Input required for cable sizing
STEPS TO BE FOLLOWED FOR CABLE                                                                   calculations:
     SIZING CALCULATIONS.                                                                             1. Soil thermal resistivity
                                                                                                      2. Short circuit study report
                                                                                                      3. Allowable voltage drops
                                                                                                      4. Cable length
                                                                                                      5. Site conditions (Ambient
                                                                                                      temperature)
                                                                                                      6. Cable installation details
LV CABLE SIZING                                                      HV/MV CABLE SIZING
        1. As per continuous current carrying capacity                       1. As per continuous current carrying capacity
        2. As per allowable voltage drop                                     2. As per allowable voltage drop
        3. Checking of SCPD operation for end of cable fault                  3. Checking of conductor cross-section
                                                                              to withstand the fault current
    Step 1: As per continuous current carrying capacity
    No.of runs required=                            (Load current)
                                ((Cable current carrying capacity) x (Total derating factor))
    a) calculate the load current
    b) find the current carrying capacity of selected cable
    c) calculate the de-rating factor of cable as per installation type
    d) calculate no of runs as per above formula
    Step to calculate the derating factor of cable
    i) Cable running above ground in cable tray
       a) derating factor as per ambient air temperature factor
       b) derating factor as per grouping factor of cable as per no. of cable and no. of trays running together
     Derating factor above ground= a x b
    ii) Cable running below ground in cable trench
       a) derating factor as per ground ambient air temperature factor
       b) derating factor as per cable grouping factor
       c) derating factor as per cable depth of laying factor
       d) derating factor as per soil thermal resistivity
     Derating factor below ground = a x b x c x d
    Step 2: As per allowable voltage drop:
    check the voltage drop as per design basis / standard and ensure that running and starting voltage drop is less than
    allowable voltage drop:
    Voltage Drop=       3× I x L x (( R Ccos ) + (X sin ))
                                  N×1000
    Where,
    I =Full load current (Amp)
    cosΦ =power factor
    R =Cable resistance (Ohm/km)
    X =Cable reactance (Ohm/km)
    L = Cable length (metre)
    N = No. of cable runs
    Step 3: Checking of conductor cross-section to withstand the fault current
    Calculate the conductor cross-section to withstand the fault current as per below formula
                    S= (I       t)
                            k
    Where,
    S = Cross-sectional area, in mm2
    I = Prospective fault current for a fault of negligible impedance in Ampere
    t = Operating time of protective device for automatic disconnection, in second
    k = Factor dependent on the material of the conductor