El 1262 en
El 1262 en
EL1262
Digital Input Terminal with oversampling
Table of contents
1 Foreword .................................................................................................................................................... 5
1.1 Notes on the documentation.............................................................................................................. 5
1.2 Safety instructions ............................................................................................................................. 6
1.3 Documentation issue status .............................................................................................................. 7
1.4 Version identification of EtherCAT devices ....................................................................................... 7
1.4.1 Beckhoff Identification Code (BIC)................................................................................... 12
2 Product overview..................................................................................................................................... 14
2.1 EL1262 - Introduction ...................................................................................................................... 14
2.2 EL1262 - Technical data.................................................................................................................. 16
2.3 Technology ...................................................................................................................................... 17
2.4 Start ................................................................................................................................................. 17
5 Commissioning........................................................................................................................................ 47
5.1 TwinCAT Quick Start ....................................................................................................................... 47
5.1.1 TwinCAT 2 ....................................................................................................................... 50
5.1.2 TwinCAT 3 ....................................................................................................................... 60
5.2 TwinCAT Development Environment .............................................................................................. 73
5.2.1 Installation of the TwinCAT real-time driver..................................................................... 74
5.2.2 Notes regarding ESI device description........................................................................... 79
5.2.3 TwinCAT ESI Updater ..................................................................................................... 83
5.2.4 Distinction between Online and Offline............................................................................ 83
5.2.5 OFFLINE configuration creation ...................................................................................... 84
5.2.6 ONLINE configuration creation ........................................................................................ 89
5.2.7 EtherCAT subscriber configuration.................................................................................. 97
5.3 General Notes - EtherCAT Slave Application ................................................................................ 106
5.4 Oversampling terminals/boxes and TwinCAT Scope .................................................................... 114
1 Foreword
This description is only intended for the use of trained specialists in control and automation engineering who
are familiar with the applicable national standards.
It is essential that the documentation and the following notes and explanations are followed when installing
and commissioning these components.
It is the duty of the technical personnel to use the documentation published at the respective time of each
installation and commissioning.
The responsible staff must ensure that the application or use of the products described satisfy all the
requirements for safety, including all the relevant laws, regulations, guidelines and standards.
Disclaimer
The documentation has been prepared with care. The products described are, however, constantly under
development.
We reserve the right to revise and change the documentation at any time and without prior announcement.
No claims for the modification of products that have already been supplied may be made on the basis of the
data, diagrams and descriptions in this documentation.
Trademarks
Beckhoff®, TwinCAT®, EtherCAT®, EtherCAT G®, EtherCAT G10®, EtherCAT P®, Safety over EtherCAT®,
TwinSAFE®, XFC®, XTS® and XPlanar® are registered trademarks of and licensed by Beckhoff Automation
GmbH. Other designations used in this publication may be trademarks whose use by third parties for their
own purposes could violate the rights of the owners.
Patent Pending
The EtherCAT Technology is covered, including but not limited to the following patent applications and
patents: EP1590927, EP1789857, EP1456722, EP2137893, DE102015105702 with corresponding
applications or registrations in various other countries.
EtherCAT® is registered trademark and patented technology, licensed by Beckhoff Automation GmbH,
Germany.
Copyright
Exclusion of liability
All the components are supplied in particular hardware and software configurations appropriate for the
application. Modifications to hardware or software configurations other than those described in the
documentation are not permitted, and nullify the liability of Beckhoff Automation GmbH & Co. KG.
Personnel qualification
This description is only intended for trained specialists in control, automation and drive engineering who are
familiar with the applicable national standards.
Description of instructions
DANGER
Serious risk of injury!
Failure to follow this safety instruction directly endangers the life and health of persons.
WARNING
Risk of injury!
Failure to follow this safety instruction endangers the life and health of persons.
CAUTION
Personal injuries!
Failure to follow this safety instruction can lead to injuries to persons.
NOTE
Damage to environment/equipment or data loss
Failure to follow this instruction can lead to environmental damage, equipment damage or data loss.
Tip or pointer
This symbol indicates information that contributes to better understanding.
Notes
• The elements mentioned above result in the technical designation. EL3314-0000-0016 is used in the
example below.
• EL3314-0000 is the order identifier, in the case of “-0000” usually abbreviated to EL3314. “-0016” is the
EtherCAT revision.
• The order identifier is made up of
- family key (EL, EP, CU, ES, KL, CX, etc.)
- type (3314)
- version (-0000)
• The revision -0016 shows the technical progress, such as the extension of features with regard to the
EtherCAT communication, and is managed by Beckhoff.
In principle, a device with a higher revision can replace a device with a lower revision, unless specified
otherwise, e.g. in the documentation.
Associated and synonymous with each revision there is usually a description (ESI, EtherCAT Slave
Information) in the form of an XML file, which is available for download from the Beckhoff web site.
From 2014/01 the revision is shown on the outside of the IP20 terminals, see Fig. “EL5021 EL terminal,
standard IP20 IO device with batch number and revision ID (since 2014/01)”.
• The type, version and revision are read as decimal numbers, even if they are technically saved in
hexadecimal.
Identification number
Beckhoff EtherCAT devices from the different lines have different kinds of identification numbers:
The serial number for Beckhoff IO devices is usually the 8-digit number printed on the device or on a sticker.
The serial number indicates the configuration in delivery state and therefore refers to a whole production
batch, without distinguishing the individual modules of a batch.
Example with
Ser. no.: 12063A02: 12 - production week 12 06 - production year 2006 3A - firmware version 3A 02 -
hardware version 02
Exceptions can occur in the IP67 area, where the following syntax can be used (see respective device
documentation):
Syntax: D ww yy x y z u
D - prefix designation
ww - calendar week
yy - year
x - firmware version of the bus PCB
Example: D.22081501 calendar week 22 of the year 2008 firmware version of bus PCB: 1 hardware version
of bus PCB: 5 firmware version of I/O PCB: 0 (no firmware necessary for this PCB) hardware version of I/O
PCB: 1
In addition, in some series each individual module has its own unique serial number.
Examples of markings
Fig. 1: EL5021 EL terminal, standard IP20 IO device with serial/ batch number and revision ID (since
2014/01)
Fig. 2: EK1100 EtherCAT coupler, standard IP20 IO device with serial/ batch number
Fig. 4: EL3202-0020 with serial/ batch number 26131006 and unique ID-number 204418
Fig. 5: EP1258-00001 IP67 EtherCAT Box with batch number/ date code 22090101 and unique serial
number 158102
Fig. 6: EP1908-0002 IP67 EtherCAT Safety Box with batch number/ date code 071201FF and unique serial
number 00346070
Fig. 7: EL2904 IP20 safety terminal with batch number/ date code 50110302 and unique serial number
00331701
Fig. 8: ELM3604-0002 terminal with unique ID number (QR code) 100001051 and serial/ batch number
44160201
The BIC will be introduced step by step across all product groups.
The BIC is machine-readable and contains information that can also be used by the customer for handling
and product management.
Each piece of information can be uniquely identified using the so-called data identifier
(ANSI MH10.8.2-2016). The data identifier is followed by a character string. Both together have a maximum
length according to the table below. If the information is shorter, spaces are added to it. The data under
positions 1 to 4 are always available.
Further types of information and data identifiers are used by Beckhoff and serve internal processes.
Example of composite information from item 1 to 4 and 6. The data identifiers are marked in red for better
display:
BTN
An important component of the BIC is the Beckhoff Traceability Number (BTN, item no. 2). The BTN is a
unique serial number consisting of eight characters that will replace all other serial number systems at
Beckhoff in the long term (e.g. batch designations on IO components, previous serial number range for
safety products, etc.). The BTN will also be introduced step by step, so it may happen that the BTN is not yet
coded in the BIC.
NOTE
This information has been carefully prepared. However, the procedure described is constantly being further
developed. We reserve the right to revise and change procedures and documentation at any time and with-
out prior notice. No claims for changes can be made from the information, illustrations and descriptions in
this information.
2 Product overview
The EL1262 digital input terminal acquires the fast binary control signals from the process level and
transmits them, in an electrically isolated form, to the controller. The signals are sampled with a configurable,
integer multiple (oversampling factor: n) of the bus cycle time (n microcycles per bus cycle). For each
microcycle, the EtherCAT Terminal generates a process data block that is transferred collectively during the
next bus cycle. The time base of the terminal can be synchronized precisely with other EtherCAT devices via
distributed clocks. This procedure enables the temporal resolution of the acquisition of the digital input
signals to be increased to n times the bus cycle time.
The EL1262-0050 offers a version with 5 V input voltage (TTL level) and 5 V supply voltage.
Quick links
Electrical supply
The fast input circuits of the EL1262-xxxx are supplied via the power contacts. Please note that the
EL1262-0050 can only be operated with a 5 V supply voltage! If necessary, use a EL9505 power
supply terminal for supplying the EL1262-0050.
2.3 Technology
Functioning
The EL1262 is a digital input terminal with two channels. It can read the voltage level not only cyclically with
the EtherCAT cycle, but also several times in between based on distributed clock support of the EL1262. In
the EL1262 the ESC (EtherCAT slave controller) handles the data communication to the EtherCAT fieldbus
and supports the distributed clock functionality. This enables the ESC to read the inputs of the EL1262
cyclically and equidistantly with high precision and store the values in the memory. When the EtherCAT
frame fetches the data from the EL1262, a whole set of process data is ready for transfer. The inputs can be
sampled with significantly higher frequency than the fieldbus cycle. Hence the term oversampling.
Further information on commissioning can be found in section “Basic function principles [} 132]”
2.4 Start
For commissioning:
• mount the EL12xx as described in the section Mounting and wiring [} 29]
• configure the EL12xx in TwinCAT as described in the section Commissioning [} 47].
3 Basics communication
For connecting EtherCAT devices only Ethernet connections (cables + plugs) that meet the requirements of
at least category 5 (CAt5) according to EN 50173 or ISO/IEC 11801 should be used. EtherCAT uses 4 wires
for signal transfer.
EtherCAT uses RJ45 plug connectors, for example. The pin assignment is compatible with the Ethernet
standard (ISO/IEC 8802-3).
Pin Color of conductor Signal Description
1 yellow TD + Transmission Data +
2 orange TD - Transmission Data -
3 white RD + Receiver Data +
6 blue RD - Receiver Data -
Due to automatic cable detection (auto-crossing) symmetric (1:1) or cross-over cables can be used between
EtherCAT devices from Beckhoff.
Recommended cables
It is recommended to use the appropriate Beckhoff components e.g.
- cable sets ZK1090-9191-xxxx respectively
- RJ45 connector, field assembly ZS1090-0005
- EtherCAT cable, field assembly ZB9010, ZB9020
Suitable cables for the connection of EtherCAT devices can be found on the Beckhoff website!
E-Bus supply
A bus coupler can supply the EL terminals added to it with the E-bus system voltage of 5 V; a coupler is
thereby loadable up to 2 A as a rule (see details in respective device documentation).
Information on how much current each EL terminal requires from the E-bus supply is available online and in
the catalogue. If the added terminals require more current than the coupler can supply, then power feed
terminals (e.g. EL9410) must be inserted at appropriate places in the terminal strand.
The pre-calculated theoretical maximum E-Bus current is displayed in the TwinCAT System Manager. A
shortfall is marked by a negative total amount and an exclamation mark; a power feed terminal is to be
placed before such a position.
NOTE
Malfunction possible!
The same ground potential must be used for the E-Bus supply of all EtherCAT terminals in a terminal block!
The EtherCAT slave controller (ESC) in the EL2xxx terminals features two watchdogs:
• SM watchdog (default: 100 ms)
• PDI watchdog (default: 100 ms)
The SyncManager watchdog is reset after each successful EtherCAT process data communication with the
terminal. If no EtherCAT process data communication takes place with the terminal for longer than the set
and activated SM watchdog time, e.g. in the event of a line interruption, the watchdog is triggered and the
outputs are set to FALSE. The OP state of the terminal is unaffected. The watchdog is only reset after a
successful EtherCAT process data access. Set the monitoring time as described below.
The SyncManager watchdog monitors correct and timely process data communication with the ESC from the
EtherCAT side.
If no PDI communication with the EtherCAT slave controller (ESC) takes place for longer than the set and
activated PDI watchdog time, this watchdog is triggered.
PDI (Process Data Interface) is the internal interface between the ESC and local processors in the EtherCAT
slave, for example. The PDI watchdog can be used to monitor this communication for failure.
The PDI watchdog monitors correct and timely process data communication with the ESC from the
application side.
The settings of the SM- and PDI-watchdog must be done for each slave separately in the TwinCAT System
Manager.
Fig. 13: EtherCAT tab -> Advanced Settings -> Behavior -> Watchdog
Notes:
• the multiplier is valid for both watchdogs.
• each watchdog has its own timer setting, the outcome of this in summary with the multiplier is a
resulting time.
• Important: the multiplier/timer setting is only loaded into the slave at the start up, if the checkbox is
activated.
If the checkbox is not activated, nothing is downloaded and the ESC settings remain unchanged.
Multiplier
Multiplier
Both watchdogs receive their pulses from the local terminal cycle, divided by the watchdog multiplier:
1/25 MHz * (watchdog multiplier + 2) = 100 µs (for default setting of 2498 for the multiplier)
The standard setting of 1000 for the SM watchdog corresponds to a release time of 100 ms.
The value in multiplier + 2 corresponds to the number of basic 40 ns ticks representing a watchdog tick.
The multiplier can be modified in order to adjust the watchdog time over a larger range.
This checkbox enables manual setting of the watchdog times. If the outputs are set and the EtherCAT
communication is interrupted, the SM watchdog is triggered after the set time and the outputs are erased.
This setting can be used for adapting a terminal to a slower EtherCAT master or long cycle times. The
default SM watchdog setting is 100 ms. The setting range is 0...65535. Together with a multiplier with a
range of 1...65535 this covers a watchdog period between 0...~170 seconds.
Calculation
Multiplier = 2498 → watchdog base time = 1 / 25 MHz * (2498 + 2) = 0.0001 seconds = 100 µs
SM watchdog = 10000 → 10000 * 100 µs = 1 second watchdog monitoring time
CAUTION
Undefined state possible!
The function for switching off of the SM watchdog via SM watchdog = 0 is only implemented in terminals
from version -0016. In previous versions this operating mode should not be used.
CAUTION
Damage of devices and undefined state possible!
If the SM watchdog is activated and a value of 0 is entered the watchdog switches off completely. This is
the deactivation of the watchdog! Set outputs are NOT set in a safe state, if the communication is inter-
rupted.
The regular state of each EtherCAT slave after bootup is the OP state.
Init
After switch-on the EtherCAT slave in the Init state. No mailbox or process data communication is possible.
The EtherCAT master initializes sync manager channels 0 and 1 for mailbox communication.
Pre-Operational (Pre-Op)
During the transition between Init and Pre-Op the EtherCAT slave checks whether the mailbox was initialized
correctly.
In Pre-Op state mailbox communication is possible, but not process data communication. The EtherCAT
master initializes the sync manager channels for process data (from sync manager channel 2), the FMMU
channels and, if the slave supports configurable mapping, PDO mapping or the sync manager PDO
assignment. In this state the settings for the process data transfer and perhaps terminal-specific parameters
that may differ from the default settings are also transferred.
Safe-Operational (Safe-Op)
During transition between Pre-Op and Safe-Op the EtherCAT slave checks whether the sync manager
channels for process data communication and, if required, the distributed clocks settings are correct. Before
it acknowledges the change of state, the EtherCAT slave copies current input data into the associated DP-
RAM areas of the EtherCAT slave controller (ECSC).
In Safe-Op state mailbox and process data communication is possible, although the slave keeps its outputs
in a safe state, while the input data are updated cyclically.
Operational (Op)
Before the EtherCAT master switches the EtherCAT slave from Safe-Op to Op it must transfer valid output
data.
In the Op state the slave copies the output data of the masters to its outputs. Process data and mailbox
communication is possible.
Boot
In the Boot state the slave firmware can be updated. The Boot state can only be reached via the Init state.
In the Boot state mailbox communication via the file access over EtherCAT (FoE) protocol is possible, but no
other mailbox communication and no process data communication.
The CoE interface (CAN application protocol over EtherCAT)) is used for parameter management of
EtherCAT devices. EtherCAT slaves or the EtherCAT master manage fixed (read only) or variable
parameters which they require for operation, diagnostics or commissioning.
CoE parameters are arranged in a table hierarchy. In principle, the user has read access via the fieldbus.
The EtherCAT master (TwinCAT System Manager) can access the local CoE lists of the slaves via
EtherCAT in read or write mode, depending on the attributes.
Different CoE parameter types are possible, including string (text), integer numbers, Boolean values or larger
byte fields. They can be used to describe a wide range of features. Examples of such parameters include
manufacturer ID, serial number, process data settings, device name, calibration values for analog
measurement or passwords.
The order is specified in two levels via hexadecimal numbering: (main)index, followed by subindex. The
value ranges are
• Index: 0x0000 …0xFFFF (0...65535dez)
• SubIndex: 0x00…0xFF (0...255dez)
A parameter localized in this way is normally written as 0x8010:07, with preceding “0x” to identify the
hexadecimal numerical range and a colon between index and subindex.
Availability
Not every EtherCAT device must have a CoE list. Simple I/O modules without dedicated processor
usually have no variable parameters and therefore no CoE list.
If a device has a CoE list, it is shown in the TwinCAT System Manager as a separate tab with a listing of the
elements:
The figure above shows the CoE objects available in device “EL2502”, ranging from 0x1000 to 0x1600. The
subindices for 0x1018 are expanded.
Some parameters, particularly the setting parameters of the slave, are configurable and writeable. This can
be done in write or read mode
• via the System Manager (Fig. “CoE Online” tab) by clicking
This is useful for commissioning of the system/slaves. Click on the row of the index to be
parameterized and enter a value in the “SetValue” dialog.
• from the control system/PLC via ADS, e.g. through blocks from the TcEtherCAT.lib library
This is recommended for modifications while the system is running or if no System Manager or
operating staff are available.
Data management
If slave CoE parameters are modified online, Beckhoff devices store any changes in a fail-safe
manner in the EEPROM, i.e. the modified CoE parameters are still available after a restart.
The situation may be different with other manufacturers.
An EEPROM is subject to a limited lifetime with respect to write operations. From typically 100,000
write operations onwards it can no longer be guaranteed that new (changed) data are reliably saved
or are still readable. This is irrelevant for normal commissioning. However, if CoE parameters are
continuously changed via ADS at machine runtime, it is quite possible for the lifetime limit to be
reached. Support for the NoCoeStorage function, which suppresses the saving of changed CoE val-
ues, depends on the firmware version.
Please refer to the technical data in this documentation as to whether this applies to the respective
device.
• If the function is supported: the function is activated by entering the code word 0x12345678 once
in CoE 0xF008 and remains active as long as the code word is not changed. After switching the
device on it is then inactive. Changed CoE values are not saved in the EEPROM and can thus
be changed any number of times.
• Function is not supported: continuous changing of CoE values is not permissible in view of the
lifetime limit.
Startup list
Changes in the local CoE list of the terminal are lost if the terminal is replaced. If a terminal is re-
placed with a new Beckhoff terminal, it will have the default settings. It is therefore advisable to link
all changes in the CoE list of an EtherCAT slave with the Startup list of the slave, which is pro-
cessed whenever the EtherCAT fieldbus is started. In this way a replacement EtherCAT slave can
automatically be parameterized with the specifications of the user.
If EtherCAT slaves are used which are unable to store local CoE values permanently, the Startup
list must be used.
The Startup list may already contain values that were configured by the System Manager based on the ESI
specifications. Additional application-specific entries can be created.
Online/offline list
While working with the TwinCAT System Manager, a distinction has to be made whether the EtherCAT
device is “available”, i.e. switched on and linked via EtherCAT and therefore online, or whether a
configuration is created offline without connected slaves.
In both cases a CoE list as shown in Fig. “CoE online tab” is displayed. The connectivity is shown as offline/
online.
• If the slave is offline
◦ The offline list from the ESI file is displayed. In this case modifications are not meaningful or
possible.
◦ The configured status is shown under Identity.
◦ No firmware or hardware version is displayed, since these are features of the physical device.
◦ Offline is shown in red.
Channel-based order
The CoE list is available in EtherCAT devices that usually feature several functionally equivalent channels.
For example, a 4-channel analog 0...10 V input terminal also has four logical channels and therefore four
identical sets of parameter data for the channels. In order to avoid having to list each channel in the
documentation, the placeholder “n” tends to be used for the individual channel numbers.
In the CoE system 16 indices, each with 255 subindices, are generally sufficient for representing all channel
parameters. The channel-based order is therefore arranged in 16dec/10hex steps. The parameter range
0x8000 exemplifies this:
• Channel 0: parameter range 0x8000:00 ... 0x800F:255
• Channel 1: parameter range 0x8010:00 ... 0x801F:255
• Channel 2: parameter range 0x8020:00 ... 0x802F:255
• ...
Detailed information on the CoE interface can be found in the EtherCAT system documentation on the
Beckhoff website.
Assembly
The bus coupler and bus terminals are attached to commercially available 35 mm mounting rails (DIN rails
according to EN 60715) by applying slight pressure:
Disassembly
Each terminal is secured by a lock on the mounting rail, which must be released for disassembly:
1. Pull the terminal by its orange-colored lugs approximately 1 cm away from the mounting rail. In doing
so for this terminal the mounting rail lock is released automatically and you can pull the terminal out of
the bus terminal block easily without excessive force.
2. Grasp the released terminal with thumb and index finger simultaneous at the upper and lower grooved
housing surfaces and pull the terminal out of the bus terminal block.
The electric connections between the Bus Coupler and the Bus Terminals are automatically realized by
joining the components:
• The six spring contacts of the K-Bus/E-Bus deal with the transfer of the data and the supply of the Bus
Terminal electronics.
• The power contacts deal with the supply for the field electronics and thus represent a supply rail within
the bus terminal block. The power contacts are supplied via terminals on the Bus Coupler (up to 24 V)
or for higher voltages via power feed terminals.
Power Contacts
During the design of a bus terminal block, the pin assignment of the individual Bus Terminals must
be taken account of, since some types (e.g. analog Bus Terminals or digital 4-channel Bus Termi-
nals) do not or not fully loop through the power contacts. Power Feed Terminals (KL91xx, KL92xx
or EL91xx, EL92xx) interrupt the power contacts and thus represent the start of a new supply rail.
PE power contact
The power contact labeled PE can be used as a protective earth. For safety reasons this contact mates first
when plugging together, and can ground short-circuit currents of up to 125 A.
NOTE
Possible damage of the device
Note that, for reasons of electromagnetic compatibility, the PE contacts are capacitatively coupled to the
mounting rail. This may lead to incorrect results during insulation testing or to damage on the terminal (e.g.
disruptive discharge to the PE line during insulation testing of a consumer with a nominal voltage of 230 V).
For insulation testing, disconnect the PE supply line at the Bus Coupler or the Power Feed Terminal! In or-
der to decouple further feed points for testing, these Power Feed Terminals can be released and pulled at
least 10 mm from the group of terminals.
WARNING
Risk of electric shock!
The PE power contact must not be used for other potentials!
Additional checks
For terminals with enhanced mechanical load capacity, the following additional installation instructions apply:
• The enhanced mechanical load capacity is valid for all permissible installation positions
• Use a mounting rail according to EN 60715 TH35-15
• Fix the terminal segment on both sides of the mounting rail with a mechanical fixture, e.g. an earth
terminal or reinforced end clamp
• The maximum total extension of the terminal segment (without coupler) is:
64 terminals (12 mm mounting with) or 32 terminals (24 mm mounting with)
• Avoid deformation, twisting, crushing and bending of the mounting rail during edging and installation of
the rail
• The mounting points of the mounting rail must be set at 5 cm intervals
• Use countersunk head screws to fasten the mounting rail
• The free length between the strain relief and the wire connection should be kept as short as possible. A
distance of approx. 10 cm should be maintained to the cable duct.
Overview
The Bus Terminal system offers different connection options for optimum adaptation to the respective
application:
• The terminals of KLxxxx and ELxxxx series with standard wiring include electronics and connection
level in a single enclosure.
• The terminals of KSxxxx and ESxxxx series feature a pluggable connection level and enable steady
wiring while replacing.
• The High Density Terminals (HD Terminals) include electronics and connection level in a single
enclosure and have advanced packaging density.
Standard wiring
The terminals of KLxxxx and ELxxxx series have been tried and tested for years.
They feature integrated screwless spring force technology for fast and simple assembly.
Pluggable wiring
The terminals of KSxxxx and ESxxxx series feature a pluggable connection level.
The assembly and wiring procedure for the KS series is the same as for the KLxxxx and ELxxxx series.
The KS/ES series terminals enable the complete wiring to be removed as a plug connector from the top of
the housing for servicing.
The lower section can be removed from the terminal block by pulling the unlocking tab.
Insert the new component and plug in the connector with the wiring. This reduces the installation time and
eliminates the risk of wires being mixed up.
The familiar dimensions of the terminal only had to be changed slightly. The new connector adds about 3
mm. The maximum height of the terminal remains unchanged.
A tab for strain relief of the cable simplifies assembly in many applications and prevents tangling of individual
connection wires when the connector is removed.
Conductor cross sections between 0.08 mm2 and 2.5 mm2 can continue to be used with the proven spring
force technology.
The overview and nomenclature of the product names for KSxxxx and ESxxxx series has been retained as
known from KLxxxx and ELxxxx series.
The Bus Terminals from these series with 16 connection points are distinguished by a particularly compact
design, as the packaging density is twice as large as that of the standard 12 mm Bus Terminals. Massive
conductors and conductors with a wire end sleeve can be inserted directly into the spring loaded terminal
point without tools.
Wiring HD Terminals
The High Density Terminals of the KLx8xx and ELx8xx series doesn't support steady wiring.
Wiring
Terminals for standard wiring ELxxxx/KLxxxx and for pluggable wiring ESxxxx/KSxxxx
Up to eight connections enable the connection of solid or finely stranded cables to the Bus Terminals. The
terminals are implemented in spring force technology. Connect the cables as follows:
1. Open a spring-loaded terminal by slightly pushing with a screwdriver or a rod into the square opening
above the terminal.
2. The wire can now be inserted into the round terminal opening without any force.
3. The terminal closes automatically when the pressure is released, holding the wire securely and per-
manently.
The conductors of the HD Terminals are connected without tools for single-wire conductors using the direct
plug-in technique, i.e. after stripping the wire is simply plugged into the contact point. The cables are
released, as usual, using the contact release with the aid of a screwdriver. See the following table for the
suitable wire size width.
Shielding
Shielding
Analog sensors and actors should always be connected with shielded, twisted paired wires.
The optimum installation position requires the mounting rail to be installed horizontally and the connection
surfaces of the EL/KL terminals to face forward (see Fig. Recommended distances for standard installation
position). The terminals are ventilated from below, which enables optimum cooling of the electronics through
convection. “From below” is relative to the acceleration of gravity.
Compliance with the distances shown in Fig. Recommended distances for standard installation position is
recommended.
All other installation positions are characterized by different spatial arrangement of the mounting rail - see
Fig Other installation positions.
The minimum distances to ambient specified above also apply to these installation positions.
Standards
The fundamental health and safety requirements are fulfilled by compliance with the following standards:
• EN 60079-0:2012+A11:2013
• EN 60079-15:2010
• EN 60079-31:2013 (only for certificate no. KEMA 10ATEX0075 X Issue 9)
Marking
The Beckhoff fieldbus components with standard temperature range certified according to the ATEX directive
for potentially explosive areas bear one of the following markings:
or
Notes on the use of the Beckhoff terminal systems in hazardous areas according to ATEX and
IECEx
4.9 UL notice
Application
Beckhoff EtherCAT modules are intended for use with Beckhoff’s UL Listed EtherCAT Sys-
tem only.
Examination
For cULus examination, the Beckhoff I/O System has only been investigated for risk of fire
and electrical shock (in accordance with UL508 and CSA C22.2 No. 142).
Basic principles
UL certification according to UL508. Devices with this kind of certification are marked by this sign:
LEDs
EL1262-0050
NOTE
Be sure the correct supply voltage is used!
The EL1262-0050 can only be operated with a 5 V supply voltage! The terminal will not work in a terminal
network with a 24 V supply voltage at the power contacts! If necessary, use a EL9505 power supply terminal
for supplying the EL1262-0050.
LEDs
5 Commissioning
Devices contain the terminals for the actual configuration. All configuration data can be entered directly via
editor functions (offline) or via the “Scan” function (online):
• “offline”: The configuration can be customized by adding and positioning individual components.
These can be selected from a directory and configured.
◦ The procedure for offline mode can be found under http://infosys.beckhoff.com:
TwinCAT 2 → TwinCAT System Manager → IO - Configuration → Adding an I/O Device
• “online”: The existing hardware configuration is read
◦ See also http://infosys.beckhoff.com:
Fieldbus components → Fieldbus cards and switches → FC900x – PCI Cards for Ethernet →
Installation → Searching for devices
The following relationship is envisaged from user PC to the individual control elements:
The user inserting of certain components (I/O device, terminal, box...) is the same in TwinCAT 2 and
TwinCAT 3. The descriptions below relate to the online procedure.
Based on the following sample configuration, the subsequent subsections describe the procedure for
TwinCAT 2 and TwinCAT 3:
• Control system (PLC) CX2040 including CX2100-0004 power supply unit
• Connected to the CX2040 on the right (E-bus):
EL1004 (4-channel digital input terminal 24 VDC)
• Linked via the X001 port (RJ-45): EK1100 EtherCAT Coupler
• Connected to the EK1100 EtherCAT coupler on the right (E-bus):
EL2008 (8-channel digital output terminal 24 VDC; 0.5 A)
• (Optional via X000: a link to an external PC for the user interface)
Fig. 34: Control configuration with Embedded PC, input (EL1004) and output (EL2008)
Note that all combinations of a configuration are possible; for example, the EL1004 terminal could also be
connected after the coupler, or the EL2008 terminal could additionally be connected to the CX2040 on the
right, in which case the EK1100 coupler wouldn’t be necessary.
5.1.1 TwinCAT 2
Startup
TwinCAT basically uses two user interfaces: the TwinCAT System Manager for communication with the
electromechanical components and TwinCAT PLC Control for the development and compilation of a
controller. The starting point is the TwinCAT System Manager.
After successful installation of the TwinCAT system on the PC to be used for development, the TwinCAT 2
System Manager displays the following user interface after startup:
Generally, TwinCAT can be used in local or remote mode. Once the TwinCAT system including the user
interface (standard) is installed on the respective PLC, TwinCAT can be used in local mode and thereby the
next step is “Insert Device [} 52]”.
If the intention is to address the TwinCAT runtime environment installed on a PLC as development
environment remotely from another system, the target system must be made known first. In the menu under
“Actions” → “Choose Target System...”, via the symbol “ ” or the “F8” key, open the following window:
Use “Search (Ethernet)...” to enter the target system. Thus a next dialog opens to either:
• enter the known computer name after “Enter Host Name / IP:” (as shown in red)
• perform a “Broadcast Search” (if the exact computer name is not known)
• enter the known computer IP or AmsNetID.
Fig. 37: Specify the PLC for access by the TwinCAT System Manager: selection of the target system
Once the target system has been entered, it is available for selection as follows (a password may have to be
entered):
After confirmation with “OK” the target system can be accessed via the System Manager.
Adding devices
In the configuration tree of the TwinCAT 2 System Manager user interface on the left, select “I/O Devices”
and then right-click to open a context menu and select “Scan Devices…”, or start the action in the menu bar
via . The TwinCAT System Manager may first have to be set to “Config mode” via or via menu
“Actions” → “Set/Reset TwinCAT to Config Mode…” (Shift + F4).
Confirm the warning message, which follows, and select “EtherCAT” in the dialog:
Fig. 39: Automatic detection of I/O devices: selection the devices to be integrated
Confirm the message “Find new boxes”, in order to determine the terminals connected to the devices. “Free
Run” enables manipulation of input and output values in “Config mode” and should also be acknowledged.
Based on the sample configuration [} 48] described at the beginning of this section, the result is as follows:
The whole process consists of two stages, which may be performed separately (first determine the devices,
then determine the connected elements such as boxes, terminals, etc.). A scan can also be initiated by
selecting “Device ...” from the context menu, which then reads the elements present in the configuration
below:
TwinCAT PLC Control is the development environment for the creation of the controller in different program
environments: TwinCAT PLC Control supports all languages described in IEC 61131-3. There are two text-
based languages and three graphical languages.
• Text-based languages
◦ Instruction List (IL)
After starting TwinCAT PLC Control, the following user interface is shown for an initial project:
Sample variables and a sample program have been created and stored under the name “PLC_example.pro”:
Fig. 43: Sample program with variables after a compile process (without variable integration)
Warning 1990 (missing “VAR_CONFIG”) after a compile process indicates that the variables defined as
external (with the ID “AT%I*” or “AT%Q*”) have not been assigned. After successful compilation, TwinCAT
PLC Control creates a “*.tpy” file in the directory in which the project was stored. This file (“*.tpy”) contains
variable assignments and is not known to the System Manager, hence the warning. Once the System
Manager has been notified, the warning no longer appears.
First, integrate the TwinCAT PLC Control project in the System Manager via the context menu of the PLC
configuration; right-click and select “Append PLC Project…”:
Select the PLC configuration “PLC_example.tpy” in the browser window that opens. The project including the
two variables identified with “AT” are then integrated in the configuration tree of the System Manager:
Fig. 45: PLC project integrated in the PLC configuration of the System Manager
The two variables “bEL1004_Ch4” and “nEL2008_value” can now be assigned to certain process objects of
the I/O configuration.
Assigning variables
Open a window for selecting a suitable process object (PDO) via the context menu of a variable of the
integrated project “PLC_example” and via “Modify Link...” “Standard”:
Fig. 46: Creating the links between PLC variables and process objects
In the window that opens, the process object for the variable “bEL1004_Ch4” of type BOOL can be selected
from the PLC configuration tree:
According to the default setting, certain PDO objects are now available for selection. In this sample the input
of channel 4 of the EL1004 terminal is selected for linking. In contrast, the checkbox “All types” must be
ticked for creating the link for the output variables, in order to allocate a set of eight separate output bits to a
byte variable. The following diagram shows the whole process:
Fig. 48: Selecting several PDOs simultaneously: activate “Continuous” and “All types”
Note that the “Continuous” checkbox was also activated. This is designed to allocate the bits contained in the
byte of the variable “nEL2008_value” sequentially to all eight selected output bits of the EL2008 terminal. In
this way it is possible to subsequently address all eight outputs of the terminal in the program with a byte
corresponding to bit 0 for channel 1 to bit 7 for channel 8 of the PLC. A special symbol ( ) at the yellow or
red object of the variable indicates that a link exists. The links can also be checked by selecting a “Goto Link
Variable” from the context menu of a variable. The object opposite, in this case the PDO, is automatically
selected:
The process of assigning variables to the PDO is completed via the menu selection “Actions” → “Generate
The process of creating links can also take place in the opposite direction, i.e. starting with individual PDOs
to variable. However, in this example it would then not be possible to select all output bits for the EL2008,
since the terminal only makes individual digital outputs available. If a terminal has a byte, word, integer or
similar PDO, it is possible to allocate this a set of bit-standardized variables (type “BOOL”). Here, too, a
“Goto Link Variable” from the context menu of a PDO can be executed in the other direction, so that the
respective PLC instance can then be selected.
The allocation of PDO to PLC variables has now established the connection from the controller to the inputs
and outputs of the terminals. The configuration can now be activated. First, the configuration can be verified
via (or via “Actions” → “Check Configuration”). If no error is present, the configuration can be
activated via (or via “Actions” → “Activate Configuration…”) to transfer the System Manager settings
to the runtime system. Confirm the messages “Old configurations are overwritten!” and “Restart TwinCAT
system in Run mode” with “OK”.
A few seconds later the real-time status is displayed at the bottom right in the System Manager.
The PLC system can then be started as described below.
Starting from a remote system, the PLC control has to be linked with the Embedded PC over Ethernet via
“Online” → “Choose Run-Time System…”:
In this sample “Runtime system 1 (port 801)” is selected and confirmed. Link the PLC with the real-time
system via menu option “Online” → “Login”, the F11 key or by clicking on the symbol . The control
program can then be loaded for execution. This results in the message “No program on the controller!
Should the new program be loaded?”, which should be acknowledged with “Yes”. The runtime environment
is ready for the program start:
Fig. 51: PLC Control logged in, ready for program startup
5.1.2 TwinCAT 3
Startup
TwinCAT makes the development environment areas available together with Microsoft Visual Studio: after
startup, the project folder explorer appears on the left in the general window area (cf. “TwinCAT System
Manager” of TwinCAT 2) for communication with the electromechanical components.
After successful installation of the TwinCAT system on the PC to be used for development, TwinCAT 3
(shell) displays the following user interface after startup:
First create a new project via (or under “File”→“New”→ “Project…”). In the
following dialog make the corresponding entries as required (as shown in the diagram):
Generally, TwinCAT can be used in local or remote mode. Once the TwinCAT system including the user
interface (standard) is installed on the respective PLC, TwinCAT can be used in local mode and thereby the
next step is “Insert Device [} 63]”.
If the intention is to address the TwinCAT runtime environment installed on a PLC as development
environment remotely from another system, the target system must be made known first. Via the symbol in
the menu bar:
Use “Search (Ethernet)...” to enter the target system. Thus a next dialog opens to either:
• enter the known computer name after “Enter Host Name / IP:” (as shown in red)
• perform a “Broadcast Search” (if the exact computer name is not known)
• enter the known computer IP or AmsNetID.
Fig. 56: Specify the PLC for access by the TwinCAT System Manager: selection of the target system
Once the target system has been entered, it is available for selection as follows (a password may have to be
entered):
After confirmation with “OK” the target system can be accessed via the Visual Studio shell.
Adding devices
In the project folder explorer of the Visual Studio shell user interface on the left, select “Devices” within
element “I/O”, then right-click to open a context menu and select “Scan” or start the action via in the
menu bar. The TwinCAT System Manager may first have to be set to “Config mode” via or via the
menu “TwinCAT” → “Restart TwinCAT (Config mode)”.
Confirm the warning message, which follows, and select “EtherCAT” in the dialog:
Fig. 58: Automatic detection of I/O devices: selection the devices to be integrated
Confirm the message “Find new boxes”, in order to determine the terminals connected to the devices. “Free
Run” enables manipulation of input and output values in “Config mode” and should also be acknowledged.
Based on the sample configuration [} 48] described at the beginning of this section, the result is as follows:
The whole process consists of two stages, which may be performed separately (first determine the devices,
then determine the connected elements such as boxes, terminals, etc.). A scan can also be initiated by
selecting “Device ...” from the context menu, which then reads the elements present in the configuration
below:
TwinCAT PLC Control is the development environment for the creation of the controller in different program
environments: TwinCAT PLC Control supports all languages described in IEC 61131-3. There are two text-
based languages and three graphical languages.
• Text-based languages
◦ Instruction List (IL)
◦ Structured Text (ST)
• Graphical languages
◦ Function Block Diagram (FBD)
◦ Ladder Diagram (LD)
◦ The Continuous Function Chart Editor (CFC)
◦ Sequential Function Chart (SFC)
In order to create a programming environment, a PLC subproject is added to the project sample via the
context menu of “PLC” in the project folder explorer by selecting “Add New Item….”:
In the dialog that opens select “Standard PLC project” and enter “PLC_example” as project name, for
example, and select a corresponding directory:
Fig. 62: Specifying the name and directory for the PLC programming environment
The “Main” program, which already exists by selecting “Standard PLC project”, can be opened by double-
clicking on “PLC_example_project” in “POUs”. The following user interface is shown for an initial project:
To continue, sample variables and a sample program have now been created:
Fig. 64: Sample program with variables after a compile process (without variable integration)
The control program is now created as a project folder, followed by the compile process:
The following variables, identified in the ST/ PLC program with “AT%”, are then available in under
“Assignments” in the project folder explorer:
Assigning variables
Via the menu of an instance - variables in the “PLC” context, use the “Modify Link…” option to open a
window for selecting a suitable process object (PDO) for linking:
Fig. 66: Creating the links between PLC variables and process objects
In the window that opens, the process object for the variable “bEL1004_Ch4” of type BOOL can be selected
from the PLC configuration tree:
According to the default setting, certain PDO objects are now available for selection. In this sample the input
of channel 4 of the EL1004 terminal is selected for linking. In contrast, the checkbox “All types” must be
ticked for creating the link for the output variables, in order to allocate a set of eight separate output bits to a
byte variable. The following diagram shows the whole process:
Fig. 68: Selecting several PDOs simultaneously: activate “Continuous” and “All types”
Note that the “Continuous” checkbox was also activated. This is designed to allocate the bits contained in the
byte of the variable “nEL2008_value” sequentially to all eight selected output bits of the EL2008 terminal. In
this way it is possible to subsequently address all eight outputs of the terminal in the program with a byte
corresponding to bit 0 for channel 1 to bit 7 for channel 8 of the PLC. A special symbol ( ) at the yellow or
red object of the variable indicates that a link exists. The links can also be checked by selecting a “Goto Link
Variable” from the context menu of a variable. The object opposite, in this case the PDO, is automatically
selected:
The process of creating links can also take place in the opposite direction, i.e. starting with individual PDOs
to variable. However, in this example it would then not be possible to select all output bits for the EL2008,
since the terminal only makes individual digital outputs available. If a terminal has a byte, word, integer or
similar PDO, it is possible to allocate this a set of bit-standardized variables (type “BOOL”). Here, too, a
“Goto Link Variable” from the context menu of a PDO can be executed in the other direction, so that the
respective PLC instance can then be selected.
In TwinCAT it is possible to create a structure from the mapped process data of a terminal. An instance of
this structure can then be created in the PLC, so it is possible to access the process data directly from the
PLC without having to declare own variables.
The procedure for the EL3001 1-channel analog input terminal -10...+10 V is shown as an example.
1. First the required process data must be selected in the “Process data” tab in TwinCAT.
2. After that, the PLC data type must be generated in the tab “PLC” via the check box.
3. The data type in the “Data Type” field can then be copied using the “Copy” button.
4. An instance of the data structure of the copied data type must then be created in the PLC.
5. Then the project folder must be created. This can be done either via the key combination “CTRL +
Shift + B” or via the “Build” tab in TwinCAT.
6. The structure in the “PLC” tab of the terminal must then be linked to the created instance.
7. In the PLC the process data can then be read or written via the structure in the program code.
Fig. 73: Reading a variable from the structure of the process data
The allocation of PDO to PLC variables has now established the connection from the controller to the inputs
and outputs of the terminals. The configuration can now be activated with or via the menu under
“TwinCAT” in order to transfer settings of the development environment to the runtime system. Confirm the
messages “Old configurations are overwritten!” and “Restart TwinCAT system in Run mode” with “OK”. The
corresponding assignments can be seen in the project folder explorer:
A few seconds later the corresponding status of the Run mode is displayed in the form of a rotating symbol
at the bottom right of the VS shell development environment. The PLC system can then be started as
described below.
Select the menu option “PLC” → “Login” or click on to link the PLC with the real-time system and load
the control program for execution. This results in the message No program on the controller! Should the new
program be loaded?, which should be acknowledged with “Yes”. The runtime environment is ready for
program start by click on symbol , the “F5” key or via “PLC” in the menu selecting “Start”. The started
programming environment shows the runtime values of individual variables:
Fig. 74: TwinCAT development environment (VS shell): logged-in, after program startup
The two operator control elements for stopping and logout result in the required action
(accordingly also for stop “Shift + F5”, or both actions can be selected via the PLC menu).
Details:
• TwinCAT 2:
◦ Connects I/O devices to tasks in a variable-oriented manner
◦ Connects tasks to tasks in a variable-oriented manner
◦ Supports units at the bit level
◦ Supports synchronous or asynchronous relationships
◦ Exchange of consistent data areas and process images
◦ Datalink on NT - Programs by open Microsoft Standards (OLE, OCX, ActiveX, DCOM+, etc.)
Additional features:
• TwinCAT 3 (eXtended Automation):
◦ Visual-Studio®-Integration
◦ Choice of the programming language
◦ Supports object orientated extension of IEC 61131-3
◦ Usage of C/C++ as programming language for real time applications
◦ Connection to MATLAB®/Simulink®
◦ Open interface for expandability
◦ Flexible run-time environment
◦ Active support of Multi-Core- und 64-Bit-Operatingsystem
◦ Automatic code generation and project creation with the TwinCAT Automation Interface
◦ More…
Within the following sections commissioning of the TwinCAT Development Environment on a PC System for
the control and also the basically functions of unique control elements will be explained.
In the System Manager call up the TwinCAT overview of the local network interfaces via Options → Show
Real Time Ethernet Compatible Devices.
This have to be called up by the Menü “TwinCAT” within the TwinCAT 3 environment:
Interfaces listed under “Compatible devices” can be assigned a driver via the “Install” button. A driver should
only be installed on compatible devices.
Alternatively an EtherCAT-device can be inserted first of all as described in chapter Offline configuration
creation, section “Creating the EtherCAT device” [} 84] in order to view the compatible ethernet ports via its
EtherCAT properties (tab “Adapter”, button “Compatible Devices…”):
Fig. 78: EtherCAT device properties(TwinCAT 2): click on “Compatible Devices…” of tab “Adapte””
TwinCAT 3: the properties of the EtherCAT device can be opened by double click on “Device .. (EtherCAT)”
within the Solution Explorer under “I/O”:
After the installation the driver appears activated in the Windows overview for the network interface
(Windows Start → System Properties → Network)
Fig. 80: Exemplary correct driver setting for the Ethernet port
IP address/DHCP
In most cases an Ethernet port that is configured as an EtherCAT device will not transport general
IP packets. For this reason and in cases where an EL6601 or similar devices are used it is useful to
specify a fixed IP address for this port via the “Internet Protocol TCP/IP” driver setting and to disable
DHCP. In this way the delay associated with the DHCP client for the Ethernet port assigning itself a
default IP address in the absence of a DHCP server is avoided. A suitable address space is
192.168.x.x, for example.
The TwinCAT EtherCAT master/System Manager needs the device description files for the devices to be
used in order to generate the configuration in online or offline mode. The device descriptions are contained
in the so-called ESI files (EtherCAT Slave Information) in XML format. These files can be requested from the
respective manufacturer and are made available for download. An *.xml file may contain several device
descriptions.
The ESI files for Beckhoff EtherCAT devices are available on the Beckhoff website.
Default settings:
• TwinCAT 2: C:\TwinCAT\IO\EtherCAT
• TwinCAT 3: C:\TwinCAT\3.1\Config\Io\EtherCAT
The files are read (once) when a new System Manager window is opened, if they have changed since the
last time the System Manager window was opened.
A TwinCAT installation includes the set of Beckhoff ESI files that was current at the time when the TwinCAT
build was created.
For TwinCAT 2.11/TwinCAT 3 and higher, the ESI directory can be updated from the System Manager, if the
programming PC is connected to the Internet; by
• TwinCAT 2: Option → “Update EtherCAT Device Descriptions”
• TwinCAT 3: TwinCAT → EtherCAT Devices → “Update Device Descriptions (via ETG Website)…”
ESI
The *.xml files are associated with *.xsd files, which describe the structure of the ESI XML files. To
update the ESI device descriptions, both file types should therefore be updated.
Device differentiation
EtherCAT devices/slaves are distinguished by four properties, which determine the full device identifier. For
example, the device identifier EL2521-0025-1018 consists of:
• family key “EL”
• name “2521”
• type “0025”
• and revision “1018”
The order identifier consisting of name + type (here: EL2521-0010) describes the device function. The
revision indicates the technical progress and is managed by Beckhoff. In principle, a device with a higher
revision can replace a device with a lower revision, unless specified otherwise, e.g. in the documentation.
Each revision has its own ESI description. See further notes [} 7].
Online description
If the EtherCAT configuration is created online through scanning of real devices (see section Online setup)
and no ESI descriptions are available for a slave (specified by name and revision) that was found, the
System Manager asks whether the description stored in the device should be used. In any case, the System
Manager needs this information for setting up the cyclic and acyclic communication with the slave correctly.
In TwinCAT 3 a similar window appears, which also offers the Web update:
If possible, the Yes is to be rejected and the required ESI is to be requested from the device manufacturer.
After installation of the XML/XSD file the configuration process should be repeated.
NOTE
Changing the “usual” configuration through a scan
ü If a scan discovers a device that is not yet known to TwinCAT, distinction has to be made between two
cases. Taking the example here of the EL2521-0000 in the revision 1019
a) no ESI is present for the EL2521-0000 device at all, either for the revision 1019 or for an older revision.
The ESI must then be requested from the manufacturer (in this case Beckhoff).
b) an ESI is present for the EL2521-0000 device, but only in an older revision, e.g. 1018 or 1017.
In this case an in-house check should first be performed to determine whether the spare parts stock al-
lows the integration of the increased revision into the configuration at all. A new/higher revision usually
also brings along new features. If these are not to be used, work can continue without reservations with
the previous revision 1018 in the configuration. This is also stated by the Beckhoff compatibility rule.
Refer in particular to the chapter “General notes on the use of Beckhoff EtherCAT IO components” and for
manual configuration to the chapter “Offline configuration creation [} 84]”.
If the OnlineDescription is used regardless, the System Manager reads a copy of the device description from
the EEPROM in the EtherCAT slave. In complex slaves the size of the EEPROM may not be sufficient for the
complete ESI, in which case the ESI would be incomplete in the configurator. Therefore it’s recommended
using an offline ESI file with priority in such a case.
The System Manager creates for online recorded device descriptions a new file
“OnlineDescription0000...xml” in its ESI directory, which contains all ESI descriptions that were read online.
Is a slave desired to be added manually to the configuration at a later stage, online created slaves are
indicated by a prepended symbol “>” in the selection list (see Figure Indication of an online recorded ESI of
EL2521 as an example).
If such ESI files are used and the manufacturer's files become available later, the file OnlineDescription.xml
should be deleted as follows:
• close all System Manager windows
• restart TwinCAT in Config mode
• delete “OnlineDescription0000...xml”
• restart TwinCAT System Manager
This file should not be visible after this procedure, if necessary press <F5> to update
If an ESI file is faulty and the System Manager is unable to read it, the System Manager brings up an
information window.
Fig. 88: Information window for faulty ESI file (left: TwinCAT 2; right: TwinCAT 3)
The ESI Updater (TwinCAT 3) is a convenient option for automatic downloading of ESI data provided by
EtherCAT manufacturers via the Internet into the TwinCAT directory (ESI = EtherCAT slave information).
TwinCAT accesses the central ESI ULR directory list stored at ETG; the entries can then be viewed in the
Updater dialog, although they cannot be changed there.
If the designed control system is already connected to the EtherCAT system and all components are
energised and the infrastructure is ready for operation, the TwinCAT configuration can simply be generated
through “scanning” from the runtime system. This is referred to as online configuration.
In any case, during each startup the EtherCAT master checks whether the slaves it finds match the
configuration. This test can be parameterised in the extended slave settings. Refer to note “Installation of
the latest ESI-XML device description” [} 79].
• the devices/modules be connected to the power supply and ready for communication
• TwinCAT must be in CONFIG mode on the target system.
The scan with existing configuration [} 94] can also be carried out for comparison.
Select type “EtherCAT” for an EtherCAT I/O application with EtherCAT slaves. For the present publisher/
subscriber service in combination with an EL6601/EL6614 terminal select “EtherCAT Automation Protocol
via EL6601”.
Then assign a real Ethernet port to this virtual device in the runtime system.
This query may appear automatically when the EtherCAT device is created, or the assignment can be set/
modified later in the properties dialog; see Fig. “EtherCAT device properties (TwinCAT 2)”.
TwinCAT 3: the properties of the EtherCAT device can be opened by double click on “Device .. (EtherCAT)”
within the Solution Explorer under “I/O”:
The dialog for selecting a new device opens. Only devices for which ESI files are available are displayed.
Only devices are offered for selection that can be appended to the previously selected device. Therefore the
physical layer available for this port is also displayed (Fig. “Selection dialog for new EtherCAT device”, A). In
the case of cable-based Fast-Ethernet physical layer with PHY transfer, then also only cable-based devices
are available, as shown in Fig. “Selection dialog for new EtherCAT device”. If the preceding device has
several free ports (e.g. EK1122 or EK1100), the required port can be selected on the right-hand side (A).
• “E-Bus”: LVDS “terminal bus”, “EJ-module”: EL/ES terminals, various modular modules
The search field facilitates finding specific devices (since TwinCAT 2.11 or TwinCAT 3).
By default only the name/device type is used as selection criterion. For selecting a specific revision of the
device the revision can be displayed as “Extended Information”.
In many cases several device revisions were created for historic or functional reasons, e.g. through
technological advancement. For simplification purposes (see Fig. “Selection dialog for new EtherCAT
device”) only the last (i.e. highest) revision and therefore the latest state of production is displayed in the
selection dialog for Beckhoff devices. To show all device revisions available in the system as ESI
descriptions tick the “Show Hidden Devices” check box, see Fig. “Display of previous revisions”.
Example
If current ESI descriptions are available in the TwinCAT system, the last revision offered in the selection
dialog matches the Beckhoff state of production. It is recommended to use the last device revision when
creating a new configuration, if current Beckhoff devices are used in the real application. Older revisions
should only be used if older devices from stock are to be used in the application.
In this case the process image of the device is shown in the configuration tree and can be parameterized as
follows: linking with the task, CoE/DC settings, plug-in definition, startup settings, ...
Fig. 100: EtherCAT terminal in the TwinCAT tree (left: TwinCAT 2; right: TwinCAT 3)
The online device search can be used if the TwinCAT system is in CONFIG mode. This can be indicated by
a symbol right below in the information bar:
• on TwinCAT 2 by a blue display “Config Mode” within the System Manager window: .
The TwinCAT 2 icon ( ) or TwinCAT 3 icon ( ) within the Windows-Taskbar always shows the
TwinCAT mode of the local IPC. Compared to that, the System Manager window of TwinCAT 2 or the user
interface of TwinCAT 3 indicates the state of the target system.
Right-clicking on “I/O Devices” in the configuration tree opens the search dialog.
This scan mode attempts to find not only EtherCAT devices (or Ethernet ports that are usable as such), but
also NOVRAM, fieldbus cards, SMB etc. However, not all devices can be found automatically.
Fig. 103: Note for automatic device scan (left: TwinCAT 2; right: TwinCAT 3)
Ethernet ports with installed TwinCAT real-time driver are shown as “RT Ethernet” devices. An EtherCAT
frame is sent to these ports for testing purposes. If the scan agent detects from the response that an
EtherCAT slave is connected, the port is immediately shown as an “EtherCAT Device” .
Via respective checkboxes devices can be selected (as illustrated in Fig. “Detected Ethernet devices” e.g.
Device 3 and Device 4 were chosen). After confirmation with “OK” a device scan is suggested for all selected
devices, see Fig.: “Scan query after automatic creation of an EtherCAT device”.
NOTE
Slave scanning in practice in series machine production
The scanning function should be used with care. It is a practical and fast tool for creating an initial configu-
ration as a basis for commissioning. In series machine production or reproduction of the plant, however, the
function should no longer be used for the creation of the configuration, but if necessary for comparison
[} 94] with the defined initial configuration.Background: since Beckhoff occasionally increases the revision
version of the delivered products for product maintenance reasons, a configuration can be created by such
a scan which (with an identical machine construction) is identical according to the device list; however, the
respective device revision may differ from the initial configuration.
Example:
Company A builds the prototype of a machine B, which is to be produced in series later on. To do this the
prototype is built, a scan of the IO devices is performed in TwinCAT and the initial configuration “B.tsm” is
created. The EL2521-0025 EtherCAT terminal with the revision 1018 is located somewhere. It is thus built
into the TwinCAT configuration in this way:
Likewise, during the prototype test phase, the functions and properties of this terminal are tested by the
programmers/commissioning engineers and used if necessary, i.e. addressed from the PLC “B.pro” or the
NC. (the same applies correspondingly to the TwinCAT 3 solution files).
The prototype development is now completed and series production of machine B starts, for which Beckhoff
continues to supply the EL2521-0025-0018. If the commissioning engineers of the series machine production
department always carry out a scan, a B configuration with the identical contents results again for each
machine. Likewise, A might create spare parts stores worldwide for the coming series-produced machines
with EL2521-0025-1018 terminals.
After some time Beckhoff extends the EL2521-0025 by a new feature C. Therefore the FW is changed,
outwardly recognizable by a higher FW version and a new revision -1019. Nevertheless the new device
naturally supports functions and interfaces of the predecessor version(s); an adaptation of “B.tsm” or even
“B.pro” is therefore unnecessary. The series-produced machines can continue to be built with “B.tsm” and
“B.pro”; it makes sense to perform a comparative scan [} 94] against the initial configuration “B.tsm” in order
to check the built machine.
However, if the series machine production department now doesn’t use “B.tsm”, but instead carries out a
scan to create the productive configuration, the revision -1019 is automatically detected and built into the
configuration:
This is usually not noticed by the commissioning engineers. TwinCAT cannot signal anything either, since
virtually a new configuration is created. According to the compatibility rule, however, this means that no
EL2521-0025-1018 should be built into this machine as a spare part (even if this nevertheless works in the
vast majority of cases).
In addition, it could be the case that, due to the development accompanying production in company A, the
new feature C of the EL2521-0025-1019 (for example, an improved analog filter or an additional process
data for the diagnosis) is discovered and used without in-house consultation. The previous stock of spare
part devices are then no longer to be used for the new configuration “B2.tsm” created in this way. Þ if series
machine production is established, the scan should only be performed for informative purposes for
comparison with a defined initial configuration. Changes are to be made with care!
If an EtherCAT device was created in the configuration (manually or through a scan), the I/O field can be
scanned for devices/slaves.
Fig. 108: Scan query after automatic creation of an EtherCAT device (left: TwinCAT 2; right: TwinCAT 3)
Fig. 109: Manual triggering of a device scan on a specified EtherCAT device (left: TwinCAT 2; right:
TwinCAT 3)
In the System Manager (TwinCAT 2) or the User Interface (TwinCAT 3) the scan process can be monitored
via the progress bar at the bottom in the status bar.
The configuration is established and can then be switched to online state (OPERATIONAL).
In Config/FreeRun mode the System Manager display alternates between blue and red, and the EtherCAT
device continues to operate with the idling cycle time of 4 ms (default setting), even without active task (NC,
PLC).
Fig. 112: Displaying of “Free Run” and “Config Mode” toggling right below in the status bar
Fig. 113: TwinCAT can also be switched to this state by using a button (left: TwinCAT 2; right: TwinCAT 3)
The EtherCAT system should then be in a functional cyclic state, as shown in Fig. Online display example.
Please note:
• all slaves should be in OP state
• the EtherCAT master should be in “Actual State” OP
• “frames/sec” should match the cycle time taking into account the sent number of frames
• no excessive “LostFrames” or CRC errors should occur
The configuration is now complete. It can be modified as described under manual procedure [} 84].
Troubleshooting
In the System Manager such devices may be set up as EK0000 or unknown devices. Operation is not
possible or meaningful.
NOTE
Change of the configuration after comparison
With this scan (TwinCAT 2.11 or 3.1) only the device properties vendor (manufacturer), device name and
revision are compared at present! A “ChangeTo” or “Copy” should only be carried out with care, taking into
consideration the Beckhoff IO compatibility rule (see above). The device configuration is then replaced by
the revision found; this can affect the supported process data and functions.
If a scan is initiated for an existing configuration, the actual I/O environment may match the configuration
exactly or it may differ. This enables the configuration to be compared.
If differences are detected, they are shown in the correction dialog, so that the user can modify the
configuration as required.
It is advisable to tick the “Extended Information” check box to reveal differences in the revision.
Color Explanation
green This EtherCAT slave matches the entry on the other side. Both type and revision match.
blue This EtherCAT slave is present on the other side, but in a different revision. This other revision can
have other default values for the process data as well as other/additional functions.
If the found revision is higher than the configured revision, the slave may be used provided
compatibility issues are taken into account.
If the found revision is lower than the configured revision, it is likely that the slave cannot be used.
The found device may not support all functions that the master expects based on the higher
revision number.
light This EtherCAT slave is ignored (“Ignore” button)
blue
red • This EtherCAT slave is not present on the other side.
• It is present, but in a different revision, which also differs in its properties from the one specified.
The compatibility principle then also applies here: if the found revision is higher than the
configured revision, use is possible provided compatibility issues are taken into account, since
the successor devices should support the functions of the predecessor devices.
If the found revision is lower than the configured revision, it is likely that the slave cannot be
used. The found device may not support all functions that the master expects based on the
higher revision number.
Example
If current ESI descriptions are available in the TwinCAT system, the last revision offered in the selection
dialog matches the Beckhoff state of production. It is recommended to use the last device revision when
creating a new configuration, if current Beckhoff devices are used in the real application. Older revisions
should only be used if older devices from stock are to be used in the application.
In this case the process image of the device is shown in the configuration tree and can be parameterized as
follows: linking with the task, CoE/DC settings, plug-in definition, startup settings, ...
Once all modifications have been saved or accepted, click “OK” to transfer them to the real *.tsm
configuration.
TwinCAT offers a function Change to Compatible Type… for the exchange of a device whilst retaining the
links in the task.
Fig. 120: Dialog “Change to Compatible Type…” (left: TwinCAT 2; right: TwinCAT 3)
The TwinCAT System Manager offers a function for the exchange of a device: Change to Alternative Type
If called, the System Manager searches in the procured device ESI (in this example: EL1202-0000) for
details of compatible devices contained there. The configuration is changed and the ESI-EEPROM is
overwritten at the same time – therefore this process is possible only in the online state (ConfigMode).
In the right-hand window of the TwinCAT System Manager (TwinCAT 2) or the Development Environment
(TwinCAT 3), various tabs are now available for configuring the terminal. And yet the dimension of
complexity of a subscriber determines which tabs are provided. Thus as illustrated in the example above the
terminal EL3751 provides many setup options and also a respective number of tabs are available. On the
contrary by the terminal EL1004 for example the tabs “General”, “EtherCAT”, “Process Data” and “Online“
are available only. Several terminals, as for instance the EL6695 provide special functions by a tab with its
own terminal name, so “EL6695” in this case. A specific tab “Settings” by terminals with a wide range of
setup options will be provided also (e.g. EL3751).
“General” tab
“EtherCAT” tab
The link at the bottom of the tab points to the product page for this EtherCAT device on the web.
Indicates the configuration of the process data. The input and output data of the EtherCAT slave are
represented as CANopen process data objects (Process Data Objects, PDOs). The user can select a PDO
via PDO assignment and modify the content of the individual PDO via this dialog, if the EtherCAT slave
supports this function.
The process data (PDOs) transferred by an EtherCAT slave during each cycle are user data which the
application expects to be updated cyclically or which are sent to the slave. To this end the EtherCAT master
(Beckhoff TwinCAT) parameterizes each EtherCAT slave during the start-up phase to define which process
data (size in bits/bytes, source location, transmission type) it wants to transfer to or from this slave. Incorrect
configuration can prevent successful start-up of the slave.
For Beckhoff EtherCAT EL, ES, EM, EJ and EP slaves the following applies in general:
• The input/output process data supported by the device are defined by the manufacturer in the ESI/XML
description. The TwinCAT EtherCAT Master uses the ESI description to configure the slave correctly.
• The process data can be modified in the System Manager. See the device documentation.
Examples of modifications include: mask out a channel, displaying additional cyclic information, 16-bit
display instead of 8-bit data size, etc.
• In so-called “intelligent” EtherCAT devices the process data information is also stored in the CoE
directory. Any changes in the CoE directory that lead to different PDO settings prevent successful
startup of the slave. It is not advisable to deviate from the designated process data, because the
device firmware (if available) is adapted to these PDO combinations.
If the device documentation allows modification of process data, proceed as follows (see Figure Configuring
the process data).
• A: select the device to configure
• B: in the “Process Data” tab select Input or Output under SyncManager (C)
• D: the PDOs can be selected or deselected
• H: the new process data are visible as linkable variables in the System Manager
The new process data are active once the configuration has been activated and TwinCAT has been
restarted (or the EtherCAT master has been restarted)
• E: if a slave supports this, Input and Output PDO can be modified simultaneously by selecting a so-
called PDO record (“predefined PDO settings”).
“Startup” tab
The Startup tab is displayed if the EtherCAT slave has a mailbox and supports the CANopen over EtherCAT
(CoE) or Servo drive over EtherCAT protocol. This tab indicates which download requests are sent to the
mailbox during startup. It is also possible to add new mailbox requests to the list display. The download
requests are sent to the slave in the same order as they are shown in the list.
Column Description
Transition Transition to which the request is sent. This can either be
• the transition from pre-operational to safe-operational (PS), or
• the transition from safe-operational to operational (SO).
If the transition is enclosed in “<>” (e.g. <PS>), the mailbox request is fixed and cannot be
modified or deleted by the user.
Protocol Type of mailbox protocol
Index Index of the object
Data Date on which this object is to be downloaded.
Comment Description of the request to be sent to the mailbox
Move Up This button moves the selected request up by one position in the list.
Move Down This button moves the selected request down by one position in the list.
New This button adds a new mailbox download request to be sent during startup.
Delete This button deletes the selected entry.
Edit This button edits an existing request.
The additional CoE - Online tab is displayed if the EtherCAT slave supports the CANopen over EtherCAT
(CoE) protocol. This dialog lists the content of the object list of the slave (SDO upload) and enables the user
to modify the content of an object from this list. Details for the objects of the individual EtherCAT devices can
be found in the device-specific object descriptions.
Update List The Update list button updates all objects in the displayed list
Auto Update If this check box is selected, the content of the objects is updated automatically.
Advanced The Advanced button opens the Advanced Settings dialog. Here you can specify which
objects are displayed in the list.
Online - via SDO Information If this option button is selected, the list of the objects included in the object
list of the slave is uploaded from the slave via SDO information. The list
below can be used to specify which object types are to be uploaded.
Offline - via EDS File If this option button is selected, the list of the objects included in the object
list is read from an EDS file provided by the user.
“Online” tab
State Machine
Init This button attempts to set the EtherCAT device to the Init state.
Pre-Op This button attempts to set the EtherCAT device to the pre-operational state.
Op This button attempts to set the EtherCAT device to the operational state.
Bootstrap This button attempts to set the EtherCAT device to the Bootstrap state.
Safe-Op This button attempts to set the EtherCAT device to the safe-operational state.
Clear Error This button attempts to delete the fault display. If an EtherCAT slave fails during
change of state it sets an error flag.
Example: An EtherCAT slave is in PREOP state (pre-operational). The master now
requests the SAFEOP state (safe-operational). If the slave fails during change of
state it sets the error flag. The current state is now displayed as ERR PREOP.
When the Clear Error button is pressed the error flag is cleared, and the current
state is displayed as PREOP again.
Current State Indicates the current state of the EtherCAT device.
Requested State Indicates the state requested for the EtherCAT device.
DLL Status
Indicates the DLL status (data link layer status) of the individual ports of the EtherCAT slave. The DLL status
can have four different states:
Status Description
No Carrier / Open No carrier signal is available at the port, but the port is open.
No Carrier / Closed No carrier signal is available at the port, and the port is closed.
Carrier / Open A carrier signal is available at the port, and the port is open.
Carrier / Closed A carrier signal is available at the port, but the port is closed.
Sync Manager
If an input is selected, the corresponding PDO assignment is displayed in the PDO Assignment list below.
PDO Assignment
PDO assignment of the selected Sync Manager. All PDOs defined for this Sync Manager type are listed
here:
• If the output Sync Manager (outputs) is selected in the Sync Manager list, all RxPDOs are displayed.
• If the input Sync Manager (inputs) is selected in the Sync Manager list, all TxPDOs are displayed.
The selected entries are the PDOs involved in the process data transfer. In the tree diagram of the System
Manager these PDOs are displayed as variables of the EtherCAT device. The name of the variable is
identical to the Name parameter of the PDO, as displayed in the PDO list. If an entry in the PDO assignment
list is deactivated (not selected and greyed out), this indicates that the input is excluded from the PDO
assignment. In order to be able to select a greyed out PDO, the currently selected PDO has to be deselected
first.
PDO list
List of all PDOs supported by this EtherCAT device. The content of the selected PDOs is displayed in the
PDO Content list. The PDO configuration can be modified by double-clicking on an entry.
Column Description
Index PDO index.
Size Size of the PDO in bytes.
Name Name of the PDO.
If this PDO is assigned to a Sync Manager, it appears as a variable of the slave with this
parameter as the name.
Flags F Fixed content: The content of this PDO is fixed and cannot be changed by the
System Manager.
M Mandatory PDO. This PDO is mandatory and must therefore be assigned to a
Sync Manager! Consequently, this PDO cannot be deleted from the PDO
Assignment list
SM Sync Manager to which this PDO is assigned. If this entry is empty, this PDO does not take
part in the process data traffic.
SU Sync unit to which this PDO is assigned.
PDO Content
Indicates the content of the PDO. If flag F (fixed content) of the PDO is not set the content can be modified.
Download
If the device is intelligent and has a mailbox, the configuration of the PDO and the PDO assignments can be
downloaded to the device. This is an optional feature that is not supported by all EtherCAT slaves.
PDO Assignment
If this check box is selected, the PDO assignment that is configured in the PDO Assignment list is
downloaded to the device on startup. The required commands to be sent to the device can be viewed in the
Startup [} 100] tab.
PDO Configuration
If this check box is selected, the configuration of the respective PDOs (as shown in the PDO list and the
PDO Content display) is downloaded to the EtherCAT slave.
Generally speaking an EtherCAT Slave provides a variety of diagnostic information that can be used by the
controlling task.
This diagnostic information relates to differing levels of communication. It therefore has a variety of sources,
and is also updated at various times.
Any application that relies on I/O data from a fieldbus being correct and up to date must make diagnostic
access to the corresponding underlying layers. EtherCAT and the TwinCAT System Manager offer
comprehensive diagnostic elements of this kind. Those diagnostic elements that are helpful to the controlling
task for diagnosis that is accurate for the current cycle when in operation (not during commissioning) are
discussed below.
• communication diagnosis typical for a slave (diagnosis of successful participation in the exchange of
process data, and correct operating mode)
This diagnosis is the same for all slaves.
as well as
• function diagnosis typical for a channel (device-dependent)
See the corresponding device documentation
The colors in Fig. Selection of the diagnostic information of an EtherCAT Slave also correspond to the
variable colors in the System Manager, see Fig. Basic EtherCAT Slave Diagnosis in the PLC.
Colour Meaning
yellow Input variables from the Slave to the EtherCAT Master, updated in every cycle
red Output variables from the Slave to the EtherCAT Master, updated in every cycle
green Information variables for the EtherCAT Master that are updated acyclically. This means that
it is possible that in any particular cycle they do not represent the latest possible status. It is
therefore useful to read such variables through ADS.
Fig. Basic EtherCAT Slave Diagnosis in the PLC shows an example of an implementation of basic EtherCAT
Slave Diagnosis. A Beckhoff EL3102 (2-channel analogue input terminal) is used here, as it offers both the
communication diagnosis typical of a slave and the functional diagnosis that is specific to a channel.
Structures are created as input variables in the PLC, each corresponding to the process image.
NOTE
Diagnostic information
It is strongly recommended that the diagnostic information made available is evaluated so that the applica-
tion can react accordingly.
The CoE parameter directory (CanOpen-over-EtherCAT) is used to manage the set values for the slave
concerned. Changes may, in some circumstances, have to be made here when commissioning a relatively
complex EtherCAT Slave. It can be accessed through the TwinCAT System Manager, see Fig. EL3102, CoE
directory:
Commissioning interfaces are being introduced as part of an ongoing process for EL/EP EtherCAT devices.
These are available in TwinCAT System Managers from TwinCAT 2.11R2 and above. They are integrated
into the System Manager through appropriately extended ESI configuration files.
Although the “Process Data”, “DC”, “Startup” and “CoE-Online” that used to be necessary for this are still
displayed, it is recommended that, if the commissioning aid is used, the automatically generated settings are
not changed by it.
The commissioning tool does not cover every possible application of an EL/EP device. If the available setting
options are not adequate, the user can make the DC, PDO and CoE settings manually, as in the past.
EtherCAT State: automatic default behaviour of the TwinCAT System Manager and manual operation
After the operating power is switched on, an EtherCAT Slave must go through the following statuses
• INIT
• PREOP
• SAFEOP
• OP
to ensure sound operation. The EtherCAT Master directs these statuses in accordance with the initialization
routines that are defined for commissioning the device by the ES/XML and user settings (Distributed Clocks
(DC), PDO, CoE). See also the section on "Principles of Communication, EtherCAT State Machine [} 21]" in
this connection. Depending how much configuration has to be done, and on the overall communication,
booting can take up to a few seconds.
The EtherCAT Master itself must go through these routines when starting, until it has reached at least the
OP target state.
The target state wanted by the user, and which is brought about automatically at start-up by TwinCAT, can
be set in the System Manager. As soon as TwinCAT reaches the status RUN, the TwinCAT EtherCAT
Master will approach the target states.
Standard setting
In addition, the target state of any particular Slave can be set in the “Advanced Settings” dialogue; the
standard setting is again OP.
Manual Control
There are particular reasons why it may be appropriate to control the states from the application/task/PLC.
For instance:
In that case it is appropriate in the PLC application to use the PLC function blocks from the TcEtherCAT.lib,
which is available as standard, and to work through the states in a controlled manner using, for instance,
FB_EcSetMasterState.
It is then useful to put the settings in the EtherCAT Master to INIT for master and slave.
EL/ES terminals are placed on the DIN rail at a coupler on the terminal strand. A Bus Coupler can supply the
EL terminals added to it with the E-bus system voltage of 5 V; a coupler is thereby loadable up to 2 A as a
rule. Information on how much current each EL terminal requires from the E-bus supply is available online
and in the catalogue. If the added terminals require more current than the coupler can supply, then power
feed terminals (e.g. EL9410) must be inserted at appropriate places in the terminal strand.
The pre-calculated theoretical maximum E-Bus current is displayed in the TwinCAT System Manager as a
column value. A shortfall is marked by a negative total amount and an exclamation mark; a power feed
terminal is to be placed before such a position.
From TwinCAT 2.11 and above, a warning message “E-Bus Power of Terminal...” is output in the logger
window when such a configuration is activated:
NOTE
Caution! Malfunction possible!
The same ground potential must be used for the E-Bus supply of all EtherCAT terminals in a terminal block!
Oversampling means that an analog or digital input device supplies not only one measured value for each
process data cycle/EtherCAT cycle (duration T), but several, which are determined at a constant interval
t < T. The ratio T/t is the oversampling factor n.
A channel thus offers not only one PDO for linking in the process data, as in the example here with the
EL3102, but n PDOs as in the case of the EL3702 and other oversampling terminals/boxes.
The definition of “oversampling” by the Beckhoff’s point of view shouldn’t be mixed up with the oversampling
process of a deltaSigma ADC:
• deltaSigma ADC: the frequency used by the ADC to sample the analogue signal is faster than a
multiple times than the frequency of the provided digital data (typically in kHz range). This is called
oversampling resulting by the functional principle of this converter type and serve amongst others for
anti-aliasing.
• Beckhoff: the device/ the terminal/box read of the used ADC (could be a deltaSigma ADC also) digital
sample data n-times more than the PLC/ bus cycle time is set and transfers every sample to the control
– bundled as an oversampling PDO package.
For example these both procedures are arranged sequentially by their technical implementation within the
EL3751 and can also be present simultaneously.
Fig. 141: Oversampling PDO of the EL37xx series and in the comparison with EL31xx
Accordingly the Scope2 (TC2) or ScopeView (TC3) can read in and display several PDOs per cycle in
correct time.
By a precondition of an already created TwinCAT 3 – project and a connected PLC with an oversampling
able terminal/box within the configuration it will be illustrated how an oversampling variable can be
represented by the Scope (as a standard part of the TwinCAT 3 environment). This will be explained by
means of several steps based on an example project “SCOPE_with_Oversampling“ as a standard PLC
project.
Within the TwinCAT 3 development environment an input variable as an array with respective amount than is
given by the oversampling factor have to be defined at first how it’s illustrated in an example for the POU
“MAIN” and an oversampling factor 10 with structured text (ST) as follows:
PROGRAM MAIN
VAR
aU1_Samples AT%I* : ARRAY[0..9] OF INT;
END_VAR
The identification “AT%I*” stands for swapping out this array variable to link it with the process data objects
(PDOs) of a terminal/box later. Notice that at least the number of elements has to be the same as the
oversampling factor so that the indices can be set from 0 to 9 also. As soon as the compiling procedure was
started and ended successful (in doing so no program code may be present) the array appears into the
solution explorer of the TwinCAT 3 development environment within the section PLC under “..Instance”.
The following illustration shows extracts of the solution explorer on the right. As an example that linking of an
array variable to a set of oversampling process data is represented herewith:
Fig. 143: Representation of a created PLC array variable („aUI_Samples“) to link with oversampling PDOs of
EL3773
When a POU is not needed onto the particular system, a referenced variable could be applied via a free task
also. If a free task is not existing still yet, it can be created by a right-click to “Task” of the project within
SYSTEM with “Add New Item…”.
The Task has to be inserted as “TwinCAT Task With Image” and also creates an “Inputs” and “Outputs”
folder therefore. The properties of the new (or as the case may be already existing) task must have activated
the attribute “Create symbols” to make them selectable by the “Target Browser” of the Scope later on. The
task cycle time has to be changed if so. Then, with10 x Oversampling 1 ms at 100 µs base time, resulting 10
ticks will be set by the usage of the EL3751 for example:
There’s a default value given for the Port number (301) that should be changed, if necessary. This number
has to make acquainted for the Scope, if applicable, later on. By a right click on “Inputs” that oversampling
based variable can now be appended with the fitting datatype of an array. „ARRAY [0..9] OF DINT“ referred
to as „Var 1“ in this case:
Fig. 146: Insertion of variable "Var 1" fitting to the oversampling (-factor)
By right click on “MAIN.aUI_Samples” (according to the last preceding paragraph Step 2a) or rather
“Var 1” (according to the last preceding paragraph Step 2b) within the Solution Explorer a window opens to
select the process data:
Fig. 147: Set up the link of the PLC array variable (left: for the last preceding paragraph Step 2a, right: for the
last preceding paragraph Step 2b)
Fig. 148: Select the EL3773 PDO "L1 Voltage Samples" to create a link to the PLC array variable
„aUI_Samples“
The selection of PDO "U1 Samples" of the EL3773 for “MAIN.aUI_Samples” based by the last preceding
paragraph Step 2a as illustrated above have to be done in the same way for “Var 1” accordingly.
Step 4: Selection of the PLC array variable for the Y-axis of the scope
Now the configuration will be activated ( ) and logged in the PLC ( ), so the array variable will be
visible for the target browser of the scope for being selected.
Thereby the drop down menu will be opened by right clicking on “Axis” (A) for selection of the scope features
(B):
Fig. 149: Selection of the oversampling variable with the target browser
By addressing the corresponding system that represents the PLC containing the array variable (“Any PC
(CX2040)” in this case) navigation up to the variable “aUI_Samples“ (C) have to be done.
Fig. 150: Appending the variable "aUI_Samples“ below “axis” within the scope project of the solution explorer
Using “Add symbol” displays the variable "aUI_Samples“ below “axis” within the scope project of the solution
explorer directly.
Now the program start has to be done with formally although there’s no program still yet. Using “Start
Recording“ the process data value of the oversampling PDO “L1 Voltage Samples “ via the linked PLC
array variable can be recorded time dependent now.
As an example a sine wave input measurement value (204.5 Hz) will be illustrated below:
Fig. 151: Example of recording a sine signal with 10 x oversampling at 1 ms measurement cycle time
The X-axis view was fitted properly by using “Panning X” after the recording was stopped .
Following the “Chart” property “Use X-Axis SubGrid” was set to true with 10 divisions as well as the
“ChannelNodeProperties” attribute “Marks” was set to “On” with the colors “Line Color” blue and “Mark Color”
red. Therefore the latter indicates that 10 oversampling measurement points by the red marks.
In former TwinCAT 3 versions (or a lower revision as specified in the table [} 115] above) the oversampling
PDO of the respective oversampling able terminal/box can be made visible for the ScopeView by activation
of the ADS server.
Fig. 152: Activation of the ADS server of the EtherCAT device (TwinCAT 3)
The activation of the server can be carried out by selection of “Image” within the left sided solution explorer:
„I/O → Devices → Device .. (EtherCAT) → Image“.
Next the register card “ADS” have to be selected to activate each checkbox „Enable ADS Server“ and
„Create symbols“ then (the port entry is done automatically).
Thereby it is possible to access process data without an embedded POU and accordingly without a linked
variable:
System requirements
A TwinCAT Scope2 must be installed on the system.
An oversampling-able terminal must be present in the configuration.
The data type of the variables is also conveyed to the TwinCAT Scope2 via the ADS data. Therefore the
array variable must be created
• in the PLC, see step 1a [} 124]
• or directly in the System Manager if only one free task is present, see step 1b [} 124]
The same settings are to be made in the Scope2 for both cases, see step 2 [} 126]
Since the channel data are to be used in the PLC, a linkable ARRAY variable must be created there, as
shown in the following example:
This then appears in the list in the System Manager; as a rule it can also be reached via ADS without further
measures since PLC variables are always created as ADS symbols in the background.
Note: the Scope2 can only "see" such variables in the variable browser if TwinCAT and the PLC are in RUN
mode.
So that the linking works, an array variable with the channel data must be present in the system manager;
i.e. each oversampling data package must be present in an array. This array variable must be defined and
created manually in the System Manager.
An ARRAY variable of the type as known by the PLC must be created in the syntax as known from the PLC.
In this example an array of 0..9 of type INT, i.e. with 10 fields.
If this variable is known to the System Manager, an instance of it can be assigned to an additional task with a
right-click. It appears in the overview, sorted according to bit size.
In this example the variable Var152 is created. It can now be linked with the PDO-Array of the respective
channel of the terminal/box.
If MatchingSize is activated in the dialog, the individual channels are offered directly.
So that the variables can also be found via ADS in the Scope2, the ADS symbols must be activated as well
as the Enable Auto-Start, otherwise the task will not run automatically. ADS symbol tables are then created
for all variables that have this task in their process data images.
So that the linking works, an array variable with the channel data of the respective terminal/box must be
present in the system manager; i.e. each oversampling data package must be present in an array. This array
variable must be defined and created manually; see above [} 124].
The array is then not to be opened; instead the array symbol is to be selected by right-clicking on
AddSymbol.
ForceOversampling and DataType INT16 must be set in the channel which has now been created. If
necessary SymbolBased must be temporarily deactivated in addition.
In order to check that individual oversampling values are really being logged, the Marks can be activated in
the Scope2. Please observe the interrelationships between task cycle time, sampling time of the Scope2
channel and oversampling factor.
An additional example illustrates the following image by representation of an oversampling – variable from
the EL3751 with 10 x oversampling:
Within the image was marked subsequently that the oversampling variable originated by the PLC was just
added to the Y-axis (observe selection of the PLC-POU name “MAIN” within the “ROUTES” tree). Herewith
“Force Oversampling“ was activated due to the oversampling variable is not provided by the terminal/box.
In former TwinCAT 2 versions (or a lower revision as specified in the table [} 115] above) the oversampling
PDO of the respective oversampling able terminal/box can be made visible for the Scope2 by activation of
the ADS server.
So the creation of a PLC variable can be disclaimed as well. Therefore the ADS server of the EtherCAT
Device where the oversampling able terminal/box is connected with have to be activated.
Fig. 167: Activation of the ADS server of the EtherCAT Device (TwinCAT 2)
The activation of the ADS server have to be carried out by selection of the “Device – Image” on the left sided
configuration tree:
„I/O – Configuration → I/O Devices → Device .. (EtherCAT) → Device .. – Image“.
Next the register card “ADS” have to be selected to activate each checkbox „Enable ADS Server“ and
„Create symbols“ then (the port entry is done automatically).
Thus with the Scope2 process data can be accessed via the target browser without an embedded POU and
without a variable reference respectively.
Beckhoff TwinCAT supports the Scope2 with some oversampling devices in a special way by automatically
calculating a special ADS array symbol in the background, which appears in the Scope2 in the variable
browser. This can be then linked as a variable and automatically brings along the array information.
Summary: an array variable have to be provided which is reachable via ADS. This can be a PLC variable of
a POU or a defined array variable by the system manager or alternatively the ADS server of the terminals/
boxes device is just activated. This is then detected by Scope2.
Delivery state
It is not necessary to make any particular settings when operation of the EL1262 is first started. The EL1262
operates as a normal 2-channel digital input terminal.
Distributed Clock
Distributed Clock Oversampling requires a clock generator in the terminal that triggers the individual data
sampling events. The local clock in the terminal, referred to as distributed clock, is used for this purpose.
The distributed clock represents a local clock in the ESC with the following characteristics:
• Unit 1 ns
• Zero point 1.1.2000 00:00
• Size 64 bit (sufficient for the next 584 years); however, some EtherCAT slaves only offer 32-bit
support, i.e. the variable overflows after approx. 4.2 seconds
• The EtherCAT master automatically synchronizes the local clock with the master clock in the EtherCAT
bus with a precision of < 100 ns.
Example:
The fieldbus/EtherCAT master is operated with a cycle time of 1 ms to match the higher-level PLC cycle time
of 1 ms, for example. This means that every 1 ms an Ethernet frame is sent to collect the process data from
the EL1262. The local terminal clock therefore triggers an interrupt in the ESC every 1 ms (1 kHz), in order to
make the process data available in time for collection by the EtherCAT frame. This first interrupt is called
SYNC1.
Let's assume the EL1262 is set to an oversampling rate n = 1000 in the TwinCAT System Manager. See
selection dialog for EL1262 oversampling factors in the TwinCAT System Manager. This causes the ESC to
generate a second interrupt in the terminal with an n-times higher frequency, in this case 1 MHz or 1 µs
period. This interrupt is called SYNC0. With each SYNC0 signal the voltage is sampled as a digital value
(0/1) and the corresponding values are sequentially stored in a buffer.
Generation of the SYNC0 pulse from the local synchronized clock within the distributed clock network
ensures that the input values are sampled at highly equidistant intervals with the period of the SYNC1 pulse.
The maximum oversampling factor depends on the memory size of the used ESC. In the KKYY0200 version
of the EL1262 it is n = 1000.
The values accumulated in the buffer are sent as a packet to the higher-level controller. With two channels
and n = 1000, 2 x 1000 = 2000 bits = 250 bytes of process data are transferred during each EtherCAT cycle.
The oversampling factor for the EL1262 can be set to predefined values between 1 and 1000.
Fig. 170: EL1262 oversampling factor selection dialog in the TwinCAT System Manager
Please note that the EL1262 process image characteristics change depending on the oversampling factor,
see Process data [} 134] description.
Oversampling factor
Regarding the calculation of SYNC0 from the SYNC1 pulse based on manual specification of an
oversampling factor, please note that for SYNC0 only integer values are calculated at nanosecond
intervals. Example: 187,500 µs is permitted, 333.3 µs is not! Values other than those offered in the
dialog are not possible. If implausible values are used, the terminal will reach the OP state, but its
behavior will correspond to an oversampling factor of 1, and only the first bit will contain valid data.
Example: For SYNC1/EtherCAT cycle = 1 ms oversampling factors such as 1, 2, 5 or 100 are per-
mitted, but not 3.
Input characteristics
The input characteristics of the EL1262 meet the requirements of EN61131-2:2003 Type 1.
Fig. 171: Typical EL1262 input characteristics. Beckhoff reserves the right to make unannounced changes.
The input circuit of the EL12xx is optimized for fast signal changes and for the fastest possible signal
acquisition. The duration required by a signal change (a rising or falling edge) to propagate from the
clamping point at the front of the terminal through to the logic of the central evaluation unit (ESC) is specified
for the EL12xx series as Ton/Toff < 1 µs, for both rising (Ton) and falling edges (Toff). The low absolute
magnitude of this propagation time means that the temperature drift of the propagation time is also very
small.
It should be borne in mind that the input circuit does not include any filtering. It has been optimized for the
fastest possible signal transmission from the input to the evaluation unit. Fast level changes or pulses in the
µs range therefore reach the evaluation unit unfiltered or unattenuated. It may be necessary to use screened
cables in order to eliminate interference from the surroundings.
The sensor/signal transducer must be able to generate sufficiently steep signal edges. The power supply unit
used should have sufficient buffer reserves to ensure that the signal reaches the terminal with a sufficiently
steep edge in spite of capacitive or inductive cable losses.
Start-up behavior
From the time the EtherCAT fieldbus starts up the EL1262 takes around 60 bus cycles until it delivers
process data in OP state for the first time and continuously.
Process data
The EL1262 offers a range of process data for transfer. In the default state the terminal appears in the
System Manager as shown in EL1262 default state.
In the EL1262 Distributed Clock options under Advanced Settings the time of the SYNC1 interrupt can be
shifted forward slightly, see EL1262 Advanced Settings, Distributed Clock. By activating the "Based on Input
Reference" checkbox the SYNC1 interrupt is shifted forward by a few µs. For further information please refer
to the Distributed Clock system description [} 132].
The option “Change Multi Link” can be used to link larger memory areas with continuous variables. Proceed
as follows:
Fig. 174: Select the variables in the terminal with the mouse
It should be considered that the input circuitry has little or no filtering, depending on the type. It is optimized
for fastest signal transmission from the input to the evaluation unit. Fast level changes/pulses in the µs
range, e.g. due to possible EMC influences, thus arrive at the evaluation unit unfiltered/undamped and are
possibly visible as a change of state of the input.
If necessary, shielded cables should be used to exclude environmental influences.
The SENT protocol is a point-to-point scheme for transmitting signal values from a sensor to a controller. It is
intended to allow high resolution data transmission with a lower system cost than available serial data
solutions. (1)
Hardware
The SENT protocol is a one-way, synchronous voltage interface which requires three wires: a signal line
(low state < 0.5V, high state > 4.1V), a supply voltage line (5 V) and a ground line.
Protocol
Data is transmitted in units of 4 bits (1 Nibble). The interval between two falling edges (single edge) of the
modulated signal with a constant amplitude voltage identifies the beginning of a frame and have to be
evaluated on the receiver side.
A SENT message is 32 bits long (8 Nibbles) and consists of the following components:
• 24 bits of signal data (6 Nibbles) that represents 2 measurement channels of 3 Nibbles each (such as
pressure and temperature)
• 4 bits (1 Nibble) for CRC error detection
• 4 bits (1 Nibble) of status/communication information
(1) SAE J2716 standard, sae.org, accessed 2011-09-13
The URN can be read out with the example to use further functions of it.
Download: (https://infosys.beckhoff.com/content/1033/el1262/Resources/zip/1675495563.zip)
Data:
• 1 ms cycle time
• 1000x oversampling on both channels
Connection diagram:
The EL1262 is able to work with an oversampling of 1 µs and also 1000 Bit per 1 ms are available.
A Sent telegram has a resolution of 3 µs per digit. So, if 1 µ resolution will be used, it is enough to interpret
the received data signal.
Connection diagram:
The application examples have been tested with a test configuration and are described accordingly.
Certain deviations when setting up actual applications are possible.
The following hardware and software were used for the test configuration:
• TwinCAT master PC with Windows XP Professional SP 3, TwinCAT version 2.10 (Build 1330) and
INTEL PRO/100 VE Ethernet adapter
• Beckhoff EtherCAT Coupler EK1100, EL1262 and EL9011 Terminals
• Inductive proximity limit switch, switching to positive potential, with 3-wire connection, max. switching
frequency: 3000 Hz
Activate and confirm the configuration (Fig. Activation of the configuration + Confirming the activation of the
configuration)
• Confirm new variable mapping, restart in RUN mode (Fig. Generate variable mapping + Restarting
TwinCAT in RUN mode)
• In TwinCAT PLC, under the “Project” menu, select “Rebuild all” to compile the project (Fig. Compile
project)
• In TwinCAT PLC: log in with the “F11” button, confirm loading the program (Fig. Confirming program
start), run the program with the “F5” button
This sample program illustrates how to read/write the data of a separate TEDS module (TEDS = Transducer
Electronic Data Sheet). Such TEDS modules are available on the market for retrofitting sensors or actuators,
in order to identify the device after installation or to read out specific data (calibration, manufacturer etc.).
The device used in this example was an HBM TEDS 1−TEDS−BOARD−L, version 2018.
This sample program is expressly intended as a feasibility demonstration. Specifically, there is no claim to
interoperability with any other TEDS modules. It is the responsibility of users to transfer the methods
formulated here to their own implementations.
This demonstration does not cover TEDS modules that are integrated in the sensor and communicate on the
sensor lines. This is common for IEPE (vibration) or strain gauges/measuring bridges. It is possible to
connect an IEPE sensor equipped with TEDS to Beckhoff ELM3602/ELM3604 terminals.
The configuration can control 2 TEDS modules. Only single-channel operation is shown in the example.
The voltage divider can be dimensioned with R1 = 2180 Ω (e.g. 680 Ω + 1500 Ω), R2 = 680 Ω and Z = 5,1 V
for example.
First the URN has to be read (A). Only then are further functions available.
The program determines the URN for each bit by reinitializing the module, since the terminal for the input
causes a time offset that is too large (see "Bit repeat count" at the top right).
Data can be written either by entering hexadecimal values (B) or a text string (ASCII) (C); hexadecimal
values must be separated by spaces in the text field. Which of the two inputs is to be used for writing can be
specified with the checkbox “Write ASCII data” (E):
Fig. 190: Visualization of the sample program for TEDS with EL1262-0050 and EL2262
The basic function after the identified URN is (D) reading (READ MEM) and writing (WRITE MEM) TEDS
data. By issuing such a command, the associated command statement is generated in the text field (H) and
can also be changed and then executed with "Execute command". Via +/- the TEDS address or page can be
changed (F). Both the start address and "page" can be entered directly for read / write accesses.
The hexadecimal data (B) of text field #1 to #4 each represent 32 bytes of the total read/write buffer size of
128 bytes, as configured in the sample program. If the checkbox “Complete read size” (G) is unchecked,
only text field #1 will be used for writing usually (except the module supports page sizes > 32 byte).
Accordingly, only the first characters of the ASCII data text will be written. In any case, the number of bytes
as a page of the TEDS module is configured will be used. Note, that the module usually supports write
access to addresses of a multiple value of the page size only. For example, assuming a page size of 32
bytes and the address 234 is input, an error 0x35 ‘writing fail’ will occur by a WRITE MEM command; but if
address 352 is used, this is valid and there is no error).
Selection of “Include application register” provides whether the application register shall be written or read
additionally (G).
Download:
https://infosys.beckhoff.com/content/1033/el1262/Resources/zip/5750275595.zip
See information about the TEDS feature of the ELM3xxx in section “ELM Features/ TEDS”.
Fig. 192: Search of the existing HW configuration for the EtherCAT configuration of the example
• Checking NetId: the “EtherCAT” tab of the EtherCAT device shows the configured NetId:
.
The first 4 numbers have to be identical with the project NetId of the target system. The project NetId
can be viewed within the TwinCAT environment above, where a pull down menu can be opened to
choose a target system (by clicking right in the text field). The number blocks are placed in brackets
there next to each computer name of a target system.
• Modify the NetId: By right clicking on “EtherCAT device” within the solution explorer a context menu
opens where “Change NetId...” have to be selected. The first four numbers of the NetId of the target
computer have to be entered; the both last values are 4.1 usually.
Example:
◦ NetId of project: myComputer (123.45.67.89.1.1)
◦ Entry via „Change NetId...“: 123.45.67.89.4.1
6 Appendix
NOTE
Only use TwinCAT 3 software!
A firmware update of Beckhoff IO devices must only be performed with a TwinCAT 3 installation. It is rec-
ommended to build as up-to-date as possible, available for free download on the Beckhoff website https://
www.beckhoff.com/en-us/.
To update the firmware, TwinCAT can be operated in the so-called FreeRun mode, a paid license is not re-
quired.
The device to be updated can usually remain in the installation location, but TwinCAT has to be operated in
the FreeRun. Please make sure that EtherCAT communication is trouble-free (no LostFrames etc.).
Other EtherCAT master software, such as the EtherCAT Configurator, should not be used, as they may not
support the complexities of updating firmware, EEPROM and other device components.
Storage locations
Customers can access the data via the EtherCAT fieldbus and its communication mechanisms. Acyclic
mailbox communication or register access to the ESC is used for updating or reading of these data.
The TwinCAT System Manager offers mechanisms for programming all three parts with new data, if the
slave is set up for this purpose. Generally the slave does not check whether the new data are suitable, i.e. it
may no longer be able to operate if the data are unsuitable.
The update using so-called bundle firmware is more convenient: in this case the controller firmware and the
ESI description are combined in a *.efw file; during the update both the firmware and the ESI are changed in
the terminal. For this to happen it is necessary
• for the firmware to be in a packed format: recognizable by the file name, which also contains the
revision number, e.g. ELxxxx-xxxx_REV0016_SW01.efw
• for password=1 to be entered in the download dialog. If password=0 (default setting) only the firmware
update is carried out, without an ESI update.
• for the device to support this function. The function usually cannot be retrofitted; it is a component of
many new developments from year of manufacture 2016.
NOTE
Risk of damage to the device!
ü Note the following when downloading new device files
a) Firmware downloads to an EtherCAT device must not be interrupted
b) Flawless EtherCAT communication must be ensured. CRC errors or LostFrames must be avoided.
c) The power supply must adequately dimensioned. The signal level must meet the specification.
ð In the event of malfunctions during the update process the EtherCAT device may become unusable and
require re-commissioning by the manufacturer.
The ESI device description is stored locally on the slave and loaded on start-up. Each device description has
a unique identifier consisting of slave name (9 characters/digits) and a revision number (4 digits). Each slave
configured in the System Manager shows its identifier in the EtherCAT tab:
Fig. 193: Device identifier consisting of name EL3204-0000 and revision -0016
The configured identifier must be compatible with the actual device description used as hardware, i.e. the
description which the slave has loaded on start-up (in this case EL3204). Normally the configured revision
must be the same or lower than that actually present in the terminal network.
For further information on this, please refer to the EtherCAT system documentation.
The simplest way to ascertain compliance of configured and actual device description is to scan the
EtherCAT boxes in TwinCAT mode Config/FreeRun:
Fig. 194: Scan the subordinate field by right-clicking on the EtherCAT device
If the found field matches the configured field, the display shows
otherwise a change dialog appears for entering the actual data in the configuration.
In this example in Fig. Change dialog, an EL3201-0000-0017 was found, while an EL3201-0000-0016 was
configured. In this case the configuration can be adapted with the Copy Before button. The Extended
Information checkbox must be set in order to display the revision.
The new ESI description is selected in the following dialog, see Fig. Selecting the new ESI. The checkbox
Show Hidden Devices also displays older, normally hidden versions of a slave.
A progress bar in the System Manager shows the progress. Data are first written, then verified.
Beckhoff EtherCAT slaves feature serial numbers applied by laser. The serial number has the following
structure: KK YY FF HH
12 - week of production 12
10 - year of production 2010
03 - firmware version 03
02 - hardware version 02
The TwinCAT System Manager shows the version of the controller firmware if the master can access the
slave online. Click on the E-Bus Terminal whose controller firmware you want to check (in the example
terminal 2 (EL3204)) and select the tab CoE Online (CAN over EtherCAT).
In Fig. Display of EL3204 firmware version the firmware version of the selected EL3204 is shown as 03 in
CoE entry 0x100A.
In (A) TwinCAT 2.11 shows that the Online CoE directory is currently displayed. If this is not the case, the
Online directory can be loaded via the Online option in Advanced Settings (B) and double-clicking on
AllObjects.
Switch to the Online tab to update the controller firmware of a slave, see Fig. Firmware Update.
Proceed as follows, unless instructed otherwise by Beckhoff support. Valid for TwinCAT 2 and 3 as
EtherCAT master.
• Switch TwinCAT system to ConfigMode/FreeRun with cycle time >= 1 ms (default in ConfigMode is
4 ms). A FW-Update during real time operation is not recommended.
The firmware version number included in the terminal serial number contains both firmware components. If
one of these firmware components is modified this version number is updated.
The TwinCAT System Manager indicates the FPGA firmware version. Click on the Ethernet card of your
EtherCAT strand (Device 2 in the example) and select the Online tab.
The Reg:0002 column indicates the firmware version of the individual EtherCAT devices in hexadecimal and
decimal representation.
If the column Reg:0002 is not displayed, right-click the table header and select Properties in the context
menu.
The Advanced Settings dialog appears where the columns to be displayed can be selected. Under
Diagnosis/Online View select the '0002 ETxxxx Build' check box in order to activate the FPGA firmware
version display.
Update
The following sequence order have to be met if no other specifications are given (e.g. by the Beckhoff
support):
• Switch TwinCAT system to ConfigMode/FreeRun with cycle time >= 1 ms (default in ConfigMode is
4 ms). A FW-Update during real time operation is not recommended.
• In the TwinCAT System Manager select the terminal for which the FPGA firmware is to be updated (in
the example: Terminal 5: EL5001) and
click the Advanced Settings button in the EtherCAT tab:
• The Advanced Settings dialog appears. Under ESC Access/E²PROM/FPGA click on Write FPGA
button:
• Select the file (*.rbf) with the new FPGA firmware, and transfer it to the EtherCAT device:
NOTE
Risk of damage to the device!
A download of firmware to an EtherCAT device must not be interrupted in any case! If you interrupt this
process by switching off power supply or disconnecting the Ethernet link, the EtherCAT device can only be
recommissioned by the manufacturer!
Select the required slaves and carry out the firmware update in BOOTSTRAP mode as described above.
Double-click on SubIndex 001 to enter the Set Value dialog. Enter the value 1684107116 in field Dec or the
value 0x64616F6C in field Hex and confirm with OK (Fig. Entering a restore value in the Set Value dialog).
All backup objects are reset to the delivery state.
Please contact your Beckhoff branch office or representative for local support and service on Beckhoff
products!
The addresses of Beckhoff's branch offices and representatives round the world can be found on her internet
pages: https://www.beckhoff.com
You will also find further documentation for Beckhoff components there.
Beckhoff Support
Support offers you comprehensive technical assistance, helping you not only with the application of
individual Beckhoff products, but also with other, wide-ranging services:
• support
• design, programming and commissioning of complex automation systems
• and extensive training program for Beckhoff system components
Hotline: +49 5246 963 157
Fax: +49 5246 963 9157
e-mail: support@beckhoff.com
Beckhoff Service
The Beckhoff Service Center supports you in all matters of after-sales service:
• on-site service
• repair service
• spare parts service
• hotline service
Hotline: +49 5246 963 460
Fax: +49 5246 963 479
e-mail: service@beckhoff.com
Beckhoff Headquarters
Huelshorstweg 20
33415 Verl
Germany
Phone: +49 5246 963 0
Fax: +49 5246 963 198
e-mail: info@beckhoff.com
web: https://www.beckhoff.com
List of Illustrations
Fig. 1 EL5021 EL terminal, standard IP20 IO device with serial/ batch number and revision ID (since
2014/01)....................................................................................................................................... 9
Fig. 2 EK1100 EtherCAT coupler, standard IP20 IO device with serial/ batch number......................... 9
Fig. 3 CU2016 switch with serial/ batch number.................................................................................... 10
Fig. 4 EL3202-0020 with serial/ batch number 26131006 and unique ID-number 204418 ................... 10
Fig. 5 EP1258-00001 IP67 EtherCAT Box with batch number/ date code 22090101 and unique se-
rial number 158102...................................................................................................................... 10
Fig. 6 EP1908-0002 IP67 EtherCAT Safety Box with batch number/ date code 071201FF and
unique serial number 00346070 .................................................................................................. 10
Fig. 7 EL2904 IP20 safety terminal with batch number/ date code 50110302 and unique serial num-
ber 00331701............................................................................................................................... 11
Fig. 8 ELM3604-0002 terminal with unique ID number (QR code) 100001051 and serial/ batch num-
ber 44160201............................................................................................................................... 11
Fig. 9 BIC as data matrix code (DMC, code scheme ECC200)............................................................. 12
Fig. 10 EL1262-0000 ............................................................................................................................... 14
Fig. 11 EL1262-0050 ............................................................................................................................... 14
Fig. 12 System manager current calculation .......................................................................................... 19
Fig. 13 EtherCAT tab -> Advanced Settings -> Behavior -> Watchdog .................................................. 20
Fig. 14 States of the EtherCAT State Machine........................................................................................ 22
Fig. 15 “CoE Online” tab .......................................................................................................................... 24
Fig. 16 Startup list in the TwinCAT System Manager ............................................................................. 25
Fig. 17 Offline list ..................................................................................................................................... 26
Fig. 18 Online list .................................................................................................................................... 26
Fig. 19 Spring contacts of the Beckhoff I/O components......................................................................... 29
Fig. 20 Attaching on mounting rail ........................................................................................................... 30
Fig. 21 Disassembling of terminal............................................................................................................ 31
Fig. 22 Power contact on left side............................................................................................................ 32
Fig. 23 Standard wiring............................................................................................................................ 34
Fig. 24 Pluggable wiring .......................................................................................................................... 34
Fig. 25 High Density Terminals................................................................................................................ 35
Fig. 26 Mounting a cable on a terminal connection ................................................................................. 36
Fig. 27 Recommended distances for standard installation position ........................................................ 38
Fig. 28 Other installation positions .......................................................................................................... 39
Fig. 29 Correct positioning....................................................................................................................... 40
Fig. 30 Incorrect positioning..................................................................................................................... 40
Fig. 31 EL1262-0000 ............................................................................................................................... 45
Fig. 32 EL1262-0050 ............................................................................................................................... 46
Fig. 33 Relationship between user side (commissioning) and installation............................................... 48
Fig. 34 Control configuration with Embedded PC, input (EL1004) and output (EL2008) ........................ 49
Fig. 35 Initial TwinCAT 2 user interface................................................................................................... 50
Fig. 36 Selection of the target system ..................................................................................................... 51
Fig. 37 Specify the PLC for access by the TwinCAT System Manager: selection of the target system .. 51
Fig. 38 Select “Scan Devices...” .............................................................................................................. 52
Fig. 39 Automatic detection of I/O devices: selection the devices to be integrated................................. 52
Fig. 40 Mapping of the configuration in the TwinCAT 2 System Manager............................................... 53
Fig. 41 Reading of individual terminals connected to a device................................................................ 53
Fig. 88 Information window for faulty ESI file (left: TwinCAT 2; right: TwinCAT 3).................................. 81
Fig. 89 Using the ESI Updater (>= TwinCAT 2.11).................................................................................. 83
Fig. 90 Using the ESI Updater (TwinCAT 3)............................................................................................ 83
Fig. 91 Append EtherCAT device (left: TwinCAT 2; right: TwinCAT 3) ................................................... 84
Fig. 92 Selecting the EtherCAT connection (TwinCAT 2.11, TwinCAT 3)............................................... 84
Fig. 93 Selecting the Ethernet port ......................................................................................................... 84
Fig. 94 EtherCAT device properties (TwinCAT 2) ................................................................................... 85
Fig. 95 Appending EtherCAT devices (left: TwinCAT 2; right: TwinCAT 3)............................................. 85
Fig. 96 Selection dialog for new EtherCAT device ................................................................................. 86
Fig. 97 Display of device revision ........................................................................................................... 86
Fig. 98 Display of previous revisions ...................................................................................................... 87
Fig. 99 Name/revision of the terminal ...................................................................................................... 87
Fig. 100 EtherCAT terminal in the TwinCAT tree (left: TwinCAT 2; right: TwinCAT 3).............................. 88
Fig. 101 Differentiation local/target system (left: TwinCAT 2; right: TwinCAT 3)....................................... 89
Fig. 102 Scan Devices (left: TwinCAT 2; right: TwinCAT 3) ...................................................................... 89
Fig. 103 Note for automatic device scan (left: TwinCAT 2; right: TwinCAT 3)........................................... 89
Fig. 104 Detected Ethernet devices .......................................................................................................... 90
Fig. 105 Example default state .................................................................................................................. 90
Fig. 106 Installing EthetCAT terminal with revision -1018 ......................................................................... 91
Fig. 107 Detection of EtherCAT terminal with revision -1019 .................................................................... 91
Fig. 108 Scan query after automatic creation of an EtherCAT device (left: TwinCAT 2; right: Twin-
CAT 3) ......................................................................................................................................... 91
Fig. 109 Manual triggering of a device scan on a specified EtherCAT device (left: TwinCAT 2; right:
TwinCAT 3).................................................................................................................................. 92
Fig. 110 Scan progressexemplary by TwinCAT 2 ..................................................................................... 92
Fig. 111 Config/FreeRun query (left: TwinCAT 2; right: TwinCAT 3)......................................................... 92
Fig. 112 Displaying of “Free Run” and “Config Mode” toggling right below in the status bar .................... 92
Fig. 113 TwinCAT can also be switched to this state by using a button (left: TwinCAT 2; right: Twin-
CAT 3) ......................................................................................................................................... 92
Fig. 114 Online display example ............................................................................................................... 93
Fig. 115 Faulty identification ...................................................................................................................... 93
Fig. 116 Identical configuration (left: TwinCAT 2; right: TwinCAT 3) ......................................................... 94
Fig. 117 Correction dialog ......................................................................................................................... 94
Fig. 118 Name/revision of the terminal ...................................................................................................... 95
Fig. 119 Correction dialog with modifications ........................................................................................... 96
Fig. 120 Dialog “Change to Compatible Type…” (left: TwinCAT 2; right: TwinCAT 3) .............................. 96
Fig. 121 TwinCAT 2 Dialog Change to Alternative Type ........................................................................... 96
Fig. 122 Branch element as terminal EL3751............................................................................................ 97
Fig. 123 “General” tab................................................................................................................................ 97
Fig. 124 “EtherCAT” tab............................................................................................................................. 98
Fig. 125 “Process Data” tab....................................................................................................................... 99
Fig. 126 Configuring the process data....................................................................................................... 100
Fig. 127 “Startup” tab................................................................................................................................. 101
Fig. 128 “CoE - Online” tab........................................................................................................................ 102
Fig. 129 Dialog “Advanced settings”.......................................................................................................... 103
Fig. 130 “Online” tab .................................................................................................................................. 103
Fig. 131 “DC” tab (Distributed Clocks)....................................................................................................... 104
Fig. 132 Selection of the diagnostic information of an EtherCAT Slave ................................................... 106
Fig. 133 Basic EtherCAT Slave Diagnosis in the PLC............................................................................... 107
Fig. 134 EL3102, CoE directory ................................................................................................................ 109
Fig. 135 Example of commissioning aid for a EL3204 .............................................................................. 110
Fig. 136 Default behaviour of the System Manager .................................................................................. 111
Fig. 137 Default target state in the Slave .................................................................................................. 111
Fig. 138 PLC function blocks .................................................................................................................... 112
Fig. 139 Illegally exceeding the E-Bus current ......................................................................................... 113
Fig. 140 Warning message for exceeding E-Bus current ......................................................................... 113
Fig. 141 Oversampling PDO of the EL37xx series and in the comparison with EL31xx ........................... 114
Fig. 142 Adding a Scope project into an already existing project .............................................................. 116
Fig. 143 Representation of a created PLC array variable („aUI_Samples“) to link with oversampling
PDOs of EL3773.......................................................................................................................... 117
Fig. 144 Insertion of a free task ................................................................................................................. 117
Fig. 145 Task property "Create symbols" must be activated ..................................................................... 118
Fig. 146 Insertion of variable "Var 1" fitting to the oversampling (-factor).................................................. 118
Fig. 147 Set up the link of the PLC array variable (left: for the last preceding paragraph Step 2a, right:
for the last preceding paragraph Step 2b) ................................................................................... 119
Fig. 148 Select the EL3773 PDO "L1 Voltage Samples" to create a link to the PLC array variable
„aUI_Samples“............................................................................................................................. 119
Fig. 149 Selection of the oversampling variable with the target browser................................................... 120
Fig. 150 Appending the variable "aUI_Samples“ below “axis” within the scope project of the solution
explorer........................................................................................................................................ 120
Fig. 151 Example of recording a sine signal with 10 x oversampling at 1 ms measurement cycle time ... 121
Fig. 152 Activation of the ADS server of the EtherCAT device (TwinCAT 3) ............................................ 122
Fig. 153 Direct access to PDOs of the terminal by ScopeView ................................................................. 122
Fig. 154 PLC declaration ........................................................................................................................... 124
Fig. 155 PLC in the System Manager........................................................................................................ 124
Fig. 156 Add Variable Type ....................................................................................................................... 124
Fig. 157 Definition of the variable type ...................................................................................................... 125
Fig. 158 Overview of declared types ......................................................................................................... 125
Fig. 159 Linking ......................................................................................................................................... 126
Fig. 160 Array variables of an oversampling terminal................................................................................ 126
Fig. 161 Settings in the additional task ...................................................................................................... 126
Fig. 162 Variable browser up to the array VAR152 ................................................................................... 127
Fig. 163 AddSymbol on the array .............................................................................................................. 127
Fig. 164 Channel settings .......................................................................................................................... 127
Fig. 165 Activation of the marks ................................................................................................................ 128
Fig. 166 Illustration of a 10 x oversampling variable of the EL3751 by the Scope2 .................................. 129
Fig. 167 Activation of the ADS server of the EtherCAT Device (TwinCAT 2)............................................ 130
Fig. 168 Direct access of the Scope2 to the terminal's PDOs ................................................................... 130
Fig. 169 Automatically calculated array variable (red) in the Scope2........................................................ 131
Fig. 170 EL1262 oversampling factor selection dialog in the TwinCAT System Manager ........................ 133
Fig. 171 Typical EL1262 input characteristics. Beckhoff reserves the right to make unannounced
changes. ...................................................................................................................................... 134
Fig. 172 EL1262 default state.................................................................................................................... 135
Fig. 173 EL1262 Advanced Settings, Distributed Clocks .......................................................................... 136
Fig. 174 Select the variables in the terminal with the mouse..................................................................... 137
Fig. 175 Right-click, Change Multi Link ..................................................................................................... 138
Fig. 176 Select the variable range from the task ....................................................................................... 139
Fig. 177 SENT Protokoll ............................................................................................................................ 140
Fig. 178 Extract of the ST implementation within TwinCAT....................................................................... 140
Fig. 179 Wiring for example program 1 ..................................................................................................... 141
Fig. 180 Wiring for example program 2 ..................................................................................................... 142
Fig. 181 Searching the Ethernet adapter................................................................................................... 143
Fig. 182 Selection and confirmation of the Ethernet adapter..................................................................... 143
Fig. 183 Activation of the configuration...................................................................................................... 143
Fig. 184 Confirming the activation of the configuration.............................................................................. 144
Fig. 185 Generating variable mapping....................................................................................................... 144
Fig. 186 Restarting TwinCAT in RUN mode .............................................................................................. 144
Fig. 187 Compile project............................................................................................................................ 144
Fig. 188 Confirming program start ............................................................................................................. 145
Fig. 189 Wiring for sample program 3 ....................................................................................................... 146
Fig. 190 Visualization of the sample program for TEDS with EL1262-0050 and EL2262 ......................... 147
Fig. 191 Opening the *. tnzip archive......................................................................................................... 148
Fig. 192 Search of the existing HW configuration for the EtherCAT configuration of the example ........... 148
Fig. 193 Device identifier consisting of name EL3204-0000 and revision -0016 ...................................... 150
Fig. 194 Scan the subordinate field by right-clicking on the EtherCAT device .......................................... 151
Fig. 195 Configuration is identical ............................................................................................................. 151
Fig. 196 Change dialog ............................................................................................................................. 152
Fig. 197 EEPROM Update ........................................................................................................................ 152
Fig. 198 Selecting the new ESI.................................................................................................................. 153
Fig. 199 Display of EL3204 firmware version ............................................................................................ 154
Fig. 200 Firmware Update ......................................................................................................................... 155
Fig. 201 FPGA firmware version definition ............................................................................................... 157
Fig. 202 Context menu Properties ............................................................................................................ 157
Fig. 203 Dialog Advanced Settings ........................................................................................................... 158
Fig. 204 Multiple selection and firmware update ...................................................................................... 160
Fig. 205 Selecting the Restore default parameters PDO........................................................................... 161
Fig. 206 Entering a restore value in the Set Value dialog.......................................................................... 161