avoided, could result in death or serious
injury.
or to call attention to information that Avertissement
Indique une situation dangereuse qui, si elle
clarifies a procedure. n'est pas evitée, pourrait entraîner la mort
ou de graves blessures.
Notice
It is used to notify of practices not related
to personal injury. Failure to comply with
these instructions may result in product
damage.
Remarque
Il est utilisé pour notifier des pratiques non
liées à des blessures corporelles. Le non-re-
spect de ces instructions peut entraîner
des dommages au produits.
12 Z e n i t h Z B T S T- s e r i e s 1 0 0 0 A - 3 0 0 0 A By pass Is o l at i o n AT S
—
1.2 Definitions
ATS/BYP PARALLEL
Both ATS and Bypass switch contacts are
connected to source 1 power / source 2
power
Ekip
Electronic accessories / Ekip-modules;
communication, signaling and
connectivity modules
HMI
Human Machine Interface for operating
and configuring of the ATS control system
Level 4 Controls
Controls with touch screen HMI and
sensor module
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 13
—
1.3 Warranty
1
available at the time of its publication. The standard warranty period for ZBTS
While efforts have been made to ensure T-series transfer switch products is
accuracy, the information contained twenty-four (24) months from the date of
herein does not cover all details or shipment.
variations in hardware and software, nor
does it provide for every possible Notes:
contingency in connection with This warranty is valid only for products
installation, operation, and maintenance. sold in the United States – consult your
Features that are not present in all local ABB representative for Non-US
hardware and software systems may be warranty terms and conditions.
described herein.
For support in the United States, contact
ABB Inc. assumes no obligation of notice service team at +1 800 637 1738 or epis.
to holders of this document with respect pqservice@abb.com for 24-hour support.
to changes subsequently made. ABB Inc.
makes no representation or warranty, For international support, contact
expressed, implied, or statutory, and epis.pqservice@abb.com.
assumes no responsibility for the
accuracy, completeness, sufficiency, or
usefulness of the information contained
herein. No warrantees of merchantability
or fitness for purpose shall apply.
—
1.4 Product Specification
—
Zenith ZBTS T-series bypass isolation automatic transfer
switches, from 1000 A up to 3000 A, are designed for use in
Business, industrial and Mission critical low-voltage
automatic transfer switch applications that require the
highest level of power continuity and redundancy. The ZBTS
T-series is a single-unit enclosed LV transfer switch system
that combines a drawout automatic transfer switch with an
isolation mechanism and a manual bypass switch –
enabling redundant power transfer and maintenance
capability while maintaining power supply to the load. For
regular operation, the Zenith ZBTS T-series bypass isolation
ATS can be configured, monitored, and controlled by a
touchscreen control interface (HMI).
—
2.1 General overview
1
1 4
5
2
—
Fig. 2.1 Front exterior view – Bypass isolation ATS, Zenith ZBTS T-series
1
1 3
4
2
5
—
Fig. 2.2 Front exterior view with door open – Bypass isolation ATS, Zenith ZBTS T-series
2
—
Fig. 2.3 Rear internal view – Bypass isolation ATS, Zenith ZBTS T-series
1 5 6 1
1
4
3 97
2
4
—
Fig. 2.4 ATS-R5B with and without covers shown
1 Lifting eye
2 SCR Assemblies. Access by removing cover screws on the front of panel
3 Customer manual operating ports
4 Transfer Coil Solenoids
5 Arc Chute Assemblies (Arc Quenching assemblies)
6 Movable Contact Assemblies
7 Position Limit Switches Auxiliary Contact Limit Switches
8 Mechanical Drive Assembly -mechanical interlock system
9 Source position status
I= contacts closed
O= contacts open
20 Z e n i t h Z B T S T- s e r i e s 1 0 0 0 A - 3 0 0 0 A By pass Is o l at i o n AT S
S1 I OII S2 S1 I II S2
Load Load
ZBTS T-series HMI (with touch screen) and connections of control circuit
Suitable
S1 O S2 S1 S2
l ll ! l ll !
LOAD AUTO LOAD AUTO
l O ll l ll
ON OFF ON
ON ON
—
Table 2.1 The differences of level types / operation types and the suitability of Ekip-modules
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 21
—
2.2 Controller and HMI
2.2.1 Controller 2.2.2 HMI
The ATS Controller OXCO_ TruCONTROL The HMI is the control interface (Human
is designed for use with Zenith ZBTS Machine Interface) of the ATS.
T-series. A color touchscreen HMI (Hu- Zenith ZBTS T-series has a color touch-
1
man Machine Interface) is used to oper- screen LCD HMI with push buttons. The
ate the TruCONTROL ATS controller. HMI is used to configure parameters for
automatic operation.
ZBTS:
HMI with
Touch screen
S1 O S2 S1 S2
l ll ! l ll !
l O ll l ll
ON OFF ON ON ON
I - O - II (or II - O - I)
—
Fig. 2.6 The HMI form will correspond to the type
of ZBTS T-series - open or delayed transition
—
Fig. 2.5 TruCONTROL ATS controller, type OXCO
T1: Source 1
T2: Source 2
T4: Current sensor
T5: ATS transfer command
T8: Digital output
T9: Digital and fire fighting input
T11: ATS status
T12: Temperature sensor
T13: CAN bus(Ekip 10k)
22 Z e n i t h Z B T S T- s e r i e s 1 0 0 0 A - 3 0 0 0 A By pass Is o l at i o n AT S
—
2.3 Zenith ZBTS T-series features
Features ZBTS controls (Touch screen)
S1 O S2 S1 S2
l ll ! l ll !
l O ll l ll
ON OFF ON ON ON
S1 O S2 S1 S2
l ll ! l ll !
l O ll l ll
ON OFF ON ON ON
1
Transfer from SOURCE 1 to SOURCE 2, sec 0-3600
Override momentary SOURCE 2 Outage, sec 0-60
Transfer from SOURCE 2 to SOURCE 1, min 0-120
Generator stop delay, min 0-60
Center-OFF delay, sec 0-300
Post-transfer delay S1 to S2, sec 0-300
Pre-transfer delay from S2 to S1, sec 0-300
Post-transfer delay from S2 to S1, sec 0-300
Elevator Pre-signal delay S1 to S2, sec 0-60
Elevator Post-signal delay S1 to S2, sec 0-60
Elevator Pre-signal delay S2 to S1, sec 0-60
Elevator Post-signal delay S2 to S1, sec 0-60
Load shed delay, sec 0-60
Source failure detections
No voltage Yes
Undervoltage Yes
Overvoltage Yes
Phase missing Yes
Voltage imbalance Yes
Invalid frequency Yes
Incorrect phase sequence Yes
Measuring and control features
Controls Touch + keys
LED indications for ATS, S1 and S2 status Yes
Programmable digital inputs/outputs Yes
Auto config (voltage, frequency, phase system) Yes
Source priority SOURCE 1/2, No priority
Manual re-transfer Yes
24 Z e n i t h Z B T S T- s e r i e s 1 0 0 0 A - 3 0 0 0 A By pass Is o l at i o n AT S
S1 O S2 S1 S2
l ll ! l ll !
l O ll l ll
ON OFF ON ON ON
1
—
Table 2.2 Zenith ZBTS T-series features not limited to what is in the table above
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 25
—
2.4 Typical applications
1
switches from 100 A up to 3000 A, are
designed for use in emergency or standby
systems to choose and to switch between
two power sources. See possible supply
phase scenarios on next page. You have to
define your own supply phase system - OX_
reference Chapter 4 / Navigating menu /
Parameters: Power distribution systems.
Factory setting: 3 phases with neutral.
Load
Source 1 Source 2
OX_
Load
—
Fig. 2.7 Typical applications of
automatic transfer switches
26 Z e n i t h Z B T S T- s e r i e s 1 0 0 0 A - 3 0 0 0 A By pass Is o l at i o n AT S
Phase A
Phase B F Phase A
Phase A
D F
1
D
F Phase B F Phase A
Neutral
F Phase B F
D D F F
F D Neutral
PhaseFC Phase B Phase
F C
D
Three-phase, four-wire Three-phase, three-wire
F
Phase C Phase C
D E F
Phase A
200-480 Vac L-N 200-480 Vac L-L 200-480 Vac L-L
120 240 240
Vac Vac Vac
Phase A High Leg
—
Fig. 2.8 Possible supply phase scenarios
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 27
—
2.5 Sequence of Operation
1
2.5.1 Switching sequence / Automatic
(Open / Delayed transition)
Switch position I
Switch position O
1
Switch position II
SOURCE 1 OK
SOURCE 2 OK
Generator started
Pre-transfer signal
Note: The functionality and sequence of ‘Elevator pre- and post-signals’ is equivalent to
‘Pre- and Post-transfer’ features.
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 29
1. SOURCE 2 is restored
1.
An anomaly occurs on SOURCE 2
2. Transfer from S1 to S2 delay
2. Override momentary S2 outage delay
3. Pre-transfer signal on
1
3. Transfer from S2 to S1 delay
4. Pre-transfer S1 to S2 delay
4. Pre-transfer signal on
5. Transfer switch to position O
5. Load shed signal on
6. Center-off delay (only with Delayed
6. Pre-transfer S2 to S1 delay
transition I - O - II type)
7. Load shed delay
7. Transfer switch to position I
8. Transfer switch to position O
8. Load shed signal off
9. Center-off delay (only with Delayed
9. Post-transfer S1 to S2 delay
transition I - O - II type)
10. Pre-transfer signal off
10. Transfer switch to position I
11. Post-transfer S2 to S1 delay
12. Pre-transfer signal off
30 Z e n i t h Z B T S T- s e r i e s 1 0 0 0 A - 3 0 0 0 A By pass Is o l at i o n AT S
Switch position I
Switch position O
1
Switch position II
SOURCE 1 OK
SOURCE 2 OK
Pre-transfer signal
Note: The functionality and sequence of ‘Elevator pre- and post-signals’ is equivalent to
‘Pre- and Post-transfer’ features.
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 31
The switching to available source can be When an anomaly occurs in the source in-
summarized in the following steps: use, the re-transfer to available source
can be summarized in the following steps:
1
1.
An anomaly occurs on SOURCE 1 1.
SOURCE 1 is restored
2. Override momentary S1 outage delay 2. An anomaly occurs on the SOURCE 2
3.
Pre-transfer signal on 3.
Pre-transfer signal on
4. Pre-transfer S1 to S2 delay 4. Pre-transfer S2 to S1 delay
5. Transfer switch to position O 5. Transfer switch to position O
6. Center-off delay (only with Delayed 6. Center-off delay (only with Delayed
transition I - O - II type) transition I - O - II type)
7. Transfer switch to position II 7. Transfer switch to position I
8. Post-transfer S1 to S2 delay 8. Post-transfer S2 to S1 delay
9. Pre-transfer signal off 9. Pre-transfer signal off
32 Z e n i t h Z B T S T- s e r i e s 1 0 0 0 A - 3 0 0 0 A By pass Is o l at i o n AT S
Switch position I
Switch position O
1
Switch position II
SOURCE 1 OK
SOURCE 2 OK
Pre-transfer signal
Note: The functionality and sequence of ‘Elevator pre- and post-signals’ is equivalent to
‘Pre- and Post-transfer’ features.
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 33
1
summarized in the following steps: rized in the following steps:
1. Activate test on load (HMI or digital 1. Cancel test on load (HMI or digital
input) input)
2. Generator start 2. SOURCE 1 availability timer
3. Run engine warm-up timer 3. Pre-transfer S2 to S1 delay
4. Pre-transfer S1 to S2 delay 4. Check source synchronization
5. Check source synchronization 5. Close SOURCE 1 contacts
6. Close SOURCE 2 contacts 6. Open SOURCE 2 contacts, start ETT
7. Open SOURCE 1 contacts, start ETT timer (parallel mode)
timer (parallel mode) 7. Post-transfer S2 to S1 delay
8. Post-transfer S1 to S2 delay 8. Run engine cool down timer
9. Generator stop
34 Z e n i t h Z B T S T- s e r i e s 1 0 0 0 A - 3 0 0 0 A By pass Is o l at i o n AT S
Switch position I
Switch position II
1
SOURCE 1 OK
SOURCE 2 OK
Generator started
Generator stopped
Elevator/pre-transfer signal
Elevator/post-transfer signal
Pre-transfer S1 to S2 delay
Post-transfer S1 to S2 delay
Pre-transfer S2 to S1 delay
Post-transfer S2 to S1 delay
Check source synchronization
S1 availability delay
S2 availability delay
Engine warm up delay
Engine cooldown delay
—
Table 2.6 Closed Transition Switching Sequences, SOURCE 1 Priority (SOURCE 2 = Generator)
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 35
1 Activate test on load (HMI or digital 1 Cancel test on load (HMI or digital
1
input) input)
2 Pre-transfer S2 to S1 delay 2 SOURCE 2 availability timer
3 Check source synchronization 3 Pre-transfer S1 to S2 delay
4 Close SOURCE 1 contacts 4 Check source synchronization
5 Open SOURCE 2 contacts, start ETT 5 Close SOURCE 2 contacts
timer (parallel mode) 6 Open SOURCE 1 contacts, start ETT
6 Post-transfer S2 to S1 delay timer (parallel mode)
7 Post-transfer S1 to S2 delay
36 Z e n i t h Z B T S T- s e r i e s 1 0 0 0 A - 3 0 0 0 A By pass Is o l at i o n AT S
Switch position I
Switch position II
SOURCE 1 OK
1
SOURCE 2 OK
Elevator/pre-transfer signal
Elevator/post-transfer signal
Pre-transfer S1 to S2 delay
Post-transfer S1 to S2 delay
Pre-transfer S2 to S1 delay
Post-transfer S2 to S1 delay
Check source synchronization
S1 availability delay
S2 availability delay
—
Table 2.7 Closed Transition Switching Sequences, SOURCE 2 Priority (No Generator)
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 37
—
2.6 Special features description
1
2.6.1 Automatic configuration 2.6.3 Powering supply scenarios
Basic system parameters can be automat- Device can be powered by the the follow-
ically configured from the HMI: rated volt- ing methods:
age, rated frequency, each supply power
distribution system type, and neutral • Direct from SOURCE 1 or SOURCE 2:
location will be recognized and set by Controller and HMI are powered and ATS
the controller. Other parameters are can be operated electrically.
set to factory values; see Chapter 4, • Auxiliary power supply module, OXEA1:
Navigating menu. Controller and HMI are powered, but
load transfer cannot be performed.
2.6.2 In-phase monitor • Programming port on HMI (USB port):
In-phase monitor can be set On/Off by Only the main board is powered. Allows
using HMI (controller levels 2, 3 and 4) or software update to main device and
Ekip Connect tool (levels 3 and 4). connection of Ekip Connect commis-
sioning tool.
Function calculates the phase difference
of voltage sources and enables the
automatic transfer sequence I -> II or II -> I
only when sources are synchronized.
Frequency difference of the sources must
be less than 0.2 Hz. Otherwise in-phase
monitor activates 'Frequency Difference'
alarm and disables transfer operations.
38 Z e n i t h Z B T S T- s e r i e s 1 0 0 0 A - 3 0 0 0 A By pass Is o l at i o n AT S
1
—
3. General operation
—
3.1 ATS position indication
3.1.1 Position Indication
2
1
—
Fig. 3.1 View of Automatic Transfer Switch (standalone) panel highlighting customer points of interest.
Applicable for Standard, Delay, and Close Transition Type Automatic Transfer Switch Equipment.
40 Z e n it h Z B T S T- s e r i e s 1 0 0 0 A - 3 0 0 0 A By pass I s o l ati o n AT S
—
3.2 Manual operation of ATS equipment
1
Danger
Hazardous Voltage May Cause Severe Injury or
Death
Manual opening and closing of the contacts
should only be performed with the power
disconnected.
Failure to comply with these instructions may
result in death or serious injury.
Danger
Une tension dangereuse peut causer de graves
blessures ou la mort. L'ouverture ou la ferme-
ture manuelle des contacts ne doivent être ef-
fectuées qu'avec l'alimentation deconnectée.
Le non-respect de ces instructions peut en-
traîner la mort ou de graves blessures.
Warning
Improper Installation Operation and
Maintenance
Ensure only qualified personnel install, operate,
service and maintain all electrical equipment.
DISCONNECT all power sources prior to instal-
lation, operation, service, and maintenance of
all electrical equipment. These activities shall
be performed only by certifed ABB Zenith tech-
nicians or qualifed electricians. Only use the
charging handle to perform manual operation
of the transfer switch. No motorized device
shall be used as a substitute.
Failure to comply with these instructions may
result in death or serious injury.
Avertissement
Mauvais fonctionnement et maintenance de
l'installation.
Assurez-vous que seul le personnel qualifié in-
stalle, utilise, entretient et exploite tous les
équipments électriques.
Debranchez toutes les ources d'alimentation
avant l'installation, l'utilisation, l'entretien, et
la maintenance de tous les équipments élec-
triques. Ces activitées doivent être effectuées
seulement par des techniciens certifiés par
ABB Zenith ou des électriciens qualifiés.
Utilisez uniquement la poignée de charge pour
effectuer une opération manuelle du commuta-
teur de transfert. Aucun appareil motorisé ne
doit être utilisé comme substitut.
Le non-respect de ces instructions peut en-
traîner la mort ou de graves blessures.
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 41
Stand-alone ABB Zenith automatic trans- 4. Rotate handle with two hands, in the
fer switches are not designed to be oper- direction as shown on the markings, to
ated manually under load. In the event the achieve the proper contact state (Fig. 3.3).
automatic transfer switch has to be oper-
ated manually, with no power available,
please follow these steps:
1
1
1. Verify all voltage input sources to the
automatic transfer switch have been re-
moved with proper LOTO procedures
followed. Consider stored energy sources
as well.
—
Fig. 3.2 Operating handle inserted for manual operation
42 Z e n it h Z B T S T- s e r i e s 1 0 0 0 A - 3 0 0 0 A By pass I s o l ati o n AT S
1
1 Contact State = Closed
2 Contact State = Open
—
Fig. 3.4 Contact status of automatic transfer switch
—
3.3 LED functionality in HMI
At the top of the ZBTS Lvl 4 HMI, there is a set of LEDs intended to ΔU 20% / Δf 10%
model the state of the transfer switch sources, position, alarms, and mode. Generator O Position
stop delay delay
A considerable amount of information can be deciphered from the LED states.
1
S1 Failure S1 Return
See the tables below for more information. delay
0
[s]
2 4
delay [min]
10 20 30 s 0s
1 3 5 15 30 4 min 4s
S1 O S2 S1
Lamp
Off S2
On Bypass
Auto
load load time
test Alarm reset
l ll ! l test ll test delay
!
— Autoconfig
In-phase
monitor
Priority Manual
retransfer
Auto In-phase Priority Manual
config monitor retransfer
Fig. 3.5 On left: LEDs in ZTBSD/ ZBTSCT delayed/closed transition, I - O - II. On right: LEDs in ZBTS, open transition I - II.
ΔU 10% / Δf 5%
ΔU 15% / Δf 10%
ΔU 20% / Δf 10%
LED Indication Description
Generator
Power led
stop delay
S1 Return
delay [min] ON, fixed light Power supply and communication present
S2
10 20 30 s
15 30 4 min
n
min]
2 quick flashes/1 s Power supply present, communication
20 30 s
! 0s absent between switch and the HMI
30 4 min 4s
Off On Bypass
Lamp Auto
load load time
test Alarm reset
test test delay
I, II and 0 leds
ON, fixed light nnnn Switch position is indicated with fixed
l O Generator
ll O Position
ONS1 OOFF S2
stop delay
ON
delay
light in I, O or II led. Only one can be on
S1 Failure S1 Return
delay [s] delay [min] simultaneously
0 2 l4 10 ll 20 30 s ! 0s
1 3 5 15 30 4 min 4s
LOAD AUTO
S1 Failure S1 Return
S1
delay [s]
O delay [min]
S2 30Bypass
1
4 ON10 LOAD
20
l
delay [min] O
30 OFF
s AUTO
0s
ll
ON
5 15 30 4 min 4s
Load led
S1 O S2
ON nnnn Supply ok and connected to load
In-phase l ll
Priority Manual !
Offmonitor On Bypass OFF nnnn
retransfer Not connected to load
Bypass Auto
load load time
time
Auto
test
On
LOAD
test
No priority
delay
On
AUTO
Alarm reset
Alarm reset
delay
llAuto led O ll
ON
ON In-phase OFF Priority ONManual
monitor ON, fixed light nnnn
retransfer Switch is in automatic mode
S2 On No priority On
Off Source 1 Flash/1
Off s, 50 %/50 % nn Test on load
!
Dropout ΔU / Δf ΔU 5% / Δf 5% Flash/1 s, 90 %/10 % Test off load
AUTO Flash/1 s, 10 %/90 % If blinks simultaneously with Alarm led
then 'Remote control to S1','Remote
5 15 30 4 min 4s control to S2', 'Remote control to OFF' or
'Inhibit transfer' digital input is activated.
5 flashes/1 s, 50 %/50 % Autoconfig completed
Off On Bypass
load Alarm
loadled time
Auto
Alarm reset
test test delay
OFF nnnn No alarms
S2
ON, fixed light nnnn Handle attached, locked, other alarm
O! ll
N OFF ON 2 quick flashes/1s nnyy nyy Control Alarm
AUTO
5 flashes/1 s, 50 %/50 % Auto configuration ongoing
Flash/1 s, 50 %/50 % nn Control Retry
ority Manual Flash/1 s, 10 %/90 % ynn Auto mode off
retransfer
No priority On
Flash/1 s, 10%/90 % ynn If blinks simultaneously with Alarm led
Source 1 Off
then 'Remote control to S1', 'Remote
control to S2', 'Remote control to OFF' or
'Inhibit transfer' digital input is activated.
If Auto led is fixed light then manual
retransfer is required.
—
Table 3.1 LED functionality
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 45
—
3.4 Using Level 4 (touch) control interface HMI
1
3.4.1 Keypad 1
2 3
Open transition, I - II
—
Fig. 3.6 Keypad in Level 4 HMI with touch screen
46 Z e n it h Z B T S T- s e r i e s 1 0 0 0 A - 3 0 0 0 A By pass I s o l ati o n AT S
—
3.5 Bypass isolation ATS indication panel
The bypass isolation ATS indication panel is located at the top of the equipment en-
1
closure. This panel is connected to the electrical controls compartment and TruCO-
NTROL. Status and alarm signals are displayed on this indication panel, as well as
the HMI.
Specifically, the Bypass Panel indicates connection status of S1, S2, Bypass device
and ATS. ATS racking in/out status is also shown by the panel. This panel is illus-
trated in figure 3.12. Detailed LED descriptions are listed below in table 3.2.
—
Fig. 3.7 Bypass isolation ATS indication panel
1
transfer when it is on the “Inhibit” position (LED on) and
allows automatic operation when it is on the “Auto” position
DS SWITCH INHIBIT POSITION (LED off)
Only available in delayed and closed transition. Pushing the
button will make the ATS contacts switch to the same source
CONTACT RESET as the MTS
—
Table 3.2 Bypass isolation ATS indication panel LED descriptions
48 Z e n it h Z B T S T- s e r i e s 1 0 0 0 A - 3 0 0 0 A By pass I s o l ati o n AT S
—
3.6 Bypass access panel
The bypass access panel illustrates MTS contact position of both source 1 and source 2.
1
5
6 13
7 14
—
Fig. 3.8 Bypass access panel
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 49
—
3.7 Bypass manual operation
“Manual Close” button for closing MTS contact. Control mechanism needs charging.
1
“Manual Close” instruction:
1 Manually turn the “Manual Charge” knob on the Bypass access panel until the
“charge status” window become full green and display “Charged”.
2 Then, press “Manual Close” button. This will close the MTS contacts to
corresponding source
—
Fig. 3.9 Bypass manual close instruction
“Manual Open” button for Open MTS contact. Control mechanism does not need
charging.
“Manual Open” instruction:
Press “Manual Open” button. This will switch the MTS contacts to off position.
—
Fig. 3.10 Bypass manual open instruction
50 Z e n it h Z B T S T- s e r i e s 1 0 0 0 A - 3 0 0 0 A By pass I s o l ati o n AT S
—
3.8 Bypass-isolation operation
There are three positions for the will automatically start the engine-gener-
1
ATS: CONNECTED, TEST, and ISOLATED. ator set. When the second source is avail-
The ATS can be racked out/in to these po- able, the Bypass MTS may be operated to
sitions manually as desired. transfer the load to the available source.
The operation instructions for racking Use the key to open bypass operator ac-
out/in the ATS to the three positions are cess panel door before you do bypass-iso-
mounted on the front of door along with lation operation.
bypass operator access panel.
1
Step Process Picture Requirements or
Instructions
1 Turn the disconnect switch Auto mode on HMI should be
from “Auto” to “Inhibit”. disable
1
disconnect switch is at “Auto”
position
1
disconnect switch is on “Auto”
position
Instructions
1 Make sure MTS contacts are
on one source.
Make sure the front cabinet
door is closed. Racking in
operation could not be done if
the cabinet front door is not
closed.
2 Turn the disconnect switch Auto mode on HMI should be
from “Auto” to “Inhibit” if the disable
disconnect switch is on “Auto”
position
1
in off position
1
door is closed. Racking-in
operation could not be done if
the cabinet front door is not
closed.
2 Turn the disconnect switch Auto mode on HMI should be
from “Auto” to “Inhibit” if the disable
disconnect switch is on “Auto”
position
“Inhibit” mode
2 If the ATS and MTS not on the ATS contact would be closed
same source and disconnect to the same source with MTS
switch is on “Auto” mode, contact
press contact reset button on CO N
TAC
indication panel RE S E T
T
—
3.9 ATS operation
1
For the description of possible ATS switching sequences, refer to section 2.5
62 Z e n it h Z B T S T- s e r i e s 1 0 0 0 A - 3 0 0 0 A By pass I s o l ati o n AT S
1
—
4. Navigating HMI menu
—
4.1 Start Menu
60s G 11:06
Overviews Analog Meters
System Overview
S1 Ok Not Ok S2
S1 Connected to Load
Main Menu Measures
Load Current
393 A
—
Fig. 4.2
System Overview
Switch not in AUTO mode
Invalid Date S1 Ok Not Ok S2
1
S1 Connected to Load
Load Current
393 A
— —
Fig. 4.3 Fig. 4.4
By touching on the alarm indication on the lower The location of the small icons and the alarms.
edge of the screen you will get the Alarm List.
Programming
Application 2 Transformers/S1 Priority
The small icons in System Overview
-pages are:
11:06 Time
On the lower edge of the screen you can G Application set up as Transformer-
see the Alarms. If you touch on the alarm Generator. Generator start-up
you will get the Alarm List. signal deactivated
—
4.2 Using main menu and setting parameters
1
Operation Parameters Measurements
—
Fig. 4.6
By touching on Start Menu lower left corner -image
you can move to the Main Menu page of Operation,
Parameters, Measurements, Settings, Test and
About, see the table below for the selections.
Information Information
When you have changed the parameter, go The default values are marked in the menu
always back in the menu and confirm the tree by *-marking.
change always when asked.
Password
Programming
Password
Application 2 Transformers/S1 Priority
0 * * * *
Confirm
Confirm Abort Modify
—
Fig. 4.7
Enter the password when asked, choose the
right number by arrowheads and confirm, go
forward entering number after number.
—
4.3 Menus and parameters
Operation *Default
Alarm Reset Reset any active switch control alarms (open I failure, close I failure, open II
1
Parameters *Default
System parameters
1
Start Automatic Configuration
Power distribution systems (see Fig. 2.2)
Source 1 1 Phase, 2 Wire
1 Phase, 3 Wire (Split-Phase)
3 Phases, no Neutral (3ph3w)
3 Phase with Neutral (3ph4w)*
3 Phase, High-Leg Delta
Source 2 1 Phase, 2 Wire
1 Phase, 3 Wire (Split-Phase)
3 Phases, no Neutral (3ph3w)
3 Phase with Neutral (3ph4w)*
3 Phase, High-Leg Delta
Rated Voltage
200 V (3ph), 208 V (3ph), 220 V (3ph), 230 V (3ph), 240 V (3ph), 277 V (3ph), 347 V
(3ph), 380 V (3ph), 400 V (3ph)*, 415 V (3ph), 440 V (3ph), 460 V (3ph), 480 V (3ph),
200 V (1ph), 220 V (1ph), 230 V (1ph), 240 V (1ph)
Rated Frequency
50 Hz*
60 Hz
Neutral Pole Location
Pole 4* 1)
Pole 1
Phase Sequence
ABC*
ACB
Not Enabled
1)
Overlapping neutral always on Pole 4, this cannot be changed. Continued on the next page
68 Z e nith Z B T S T- s e r i e s 1 0 0 0 A - 3 0 0 0 A By pass I so l ation AT S
1
to S1.
Transfer from 0...120 min S1 priority: How long the device waits before
S2 to S1 (2* s) transfer sequence back to available S1 begins.
This delay is overridden by 'Override S2
Failure' in case of S2 failure.
S2 priority: How long the device is keeping the
load on failed S2 although S1 is already
available.
Elevator Pre-transfer signal 1 / 2 / 3 / 4
Elevator Pre-signal S1-S2 0*...60 s Enabled only when any digital output is
Elevator Post-signal S1-S2 configured as 'Elevator pre-signal'.
Elevator Pre-signal S2-S1
Elevator Post-signal S2-S1 Pre-transfer: How long the device is keeping
pre-signal activated before transferring from
S1 to S2 or from S2 to S1.
pick-up higher.
S1 Setpoints
S1 Drop-out Upper Threshold 102...120 % Un (115* % Un)
Voltage Lower Threshold 75...97 % Un (85* % Un)
S1 Pick-up Upper Threshold 101...119 % Un (114* % Un)
Voltage Lower Threshold 85...99 % Un (90* % Un)
S1 Drop-out Upper Threshold 101...120 % fn (115* % fn)
Frequency Lower Threshold 80...99 % fn (85* % fn)
S1 Pick-up Upper Threshold 100.5...119.5 % fn (114* % fn)
Frequency
Lower Threshold 80.5...99.5 % fn (86* % fn)
S2 Setpoints
S2 Drop-out Upper Threshold 102...120 % Un (115* % Un)
Voltage Lower Threshold 75...97 % Un (85* % Un)
S2 Pick-up Upper Threshold 101...119 % Un (114* % Un)
Voltage Lower Threshold 85...99 % Un (90* % Un)
S2 Drop-out Upper Threshold 101...120 % fn (115* % fn)
Frequency Lower Threshold 80...99 % fn (85* % fn)
S2 Pick-up Upper Threshold 100.5...119.5 % fn (114* % fn)
Frequency
Lower Threshold 80.5...99.5 % fn (86* % fn)
Voltage Unbalance Options to change voltage unbalance measurement limits or
Setpoints disable unbalance measurement completely.
Unbalance Drop-Out ±5...30 % Un (±10* % Un)
Unbalance Pick-Up ±3...28 % Un (±8* % Un)
Unbalance Measuring Off*
On
Continued on the next page
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 71
1
the highest priority.
Exerciser 1 / 2 / 3 / 4
Status Disabled*
Non-periodic
Daily
Weekly
Bi-weekly
Monthly
Yearly
Function No Function*
Test on Load
Test off load
Duration 00:00:00...24:00:59 (00:01:00*)
(hh:mm:ss)
Time Starting time of the event.
(hh:mm) 00:00*...23:59
Date (month day, Starting date of the event
year) Jan 01, 2020... (---*)
Application
S1-Transformer/S2-Generator*
S2-Transformer/S1-Generator
2 Transformers/S1 Priority
2 Transformers/S2 Priority
2 Transformers/No Priority
Commit Transfer
Off* If priority source fails, device cancels the
transfer sequence to non-priority source
(generator) if priority source returns before
non-priority source becomes acceptable.
If priority source fails, device countinues transfer
On sequence to non-priority source (generator)
even if priority returns before non-priority
souce becomes acceptable. Retransfer sequence
according to time delays.
operating normally.
Disabled*
Alarm reset required
Yes User confirmation is required before re-
entering normal operation after high current
status.
No* Normal operation is started automatically after
high current status.
Transfer to Dead Source
On* User can transfer to an unavailable source by
using HMI keys I/II or by a remote command.
Measurements
Switch Diagnostic
Total operations I-O-II switches: Total number of transfers I-O, O-II,
II-O and O-I.
I-II switches: Total number of transfers I-II and II-I
Manual operations Total transfers operated by the handle.
Number of load transfers Total number of transfers I-II and II-I
Transfer time Time it took to transfer the load between sources (ms)
1
Source fail transfers Total number of automatic transfers due to source
failures.
Days energized
Total time on S1 Hours
Total time on S2 Hours
Time S1 available Minutes
Time S2 available Minutes
Last generator start MMM DD, YYYY hh:mm:ss
Generator starting time How long it took for the generator to become
acceptable after latest start (s).
In-phase How long it took for the in-phase monitor to achieve
time synchronized transfer (s).
Event Log
View Log 250 time stamped events, latest first.
Clear Log Delete all log entries.
Harmonics Harmonic components up to 15th are calculated for
the selected phase.
Measured Disabled*
Phase Phase 1
Phase 2
Phase 3
Voltage Total distortion THD for each phase of both voltage sources.
Settings *Default
Standard I/O settings
I 01 / I 02 / I 03
Function No function Input disabled.
Emergency Stop Transfers to O position in delayed transition I-O-II
type switches. Disables automatic control mode in
both delayed and open transition types.
1
1
S1*(default in O 01)
Load Disconnected Switch in position O.
Load Connected to Switch in position II.
S2*(default in O 02)
Pre-transfer Signal 1 Signal is activated and transfer is delayed
according to pre-transfer delay. Signal is kept
activated according to post-transfer delay after
transfer.
Pre-transfer Signal 2 Signal is activated and transfer is delayed
according to pre-transfer delay. Signal is kept
activated according to post-transfer delay after
transfer.
Pre-transfer Signal 3 Signal is activated and transfer is delayed
according to pre-transfer delay. Signal is kept
activated according to post-transfer delay after
transfer.
Pre-transfer Signal 4 Signal is activated and transfer is delayed
according to pre-transfer delay. Signal is kept
activated according to post-transfer delay after
transfer.
Source 1 available*
(default in O 03) No anomalies in S1 voltage supply.
Source 1 available*
(default in O 04) No anomalies in S2 voltage supply.
Load Shed Output Used for shedding non-essential loads before
Signal transferring to non-priority source. Signal is
activated before transferring to non-priority
source according to load shed delay and kept
activated until load is transferred back to
priority source.
Continued on the next page
76 Z e nith Z B T S T- s e r i e s 1 0 0 0 A - 3 0 0 0 A By pass I so l ation AT S
transfer.
Elevator pre-signal 2 Signal is activated and transfer is delayed according
to Elevator pre-signal delay. Signal is kept activated
according to Elevator post-signal delay after
transfer.
1
L2
L3
S1 Voltmeter Phase
V Max*
U12
U23
U31
S2 Voltmeter Phase
V Max*
U12
U23
U31
78 Z e nith Z B T S T- s e r i e s 1 0 0 0 A - 3 0 0 0 A By pass I so l ation AT S
Test *Default
On-Load Test Settings
Bypass Local Test
Bypass if Generator Fails*
Stay on Generator
Bypass Remote Test
Bypass if Generator Fails*
1
Stay on Generator
Bypass Generator Exerciser
Bypass if Generator Fails*
Stay on Generator
Test On Load Test generator with transferring the load. Test with switch
transfer.
Test Off Load Test generator without transferring the load. Test without
switch transfer.
HMI Test Initiate display test screen and turn all LED's on.
This function is not available when time delay is ongoing.
Optional modules (See Chapter 5, Electronic accessories)
About
HMI HMI serial number
Software version
Software subversion
HMI Type code
Controller Unit Time
Date
Serial number
Normative
Controller software version
Controller software subversion
Automatic Transfer Switch TAG name
ATS Type Code
ATS serial number
Rated current
Number of Poles
ATS Type
Modules (See Chapter 5, Electronic accessories)
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 79
—
4.4 Analog meters and Measures
1
50 75
25 100
S1
0 125
0.0V
Main Menu Measures U12
—
Fig. 4.3 By touching on Start Menu upper
right corner -image you can find the analog
meters information, see the table below
S1 Voltage meter
S2 Voltage meter
Current meter
Power meter
VAR meter
VA meter
80 Z e nith Z B T S T- s e r i e s 1 0 0 0 A - 3 0 0 0 A By pass I so l ation AT S
G 11:06
Overviews Analog Meters
Voltages (S1)
1
—
Fig. 4.9 By touching on Start Menu lower
right corner -image you can find the
measured data, see the table below
Voltages (S1)
Voltages (S2)
Current
Active power
Reactive power
Apparent power
Energy counters
—
5. Electronic accessories
—
Fig. 5.2 Ekip Signalling and Com -modules are
mounted to Bypass isolation automatic transfer switch
with a auxiliary power supply module, OXEA1.
—
Fig. 5.1 Ekip Programming
82 Z e n i t h Z B T S T- se r i es 1 0 0 0 A - 3 0 0 0 A By pass Is o l at i o n AT S
—
5.1 Ekip Connect -software
1
Ekip Connect is a freeware for communi- With its communication function, it al-
cation and test of TruONE automatic lows you to:
transfer switches. The software is com-
patible with all TruONE automatic trans- • Monitor the state of the connected au-
fer switches. It can be installed on PCs tomatic transfer switches and record in-
equipped with the Microsoft Windows® for
operating system. Download it from the • Configure automatic transfer switches
website, see the address below: with customized parameters.
http://www.abb.com/abblibrary/ • Configure electronic accessories, con-
DownloadCenter/ nected to automatic transfer switch via
Local Bus.
• Download information from automatic
transfer switches.
• Create communication reports.
• Reset configurations.
—
Fig. 5.3 Ekip Connect -software
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 83
—
5.2 Ekip Programming -module
1
The Ekip Programming -module is suit- The Ekip Programming -module draws its
able to use with all ZBTS 1000A-3000A, power from the PC and connects one side
Bypass isolation automatic transfer directly to the programming port (see Fig.
switches. You can connect the module via 5.6) and on the other to the USB port of
the programming port, see Fig. 5.5. The the PC with the cable supplied.
programming port is only compatible for
use with Ekip Programming.
Notice
Ekip Programming only powers the control-
Ekip Programming -module allows you to: ler board (HMI and external modules ex-
cluded). Therefore, in order to identify all
connected parts with Ekip Connect, the
auxiliary power supply module, type OXEA1,
• With Ekip Connect software update the must be used (see chapter 5.4).
Remarque
software and load, set and read the pa- Ekip programmation alimente uniquement
la carte de contrôleur (IHM et modules ex-
rameters ternes exlus). Par conséquent, afin d'identi-
fier toutes les parties connectées avec Ekip
Connect, le module d'alimentation auxilia-
ire, type OXEA1, doit être utilisé (voir
If the firmware is updated while the de- chapitre 5.4).
—
— Fig. 5.5 Programming port (USB port) is
Fig. 5.4 Ekip Programming -module situated in the front of the HMI, on left side
84 Z e n i t h Z B T S T- se r i es 1 0 0 0 A - 3 0 0 0 A By pass Is o l at i o n AT S
—
5.3 Auxiliary power supply module
1
The auxiliary power supply module, type control unit, for example: operation of
OXEA1, supplies non-insulated power to sensor module is not possible.
the external Ekip-modules, HMI and main
control unit. It is supplied by external sup- Connections are push-in spring terminals,
ply, for example from generator battery or no tool is required.
from isolated transformer connected to
the main circuit. Powering product only For external wiring, cable cross section;
with auxiliary power supply module limits AWG 22-16 / 0.5-1.5 mm2.
some operation functions of the main
—
Fig. 5.6 Auxiliary power supply module, type
OXEA1, is needed when Ekip Signalling, Com and —
Link -modules are mounted to TruCONTROL_ Fig. 5.7 Signals of auxiliary power supply module OXEA1
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 85
—
5.4 Ekip Signalling 2K-_ -module
1
The Ekip Signalling 2K-_ is a signalling ac-
Component Characteristics
cessory module. It is suitable for Level 4
controllers (touch control interfaces). The Output Maximum switching voltage*:
contacts 150 V DC / 250 V AC
module has:
Breaking power*: 2 A @ 30 V DC,
0.8 A @ 50 V DC, 0.2 A @ 150 V
• Two digital inputs, and two contacts for DC, 4 A @ 250 V AC
output signals. Dielectric strength between
• A power status LED, and four signalling each contact and coil: 1000 V AC
(1 minute @ 50 Hz)
LEDs (one LED for every input/output).
Dielectric strength between
open contacts: 1000 V AC (1
minute @ 50 Hz)
Notice Input contacts 5 V@2.5 mA
On each ATS, a maximum of three Ekip Sig-
nalling 2K modules can be installed: one 2K- Do not connect to any power
1, one 2K-2, and one 2K-3. These modules supply
differ by their name and label, and have dis-
tinct wiring, but they are identical in terms
of their characteristics and manner of
installation. —
Remarque
Sur chaque ATS, un maximum de trois mod- Table 5.3 Electrical characteristics of
ules Ekip signalisation 2K peuvent être in- Ekip Signalling 2K-_ -module
stallés: un 2K-1, un 2K-2 et un 2K-3. Ces
modules diffèrents par leur noms et leur la-
bels, et ont un câblage different, mais ils
sont identiques par leurs caractéristiques 5.4.2 Access from the display /
et leur mode d'installation.
Ekip Signalling 2K-_ -module
With modules energized, and Local Bus
enabled, the presence of the modules on
5.4.1 Electrical characteristics of the module slot activates additional
Ekip Signalling 2K-_ -module menus on the display:
The following table lists the electrical • In order to configure the inputs and out-
characteristics of the module: put contacts.
• To display information on the modules
and the state of inputs and outputs.
—
Fig. 5.8 Ekip Signalling 2K -module
86 Z e n i t h Z B T S T- se r i es 1 0 0 0 A - 3 0 0 0 A By pass Is o l at i o n AT S
1
Load Connected to S1 Switch in position I.
Load Disconnected Switch in position O.
Load Connected to S2 Switch in position II
Pre-transfer Signal 1 Signal is activated and transfer is delayed according to
pre-transfer delay. Signal is kept activated according to
post-transfer delay after transfer.
Pre-transfer Signal 2 Signal is activated and transfer is delayed according to
pre-transfer delay. Signal is kept activated according to
post-transfer delay after transfer.
Pre-transfer Signal 3 Signal is activated and transfer is delayed according to
pre-transfer delay. Signal is kept activated according to
post-transfer delay after transfer.
Pre-transfer Signal 4 Signal is activated and transfer is delayed according to
pre-transfer delay. Signal is kept activated according to
post-transfer delay after transfer.
Source 1 Available No anomalies in S1 voltage supply.
Source 2 Available No anomalies in S2 voltage supply.
Load Shed Output Used for shedding non-essential loads before
Signal transferring to non-priority source. Signal is activated
before transferring to non-priority source according to
load shed delay and kept activated until load is
transferred back to priority source.
Elevator pre-signal 1 Signal is activated and transfer is delayed according to
Elevator pre-signal delay. Signal is kept activated
according to Elevator post-signal delay after transfer.
Elevator pre-signal 2 Signal is activated and transfer is delayed according to
Elevator pre-signal delay. Signal is kept activated
according to Elevator post-signal delay after transfer.
Elevator pre-signal 3 Signal is activated and transfer is delayed according to
Elevator pre-signal delay. Signal is kept activated
according to Elevator post-signal delay after transfer.
Elevator pre-signal 4 Signal is activated and transfer is delayed according to
Elevator pre-signal delay. Signal is kept activated
according to Elevator post-signal delay after transfer.
Transfer Alarm 1) Activate output after ATS has transferred to non-priority
source.
Contact NC Active open
Type NO* Active closed
88 Z e n i t h Z B T S T- se r i es 1 0 0 0 A - 3 0 0 0 A By pass Is o l at i o n AT S
Test
:
Modules (Optional modules)
Ekip Signalling 2K-1 / -2 / -3 Auto Test
:
—
1
Table 5.4 Configuration and test parameters of Ekip Signalling 2K-_ -module in HMI
The following table illustrates the path from the display for accessing information on
the module:
About Description
:
Modules (Optional modules)
Ekip Signalling 2K-1 / -2 / -3
SN Serial number
Version Software version
Input 1 The logical state of the inputs:
Input 2 “Off” if not active, “On” if active
:
—
Table 5.5. Information of Ekip Signalling 2K-_ -module in HMI
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 89
5.4.3 LED indications and inputs/ 2 Green3) LED for signalling the physical
outputs of Ekip Signalling 2K-_ -module state of the input H x I2). The possible
states are:
– Off: floating input
1 – On fixed: input short-circuited on
10 5 H Cx 2)
1
9 4
state of the input H x22). The possible
8 states are:
3
7 – Off: floating input
6 2
– On fixed: input short-circuited on
H Cx
—
Fig. 5.9 Signals and inputs/outputs of 4 Green3) LED for signalling contact K x1
Ekip Signalling 2K-_ -module
- K x22). The possible states are:
– Off: contact open
1 Power LED, green. The possible – On fixed: contact closed
states are:
5 Green3) LED for signalling the state of
– Off: power supply absent.
the contact K x3 - K x4 2). The possible
– On fixed: power supply and
states are:
communication with the device
– Off: contact open
present (with a device with the
– On fixed: contact closed
Alive LED option disabled).
- On, with one flash per second 6 Input I x1
(synchronized with that of the
7 Conductive part of the inputs H x1
green LED on the device): power
and H x22)
supply and communication with
device present (with a device 8 Input I x22)
with the Alive LED option
9 Output contact pin O x1 2)
enabled)
- On, with two quick flashes per 10 Output contact pin O x22)
second (not synchronized with
those of the green LED on the 1) The absence of communication is signalled immedi-
ately by the power LED, unlike the outputs which
device): power supply present, (apart from those programmed to be activated in
the case of disconnection) are deactivated if the
and communication with device condition persists for at least 8 s
absent (for example: for Local 2) With x = 1, 2, or 3
Bus disabled) 1) 3) The LED turns on and off according to the physical
state of the input, without taking any account of
how the Delay parameter is set.
—
5.5 Ekip Com _ -modules
1
Suitable Ekip Com_ -modules are: 5.5.1 Ekip Com Modbus RTU -module
The Ekip Com Modbus RTU is a communi-
• Ekip Com Modbus RTU -OX cation accessory module, which inte-
• Ekip Com Modbus TCP-OX grates the automatic transfer switch in an
• Ekip Com Profibus DP industrial remote supervision and control
• Ekip Com DeviceNet network. The module is suitable for all
• Ekip Com Profinet ZBTS 1000A-3000 A and ZTSCT 400-3000
• Ekip Com EtherNet/IP A,
• Ekip Com Hub Bypass Isolation ATS.
—
Fig. 5.10 Ekip Com Modbus RTU -module
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 91
1
green
lected before the installation of the mod-
On fixed Power supply and ule. With the Ekip Com Modbus RTU
communication with
the device present. modules, the dip-switches 3 and 4 of the
On, with two Power supply present, Rpol (polarization resistance) are not
quick and communication used.
flashes per with device absent.
second
RX and TX Off Modbus RTU
LEDs, communication not
green active.
On, flashing Modbus RTU
rapidly communication active.
—
Table 5.6 Indication / Ekip Com Modbus RTU -module
ON IA
1 2 3 4
Rterm Rpol
120Ω
on on
off off
— —
Fig. 5.11 Signals of Ekip Com Modbus RTU -module Fig. 5.12 Termination resistor; To enable the Rterm, the dip-
switches 1 and 2 must be positioned to ON. This option
must be selected before the installation of the module
92 Z e n i t h Z B T S T- se r i es 1 0 0 0 A - 3 0 0 0 A By pass Is o l at i o n AT S
About Description
:
Modules (Optional modules)
Ekip Com Modbus RTU
SN Serial number
Version Software version
:
—
Table 5.8 Information of Ekip Com Modbus RTU -module in HMI
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 93
1
• Provide the status information of the
automatic transfer switch (open,
closed).
—
Fig. 5.13 Ekip Com Profibus DP -module
94 Z e n i t h Z B T S T- se r i es 1 0 0 0 A - 3 0 0 0 A By pass Is o l at i o n AT S
device present.
On, with two quick flashes per second Power supply present, and communication
with device absent.
RX LED, green Off Communication not active.
On, fixed Communication active.
TX LED, green Off Communication not active.
On, flashing Communication active.
—
Table 5.9 Indication / Ekip Com Profibus DP -module
ON IA
1 2 3 4
Rterm Rpol
120Ω
on on
off off
— —
Fig. 5.14 Signals of Ekip Com Profibus DB -module Fig. 5.15 Termination resistor; To enable the Rterm, the
dip-switches 1 and 2 must be positioned to ON. When Rterm
is activated, the Rpol must also be activated by turning
dip-switches 3 and 4 to ON position. These options must
be selected before the installation of the modules
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 95
1
accessing the configuration parameters
of the modules from the display:
About Description
:
Modules (Optional modules)
Ekip Com Profibus DB -module
SN Serial number
Version Software version
:
—
Table 5.11 Information of Ekip Com Profibus DP -module in HMI
96 Z e n i t h Z B T S T- se r i es 1 0 0 0 A - 3 0 0 0 A By pass Is o l at i o n AT S
—
Fig. 5.16 Ekip Com DeviceNet -module
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 97
1
device present.
On, with two quick flashes per second Power supply present, and communication
with device absent.
Network LED, red Off Device off line (with red LED off) 1), or in
error conditions (with red LED on).
On, fixed Device on line, and allocated on a master
(operating condition).
On, flashing Device on line, but not allocated on a
master (device ready for communication).
Status LED, green Off No error.
On, fixed Device in bus off, or Network Power absent
condition.
On, flashing I/O connection (cyclic data) in timeout.
1)
The device has not yet sent Duplicate ID sequence on line.
—
Table 5.12 Indication / Ekip Com DeviceNet -module in HMI
—
Fig. 5.17 Signals of Ekip Com DeviceNet -module
98 Z e n i t h Z B T S T- se r i es 1 0 0 0 A - 3 0 0 0 A By pass Is o l at i o n AT S
ON IA
1 2 3 4
Rterm Rpol
120Ω
on on
off off
—
Fig. 5.18 Termination resistor; To enable the Rterm, the dip-
switches 1 and 2 must be positioned to ON. This option
must be selected before the installation of the module.
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 99
1
accessing the configuration parameters
of the modules from the display:
About Description
:
Modules (Optional modules)
Ekip Com DeviceNet
SN Serial number
Version Software version
:
—
Table 5.14 Information of Ekip Com
DeviceNet -module in HMI
100 Z e n i t h Z B T S T- se r i es 1 0 0 0 A - 3 0 0 0 A By pass Is o l at i o n AT S
5.5.4 Ekip Com Modbus TCP -module As an HTTP Server connected to an Ether-
Ekip Com Modbus TCP is an accessory net network, it allows read-only access to
module that can function as a communi- the information of the automatic transfer
cation module integrating the automatic switch. This access is possible through a
transfer switch in an industrial remote su- browser by inserting the IP address of the
pervision and control network or as an module as the URL. Once the switch is
HTTP Server. The module is suitable for found, a login page prompts and asks for
1
Level 4 controllers(touch control the user password. Insert the same pass-
interfaces). word used for editing parameters.
—
Fig. 5.19 Ekip Com Modbus TCP -module
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 101
1
320/udp
—
Table 5.15 Ports of Ekip Com Modbus TCP -module
Link
Activity
—
Fig. 5.20 Signals of Ekip Com Modbus TCP -module
102 Z e n i t h Z B T S T- se r i es 1 0 0 0 A - 3 0 0 0 A By pass Is o l at i o n AT S
of the modules.
• In order to display information on the
modules.
About Description
:
Modules (Optional modules)
1
Ekip Com Modbus TCP
SN Serial number
Version Software version
IP Address The address assigned to the modules at the moment of connection to
the network. It consists of four bytes (for a total of 32 bits), each of
which can have value from 0 to 255. By default, allocation is dynamic.
With dynamic allocation, the modules wait to receive the IP address
from a DHCP server. Without a DHCP server, the modules adopt an
Autoconfiguration IP Address in the range 169.254.xxx.xxx, calculated
in a pseudo random manner so as to be the same at every switch-on.
Alternatively, you can enable the static IP address option, which allows
the IP address to be forced. In this case, you must make sure that the IP
address inserted is different to those of the other devices connected to
the same network.
Network Mask The subnet mask which identifies the method to recognize the subnet
to which the modules belong, with the possibility of searching for the
modules within a defined set of recipients. If you enable the static IP
address option, you must also enter the correct Network Mask.
Gateway Address The IP address of the node to which the module is connected in the
presence of multiple subnets. If you enable the Static IP address option,
you must also enter the correct Gateway Address.
TCP Client Three IP addresses of the client devices connected to the modules.
MAC Address The address assigned by ABB, having an OUI equal to ac:d3:641).
:
1)
Organizationally Unique Identifier, formed of the first three bytes of a MAC address, that uniquely
identifies the manufacturer of an Ethernet device.
—
Table 5.18 Information of Ekip Com Modbus TCP -module in HMI
104 Z e n i t h Z B T S T- se r i es 1 0 0 0 A - 3 0 0 0 A By pass Is o l at i o n AT S
—
Fig. 5.21 Ekip Com Profinet -module
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 105
1
0x0800 34964/udp Profinet-cm DCE/RP
(Context Manager)
—
Table 5.19 Ports of Ekip Com Profinet –module
Link
Activity
—
Fig. 5.22 Signals of Ekip Com Profinet -module
106 Z e n i t h Z B T S T- se r i es 1 0 0 0 A - 3 0 0 0 A By pass Is o l at i o n AT S
About
:
Modules (Optional modules)
Ekip Com Profinet -module
SN Serial number
Version Software version
MAC Address The address (with an OUI) assigned by ABB equal to ac:d 3:64
Organizationally Unique Identifier, formed of the first three
bytes of a MAC address, that uniquely identifies the
manufacturer of an Ethernet device.
:
—
Table 5.21 Information of Ekip Com Profinet -module
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 107
1
of the control system of an installation). It
suitable for Level 4 controllers(LCD and is the responsibility of the installer to make
sure that all the necessary security mea-
touch control interfaces). sures are adopted (for example firewalls
and other measures). The module cannot be
connected directly to the Internet. It is rec-
ommended to connect it only to dedicated
It can be connected to an Ethernet net- Ethernet networks using the EtherNet/IP™
-communication protocol.
work with a EtherNet/IP™ -communica- Remarque
Parce que ce module permet d'accéder aux
tion protocol, and allows you to: données contenues dans le dans le commu-
tateur de transfert automatique ou l'auto-
commutateur, il doit ne doit être connecté
qu'aux réseaux possédant toutes les condi-
• Connect the automatic transfer switch tions nécessaires à la prévention des accès
non autorisés (par exemple, le réseau du
to the network with dialog functionality. système de contrôle d'une installation). Il
est de la responabilité de l'installateur de
• Provide the status information of the s'assurer que toutes les mesures de sécu-
rité nécessaires sont adoptées (par exem-
automatic transfer switch (open, ple, le pare-feu et les autres mesures). Le
module ne peut pas être connecté direct-
closed). ment à l'internet. Il est recommandé de le
connecter uniquement qu'aux réseaux
Ethernet dédiés utilisant le protocole de
communication EtherNet/IP.
—
Fig. 5.23 Ekip Com EtherNet/IP -module
108 Z e n i t h Z B T S T- se r i es 1 0 0 0 A - 3 0 0 0 A By pass Is o l at i o n AT S
Link
Activity
—
Fig. 5.24 Signals of Ekip Com EtherNet/IP -module
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 109
1
• To set the addressing of the modules.
• In order to display information on the
modules.
About Description
:
Modules (Optional modules)
1
1
sibility to ensure that all the necessary
TruCONTROL equipped with Ekip Com safety measures are adopted (for example,
firewalls, and other measures).) to protect
Hub can establish the connection to ABB the product, the network, the customer
system and interface against any kind of se-
Ability for the whole low-voltage power curity breaches, unauthorized access, inter-
ference, intrusion, loss and/ or theft of data
distribution panel. This dedicated car- or information.
Remarque
tridge-type communication module just Il est de la seule responsabilité du client de
fournir et d'assurer en permanence une
needs to be inserted into the TruONE and connexion sécurisée entre Ekip Com Hub et
le réseau du client ou tout autre réseau
connected to the internet. (selon le cas). Il est de la responsabilité de
l'installateur de s'assurer que toutes les me-
sures de sécurité nécessaires sont
adoptées (par exemple, pare-feu et les au-
The Ekip Com Modbus RTU and Ekip Com tres mesures) pour protéger le produit, le
réseau, le système du client, et l'interface
Modbus TCP modules can be configured contre toute forme d'atteinte à la sécurité,
d'accès non autorisé, ingérence, intrusion,
to support Ekip Com Hub in the collection perte et ou vol de données ou d'informa-
tions.
of data to send to cloud.
—
Fig. 5.25 Ekip Com Hub -module
112 Z e n i t h Z B T S T- se r i es 1 0 0 0 A - 3 0 0 0 A By pass Is o l at i o n AT S
Link
Activity
—
Fig. 5.26 Signals of Ekip Com Hub -module
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 113
1
• In order to display information on the
modules.
About Description
:
Modules (Optional modules)
1
—
5.6 Ekip Signaling 10k module
1
The Ekip Signaling 10k is an accessory The module is connected to TruCONTROL
module for external signaling that can be via Local Bus connection and supplied by
installed on a standard 35 mm DIN rail 24V DC.
(DIN EN 50022 type TS 35×15mm). In cer-
tain ZBTS T-series offerings, this module Further information on Ekip Signalling
is pre-installed, with a certain number of 10K is available on the website http://
pre-programmed functions. www.abb.com/abblibrary/DownloadCen-
ter/, in particular in the manual
This Ekip module has: 1SDH001318R0002.
• Ten programmable output contacts. IMPORTANT: Make sure that you have read
• Ten or eleven programmable digital in- the recommendations concerning secu-
puts. rity and precaution from unauthorized
• A power-on LED, and twenty or twen- access.
ty-one signaling LEDs (one for each out-
put/input).
—
Fig. 5.27 Ekip 10k module
116 Z e n i t h Z B T S T- se r i es 1 0 0 0 A - 3 0 0 0 A By pass Is o l at i o n AT S
—
5.7 Current measurement -modules
Zenith ZBTS T-series includes embedded
current measurement in the standard of-
fering. The current measurement module
utilizes rating plugs to improve measure-
1
ment accuracy.
The rating plugs are field interchangeable Type C sensors are openable sensors
from the front of the TruCONTROL ATS without bushing bar. Current sensors are
controller. An assortment of rating plugs installed on each phase; the rated unit
are provided with the equipment. The rat- current can be configured with the inter-
ing plug sized for the expected typical op- changeable rating plug module.
erational load should be installed for best
measurement accuracy. Type C sensors guarantee an insulation
resistance of 1000 Vrms CAT III / 600
Rating plugs for currents 1000A-4000A Vrms CAT IV and an IP67 protection
degree.
• 1SDA074224R1 1000A
• 1SDA079730R1 1200A Sensor type code includes three or four
• 1SDA074226R1 1600A sensors of the same type and size, de-
• 1SDA074227R1 2000A pending on the automatic transfer switch
• 1SDA074228R1 2500A (3P or 4P) operated by TruCONTROL ATS
• 1SDA074229R1 3200A controller.
—
Fig. 5.28 Rating plug
—
Fig. 5.29 Current sensor
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 117
—
5.8 Temperature measurement
1
High precision temperature sensors are
used on the Zenith ZBTS T-series By-
pass-Isolation ATS. Sensors are installed
on the highest temperature contact of the
load (L2). Therefore, measuring the tem-
perature of L2 can indicate the accurate
temperature.
—
Fig. 5.30 Temperature measurement
118 Z e n i t h Z B T S T- se r i es 1 0 0 0 A - 3 0 0 0 A By pass Is o l at i o n AT S
—
5.9 Switch-Test/Auto/Inhibit/Start
1
The 4-position switch is an optional accessory which can change the ATS status by
switching the key position. The 4-position switch can send signal via controller to con-
trol the ATS. Operation of 4 positions are listed below:
Instructions:
—
5.10 Audible Transfer Alarm
1
The audible transfer alarm will sound and illuminate when the ATS is connected to
source 2 (normally, the default main power supply is source 1). Alarm can be silenced via
the HMI and will otherwise be reset by retransferring back to source 1.
120 Z e n i t h Z B T S T- se r i es 1 0 0 0 A - 3 0 0 0 A By pass Is o l at i o n AT S
1
—
6. Troubleshooting
Warning
Any troubleshooting should be conducted by trained and authorized personnel only. Appropriate personal
protective equipment (PPE) should be used when troubleshooting the ATS panel.
Hazardous voltage may be present. Disconnect all power sources before performing work inside the ATS
panel.
Failure to do so may result in serious injury or death.
Avertissement
Tout dépannage doit être effectué uniquement que par un personel formé et autorisé. Un équipment de
protection individualle (EPI) approprié doit être utilisé lors du dépannage du panneau ATS. Une tension dan-
gereuse peut être présente. Débranchez toutes les sources d'alimentation avant d'effectuer des travaux à
l'intérieur du panneau d'ATS. Ne pas le faire peut entraîner des graves blessures ou la mort.
—
6.1 Alarms Touch
missing connections
S2 unbalance Phases of source 2 are not symmetric Check the power source
S2 phase rotation Phase rotation of source 2 is different Connect the phases according to the
from the value of parameter “Phase configuration
sequence“
S2 neutral Neutral is disconnected from source 2. Check connection of neutral in source 2
disconnected Note: The loss of neutral will be and that the corre-sponding power
detected in 3 phase distribution distribution system parameter is set
systems with unbalanced loads correctly
S2 invalid frequency Frequency of source 2 is out of range Check the correlation between power
set in parameters “Drop-out frequency, source and device configuration
upper threshold” and “Drop-out
frequency, lower threshold“
Frequency Difference Frequency difference of volt-age Alarm is active and transfer op-erations
sources is greater than 0.2 Hz while in disabled as long as the frequency
phase monitor is on difference is above the accepted level
High current alarm Measured current is higher than ten Alarm is active and transfer operations
times the nominal value disabled as long as the high current
status remains
Open I failure, Alarm Switch transfer from position I to O or Reset alarm by pressing Auto button or
LED blinking II failed via menu page Operation / Alarm Reset
Close I failure, Alarm Switch transfer to position I failed Reset alarm by pressing Auto button or
LED blinking via menu page Operation / Alarm Reset
Open II failure, Alarm Switch transfer from position II to O or Reset alarm by pressing Auto button or
LED blinking I failed via menu page Operation / Alarm Reset
Close II failure, Alarm Switch transfer to position II failed Reset alarm by pressing Auto button or
LED blinking via menu page Operation / Alarm Reset
Switch position alarm, Switch position indication inputs are ATS is not in the Connected/Test
Alarm LED on activated correctly position.
Switch service needed
Pole temperature Measured pole temperature is too high Load is too high
alarm Switch service needed
Continued on the next page
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 123
1
Configuration Error Invalid configuration Check parameter values
Ekip Com Hub Alarm Ekip Com Hub failure Check configuration
Firmware versions of HMI and device Check current versions and update
HMI Not Compatible are not compatible to be used together compatible versions
—
Table 6.1 Alarms-list in touch control interfaces
—
6.2 Warnings
Touch
Message Reason
S1 and S2 not in sync Voltage sources are not synchronized
Voltage Not Calibrated Calibration data in power module is invalid or unavailable
Current Not Calibrated Calibration data in current measurement module is invalid or unavailable
Control Retry Failed transfer sequence retry activated
Pole temperature warning Measured pole temperature is near the alarm level
Auto Control Disabled Device is in manual operating mode
Module heartbeat error.
Local Bus Check connection. Can be cleared using "Alarm Reset"
Configuration Configuration session ports are open
Real time clock is not yet operational, date & time setting is disable as
long as this warning is active. Clock capacitor is charged from source
Clock capacitor charging voltage (not AUX) and takes about 10 minutes
Generator failed to start Generator has not been started within 1 minute after sending start
signal or it has failed during any test sequence
—
Table 6.2 Warnings-list in touch control interfaces
124 Z e n i t h Z B T S T- s e r i e s 1 0 0 0 A - 3 0 0 0 A By pass Is o l at i o n AT S
—
6.3 Information
Touch
1
Message Description
Invalid Date Date not set
Test on Load Test on load sequence active
Test off Load Test off load sequence active
Alarm/Product Availability Digital output function activated
Position I Digital output function activated
Position O Digital output function activated
Position II Digital output function activated
Pre-transfer Signal Digital output function activated
Source 1 Available Digital output function activated
Source 2 Available Digital output function activated
Load Shed Digital output function activated
Emergency Stop Digital input function activated
Remote Test on Load Digital input function activated
Remote Test off Load Digital input function activated
Inhibit Auto Mode Digital input function activated
Manual Retransfer Digital input function activated
Priority S1 Digital input function activated
Priority S2 Digital input function activated
Inhibit Transfer Digital input function activated
Bypass Running Delays Digital input function activated
Remote Control to S1 Digital input function activated
Remote Control to Off Digital input function activated
Remote Control to S2 Digital input function activated
Alarm Reset Digital input function activated
Manual-Auto Mode Digital input function activated
—
Table 6.3 Info statements in touch control interfaces
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 125
—
6.4 Light indication and alarm
Bypass panel, located on the upper part of the cabinet, shows status of bypass device
and the ATS.
1
Message Description
S1 AVAILABLE, LED off S1 is not available
S2 AVAILBALE, LED off S2 is not available
BS1 ENGAGED, LED off Bypass contact is not connected to source 1
BS2 ENGAGED, LED off Bypass contact is not connected to source 2
AS1 ENGAGED, LED off ATS contact is not connected to source 1
AS2 ENGAGED, LED off ATS contact is not connected to source 2
ATS and bypass contact are connected to the same
ATS/BYP PARALLEL, Alarm LED on source.
DS SWITCH INHIBIT POSITION, Alarm LED on Disconnect switch is in the inhibit mode
—
Table 6.4 Bypass panel LED indication and alarm
—
6.5 Elimination of simple malfunctions
Disturbance Reason
ATS can’t be transfer by HMI button “I ON”, “II ON”, Disconnect switch is in the inhibit position
“O off” ATS is in the Auto mode
ATS can’t be transfer to the same source with MTS Disconnect switch is in the inhibit position
during pressing “contact reset” button MTS contact is not close into Source1 or Source2
TruControl Input had not configuration correctly
Disconnect switch is turned into “Auto” position, but ATS not in the Connected/Test position.
“Auto mode” on HMI have not been lighted MTS contact is not in off position
ATS not configurate to Auto Mode
Operation handle can’t insert into RIRO hole MTS S1 and S2 both at “Open” position
Disconnect switch is in the “Auto” position
RIRO release sheet at “Lock” position
The front door is opened (If the door interlock has
been applicated)
ATS can’t be rack out from Connected position ATS and MTS connected to different source (For
Open ATS).
ATS is not at “O off” status (For Delay/Close ATS)
Bypass Panel lock is not at “Release” position
Disconnect switch is in the “AUTO” position
126 Z e n i t h Z B T S T- s e r i e s 1 0 0 0 A - 3 0 0 0 A By pass Is o l at i o n AT S
ATS can’t be rack into Connected position ATS and MTS connected to different source (For
Open ATS).
ATS no at “O off” status (For Delay/Close ATS)
Bypass Panel lock not at “Release” position
Disconnect switch is in the “AUTO” position
ATS can’t be rack out from Test position Bypass Panel lock not at “Release” position
1
—
Table 7.1 Automatic transfer switch I/O contacts
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 129
1
440 0.1 44
—
Table 7.2 Technical data for auxiliary contacts according to IEC 60947-5-1, for OA1G_, OA3G_
Environmental Value
Operating temperature -20… +65 °C
Transportation and storage temperature -20… +75 °C
Altitude Up to 2000 m
—
Table 7.3 General technical data of automatic transfer switch
—
Table 7.4 Specified technical data of operating times
130 Z e n it h Z B T S T- s e ri e s 1 0 0 0 A - 3 0 0 0 A By pass I so l atio n AT S
—
7.2 Circuit diagrams
1
—
Fig. 7.1 Primary circuit for ATS and bypass
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 131
—
Fig. 7.2 ATS control circuit diagram
132 Z e n it h Z B T S T- s e ri e s 1 0 0 0 A - 3 0 0 0 A By pass I so l atio n AT S
1
—
Fig. 7.3 Bypass control circuit diagram
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 133
1
—
Fig. 7.4 Customer Engine start and Auxiliary contact relay
Note:
1 Program “Application” =” S1-Transformer/S2-Generator”
2 Generator starts and shuts down by TruControl in the "Connected" and "test"
positions, starts and shuts down by the RNH relay in the "Isolated" position.
134 Z e n it h Z B T S T- s e ri e s 1 0 0 0 A - 3 0 0 0 A By pass I so l atio n AT S
EKIP Input/Output
Modules Cable Input Output
EKIP2K 0.75…2.5mm2 5V@2.5mA 2A@30V DC; 0.8A@50V DC
28…16 AWG Do not connect to any power 0.2A@150V DC; 4A@250V AC
EKIP10K
supply
—
Table 7.5 Customer Ekip module -Input/output
1
Fire Fighting
Modules Description Cabling Remark
T9-1 Fire fighting input 24V DC(+) 0.75…2.5mm2 Only in I-O-II
—
Table 7.6 Customer Fire fighting
—
7.3 Overall Dimensions
—
Table 7.7 Overall dimensions
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 135
1
—
Fig. 7.5 Overall dimensions
—
Fig. 7.6 ATSE dimensions
136 Z e n it h Z B T S T- s e ri e s 1 0 0 0 A - 3 0 0 0 A By pass I so l atio n AT S
1
—
8. Maintenance
On the other hand, when the contacts
Warning have seen an event, or have met the end of
Any maintenance should be conducted by
trained and authorized personnel only. their lifetime, the whole switch should be
Appropriate personal protective equipment
(PPE) shall be used when performing mainte- replaced – which can be done easily by re-
nance on the ATS panel.
Hazardous voltage may be present. placing the complete ZBTS power panel
Disconnect all power sources before perform-
ing work inside the ATS panel. within the enclosure.
Failure to do so may result in serious injury or
death.
Avertissement
Toute maintenance doit être effectuée que par In the case you suspect a failure may be
un personnel formé et autorisé. Un équipment
de protection individuelle (EPI) approprié doit due to manufacturing defect and covered
être utilisé lors de la maintenance du panneau
d'ATS. under warranty, see Chapter 1.3.
Une tension dangereuse peut être présente.
Debranchez toutes les sources d'alimentation
avant d'effectuer des travaux à l'interieur du
panneau d'ATS. Ne pas le faire peut entraîner Refer to Chapter 7 Technical data for ATS
des graves blessures ou la mort.
contact endurance and note that the num-
ber of operations can be viewed in the in-
formation menu from the HMI.
Maintenance Principle
The Zenith ZBTS T-series 1000A-3000 A,
Routine Inspection
Bypass Isolation Automatic Transfer
ABB recommends a routine (such as
Switches, are designed so that the con-
annual) inspection to, for example, check
tacts last their designed lifetime without
electrical termination temperatures,
replacing any parts. If there are abnormal
ensure the unit is clean, check voltage
conditions such as a fault or overload
levels, test transfers, check number of
without adequate protection, or extreme
operations, etc. to ensure everything is in
environment conditions, a failure of ATS
proper working order.
components may occur. Fortunately, all
critical modules, including complete
Recommended annual inspection
mechanism with electronics (controller,
includes:
power module, and solenoid mechanism),
- Review event log
lights, HMI, and accessories are easily re-
- Check number of operations and other
placeable. Refer to Chapter 11 for replace-
switch status figures
ment parts.
- Visually inspect both inside and outside
of enclosure for damage
Note: The designed lifecycle for lights is 5
or debris
years. Please check the brightness regu-
- Test transfer of load
larly and replace any malfunctioning light.
- Observe voltage levels of both sources
Please note that malfunctioning light may
within expected range
mislead users.
- Verify cable lug torque
- Check lights brightness
- Lubricate MST interlock mechanical
parts
138 Z e n i t h Z B T S T- s e ri e s 1 0 0 0 A - 3 0 0 0 A By pass I s o l at i o n AT S
1
—
9. Installation
Before mounting the product, please check the product identification from the product
identification label, which is located on the front panel under the control interface unit
(HMI). This label indicates the product model (type number) and important technical in-
formation including but not limited to, suitable wire.
Notice
Final inspection of the equipment should Assurez-vous que toutes les connexions de
be performed prior to energizing the auto- câbles sont correctes et que la rotation de
matic transfer switch. phase des deux sources correspondent.
Remove any dirt or debris that may have Inspectez les connexions de démarrage du
collected during shipment or installation. moteur et vérifiez que la connexion de tous
NEVER use compressed air. Doing so could les câbles de commande est correcte.
drive dirt or other foreign objects into elec-
trical or mechanical components, which Verifiez tous les points programmables et
could cause damage. Use an industri- ajustez-les si nécessaire. En plus, réglez les
al-quality vacuum cleaner to remove any accessoires optionels selon les besoins.
dirt or foreign objects.
Assurez-vous que les valeurs de couple de
Be certain all cable connections are correct cosse réelles sont conformes aux exigences
and that the phase rotation of both sources décrites dans le manuel d'instructions pour
match. garantir l'intégrité de la connexion
d'alimentation.
Inspect the engine start connections and
verify the correct connection of all control Assurez-vous que tous les couvercles et bar-
wires. rières sont correctment installés et fixées.
Sides dommages sont decouverts ou sus-
Check all programmable set points and ad- pectés, déposez une reclammation le plutôt
just as necessary. In addition, adjust any que possible aupès du transporteur et infor-
optional accessories as required. mez le représentant de ABB Zenith le plus ou
appelez le 1-800-637-1738.
Be certain that the actual lug torque values
are within the requirements outlined in the
instruction book to ensure the integrity of
power connections.
—
9.1 Basic Tools for Installation and Maintenance
Tool Task
1/4" to 1/2" Allen head socket driver Power cable connection
Torqueing of the lugs and other hardware as required.
Torque wrench Range of device to be 50 - 500 in-lbs (5-57 N-m)
Torqueing of control wire terminations, auxiliary contact
Torque screwdriver input terminals. 5 - 25 in-lbs (0.5 - 2.8 N-m)
Auxiliary contacts wire installation, optional accessory
Wire cutters/wire crimpers installation
Trouble shooting tool for measuring incoming voltage,
Voltmeter frequency, continuity and control signal transmission.
Controller default password 00001 Changing parameters within the controller
—
Table 9.1 Required tools for common installation and maintenace tasks
2
—
9.2 Equipment Inspection and Storage
—
9.3 Lifting and Mounting the Panel
Lifting guidelines
Adequate lifting means must be used to circulation and heat if necessary to pre-
mount the transfer switch into place. The vent condensation. See table 7.3 for rec-
recommended method for moving the ommended storage and ambient operat-
ABB Zenith Bypass Isolation Automatic ing temperatures.
Transfer Switch in the enclosure, is using
forklift and forklift equipment properly ABB Zenith Bypass Isolation Automatic
rated for the equipment/enclosure Transfer Switches are packaged as per
weight. the standard packaging regulatory stan-
dards suitable for domestic and interna-
2
THE LIFTING EYELETS ON THE ENCLO- tional shipment through all modes of
SURE ARE FOR ASSEMLY PURPOSES transportation (air, sea and road). Once
ONLY. LIFTING OF COMPLETE ASSEMBLY you unpack the units, please make sure all
SHOULD ONLY BE DONE FROM BOTTOM the components are received as per the
SURFACES USING APPROPRIATELY RATED BOM. For any missing items, contact your
LIFT EQUIPMENT. local ABB Zenith service representative.
1. ABB Zenith Bypass Isolation Automatic Figure 9.1 shows the enclosure. Two indi-
Transfer Switches are mounted and se- cation marks for forklift points are lo-
cured onto a wooden enclosure using cated at the bottom of the enclosure.
bolts and nuts When using a forklift, make sure the forks
are inserted into correct position and
2. Refer to table 7.7 for the enclosure/
completely through the package.
equipment weight and make sure that the
forklift is properly rated to handle the
weight.
—
Fig. 9.1 package
—
Fig. 9.2 Fork lift point indication marks.
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 143
1. ABB Zenith Bypass Isolation Automatic 4. Refer to Table 7.7 for the weight infor-
Transfer Switches are mounted onto a mation, or the dimensional drawing for
wooden pallet using bolts and nuts. the center of gravity dimensional drawing
Please remove the bolts and nuts prior to for the CG, weight information, and lifting
lifting. provisions to select the properly rated
lifting devices.
2. Make sure the Bypass Isolation Auto-
matic Transfer Switch is on “ISOLATED” 5. While lifting the unit using lifting
position before lifting – refer to session chains, it is recommended to maintain a
3.8. 45° angle as shown in Fig. 9.3.
3. ABB Zenith Bypass Isolation Automatic 6. ABB Zenith Automatic Transfer Switch
Transfer Switches have the provisions for units should be lifted using properly rated
lifting through lifting holes as shown in lifting devices.
2
Fig. 9.3.
Danger
Hazardous Voltage can Cause Severe Injury or
Death
Disconnect all power before installing, adjust-
ing, or removing transfer switch or any of its
Lifting bolts components.
Danger
Une tension dangereuse peut causer de
graves blessures ou la mort. Débranchez
toute alimentation avant d'installer, de régler
ou de retirer le commutateur/ l'autocommuta-
teur de transfert ou l'un des composants.
450
Warning
Due to hazardous voltages and currents,
ABB recommends that only an ABB certified
technician or a qualified electrician per-
form the installation & maintenance of the
switch.
Avertissement
En raison des tensions et courants dan-
gereux, ABB recommande qu'un technicien
certifié d'ABB ou un electricien qualifé ef-
fectue l'installation et la maintenance de
l'interrupteur.
—
Fig. 9.3 ATS lifting.
144 Z e n i t h Z B T S T- s e r i e s 1 0 0 0 A - 3 0 0 0 A By pass I s o l at i o n AT S
Danger
Hazardous Voltage can Cause Severe Injury or
Death
Automatic Transfer Switch Equipment must
be electrically grounded. Failure to do so may
result in malfunction of the switch and possi-
ble damage to surrounding equipment.
Danger
Une tension dangereuse peut causer de grave
blessures ou la mort.
L'équipment du commutateur de transfert au-
tomatique doit être etablit à la terre
électriquement.
Le non-respect de cette consigne peut en-
traîner un dysfonctionnement de l'interrupt-
eur et des dommages éventuels à l'equipment
environnant.
Warning
Before drilling conduit entry holes or any
accessory mounting holes, cover and pro-
2
Warning
Not following ABB lifting guidelines may
result in severe injury or death.
Avertissement
Ne pas suivre les directives de levage d' ABB
peut entraîner de graves blessures ou la
mort.
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 145
—
9.4 Mounting the automatic transfer switch
Before mounting, please make sure there is enough space for the cabinet.
In order to fully open the cabinet door, the smallest distance from front door to any bar-
rier is 47.5 in (1.2 m). Allow at least 39.5 in (1 m) of clearance behind enclosure, and 20 in
(0.5 m) of clearance above the enclosure. Please note that these values provided are for
the minimum required room size, For reasonably practical operation such as lifting,
racking in/out, a larger space is recommended. Please consult qualified personnel to
obtain space size.
2
31.5in(0.8 m)
Right
Front Rear
Left
—
Fig. 9.4 Minimum distance from the cabinet top to the ceiling. Unit: Inch (mm)
146 Z e n i t h Z B T S T- s e r i e s 1 0 0 0 A - 3 0 0 0 A By pass I s o l at i o n AT S
At the bottom of the cabinet, there are two base steels which fix the cabinet on a
platform or ground. On each base steel, two 15mm diameter holes allow the cabi-
net is fixed via screws. Mounting hole dimensions are shown in figure 9.6.
2
41.34
0.59
64.77
—
Fig. 9.5 Mounting hole dimensions.
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 147
—
9.5 Wire Connection
9.5.1 Main circuit
Tightening Torque1,
Function LUG Type Wire Range Cables per pole lb-in (N-m)
2
Table 9.2 Power Cable Torque Requirements
Detailed dimensions and location of S1, S2, Load and Ground bars are shown in market
drawing.
T9
—
Fig. 9.6 Fire Fighting connector located on the front of ATS Controller OXCO_
Connector/
—
9.5.3 Generator start/stop and ATS contact position
2
A42NO
A42NO
A32NO
A42NC
A42NC
A31NO
A32NC
A31NC
A42C
A42C
A32C
A31C
E13
E12
E11
—
Fig. 9.7 Generator start/stop and ATS contact position located on electrical panel
Connector/
2
position NO
—
9.6 Final Equipment
Inspection Inspection
Prior to energizing the transfer switch: Each ABB Zenith transfer switch is factory
wired and tested. A complete information
1. Remove any debris incurred, with a
package is furnished with each switch
vacuum, due to shipment or installation.
which includes:
2. Verify that all cabled connections are - Sequence of operation.
correct and that phase rotation of both - Description and operation of all
sources match. accessories supplied.
- Power panel connection diagram
3. Check engine start connections.
and schematic.
4. Verify the correct connection of all - Description and identification of all
control wires. customer field connections.
2
5. Check settings of all timers and Installation of ABB Zenith Bypass isola-
adjust as necessary. tion automatic transfer switch includes:
- Mounting the ATS cabinet
6. Adjust any optional accessories as
- Connection of Source 1, Source 2, and
required.
Load cables or bus bars.
7. C
heck the lug torque values of the power - Connection of external control circuits
connections. as required.
—
9.7 Initial Energizing
Before proceeding, refer to the informa-
tion package supplied with the ATS and Energizing the panel
read and understand the information on 1. Close Source 1 circuit breaker.
all accessories provided, including this
NOTE: The HMI should illuminate if line
complete document.
voltage is present and S1 LED should
light up.
Before energizing the panel
1. Confirm that installation has been 2. Verify the phase to phase voltages at
performed by a qualified person and in the Source 1 terminals.
accordance with NFPA 70 (NEC).
3. Initiate auto configure from HMI default
screen: Enter > Parameters >
2
Notice System Parameters > Start Automatic
This installation should be properly oper-
ated and maintained in accordance with the Configuration and allow a few seconds
safety practices of NFPA 70E.
Remarque for system parameters to set"
Cette installation doit être correctement
exploitée et entretenue conformément aux
pratiques de sécurité de la norme NFPA 4. Close the Source 2 circuit breaker.
70E.
2. Confirm rating label matches the in- NOTE: If generator voltage is present at
stalled application. Rating label is lo- Source 2 terminals, S2 LED should light
cated inside the panel enclosure. up.
3. C
onfirm that cables are connected 6. Verify phase rotation of S1 matches
properly and torqued according to the that of S2.
ATS labeling.
NOTE: The ATS will not allow transfer if
4. Verify that the enclosure ground con- phase rotation does not match.
nection is properly terminated.
7. Shut down the generator engine.
5. Confirm that control wiring for engine
8. Place the ATS in AUTO mode from the
start is properly terminated to the en
HMI by pressing AUTO key.
gine start contact (located in Chapter
9.5.3). Additionally, connect all 8. For additional start-up guidance for the
applicable digital I/O, communications, ATS, please refer to ZTG Quick Start ,
and auxiliary contact wiring. Guide, document number
1SCC303023K0201.
6. Flip slide switch (Fig. 3.13 number 4)
to AUTO.
7. E
nsure that all objects and debris are
removed from enclosure, and enclosure
is closed and latched.
152 Z e n i t h Z B T S T- s e r i e s 1 0 0 0 A - 3 0 0 0 A By pass I s o l at i o n AT S
2
—
10. Accessories
Warning
Any troubleshooting should be conducted
by trained and authorized personnel only.
Appropriate personal protective equipment
(PPE) should be used when troubleshooting
the ATS panel.
Hazardous voltage may be present. Discon-
nect all power sources before performing
work inside the ATS panel.
Failure to do so may result in serious injury
or death.
Avertissement
Tout dépannage doit être effectué unique-
ment que par un personel formé et autorisé.
Un équipment de protection individualle
(EPI) approprié doit être utilisé lors du
dépannage du panneau d'ATS. Une tension
dangereuse peut être présente. Débran-
chez toutes les sources d'alimentation
avant d'effectuer des travaux à l'intérieur
du panneau d'ATS. Ne pas le faire peut en-
traîner des graves blessures ou la mort.
—
10.1 Auxiliary power supply and Ekip -modules
ZBTS T-series bypass isolation automatic For more information, see Chapter 5,
transfer switches, 1000A-3000A, 200-480 Electronic accessories. The maximum
Vac can be equipped with Ekip-modules. number of Ekip-modules is 4.
Ekip-modules are mounted with a
auxiliary power supply module, OXEA1.
Suitable Ekip-modules are: Ekip link,
signalling and connectivity modules.
154 Z e n i t h Z B T S T- se r i es 1 0 0 0 A - 3 0 0 0 A By pass Is o l at i o n AT S
OXEA1
2
Ekip
—
Fig. 10.1 Mounting of the auxiliary power supply
module OXEA1 and Ekip –modules
—
Fig. 10.2 Removing the auxiliary power
supply module OXEA1 and Ekip –modules
from the automatic transfer switch
O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E 155
—
10.2 HMI protective cover
2
0.8 Nm / 7.1 lb.in
OXEC21
IP54
1
A07491
Ø 4 mm
0.16 in
156 Z e n i t h Z B T S T- se r i es 1 0 0 0 A - 3 0 0 0 A By pass Is o l at i o n AT S
2
—
11. Replacement Parts
Mark DESCRIPTION ABB Part number
Operating handle Rotary handle 7004629208a
Limit switch (SN, SE, A3, A4) Limit switch 5GX.043.006
208V/240V standard solenoid 70010259508A
380V/400V/415V Standard 3P solenoid 70010425427A
440V/480V Standard 3P solenoid 70010425470A
380V/400V/415V Standard 4P solenoid 7006019398A
Solenoid
440V/480V/ Standard 4P solenoid 70010259489A
208V/240V Delay/Close solenoid 70010270854A
380V/400V/415V Delay/Close solenoid 7008561306A
440V/480V Delay/Close solenoid 70010276342A
SCR 5GX.579.001 or PS-8903
ATS Harness for BYPASS,
2TFR360463A1001
OPEN
ATS Harness for BYPASS,
2TFR360463A1002
Close and Delay
DISCONNECT SWITCH-BODY 2TFR360012A1001
DS SWITCH DISCONNECT SWITCH-AUXILIARIA SWITCH 2TFR360013A1001
DISCONNECT SWITCH-SELECTOR HANDLES 2TFR360014A1001
LIGHT RED VOLTAGE 24 V AC / DC 2TFR360017A1001
LIGHT LIGHT GREEN VOLTAGE 24 V AC / DC 2TFR360018A1001
LIGHT YELLOW VOLTAGE 24 V AC / DC 2TFR360019A1001
PUSHBUTTONS FLUSH PUSHBUTTONS - MOMENTARY 2TFR360020A1001
POWER RELAY MY4-D DC24V 2TFR360021A1001
RELAY
RELAY SOCKET PYFZ-14-E 2TFR360022A1001
LIMIT SWITCH(AI,AT,AA) LIMIT SWITCH SPDP PIN PLUNGER 2TFR360023A1001
LIMIT SWITCH(AB3,AB4) LIMIT SWITCH SPDP HINGE LEVER 2TFR360024A1001
TERMINAL WDU 2.5 FEED-THROUGH 2TFR360025A1001
CROSS-CONNECTOR WQV 2.5/2 W-SERIES 2TFR360026A1001
Terminal END PLATE WAP 2.5-10 W-SERIES 2TFR360027A1001
END BRACKET WEW-35/2 W-SERIES 2TFR360028A1001
PCB TERMINALS FASTON 0.250 2TFR360031A1001
BYPASS BRAIN XFR ASY 416-440 150045790
BYPASS BRAIN XFR ASY 208-220 (211V) 150045787
BYPASS BRAIN XFR ASY 230-240 150045788
PCBA
BYPASS BRAIN XFR ASY 380-400 (386V) 150045789
BYPASS BRAIN XFR ASY 460/480 150045791
BYPASS LOGIC BOARD ASSY 150044004
Open CS 3P type C 120 1SDA083372R1
Current sensors
Open CS 4P type C 120 1SDA083373R1
Temperature sensor External probe PT1000 3 m 1SDA085695R1
Continued on the next page
158 Z enit h Z B T S T- series 1 0 0 0 A - 3 0 0 0 A By pass I so l ation AT S
1
—
Contact us
24-hour support:
ABB Technical Services
+1 (800) 637-1738
epis.pqservice@abb.com
abb.com/lowvoltage