2-8 Loop Fire Alarm Control Panel
The MxPro 5 series is fully expandable
from 2 to 8 loops and supplied with 8
on-board sounder circuits, 20
programmable Zonal LEDs with slide-in
labels, and 25 System LEDs for
information purposes. There are also 8
programmable function buttons with LED
indication for confirmation of operation.
The control panel consists of the latest
dual flash-based microprocessor
technology combined with a high
resolution, high contrast, graphical LCD
display and tactile keypad providing a
simple select & click programming aid for
engineer configuration and end-user
operation.
Powerful cause-and-effect programming
coupled with dynamic zoning, and
enhanced Trace Diagnostics makes the
panel suitable for a wide range of site Features
applications from small to large complex
multi-area systems. Fully programmable
Fully expandable from 2 - 8 loops via Fully programmable via the on-board
onsite via the on-board alphanumeric
plug-in loop driver boards. alphanumeric keypad, or PC
keypad, or PC-NeT configuration software.
20 programmable Zonal / 25 System configuration tools.
An extensive suite of user-friendly
LEDs with slide-in labels. The graphical display can be
Windows based PC software programs
Dedicated loop driver for Apollo or configured to operate with virtually
has been developed to enhance your
Hochiki protocol support. any language or character set, and
experience when using MxPro 5 series fire
Advanced graphical LCD user allow the installer's logo to be
panels. The suite incorporates a number
interface and support for up to 200 applied using the Logo application
of different programmes to include a
fire zones by default allowing full software.
configuration, service, logo and virtual
EN54 compliance without additional Robust removable equipment
panel tool to allow the flexibility of the
hardware. chassis with plug-in connectors for
equipment to be fully explored.
Dual flash-based microprocessor simple fixing and cable termination.
technology with real-time clock 2 x 5 Amp power supply and charger
Simply adding a network card allows the on-board. to En54 part 4.
panel to communicate with any other Dedicated USB & RS232 serial port Integral P-Bus for system expansion
MxPro 5/MxPro 4 fire panel, remote for direct PC or modem connection. via available option cards.
terminal, or network peripheral, such as, Installer friendly Auto-learn, Loop Ad-NeT peer-to-peer network with
ipGateway™ or BMS/graphical interface. Detection and On-board Scope up to 2000 zones.
The network operates as a true facility for ease of commissioning
peer-to-peer system and can be and fault finding.
configured in a fault tolerant loop or radial
format.
v1.0
Key Features
Dedicated 2 - 8 Loop Global Compliance 3 Year Warranty Programmable Push Buttons
Multiple Languages Fully Networkable 20 Zonal / 25 System LEDs Slide-in Labels
Specification
Base Technology Dual flash-based processors with real-time clock, trace diagnostics, programmable languages and character
sets
Display White backlit 240 x 64 graphical LCD
LED Indicators 22 red (1 x Fire, 1 x More Alarms, 20 x Zonal Programmable), 1 green (Power), 13 amber and 7 bi-colour
(Fault & System)
Controls Alpha numeric keypad permitting Navigation, Reset, Mute, Silence, Resound, Evacuate, and 4 x
Programmable Push ButtonsActual 2
Protocols Apollo (Xp95 / Discovery), Hochiki ESP, Argus Vega and Nittan Evolution
Number of Fire Zones 2000 when networked (400 max across 8 loops)
Number of loops Dedicated 2-8 loop control panel
Devices per loop Protocol dependent
Loop Current 500mA max per loop
On-Board Sounder Circuits 8 x 1 Amp programmable
On-Board Relays 4 x 1 Amp 30v AC/DC programmable (10mA, 5v min) - expandable to 8 using 2 x Mxp-507
Auxiliary Supply 2 x 24v 500mA 2
Programmable Input 2 x On-board Programmable Input
Programmable Key Switch Inputs 16 volt free digital inputs
Total Available Output Current 2 x 5A maximum available for loop current + sounder outputs + auxiliary supply
Mains Supply 200 - 240v 47-63 Hz AC (+10%, -15% tolerance) 1.4A max
Battery Capacity 2 x 24V 4Ah internal (min), 2 x 24V, 18Ah internal (max), or 1 x 24V 45Ah internal (max) and 1 x 24V 45Ah
external (max) using optional battery enclosure
Charger Current 2 x 2.0A temperature compensated
Serial ports 2 x on-board RS232 connection for PC, modem, IP or portable printer
USB Interface 2 x USB B type connection for PC communication
Programming On-board keypad or PC running Windows tools
Event Log 2 x 5000 Event & Diagnostic + 500 Fire
Printer (Optional) On-board
Enclosure / Colour Steel IP30 / RAL7035
Cable Entry (20mm knockouts) 30 x top, 6 x rear, 3 x bottom plus 2 x double knockout rear
Size H x W x D mm 750 x 450 x 190
Metalwork Options Flushing bezel, battery box, utility enclosure, termination enclosure and rack mount
Order Codes and Options
Mx-580x*: Multi Loop Panel in Standard x: Add loop driver quantity 2 - 8
Enclosure with standard network cards /FT: Add Fault-tolerant network cards
fitted *: Add V for Vega, and add N for Nittan
Evolution protocol
v1.0