El 6601
El 6601
EL6601, EL6614
Version: 4.2
Date: 2019-05-03
Table of contents
Table of contents
1 Foreword .................................................................................................................................................... 5
1.1 Notes on the documentation.............................................................................................................. 5
1.2 Safety instructions ............................................................................................................................. 6
1.3 Documentation issue status .............................................................................................................. 7
1.4 Version identification of EtherCAT devices ....................................................................................... 8
2 Product overview..................................................................................................................................... 12
2.1 Introduction ...................................................................................................................................... 12
2.2 Technical data ................................................................................................................................. 14
2.3 Basic function principles .................................................................................................................. 14
2.4 EL66xx - Non Realtime.................................................................................................................... 17
2.5 EL66xx and Beckhoff network variables.......................................................................................... 22
2.5.1 Explanation network variables ......................................................................................... 22
2.5.2 Settings in the System Manager...................................................................................... 24
2.5.3 Notes ............................................................................................................................... 25
2.5.4 Suppress publisher .......................................................................................................... 25
2.5.5 Filter subscribers ............................................................................................................. 26
2.5.6 Setting up TwinCAT 2.10................................................................................................. 26
2.5.7 Setting up TwinCAT 2.11................................................................................................. 29
2.6 Configuration in the CX20x0 & CX50x0 system .............................................................................. 30
5 Commissioning........................................................................................................................................ 50
5.1 TwinCAT Development Environment .............................................................................................. 50
5.1.1 Installation of the TwinCAT real-time driver..................................................................... 50
5.1.2 Notes regarding ESI device description........................................................................... 56
5.1.3 OFFLINE configuration creation ...................................................................................... 60
5.1.4 ONLINE configuration creation ........................................................................................ 65
5.1.5 EtherCAT subscriber configuration.................................................................................. 73
5.2 General Notes - EtherCAT Slave Application .................................................................................. 82
5.3 Object description and parameterization ......................................................................................... 90
5.3.1 Objects for commissioning............................................................................................... 90
1 Foreword
This description is only intended for the use of trained specialists in control and automation engineering who
are familiar with the applicable national standards.
It is essential that the documentation and the following notes and explanations are followed when installing
and commissioning these components.
It is the duty of the technical personnel to use the documentation published at the respective time of each
installation and commissioning.
The responsible staff must ensure that the application or use of the products described satisfy all the
requirements for safety, including all the relevant laws, regulations, guidelines and standards.
Disclaimer
The documentation has been prepared with care. The products described are, however, constantly under
development.
We reserve the right to revise and change the documentation at any time and without prior announcement.
No claims for the modification of products that have already been supplied may be made on the basis of the
data, diagrams and descriptions in this documentation.
Trademarks
Beckhoff®, TwinCAT®, EtherCAT®, EtherCAT P®, Safety over EtherCAT®, TwinSAFE®, XFC® and XTS® are
registered trademarks of and licensed by Beckhoff Automation GmbH.
Other designations used in this publication may be trademarks whose use by third parties for their own
purposes could violate the rights of the owners.
Patent Pending
The EtherCAT Technology is covered, including but not limited to the following patent applications and
patents: EP1590927, EP1789857, DE102004044764, DE102007017835 with corresponding applications or
registrations in various other countries.
The TwinCAT Technology is covered, including but not limited to the following patent applications and
patents: EP0851348, US6167425 with corresponding applications or registrations in various other countries.
EtherCAT® is registered trademark and patented technology, licensed by Beckhoff Automation GmbH,
Germany.
Copyright
Exclusion of liability
All the components are supplied in particular hardware and software configurations appropriate for the
application. Modifications to hardware or software configurations other than those described in the
documentation are not permitted, and nullify the liability of Beckhoff Automation GmbH & Co. KG.
Personnel qualification
This description is only intended for trained specialists in control, automation and drive engineering who are
familiar with the applicable national standards.
Description of instructions
DANGER
Serious risk of injury!
Failure to follow this safety instruction directly endangers the life and health of persons.
WARNING
Risk of injury!
Failure to follow this safety instruction endangers the life and health of persons.
CAUTION
Personal injuries!
Failure to follow this safety instruction can lead to injuries to persons.
NOTE
Damage to environment/equipment or data loss
Failure to follow this instruction can lead to environmental damage, equipment damage or data loss.
Tip or pointer
This symbol indicates information that contributes to better understanding.
Notes
• The elements mentioned above result in the technical designation. EL3314-0000-0016 is used in the
example below.
• EL3314-0000 is the order identifier, in the case of “-0000” usually abbreviated to EL3314. “-0016” is the
EtherCAT revision.
• The order identifier is made up of
- family key (EL, EP, CU, ES, KL, CX, etc.)
- type (3314)
- version (-0000)
• The revision -0016 shows the technical progress, such as the extension of features with regard to the
EtherCAT communication, and is managed by Beckhoff.
In principle, a device with a higher revision can replace a device with a lower revision, unless specified
otherwise, e.g. in the documentation.
Associated and synonymous with each revision there is usually a description (ESI, EtherCAT Slave
Information) in the form of an XML file, which is available for download from the Beckhoff web site.
From 2014/01 the revision is shown on the outside of the IP20 terminals, see Fig. “EL5021 EL terminal,
standard IP20 IO device with batch number and revision ID (since 2014/01)”.
• The type, version and revision are read as decimal numbers, even if they are technically saved in
hexadecimal.
Identification number
Beckhoff EtherCAT devices from the different lines have different kinds of identification numbers:
The serial number for Beckhoff IO devices is usually the 8-digit number printed on the device or on a sticker.
The serial number indicates the configuration in delivery state and therefore refers to a whole production
batch, without distinguishing the individual modules of a batch.
Example with
Ser. no.: 12063A02: 12 - production week 12 06 - production year 2006 3A - firmware version 3A 02 -
hardware version 02
Exceptions can occur in the IP67 area, where the following syntax can be used (see respective device
documentation):
Syntax: D ww yy x y z u
D - prefix designation
ww - calendar week
yy - year
x - firmware version of the bus PCB
y - hardware version of the bus PCB
z - firmware version of the I/O PCB
u - hardware version of the I/O PCB
Example: D.22081501 calendar week 22 of the year 2008 firmware version of bus PCB: 1 hardware version
of bus PCB: 5 firmware version of I/O PCB: 0 (no firmware necessary for this PCB) hardware version of I/O
PCB: 1
In addition, in some series each individual module has its own unique serial number.
Examples of markings
Fig. 1: EL5021 EL terminal, standard IP20 IO device with serial/ batch number and revision ID (since
2014/01)
Fig. 2: EK1100 EtherCAT coupler, standard IP20 IO device with serial/ batch number
Fig. 4: EL3202-0020 with serial/ batch number 26131006 and unique ID-number 204418
Fig. 5: EP1258-00001 IP67 EtherCAT Box with batch number/ date code 22090101 and unique serial
number 158102
Fig. 6: EP1908-0002 IP67 EtherCAT Safety Box with batch number/ date code 071201FF and unique serial
number 00346070
Fig. 7: EL2904 IP20 safety terminal with batch number/ date code 50110302 and unique serial number
00331701
Fig. 8: ELM3604-0002 terminal with unique ID number (QR code) 100001051 and serial/ batch number
44160201
2 Product overview
2.1 Introduction
The switch terminals for Ethernet are used for decentralized connection of random Ethernet devices to the
EtherCAT terminal network. The EtherCAT system relays the Ethernet communication of the connected
devices fully transparent and collision-free.
The 4 port Ethernet switch terminal EL6614 purposefully forwards the incoming frames from the ports to the
destination ports. In full duplex mode, it thus enables collision-free communication of the connected devices
with each other.
Any number of EL6601/EL6614 can be used simultaneously and at any position in the EtherCAT terminal
network. No configuration is required. In conjunction with the network port at the EtherCAT master the
EL6601/EL6614 devices operate like a virtual switch whose ports are distributed in the field. The EtherCAT
fieldbus is the backbone of this switch.
Further benefits underline the particular suitability for the application in industrial environments:
• Compact design in EtherCAT terminal housing
• 10/100 MBaud, half or full duplex, with automatic baud rate detection
• Autocrossing (automatic detection of crossed lines)
LEDs
* only EL6614
Connections
max 32 Publishers with total of max. 1024 bytes total data [} 22]
max 32 Subscriber with total of max. 1024 bytes total data [} 22]
Distributed Clocks no
Diagnostics Status-LEDs, CoE data about ADS
Power supply via the E-bus
Current consumption via E-bus typ. 310 mA typ. 450 mA
Electrical isolation 500 V (E-Bus/Ethernet)
Bit width in process image -
Configuration TwinCAT System Manager/EtherCAT Master
Weight approx. 75 g approx. 85 g
Permissible ambient temperature -25°C ... +60°C (extended Horizontal installation position:
range during operation temperature range) -25°C ... +60°C (extended
temperature range)
Diagnostics
Online diagnostics
The following objects are available for initial diagnostic in the CoE directory:
• 0xFA01, subindex 01: Frame Counter Rx (incoming to RJ45 socket).
• 0xFA01, subindex 02: Frame Counter Tx (outgoing from RJ45 socket).
The values can be read from the controller using PLC function blocks (FB_EcCoeSdoRead in
TcEtherCAT.lib).
This and further diagnostic information from the CoE of the EL66xx are accessible via https://
infosys.beckhoff.com/content/1033/el6601_el6614/Resources/zip/2349552907.zip .
Error LED
If the occurrence of an overrun causes data to be lost, higher protocol layers in an Ethernet network are
responsible for repeating the transmission.
Overruns
The following measures can be used to counter overruns:
• activating the Subscriber Filter [} 22] in the EL66xx concerned
• Increasing/decelerating the cycle time of the publisher
• Suppressing temporarily publisher transmission or modulo in the System Manager
• Reducing/accelerating the EtherCAT cycle time of the subscriber, so that more data are fetched
by the EL66xx
Cable redundancy
If the EL66xx is operated in a system with cable redundancy, please keep the following in mind:
• real-time operation with network variables is possible
• in the event of non-real-time operation with IP transfer the IP traffic is routed via the primary EtherCAT
port. Therefore the Windows IP settings of this port are also used.
If there is no longer a link to this port, from Windows under TwinCAT 2 or 3 there is also no IP
communication to this port currently.
For this reason, do not let the Ethernet connection between the primary EtherCAT port and the first
EtherCAT slave fail, since otherwise IP communication is no longer possible via the EL66xx.
Fig. 13: Connection failure between primary EtherCAT port and 1st slave (X)
In addition to regular cyclical process data exchange an EtherCAT master offers a further mechanism for
transporting data to an EtherCAT slave or reading data from it. This mechanism is used for one-time or
dynamically alternating Data Exchange, such as e.g. the parameterization of an EtherCAT slave. Mailbox
communication can also be used for transporting large data blocks acyclically on request from master or
slave. This additional communication takes place between the cyclical process data frames (the conventional
EtherCAT frames) on the EtherCAT bus.
The EoE method (Ethernet over EtherCAT) is used for the EL66xx. Dedicated settings are available for this
in the System Manager.
Data throughput
with an EtherCAT cycle time of 100 µs and a mailbox size of 1024 bytes.
Fig. 14: Real frame structure from the TwinCAT System Manager
Address assignment
From FW03 onwards, the EL6601/6614 can also assign IP addresses to connected devices and works as a
DHCP or BOOTP server for one device. The following settings are required in the System Manager (EL66xx
--> Advanced Settings --> Mailbox --> EoE):
• Setting "Switch Port", Fig. Default setting of the EL66xx as switch port without IP address assignment.
The EL66xx works like a normal switch and passes Ethernet frames transparently through to TwinCAT/
Windows
• Setting for “IP Port”, Fig. From FW03: Settings for dynamically assigned IP address
The EL66xx works with address assignment to one connected Ethernet device. A DHCP or a BootP
Client must be activated in the device (refer to the network adaptor settings in the operating system).
The EL66xx responds to the device’s corresponding DHCP/BootP query by assigning the specified IP
address/subnet mask to the device. In the DHCP method this address is regularly queried by the client
and assigned to the server/EL66xx.
Fig. 15: Default setting of the EL66xx as switch port without IP address assignment
Please note:
• The “DHCP” checkbox must not be used - the “IP address” checkbox activates the DHCP/BootP
function in the EL66xx.
• The Gateway, Mask and Server settings are likewise communicated to the client/the device
• Only one address can be assigned, i.e. no switch with connected subscribers may follow.
• the address range must be identical to that of the EtherCAT adapter.
• DHCP Server Identifier: several DHCP Servers need a ServerID in the response telegram.
Solution for the EL6601 from firmware 15: the value 0x1000 has to be entered in the object 0xF800:01.
If a Default Gateway is registered in the EL6601, it is used as a DHCP Server Identifier.
Mailbox settings
The mailbox size can be modified in the Beckhoff TwinCAT System Manager:
By default the mailbox is set to 522 Byte Input and 522 Byte Output (20 Ahex), see Fig. Default Settings of the
Mailbox, Entries for SyncManager 0 and 1. To increase the data throughput the size of the mailbox can be
increased to 1024 Byte, see Fig. Increasing the Size of the Mailbox.
Under EL6601 -> EtherCAT tab -> "Advanced Settings…" -> "Mailbox" the "Out Size" can be set to
hexadecimal values between 42dec/2Ahex and 1024dec/400hex bytes. Ethernet frames that are larger than the
EL6601 mailbox are fragmented by the EL6601 or the EtherCAT master and reassembled after passing
through the EtherCAT system.
The EL66xx devices in the TwinCAT system generally appear as virtual switches, with the EtherCAT system
as the "backbone".
The required settings will be found under TwinCAT | EtherCAT device | Advanced settings
Notes
• If a large number of EL66xx devices are used along the EtherCAT strand it may be helpful to increase
the value of MaxFrames
• If the EL66xx is used exclusively to transfer network variables, ConnectToTcpStack should be
deactivated
• IP-routing is active by default. This can also be checked by entering "ipconfig /all" on the command line
(Windows)
Network variables
The EL66xx support sending/receiving network variables. This applies for the EL6601 as of Firmware 07, for
the EL6614 as of Firmware 03.
A maximum of 32 for each, publishers and subscriber, are permitted per EL66xx.
Hardware replacement
If the system was designed with a previous EL6601 version (EL6601-0000-0000), this can be re-
placed with versions from EL6601-0000-0017 without problem. If the system was designed for ver-
sion EL6601-0000-0017 or higher, replacement with a previous version is not possible due to un-
supported network variables.
Network variables are specially configured Ethernet frames that enable Beckhoff devices to communicate
with each other in real-time via Ethernet. Such device can send (publisher) or receive (subscriber)
messages.
An Ethernet frame is sent for each publisher (Ethernet-based). A maximum of 1500 bytes of data can thus
be sent per publisher. Within a publisher/subscriber several variables (publisher and subscriber variables)
can be created.
Generally, several publishers/subscribers can be configured for each sending/receiving device (e.g. IPC or
EL6601).
The EL66xx can also process publishers and subscribers which are frame data
• Max. 32 publishers and/or subscribers
• For each transmit direction (publisher or subscriber) the following maxima apply:
◦ all publishers: 1024 bytes total data [} 22]
◦ all subscribers: 1024 bytes total data [} 22]
With appropriate EtherCAT cycle time and depending on the scale and number of the publishers/subscribers
configured in the EL66xx, real-time cycle times down to 500 µs or below are possible.
The EL6601 is used as a sample to explain configuration as publisher or subscriber for network variables.
The dialogs under TwinCAT 2.10 and TwinCAT 2.11 here are slightly different.
The following descriptions of the dialogs of the EL6601 in the TwinCAT System Manager can be applied
equally to the EL6614.
For each data direction the EL6601/EL6614 from Rev. -0018 can transfer a maximum of 1024 byte total
data. The total data consist of the user data (e.g. a UDINT) and the diagnostic data for the EL66xx.
If the configured data quantity exceeds 1024 bytes, a corresponding message window appears when
activation is attempted:
The EL66xx (EL6601 from FW07, EL6614 from FW03) has an 8 kbyte data memory with the following
default allocation
If more publisher or subscriber data are required for an application, the SyncManagers can be modified
accordingly. The mailbox cannot be modified.
The following sample illustrates the setup for a publisher and a subscriber variable (each with a size of a 16-
bit word) on an EL6601 under TwinCAT 2.10.
Process data:
• "CycleIdx": must be served by the application in order to be evaluated on the subscriber side
• "CycleIndex": CycleIdx counterpart on the subscriber side.
• "VarData": the data to be sent.
2.5.3 Notes
• The RT statistics displays are not supported under TwinCAT for an EL66xx-RT device.
Solution: As an alternative, corresponding CoE parameters can be read for diagnostic purposes.
• The publisher features of "OnChangeOnly" and "DataExchange (divider/modulo)" are not supported
together with the EL66xx.
Solution: [from FW08] Transmitting the configured publisher variables can be cyclically suppressed by
DevCtrl.
• If a publisher is set up on an EL66xx, the publisher's CycleIndex [} 106] must be taken care of by the
user. On a PC, on the other hand, they are incremented by TwinCAT.
• The following is recommended for diagnosis of a network variable connection:
1. Monitor the link status in the "DevState" of the RT device (Device --> Inputs --> DevState). The
expected state is DevState = 0.
2. Monitor the Quality and CycleIndex in the subscriber.
• The link LED in the EL66xx only indicates the status of the cable connection, not that of any network
variable connection that may exist.
• If the EL66xx is used exclusively to transfer network variables, ConnectToTcpStack [} 22] should be
deactivated.
• A maximum of 32 for each, publishers and subscriber, are permitted per EL66xx.
Applicable: TwinCAT from version 2.11, EL6601 from FW08, EL6614 from FW04
If the EL66xx is operated with a short cycle time and with publishers configured, this can place a high loading
on the connected network. For this reason, the EL66xx can be configured in such a way that the
transmission of individual publishers can be blocked through the DevCtrl variable. The object 0xF800:02
must be occupied in the CoE (CanOpenOverEtherCAT) for this purpose.
Groups of publisher boxes can be blocked by setting appropriate bits (publisher frames). The topmost 4 bits
(the high nibble of high byte) from 0xF800:02 specify the granularity of the groups 1..15, i.e. how many
publisher frames are handled together as one group:
The upper 8 bits of DevCtrl (format: 16 bits) then block the transmission of the publisher frames located in
the corresponding group in the current cycle.
Sample:
DevCtrl.10 = true and 0xF800:02 = 0x2000 signifies that the third group will be blocked in this PLC cycle.
One group consists of 2 publisher frames, which means that in this case all the publisher variables that are
located in publisher frames 5 and 6 will not be transmitted.
NOTE
Suppressing individual publishers
The structure of a "publisher" as a publisher box in the System Manager is
- an Ethernet frame containing
- n publishers
The individual bits in DevCtrl each block a group of publisher frames.
The success achieved in this way can be observed using, for instance, a network monitor such as
Wireshark.
Note: In this documentation, bit counting starts from 0: value.0, value.1, ...
Applicable: TwinCAT from version 2.11, EL6601 from FW08, EL6614 from FW06
Depending on how the Ethernet network is configured, large or small numbers of the publisher telegrams
being used there arrive at the EL66xx devices included in the network. At the start, the EL 66xx is configured
by the EtherCAT Master to the subscriber variables that it is to receive: source AMS Net ID and ID of the
variables are loaded into the CoE for each subscriber. The CoE objects 0x60n0:01 and 0x60n0:02 then
respectively contain the AmsNetId and Variables ID to be checked. The EL66xx devices can therefore filter
according to the incoming publisher IDs, and compare them with their own subscriber IDs. For this purpose
the publisher variables contained in the Ethernet frames received are disassembled and checked
individually.
If an incoming subscriber
• corresponds to a configured AMS Net ID and Variables ID, then the contents are transferred to
EtherCAT via PDO.
• does NOT correspond to the above, then the contents are transferred as standard to the acyclic
mailbox interface for transmission to the Master.
The second way generates a high acyclic EtherCAT transport load, because subscribers received by the
EL66xx are transported that should not be transported by this EL66xx at all. For this reason the subscriber
filter can be activated by the CoE entry 0xF800:02 = 0x0100 (bit 8 = TRUE). The subscriber data that do
not correspond to the AmsNetID/Variables ID filter are then discarded in the terminal and are not transferred
to the mailbox.
Filter subscribers
Activation of the subscriber filter is recommended.
Since the EL66xx needs to be re-initialized with each INIT-OP transition, it is essential to set the
named CoE entry in the startup list.
Note: In this documentation, bit counting starts from 0: value.0, value.1, ...
In the selection dialog an EL6601 is offered as a real-time Ethernet device. The EL6601 must also be
selected here when an EL6614 is being used.
The "EL6601 device" is now linked to the actual EL6601 or EL6614 in the selection dialog ("Adapter" tab ->
"Search...").
The new device is automatically assigned to an available EL66xx, or this can also be done manually:
Multiple publishers and subscribers can be created for each EtherCAT Automation Protocol device.
Fig. 34: Virtual TwinCAT switch in the CX20x0 & CX50x0 system
Due to the internal connection via FPGA and the automatic E-bus and K-bus detection, with offline
configuration the Ethernet port only becomes visible when the configuration is activated. To configure the
Ethernet port offline, proceed as follows:
• Due to the automatic E-bus and K-bus switching, any terminal should be connected with the
appropriate bus
• The internal PCI port is detected during offline configuration and must be selected
• The customer specified configuration can be created, and the EL66xx can be inserted in the
configuration
• The Ethernet port is detected after "Reload I/O devices" (F4) and then appears under network
connections
• as "Local Area Connection 4"
Fig. 37: New Network “Local Area Connection” in the Windows network connections
• The port can now be configured as required. The settings are applied and saved. Even if the port
disappears again, the settings are retained for subsequent commissioning.
If the problem persists, i.e. if the Ethernet port of the EL66xx still fails to show up in the network connection,
see troubleshooting tips below. Follow these tips and the countermeasures listed.
Prerequisites
3 Basics communication
For connecting EtherCAT devices only Ethernet connections (cables + plugs) that meet the requirements of
at least category 5 (CAt5) according to EN 50173 or ISO/IEC 11801 should be used. EtherCAT uses 4 wires
for signal transfer.
EtherCAT uses RJ45 plug connectors, for example. The pin assignment is compatible with the Ethernet
standard (ISO/IEC 8802-3).
Due to automatic cable detection (auto-crossing) symmetric (1:1) or cross-over cables can be used between
EtherCAT devices from Beckhoff.
Recommended cables
Suitable cables for the connection of EtherCAT devices can be found on the Beckhoff website!
E-Bus supply
A bus coupler can supply the EL terminals added to it with the E-bus system voltage of 5 V; a coupler is
thereby loadable up to 2 A as a rule (see details in respective device documentation).
Information on how much current each EL terminal requires from the E-bus supply is available online and in
the catalogue. If the added terminals require more current than the coupler can supply, then power feed
terminals (e.g. EL9410) must be inserted at appropriate places in the terminal strand.
The pre-calculated theoretical maximum E-Bus current is displayed in the TwinCAT System Manager. A
shortfall is marked by a negative total amount and an exclamation mark; a power feed terminal is to be
placed before such a position.
NOTE
Malfunction possible!
The same ground potential must be used for the E-Bus supply of all EtherCAT terminals in a terminal block!
The EtherCAT slave controller (ESC) in the EL2xxx terminals features 2 watchdogs:
• SM watchdog (default: 100 ms)
• PDI watchdog (default: 100 ms)
The SyncManager watchdog is reset after each successful EtherCAT process data communication with the
terminal. If no EtherCAT process data communication takes place with the terminal for longer than the set
and activated SM watchdog time, e.g. in the event of a line interruption, the watchdog is triggered and the
outputs are set to FALSE. The OP state of the terminal is unaffected. The watchdog is only reset after a
successful EtherCAT process data access. Set the monitoring time as described below.
The SyncManager watchdog monitors correct and timely process data communication with the ESC from the
EtherCAT side.
If no PDI communication with the EtherCAT slave controller (ESC) takes place for longer than the set and
activated PDI watchdog time, this watchdog is triggered.
PDI (Process Data Interface) is the internal interface between the ESC and local processors in the EtherCAT
slave, for example. The PDI watchdog can be used to monitor this communication for failure.
The PDI watchdog monitors correct and timely process data communication with the ESC from the
application side.
The settings of the SM- and PDI-watchdog must be done for each slave separately in the TwinCAT System
Manager.
Fig. 39: EtherCAT tab -> Advanced Settings -> Behavior -> Watchdog
Notes:
• the multiplier is valid for both watchdogs.
• each watchdog has its own timer setting, the outcome of this in summary with the multiplier is a
resulting time.
• Important: the multiplier/timer setting is only loaded into the slave at the start up, if the checkbox is
activated.
If the checkbox is not activated, nothing is downloaded and the ESC settings remain unchanged.
Multiplier
Multiplier
Both watchdogs receive their pulses from the local terminal cycle, divided by the watchdog multiplier:
1/25 MHz * (watchdog multiplier + 2) = 100 µs (for default setting of 2498 for the multiplier)
The standard setting of 1000 for the SM watchdog corresponds to a release time of 100 ms.
The value in multiplier + 2 corresponds to the number of basic 40 ns ticks representing a watchdog tick.
The multiplier can be modified in order to adjust the watchdog time over a larger range.
This checkbox enables manual setting of the watchdog times. If the outputs are set and the EtherCAT
communication is interrupted, the SM watchdog is triggered after the set time and the outputs are erased.
This setting can be used for adapting a terminal to a slower EtherCAT master or long cycle times. The
default SM watchdog setting is 100 ms. The setting range is 0..65535. Together with a multiplier with a range
of 1..65535 this covers a watchdog period between 0..~170 seconds.
Calculation
Multiplier = 2498 → watchdog base time = 1 / 25 MHz * (2498 + 2) = 0.0001 seconds = 100 µs
SM watchdog = 10000 → 10000 * 100 µs = 1 second watchdog monitoring time
CAUTION
Undefined state possible!
The function for switching off of the SM watchdog via SM watchdog = 0 is only implemented in terminals
from version -0016. In previous versions this operating mode should not be used.
CAUTION
Damage of devices and undefined state possible!
If the SM watchdog is activated and a value of 0 is entered the watchdog switches off completely. This is
the deactivation of the watchdog! Set outputs are NOT set in a safe state, if the communication is inter-
rupted.
The regular state of each EtherCAT slave after bootup is the OP state.
Init
After switch-on the EtherCAT slave in the Init state. No mailbox or process data communication is possible.
The EtherCAT master initializes sync manager channels 0 and 1 for mailbox communication.
Pre-Operational (Pre-Op)
During the transition between Init and Pre-Op the EtherCAT slave checks whether the mailbox was initialized
correctly.
In Pre-Op state mailbox communication is possible, but not process data communication. The EtherCAT
master initializes the sync manager channels for process data (from sync manager channel 2), the FMMU
channels and, if the slave supports configurable mapping, PDO mapping or the sync manager PDO
assignment. In this state the settings for the process data transfer and perhaps terminal-specific parameters
that may differ from the default settings are also transferred.
Safe-Operational (Safe-Op)
During transition between Pre-Op and Safe-Op the EtherCAT slave checks whether the sync manager
channels for process data communication and, if required, the distributed clocks settings are correct. Before
it acknowledges the change of state, the EtherCAT slave copies current input data into the associated DP-
RAM areas of the EtherCAT slave controller (ECSC).
In Safe-Op state mailbox and process data communication is possible, although the slave keeps its outputs
in a safe state, while the input data are updated cyclically.
Operational (Op)
Before the EtherCAT master switches the EtherCAT slave from Safe-Op to Op it must transfer valid output
data.
In the Op state the slave copies the output data of the masters to its outputs. Process data and mailbox
communication is possible.
Boot
In the Boot state the slave firmware can be updated. The Boot state can only be reached via the Init state.
In the Boot state mailbox communication via the file access over EtherCAT (FoE) protocol is possible, but no
other mailbox communication and no process data communication.
The CoE interface (CANopen over EtherCAT) is used for parameter management of EtherCAT devices.
EtherCAT slaves or the EtherCAT master manage fixed (read only) or variable parameters which they
require for operation, diagnostics or commissioning.
CoE parameters are arranged in a table hierarchy. In principle, the user has read access via the fieldbus.
The EtherCAT master (TwinCAT System Manager) can access the local CoE lists of the slaves via
EtherCAT in read or write mode, depending on the attributes.
Different CoE parameter types are possible, including string (text), integer numbers, Boolean values or larger
byte fields. They can be used to describe a wide range of features. Examples of such parameters include
manufacturer ID, serial number, process data settings, device name, calibration values for analog
measurement or passwords.
The order is specified in 2 levels via hexadecimal numbering: (main)index, followed by subindex. The value
ranges are
• Index: 0x0000 …0xFFFF (0...65535dez)
• SubIndex: 0x00…0xFF (0...255dez)
A parameter localized in this way is normally written as 0x8010:07, with preceding "x" to identify the
hexadecimal numerical range and a colon between index and subindex.
Availability
Not every EtherCAT device must have a CoE list. Simple I/O modules without dedicated processor
usually have no variable parameters and therefore no CoE list.
If a device has a CoE list, it is shown in the TwinCAT System Manager as a separate tab with a listing of the
elements:
The figure above shows the CoE objects available in device "EL2502", ranging from 0x1000 to 0x1600. The
subindices for 0x1018 are expanded.
Some parameters, particularly the setting parameters of the slave, are configurable and writeable. This can
be done in write or read mode
• via the System Manager (Fig. "CoE Online " tab) by clicking
This is useful for commissioning of the system/slaves. Click on the row of the index to be
parameterised and enter a value in the "SetValue" dialog.
• from the control system/PLC via ADS, e.g. through blocks from the TcEtherCAT.lib library
This is recommended for modifications while the system is running or if no System Manager or
operating staff are available.
Data management
If slave CoE parameters are modified online, Beckhoff devices store any changes in a fail-safe
manner in the EEPROM, i.e. the modified CoE parameters are still available after a restart.
The situation may be different with other manufacturers.
An EEPROM is subject to a limited lifetime with respect to write operations. From typically 100,000
write operations onwards it can no longer be guaranteed that new (changed) data are reliably saved
or are still readable. This is irrelevant for normal commissioning. However, if CoE parameters are
continuously changed via ADS at machine runtime, it is quite possible for the lifetime limit to be
reached. Support for the NoCoeStorage function, which suppresses the saving of changed CoE val-
ues, depends on the firmware version.
Please refer to the technical data in this documentation as to whether this applies to the respective
device.
• If the function is supported: the function is activated by entering the code word 0x12345678 once
in CoE 0xF008 and remains active as long as the code word is not changed. After switching the
device on it is then inactive. Changed CoE values are not saved in the EEPROM and can thus
be changed any number of times.
• Function is not supported: continuous changing of CoE values is not permissible in view of the
lifetime limit.
Startup list
Changes in the local CoE list of the terminal are lost if the terminal is replaced. If a terminal is re-
placed with a new Beckhoff terminal, it will have the default settings. It is therefore advisable to link
all changes in the CoE list of an EtherCAT slave with the Startup list of the slave, which is pro-
cessed whenever the EtherCAT fieldbus is started. In this way a replacement EtherCAT slave can
automatically be parameterized with the specifications of the user.
If EtherCAT slaves are used which are unable to store local CoE values permanently, the Startup
list must be used.
The Startup list may already contain values that were configured by the System Manager based on the ESI
specifications. Additional application-specific entries can be created.
Online/offline list
While working with the TwinCAT System Manager, a distinction has to be made whether the EtherCAT
device is "available", i.e. switched on and linked via EtherCAT and therefore online, or whether a
configuration is created offline without connected slaves.
In both cases a CoE list as shown in Fig. “’CoE online’ tab” is displayed. The connectivity is shown as offline/
online.
• If the slave is offline
◦ The offline list from the ESI file is displayed. In this case modifications are not meaningful or
possible.
◦ The configured status is shown under Identity.
◦ No firmware or hardware version is displayed, since these are features of the physical device.
◦ Offline is shown in red.
Channel-based order
The CoE list is available in EtherCAT devices that usually feature several functionally equivalent channels.
For example, a 4-channel analog 0..10 V input terminal also has 4 logical channels and therefore 4 identical
sets of parameter data for the channels. In order to avoid having to list each channel in the documentation,
the placeholder "n" tends to be used for the individual channel numbers.
In the CoE system 16 indices, each with 255 subindices, are generally sufficient for representing all channel
parameters. The channel-based order is therefore arranged in 16dec/10hex steps. The parameter range
0x8000 exemplifies this:
• Channel 0: parameter range 0x8000:00 ... 0x800F:255
• Channel 1: parameter range 0x8010:00 ... 0x801F:255
• Channel 2: parameter range 0x8020:00 ... 0x802F:255
• ...
Detailed information on the CoE interface can be found in the EtherCAT system documentation on the
Beckhoff website.
WARNING
Risk of electric shock and damage of device!
Bring the bus terminal system into a safe, powered down state before starting installation, disassembly or
wiring of the Bus Terminals!
Mounting
• Fit the mounting rail to the planned assembly location.
and press (1) the terminal module against the mounting rail until it latches in place on the mounting
rail (2).
Demounting
• Remove all the cables.
• Lever the unlatching hook back with thumb and forefinger (3). An internal mechanism pulls the two
latching lugs (3a) from the top hat rail back into the terminal module.
• Pull (4) the terminal module away from the mounting surface.
Avoid canting of the module; you should stabilize the module with the other hand, if required.
The optimum installation position requires the mounting rail to be installed horizontally and the connection
surfaces of the EL/KL terminals to face forward (see Fig. “Recommended distances for standard installation
position”). The terminals are ventilated from below, which enables optimum cooling of the electronics through
convection. "From below" is relative to the acceleration of gravity.
Compliance with the distances shown in Fig. “Recommended distances for standard installation position” is
recommended.
All other installation positions are characterized by different spatial arrangement of the mounting rail - see
Fig “Other installation positions”.
The minimum distances to ambient specified above also apply to these installation positions.
Standards
The fundamental health and safety requirements are fulfilled by compliance with the following standards:
• EN 60079-0:2012+A11:2013
• EN 60079-15:2010
Marking
The Beckhoff fieldbus components with extended temperature range (ET) certified for potentially explosive
areas bear the following marking:
or
Notes about operation of the Beckhoff terminal systems in potentially explosive areas (ATEX)
5 Commissioning
Details:
• TwinCAT 2:
◦ Connects I/O devices to tasks in a variable-oriented manner
◦ Connects tasks to tasks in a variable-oriented manner
◦ Supports units at the bit level
◦ Supports synchronous or asynchronous relationships
◦ Exchange of consistent data areas and process images
◦ Datalink on NT - Programs by open Microsoft Standards (OLE, OCX, ActiveX, DCOM+, etc.)
◦ Integration of IEC 61131-3-Software-SPS, Software- NC and Software-CNC within Windows
NT/2000/XP/Vista, Windows 7, NT/XP Embedded, CE
◦ Interconnection to all common fieldbusses
◦ More…
Additional features:
• TwinCAT 3 (eXtended Automation):
◦ Visual-Studio®-Integration
◦ Choice of the programming language
◦ Supports object orientated extension of IEC 61131-3
◦ Usage of C/C++ as programming language for real time applications
◦ Connection to MATLAB®/Simulink®
◦ Open interface for expandability
◦ Flexible run-time environment
◦ Active support of Multi-Core- und 64-Bit-Operatingsystem
◦ Automatic code generation and project creation with the TwinCAT Automation Interface
◦ More…
Within the following sections commissioning of the TwinCAT Development Environment on a PC System for
the control and also the basically functions of unique control elements will be explained.
In the System Manager call up the TwinCAT overview of the local network interfaces via Options → Show
Real Time Ethernet Compatible Devices.
This have to be called up by the Menü “TwinCAT” within the TwinCAT 3 environment:
Interfaces listed under “Compatible devices” can be assigned a driver via the “Install” button. A driver should
only be installed on compatible devices.
Alternatively an EtherCAT-device can be inserted first of all as described in chapter Offline configuration
creation, section “Creating the EtherCAT device” [} 60] in order to view the compatible ethernet ports via its
EtherCAT properties (tab „Adapter“, button „Compatible Devices…“):
Fig. 52: EtherCAT device properties(TwinCAT 2): click on „Compatible Devices…“ of tab “Adapter”
TwinCAT 3: the properties of the EtherCAT device can be opened by double click on “Device .. (EtherCAT)”
within the Solution Explorer under “I/O”:
After the installation the driver appears activated in the Windows overview for the network interface
(Windows Start → System Properties → Network)
Fig. 54: Exemplary correct driver setting for the Ethernet port
IP address/DHCP
In most cases an Ethernet port that is configured as an EtherCAT device will not transport general
IP packets. For this reason and in cases where an EL6601 or similar devices are used it is useful to
specify a fixed IP address for this port via the “Internet Protocol TCP/IP” driver setting and to disable
DHCP. In this way the delay associated with the DHCP client for the Ethernet port assigning itself a
default IP address in the absence of a DHCP server is avoided. A suitable address space is
192.168.x.x, for example.
The TwinCAT EtherCAT master/System Manager needs the device description files for the devices to be
used in order to generate the configuration in online or offline mode. The device descriptions are contained
in the so-called ESI files (EtherCAT Slave Information) in XML format. These files can be requested from the
respective manufacturer and are made available for download. An *.xml file may contain several device
descriptions.
The ESI files for Beckhoff EtherCAT devices are available on the Beckhoff website.
Default settings:
• TwinCAT 2: C:\TwinCAT\IO\EtherCAT
• TwinCAT 3: C:\TwinCAT\3.1\Config\Io\EtherCAT
The files are read (once) when a new System Manager window is opened, if they have changed since the
last time the System Manager window was opened.
A TwinCAT installation includes the set of Beckhoff ESI files that was current at the time when the TwinCAT
build was created.
For TwinCAT 2.11/TwinCAT 3 and higher, the ESI directory can be updated from the System Manager, if the
programming PC is connected to the Internet; by
• TwinCAT 2: Option → “Update EtherCAT Device Descriptions”
• TwinCAT 3: TwinCAT → EtherCAT Devices → “Update Device Descriptions (via ETG Website)…”
ESI
The *.xml files are associated with *.xsd files, which describe the structure of the ESI XML files. To
update the ESI device descriptions, both file types should therefore be updated.
Device differentiation
EtherCAT devices/slaves are distinguished by four properties, which determine the full device identifier. For
example, the device identifier EL2521-0025-1018 consists of:
• family key “EL”
• name “2521”
• type “0025”
• and revision “1018”
The order identifier consisting of name + type (here: EL2521-0010) describes the device function. The
revision indicates the technical progress and is managed by Beckhoff. In principle, a device with a higher
revision can replace a device with a lower revision, unless specified otherwise, e.g. in the documentation.
Each revision has its own ESI description. See further notes [} 8].
Online description
If the EtherCAT configuration is created online through scanning of real devices (see section Online setup)
and no ESI descriptions are available for a slave (specified by name and revision) that was found, the
System Manager asks whether the description stored in the device should be used. In any case, the System
Manager needs this information for setting up the cyclic and acyclic communication with the slave correctly.
In TwinCAT 3 a similar window appears, which also offers the Web update:
If possible, the Yes is to be rejected and the required ESI is to be requested from the device manufacturer.
After installation of the XML/XSD file the configuration process should be repeated.
NOTE
Changing the ‘usual’ configuration through a scan
ü If a scan discovers a device that is not yet known to TwinCAT, distinction has to be made between two
cases. Taking the example here of the EL2521-0000 in the revision 1019
a) no ESI is present for the EL2521-0000 device at all, either for the revision 1019 or for an older revision.
The ESI must then be requested from the manufacturer (in this case Beckhoff).
b) an ESI is present for the EL2521-0000 device, but only in an older revision, e.g. 1018 or 1017.
In this case an in-house check should first be performed to determine whether the spare parts stock al-
lows the integration of the increased revision into the configuration at all. A new/higher revision usually
also brings along new features. If these are not to be used, work can continue without reservations with
the previous revision 1018 in the configuration. This is also stated by the Beckhoff compatibility rule.
Refer in particular to the chapter ‘General notes on the use of Beckhoff EtherCAT IO components’ and for
manual configuration to the chapter ‘Offline configuration creation’ [} 60].
If the OnlineDescription is used regardless, the System Manager reads a copy of the device description from
the EEPROM in the EtherCAT slave. In complex slaves the size of the EEPROM may not be sufficient for the
complete ESI, in which case the ESI would be incomplete in the configurator. Therefore it’s recommended
using an offline ESI file with priority in such a case.
The System Manager creates for online recorded device descriptions a new file
“OnlineDescription0000...xml” in its ESI directory, which contains all ESI descriptions that were read online.
Is a slave desired to be added manually to the configuration at a later stage, online created slaves are
indicated by a prepended symbol “>” in the selection list (see Figure “Indication of an online recorded ESI of
EL2521 as an example”).
If such ESI files are used and the manufacturer's files become available later, the file OnlineDescription.xml
should be deleted as follows:
• close all System Manager windows
• restart TwinCAT in Config mode
• delete "OnlineDescription0000...xml"
• restart TwinCAT System Manager
This file should not be visible after this procedure, if necessary press <F5> to update
If an ESI file is faulty and the System Manager is unable to read it, the System Manager brings up an
information window.
Fig. 62: Information window for faulty ESI file (left: TwinCAT 2; right: TwinCAT 3)
Select type ‘EtherCAT’ for an EtherCAT I/O application with EtherCAT slaves. For the present publisher/
subscriber service in combination with an EL6601/EL6614 terminal select “EtherCAT Automation Protocol
via EL6601”.
Then assign a real Ethernet port to this virtual device in the runtime system.
This query may appear automatically when the EtherCAT device is created, or the assignment can be set/
modified later in the properties dialog; see Fig. “EtherCAT device properties (TwinCAT 2)”.
TwinCAT 3: the properties of the EtherCAT device can be opened by double click on “Device .. (EtherCAT)”
within the Solution Explorer under “I/O”:
The dialog for selecting a new device opens. Only devices for which ESI files are available are displayed.
Only devices are offered for selection that can be appended to the previously selected device. Therefore the
physical layer available for this port is also displayed (Fig. “Selection dialog for new EtherCAT device”, A). In
the case of cable-based Fast-Ethernet physical layer with PHY transfer, then also only cable-based devices
are available, as shown in Fig. “Selection dialog for new EtherCAT device”. If the preceding device has
several free ports (e.g. EK1122 or EK1100), the required port can be selected on the right-hand side (A).
The search field facilitates finding specific devices (since TwinCAT 2.11 or TwinCAT 3).
By default only the name/device type is used as selection criterion. For selecting a specific revision of the
device the revision can be displayed as “Extended Information”.
In many cases several device revisions were created for historic or functional reasons, e.g. through
technological advancement. For simplification purposes (see Fig. “Selection dialog for new EtherCAT
device”) only the last (i.e. highest) revision and therefore the latest state of production is displayed in the
selection dialog for Beckhoff devices. To show all device revisions available in the system as ESI
descriptions tick the “Show Hidden Devices” check box, see Fig. “Display of previous revisions”.
Example:
If current ESI descriptions are available in the TwinCAT system, the last revision offered in the selection
dialog matches the Beckhoff state of production. It is recommended to use the last device revision when
creating a new configuration, if current Beckhoff devices are used in the real application. Older revisions
should only be used if older devices from stock are to be used in the application.
In this case the process image of the device is shown in the configuration tree and can be parameterised as
follows: linking with the task, CoE/DC settings, plug-in definition, startup settings, ...
Fig. 72: EtherCAT terminal in the TwinCAT tree (left: TwinCAT 2; right: TwinCAT 3)
The online device search can be used if the TwinCAT system is in CONFIG mode. This can be indicated by
a symbol right below in the information bar:
• on TwinCAT 2 by a blue display “Config Mode” within the System Manager window: .
The TwinCAT 2 icon ( ) or TwinCAT 3 icon ( ) within the Windows-Taskbar always shows the
TwinCAT mode of the local IPC. Compared to that, the System Manager window of TwinCAT 2 or the user
interface of TwinCAT 3 indicates the state of the target system.
Right-clicking on “I/O Devices” in the configuration tree opens the search dialog.
This scan mode attempts to find not only EtherCAT devices (or Ethernet ports that are usable as such), but
also NOVRAM, fieldbus cards, SMB etc. However, not all devices can be found automatically.
Fig. 75: Note for automatic device scan (left: TwinCAT 2; right: TwinCAT 3)
Ethernet ports with installed TwinCAT real-time driver are shown as “RT Ethernet” devices. An EtherCAT
frame is sent to these ports for testing purposes. If the scan agent detects from the response that an
EtherCAT slave is connected, the port is immediately shown as an “EtherCAT Device” .
Via respective checkboxes devices can be selected (as illustrated in Fig. “Detected Ethernet devices” e.g.
Device 3 and Device 4 were chosen). After confirmation with “OK” a device scan is suggested for all selected
devices, see Fig.: “Scan query after automatic creation of an EtherCAT device”.
NOTE
Slave scanning in practice in series machine production
The scanning function should be used with care. It is a practical and fast tool for creating an initial configu-
ration as a basis for commissioning. In series machine production or reproduction of the plant, however, the
function should no longer be used for the creation of the configuration, but if necessary for comparison
[} 70] with the defined initial configuration.Background: since Beckhoff occasionally increases the revision
version of the delivered products for product maintenance reasons, a configuration can be created by such
a scan which (with an identical machine construction) is identical according to the device list; however, the
respective device revision may differ from the initial configuration.
Example:
Company A builds the prototype of a machine B, which is to be produced in series later on. To do this the
prototype is built, a scan of the IO devices is performed in TwinCAT and the initial configuration ‘B.tsm’ is
created. The EL2521-0025 EtherCAT terminal with the revision 1018 is located somewhere. It is thus built
into the TwinCAT configuration in this way:
Likewise, during the prototype test phase, the functions and properties of this terminal are tested by the
programmers/commissioning engineers and used if necessary, i.e. addressed from the PLC ‘B.pro’ or the
NC. (the same applies correspondingly to the TwinCAT 3 solution files).
The prototype development is now completed and series production of machine B starts, for which Beckhoff
continues to supply the EL2521-0025-0018. If the commissioning engineers of the series machine production
department always carry out a scan, a B configuration with the identical contents results again for each
machine. Likewise, A might create spare parts stores worldwide for the coming series-produced machines
with EL2521-0025-1018 terminals.
After some time Beckhoff extends the EL2521-0025 by a new feature C. Therefore the FW is changed,
outwardly recognizable by a higher FW version and a new revision -1019. Nevertheless the new device
naturally supports functions and interfaces of the predecessor version(s); an adaptation of ‘B.tsm’ or even
‘B.pro’ is therefore unnecessary. The series-produced machines can continue to be built with ‘B.tsm’ and
‘B.pro’; it makes sense to perform a comparative scan [} 70] against the initial configuration ‘B.tsm’ in order
to check the built machine.
However, if the series machine production department now doesn’t use ‘B.tsm’, but instead carries out a
scan to create the productive configuration, the revision -1019 is automatically detected and built into the
configuration:
This is usually not noticed by the commissioning engineers. TwinCAT cannot signal anything either, since
virtually a new configuration is created. According to the compatibility rule, however, this means that no
EL2521-0025-1018 should be built into this machine as a spare part (even if this nevertheless works in the
vast majority of cases).
In addition, it could be the case that, due to the development accompanying production in company A, the
new feature C of the EL2521-0025-1019 (for example, an improved analog filter or an additional process
data for the diagnosis) is discovered and used without in-house consultation. The previous stock of spare
part devices are then no longer to be used for the new configuration ‘B2.tsm’ created in this way.Þ if series
machine production is established, the scan should only be performed for informative purposes for
comparison with a defined initial configuration. Changes are to be made with care!
If an EtherCAT device was created in the configuration (manually or through a scan), the I/O field can be
scanned for devices/slaves.
Fig. 80: Scan query after automatic creation of an EtherCAT device (left: TwinCAT 2; right: TwinCAT 3)
Fig. 81: Manual triggering of a device scan on a specified EtherCAT device (left: TwinCAT 2; right:
TwinCAT 3)
In the System Manager (TwinCAT 2) or the User Interface (TwinCAT 3) the scan process can be monitored
via the progress bar at the bottom in the status bar.
The configuration is established and can then be switched to online state (OPERATIONAL).
In Config/FreeRun mode the System Manager display alternates between blue and red, and the EtherCAT
device continues to operate with the idling cycle time of 4 ms (default setting), even without active task (NC,
PLC).
Fig. 84: Displaying of “Free Run” and “Config Mode” toggling right below in the status bar
Fig. 85: TwinCAT can also be switched to this state by using a button (left: TwinCAT 2; right: TwinCAT 3)
The EtherCAT system should then be in a functional cyclic state, as shown in Fig. “Online display example”.
Please note:
• all slaves should be in OP state
• the EtherCAT master should be in “Actual State” OP
• “frames/sec” should match the cycle time taking into account the sent number of frames
• no excessive “LostFrames” or CRC errors should occur
The configuration is now complete. It can be modified as described under manual procedure [} 60].
Troubleshooting
In the System Manager such devices may be set up as EK0000 or unknown devices. Operation is not
possible or meaningful.
NOTE
Change of the configuration after comparison
With this scan (TwinCAT 2.11 or 3.1) only the device properties vendor (manufacturer), device name and
revision are compared at present! A ‘ChangeTo’ or ‘Copy’ should only be carried out with care, taking into
consideration the Beckhoff IO compatibility rule (see above). The device configuration is then replaced by
the revision found; this can affect the supported process data and functions.
If a scan is initiated for an existing configuration, the actual I/O environment may match the configuration
exactly or it may differ. This enables the configuration to be compared.
If differences are detected, they are shown in the correction dialog, so that the user can modify the
configuration as required.
It is advisable to tick the “Extended Information” check box to reveal differences in the revision.
Colour Explanation
green This EtherCAT slave matches the entry on the other side. Both type and revision match.
blue This EtherCAT slave is present on the other side, but in a different revision. This other
revision can have other default values for the process data as well as other/additional
functions.
If the found revision is higher than the configured revision, the slave may be used provided
compatibility issues are taken into account.
If the found revision is lower than the configured revision, it is likely that the slave cannot be
used. The found device may not support all functions that the master expects based on the
higher revision number.
light blue This EtherCAT slave is ignored (“Ignore” button)
red • This EtherCAT slave is not present on the other side.
• It is present, but in a different revision, which also differs in its properties from the one
specified.
The compatibility principle then also applies here: if the found revision is higher than the
configured revision, use is possible provided compatibility issues are taken into account,
since the successor devices should support the functions of the predecessor devices.
If the found revision is lower than the configured revision, it is likely that the slave cannot
be used. The found device may not support all functions that the master expects based on
the higher revision number.
Example:
If current ESI descriptions are available in the TwinCAT system, the last revision offered in the selection
dialog matches the Beckhoff state of production. It is recommended to use the last device revision when
creating a new configuration, if current Beckhoff devices are used in the real application. Older revisions
should only be used if older devices from stock are to be used in the application.
In this case the process image of the device is shown in the configuration tree and can be parameterised as
follows: linking with the task, CoE/DC settings, plug-in definition, startup settings, ...
Once all modifications have been saved or accepted, click “OK” to transfer them to the real *.tsm
configuration.
TwinCAT offers a function “Change to Compatible Type…” for the exchange of a device whilst retaining the
links in the task.
Fig. 92: Dialog “Change to Compatible Type…” (left: TwinCAT 2; right: TwinCAT 3)
The TwinCAT System Manager offers a function for the exchange of a device: Change to Alternative Type
If called, the System Manager searches in the procured device ESI (in this example: EL1202-0000) for
details of compatible devices contained there. The configuration is changed and the ESI-EEPROM is
overwritten at the same time – therefore this process is possible only in the online state (ConfigMode).
In the right-hand window of the TwinCAT System manager (TwinCAT 2) or the Development Environment
(TwinCAT 3), various tabs are now available for configuring the terminal. And yet the dimension of
complexity of a subscriber determines which tabs are provided. Thus as illustrated in the example above the
terminal EL3751 provides many setup options and also a respective number of tabs are available. On the
contrary by the terminal EL1004 for example the tabs "General", "EtherCAT", "Process Data" and “Online“
are available only. Several terminals, as for instance the EL6695 provide special functions by a tab with its
own terminal name, so “EL6695” in this case. A specific tab “Settings” by terminals with a wide range of
setup options will be provided also (e.g. EL3751).
„General“ tab
„EtherCAT“ tab
The link at the bottom of the tab points to the product page for this EtherCAT device on the web.
Indicates the configuration of the process data. The input and output data of the EtherCAT slave are
represented as CANopen process data objects (Process Data Objects, PDOs). The user can select a PDO
via PDO assignment and modify the content of the individual PDO via this dialog, if the EtherCAT slave
supports this function.
The process data (PDOs) transferred by an EtherCAT slave during each cycle are user data which the
application expects to be updated cyclically or which are sent to the slave. To this end the EtherCAT master
(Beckhoff TwinCAT) parameterizes each EtherCAT slave during the start-up phase to define which process
data (size in bits/bytes, source location, transmission type) it wants to transfer to or from this slave. Incorrect
configuration can prevent successful start-up of the slave.
For Beckhoff EtherCAT EL, ES, EM, EJ and EP slaves the following applies in general:
• The input/output process data supported by the device are defined by the manufacturer in the ESI/XML
description. The TwinCAT EtherCAT Master uses the ESI description to configure the slave correctly.
• The process data can be modified in the system manager. See the device documentation.
Examples of modifications include: mask out a channel, displaying additional cyclic information, 16-bit
display instead of 8-bit data size, etc.
• In so-called “intelligent” EtherCAT devices the process data information is also stored in the CoE
directory. Any changes in the CoE directory that lead to different PDO settings prevent successful
startup of the slave. It is not advisable to deviate from the designated process data, because the
device firmware (if available) is adapted to these PDO combinations.
If the device documentation allows modification of process data, proceed as follows (see Figure “Configuring
the process data”).
• A: select the device to configure
• B: in the “Process Data” tab select Input or Output under SyncManager (C)
• D: the PDOs can be selected or deselected
• H: the new process data are visible as linkable variables in the system manager
The new process data are active once the configuration has been activated and TwinCAT has been
restarted (or the EtherCAT master has been restarted)
• E: if a slave supports this, Input and Output PDO can be modified simultaneously by selecting a so-
called PDO record (“predefined PDO settings”).
„Startup“ tab
The Startup tab is displayed if the EtherCAT slave has a mailbox and supports the CANopen over EtherCAT
(CoE) or Servo drive over EtherCAT protocol. This tab indicates which download requests are sent to the
mailbox during startup. It is also possible to add new mailbox requests to the list display. The download
requests are sent to the slave in the same order as they are shown in the list.
Column Description
Transition Transition to which the request is sent. This can either be
• the transition from pre-operational to safe-operational (PS), or
• the transition from safe-operational to operational (SO).
If the transition is enclosed in "<>" (e.g. <PS>), the mailbox request is fixed and cannot be
modified or deleted by the user.
Protocol Type of mailbox protocol
Index Index of the object
Data Date on which this object is to be downloaded.
Comment Description of the request to be sent to the mailbox
The additional CoE - Online tab is displayed if the EtherCAT slave supports the CANopen over EtherCAT
(CoE) protocol. This dialog lists the content of the object list of the slave (SDO upload) and enables the user
to modify the content of an object from this list. Details for the objects of the individual EtherCAT devices can
be found in the device-specific object descriptions.
Update List The Update list button updates all objects in the displayed list
Auto Update If this check box is selected, the content of the objects is updated automatically.
Advanced The Advanced button opens the Advanced Settings dialog. Here you can specify
which objects are displayed in the list.
Online - via SDO Information If this option button is selected, the list of the objects included in the object
list of the slave is uploaded from the slave via SDO information. The list
below can be used to specify which object types are to be uploaded.
Offline - via EDS File If this option button is selected, the list of the objects included in the object
list is read from an EDS file provided by the user.
„Online“ tab
State Machine
Init This button attempts to set the EtherCAT device to the Init state.
Pre-Op This button attempts to set the EtherCAT device to the pre-operational state.
Op This button attempts to set the EtherCAT device to the operational state.
Bootstrap This button attempts to set the EtherCAT device to the Bootstrap state.
Safe-Op This button attempts to set the EtherCAT device to the safe-operational state.
Clear Error This button attempts to delete the fault display. If an EtherCAT slave fails during
change of state it sets an error flag.
Example: An EtherCAT slave is in PREOP state (pre-operational). The master now
requests the SAFEOP state (safe-operational). If the slave fails during change of state
it sets the error flag. The current state is now displayed as ERR PREOP. When the
Clear Error button is pressed the error flag is cleared, and the current state is
displayed as PREOP again.
Current State Indicates the current state of the EtherCAT device.
Requested State Indicates the state requested for the EtherCAT device.
DLL Status
Indicates the DLL status (data link layer status) of the individual ports of the EtherCAT slave. The DLL status
can have four different states:
Status Description
No Carrier / Open No carrier signal is available at the port, but the port is open.
No Carrier / Closed No carrier signal is available at the port, and the port is closed.
Carrier / Open A carrier signal is available at the port, and the port is open.
Carrier / Closed A carrier signal is available at the port, but the port is closed.
Sync Manager
If an input is selected, the corresponding PDO assignment is displayed in the PDO Assignment list below.
PDO Assignment
PDO assignment of the selected Sync Manager. All PDOs defined for this Sync Manager type are listed
here:
• If the output Sync Manager (outputs) is selected in the Sync Manager list, all RxPDOs are displayed.
• If the input Sync Manager (inputs) is selected in the Sync Manager list, all TxPDOs are displayed.
The selected entries are the PDOs involved in the process data transfer. In the tree diagram of the System
Manager these PDOs are displayed as variables of the EtherCAT device. The name of the variable is
identical to the Name parameter of the PDO, as displayed in the PDO list. If an entry in the PDO assignment
list is deactivated (not selected and greyed out), this indicates that the input is excluded from the PDO
assignment. In order to be able to select a greyed out PDO, the currently selected PDO has to be deselected
first.
PDO list
List of all PDOs supported by this EtherCAT device. The content of the selected PDOs is displayed in the
PDO Content list. The PDO configuration can be modified by double-clicking on an entry.
Column Description
Index PDO index.
Size Size of the PDO in bytes.
Name Name of the PDO.
If this PDO is assigned to a Sync Manager, it appears as a variable of the slave with this
parameter as the name.
Flags F Fixed content: The content of this PDO is fixed and cannot be changed by the
System Manager.
M Mandatory PDO. This PDO is mandatory and must therefore be assigned to a
Sync Manager! Consequently, this PDO cannot be deleted from the PDO
Assignment list
SM Sync Manager to which this PDO is assigned. If this entry is empty, this PDO does not take
part in the process data traffic.
SU Sync unit to which this PDO is assigned.
PDO Content
Indicates the content of the PDO. If flag F (fixed content) of the PDO is not set the content can be modified.
Download
If the device is intelligent and has a mailbox, the configuration of the PDO and the PDO assignments can be
downloaded to the device. This is an optional feature that is not supported by all EtherCAT slaves.
PDO Assignment
If this check box is selected, the PDO assignment that is configured in the PDO Assignment list is
downloaded to the device on startup. The required commands to be sent to the device can be viewed in the
Startup [} 76] tab.
PDO Configuration
If this check box is selected, the configuration of the respective PDOs (as shown in the PDO list and the
PDO Content display) is downloaded to the EtherCAT slave.
Generally speaking an EtherCAT Slave provides a variety of diagnostic information that can be used by the
controlling task.
This diagnostic information relates to differing levels of communication. It therefore has a variety of sources,
and is also updated at various times.
Any application that relies on I/O data from a fieldbus being correct and up to date must make diagnostic
access to the corresponding underlying layers. EtherCAT and the TwinCAT System Manager offer
comprehensive diagnostic elements of this kind. Those diagnostic elements that are helpful to the controlling
task for diagnosis that is accurate for the current cycle when in operation (not during commissioning) are
discussed below.
as well as
• function diagnosis typical for a channel (device-dependent)
See the corresponding device documentation
The colors in Fig. “Selection of the diagnostic information of an EtherCAT Slave” also correspond to the
variable colors in the System Manager, see Fig. “Basic EtherCAT Slave Diagnosis in the PLC”.
Colour Meaning
yellow Input variables from the Slave to the EtherCAT Master, updated in every cycle
red Output variables from the Slave to the EtherCAT Master, updated in every cycle
green Information variables for the EtherCAT Master that are updated acyclically. This means that
it is possible that in any particular cycle they do not represent the latest possible status. It is
therefore useful to read such variables through ADS.
Fig. “Basic EtherCAT Slave Diagnosis in the PLC” shows an example of an implementation of basic
EtherCAT Slave Diagnosis. A Beckhoff EL3102 (2-channel analogue input terminal) is used here, as it offers
both the communication diagnosis typical of a slave and the functional diagnosis that is specific to a channel.
Structures are created as input variables in the PLC, each corresponding to the process image.
NOTE
Diagnostic information
It is strongly recommended that the diagnostic information made available is evaluated so that the applica-
tion can react accordingly.
The CoE parameter directory (CanOpen-over-EtherCAT) is used to manage the set values for the slave
concerned. Changes may, in some circumstances, have to be made here when commissioning a relatively
complex EtherCAT Slave. It can be accessed through the TwinCAT System Manager, see Fig. “EL3102,
CoE directory”:
Commissioning interfaces are being introduced as part of an ongoing process for EL/EP EtherCAT devices.
These are available in TwinCAT System Managers from TwinCAT 2.11R2 and above. They are integrated
into the System Manager through appropriately extended ESI configuration files.
Although the "Process Data", "DC", "Startup" and "CoE-Online" that used to be necessary for this are still
displayed, it is recommended that, if the commissioning aid is used, the automatically generated settings are
not changed by it.
The commissioning tool does not cover every possible application of an EL/EP device. If the available setting
options are not adequate, the user can make the DC, PDO and CoE settings manually, as in the past.
EtherCAT State: automatic default behaviour of the TwinCAT System Manager and manual operation
After the operating power is switched on, an EtherCAT Slave must go through the following statuses
• INIT
• PREOP
• SAFEOP
• OP
to ensure sound operation. The EtherCAT Master directs these statuses in accordance with the initialization
routines that are defined for commissioning the device by the ES/XML and user settings (Distributed Clocks
(DC), PDO, CoE). See also the section on "Principles of Communication, EtherCAT State Machine [} 36]" in
this connection. Depending how much configuration has to be done, and on the overall communication,
booting can take up to a few seconds.
The EtherCAT Master itself must go through these routines when starting, until it has reached at least the
OP target state.
The target state wanted by the user, and which is brought about automatically at start-up by TwinCAT, can
be set in the System Manager. As soon as TwinCAT reaches the status RUN, the TwinCAT EtherCAT
Master will approach the target states.
Standard setting
In addition, the target state of any particular Slave can be set in the "Advanced Settings" dialogue; the
standard setting is again OP.
Manual Control
There are particular reasons why it may be appropriate to control the states from the application/task/PLC.
For instance:
• for diagnostic reasons
• to induce a controlled restart of axes
• because a change in the times involved in starting is desirable
In that case it is appropriate in the PLC application to use the PLC function blocks from the TcEtherCAT.lib,
which is available as standard, and to work through the states in a controlled manner using, for instance,
FB_EcSetMasterState.
It is then useful to put the settings in the EtherCAT Master to INIT for master and slave.
EL/ES terminals are placed on the DIN rail at a coupler on the terminal strand. A Bus Coupler can supply the
EL terminals added to it with the E-bus system voltage of 5 V; a coupler is thereby loadable up to 2 A as a
rule. Information on how much current each EL terminal requires from the E-bus supply is available online
and in the catalogue. If the added terminals require more current than the coupler can supply, then power
feed terminals (e.g. EL9410) must be inserted at appropriate places in the terminal strand.
The pre-calculated theoretical maximum E-Bus current is displayed in the TwinCAT System Manager as a
column value. A shortfall is marked by a negative total amount and an exclamation mark; a power feed
terminal is to be placed before such a position.
From TwinCAT 2.11 and above, a warning message "E-Bus Power of Terminal..." is output in the logger
window when such a configuration is activated:
NOTE
Caution! Malfunction possible!
The same ground potential must be used for the E-Bus supply of all EtherCAT terminals in a terminal block!
Introduction
The following section first describes the objects required for normal operation, followed by a complete
overview of missing objects.
Index 6002-67FA Receiving Frame Identification (Ignore Item Net Var Subscriber)
Index (hex) Name Meaning Data type Flags Default
6002+n*8:0 Receiving Frame Max. subindex UINT8 RW P 0x05 (5dec)
Identification (each module gets its own entry (Index 0x6002+n*8),
(Ignore Item Net Var 0 ≤ n < maximum number of modules
Subscriber)
(6002+n*8): Net Id "Net Id" 0: Entry is checked. If equality is de- UINT8 RW P 0x01 (1dec)
01 tected, the associated data areas are
(6002+n*8): Var Id "Var Id" transferred in the process data. UINT8 RW P 0x00 (0dec)
02 1: Entry is skipped. Associated data
(6000+n*8): Quality "Quality" areas are not transferred in the UINT8 RW P 0x01 (1dec)
03 process data.
(6002+n*8): Cycle Index "Cycle Index" UINT8 RW P 0x01 (1dec)
04
(6002+n*8): Data area 001 "Data area 001" UINT8 RW P 0x01 (1dec)
05
Index 6003-67FB Receiving Frame Length (Area Length Nat Var Subscriber)
Index (hex) Name Meaning Data type Flags Default
6003+n*8:0 Receiving Frame Max. subindex UINT8 RW P 0x05 (5dec)
Length (each module gets its own entry (Index 0x6003+n*8),
(Area Length Nat Var 0 ≤ n < maximum number of modules
Subscriber)
(6003+n*8): Net Id Length of the "Net Id" field UINT16 RW P 0x0006 (6dec)
01
(6003+n*8): Var Id Length of the "Var Id" field UINT16 RW P 0x0002 (2dec)
02
(6003+n*8): Quality Length of the "Quality" field UINT16 RW P 0x0002 (2dec)
03
(6003+n*8): Cycle Index Length of the "Cycle Index" field UINT16 RW P 0x0002 (2dec)
04
(6003+n*8): Data area 001 Length of the "Data area" field UINT16 RW P 0x0002 (2dec)
05
Index 7003-77FB Sending Frame Length (Area length Net Var Publisher)
Index (hex) Name Meaning Data type Flags Default
7003+n*8:0 Sending Frame Max. subindex UINT8 RW P -
Length (each module gets its own entry (Index 0x7003+n*8),
(Area length Net Var 0 ≤ n < maximum number of modules
Publisher)
(7003+n*8): Destination MAC ad- MAC-Destination address Ethernet telegram UINT48 RW P -
01 dress
(7003+n*8): Source MAC address MAC-Source address Ethernet telegram UINT48 RW P -
02
(7003+n*8): Ethernet type Beckhoff Ethertype UINT16 RW P 0x88A4
03 (42120dec)
(7003+n*8): Header Bit 0-10: UINT16 RW P -
04 Length of the following entries
Bit 11: 0,
Bit 12-15: 4, Network variable -type
(7003+n*8): Net Id Source AMS Net Id UINT48 RW P -
05
(7003+n*8): # of Vars Number of variables UINT16 RW P -
06
(7003+n*8): Cycle Index Entry is incremented with each Publisher cycle UINT16 RW P -
07
(7003+n*8): reserved reserved UINT16 RW P -
08
(7000+n*8): Net Var 001 Id Identification of network variables UINT16 RW P -
09
(7003+n*8): Net Var 001 Header Byte 0,1: Hash value UINT48 RW P -
0A Byte 2,3: Length of the data
Byte 4,5: Quality
(7003+n*8): Net Var 001 Data Data range STRING RW P -
0B
-
(7003+n*8) Net Var y Id Identification of network variables UINT16 RW P -
:(3*y+6)
(7003+n*8) Net Var y Header Byte 0,1: Hash value UINT48 RW P -
:(3*y+7) Byte 2,3: Length of the data
Byte 4,5: Quality
(7003+n*8) Net Var y Data Data range OCTED_STRI RW P -
:(3*y+8) NG
5.4.1 Introduction
Network variables are any variables that are cyclically exchanged between PC/CX1000 via TwinCAT.
Variables with any data types, including complex types, can be exchanged. The Publisher/Subscriber model
is used. For highly deterministic communication, the real-time Ethernet driver for TwinCAT must be installed.
Publisher/Subscriber model
In the Publisher/Subscriber model, the Publisher makes variables available. Subscribers can subscribe to a
variable. The Publisher can make the variable available to a Subscriber, several Subscribers or all
Subscribers. In Broadcast mode the variable is made available to all PCs, in Multicast mode to selected PCs
and in Unicast mode only to one selected PC. A Subscriber can also be Publisher at the same time. In this
way, a bidirectional data link can be provided.
Unicast
The Publisher makes the network variable available to a single selected PC.
Multicast
Broadcast
The network variables are inserted underneath the box. Enter a name (nCounterPub in the sample) and a
data type (UINT32 in the sample, corresponding to UDINT).
The FrameState input under the box indicates the current status of the sent Ethernet frames.
A Control Word can be written in the FrameCtrl output under the box.
The VarState input under the network variable indicates the current status of the network variable.
The following values are possible for VarState:
A Control Word can be written in the VarCtrl output under the network variable.
Mappings
The network variable of the Publisher can be mapped to any output variable with a suitable data type. In the
sample, the network variable is linked to the output variable of a PLC.
Fig. 117: Mapping of the network variable with an output variable of the PLC
The link to a Publisher variable can be created automatically. First, you need to find the Publisher computer.
All variables of this Publisher are then shown in a list.
The FrameState input and the FrameCtrl output underneath the box give information about the current status
or control of the received Ethernet Frames. FrameState and FrameCtrl are reserved and are currently not
supported.
The VarState input and the VarCtrl output under the network variable indicate the current status (or control)
of the received network variable. VarState and VarCtrl are reserved and are currently not supported.
The quality of a network variable is assessed on the Subscriber side. Two input variables are available for
this purpose under the network variable. The Quality variable provides a counter with a resolution of 100 µs.
The counter value indicates the variable delay. The sample below shows the online value of Quality when
the network connector is unplugged (counter increases) and reconnected (counter value 0).
In addition to the Quality variables, the CycleIndex variable is incremented in each Publisher cycle.
The telegram with the process data arrives at the recipient device (network port) via these addressing
modes. In the Ethernet device/TwinCAT several transported process data are allocated via a variable ID
All network variables must be declared in the System Manager before they can be used.
Diagnostic variables on the publisher and subscriber side provide information about the connection quality.
If network variables are used, the temporal boundary conditions for the network topology used must be taken
into account: in the case of IP addressing (routed) on a case-by-case basis several 100 ms communications
cycle can be achieved, in the case of MAC addressing (switched) approximately 10 ms and less.
Note:
The reason for determining the delay so precisely is that the NWVs are managed directly by the IO
driver, independent of the cycle. Nevertheless, the data of an NWV that is delayed by a few percent of
the cycle time will not be taken into account until the input process image is read during the next task
cycle.
Note EL6601/EL6614:
Even with the EL66xx the NWV arrival time is defined as the time when the data are available in the
input process image of the RT device, not the time of arrival at the EL66xx or in the input image of the
EtherCAT device.
• Variable ID
The variable ID (16 bit) is used for global identification of the individual process data. Therefore, an ID
in the Publisher or Subscriber group may only be used once within a TwinCAT device, see Fig. Sample
for communication via network variables: Publishers 1 and 2 on PC1 must have different IDs (10 and
8), although the same ID (8) may be used in Publisher 2 and Subscriber 1.
• Cycle Index
The 16-bit cycle index is a counter sent by the Publisher together with the data. It is generally
incremented with each transmission and can therefore be used as an indicator for flawless transfer. It
can be read on the subscriber side as CycleIndex. Its appearance depends on the Publisher platform:
- Publisher on a PC: The variable CycleIndex is not visible and is automatically and cyclically
incremented by the System Manager
- Publisher on an EL66xx: The variable CycleIndex is visible and must be incremented/served by the
user such that it is not equal 0 on the subscriber side.
Fig. 128: Data representation e.g. x86 Systems vs. ARM Systems
The following settings options are available in the Beckhoff System Manager TwinCAT 2.10 build 1328:
Publisher, Box
RT Ethernet settings:
• MAC-Broadcast: Sent to all network devices, destination MAC FF:FF:FF:FF:FF:FF.
• Multicast: A destination MAC address becomes a multicast address if the first bit in the first byte of the
MAC (the so-called group bit) is set. With the Beckhoff ID "00 01 05" the default target address "01 01
05 04 00 00" is formed, as shown in Fig. Publisher RT Ethernet settings.
The MAC range 01:00:5E:00:00:00 to 01:00:5E:FF:FF:FF is intended for general multicast application,
with the first 3 bytes specified by the IEEE and the last 3 bytes derived from the lower part of the IP
address of the destination PC. The resulting destination MAC therefore never physically exists in the
network. Instead, the destination network card detects Ethernet frames formed in this way as multicast
frames sent to it, although the Ethernet port itself can have another, unique MAC address. Please refer
to the relevant literature for further rules relating to the formation of multicast MAC/IP addresses.
• Unicast: Either direct entry of the destination MAC or via the AMS Net ID of the destination device, e.g.
123.456.123.456.1.1, in which case this route must be entered in the local AMS router (right-click on
the TwinCAT icon in the taskbar --> Properties --> AMS router)
Advanced Settings:
• Data exchange: The task cycle time * divider is the rhythm at which this network variable is sent. (not
for EL66xx).
• VLAN support: In conjunction with manageable switches the Ethernet frame parameterized here can
be assigned a fixed route via VLAN tagging (Virtual Local Area Network).
UDP/IP settings - the addressing technique of the IP network layer with IP addresses is used. UDP is a
connection-less protocol without feedback.
• Broadcast: Sent to all device with destination IP (v4) 255.255.255.255
• Multicast: The destination IP must be specified, see notes on MAC multicast
• Unicast: Specify the target device (e.g.: 192.168.0.1), making sure that it can be reached through the
subnet mask
Advanced Settings:
• "ARP Retry Interval": In order to ascertain the presence of the recipient, the publisher sends an ARP
request to the target device at these intervals. If the network administration of the recipient is
operational, it sends an ARP reply. This is only meaningful with unicast.
In the event of an error bit 3 is set (0x0004) in the diagnostic FrameState variable.
Note: ARP handling (ARP = Address Resolution Protocol: allocation of hardware/MAC addresses to
network addresses [IP]) is managed by the operating system (Windows).
• "Disable Subscriber Monitoring": deactivates the procedure described above.
• "Target Address changeable": In this case the destination IP can be changed dynamically.
Publisher, Variable
Settings:
• "Variable ID": Identification number with which the variable is sent. Can be changed online via PLC
where appropriate.
• "Data exchange": see above (not for EL66xx).
• "On change only": NWV is only sent if the value changes (not for EL66xx).
Subscriber, Box
Settings:
• "Receiving Options": Only permits NWVs from a certain publisher for this subscriber
Process data:
• "VarId": If activated, the variable ID can be modified online
Subscriber, variable
Settings:
• "Variable ID": Only permits NWVs with a certain ID for this subscriber. Can be changed dynamically via
PLC where appropriate.
• "Ignore Data Type Hash": Hash calculation is currently not supported
Process data:
• "Quality": See explanatory notes above.
• "CycleIndex": This index is incremented with each successful transfer, IF this is done by the opposite
side, i.e. the publisher. If the publisher is an EL66x, the user must increment CycleIdx there.
• "VarData": Transferred data.
6 Application samples
With appropriate EtherCAT cycle time and depending on the scale and number of the publishers/subscribers
configured in the EL66xx, real-time cycle times down to 500 µs or below are possible.
The EL6601 is used as a sample to explain configuration as publisher or subscriber for network variables.
The dialogs under TwinCAT 2.10 and TwinCAT 2.11 here are slightly different.
The following objects are available for initial diagnostic in the CoE directory:
• 0xFA01, subindex 01: Frame Counter Rx (incoming to RJ45 socket)
• 0xFA01, subindex 02: Frame Counter Tx (outgoing from RJ45 socket)
The values can be read from the controller using PLC function blocks (FB_EcCoeSdoRead in
TcEtherCAT.lib).
This and further diagnostic information from the CoE of the EL66xx are accessible via https://
infosys.beckhoff.com/content/1033/el6601_el6614/Resources/zip/2349552907.zip.
A network printer is connected to the EL6601 within the terminal network via the Control Panel of the control
system IPC:
Legend:
EtherCAT connection
Ethernet connection
• The EL6601 should appear in the system configuration being in OP mode (see Online [} 73] tab
EtherCAT Status Machine)
• Connect the network printer with the EL6601 via a CAT-5 (1:1) cable
• In the Control Panel of the controller IPC, check the network adapter via which the EtherCAT system is
operated:
Network Connections [Properties] -> Local Area Connection (TwinCAT LAN adapter), [Properties]->
Internet Protocol (TCP/IP) [Properties]
• Enter an IP address for the subnet of the network printer (e.g. 192.168.0.1/255.255.255.0) and confirm
with OK
Fig. 139: Entry of the IP address of the subnetwork of the network printer
Network address
The network address in the sample is only used for the purpose of illustrating the configuration.
Please note that in your application the IP address of network printer must match the IP number
range/subnet mask of the master PC.
• Configure the network printer (in the configuration menu of the printer) and allocate the printer an IP
address from the IP number range of the subnet defined above
(Follow the user guide of your printer), e.g.: 192.168.0.37
• Configure the network printer via the Control Panel:
Printers & Faxes -> Add a printer , in the Add Printer Wizard select Local printer, and in the following
pull-down menu Create a new port. .. select Standard TCP/IP Port
Fig. 140: Control Panel “Add a Printer” under “Printers and Faxes”
• In the following menu under Printer Name or IP Address enter the IP address of the printer defined in
the configuration menu (in the sample 192.168.0.37)
• In analogy to the configuration of a network printer the IP number of the EtherCAT network port of the
TwinCAT Master-PC in the subnet is e.g. 192.168.0.1
• Open the Control Panel of the TwinCAT master PC and click on Security Center -> Windows Firewall
Fig. 146: Selection of “Security Center” in the View Control Panel Category
Fig. 148: At the “Exceptions” Tab activate the “Remote desktop” service
• Return to the Control Panel of TwinCAT master PC and select Performance and Maintenance ->
System
Fig. 149: Select “Service and Maintenance” from “System” in the View Control Panel
• Click on the Remote tab, and in the Remote Desktop category select the option Allow users to
establish a remote desktop connection
• Open the list of remote desktop users via the button Select remote users... and add additional users if
required
• Confirm with OK.
For a remote desktop connection with the TwinCAT master PC via the EL6601 the network address of the
service PC has to be set according to the IP number range of the TwinCAT master PC subnet.
• Connect the Ethernet port of the service PC with the EL6601 via a CAT-5 (1:1) cable
• In the Control Panel of the Service-PC check the Ethernet network adapter, via which the EtherCAT
system is operated:
Network Connections [Properties] -> Local Area Connection (Ethernet LAN adapter), [Properties]->
Internet Protocol (TCP/IP) [Properties]
• Enter an IP address for the subnet of the network printer (e.g. 192.168.0.38/255.255.255.0) and
confirm with OK
• The Ethernet connection to the TwinCAT master PC is now tunneled via the EL6601 through the
EtherCAT terminal network and can be established via the remote desktop.
• Enter the IP address of the TwinCAT master PC (e.g. 192.168.0.1) and click Connect
• The login window of the TwinCAT master PC appears on the desktop of the service PC
• Enter your user name and password for the TwinCAT master PC and confirm with OK
The IP address of the TwinCAT master PC is shown above the remote desktop
Fig. 158: Login window of the remote PC via the remote desktop connection
• The TwinCAT system can now be remotely controlled via the service PC.
To log out close the remote desktop window.
For a connection with the TwinCAT master PC via the EL6601 the network address of the subordinate
control system has to be set according to the IP number range of the TwinCAT master PC subnet.
• From the desktop of the lower-level control system (Windows CE) choose Start -> Settings -> Network
and Dial-up Connections to start the configuration of the network settings
(You can also find information about setting the network address of a lower-level control system from
the Documentation on TwinCAT System Manager)
• Open the network settings for this connection by double-clicking on the TCIXPNPE1 connection
(Ethernet port)
• Enter an IP number from the IP number range of the subnet (e.g. 192.168.0.39/255.255.255.0) for the
TwinCAT master PC and confirm with OK.
• In analogy to the configuration of a network printer, the IP number of the TwinCAT master PC in the
subnet might be 192.168.0.1, for sample
• Connect the subordinate control unit (target system) with the EL6601 via a CAT-5 (1:1) cable
• Start another system manager session in Config mode and click on Select Target System...-> Search
(Ethernet)
• Enter the IP address of the subordinate control system in the field next to Enter Host Name / IP:
• After confirming the button Enter Host Name / IP: the name of the target system appears in the
selection box
Fig. 166: In the “Route Dialog” add the route of the target system
• Click on Add Route and enter the access data for the target system as required
• After closing the dialog box the name of the target system appears in the selection menu
• Make your selection and confirm with OK
• Activate free-run mode for reading the Bus Terminal configuration of the subordinate control system
To do this, the Master PC "TwinCAT Master" (B) must be setup as a TCP/IP bridge in order to route TCP/IP
telegrams through to the subordinate CX1020 (C) or to relay them in the opposite direction. The partner
device is a PC (A).
Distinction must be made between two cases here: static addresses [} 135] and DHCP address assignment
[} 138] (network).
• Configure the three PCs as shown in the diagram. The dialogs for the properties of the Internet
protocol were explained in the preceding samples.
• Using the registry editor (Start --> Run --> regedit), set the entry "IPEnableRouter" in the "bridge" PC B
to the value 1. The entry is usually located under HKEY_LOCAL_MACHINE\SYSTEM
\ControlSet001\Services\TCPIP\Parameters or also under HKEY_LOCAL_MACHINE\SYSTEM
\CurrentControlSet\Services\TCPIP\Parameters.
• Following a restart, routing for IP telegrams is active for this PC. The connection can then be checked
by means of a ping (Start --> Run --> cmd --> ping 192.168.1.1) to the EtherCAT port 192.168.1.1.
• If the EtherCAT master is in a normal and error-free state (TwinCAT in "Config"/"FreeRun" or "Run"
mode), the connected Ethernet device with the IP address 192.168.1.10 can be reached via the
EL6601.
• Explanation of the entry Gateway, using PC A as an sample: PC A has the IP address 10.16.2.8 with a
subnet mask 255.255.255.0. This means that it can reach all IP telegrams within a range from
10.16.2.0 to 10.16.2.255. If it is required to send an IP telegram to a different address range (e.g. to
192.168.1.1), this must run via the defined gateway, in this case 10.16.2.21, which in turn can relay the
telegram to 192.168.1.10 via the configured IP routing.
• Windows offers the useful command line command ipconfig for checking the configuration. If PC A is
configured correctly, the command Start Run cmd ipconfig/all displays the following screen:
Fig. 171: Checking the configuration with command line command “ipconfig /all”
• IP routing is disabled (default) and the IP address of the selected adaptor (here called LAN) is
assigned fixedly. Since DHCP was set beforehand, WINS entries are still present.
• The same command on PC C displays:
"ipconfig" switches
Using the switches /release and /renew, the command ipconfig can be used to re-establish IP con-
nections.
• "Ping" works
A connection between the PCs C and A (or the network) is not possible.
Explanation: Computers (A) and (B) receive their IP addresses from the DHCP server if the Ethernet ports
are configured accordingly. One possible sequence is as follows (see RFC1541 and RFC2131):
• A newly connected PC sends a DHCPDISCOVER message with its MAC address via MAC Broadcast
to all other network devices
• The DHCP server offers the requesting device one or more IP addresses in the DHCPOFFER
message
• The requesting PC selects an IP address and answers via MAC Broadcast with a DHCPREQUEST
message to the DHCP server
• The DHCP server confirms the selection with a DHCPACK message.
This works for computers (A) and (B). The DHCPDISCOVER messages from computer (C) are accepted by
the EL6601 and relayed in computer (B) to Windows via the EtherCAT port, but Windows (B) does not route
these messages (and all other DHCP telegrams) through to the relaying Ethernet port – this function, known
as DHCP Relay Agent, is only available in the server version of Windows.
This is the normal operating case when Windows PCs configured as DHCP devices are linked with each
other.
Remedy:
• Install a local DHCP server on computer (B), taking care that no conflict arises with the superordinate
network DHCP server
• It is possible that two Windows PCs, which are configured as DHCP devices and connected to each
other, will only establish their addresses after a short time (several minutes)
This sample illustrates the principle of remote access from a subordinate PC to the central EtherCAT
controller via a flexibly connected EL6601 and EtherCAT.
The approach
The task is to commission an extensive system with EtherCAT topology. To this end frequent access to the
TwinCAT System Manager on the central PC is required. In practice the technician will primarily be at the
local terminals/EtherCAT slaves during commissioning. The central System Manager as the TwinCAT target
system should therefore be accessed from the respective coupler location via a remote PC and Ethernet.
A freely pluggable combination of EK1101 and EL6601 (HotConnect group) can now be used as a flexible
Ethernet interface.
Possible configuration
The system offers EK1110 (end couplers), EK1122 (junction terminals) and free EK1100 ports for connecting
the HotConnect group. The IP addresses should be regarded as samples, the notes from the previous
samples must be taken into account.
No further settings are required at the TwinCAT/EtherCAT master. EoE is automatically forwarded in
TwinCAT 2.11.
Sample configuration
A small EtherCAT system is commissioned, the offline topology view in the System Manager shows two
coupler stations and one non-localized station with an EK1101.
• In offline state the System Manager does not know where the EK1101 station with its ID was
connected.
• The current assignment is visible online, the EK1101 with the EL6601 is connected to the second port
of the EK1100.
• All slaves are in OP state, so that this system can now be accessed as target system from the remote
PC.
• In the remote system an empty System Manager is opened and the EtherCAT computer with the IP
172.1.1.1 (in this sample) is located as the target system via IP
(Tab Actions -> Choose Target System -> "Search (Ethernet)" -> [enter IP 172.1.1.1] -> "Enter Host
Name / IP")
• After double-clicking on the line showing the found target system the user can log into the target
system:
• After successful connection the configuration can be loaded by the target system through "Open from
target system".
Checklist
The following checklist can be used for a successful configuration up to remote access:
Ethernet connection
It is advisable to use credible addresses in the Properties dialog of the network interface, IP proto-
col (Windows XP SP2) Default gateway and DNS server, although they are not actually required.
Settings of the remote PC from the sample:
7 Appendix
7.1 UL notice
Application
Beckhoff EtherCAT modules are intended for use with Beckhoff’s UL Listed EtherCAT Sys-
tem only.
Examination
For cULus examination, the Beckhoff I/O System has only been investigated for risk of fire
and electrical shock (in accordance with UL508 and CSA C22.2 No. 142).
Basic principles
Two UL certificates are met in the Beckhoff EtherCAT product range, depending upon the components:
1. UL certification according to UL508. Devices with this kind of certification are marked by this sign:
2. UL certification according to UL508 with limited power consumption. The current consumed by the de-
vice is limited to a max. possible current consumption of 4 A. Devices with this kind of certification are
marked by this sign:
Almost all current EtherCAT products (as at 2010/05) are UL certified without restrictions.
Application
If terminals certified with restrictions are used, then the current consumption at 24 VDC must be limited
accordingly by means of supply
• from an isolated source protected by a fuse of max. 4 A (according to UL248) or
• from a voltage supply complying with NEC class 2.
A voltage source complying with NEC class 2 may not be connected in series or parallel with another
NEC class 2compliant voltage supply!
These requirements apply to the supply of all EtherCAT bus couplers, power adaptor terminals, Bus
Terminals and their power contacts.
Note
• It is recommended to use the newest possible firmware for the respective hardware.
• Beckhoff is not under any obligation to provide customers with free firmware updates for delivered
products.
NOTE
Risk of damage to the device!
Pay attention to the instructions for firmware updates on the separate page [} 146]. If a device is placed in
BOOTSTRAP mode for a firmware update, it does not check when downloading whether the new firmware
is suitable. This can result in damage to the device! Therefore, always make sure that the firmware is suit-
able for the hardware version!
EL6601
Hardware (HW) Firmware (FW) Revision No. Date of release
05 - 14 06 2009/07
07 EL6601-0000-0017 2009/09
08 2009/11
09 2010/07
EL6601-0000-0018 2010/09
10 2011/09
EL6601-0000-0019 2012/10
11 2013/04
12 EL6601-0000-0020 2014/07
15 – 16* 13 EL6601-0000-0021 2014/12
14 2015/07
15* 2017/02
EL6614
Hardware (HW) Firmware (FW) Revision No. Date of release
00 - 09* 01 EL6614-0000-0017 2008/05
02 2008/12
03 2009/08
04 2009/11
05 2010/07
EL6614-0000-0018 2010/09
06 2011/09
EL6614-0000-0019 2012/10
07 2013/04
08 EL6614-0000-0020 2014/07
10 – 13* 09 EL6614-0000-0021 2014/12
10 2015/07
11* 2017/02
*) This is the current compatible firmware/hardware version at the time of the preparing this documentation.
Check on the Beckhoff web page whether more up-to-date documentation is available.
Storage locations
Customers can access the data via the EtherCAT fieldbus and its communication mechanisms. Acyclic
mailbox communication or register access to the ESC is used for updating or reading of these data.
The TwinCAT System Manager offers mechanisms for programming all 3 parts with new data, if the slave is
set up for this purpose. Generally the slave does not check whether the new data are suitable, i.e. it may no
longer be able to operate if the data are unsuitable.
The update using so-called bundle firmware is more convenient: in this case the controller firmware and the
ESI description are combined in a *.efw file; during the update both the firmware and the ESI are changed in
the terminal. For this to happen it is necessary
• for the firmware to be in a packed format: recognizable by the file name, which also contains the
revision number, e.g. ELxxxx-xxxx_REV0016_SW01.efw
• for password=1 to be entered in the download dialog. If password=0 (default setting) only the firmware
update is carried out, without an ESI update.
• for the device to support this function. The function usually cannot be retrofitted; it is a component of
many new developments from year of manufacture 2016.
NOTE
Risk of damage to the device!
Note the following when downloading new device files
In the event of malfunctions during the update process the EtherCAT device may become unusable and re-
quire re-commissioning by the manufacturer.
The ESI device description is stored locally on the slave and loaded on start-up. Each device description has
a unique identifier consisting of slave name (9 characters/digits) and a revision number (4 digits). Each slave
configured in the System Manager shows its identifier in the EtherCAT tab:
Fig. 184: Device identifier consisting of name EL3204-0000 and revision -0016
The configured identifier must be compatible with the actual device description used as hardware, i.e. the
description which the slave has loaded on start-up (in this case EL3204). Normally the configured revision
must be the same or lower than that actually present in the terminal network.
For further information on this, please refer to the EtherCAT system documentation.
The simplest way to ascertain compliance of configured and actual device description is to scan the
EtherCAT boxes in TwinCAT mode Config/FreeRun:
Fig. 185: Scan the subordinate field by right-clicking on the EtherCAT device
If the found field matches the configured field, the display shows
otherwise a change dialog appears for entering the actual data in the configuration.
In this example in Fig. Change dialog, an EL3201-0000-0017 was found, while an EL3201-0000-0016 was
configured. In this case the configuration can be adapted with the Copy Before button. The Extended
Information checkbox must be set in order to display the revision.
The new ESI description is selected in the following dialog, see Fig. Selecting the new ESI. The checkbox
Show Hidden Devices also displays older, normally hidden versions of a slave.
A progress bar in the System Manager shows the progress. Data are first written, then verified.
Beckhoff EtherCAT slaves feature serial numbers applied by laser. The serial number has the following
structure: KK YY FF HH
12 - week of production 12
10 - year of production 2010
03 - firmware version 03
02 - hardware version 02
The TwinCAT System Manager shows the version of the controller firmware if the master can access the
slave online. Click on the E-Bus Terminal whose controller firmware you want to check (in the example
terminal 2 (EL3204)) and select the tab CoE Online (CAN over EtherCAT).
In Fig. Display of EL3204 firmware version the firmware version of the selected EL3204 is shown as 03 in
CoE entry 0x100A.
In (A) TwinCAT 2.11 shows that the Online CoE directory is currently displayed. If this is not the case, the
Online directory can be loaded via the Online option in Advanced Settings (B) and double-clicking on
AllObjects.
Switch to the Online tab to update the controller firmware of a slave, see Fig. Firmware Update.
Proceed as follows, unless instructed otherwise by Beckhoff support. Valid for TwinCAT 2 and 3 as
EtherCAT master.
• Switch TwinCAT system to ConfigMode/FreeRun with cycle time >= 1 ms (default in ConfigMode is 4
ms). A FW-Update during real time operation is not recommended.
The firmware version number included in the terminal serial number contains both firmware components. If
one of these firmware components is modified this version number is updated.
The TwinCAT System Manager indicates the FPGA firmware version. Click on the Ethernet card of your
EtherCAT strand (Device 2 in the example) and select the Online tab.
The Reg:0002 column indicates the firmware version of the individual EtherCAT devices in hexadecimal and
decimal representation.
If the column Reg:0002 is not displayed, right-click the table header and select Properties in the context
menu.
The Advanced Settings dialog appears where the columns to be displayed can be selected. Under
Diagnosis/Online View select the '0002 ETxxxx Build' check box in order to activate the FPGA firmware
version display.
Update
The following sequence order have to be met if no other specifications are given (e.g. by the Beckhoff
support):
• Switch TwinCAT system to ConfigMode/FreeRun with cycle time >= 1 ms (default in ConfigMode is
4 ms). A FW-Update during real time operation is not recommended.
• In the TwinCAT System Manager select the terminal for which the FPGA firmware is to be updated (in
the example: Terminal 5: EL5001) and
click the Advanced Settings button in the EtherCAT tab:
• The Advanced Settings dialog appears. Under ESC Access/E²PROM/FPGA click on Write FPGA
button:
• Select the file (*.rbf) with the new FPGA firmware, and transfer it to the EtherCAT device:
NOTE
Risk of damage to the device!
A download of firmware to an EtherCAT device must not be interrupted in any case! If you interrupt this
process by switching off power supply or disconnecting the Ethernet link, the EtherCAT device can only be
recommissioned by the manufacturer!
Select the required slaves and carry out the firmware update in BOOTSTRAP mode as described above.
Double-click on SubIndex 001 to enter the Set Value dialog. Enter the value 1684107116 in field Dec or the
value 0x64616F6C in field Hex and confirm with OK (Fig. Entering a restore value in the Set Value dialog).
All backup objects are reset to the delivery state.
Please contact your Beckhoff branch office or representative for local support and service on Beckhoff
products!
The addresses of Beckhoff's branch offices and representatives round the world can be found on her internet
pages:
http://www.beckhoff.com
You will also find further documentation for Beckhoff components there.
Beckhoff Headquarters
Huelshorstweg 20
33415 Verl
Germany
Phone: +49(0)5246/963-0
Fax: +49(0)5246/963-198
e-mail: info@beckhoff.com
Beckhoff Support
Support offers you comprehensive technical assistance, helping you not only with the application of
individual Beckhoff products, but also with other, wide-ranging services:
• support
• design, programming and commissioning of complex automation systems
• and extensive training program for Beckhoff system components
Hotline: +49(0)5246/963-157
Fax: +49(0)5246/963-9157
e-mail: support@beckhoff.com
Beckhoff Service
The Beckhoff Service Center supports you in all matters of after-sales service:
• on-site service
• repair service
• spare parts service
• hotline service
Hotline: +49(0)5246/963-460
Fax: +49(0)5246/963-479
e-mail: service@beckhoff.com
List of illustrations
Fig. 1 EL5021 EL terminal, standard IP20 IO device with serial/ batch number and revision ID (since
2014/01)....................................................................................................................................... 9
Fig. 2 EK1100 EtherCAT coupler, standard IP20 IO device with serial/ batch number......................... 10
Fig. 3 CU2016 switch with serial/ batch number.................................................................................... 10
Fig. 4 EL3202-0020 with serial/ batch number 26131006 and unique ID-number 204418 ................... 10
Fig. 5 EP1258-00001 IP67 EtherCAT Box with batch number/ date code 22090101 and unique se-
rial number 158102...................................................................................................................... 11
Fig. 6 EP1908-0002 IP67 EtherCAT Safety Box with batch number/ date code 071201FF and
unique serial number 00346070 .................................................................................................. 11
Fig. 7 EL2904 IP20 safety terminal with batch number/ date code 50110302 and unique serial num-
ber 00331701............................................................................................................................... 11
Fig. 8 ELM3604-0002 terminal with unique ID number (QR code) 100001051 and serial/ batch num-
ber 44160201............................................................................................................................... 11
Fig. 9 EL6601, EL6614 .......................................................................................................................... 12
Fig. 10 EL6601 as a virtual, field-distributed switch................................................................................. 13
Fig. 11 EL66xx data diagram................................................................................................................... 15
Fig. 12 IP settings EtherCAT port ............................................................................................................ 16
Fig. 13 Connection failure between primary EtherCAT port and 1st slave (X) ........................................ 17
Fig. 14 Real frame structure from the TwinCAT System Manager .......................................................... 18
Fig. 15 Default setting of the EL66xx as switch port without IP address assignment.............................. 19
Fig. 16 From FW03: Settings for dynamically assigned IP address ........................................................ 19
Fig. 17 Default mailbox settings............................................................................................................... 20
Fig. 18 Increasing the mailbox................................................................................................................. 21
Fig. 19 TwinCAT 2.11, virtual TwinCAT switch........................................................................................ 21
Fig. 20 TwinCAT 2.11, virtual TwinCAT switch........................................................................................ 22
Fig. 21 Notice on exceeding configured data volume.............................................................................. 24
Fig. 22 Network variable sample configuration on an EL6601 ................................................................ 24
Fig. 23 Append device ............................................................................................................................. 27
Fig. 24 Select EL6601 ............................................................................................................................. 27
Fig. 25 Append box.................................................................................................................................. 28
Fig. 26 Append network variable ............................................................................................................. 28
Fig. 27 Link device with EL6601 .............................................................................................................. 28
Fig. 28 Append new device ..................................................................................................................... 29
Fig. 29 Select EtherCAT Automation Protocol......................................................................................... 29
Fig. 30 Device assignment to the EL66xx ............................................................................................... 29
Fig. 31 Append box.................................................................................................................................. 30
Fig. 32 Publisher/Subscriber.................................................................................................................... 30
Fig. 33 Topology view.............................................................................................................................. 30
Fig. 34 Virtual TwinCAT switch in the CX20x0 & CX50x0 system........................................................... 31
Fig. 35 Dialog for selection of the PCI port .............................................................................................. 31
Fig. 36 Insertion of the EL66xx in the Configuration................................................................................ 32
Fig. 37 New Network “Local Area Connection” in the Windows network connections ............................ 32
Fig. 38 System manager current calculation .......................................................................................... 34
Fig. 39 EtherCAT tab -> Advanced Settings -> Behavior -> Watchdog .................................................. 35
Fig. 40 States of the EtherCAT State Machine........................................................................................ 37
Fig. 41 "CoE Online " tab ........................................................................................................................ 39