Duplex submersible Waste Water pumps SP-02-01, 02
1-Flow Capacity Calculation:
Fixture name Quantity Drainage Fixture
Unit
“DFU”
Floor Drain 10 2
Lavatory 16 2
WC Flush Tank type 12 4
Urinal 4 2
Total Drainage Fixture Units: 108 DFU
Total Fixture Drainage Flow: 46 gpm
see attached ASPE Handbook and Uniform Plumbing Code
Flow required = Fixture Drain Flow = 108 = 46 gpm
Where The Design inflow is 50 GPM is safe
The flow Capacity 50 GPM
2- Head Calculation:
H “static” = 6.5 m = 22 ft.
H “Friction” =
Length of Run from pump to inspection chamber “ft.” X friction loss factor X F1 X F2
Where, F1 (30 % Safety Factor for fittings) & F2 (10% safety Factor for unforeseen Accessories)
= 35 ft. X (2 ft. / 100 ft.) X 1.3 X 1.1 = 1 ft.
Total Head = H static + H Friction = 22+1 =23 ft. = 23 ft. / 2.31 = 10 psi
Where The Design Head is 30 psi is safe
The Pump Head 30 psi
Duplex submersible Waste Water pumps SP-02-01, 02
3- Sump pit Sizing Calculation:
50 GPM flow Required Capacity. “See attached shop Drawing”
Minimum 2.5 minutes of pump capacity between high and low water level will
provide satisfactory pump cycling. “See attached ASPE Design reference”
Design Area 1500 x 1500 mm = 2.25 m2 = 24.2 ft2
V (volume (gallon)) = Q (flow rate (gpm) X t (time (min))
Volume = 50 X 2.5 = 125 gallon =16.7 ft3
Effective area = 1.5 m X 1.5 m= 2.25 m2 = 24.2 ft2
Effective depth between high level and low level
= Volume / Effective area = 16.7 ft3 / 24.2 ft2 = 0.69 ft. =21 cm
the high water level should be maintained at least 3”= 7.5 cm below the invert of
the entering pipe
the low level should be maintained at least 12” to 18” above the bottom of the
Basin use 12” = 30 cm as per the manufacturer recommendation “attached”
10 cm for the second pump start above the effective depth
invert level for the entering pipe from finish floor level = 97 cm
“See attached ASPE Design reference”
Total required depth = 21 cm +7.5 cm + 30 cm +10 cm + 97 cm =165.5cm
The Design Depth 200 cm is safe
Sump pump Basin Dimension 1500 mm X 1500 mm x 2000 mm is OK