The document outlines the general notes and specifications for electrical installations in accordance with the Philippine Electrical Code and local regulations. It specifies that all work must be performed by licensed professionals, using approved materials, and details the requirements for wiring, grounding, and installation heights. Additionally, it emphasizes the need for proper supervision by a registered electrical engineer or master electrician.

Uploaded by

EMMANUEL DAÑO
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
13 views1 page

MB 7

The document outlines the general notes and specifications for electrical installations in accordance with the Philippine Electrical Code and local regulations. It specifies that all work must be performed by licensed professionals, using approved materials, and details the requirements for wiring, grounding, and installation heights. Additionally, it emphasizes the need for proper supervision by a registered electrical engineer or master electrician.

Uploaded by

EMMANUEL DAÑO
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

GENERAL NOTES

1.ELECTRICAL INSTALLATION HEREIN SHALL BE DONE IN ACCORDANCE WITH


THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE & RULES AND
REGULATION OF THE MUNICIPALITY HAVING JURISDICTION. MESSENGER WIRE

16mmØ EYE BOLT

0.30m 0.30m
2. ALL ELECTRICAL WORKS HEREIN SHALL BE EXECUTED BY EXPERIENCED
SERVICE SPOOL PORCELAIN
MEN UNDER THE DIRECT SUPERVISION OF A DULY LICENSED ELECTRICAL [ BY OWNER / MERALCO ]
CT METERING BOX

ENGINEER OR A MASTER ELECTRICIAN, WORKS SHALL BE NEATLY PLACED, [ BY MERALCO ]

SECURELY FASTENED AND PROPERLY FINISHED. 20mmØ IMC

VARIES ( CHECK HEIGHT )


3. TYPE PF SERVICE ENTRANCE SHALL BE SINGLE PHASE, TWO WIRES, 230 V, 60 HZ.
KILO-WATTHOUR
METER
[ BY MERALCO ]
4. ALL MATERIALS SHALL BE NEW & APPROVED TYPE FOR THE LOCATION AND PURPOSE.
GROUNDING WIRE
IN 15mmØ PVC

5. ALL INSTALLATION SHALL BE CONCEALED FROM BY INSTALLING CONDUCTOR 2 THHN [ BLACK COLOR ] +
21-30mm GRD.[ WHITE COLOR ]
[ BY OWNER ]

1.80m
IN PVC EMBEDDED IN CONCRETE, PARTITION OR CEILING. IN 65mmØ PVC / IMC
GROUNDING WIRE
[ WHITE COLOR ]
[ LOOP AT GRND. ROD ]
NGL
6. MINIMUM SIZE OF CONDUCTOR AND CONDUIT WHEN NOT INDICATED SHALL BE

0.90m
1.6 mm DIA. ( NO. 14 ) AND 15 mm NOMINAL DIA. FOR CONDUIT RESPECTIVELY. EARTHFILL

1.20m
0.30m
TO PANELBOARD "LP"
7. MOUNTING HEIGHT OF DEVICES SHALL BE AS FOLLOWS: LOCATED INSIDE
KITCHEN
10mmØ GROUNDING ROD
3.0m LENGTH
EARTHFILL [ EMBEDDED ]

A. PANEL BOARD - 1.80 m FROM TOP OF PANEL TO FFL


B. WALL SWITCHES - 1.37 m ABOVE FINISH FLR LEVEL
C. CONVENIENCE OUTLET - 0.30 m ABOVE FIN FLOOR LEVEL
0.15 m ABOVE WORKING COUNTER
LEGEND

LIGHTING OUTLET 1 CIRCUIT HOMERUN

FLUORESCENT LIGHT PANEL BOARD


PB
2-GANG CONVENIENCE OUTLET S3way 3-WAY SWITCH

Sa SINGLE SWITCH WH WATER HEATER

Sab 2-GANG SWITCH

GENERAL NOTES AND SPECIFICATIONS:


1. THIS ELECTRICAL INSTALLATIONS SHALL CONFORM WITH THE PROVISION OF THE P.E.C., THE REGULATIONS OF PASIG
AUTHORITIES AND THE REQUIREMENTS OF MERALCO.

2. POWER SUPPLY SHALL BE 230V, 1 PHASE, 2 WIRE, THERE SHALL BE ONLY ONE SERVICE DROP TO THE BUILDING.

3. WIRING SHALL BE IN uPVC, UNLESS NOTED OTHERWISE, WIRES SHALL BE COPPER TYPE THHN MINIMUM SIZE SHALL BE 2.0
SQ.MM.

4. ALL METAL, NON- CURRENT CARRYING PARTS OF THE SYSTEM SHALL BE PROPERLY GROUNDED. A THIRD GROUNDING WIRE
SHALL BE PROVIDED FOR ALL BRANCH CIRCUIT RUNS.

5. ALL MATERIALS TO BE USED SHALL BE THE TYPES APPROVED FOR THE LOCATION AND PURPOSE.

6. THE ELECTRICAL INSTALLATION SHALL BE UNDER THE SUPERVISION OF A REGISTERED ELECTRICAL OR MASTER
ELECTRICIAN.

CERTIFIED BY: PRC No. PROJECT TITLE: APPROVAL: SHEET CONTENT: REVISIONS: SHEET NO.:
VALIDITY

ELECTRICAL ENGINEER/MASTER ELECT'N


PTR No.
ISSUED AT TWO (2) STOREY RESIDENTIAL UNIT
OWNER
AS SHOWN
E
ISSUED ON
TIN
2 2
I CERTIFY THAT THIS WORK WAS PREPARED BY ME
OR DONE UNDER MY DIRECT SUPERVISION LOCATION: PUROK #4, BRGY. MALASIN, AURORA, ISABELA ADDRESS: PUROK #4, BRGY. MALASIN, AURORA, ISABELA NO. DESCRIPTION DATE