Sump Pit Calculation

The document outlines the calculations for flow capacity, head, and sump pit sizing for duplex submersible wastewater pumps SP-02-01 and 02, indicating a total drainage fixture unit of 108 DFU and a required flow capacity of 50 GPM. The total head calculated is 30 psi, and the sump pit is designed to accommodate a minimum depth of 200 cm, ensuring proper pump cycling and operation. All calculations reference attached ASPE Handbook and Uniform Plumbing Code for compliance.

Uploaded by

M Mostafa Edris
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
53 views2 pages

Sump Pit Calculation

The document outlines the calculations for flow capacity, head, and sump pit sizing for duplex submersible wastewater pumps SP-02-01 and 02, indicating a total drainage fixture unit of 108 DFU and a required flow capacity of 50 GPM. The total head calculated is 30 psi, and the sump pit is designed to accommodate a minimum depth of 200 cm, ensuring proper pump cycling and operation. All calculations reference attached ASPE Handbook and Uniform Plumbing Code for compliance.

Uploaded by

M Mostafa Edris
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Duplex submersible Waste Water pumps SP-02-01, 02

1-Flow Capacity Calculation:


Fixture name Quantity Drainage Fixture
Unit
“DFU”

Floor Drain 10 2

Lavatory 16 2

WC Flush Tank type 12 4

Urinal 4 2

Total Drainage Fixture Units: 108 DFU


Total Fixture Drainage Flow: 46 gpm

 see attached ASPE Handbook and Uniform Plumbing Code

Flow required = Fixture Drain Flow = 108 = 46 gpm

Where The Design inflow is 50 GPM is safe


The flow Capacity 50 GPM
2- Head Calculation:
H “static” = 6.5 m = 22 ft.
H “Friction” =
Length of Run from pump to inspection chamber “ft.” X friction loss factor X F1 X F2
Where, F1 (30 % Safety Factor for fittings) & F2 (10% safety Factor for unforeseen Accessories)

= 35 ft. X (2 ft. / 100 ft.) X 1.3 X 1.1 = 1 ft.

Total Head = H static + H Friction = 22+1 =23 ft. = 23 ft. / 2.31 = 10 psi

Where The Design Head is 30 psi is safe


The Pump Head 30 psi
Duplex submersible Waste Water pumps SP-02-01, 02

3- Sump pit Sizing Calculation:


 50 GPM flow Required Capacity. “See attached shop Drawing”

 Minimum 2.5 minutes of pump capacity between high and low water level will
provide satisfactory pump cycling. “See attached ASPE Design reference”

 Design Area 1500 x 1500 mm = 2.25 m2 = 24.2 ft2

V (volume (gallon)) = Q (flow rate (gpm) X t (time (min))


Volume = 50 X 2.5 = 125 gallon =16.7 ft3
Effective area = 1.5 m X 1.5 m= 2.25 m2 = 24.2 ft2
Effective depth between high level and low level
= Volume / Effective area = 16.7 ft3 / 24.2 ft2 = 0.69 ft. =21 cm

 the high water level should be maintained at least 3”= 7.5 cm below the invert of
the entering pipe
 the low level should be maintained at least 12” to 18” above the bottom of the
Basin use 12” = 30 cm as per the manufacturer recommendation “attached”

 10 cm for the second pump start above the effective depth

 invert level for the entering pipe from finish floor level = 97 cm

“See attached ASPE Design reference”

 Total required depth = 21 cm +7.5 cm + 30 cm +10 cm + 97 cm =165.5cm

The Design Depth 200 cm is safe

Sump pump Basin Dimension 1500 mm X 1500 mm x 2000 mm is OK