Product data sheet
Specifications
TeSys D contactor - 4P(2 NO + 2
NC) - AC-1 <= 440 V 60 A 220 V AC
50/60 Hz coil
LC1D40008M7
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range TeSys
Product name TeSys D
Product or component type Contactor
Device short name LC1D
Contactor application Resistive load
Utilisation category AC-1
Poles description 4P
Power pole contact composition 2 NO + 2 NC
[Ue] rated operational voltage Power circuit: <= 690 V AC 25...400 Hz
Power circuit: <= 300 V DC
[Ie] rated operational current 60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
Control circuit type AC at 50/60 Hz
[Uc] control circuit voltage 220 V AC 50/60 Hz
[Uimp] rated impulse withstand 6 kV conforming to IEC 60947
voltage
Overvoltage category III
[Ith] conventional free air 60 A (at 60 °C) for power circuit
thermal current
Irms rated making capacity 800 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity 800 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand 320 A 40 °C - 10 s for power circuit
current 720 A 40 °C - 1 s for power circuit
72 A 40 °C - 10 min for power circuit
165 A 40 °C - 1 min for power circuit
Associated fuse rating 80 A gG at <= 690 V coordination type 1 for power circuit
80 A gG at <= 690 V coordination type 2 for power circuit
Average impedance 1.5 mOhm - Ith 60 A 50 Hz for power circuit
[Ui] rated insulation voltage Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Power circuit: 690 V conforming to IEC 60947-4-1
Electrical durability 1.4 Mcycles 60 A AC-1 at Ue <= 440 V
Power dissipation per pole 5.4 W AC-1
Front cover Without
Mounting support Plate
Oct 27, 2021 1
Rail
Standards CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
Product certifications RINA
GL
UL
GOST
BV
LROS (Lloyds register of shipping)
DNV
CCC
CSA
UKCA
Connections - terminals Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Power circuit: screw clamp terminals 1 cable(s) 1…35 mm²flexible without cable end
Power circuit: screw clamp terminals 2 cable(s) 1…25 mm²flexible without cable end
Power circuit: screw clamp terminals 1 cable(s) 1…35 mm²flexible with cable end
Power circuit: screw clamp terminals 2 cable(s) 1…25 mm²flexible with cable end
Power circuit: screw clamp terminals 1 cable(s) 1…35 mm²solid without cable end
Power circuit: screw clamp terminals 2 cable(s) 1…25 mm²solid without cable end
Tightening torque Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
Power circuit: 8 N.m - on screw clamp terminals - cable 25…35 mm² hexagonal screw head 4 mm
Power circuit: 5 N.m - on screw clamp terminals - cable 1…25 mm² hexagonal screw head 4 mm
Operating time 4...19 ms opening
12...26 ms closing
Safety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability 6 Mcycles
Maximum operating rate 3600 cyc/h 60 °C
Complementary
Coil technology Without built-in suppressor module
Control circuit voltage limits 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz
0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz
0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz
1...1.1 Uc (60…70 °C):operational AC 50/60 Hz
Inrush power in VA 140 VA 60 Hz cos phi 0.75 (at 20 °C)
160 VA 50 Hz cos phi 0.75 (at 20 °C)
Hold-in power consumption in 13 VA 60 Hz cos phi 0.3 (at 20 °C)
VA 15 VA 50 Hz cos phi 0.3 (at 20 °C)
Heat dissipation 4…5 W at 50/60 Hz
Environment
IP degree of protection IP20 front face conforming to IEC 60529
Protective treatment TH conforming to IEC 60068-2-30
Pollution degree 3
Ambient air temperature for -40…60 °C
operation 60…70 °C with derating
Ambient air temperature for -60…80 °C
storage
Operating altitude 0...3000 m
Fire resistance 850 °C conforming to IEC 60695-2-1
Flame retardance V1 conforming to UL 94
Mechanical robustness Vibrations contactor open: 2 Gn, 5...300 Hz
Vibrations contactor closed: 4 Gn, 5...300 Hz
2
Oct 27, 2021
Shocks contactor closed: 15 Gn for 11 ms
Shocks contactor open: 10 Gn for 11 ms
Height 127 mm
Width 85 mm
Depth 125 mm
Product weight 1.44 kg
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Weight 1.47 kg
Package 1 Height 11.2 cm
Package 1 width 13.5 cm
Package 1 Length 15.2 cm
Unit Type of Package 2 S02
Number of Units in Package 2 5
Package 2 Weight 7.605 kg
Package 2 Height 15 cm
Package 2 width 30 cm
Package 2 Length 40 cm
Package 3 Height 73.5 cm
Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation REACh Declaration
REACh free of SVHC Yes
EU RoHS Directive Compliant
EU RoHS Declaration
Toxic heavy metal free Yes
Mercury free Yes
RoHS exemption information Yes
China RoHS Regulation China RoHS declaration
Pro-active China RoHS declaration (out of China RoHS legal scope)
Environmental Disclosure Product Environmental Profile
Circularity Profile End of Life Information
WEEE The product must be disposed on European Union markets following specific waste collection and
never end up in rubbish bins
California proposition 65 WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony
trioxide, which is known to the State of California to cause cancer. For more information go to
www.P65Warnings.ca.gov
Contractual warranty
Warranty 18 months
Oct 27, 2021 3