Documentation

EL6601, EL6614

Switch Terminals for Ethernet

Version: 4.2
Date: 2019-05-03
Table of contents

Table of contents
1 Foreword .................................................................................................................................................... 5
1.1 Notes on the documentation.............................................................................................................. 5
1.2 Safety instructions ............................................................................................................................. 6
1.3 Documentation issue status .............................................................................................................. 7
1.4 Version identification of EtherCAT devices ....................................................................................... 8

2 Product overview..................................................................................................................................... 12
2.1 Introduction ...................................................................................................................................... 12
2.2 Technical data ................................................................................................................................. 14
2.3 Basic function principles .................................................................................................................. 14
2.4 EL66xx - Non Realtime.................................................................................................................... 17
2.5 EL66xx and Beckhoff network variables.......................................................................................... 22
2.5.1 Explanation network variables ......................................................................................... 22
2.5.2 Settings in the System Manager...................................................................................... 24
2.5.3 Notes ............................................................................................................................... 25
2.5.4 Suppress publisher .......................................................................................................... 25
2.5.5 Filter subscribers ............................................................................................................. 26
2.5.6 Setting up TwinCAT 2.10................................................................................................. 26
2.5.7 Setting up TwinCAT 2.11................................................................................................. 29
2.6 Configuration in the CX20x0 & CX50x0 system .............................................................................. 30

3 Basics communication ........................................................................................................................... 33


3.1 EtherCAT basics.............................................................................................................................. 33
3.2 EtherCAT cabling – wire-bound....................................................................................................... 33
3.3 General notes for setting the watchdog ........................................................................................... 34
3.4 EtherCAT State Machine ................................................................................................................. 36
3.5 CoE Interface................................................................................................................................... 38
3.6 Distributed Clock ............................................................................................................................. 43

4 Mounting and wiring................................................................................................................................ 44


4.1 Recommended mounting rails ......................................................................................................... 44
4.2 Mounting and demounting - terminals with front unlocking ............................................................. 44
4.3 Positioning of passive Terminals ..................................................................................................... 45
4.4 Installation positions ........................................................................................................................ 46
4.5 ATEX - Special conditions (extended temperature range) .............................................................. 48
4.6 ATEX Documentation ...................................................................................................................... 49

5 Commissioning........................................................................................................................................ 50
5.1 TwinCAT Development Environment .............................................................................................. 50
5.1.1 Installation of the TwinCAT real-time driver..................................................................... 50
5.1.2 Notes regarding ESI device description........................................................................... 56
5.1.3 OFFLINE configuration creation ...................................................................................... 60
5.1.4 ONLINE configuration creation ........................................................................................ 65
5.1.5 EtherCAT subscriber configuration.................................................................................. 73
5.2 General Notes - EtherCAT Slave Application .................................................................................. 82
5.3 Object description and parameterization ......................................................................................... 90
5.3.1 Objects for commissioning............................................................................................... 90

EL6601, EL6614 Version: 4.2 3


Table of contents

5.3.2 Objects for regular operation ........................................................................................... 91


5.3.3 Standard objects (0x1000-0x1FFF) ................................................................................. 91
5.3.4 Profile-specific objects (0x6000-0xFFFF) ........................................................................ 94
5.4 Beckhoff network variables.............................................................................................................. 97
5.4.1 Introduction ...................................................................................................................... 97
5.4.2 Configuration of the Publisher ......................................................................................... 98
5.4.3 Configuration of the Subscriber ..................................................................................... 101
5.4.4 Beckhoff network variables - Settings............................................................................ 105

6 Application samples.............................................................................................................................. 113


6.1 Sample programs .......................................................................................................................... 113
6.2 Application sample - network printer ............................................................................................. 114
6.3 Application sample - Service interface with remote desktop ......................................................... 119
6.4 Application sample - Lower-level control system........................................................................... 129
6.5 Application sample – setting up an EtherCAT Master PC as a network bridge............................. 134
6.6 Application sample - Flexible Ethernet Port................................................................................... 139

7 Appendix ................................................................................................................................................ 144


7.1 UL notice ....................................................................................................................................... 144
7.2 Firmware compatibility ................................................................................................................... 145
7.3 Firmware Update EL/ES/EM/ELM/EPxxxx .................................................................................... 146
7.3.1 Device description ESI file/XML..................................................................................... 147
7.3.2 Firmware explanation .................................................................................................... 150
7.3.3 Updating controller firmware *.efw................................................................................. 151
7.3.4 FPGA firmware *.rbf....................................................................................................... 152
7.3.5 Simultaneous updating of several EtherCAT devices.................................................... 156
7.4 Restoring the delivery state ........................................................................................................... 157
7.5 Support and Service ...................................................................................................................... 158

4 Version: 4.2 EL6601, EL6614


Foreword

1 Foreword

1.1 Notes on the documentation


Intended audience

This description is only intended for the use of trained specialists in control and automation engineering who
are familiar with the applicable national standards.
It is essential that the documentation and the following notes and explanations are followed when installing
and commissioning these components.
It is the duty of the technical personnel to use the documentation published at the respective time of each
installation and commissioning.

The responsible staff must ensure that the application or use of the products described satisfy all the
requirements for safety, including all the relevant laws, regulations, guidelines and standards.

Disclaimer

The documentation has been prepared with care. The products described are, however, constantly under
development.

We reserve the right to revise and change the documentation at any time and without prior announcement.

No claims for the modification of products that have already been supplied may be made on the basis of the
data, diagrams and descriptions in this documentation.

Trademarks

Beckhoff®, TwinCAT®, EtherCAT®, EtherCAT P®, Safety over EtherCAT®, TwinSAFE®, XFC® and XTS® are
registered trademarks of and licensed by Beckhoff Automation GmbH.
Other designations used in this publication may be trademarks whose use by third parties for their own
purposes could violate the rights of the owners.

Patent Pending

The EtherCAT Technology is covered, including but not limited to the following patent applications and
patents: EP1590927, EP1789857, DE102004044764, DE102007017835 with corresponding applications or
registrations in various other countries.

The TwinCAT Technology is covered, including but not limited to the following patent applications and
patents: EP0851348, US6167425 with corresponding applications or registrations in various other countries.

EtherCAT® is registered trademark and patented technology, licensed by Beckhoff Automation GmbH,
Germany.

Copyright

© Beckhoff Automation GmbH & Co. KG, Germany.


The reproduction, distribution and utilization of this document as well as the communication of its contents to
others without express authorization are prohibited.
Offenders will be held liable for the payment of damages. All rights reserved in the event of the grant of a
patent, utility model or design.

EL6601, EL6614 Version: 4.2 5


Foreword

1.2 Safety instructions


Safety regulations

Please note the following safety instructions and explanations!


Product-specific safety instructions can be found on following pages or in the areas mounting, wiring,
commissioning etc.

Exclusion of liability

All the components are supplied in particular hardware and software configurations appropriate for the
application. Modifications to hardware or software configurations other than those described in the
documentation are not permitted, and nullify the liability of Beckhoff Automation GmbH & Co. KG.

Personnel qualification

This description is only intended for trained specialists in control, automation and drive engineering who are
familiar with the applicable national standards.

Description of instructions

In this documentation the following instructions are used.


These instructions must be read carefully and followed without fail!

DANGER
Serious risk of injury!
Failure to follow this safety instruction directly endangers the life and health of persons.

WARNING
Risk of injury!
Failure to follow this safety instruction endangers the life and health of persons.

CAUTION
Personal injuries!
Failure to follow this safety instruction can lead to injuries to persons.

NOTE
Damage to environment/equipment or data loss
Failure to follow this instruction can lead to environmental damage, equipment damage or data loss.

Tip or pointer
This symbol indicates information that contributes to better understanding.

6 Version: 4.2 EL6601, EL6614


Foreword

1.3 Documentation issue status


Version Comment
4.2 - Update chapter “Object description”
- Update structure
- Revision status updated
4.1 - Note in chapter “address assignment” added
- Update structure
- Revision status updated
4.0 - Migration
- Update structure
- Revision status updated
3.4 - Update structure
- “Technical data” section updated
- Revision status updated
3.3 - Update structure
- “Technical data” section updated
- Chapter “Introduction” updated
- Chapter "Configuration on the CX20x0 & CX50x0 System" inserted
- Revision status updated
3.2 - Update structure
- “Technical data” section updated
- Chapter "EtherCAT-PC as Network Bridge" updated
- Revision status updated
3.1 - Update structure
- “Technical data” section updated
- Update chapter "Mounting and wiring"
3.0 - Notes on cable redundancy added
2.9 - Notes Subscriber filter, diagnostic data added
2.8 - Technical notes added
2.7 - Technical notes added
2.6 - Technical notes added
2.5 - Chapter Firmware updated
2.4 - Technical notes network variables added
2.3 - Application sample added
2.2 - Technical notes added
2.1 - Technical notes (Subscriber, Publisher) added
2.0 - Technical notes and CoE objects added
1.9 - Note on installation position added
1.8 - Technical notes added
1.7 - Technical notes network variables added
1.6 - LED and port description added
1.5 - EL6614 added
1.4 - Application sample added
1.3 - Technical data added (object description)
1.2 - Technical data completed, explanations on mailbox communication and network variables
added
1.1 - Technical data added, UL labelling added
1.0 - Technical data added, first public issue
0.1 - Preliminary documentation for EL6601

EL6601, EL6614 Version: 4.2 7


Foreword

1.4 Version identification of EtherCAT devices


Designation

A Beckhoff EtherCAT device has a 14-digit designation, made up of


• family key
• type
• version
• revision
Example Family Type Version Revision
EL3314-0000-0016 EL terminal 3314 (4-channel thermocouple 0000 (basic type) 0016
(12 mm, non- terminal)
pluggable connection
level)
ES3602-0010-0017 ES terminal 3602 (2-channel voltage 0010 (high- 0017
(12 mm, pluggable measurement) precision version)
connection level)
CU2008-0000-0000 CU device 2008 (8-port fast ethernet switch) 0000 (basic type) 0000

Notes
• The elements mentioned above result in the technical designation. EL3314-0000-0016 is used in the
example below.
• EL3314-0000 is the order identifier, in the case of “-0000” usually abbreviated to EL3314. “-0016” is the
EtherCAT revision.
• The order identifier is made up of
- family key (EL, EP, CU, ES, KL, CX, etc.)
- type (3314)
- version (-0000)
• The revision -0016 shows the technical progress, such as the extension of features with regard to the
EtherCAT communication, and is managed by Beckhoff.
In principle, a device with a higher revision can replace a device with a lower revision, unless specified
otherwise, e.g. in the documentation.
Associated and synonymous with each revision there is usually a description (ESI, EtherCAT Slave
Information) in the form of an XML file, which is available for download from the Beckhoff web site.
From 2014/01 the revision is shown on the outside of the IP20 terminals, see Fig. “EL5021 EL terminal,
standard IP20 IO device with batch number and revision ID (since 2014/01)”.
• The type, version and revision are read as decimal numbers, even if they are technically saved in
hexadecimal.

Identification number

Beckhoff EtherCAT devices from the different lines have different kinds of identification numbers:

Production lot/batch number/serial number/date code/D number

The serial number for Beckhoff IO devices is usually the 8-digit number printed on the device or on a sticker.
The serial number indicates the configuration in delivery state and therefore refers to a whole production
batch, without distinguishing the individual modules of a batch.

Structure of the serial number: KK YY FF HH

KK - week of production (CW, calendar week)


YY - year of production
FF - firmware version
HH - hardware version

8 Version: 4.2 EL6601, EL6614


Foreword

Example with
Ser. no.: 12063A02: 12 - production week 12 06 - production year 2006 3A - firmware version 3A 02 -
hardware version 02

Exceptions can occur in the IP67 area, where the following syntax can be used (see respective device
documentation):

Syntax: D ww yy x y z u

D - prefix designation
ww - calendar week
yy - year
x - firmware version of the bus PCB
y - hardware version of the bus PCB
z - firmware version of the I/O PCB
u - hardware version of the I/O PCB

Example: D.22081501 calendar week 22 of the year 2008 firmware version of bus PCB: 1 hardware version
of bus PCB: 5 firmware version of I/O PCB: 0 (no firmware necessary for this PCB) hardware version of I/O
PCB: 1

Unique serial number/ID, ID number

In addition, in some series each individual module has its own unique serial number.

See also the further documentation in the area


• IP67: EtherCAT Box
• Safety: TwinSafe
• Terminals with factory calibration certificate and other measuring terminals

Examples of markings

Fig. 1: EL5021 EL terminal, standard IP20 IO device with serial/ batch number and revision ID (since
2014/01)

EL6601, EL6614 Version: 4.2 9


Foreword

Fig. 2: EK1100 EtherCAT coupler, standard IP20 IO device with serial/ batch number

Fig. 3: CU2016 switch with serial/ batch number

Fig. 4: EL3202-0020 with serial/ batch number 26131006 and unique ID-number 204418

10 Version: 4.2 EL6601, EL6614


Foreword

Fig. 5: EP1258-00001 IP67 EtherCAT Box with batch number/ date code 22090101 and unique serial
number 158102

Fig. 6: EP1908-0002 IP67 EtherCAT Safety Box with batch number/ date code 071201FF and unique serial
number 00346070

Fig. 7: EL2904 IP20 safety terminal with batch number/ date code 50110302 and unique serial number
00331701

Fig. 8: ELM3604-0002 terminal with unique ID number (QR code) 100001051 and serial/ batch number
44160201

EL6601, EL6614 Version: 4.2 11


Product overview

2 Product overview

2.1 Introduction

Fig. 9: EL6601, EL6614

Switch terminals for Ethernet

The switch terminals for Ethernet are used for decentralized connection of random Ethernet devices to the
EtherCAT terminal network. The EtherCAT system relays the Ethernet communication of the connected
devices fully transparent and collision-free.

The 4 port Ethernet switch terminal EL6614 purposefully forwards the incoming frames from the ports to the
destination ports. In full duplex mode, it thus enables collision-free communication of the connected devices
with each other.

Any number of EL6601/EL6614 can be used simultaneously and at any position in the EtherCAT terminal
network. No configuration is required. In conjunction with the network port at the EtherCAT master the
EL6601/EL6614 devices operate like a virtual switch whose ports are distributed in the field. The EtherCAT
fieldbus is the backbone of this switch.

12 Version: 4.2 EL6601, EL6614


Product overview

Fig. 10: EL6601 as a virtual, field-distributed switch

Further benefits underline the particular suitability for the application in industrial environments:
• Compact design in EtherCAT terminal housing
• 10/100 MBaud, half or full duplex, with automatic baud rate detection
• Autocrossing (automatic detection of crossed lines)

LEDs

LED Color Meaning


RUN green These LEDs indicate the terminal's operating state:
off State of the EtherCAT State Machine [} 73]: INIT = initialization of
the terminal or BOOTSTRAP = function for firmware updates [} 146]
of the terminal
flashing State of the EtherCAT State Machine: PREOP = function for mailbox
communication and different standard-settings set
single flash State of the EtherCAT State Machine: SAFEOP = verification of the
Sync Manager [} 74] channels and the distributed clocks.
Outputs remain in safe state
on State of the EtherCAT State Machine: OP = normal operating state;
mailbox and process data communication is possible
Link/Act green Connection / data exchange field bus
*Link/Act X1 - green Connection / data exchange Ethernet port X1- X4
X4
Eth Err red Error message EtherCAT (see Diagnostics [} 16])

* only EL6614

Connections

1 x RJ45 with 10BASE-T/100BASE-TX Ethernet (EL6601)


4 x RJ45 with 10BASE-T/100BASE-TX Ethernet (EL6614)

EL6601, EL6614 Version: 4.2 13


Product overview

2.2 Technical data


Technical data EL6601 EL6614
Bus system all Ethernet (IEEE 802.3) based protocols
Number of Ethernet ports 1 4
Ethernet interface 10BASE-T/100BASE-TX 10BASE-T/100BASE-TX Ethernet
Ethernet with 1 x RJ45 with 4 x RJ45
Cable length up to 100 m twisted pair
Data transfer rate 10/100 Mbit/s, IEEE 802.3u Auto negotiation, half or full duplex at 10
and 100 Mbit/s possible, automatic settings
Network variables EL6601 as of Firmware 07, EL6614 as of Firmware 03:

max 32 Publishers with total of max. 1024 bytes total data [} 22]
max 32 Subscriber with total of max. 1024 bytes total data [} 22]
Distributed Clocks no
Diagnostics Status-LEDs, CoE data about ADS
Power supply via the E-bus
Current consumption via E-bus typ. 310 mA typ. 450 mA
Electrical isolation 500 V (E-Bus/Ethernet)
Bit width in process image -
Configuration TwinCAT System Manager/EtherCAT Master
Weight approx. 75 g approx. 85 g
Permissible ambient temperature -25°C ... +60°C (extended Horizontal installation position:
range during operation temperature range) -25°C ... +60°C (extended
temperature range)

all other installation positions:


-25°C ... + 45°C, see note [} 46]
Permissible ambient temperature -40°C ... +85°C -40°C ... +85°C
range during storage
Permissible relative humidity 95 %, no condensation
Dimensions (W x H x D) approx. 26 mm x 100 mm x 52 mm (width aligned: 23 mm)
Mounting on 35 mm mounting rail conforms to EN 60715
Vibration/shock resistance conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2 / EN 61000-6-4
Protection class IP20
Installation position variable see note [} 46]
Approval CE
cULus [} 144]
ATEX [} 48]

2.3 Basic function principles


The EL66xx Ethernet Switchport terminals have 2 different operating modes, ideal for the tasks required for
Ethernet connectivity. The two operating modes, which can be active simultaneously, provide both the real-
time-critical transmission and reception of configured network variables as well as the transport of standard
Ethernet traffic, which, while it is not real-time-critical, does involve large data flows using, for instance, the IP
protocol:

14 Version: 4.2 EL6601, EL6614


Product overview

• Real-time data exchange: Publisher/subscriber, Beckhoff network variables, EtherCAT Automation


Protocol
The TwinCAT configuration file *.tsm configures an EL66xx when EtherCAT starts up with CoE
parameters in such a way that it
◦ transmits, as the publisher, data delivered through the cyclical data transfer in the real-time cycle.
◦ transmits subscribers received in the same way to the EtherCAT Master over the cyclical
EtherCAT data exchange.
Cyclical data exchange with the EL66xx is configured in the PDO settings of the EL66xx when
EtherCAT starts up, and cannot be changed online.
• Non-real-time data exchange
In parallel with this, the EL66xx can transfer Ethernet frames through the acyclic mailbox exchange
(EoE = Ethernet over EtherCAT) between the terminal and the EtherCAT Master/TwinCAT. This data
exchange is optimized for throughput, and may involve automatic fragmentation - by default, all
telegrams that are not transferred in the PDO context are transported through the acyclic channel by
means of EoE.

The flow of data in the EL66xx can be represented schematically as follows:

Fig. 11: EL66xx data diagram

The EL6601/EL6614 cannot transport an EtherNet Industrial Protocol (EtherNet/IP).

EL6601, EL6614 Version: 4.2 15


Product overview

Diagnostics

Online diagnostics

The following objects are available for initial diagnostic in the CoE directory:
• 0xFA01, subindex 01: Frame Counter Rx (incoming to RJ45 socket).
• 0xFA01, subindex 02: Frame Counter Tx (outgoing from RJ45 socket).

The values can be read from the controller using PLC function blocks (FB_EcCoeSdoRead in
TcEtherCAT.lib).

This and further diagnostic information from the CoE of the EL66xx are accessible via https://

infosys.beckhoff.com/content/1033/el6601_el6614/Resources/zip/2349552907.zip .

Error LED

The red Error LED lights up 250 ms in the event of


• Ethernet Receive Overrun --> in general, more Ethernet frames are received at the RJ45 connection
than can be transported away via EtherCAT (PDO or mailbox). The telegrams are discarded.
• Ethernet EoE Overrun --> more non-real-time frames are being received at the RJ45 connector than
can be transported away by EtherCAT/EoE The data are discarded.
• Ethernet Frame Error

If the occurrence of an overrun causes data to be lost, higher protocol layers in an Ethernet network are
responsible for repeating the transmission.

Overruns
The following measures can be used to counter overruns:
• activating the Subscriber Filter [} 22] in the EL66xx concerned
• Increasing/decelerating the cycle time of the publisher
• Suppressing temporarily publisher transmission or modulo in the System Manager
• Reducing/accelerating the EtherCAT cycle time of the subscriber, so that more data are fetched
by the EL66xx

Cable redundancy

If the EL66xx is operated in a system with cable redundancy, please keep the following in mind:
• real-time operation with network variables is possible
• in the event of non-real-time operation with IP transfer the IP traffic is routed via the primary EtherCAT
port. Therefore the Windows IP settings of this port are also used.

Fig. 12: IP settings EtherCAT port

If there is no longer a link to this port, from Windows under TwinCAT 2 or 3 there is also no IP
communication to this port currently.
For this reason, do not let the Ethernet connection between the primary EtherCAT port and the first
EtherCAT slave fail, since otherwise IP communication is no longer possible via the EL66xx.

16 Version: 4.2 EL6601, EL6614


Product overview

Fig. 13: Connection failure between primary EtherCAT port and 1st slave (X)

2.4 EL66xx - Non Realtime


EL66xx and Ethernet transport via mailbox communication

In addition to regular cyclical process data exchange an EtherCAT master offers a further mechanism for
transporting data to an EtherCAT slave or reading data from it. This mechanism is used for one-time or
dynamically alternating Data Exchange, such as e.g. the parameterization of an EtherCAT slave. Mailbox
communication can also be used for transporting large data blocks acyclically on request from master or
slave. This additional communication takes place between the cyclical process data frames (the conventional
EtherCAT frames) on the EtherCAT bus.

Data throughput in mailbox communication


Since mailbox communication can only take place between the regular process data frames, data
throughput with this communication method depends on the load of the EtherCAT bus. This means
that the Ethernet throughput of the EL6601 also depends on the load of the underlying EtherCAT
fieldbus.

The EoE method (Ethernet over EtherCAT) is used for the EL66xx. Dedicated settings are available for this
in the System Manager.

Data throughput

The data throughput of the EL66xx in Ethernet frames or bytes/second depends on


• The EtherCAT cycle time on the fieldbus: The shorter the EtherCAT cycle used for the process data,
the more acyclical mailbox queries can be completed. If several different EtherCAT cycle times are
used in an EtherCAT strand the fastest cycle time is the relevant time
• The time between the process data frames that is available for mailbox communication: The longer the
Ethernet line is free for acyclical mailbox communication, the higher the Ethernet data throughput of the
EL6601.
• The mailbox size [} 19] in bytes: The larger the mailbox, the more Ethernet frames the EL6601 can
send to the EtherCAT master or received from it simultaneously.
• The number of terminals in the EtherCAT system that use mailbox communication at the same time.
• The EoE settings [} 21] in the TwinCAT System Manager, see the EoE section.

The following values were determined as samples (TwinCAT 2.10, 2.11)


• > 5 Mbit/s from the EL6601 to the Ethernet device
• > 2 Mbit/s from the Ethernet device to the EL6601

with an EtherCAT cycle time of 100 µs and a mailbox size of 1024 bytes.

EL6601, EL6614 Version: 4.2 17


Product overview

Tips for shortening the response times


We recommend the following procedure to shorten the response times in your application (e.g. to
ping requests): Significantly lower the EtherCAT cycle time currently being used or insert a new task
with a lower cycle time, e.g.: 500 µs if up to this point you have been using 2.5 ms EtherCAT cycle.
Important: This task must access genuine IO process data from the EtherCAT slaves and be recog-
nizable under Device EtherCAT -> Tab EtherCAT, see Fig. Real frame structure from the TwinCAT
System Manager

Fig. 14: Real frame structure from the TwinCAT System Manager

Note regarding the specified values


These values are typical values without warranty. Throughput rates may differ in different applica-
tions depending on boundary conditions.

Address assignment

From FW03 onwards, the EL6601/6614 can also assign IP addresses to connected devices and works as a
DHCP or BOOTP server for one device. The following settings are required in the System Manager (EL66xx
--> Advanced Settings --> Mailbox --> EoE):
• Setting "Switch Port", Fig. Default setting of the EL66xx as switch port without IP address assignment.
The EL66xx works like a normal switch and passes Ethernet frames transparently through to TwinCAT/
Windows
• Setting for “IP Port”, Fig. From FW03: Settings for dynamically assigned IP address
The EL66xx works with address assignment to one connected Ethernet device. A DHCP or a BootP
Client must be activated in the device (refer to the network adaptor settings in the operating system).
The EL66xx responds to the device’s corresponding DHCP/BootP query by assigning the specified IP
address/subnet mask to the device. In the DHCP method this address is regularly queried by the client
and assigned to the server/EL66xx.

18 Version: 4.2 EL6601, EL6614


Product overview

Fig. 15: Default setting of the EL66xx as switch port without IP address assignment

Fig. 16: From FW03: Settings for dynamically assigned IP address

Please note:
• The “DHCP” checkbox must not be used - the “IP address” checkbox activates the DHCP/BootP
function in the EL66xx.
• The Gateway, Mask and Server settings are likewise communicated to the client/the device
• Only one address can be assigned, i.e. no switch with connected subscribers may follow.
• the address range must be identical to that of the EtherCAT adapter.
• DHCP Server Identifier: several DHCP Servers need a ServerID in the response telegram.
Solution for the EL6601 from firmware 15: the value 0x1000 has to be entered in the object 0xF800:01.
If a Default Gateway is registered in the EL6601, it is used as a DHCP Server Identifier.

Mailbox settings

The mailbox size can be modified in the Beckhoff TwinCAT System Manager:

EL6601, EL6614 Version: 4.2 19


Product overview

Fig. 17: Default mailbox settings

By default the mailbox is set to 522 Byte Input and 522 Byte Output (20 Ahex), see Fig. Default Settings of the
Mailbox, Entries for SyncManager 0 and 1. To increase the data throughput the size of the mailbox can be
increased to 1024 Byte, see Fig. Increasing the Size of the Mailbox.

Default mailbox size


As of Revision EL66xx-0000-0018 the mailbox is already set to 1024 Byte by default in both direc-
tions, therefore it cannot be further enlarged.
The previous statements apply for terminals with Revision -0000, -0016 or -0017.

20 Version: 4.2 EL6601, EL6614


Product overview

Fig. 18: Increasing the mailbox

Under EL6601 -> EtherCAT tab -> "Advanced Settings…" -> "Mailbox" the "Out Size" can be set to
hexadecimal values between 42dec/2Ahex and 1024dec/400hex bytes. Ethernet frames that are larger than the
EL6601 mailbox are fragmented by the EL6601 or the EtherCAT master and reassembled after passing
through the EtherCAT system.

Virtual switch setting

The EL66xx devices in the TwinCAT system generally appear as virtual switches, with the EtherCAT system
as the "backbone".

Fig. 19: TwinCAT 2.11, virtual TwinCAT switch

The required settings will be found under TwinCAT | EtherCAT device | Advanced settings

EL6601, EL6614 Version: 4.2 21


Product overview

Fig. 20: TwinCAT 2.11, virtual TwinCAT switch

Notes
• If a large number of EL66xx devices are used along the EtherCAT strand it may be helpful to increase
the value of MaxFrames
• If the EL66xx is used exclusively to transfer network variables, ConnectToTcpStack should be
deactivated
• IP-routing is active by default. This can also be checked by entering "ipconfig /all" on the command line
(Windows)

2.5 EL66xx and Beckhoff network variables

2.5.1 Explanation network variables

Network variables

The EL66xx support sending/receiving network variables. This applies for the EL6601 as of Firmware 07, for
the EL6614 as of Firmware 03.

A maximum of 32 for each, publishers and subscriber, are permitted per EL66xx.

Hardware replacement
If the system was designed with a previous EL6601 version (EL6601-0000-0000), this can be re-
placed with versions from EL6601-0000-0017 without problem. If the system was designed for ver-
sion EL6601-0000-0017 or higher, replacement with a previous version is not possible due to un-
supported network variables.

Network variables are specially configured Ethernet frames that enable Beckhoff devices to communicate
with each other in real-time via Ethernet. Such device can send (publisher) or receive (subscriber)
messages.
An Ethernet frame is sent for each publisher (Ethernet-based). A maximum of 1500 bytes of data can thus
be sent per publisher. Within a publisher/subscriber several variables (publisher and subscriber variables)
can be created.
Generally, several publishers/subscribers can be configured for each sending/receiving device (e.g. IPC or
EL6601).

Based on the sample of a data sender the hierarchy therefore consists of


• the sending device with a minimum of one Ethernet interface: IPC, CX, FC9011, EL6601, ...

22 Version: 4.2 EL6601, EL6614


Product overview

◦ FastEthernet/100 MBit and 1 GBit are supported


◦ This Ethernet interface is configured in the local TwinCAT System Manager as a real-time
Ethernet device
• 1..n configured publishers - each publisher is sent as an independent Ethernet frame and can therefore
contain a maximum of 1500 bytes
• 1..n publisher variables contained therein for linking with the task/PLC
◦ For each publisher variable the user data and diagnostic data [} 22] are transferred

On the receiver side the configuration is mirrored.

The EL66xx can also process publishers and subscribers which are frame data
• Max. 32 publishers and/or subscribers
• For each transmit direction (publisher or subscriber) the following maxima apply:
◦ all publishers: 1024 bytes total data [} 22]
◦ all subscribers: 1024 bytes total data [} 22]

Update of the terminal


The values above apply for a EL6601/6614-0000-0018. Version -0017 only supports a maximum of
300 bytes per publisher/subscriber. If a -0017 terminal is used, the values specified above can be
achieved by an update to revision -0018. Please contact our technical support.

With appropriate EtherCAT cycle time and depending on the scale and number of the publishers/subscribers
configured in the EL66xx, real-time cycle times down to 500 µs or below are possible.

Typical throughput values for EL6601, FW08, Rev. EL6601-0000-0018 are


• 1 publisher with 1000 bytes, 1 subscriber with 1000 bytes, simultaneous bidirectional operation: 2 ms
• 1 publisher with 100 bytes, 1 subscriber with 100 bytes, simultaneous bidirectional operation: 300 µs

Both characteristic values were determined with this https://infosys.beckhoff.com/content/1033/

el6601_el6614/Resources/zip/2349555083.zip . TwinCAT from version 2.11 is required for the *.tsm


System Manager file.

The EL6601 is used as a sample to explain configuration as publisher or subscriber for network variables.
The dialogs under TwinCAT 2.10 and TwinCAT 2.11 here are slightly different.

The following descriptions of the dialogs of the EL6601 in the TwinCAT System Manager can be applied
equally to the EL6614.

Note regarding the term total data

For each data direction the EL6601/EL6614 from Rev. -0018 can transfer a maximum of 1024 byte total
data. The total data consist of the user data (e.g. a UDINT) and the diagnostic data for the EL66xx.

Formula for number of diagnostic data bytes


• Publisher direction: 2 + ((number of publishers) * 2)
• Subscriber direction: 2 + ((number of subscriber variables) * 4)

If the configured data quantity exceeds 1024 bytes, a corresponding message window appears when
activation is attempted:

EL6601, EL6614 Version: 4.2 23


Product overview

Fig. 21: Notice on exceeding configured data volume

Note regarding the data quantity

The EL66xx (EL6601 from FW07, EL6614 from FW03) has an 8 kbyte data memory with the following
default allocation

Type Usable extent Operation mode Allocated memory


Mailbox Out 1024 bytes 1024 bytes (fixed)
Mailbox in 1024 bytes 1024 bytes (fixed)
Publisher 1024 bytes 3-buffer mode 3072 bytes
Subscriber 1024 bytes 3-buffer mode 3072 bytes

If more publisher or subscriber data are required for an application, the SyncManagers can be modified
accordingly. The mailbox cannot be modified.

2.5.2 Settings in the System Manager


Appearance of the variables
Depending on the platform used (PC or EL66xx), the publisher/subscriber will appear differently. A
publisher/subscriber can be created:
• on a PC network interface, see Beckhoff network variables - Settings [} 105]
• on an EL66xx

The following sample illustrates the setup for a publisher and a subscriber variable (each with a size of a 16-
bit word) on an EL6601 under TwinCAT 2.10.

Fig. 22: Network variable sample configuration on an EL6601

24 Version: 4.2 EL6601, EL6614


Product overview

Process data:
• "CycleIdx": must be served by the application in order to be evaluated on the subscriber side
• "CycleIndex": CycleIdx counterpart on the subscriber side.
• "VarData": the data to be sent.

2.5.3 Notes
• The RT statistics displays are not supported under TwinCAT for an EL66xx-RT device.
Solution: As an alternative, corresponding CoE parameters can be read for diagnostic purposes.
• The publisher features of "OnChangeOnly" and "DataExchange (divider/modulo)" are not supported
together with the EL66xx.
Solution: [from FW08] Transmitting the configured publisher variables can be cyclically suppressed by
DevCtrl.
• If a publisher is set up on an EL66xx, the publisher's CycleIndex [} 106] must be taken care of by the
user. On a PC, on the other hand, they are incremented by TwinCAT.
• The following is recommended for diagnosis of a network variable connection:
1. Monitor the link status in the "DevState" of the RT device (Device --> Inputs --> DevState). The
expected state is DevState = 0.
2. Monitor the Quality and CycleIndex in the subscriber.
• The link LED in the EL66xx only indicates the status of the cable connection, not that of any network
variable connection that may exist.
• If the EL66xx is used exclusively to transfer network variables, ConnectToTcpStack [} 22] should be
deactivated.
• A maximum of 32 for each, publishers and subscriber, are permitted per EL66xx.

2.5.4 Suppress publisher

Applicable: TwinCAT from version 2.11, EL6601 from FW08, EL6614 from FW04

If the EL66xx is operated with a short cycle time and with publishers configured, this can place a high loading
on the connected network. For this reason, the EL66xx can be configured in such a way that the
transmission of individual publishers can be blocked through the DevCtrl variable. The object 0xF800:02
must be occupied in the CoE (CanOpenOverEtherCAT) for this purpose.

Groups of publisher boxes can be blocked by setting appropriate bits (publisher frames). The topmost 4 bits
(the high nibble of high byte) from 0xF800:02 specify the granularity of the groups 1..15, i.e. how many
publisher frames are handled together as one group:

The upper 8 bits of DevCtrl (format: 16 bits) then block the transmission of the publisher frames located in
the corresponding group in the current cycle.

High byte of DevCtrl :


• 0 = no blocking
• n = each bit in DevCtrl corresponds to a group of n publishers, where n has a value in the range [1..31]

It follows that a maximum of 8 groups of publishers can be blocked.

Sample:

DevCtrl.10 = true and 0xF800:02 = 0x2000 signifies that the third group will be blocked in this PLC cycle.
One group consists of 2 publisher frames, which means that in this case all the publisher variables that are
located in publisher frames 5 and 6 will not be transmitted.

EL6601, EL6614 Version: 4.2 25


Product overview

NOTE
Suppressing individual publishers
The structure of a "publisher" as a publisher box in the System Manager is
- an Ethernet frame containing
- n publishers
The individual bits in DevCtrl each block a group of publisher frames.

The success achieved in this way can be observed using, for instance, a network monitor such as
Wireshark.

Changes in the CoE


The CoE contents can, if writable, be changed online using the TwinCAT System Manager. How-
ever, after the terminal or the EtherCAT system is restarted, this change will no longer be present;
default values will apply. As a result, any permanent change must be stored in the terminal's CoE
startup list.

Note: In this documentation, bit counting starts from 0: value.0, value.1, ...

2.5.5 Filter subscribers

Applicable: TwinCAT from version 2.11, EL6601 from FW08, EL6614 from FW06

Depending on how the Ethernet network is configured, large or small numbers of the publisher telegrams
being used there arrive at the EL66xx devices included in the network. At the start, the EL 66xx is configured
by the EtherCAT Master to the subscriber variables that it is to receive: source AMS Net ID and ID of the
variables are loaded into the CoE for each subscriber. The CoE objects 0x60n0:01 and 0x60n0:02 then
respectively contain the AmsNetId and Variables ID to be checked. The EL66xx devices can therefore filter
according to the incoming publisher IDs, and compare them with their own subscriber IDs. For this purpose
the publisher variables contained in the Ethernet frames received are disassembled and checked
individually.

If an incoming subscriber
• corresponds to a configured AMS Net ID and Variables ID, then the contents are transferred to
EtherCAT via PDO.
• does NOT correspond to the above, then the contents are transferred as standard to the acyclic
mailbox interface for transmission to the Master.

This is the standard setting of the EL66xx.

The second way generates a high acyclic EtherCAT transport load, because subscribers received by the
EL66xx are transported that should not be transported by this EL66xx at all. For this reason the subscriber
filter can be activated by the CoE entry 0xF800:02 = 0x0100 (bit 8 = TRUE). The subscriber data that do
not correspond to the AmsNetID/Variables ID filter are then discarded in the terminal and are not transferred
to the mailbox.

Filter subscribers
Activation of the subscriber filter is recommended.
Since the EL66xx needs to be re-initialized with each INIT-OP transition, it is essential to set the
named CoE entry in the startup list.

Note: In this documentation, bit counting starts from 0: value.0, value.1, ...

2.5.6 Setting up TwinCAT 2.10


Once the EtherCAT bus and its devices have been configured, the EL6601 is appended as a separate
device in the configuration tree.

26 Version: 4.2 EL6601, EL6614


Product overview

Fig. 23: Append device

In the selection dialog an EL6601 is offered as a real-time Ethernet device. The EL6601 must also be
selected here when an EL6614 is being used.

Fig. 24: Select EL6601

An imaginary box is now appended to the EL6601 as publisher or subscriber.

EL6601, EL6614 Version: 4.2 27


Product overview

Fig. 25: Append box

Fig. 26: Append network variable

The "EL6601 device" is now linked to the actual EL6601 or EL6614 in the selection dialog ("Adapter" tab ->
"Search...").

Fig. 27: Link device with EL6601

All further steps are done as described in the preceding sections.

28 Version: 4.2 EL6601, EL6614


Product overview

2.5.7 Setting up TwinCAT 2.11


If the EtherCAT configuration has been created manually or scanned from the field itself you can now
configure an EL66xx as a transmitter/receiver of network variables.

Fig. 28: Append new device

Select the EtherCAT Automation Protocol in the device dialog:

Fig. 29: Select EtherCAT Automation Protocol

The new device is automatically assigned to an available EL66xx, or this can also be done manually:

Fig. 30: Device assignment to the EL66xx

Transmitter/receiver variables must now be created:

EL6601, EL6614 Version: 4.2 29


Product overview

Fig. 31: Append box

Multiple publishers and subscribers can be created for each EtherCAT Automation Protocol device.

Fig. 32: Publisher/Subscriber

An EtherCAT Automation Protocol device appears as follows in the topology view:

Fig. 33: Topology view

All further steps are done as described in the preceding sections.

2.6 Configuration in the CX20x0 & CX50x0 system


The embedded PCs of CX20x0 and CX50x0 series feature a special integrated I/O interface for E-bus and
K-bus with automatic switching. The EL66xx devices in the TwinCAT system generally appear as virtual
switch, with the EtherCAT system as the "backbone". In the CX20x0 and CX50x0 system, the internal
interface connection is not implemented through a network interface, but through an FPGA.

30 Version: 4.2 EL6601, EL6614


Product overview

Fig. 34: Virtual TwinCAT switch in the CX20x0 & CX50x0 system

Due to the internal connection via FPGA and the automatic E-bus and K-bus detection, with offline
configuration the Ethernet port only becomes visible when the configuration is activated. To configure the
Ethernet port offline, proceed as follows:
• Due to the automatic E-bus and K-bus switching, any terminal should be connected with the
appropriate bus
• The internal PCI port is detected during offline configuration and must be selected

Fig. 35: Dialog for selection of the PCI port

• The customer specified configuration can be created, and the EL66xx can be inserted in the
configuration

EL6601, EL6614 Version: 4.2 31


Product overview

Fig. 36: Insertion of the EL66xx in the Configuration

• The Ethernet port is detected after "Reload I/O devices" (F4) and then appears under network
connections
• as "Local Area Connection 4"

Fig. 37: New Network “Local Area Connection” in the Windows network connections

• The port can now be configured as required. The settings are applied and saved. Even if the port
disappears again, the settings are retained for subsequent commissioning.

If the problem persists, i.e. if the Ethernet port of the EL66xx still fails to show up in the network connection,
see troubleshooting tips below. Follow these tips and the countermeasures listed.

Prerequisites

Check the following:


Virtual Ethernet switch is not enabled Check the virtual switch settings [} 21] and the
corresponding notes
TwinCAT2 and TwinCAT3 are installed Possible driver conflict, please contact Beckhoff support
simultaneously

32 Version: 4.2 EL6601, EL6614


Basics communication

3 Basics communication

3.1 EtherCAT basics


Please refer to the EtherCAT System Documentation for the EtherCAT fieldbus basics.

3.2 EtherCAT cabling – wire-bound


The cable length between two EtherCAT devices must not exceed 100 m. This results from the FastEthernet
technology, which, above all for reasons of signal attenuation over the length of the cable, allows a maximum
link length of 5 + 90 + 5 m if cables with appropriate properties are used. See also the Design
recommendations for the infrastructure for EtherCAT/Ethernet.

Cables and connectors

For connecting EtherCAT devices only Ethernet connections (cables + plugs) that meet the requirements of
at least category 5 (CAt5) according to EN 50173 or ISO/IEC 11801 should be used. EtherCAT uses 4 wires
for signal transfer.

EtherCAT uses RJ45 plug connectors, for example. The pin assignment is compatible with the Ethernet
standard (ISO/IEC 8802-3).

Pin Color of conductor Signal Description


1 yellow TD + Transmission Data +
2 orange TD - Transmission Data -
3 white RD + Receiver Data +
6 blue RD - Receiver Data -

Due to automatic cable detection (auto-crossing) symmetric (1:1) or cross-over cables can be used between
EtherCAT devices from Beckhoff.

Recommended cables
Suitable cables for the connection of EtherCAT devices can be found on the Beckhoff website!

E-Bus supply

A bus coupler can supply the EL terminals added to it with the E-bus system voltage of 5 V; a coupler is
thereby loadable up to 2 A as a rule (see details in respective device documentation).
Information on how much current each EL terminal requires from the E-bus supply is available online and in
the catalogue. If the added terminals require more current than the coupler can supply, then power feed
terminals (e.g. EL9410) must be inserted at appropriate places in the terminal strand.

The pre-calculated theoretical maximum E-Bus current is displayed in the TwinCAT System Manager. A
shortfall is marked by a negative total amount and an exclamation mark; a power feed terminal is to be
placed before such a position.

EL6601, EL6614 Version: 4.2 33


Basics communication

Fig. 38: System manager current calculation

NOTE
Malfunction possible!
The same ground potential must be used for the E-Bus supply of all EtherCAT terminals in a terminal block!

3.3 General notes for setting the watchdog


ELxxxx terminals are equipped with a safety feature (watchdog) that switches off the outputs after a
specifiable time e.g. in the event of an interruption of the process data traffic, depending on the device and
settings, e.g. in OFF state.

The EtherCAT slave controller (ESC) in the EL2xxx terminals features 2 watchdogs:
• SM watchdog (default: 100 ms)
• PDI watchdog (default: 100 ms)

SM watchdog (SyncManager Watchdog)

The SyncManager watchdog is reset after each successful EtherCAT process data communication with the
terminal. If no EtherCAT process data communication takes place with the terminal for longer than the set
and activated SM watchdog time, e.g. in the event of a line interruption, the watchdog is triggered and the
outputs are set to FALSE. The OP state of the terminal is unaffected. The watchdog is only reset after a
successful EtherCAT process data access. Set the monitoring time as described below.

The SyncManager watchdog monitors correct and timely process data communication with the ESC from the
EtherCAT side.

PDI watchdog (Process Data Watchdog)

If no PDI communication with the EtherCAT slave controller (ESC) takes place for longer than the set and
activated PDI watchdog time, this watchdog is triggered.
PDI (Process Data Interface) is the internal interface between the ESC and local processors in the EtherCAT
slave, for example. The PDI watchdog can be used to monitor this communication for failure.

The PDI watchdog monitors correct and timely process data communication with the ESC from the
application side.

The settings of the SM- and PDI-watchdog must be done for each slave separately in the TwinCAT System
Manager.

34 Version: 4.2 EL6601, EL6614


Basics communication

Fig. 39: EtherCAT tab -> Advanced Settings -> Behavior -> Watchdog

Notes:
• the multiplier is valid for both watchdogs.
• each watchdog has its own timer setting, the outcome of this in summary with the multiplier is a
resulting time.
• Important: the multiplier/timer setting is only loaded into the slave at the start up, if the checkbox is
activated.
If the checkbox is not activated, nothing is downloaded and the ESC settings remain unchanged.

Multiplier

Multiplier

Both watchdogs receive their pulses from the local terminal cycle, divided by the watchdog multiplier:

1/25 MHz * (watchdog multiplier + 2) = 100 µs (for default setting of 2498 for the multiplier)

The standard setting of 1000 for the SM watchdog corresponds to a release time of 100 ms.

The value in multiplier + 2 corresponds to the number of basic 40 ns ticks representing a watchdog tick.
The multiplier can be modified in order to adjust the watchdog time over a larger range.

EL6601, EL6614 Version: 4.2 35


Basics communication

Example "Set SM watchdog"

This checkbox enables manual setting of the watchdog times. If the outputs are set and the EtherCAT
communication is interrupted, the SM watchdog is triggered after the set time and the outputs are erased.
This setting can be used for adapting a terminal to a slower EtherCAT master or long cycle times. The
default SM watchdog setting is 100 ms. The setting range is 0..65535. Together with a multiplier with a range
of 1..65535 this covers a watchdog period between 0..~170 seconds.

Calculation

Multiplier = 2498 → watchdog base time = 1 / 25 MHz * (2498 + 2) = 0.0001 seconds = 100 µs
SM watchdog = 10000 → 10000 * 100 µs = 1 second watchdog monitoring time

CAUTION
Undefined state possible!
The function for switching off of the SM watchdog via SM watchdog = 0 is only implemented in terminals
from version -0016. In previous versions this operating mode should not be used.

CAUTION
Damage of devices and undefined state possible!
If the SM watchdog is activated and a value of 0 is entered the watchdog switches off completely. This is
the deactivation of the watchdog! Set outputs are NOT set in a safe state, if the communication is inter-
rupted.

3.4 EtherCAT State Machine


The state of the EtherCAT slave is controlled via the EtherCAT State Machine (ESM). Depending upon the
state, different functions are accessible or executable in the EtherCAT slave. Specific commands must be
sent by the EtherCAT master to the device in each state, particularly during the bootup of the slave.

A distinction is made between the following states:


• Init
• Pre-Operational
• Safe-Operational and
• Operational
• Boot

The regular state of each EtherCAT slave after bootup is the OP state.

36 Version: 4.2 EL6601, EL6614


Basics communication

Fig. 40: States of the EtherCAT State Machine

Init

After switch-on the EtherCAT slave in the Init state. No mailbox or process data communication is possible.
The EtherCAT master initializes sync manager channels 0 and 1 for mailbox communication.

Pre-Operational (Pre-Op)

During the transition between Init and Pre-Op the EtherCAT slave checks whether the mailbox was initialized
correctly.

In Pre-Op state mailbox communication is possible, but not process data communication. The EtherCAT
master initializes the sync manager channels for process data (from sync manager channel 2), the FMMU
channels and, if the slave supports configurable mapping, PDO mapping or the sync manager PDO
assignment. In this state the settings for the process data transfer and perhaps terminal-specific parameters
that may differ from the default settings are also transferred.

Safe-Operational (Safe-Op)

During transition between Pre-Op and Safe-Op the EtherCAT slave checks whether the sync manager
channels for process data communication and, if required, the distributed clocks settings are correct. Before
it acknowledges the change of state, the EtherCAT slave copies current input data into the associated DP-
RAM areas of the EtherCAT slave controller (ECSC).

In Safe-Op state mailbox and process data communication is possible, although the slave keeps its outputs
in a safe state, while the input data are updated cyclically.

Outputs in SAFEOP state


The default set watchdog [} 34] monitoring sets the outputs of the module in a safe state - depend-
ing on the settings in SAFEOP and OP - e.g. in OFF state. If this is prevented by deactivation of the
watchdog monitoring in the module, the outputs can be switched or set also in the SAFEOP state.

Operational (Op)

Before the EtherCAT master switches the EtherCAT slave from Safe-Op to Op it must transfer valid output
data.

In the Op state the slave copies the output data of the masters to its outputs. Process data and mailbox
communication is possible.

EL6601, EL6614 Version: 4.2 37


Basics communication

Boot

In the Boot state the slave firmware can be updated. The Boot state can only be reached via the Init state.

In the Boot state mailbox communication via the file access over EtherCAT (FoE) protocol is possible, but no
other mailbox communication and no process data communication.

3.5 CoE Interface


General description

The CoE interface (CANopen over EtherCAT) is used for parameter management of EtherCAT devices.
EtherCAT slaves or the EtherCAT master manage fixed (read only) or variable parameters which they
require for operation, diagnostics or commissioning.

CoE parameters are arranged in a table hierarchy. In principle, the user has read access via the fieldbus.
The EtherCAT master (TwinCAT System Manager) can access the local CoE lists of the slaves via
EtherCAT in read or write mode, depending on the attributes.

Different CoE parameter types are possible, including string (text), integer numbers, Boolean values or larger
byte fields. They can be used to describe a wide range of features. Examples of such parameters include
manufacturer ID, serial number, process data settings, device name, calibration values for analog
measurement or passwords.

The order is specified in 2 levels via hexadecimal numbering: (main)index, followed by subindex. The value
ranges are
• Index: 0x0000 …0xFFFF (0...65535dez)
• SubIndex: 0x00…0xFF (0...255dez)

A parameter localized in this way is normally written as 0x8010:07, with preceding "x" to identify the
hexadecimal numerical range and a colon between index and subindex.

The relevant ranges for EtherCAT fieldbus users are:


• 0x1000: This is where fixed identity information for the device is stored, including name, manufacturer,
serial number etc., plus information about the current and available process data configurations.
• 0x8000: This is where the operational and functional parameters for all channels are stored, such as
filter settings or output frequency.

Other important ranges are:


• 0x4000: In some EtherCAT devices the channel parameters are stored here (as an alternative to the
0x8000 range).
• 0x6000: Input PDOs ("input" from the perspective of the EtherCAT master)
• 0x7000: Output PDOs ("output" from the perspective of the EtherCAT master)

Availability
Not every EtherCAT device must have a CoE list. Simple I/O modules without dedicated processor
usually have no variable parameters and therefore no CoE list.

If a device has a CoE list, it is shown in the TwinCAT System Manager as a separate tab with a listing of the
elements:

38 Version: 4.2 EL6601, EL6614


Basics communication

Fig. 41: "CoE Online " tab

The figure above shows the CoE objects available in device "EL2502", ranging from 0x1000 to 0x1600. The
subindices for 0x1018 are expanded.

Data management and function "NoCoeStorage"

Some parameters, particularly the setting parameters of the slave, are configurable and writeable. This can
be done in write or read mode
• via the System Manager (Fig. "CoE Online " tab) by clicking
This is useful for commissioning of the system/slaves. Click on the row of the index to be
parameterised and enter a value in the "SetValue" dialog.
• from the control system/PLC via ADS, e.g. through blocks from the TcEtherCAT.lib library
This is recommended for modifications while the system is running or if no System Manager or
operating staff are available.

Data management
If slave CoE parameters are modified online, Beckhoff devices store any changes in a fail-safe
manner in the EEPROM, i.e. the modified CoE parameters are still available after a restart.
The situation may be different with other manufacturers.

An EEPROM is subject to a limited lifetime with respect to write operations. From typically 100,000
write operations onwards it can no longer be guaranteed that new (changed) data are reliably saved
or are still readable. This is irrelevant for normal commissioning. However, if CoE parameters are
continuously changed via ADS at machine runtime, it is quite possible for the lifetime limit to be
reached. Support for the NoCoeStorage function, which suppresses the saving of changed CoE val-
ues, depends on the firmware version.
Please refer to the technical data in this documentation as to whether this applies to the respective
device.
• If the function is supported: the function is activated by entering the code word 0x12345678 once
in CoE 0xF008 and remains active as long as the code word is not changed. After switching the
device on it is then inactive. Changed CoE values are not saved in the EEPROM and can thus
be changed any number of times.
• Function is not supported: continuous changing of CoE values is not permissible in view of the
lifetime limit.

EL6601, EL6614 Version: 4.2 39


Basics communication

Startup list
Changes in the local CoE list of the terminal are lost if the terminal is replaced. If a terminal is re-
placed with a new Beckhoff terminal, it will have the default settings. It is therefore advisable to link
all changes in the CoE list of an EtherCAT slave with the Startup list of the slave, which is pro-
cessed whenever the EtherCAT fieldbus is started. In this way a replacement EtherCAT slave can
automatically be parameterized with the specifications of the user.
If EtherCAT slaves are used which are unable to store local CoE values permanently, the Startup
list must be used.

Recommended approach for manual modification of CoE parameters


• Make the required change in the System Manager
The values are stored locally in the EtherCAT slave
• If the value is to be stored permanently, enter it in the Startup list.
The order of the Startup entries is usually irrelevant.

Fig. 42: Startup list in the TwinCAT System Manager

The Startup list may already contain values that were configured by the System Manager based on the ESI
specifications. Additional application-specific entries can be created.

Online/offline list

While working with the TwinCAT System Manager, a distinction has to be made whether the EtherCAT
device is "available", i.e. switched on and linked via EtherCAT and therefore online, or whether a
configuration is created offline without connected slaves.

In both cases a CoE list as shown in Fig. “’CoE online’ tab” is displayed. The connectivity is shown as offline/
online.
• If the slave is offline
◦ The offline list from the ESI file is displayed. In this case modifications are not meaningful or
possible.
◦ The configured status is shown under Identity.
◦ No firmware or hardware version is displayed, since these are features of the physical device.
◦ Offline is shown in red.

40 Version: 4.2 EL6601, EL6614


Basics communication

Fig. 43: Offline list

• If the slave is online


◦ The actual current slave list is read. This may take several seconds, depending on the size and
cycle time.
◦ The actual identity is displayed
◦ The firmware and hardware version of the equipment according to the electronic information is
displayed
◦ Online is shown in green.

Fig. 44: Online list

EL6601, EL6614 Version: 4.2 41


Basics communication

Channel-based order

The CoE list is available in EtherCAT devices that usually feature several functionally equivalent channels.
For example, a 4-channel analog 0..10 V input terminal also has 4 logical channels and therefore 4 identical
sets of parameter data for the channels. In order to avoid having to list each channel in the documentation,
the placeholder "n" tends to be used for the individual channel numbers.

In the CoE system 16 indices, each with 255 subindices, are generally sufficient for representing all channel
parameters. The channel-based order is therefore arranged in 16dec/10hex steps. The parameter range
0x8000 exemplifies this:
• Channel 0: parameter range 0x8000:00 ... 0x800F:255
• Channel 1: parameter range 0x8010:00 ... 0x801F:255
• Channel 2: parameter range 0x8020:00 ... 0x802F:255
• ...

This is generally written as 0x80n0.

Detailed information on the CoE interface can be found in the EtherCAT system documentation on the
Beckhoff website.

42 Version: 4.2 EL6601, EL6614


Basics communication

3.6 Distributed Clock


The distributed clock represents a local clock in the EtherCAT slave controller (ESC) with the following
characteristics:
• Unit 1 ns
• Zero point 1.1.2000 00:00
• Size 64 bit (sufficient for the next 584 years; however, some EtherCAT slaves only offer 32-bit support,
i.e. the variable overflows after approx. 4.2 seconds)
• The EtherCAT master automatically synchronizes the local clock with the master clock in the EtherCAT
bus with a precision of < 100 ns.

For detailed information please refer to the EtherCAT system description.

EL6601, EL6614 Version: 4.2 43


Mounting and wiring

4 Mounting and wiring

4.1 Recommended mounting rails


Terminal Modules und EtherCAT Modules of KMxxxx and EMxxxx series, same as the terminals of the
EL66xx and EL67xx series can be snapped onto the following recommended mounting rails:
• DIN Rail TH 35-7.5 with 1 mm material thickness (according to EN 60715)
• DIN Rail TH 35-15 with 1,5 mm material thickness

Pay attention to the material thickness of the DIN Rail


Terminal Modules und EtherCAT Modules of KMxxxx and EMxxxx series, same as the terminals of
the EL66xx and EL67xx series does not fit to the DIN Rail TH 35-15 with 2,2 to 2,5 mm material
thickness (according to EN 60715)!

4.2 Mounting and demounting - terminals with front


unlocking
The terminal modules are fastened to the assembly surface with the aid of a 35 mm mounting rail (e.g.
mounting rail TH 35-15).

Fixing of mounting rails


The locking mechanism of the terminals and couplers extends to the profile of the mounting rail. At
the installation, the locking mechanism of the components must not come into conflict with the fixing
bolts of the mounting rail. To mount the recommended mounting rails under the terminals and cou-
plers, you should use flat mounting connections (e.g. countersunk screws or blind rivets).

WARNING
Risk of electric shock and damage of device!
Bring the bus terminal system into a safe, powered down state before starting installation, disassembly or
wiring of the Bus Terminals!

Mounting
• Fit the mounting rail to the planned assembly location.

and press (1) the terminal module against the mounting rail until it latches in place on the mounting
rail (2).

44 Version: 4.2 EL6601, EL6614


Mounting and wiring

• Attach the cables.

Demounting
• Remove all the cables.
• Lever the unlatching hook back with thumb and forefinger (3). An internal mechanism pulls the two
latching lugs (3a) from the top hat rail back into the terminal module.

• Pull (4) the terminal module away from the mounting surface.
Avoid canting of the module; you should stabilize the module with the other hand, if required.

4.3 Positioning of passive Terminals


Hint for positioning of passive terminals in the bus terminal block
EtherCAT Terminals (ELxxxx / ESxxxx), which do not take an active part in data transfer within the
bus terminal block are so called passive terminals. The passive terminals have no current consump-
tion out of the E-Bus.
To ensure an optimal data transfer, you must not directly string together more than 2 passive termi-
nals!

EL6601, EL6614 Version: 4.2 45


Mounting and wiring

Examples for positioning of passive terminals (highlighted)

Fig. 45: Correct positioning

Fig. 46: Incorrect positioning

4.4 Installation positions


NOTE
Constraints regarding installation position and operating temperature range
Please refer to the technical data for a terminal to ascertain whether any restrictions regarding the installa-
tion position and/or the operating temperature range have been specified. When installing high power dissi-
pation terminals ensure that an adequate spacing is maintained between other components above and be-
low the terminal in order to guarantee adequate ventilation!

Optimum installation position (standard)

The optimum installation position requires the mounting rail to be installed horizontally and the connection
surfaces of the EL/KL terminals to face forward (see Fig. “Recommended distances for standard installation
position”). The terminals are ventilated from below, which enables optimum cooling of the electronics through
convection. "From below" is relative to the acceleration of gravity.

46 Version: 4.2 EL6601, EL6614


Mounting and wiring

Fig. 47: Recommended distances for standard installation position

Compliance with the distances shown in Fig. “Recommended distances for standard installation position” is
recommended.

Other installation positions

All other installation positions are characterized by different spatial arrangement of the mounting rail - see
Fig “Other installation positions”.

The minimum distances to ambient specified above also apply to these installation positions.

EL6601, EL6614 Version: 4.2 47


Mounting and wiring

Fig. 48: Other installation positions

4.5 ATEX - Special conditions (extended temperature


range)
WARNING
Observe the special conditions for the intended use of Beckhoff fieldbus components with
extended temperature range (ET) in potentially explosive areas (directive 94/9/EU)!
• The certified components are to be installed in a suitable housing that guarantees a protection class of at
least IP54 in accordance with EN 60529! The environmental conditions during use are thereby to be
taken into account!
• If the temperatures during rated operation are higher than 70°C at the feed-in points of cables, lines or
pipes, or higher than 80°C at the wire branching points, then cables must be selected whose tempera-
ture data correspond to the actual measured temperature values!
• Observe the permissible ambient temperature range of -25 to 60°C for the use of Beckhoff fieldbus com-
ponents with extended temperature range (ET) in potentially explosive areas!
• Measures must be taken to protect against the rated operating voltage being exceeded by more than
40% due to short-term interference voltages!
• The individual terminals may only be unplugged or removed from the Bus Terminal system if the supply
voltage has been switched off or if a non-explosive atmosphere is ensured!
• The connections of the certified components may only be connected or disconnected if the supply volt-
age has been switched off or if a non-explosive atmosphere is ensured!
• The fuses of the KL92xx/EL92xx power feed terminals may only be exchanged if the supply voltage has
been switched off or if a non-explosive atmosphere is ensured!
• Address selectors and ID switches may only be adjusted if the supply voltage has been switched off or if
a non-explosive atmosphere is ensured!

Standards

The fundamental health and safety requirements are fulfilled by compliance with the following standards:
• EN 60079-0:2012+A11:2013
• EN 60079-15:2010

Marking

The Beckhoff fieldbus components with extended temperature range (ET) certified for potentially explosive
areas bear the following marking:

48 Version: 4.2 EL6601, EL6614


Mounting and wiring

II 3G KEMA 10ATEX0075 X Ex nA IIC T4 Gc Ta: -25 … 60°C

or

II 3G KEMA 10ATEX0075 X Ex nC IIC T4 Gc Ta: -25 … 60°C

4.6 ATEX Documentation


Notes about operation of the Beckhoff terminal systems in potentially explosive ar-
eas (ATEX)
Pay also attention to the continuative documentation

Notes about operation of the Beckhoff terminal systems in potentially explosive areas (ATEX)

that is available in the download area of the Beckhoff homepage http:\\www.beckhoff.com!

EL6601, EL6614 Version: 4.2 49


Commissioning

5 Commissioning

5.1 TwinCAT Development Environment


The Software for automation TwinCAT (The Windows Control and Automation Technology) will be
distinguished into:
• TwinCAT 2: System Manager (Configuration) & PLC Control (Programming)
• TwinCAT 3: Enhancement of TwinCAT 2 (Programming and Configuration takes place via a common
Development Environment)

Details:
• TwinCAT 2:
◦ Connects I/O devices to tasks in a variable-oriented manner
◦ Connects tasks to tasks in a variable-oriented manner
◦ Supports units at the bit level
◦ Supports synchronous or asynchronous relationships
◦ Exchange of consistent data areas and process images
◦ Datalink on NT - Programs by open Microsoft Standards (OLE, OCX, ActiveX, DCOM+, etc.)
◦ Integration of IEC 61131-3-Software-SPS, Software- NC and Software-CNC within Windows
NT/2000/XP/Vista, Windows 7, NT/XP Embedded, CE
◦ Interconnection to all common fieldbusses
◦ More…

Additional features:
• TwinCAT 3 (eXtended Automation):
◦ Visual-Studio®-Integration
◦ Choice of the programming language
◦ Supports object orientated extension of IEC 61131-3
◦ Usage of C/C++ as programming language for real time applications
◦ Connection to MATLAB®/Simulink®
◦ Open interface for expandability
◦ Flexible run-time environment
◦ Active support of Multi-Core- und 64-Bit-Operatingsystem
◦ Automatic code generation and project creation with the TwinCAT Automation Interface
◦ More…

Within the following sections commissioning of the TwinCAT Development Environment on a PC System for
the control and also the basically functions of unique control elements will be explained.

Please see further information to TwinCAT 2 and TwinCAT 3 at http://infosys.beckhoff.com.

5.1.1 Installation of the TwinCAT real-time driver


In order to assign real-time capability to a standard Ethernet port of an IPC controller, the Beckhoff real-time
driver has to be installed on this port under Windows.

This can be done in several ways. One option is described here.

In the System Manager call up the TwinCAT overview of the local network interfaces via Options → Show
Real Time Ethernet Compatible Devices.

50 Version: 4.2 EL6601, EL6614


Commissioning

Fig. 49: System Manager “Options” (TwinCAT 2)

This have to be called up by the Menü “TwinCAT” within the TwinCAT 3 environment:

Fig. 50: Call up under VS Shell (TwinCAT 3)

The following dialog appears:

Fig. 51: Overview of network interfaces

Interfaces listed under “Compatible devices” can be assigned a driver via the “Install” button. A driver should
only be installed on compatible devices.

A Windows warning regarding the unsigned driver can be ignored.

Alternatively an EtherCAT-device can be inserted first of all as described in chapter Offline configuration
creation, section “Creating the EtherCAT device” [} 60] in order to view the compatible ethernet ports via its
EtherCAT properties (tab „Adapter“, button „Compatible Devices…“):

EL6601, EL6614 Version: 4.2 51


Commissioning

Fig. 52: EtherCAT device properties(TwinCAT 2): click on „Compatible Devices…“ of tab “Adapter”

TwinCAT 3: the properties of the EtherCAT device can be opened by double click on “Device .. (EtherCAT)”
within the Solution Explorer under “I/O”:

After the installation the driver appears activated in the Windows overview for the network interface
(Windows Start → System Properties → Network)

Fig. 53: Windows properties of the network interface

A correct setting of the driver could be:

52 Version: 4.2 EL6601, EL6614


Commissioning

Fig. 54: Exemplary correct driver setting for the Ethernet port

Other possible settings have to be avoided:

EL6601, EL6614 Version: 4.2 53


Commissioning

Fig. 55: Incorrect driver settings for the Ethernet port

54 Version: 4.2 EL6601, EL6614


Commissioning

IP address of the port used

IP address/DHCP
In most cases an Ethernet port that is configured as an EtherCAT device will not transport general
IP packets. For this reason and in cases where an EL6601 or similar devices are used it is useful to
specify a fixed IP address for this port via the “Internet Protocol TCP/IP” driver setting and to disable
DHCP. In this way the delay associated with the DHCP client for the Ethernet port assigning itself a
default IP address in the absence of a DHCP server is avoided. A suitable address space is
192.168.x.x, for example.

Fig. 56: TCP/IP setting for the Ethernet port

EL6601, EL6614 Version: 4.2 55


Commissioning

5.1.2 Notes regarding ESI device description

Installation of the latest ESI device description

The TwinCAT EtherCAT master/System Manager needs the device description files for the devices to be
used in order to generate the configuration in online or offline mode. The device descriptions are contained
in the so-called ESI files (EtherCAT Slave Information) in XML format. These files can be requested from the
respective manufacturer and are made available for download. An *.xml file may contain several device
descriptions.

The ESI files for Beckhoff EtherCAT devices are available on the Beckhoff website.

The ESI files should be stored in the TwinCAT installation directory.

Default settings:
• TwinCAT 2: C:\TwinCAT\IO\EtherCAT
• TwinCAT 3: C:\TwinCAT\3.1\Config\Io\EtherCAT

The files are read (once) when a new System Manager window is opened, if they have changed since the
last time the System Manager window was opened.

A TwinCAT installation includes the set of Beckhoff ESI files that was current at the time when the TwinCAT
build was created.

For TwinCAT 2.11/TwinCAT 3 and higher, the ESI directory can be updated from the System Manager, if the
programming PC is connected to the Internet; by
• TwinCAT 2: Option → “Update EtherCAT Device Descriptions”
• TwinCAT 3: TwinCAT → EtherCAT Devices → “Update Device Descriptions (via ETG Website)…”

The TwinCAT ESI Updater is available for this purpose.

ESI
The *.xml files are associated with *.xsd files, which describe the structure of the ESI XML files. To
update the ESI device descriptions, both file types should therefore be updated.

Device differentiation

EtherCAT devices/slaves are distinguished by four properties, which determine the full device identifier. For
example, the device identifier EL2521-0025-1018 consists of:
• family key “EL”
• name “2521”
• type “0025”
• and revision “1018”

Fig. 57: Identifier structure

The order identifier consisting of name + type (here: EL2521-0010) describes the device function. The
revision indicates the technical progress and is managed by Beckhoff. In principle, a device with a higher
revision can replace a device with a lower revision, unless specified otherwise, e.g. in the documentation.
Each revision has its own ESI description. See further notes [} 8].

56 Version: 4.2 EL6601, EL6614


Commissioning

Online description

If the EtherCAT configuration is created online through scanning of real devices (see section Online setup)
and no ESI descriptions are available for a slave (specified by name and revision) that was found, the
System Manager asks whether the description stored in the device should be used. In any case, the System
Manager needs this information for setting up the cyclic and acyclic communication with the slave correctly.

Fig. 58: OnlineDescription information window (TwinCAT 2)

In TwinCAT 3 a similar window appears, which also offers the Web update:

Fig. 59: Information window OnlineDescription (TwinCAT 3)

If possible, the Yes is to be rejected and the required ESI is to be requested from the device manufacturer.
After installation of the XML/XSD file the configuration process should be repeated.

NOTE
Changing the ‘usual’ configuration through a scan
ü If a scan discovers a device that is not yet known to TwinCAT, distinction has to be made between two
cases. Taking the example here of the EL2521-0000 in the revision 1019
a) no ESI is present for the EL2521-0000 device at all, either for the revision 1019 or for an older revision.
The ESI must then be requested from the manufacturer (in this case Beckhoff).
b) an ESI is present for the EL2521-0000 device, but only in an older revision, e.g. 1018 or 1017.
In this case an in-house check should first be performed to determine whether the spare parts stock al-
lows the integration of the increased revision into the configuration at all. A new/higher revision usually
also brings along new features. If these are not to be used, work can continue without reservations with
the previous revision 1018 in the configuration. This is also stated by the Beckhoff compatibility rule.

Refer in particular to the chapter ‘General notes on the use of Beckhoff EtherCAT IO components’ and for
manual configuration to the chapter ‘Offline configuration creation’ [} 60].

If the OnlineDescription is used regardless, the System Manager reads a copy of the device description from
the EEPROM in the EtherCAT slave. In complex slaves the size of the EEPROM may not be sufficient for the
complete ESI, in which case the ESI would be incomplete in the configurator. Therefore it’s recommended
using an offline ESI file with priority in such a case.

The System Manager creates for online recorded device descriptions a new file
“OnlineDescription0000...xml” in its ESI directory, which contains all ESI descriptions that were read online.

EL6601, EL6614 Version: 4.2 57


Commissioning

Fig. 60: File OnlineDescription.xml created by the System Manager

Is a slave desired to be added manually to the configuration at a later stage, online created slaves are
indicated by a prepended symbol “>” in the selection list (see Figure “Indication of an online recorded ESI of
EL2521 as an example”).

Fig. 61: Indication of an online recorded ESI of EL2521 as an example

If such ESI files are used and the manufacturer's files become available later, the file OnlineDescription.xml
should be deleted as follows:
• close all System Manager windows
• restart TwinCAT in Config mode
• delete "OnlineDescription0000...xml"
• restart TwinCAT System Manager

This file should not be visible after this procedure, if necessary press <F5> to update

OnlineDescription for TwinCAT 3.x


In addition to the file described above "OnlineDescription0000...xml" , a so called EtherCAT cache
with new discovered devices is created by TwinCAT 3.x, e.g. under Windows 7:

(Please note the language settings of the OS!)


You have to delete this file, too.

Faulty ESI file

If an ESI file is faulty and the System Manager is unable to read it, the System Manager brings up an
information window.

Fig. 62: Information window for faulty ESI file (left: TwinCAT 2; right: TwinCAT 3)

58 Version: 4.2 EL6601, EL6614


Commissioning

Reasons may include:


• Structure of the *.xml does not correspond to the associated *.xsd file → check your schematics
• Contents cannot be translated into a device description → contact the file manufacturer

EL6601, EL6614 Version: 4.2 59


Commissioning

5.1.3 OFFLINE configuration creation

Creating the EtherCAT device

Create an EtherCAT device in an empty System Manager window.

Fig. 63: Append EtherCAT device (left: TwinCAT 2; right: TwinCAT 3)

Select type ‘EtherCAT’ for an EtherCAT I/O application with EtherCAT slaves. For the present publisher/
subscriber service in combination with an EL6601/EL6614 terminal select “EtherCAT Automation Protocol
via EL6601”.

Fig. 64: Selecting the EtherCAT connection (TwinCAT 2.11, TwinCAT 3)

Then assign a real Ethernet port to this virtual device in the runtime system.

Fig. 65: Selecting the Ethernet port

This query may appear automatically when the EtherCAT device is created, or the assignment can be set/
modified later in the properties dialog; see Fig. “EtherCAT device properties (TwinCAT 2)”.

60 Version: 4.2 EL6601, EL6614


Commissioning

Fig. 66: EtherCAT device properties (TwinCAT 2)

TwinCAT 3: the properties of the EtherCAT device can be opened by double click on “Device .. (EtherCAT)”
within the Solution Explorer under “I/O”:

Selecting the Ethernet port


Ethernet ports can only be selected for EtherCAT devices for which the TwinCAT real-time driver is
installed. This has to be done separately for each port. Please refer to the respective installation
page [} 50].

Defining EtherCAT slaves

Further devices can be appended by right-clicking on a device in the configuration tree.

Fig. 67: Appending EtherCAT devices (left: TwinCAT 2; right: TwinCAT 3)

The dialog for selecting a new device opens. Only devices for which ESI files are available are displayed.

Only devices are offered for selection that can be appended to the previously selected device. Therefore the
physical layer available for this port is also displayed (Fig. “Selection dialog for new EtherCAT device”, A). In
the case of cable-based Fast-Ethernet physical layer with PHY transfer, then also only cable-based devices
are available, as shown in Fig. “Selection dialog for new EtherCAT device”. If the preceding device has
several free ports (e.g. EK1122 or EK1100), the required port can be selected on the right-hand side (A).

Overview of physical layer


• “Ethernet”: cable-based 100BASE-TX: EK couplers, EP boxes, devices with RJ45/M8/M12 connector
• “E-Bus”: LVDS “terminal bus”, “EJ-module”: EL/ES terminals, various modular modules

EL6601, EL6614 Version: 4.2 61


Commissioning

The search field facilitates finding specific devices (since TwinCAT 2.11 or TwinCAT 3).

Fig. 68: Selection dialog for new EtherCAT device

By default only the name/device type is used as selection criterion. For selecting a specific revision of the
device the revision can be displayed as “Extended Information”.

Fig. 69: Display of device revision

In many cases several device revisions were created for historic or functional reasons, e.g. through
technological advancement. For simplification purposes (see Fig. “Selection dialog for new EtherCAT
device”) only the last (i.e. highest) revision and therefore the latest state of production is displayed in the
selection dialog for Beckhoff devices. To show all device revisions available in the system as ESI
descriptions tick the “Show Hidden Devices” check box, see Fig. “Display of previous revisions”.

62 Version: 4.2 EL6601, EL6614


Commissioning

Fig. 70: Display of previous revisions

Device selection based on revision, compatibility


The ESI description also defines the process image, the communication type between master and
slave/device and the device functions, if applicable. The physical device (firmware, if available) has
to support the communication queries/settings of the master. This is backward compatible, i.e.
newer devices (higher revision) should be supported if the EtherCAT master addresses them as an
older revision. The following compatibility rule of thumb is to be assumed for Beckhoff EtherCAT
Terminals/ Boxes/ EJ-modules:
device revision in the system >= device revision in the configuration
This also enables subsequent replacement of devices without changing the configuration (different
specifications are possible for drives).

Example:

If an EL2521-0025-1018 is specified in the configuration, an EL2521-0025-1018 or higher (-1019, -1020) can


be used in practice.

Fig. 71: Name/revision of the terminal

If current ESI descriptions are available in the TwinCAT system, the last revision offered in the selection
dialog matches the Beckhoff state of production. It is recommended to use the last device revision when
creating a new configuration, if current Beckhoff devices are used in the real application. Older revisions
should only be used if older devices from stock are to be used in the application.

In this case the process image of the device is shown in the configuration tree and can be parameterised as
follows: linking with the task, CoE/DC settings, plug-in definition, startup settings, ...

EL6601, EL6614 Version: 4.2 63


Commissioning

Fig. 72: EtherCAT terminal in the TwinCAT tree (left: TwinCAT 2; right: TwinCAT 3)

64 Version: 4.2 EL6601, EL6614


Commissioning

5.1.4 ONLINE configuration creation

Detecting/scanning of the EtherCAT device

The online device search can be used if the TwinCAT system is in CONFIG mode. This can be indicated by
a symbol right below in the information bar:

• on TwinCAT 2 by a blue display “Config Mode” within the System Manager window: .

• on TwinCAT 3 within the user interface of the development environment by a symbol .

TwinCAT can be set into this mode:

• TwinCAT 2: by selection of in the Menubar or by “Actions” → “Set/Reset TwinCAT to Config


Mode…”

• TwinCAT 3: by selection of in the Menubar or by „TwinCAT“ → “Restart TwinCAT (Config Mode)“

Online scanning in Config mode


The online search is not available in RUN mode (production operation). Note the differentiation be-
tween TwinCAT programming system and TwinCAT target system.

The TwinCAT 2 icon ( ) or TwinCAT 3 icon ( ) within the Windows-Taskbar always shows the
TwinCAT mode of the local IPC. Compared to that, the System Manager window of TwinCAT 2 or the user
interface of TwinCAT 3 indicates the state of the target system.

Fig. 73: Differentiation local/target system (left: TwinCAT 2; right: TwinCAT 3)

Right-clicking on “I/O Devices” in the configuration tree opens the search dialog.

Fig. 74: Scan Devices (left: TwinCAT 2; right: TwinCAT 3)

This scan mode attempts to find not only EtherCAT devices (or Ethernet ports that are usable as such), but
also NOVRAM, fieldbus cards, SMB etc. However, not all devices can be found automatically.

Fig. 75: Note for automatic device scan (left: TwinCAT 2; right: TwinCAT 3)

EL6601, EL6614 Version: 4.2 65


Commissioning

Ethernet ports with installed TwinCAT real-time driver are shown as “RT Ethernet” devices. An EtherCAT
frame is sent to these ports for testing purposes. If the scan agent detects from the response that an
EtherCAT slave is connected, the port is immediately shown as an “EtherCAT Device” .

Fig. 76: Detected Ethernet devices

Via respective checkboxes devices can be selected (as illustrated in Fig. “Detected Ethernet devices” e.g.
Device 3 and Device 4 were chosen). After confirmation with “OK” a device scan is suggested for all selected
devices, see Fig.: “Scan query after automatic creation of an EtherCAT device”.

Selecting the Ethernet port


Ethernet ports can only be selected for EtherCAT devices for which the TwinCAT real-time driver is
installed. This has to be done separately for each port. Please refer to the respective installation
page [} 50].

Detecting/Scanning the EtherCAT devices

Online scan functionality


During a scan the master queries the identity information of the EtherCAT slaves from the slave
EEPROM. The name and revision are used for determining the type. The respective devices are lo-
cated in the stored ESI data and integrated in the configuration tree in the default state defined
there.

Fig. 77: Example default state

NOTE
Slave scanning in practice in series machine production
The scanning function should be used with care. It is a practical and fast tool for creating an initial configu-
ration as a basis for commissioning. In series machine production or reproduction of the plant, however, the
function should no longer be used for the creation of the configuration, but if necessary for comparison
[} 70] with the defined initial configuration.Background: since Beckhoff occasionally increases the revision
version of the delivered products for product maintenance reasons, a configuration can be created by such
a scan which (with an identical machine construction) is identical according to the device list; however, the
respective device revision may differ from the initial configuration.

Example:

Company A builds the prototype of a machine B, which is to be produced in series later on. To do this the
prototype is built, a scan of the IO devices is performed in TwinCAT and the initial configuration ‘B.tsm’ is
created. The EL2521-0025 EtherCAT terminal with the revision 1018 is located somewhere. It is thus built
into the TwinCAT configuration in this way:

66 Version: 4.2 EL6601, EL6614


Commissioning

Fig. 78: Installing EthetCAT terminal with revision -1018

Likewise, during the prototype test phase, the functions and properties of this terminal are tested by the
programmers/commissioning engineers and used if necessary, i.e. addressed from the PLC ‘B.pro’ or the
NC. (the same applies correspondingly to the TwinCAT 3 solution files).

The prototype development is now completed and series production of machine B starts, for which Beckhoff
continues to supply the EL2521-0025-0018. If the commissioning engineers of the series machine production
department always carry out a scan, a B configuration with the identical contents results again for each
machine. Likewise, A might create spare parts stores worldwide for the coming series-produced machines
with EL2521-0025-1018 terminals.

After some time Beckhoff extends the EL2521-0025 by a new feature C. Therefore the FW is changed,
outwardly recognizable by a higher FW version and a new revision -1019. Nevertheless the new device
naturally supports functions and interfaces of the predecessor version(s); an adaptation of ‘B.tsm’ or even
‘B.pro’ is therefore unnecessary. The series-produced machines can continue to be built with ‘B.tsm’ and
‘B.pro’; it makes sense to perform a comparative scan [} 70] against the initial configuration ‘B.tsm’ in order
to check the built machine.

However, if the series machine production department now doesn’t use ‘B.tsm’, but instead carries out a
scan to create the productive configuration, the revision -1019 is automatically detected and built into the
configuration:

Fig. 79: Detection of EtherCAT terminal with revision -1019

This is usually not noticed by the commissioning engineers. TwinCAT cannot signal anything either, since
virtually a new configuration is created. According to the compatibility rule, however, this means that no
EL2521-0025-1018 should be built into this machine as a spare part (even if this nevertheless works in the
vast majority of cases).

In addition, it could be the case that, due to the development accompanying production in company A, the
new feature C of the EL2521-0025-1019 (for example, an improved analog filter or an additional process
data for the diagnosis) is discovered and used without in-house consultation. The previous stock of spare
part devices are then no longer to be used for the new configuration ‘B2.tsm’ created in this way.Þ if series
machine production is established, the scan should only be performed for informative purposes for
comparison with a defined initial configuration. Changes are to be made with care!

If an EtherCAT device was created in the configuration (manually or through a scan), the I/O field can be
scanned for devices/slaves.

Fig. 80: Scan query after automatic creation of an EtherCAT device (left: TwinCAT 2; right: TwinCAT 3)

EL6601, EL6614 Version: 4.2 67


Commissioning

Fig. 81: Manual triggering of a device scan on a specified EtherCAT device (left: TwinCAT 2; right:
TwinCAT 3)

In the System Manager (TwinCAT 2) or the User Interface (TwinCAT 3) the scan process can be monitored
via the progress bar at the bottom in the status bar.

Fig. 82: Scan progressexemplary by TwinCAT 2

The configuration is established and can then be switched to online state (OPERATIONAL).

Fig. 83: Config/FreeRun query (left: TwinCAT 2; right: TwinCAT 3)

In Config/FreeRun mode the System Manager display alternates between blue and red, and the EtherCAT
device continues to operate with the idling cycle time of 4 ms (default setting), even without active task (NC,
PLC).

Fig. 84: Displaying of “Free Run” and “Config Mode” toggling right below in the status bar

Fig. 85: TwinCAT can also be switched to this state by using a button (left: TwinCAT 2; right: TwinCAT 3)

The EtherCAT system should then be in a functional cyclic state, as shown in Fig. “Online display example”.

68 Version: 4.2 EL6601, EL6614


Commissioning

Fig. 86: Online display example

Please note:
• all slaves should be in OP state
• the EtherCAT master should be in “Actual State” OP
• “frames/sec” should match the cycle time taking into account the sent number of frames
• no excessive “LostFrames” or CRC errors should occur

The configuration is now complete. It can be modified as described under manual procedure [} 60].

Troubleshooting

Various effects may occur during scanning.


• An unknown device is detected, i.e. an EtherCAT slave for which no ESI XML description is available.
In this case the System Manager offers to read any ESI that may be stored in the device. This case is
described in the chapter "Notes regarding ESI device description".
• Device are not detected properly
Possible reasons include:
- faulty data links, resulting in data loss during the scan
- slave has invalid device description
The connections and devices should be checked in a targeted manner, e.g. via the emergency scan.
Then re-run the scan.

Fig. 87: Faulty identification

In the System Manager such devices may be set up as EK0000 or unknown devices. Operation is not
possible or meaningful.

EL6601, EL6614 Version: 4.2 69


Commissioning

Scan over existing Configuration

NOTE
Change of the configuration after comparison
With this scan (TwinCAT 2.11 or 3.1) only the device properties vendor (manufacturer), device name and
revision are compared at present! A ‘ChangeTo’ or ‘Copy’ should only be carried out with care, taking into
consideration the Beckhoff IO compatibility rule (see above). The device configuration is then replaced by
the revision found; this can affect the supported process data and functions.

If a scan is initiated for an existing configuration, the actual I/O environment may match the configuration
exactly or it may differ. This enables the configuration to be compared.

Fig. 88: Identical configuration (left: TwinCAT 2; right: TwinCAT 3)

If differences are detected, they are shown in the correction dialog, so that the user can modify the
configuration as required.

Fig. 89: Correction dialog

It is advisable to tick the “Extended Information” check box to reveal differences in the revision.

70 Version: 4.2 EL6601, EL6614


Commissioning

Colour Explanation
green This EtherCAT slave matches the entry on the other side. Both type and revision match.
blue This EtherCAT slave is present on the other side, but in a different revision. This other
revision can have other default values for the process data as well as other/additional
functions.
If the found revision is higher than the configured revision, the slave may be used provided
compatibility issues are taken into account.
If the found revision is lower than the configured revision, it is likely that the slave cannot be
used. The found device may not support all functions that the master expects based on the
higher revision number.
light blue This EtherCAT slave is ignored (“Ignore” button)
red • This EtherCAT slave is not present on the other side.
• It is present, but in a different revision, which also differs in its properties from the one
specified.
The compatibility principle then also applies here: if the found revision is higher than the
configured revision, use is possible provided compatibility issues are taken into account,
since the successor devices should support the functions of the predecessor devices.
If the found revision is lower than the configured revision, it is likely that the slave cannot
be used. The found device may not support all functions that the master expects based on
the higher revision number.

Device selection based on revision, compatibility


The ESI description also defines the process image, the communication type between master and
slave/device and the device functions, if applicable. The physical device (firmware, if available) has
to support the communication queries/settings of the master. This is backward compatible, i.e.
newer devices (higher revision) should be supported if the EtherCAT master addresses them as an
older revision. The following compatibility rule of thumb is to be assumed for Beckhoff EtherCAT
Terminals/ Boxes/ EJ-modules:
device revision in the system >= device revision in the configuration
This also enables subsequent replacement of devices without changing the configuration (different
specifications are possible for drives).

Example:

If an EL2521-0025-1018 is specified in the configuration, an EL2521-0025-1018 or higher (-1019, -1020) can


be used in practice.

Fig. 90: Name/revision of the terminal

If current ESI descriptions are available in the TwinCAT system, the last revision offered in the selection
dialog matches the Beckhoff state of production. It is recommended to use the last device revision when
creating a new configuration, if current Beckhoff devices are used in the real application. Older revisions
should only be used if older devices from stock are to be used in the application.

In this case the process image of the device is shown in the configuration tree and can be parameterised as
follows: linking with the task, CoE/DC settings, plug-in definition, startup settings, ...

EL6601, EL6614 Version: 4.2 71


Commissioning

Fig. 91: Correction dialog with modifications

Once all modifications have been saved or accepted, click “OK” to transfer them to the real *.tsm
configuration.

Change to Compatible Type

TwinCAT offers a function “Change to Compatible Type…” for the exchange of a device whilst retaining the
links in the task.

Fig. 92: Dialog “Change to Compatible Type…” (left: TwinCAT 2; right: TwinCAT 3)

This function is preferably to be used on AX5000 devices.

Change to Alternative Type

The TwinCAT System Manager offers a function for the exchange of a device: Change to Alternative Type

Fig. 93: TwinCAT 2 Dialog Change to Alternative Type

72 Version: 4.2 EL6601, EL6614


Commissioning

If called, the System Manager searches in the procured device ESI (in this example: EL1202-0000) for
details of compatible devices contained there. The configuration is changed and the ESI-EEPROM is
overwritten at the same time – therefore this process is possible only in the online state (ConfigMode).

5.1.5 EtherCAT subscriber configuration


In the left-hand window of the TwinCAT 2 System Manager or the Solution Explorer of the TwinCAT 3
Development Environment respectively, click on the element of the terminal within the tree you wish to
configure (in the example: EL3751 Terminal 3).

Fig. 94: Branch element as terminal EL3751

In the right-hand window of the TwinCAT System manager (TwinCAT 2) or the Development Environment
(TwinCAT 3), various tabs are now available for configuring the terminal. And yet the dimension of
complexity of a subscriber determines which tabs are provided. Thus as illustrated in the example above the
terminal EL3751 provides many setup options and also a respective number of tabs are available. On the
contrary by the terminal EL1004 for example the tabs "General", "EtherCAT", "Process Data" and “Online“
are available only. Several terminals, as for instance the EL6695 provide special functions by a tab with its
own terminal name, so “EL6695” in this case. A specific tab “Settings” by terminals with a wide range of
setup options will be provided also (e.g. EL3751).

„General“ tab

Fig. 95: “General” tab

Name Name of the EtherCAT device


Id Number of the EtherCAT device
Type EtherCAT device type
Comment Here you can add a comment (e.g. regarding the
system).
Disabled Here you can deactivate the EtherCAT device.
Create symbols Access to this EtherCAT slave via ADS is only
available if this control box is activated.

EL6601, EL6614 Version: 4.2 73


Commissioning

„EtherCAT“ tab

Fig. 96: „EtherCAT“ tab

Type EtherCAT device type


Product/Revision Product and revision number of the EtherCAT device
Auto Inc Addr. Auto increment address of the EtherCAT device. The
auto increment address can be used for addressing
each EtherCAT device in the communication ring
through its physical position. Auto increment
addressing is used during the start-up phase when
the EtherCAT master allocates addresses to the
EtherCAT devices. With auto increment addressing
the first EtherCAT slave in the ring has the address
0000hex. For each further slave the address is
decremented by 1 (FFFFhex, FFFEhex etc.).
EtherCAT Addr. Fixed address of an EtherCAT slave. This address is
allocated by the EtherCAT master during the start-up
phase. Tick the control box to the left of the input field
in order to modify the default value.
Previous Port Name and port of the EtherCAT device to which this
device is connected. If it is possible to connect this
device with another one without changing the order of
the EtherCAT devices in the communication ring,
then this combination field is activated and the
EtherCAT device to which this device is to be
connected can be selected.
Advanced Settings This button opens the dialogs for advanced settings.

The link at the bottom of the tab points to the product page for this EtherCAT device on the web.

“Process Data” tab

Indicates the configuration of the process data. The input and output data of the EtherCAT slave are
represented as CANopen process data objects (Process Data Objects, PDOs). The user can select a PDO
via PDO assignment and modify the content of the individual PDO via this dialog, if the EtherCAT slave
supports this function.

74 Version: 4.2 EL6601, EL6614


Commissioning

Fig. 97: “Process Data” tab

The process data (PDOs) transferred by an EtherCAT slave during each cycle are user data which the
application expects to be updated cyclically or which are sent to the slave. To this end the EtherCAT master
(Beckhoff TwinCAT) parameterizes each EtherCAT slave during the start-up phase to define which process
data (size in bits/bytes, source location, transmission type) it wants to transfer to or from this slave. Incorrect
configuration can prevent successful start-up of the slave.

For Beckhoff EtherCAT EL, ES, EM, EJ and EP slaves the following applies in general:
• The input/output process data supported by the device are defined by the manufacturer in the ESI/XML
description. The TwinCAT EtherCAT Master uses the ESI description to configure the slave correctly.
• The process data can be modified in the system manager. See the device documentation.
Examples of modifications include: mask out a channel, displaying additional cyclic information, 16-bit
display instead of 8-bit data size, etc.
• In so-called “intelligent” EtherCAT devices the process data information is also stored in the CoE
directory. Any changes in the CoE directory that lead to different PDO settings prevent successful
startup of the slave. It is not advisable to deviate from the designated process data, because the
device firmware (if available) is adapted to these PDO combinations.

If the device documentation allows modification of process data, proceed as follows (see Figure “Configuring
the process data”).
• A: select the device to configure
• B: in the “Process Data” tab select Input or Output under SyncManager (C)
• D: the PDOs can be selected or deselected
• H: the new process data are visible as linkable variables in the system manager
The new process data are active once the configuration has been activated and TwinCAT has been
restarted (or the EtherCAT master has been restarted)
• E: if a slave supports this, Input and Output PDO can be modified simultaneously by selecting a so-
called PDO record (“predefined PDO settings”).

EL6601, EL6614 Version: 4.2 75


Commissioning

Fig. 98: Configuring the process data

Manual modification of the process data


According to the ESI description, a PDO can be identified as “fixed” with the flag “F” in the PDO
overview (Fig. “Configuring the process data”, J). The configuration of such PDOs cannot be
changed, even if TwinCAT offers the associated dialog (“Edit”). In particular, CoE content cannot be
displayed as cyclic process data. This generally also applies in cases where a device supports
download of the PDO configuration, “G”. In case of incorrect configuration the EtherCAT slave usu-
ally refuses to start and change to OP state. The System Manager displays an “invalid SM cfg” log-
ger message: This error message (“invalid SM IN cfg” or “invalid SM OUT cfg”) also indicates the
reason for the failed start.

A detailed description [} 81] can be found at the end of this section.

„Startup“ tab

The Startup tab is displayed if the EtherCAT slave has a mailbox and supports the CANopen over EtherCAT
(CoE) or Servo drive over EtherCAT protocol. This tab indicates which download requests are sent to the
mailbox during startup. It is also possible to add new mailbox requests to the list display. The download
requests are sent to the slave in the same order as they are shown in the list.

76 Version: 4.2 EL6601, EL6614


Commissioning

Fig. 99: „Startup“ tab

Column Description
Transition Transition to which the request is sent. This can either be
• the transition from pre-operational to safe-operational (PS), or
• the transition from safe-operational to operational (SO).
If the transition is enclosed in "<>" (e.g. <PS>), the mailbox request is fixed and cannot be
modified or deleted by the user.
Protocol Type of mailbox protocol
Index Index of the object
Data Date on which this object is to be downloaded.
Comment Description of the request to be sent to the mailbox

Move Up This button moves the selected request up by one


position in the list.
Move Down This button moves the selected request down by one
position in the list.
New This button adds a new mailbox download request to
be sent during startup.
Delete This button deletes the selected entry.
Edit This button edits an existing request.

“CoE – Online” tab

The additional CoE - Online tab is displayed if the EtherCAT slave supports the CANopen over EtherCAT
(CoE) protocol. This dialog lists the content of the object list of the slave (SDO upload) and enables the user
to modify the content of an object from this list. Details for the objects of the individual EtherCAT devices can
be found in the device-specific object descriptions.

EL6601, EL6614 Version: 4.2 77


Commissioning

Fig. 100: “CoE – Online” tab

Object list display


Column Description
Index Index and sub-index of the object
Name Name of the object
Flags RW The object can be read, and data can be written to the object (read/write)
RO The object can be read, but no data can be written to the object (read only)
P An additional P identifies the object as a process data object.
Value Value of the object

Update List The Update list button updates all objects in the displayed list
Auto Update If this check box is selected, the content of the objects is updated automatically.
Advanced The Advanced button opens the Advanced Settings dialog. Here you can specify
which objects are displayed in the list.

78 Version: 4.2 EL6601, EL6614


Commissioning

Fig. 101: Dialog “Advanced settings”

Online - via SDO Information If this option button is selected, the list of the objects included in the object
list of the slave is uploaded from the slave via SDO information. The list
below can be used to specify which object types are to be uploaded.
Offline - via EDS File If this option button is selected, the list of the objects included in the object
list is read from an EDS file provided by the user.

„Online“ tab

Fig. 102: „Online“ tab

EL6601, EL6614 Version: 4.2 79


Commissioning

State Machine
Init This button attempts to set the EtherCAT device to the Init state.
Pre-Op This button attempts to set the EtherCAT device to the pre-operational state.
Op This button attempts to set the EtherCAT device to the operational state.
Bootstrap This button attempts to set the EtherCAT device to the Bootstrap state.
Safe-Op This button attempts to set the EtherCAT device to the safe-operational state.
Clear Error This button attempts to delete the fault display. If an EtherCAT slave fails during
change of state it sets an error flag.
Example: An EtherCAT slave is in PREOP state (pre-operational). The master now
requests the SAFEOP state (safe-operational). If the slave fails during change of state
it sets the error flag. The current state is now displayed as ERR PREOP. When the
Clear Error button is pressed the error flag is cleared, and the current state is
displayed as PREOP again.
Current State Indicates the current state of the EtherCAT device.
Requested State Indicates the state requested for the EtherCAT device.

DLL Status

Indicates the DLL status (data link layer status) of the individual ports of the EtherCAT slave. The DLL status
can have four different states:
Status Description
No Carrier / Open No carrier signal is available at the port, but the port is open.
No Carrier / Closed No carrier signal is available at the port, and the port is closed.
Carrier / Open A carrier signal is available at the port, and the port is open.
Carrier / Closed A carrier signal is available at the port, but the port is closed.

File Access over EtherCAT


Download With this button a file can be written to the EtherCAT device.
Upload With this button a file can be read from the EtherCAT device.

"DC" tab (Distributed Clocks)

Fig. 103: "DC" tab (Distributed Clocks)

Operation Mode Options (optional):


• FreeRun
• SM-Synchron
• DC-Synchron (Input based)
• DC-Synchron
Advanced Settings… Advanced settings for readjustment of the real time determinant TwinCAT-
clock

Detailed information to Distributed Clocks are specified on http://infosys.beckhoff.com:

80 Version: 4.2 EL6601, EL6614


Commissioning

Fieldbus Components → EtherCAT Terminals → EtherCAT System documentation → EtherCAT basics →


Distributed Clocks

5.1.5.1 Detailed description of Process Data tab

Sync Manager

Lists the configuration of the Sync Manager (SM).


If the EtherCAT device has a mailbox, SM0 is used for the mailbox output (MbxOut) and SM1 for the mailbox
input (MbxIn).
SM2 is used for the output process data (outputs) and SM3 (inputs) for the input process data.

If an input is selected, the corresponding PDO assignment is displayed in the PDO Assignment list below.

PDO Assignment

PDO assignment of the selected Sync Manager. All PDOs defined for this Sync Manager type are listed
here:
• If the output Sync Manager (outputs) is selected in the Sync Manager list, all RxPDOs are displayed.
• If the input Sync Manager (inputs) is selected in the Sync Manager list, all TxPDOs are displayed.

The selected entries are the PDOs involved in the process data transfer. In the tree diagram of the System
Manager these PDOs are displayed as variables of the EtherCAT device. The name of the variable is
identical to the Name parameter of the PDO, as displayed in the PDO list. If an entry in the PDO assignment
list is deactivated (not selected and greyed out), this indicates that the input is excluded from the PDO
assignment. In order to be able to select a greyed out PDO, the currently selected PDO has to be deselected
first.

Activation of PDO assignment


ü If you have changed the PDO assignment, in order to activate the new PDO assignment,
a) the EtherCAT slave has to run through the PS status transition cycle (from pre-operational to
safe-operational) once (see Online tab [} 79]),
b) and the System Manager has to reload the EtherCAT slaves

( button for TwinCAT 2 or button for TwinCAT 3)

PDO list

List of all PDOs supported by this EtherCAT device. The content of the selected PDOs is displayed in the
PDO Content list. The PDO configuration can be modified by double-clicking on an entry.

Column Description
Index PDO index.
Size Size of the PDO in bytes.
Name Name of the PDO.
If this PDO is assigned to a Sync Manager, it appears as a variable of the slave with this
parameter as the name.
Flags F Fixed content: The content of this PDO is fixed and cannot be changed by the
System Manager.
M Mandatory PDO. This PDO is mandatory and must therefore be assigned to a
Sync Manager! Consequently, this PDO cannot be deleted from the PDO
Assignment list
SM Sync Manager to which this PDO is assigned. If this entry is empty, this PDO does not take
part in the process data traffic.
SU Sync unit to which this PDO is assigned.

EL6601, EL6614 Version: 4.2 81


Commissioning

PDO Content

Indicates the content of the PDO. If flag F (fixed content) of the PDO is not set the content can be modified.

Download

If the device is intelligent and has a mailbox, the configuration of the PDO and the PDO assignments can be
downloaded to the device. This is an optional feature that is not supported by all EtherCAT slaves.

PDO Assignment

If this check box is selected, the PDO assignment that is configured in the PDO Assignment list is
downloaded to the device on startup. The required commands to be sent to the device can be viewed in the
Startup [} 76] tab.

PDO Configuration

If this check box is selected, the configuration of the respective PDOs (as shown in the PDO list and the
PDO Content display) is downloaded to the EtherCAT slave.

5.2 General Notes - EtherCAT Slave Application


This summary briefly deals with a number of aspects of EtherCAT Slave operation under TwinCAT. More
detailed information on this may be found in the corresponding sections of, for instance, the EtherCAT
System Documentation.

Diagnosis in real time: WorkingCounter, EtherCAT State and Status

Generally speaking an EtherCAT Slave provides a variety of diagnostic information that can be used by the
controlling task.

This diagnostic information relates to differing levels of communication. It therefore has a variety of sources,
and is also updated at various times.

Any application that relies on I/O data from a fieldbus being correct and up to date must make diagnostic
access to the corresponding underlying layers. EtherCAT and the TwinCAT System Manager offer
comprehensive diagnostic elements of this kind. Those diagnostic elements that are helpful to the controlling
task for diagnosis that is accurate for the current cycle when in operation (not during commissioning) are
discussed below.

Fig. 104: Selection of the diagnostic information of an EtherCAT Slave

82 Version: 4.2 EL6601, EL6614


Commissioning

In general, an EtherCAT Slave offers


• communication diagnosis typical for a slave (diagnosis of successful participation in the exchange of
process data, and correct operating mode)
This diagnosis is the same for all slaves.

as well as
• function diagnosis typical for a channel (device-dependent)
See the corresponding device documentation

The colors in Fig. “Selection of the diagnostic information of an EtherCAT Slave” also correspond to the
variable colors in the System Manager, see Fig. “Basic EtherCAT Slave Diagnosis in the PLC”.

Colour Meaning
yellow Input variables from the Slave to the EtherCAT Master, updated in every cycle
red Output variables from the Slave to the EtherCAT Master, updated in every cycle
green Information variables for the EtherCAT Master that are updated acyclically. This means that
it is possible that in any particular cycle they do not represent the latest possible status. It is
therefore useful to read such variables through ADS.

Fig. “Basic EtherCAT Slave Diagnosis in the PLC” shows an example of an implementation of basic
EtherCAT Slave Diagnosis. A Beckhoff EL3102 (2-channel analogue input terminal) is used here, as it offers
both the communication diagnosis typical of a slave and the functional diagnosis that is specific to a channel.
Structures are created as input variables in the PLC, each corresponding to the process image.

Fig. 105: Basic EtherCAT Slave Diagnosis in the PLC

EL6601, EL6614 Version: 4.2 83


Commissioning

The following aspects are covered here:


Code Function Implementation Application/evaluation
A The EtherCAT Master's diagnostic infor- At least the DevState is to be evaluated for
mation the most recent cycle in the PLC.
updated acyclically (yellow) or provided The EtherCAT Master's diagnostic informa-
acyclically (green). tion offers many more possibilities than are
treated in the EtherCAT System Documenta-
tion. A few keywords:
• CoE in the Master for communication
with/through the Slaves
• Functions from TcEtherCAT.lib
• Perform an OnlineScan
B In the example chosen (EL3102) the Status In order for the higher-level PLC task (or cor-
EL3102 comprises two analogue input responding control applications) to be able to
• the bit significations may be
channels that transmit a single function rely on correct data, the function status must
found in the device
status for the most recent cycle. be evaluated there. Such information is
documentation
therefore provided with the process data for
• other devices may supply the most recent cycle.
more information, or none
that is typical of a slave
C For every EtherCAT Slave that has cyclic WcState (Working Counter) In order for the higher-level PLC task (or cor-
process data, the Master displays, using responding control applications) to be able to
0: valid real-time communication in
what is known as a WorkingCounter, rely on correct data, the communication sta-
the last cycle
whether the slave is participating success- tus of the EtherCAT Slave must be evaluated
fully and without error in the cyclic ex- 1: invalid real-time communication there. Such information is therefore provided
change of process data. This important, el- This may possibly have effects on with the process data for the most recent cy-
ementary information is therefore provided the process data of other Slaves cle.
for the most recent cycle in the System that are located in the same Syn-
Manager cUnit
1. at the EtherCAT Slave, and, with
identical contents
2. as a collective variable at the
EtherCAT Master (see Point A)
for linking.
D Diagnostic information of the EtherCAT State Information variables for the EtherCAT Mas-
Master which, while it is represented at the ter that are updated acyclically. This means
current Status (INIT..OP) of the
slave for linking, is actually determined by that it is possible that in any particular cycle
Slave. The Slave must be in OP
the Master for the Slave concerned and they do not represent the latest possible sta-
(=8) when operating normally.
represented there. This information cannot tus. It is therefore possible to read such vari-
be characterized as real-time, because it AdsAddr ables through ADS.
• is only rarely/never changed, The ADS address is useful for
except when the system starts up communicating from the PLC/task
via ADS with the EtherCAT Slave,
• is itself determined acyclically (e.g.
e.g. for reading/writing to the CoE.
EtherCAT Status)
The AMS-NetID of a slave corre-
sponds to the AMS-NetID of the
EtherCAT Master; communication
with the individual Slave is possible
via the port (= EtherCAT address).

NOTE
Diagnostic information
It is strongly recommended that the diagnostic information made available is evaluated so that the applica-
tion can react accordingly.

CoE Parameter Directory

The CoE parameter directory (CanOpen-over-EtherCAT) is used to manage the set values for the slave
concerned. Changes may, in some circumstances, have to be made here when commissioning a relatively
complex EtherCAT Slave. It can be accessed through the TwinCAT System Manager, see Fig. “EL3102,
CoE directory”:

84 Version: 4.2 EL6601, EL6614


Commissioning

Fig. 106: EL3102, CoE directory

EtherCAT System Documentation


The comprehensive description in the EtherCAT System Documentation (EtherCAT Basics --> CoE
Interface) must be observed!

A few brief extracts:


• Whether changes in the online directory are saved locally in the slave depends on the device. EL
terminals (except the EL66xx) are able to save in this way.
• The user must manage the changes to the StartUp list.

Commissioning aid in the TwinCAT System Manager

Commissioning interfaces are being introduced as part of an ongoing process for EL/EP EtherCAT devices.
These are available in TwinCAT System Managers from TwinCAT 2.11R2 and above. They are integrated
into the System Manager through appropriately extended ESI configuration files.

EL6601, EL6614 Version: 4.2 85


Commissioning

Fig. 107: Example of commissioning aid for a EL3204

This commissioning process simultaneously manages


• CoE Parameter Directory
• DC/FreeRun mode
• the available process data records (PDO)

Although the "Process Data", "DC", "Startup" and "CoE-Online" that used to be necessary for this are still
displayed, it is recommended that, if the commissioning aid is used, the automatically generated settings are
not changed by it.

The commissioning tool does not cover every possible application of an EL/EP device. If the available setting
options are not adequate, the user can make the DC, PDO and CoE settings manually, as in the past.

EtherCAT State: automatic default behaviour of the TwinCAT System Manager and manual operation

After the operating power is switched on, an EtherCAT Slave must go through the following statuses
• INIT
• PREOP
• SAFEOP
• OP

to ensure sound operation. The EtherCAT Master directs these statuses in accordance with the initialization
routines that are defined for commissioning the device by the ES/XML and user settings (Distributed Clocks
(DC), PDO, CoE). See also the section on "Principles of Communication, EtherCAT State Machine [} 36]" in
this connection. Depending how much configuration has to be done, and on the overall communication,
booting can take up to a few seconds.

The EtherCAT Master itself must go through these routines when starting, until it has reached at least the
OP target state.

The target state wanted by the user, and which is brought about automatically at start-up by TwinCAT, can
be set in the System Manager. As soon as TwinCAT reaches the status RUN, the TwinCAT EtherCAT
Master will approach the target states.

86 Version: 4.2 EL6601, EL6614


Commissioning

Standard setting

The advanced settings of the EtherCAT Master are set as standard:


• EtherCAT Master: OP
• Slaves: OP
This setting applies equally to all Slaves.

Fig. 108: Default behaviour of the System Manager

In addition, the target state of any particular Slave can be set in the "Advanced Settings" dialogue; the
standard setting is again OP.

Fig. 109: Default target state in the Slave

EL6601, EL6614 Version: 4.2 87


Commissioning

Manual Control

There are particular reasons why it may be appropriate to control the states from the application/task/PLC.
For instance:
• for diagnostic reasons
• to induce a controlled restart of axes
• because a change in the times involved in starting is desirable

In that case it is appropriate in the PLC application to use the PLC function blocks from the TcEtherCAT.lib,
which is available as standard, and to work through the states in a controlled manner using, for instance,
FB_EcSetMasterState.

It is then useful to put the settings in the EtherCAT Master to INIT for master and slave.

Fig. 110: PLC function blocks

Note regarding E-Bus current

EL/ES terminals are placed on the DIN rail at a coupler on the terminal strand. A Bus Coupler can supply the
EL terminals added to it with the E-bus system voltage of 5 V; a coupler is thereby loadable up to 2 A as a
rule. Information on how much current each EL terminal requires from the E-bus supply is available online
and in the catalogue. If the added terminals require more current than the coupler can supply, then power
feed terminals (e.g. EL9410) must be inserted at appropriate places in the terminal strand.

The pre-calculated theoretical maximum E-Bus current is displayed in the TwinCAT System Manager as a
column value. A shortfall is marked by a negative total amount and an exclamation mark; a power feed
terminal is to be placed before such a position.

88 Version: 4.2 EL6601, EL6614


Commissioning

Fig. 111: Illegally exceeding the E-Bus current

From TwinCAT 2.11 and above, a warning message "E-Bus Power of Terminal..." is output in the logger
window when such a configuration is activated:

Fig. 112: Warning message for exceeding E-Bus current

NOTE
Caution! Malfunction possible!
The same ground potential must be used for the E-Bus supply of all EtherCAT terminals in a terminal block!

EL6601, EL6614 Version: 4.2 89


Commissioning

5.3 Object description and parameterization


EtherCAT XML Device Description
The display matches that of the CoE objects from the EtherCAT XML Device Description. We rec-
ommend downloading the latest XML file from the download area of the Beckhoff website and in-
stalling it according to installation instructions.

Parameterization via the CoE list (CAN over EtherCAT)


The EtherCAT device is parameterized via the CoE-Online tab [} 77] (double-click on the respective
object) or via the Process Data tab [} 74](allocation of PDOs). Please note the following general CoE
notes [} 38] when using/manipulating the CoE parameters:
• Keep a startup list if components have to be replaced
• Differentiation between online/offline dictionary, existence of current XML description
• use “CoE reload” for resetting changes

Introduction

The CoE overview contains objects for different intended applications:


• Objects required for parameterization [} 90] during commissioning
• Objects intended for regular operation [} 91], e.g. through ADS access.
• Objects for indicating internal settings [} 91] (may be fixed)

The following section first describes the objects required for normal operation, followed by a complete
overview of missing objects.

5.3.1 Objects for commissioning

Index 1018 Identity


Index (hex) Name Meaning Data type Flags Default
1018:0 Identity Information for identifying the slave UINT8 RO 0x04 (4dec)
1018:01 Vendor ID Vendor ID of the EtherCAT slave UINT32 RO 0x00000002
(2dec)
1018:02 Product code Product code of the EtherCAT slave UINT32 RO 0x19C93052
(432615506dec
)
1018:03 Revision Revision number of the EtherCAT slave; the low word (bit UINT32 RO 0x00100000
0-15) indicates the special terminal number, the high (1048576dec)
word (bit 16-31) refers to the device description
1018:04 Serial number Serial number of the EtherCAT slave; the low byte (bit UINT32 RO 0x00000000
0-7) of the low word contains the year of production, the (0dec)
high byte (bit 8-15) of the low word contains the week of
production, the high word (bit 16-31) is 0

Index F800 EL6601 Para


Index (hex) Name Meaning Data type Flags Default
F800:0 EL6601 Para Max. subindex UINT8 RW 0x02 (2dec)
F800:01 General 0x0000: Standard operation UINT16 RW 0x0000 (0dec)
0x0001: VLAN TAGS are removed before filtering.
0x4000: EoE frames are blocked.
F800:02 NetVars This switch determines whether received subscriber data UINT16 RW 0x0000 (0dec)
from frames with 0x88A4 in the header, that have not
passed the subscriber filter, will be transported further via
EoE/Mailbox to the EtherCAT Master.
0x0000: default, subscriber data are forwarded via EoE
0x0100: Subscriber data are being discarded

90 Version: 4.2 EL6601, EL6614


Commissioning

5.3.2 Objects for regular operation

Index F100 Master Info


Index (hex) Name Meaning Data type Flags Default
F100:0 Master Info Max. subindex UINT8 RO 0x02 (2dec)
F100:01 Status Link Status of the Ethernet port UINT16 RO 0x0000 (0dec)
0: Link
1: No link
F100:02 Control reserved UINT16 RO 0x0000 (0dec)

Index FA01 MAC Info


Index (hex) Name Meaning Data type Flags Default
FA01:0 MAC Info Max. subindex UINT8 RW 0x03 (3dec)
FA01:01 RxPackets Received Ethernet telegrams UINT16 RW 0x0000 (0dec)
FA01:02 TxPackets Sent Ethernet telegrams UINT16 RW 0x0000 (0dec)
FA01:03 Reserved Reserved UINT16 RW 0x0000 (0dec)

5.3.3 Standard objects (0x1000-0x1FFF)


The standard objects have the same meaning for all EtherCAT slaves.

Index 1000 Device type


Index (hex) Name Meaning Data type Flags Default
1000:0 Device type Device type of the EtherCAT slave: The Lo-Word con- UINT32 RO 0x0000138A
tains the CoE profile used (5002). (5002dec)

Index 1008 Device name


Index (hex) Name Meaning Data type Flags Default
1008:0 Device name Device name of the EtherCAT slave STRING RO e.g.
EL6601-0000-
0017

Index 1009 Hardware version


Index (hex) Name Meaning Data type Flags Default
1009:0 Hardware version Hardware version of the EtherCAT slave STRING RO 00

Index 100A Software version


Index (hex) Name Meaning Data type Flags Default
100A:0 Software version Firmware version of the EtherCAT slave STRING RO 00

Index 1600-16FE RxPDO-Map


Index (hex) Name Meaning Data type Flags Default
1600+n:0 RxPDO-Map PDO Mapping RxPDO UINT8 RW 0x02 (2dec)
(each module gets its own entry (Index 0x1600+n),
0 ≤ n < maximum number of modules
(1600+n):01 Output Mapping Area 1. PDO Mapping Entry (Object 7000+n*8:07) UINT32 RW 0x7000+n*8:0
001 7, 16
(1600+n):02 Output Mapping Area 2. PDO Mapping Entry (Object 7000+n*8:0B) UINT32 RW 0x7000+n*8:0
002 B, 16

Index 1680 PDO control


Index (hex) Name Meaning Data type Flags Default
1680:0 PDO control Max. subindex UINT8 RW 0x01 (1dec)
1680:01 PDO control Entry Master Control UINT32 RW 0xF100:02, 16

EL6601, EL6614 Version: 4.2 91


Commissioning

Index 1A00-1AFE TxPDO-Map


Index (hex) Name Meaning Data type Flags Default
1A00+n:0 TxPDO Map Ch.2 PDO Mapping TxPDO UINT8 RW 0x03 (3dec)
(each module gets its own entry (Index 0x1A00+n),
0 ≤ n < maximum number of modules
(1A00+n):01 Input Mapping Area 1. PDO Mapping Entry (Object 0x6000+n*8:03) UINT32 RW 0x6000+n*8:0
001 3, 16
(1A00+n):02 Input Mapping Area 2. PDO Mapping Entry (Object 0x6000+n*8:04) UINT32 RW 0x6000+n*8:0
002 4, 16
(1A00+n):03 Input Mapping Area 3. PDO Mapping Entry (Object 0x6000+n*8:05) UINT32 RW 0x6000+n*8:0
003 5, 16

Index 1A80 PDO status


Index (hex) Name Meaning Data type Flags Default
1680:0 PDO status Max. subindex UINT8 RW 0x01 (1dec)
1680:01 PDO status Entry Master Status UINT32 RW 0xF100:01, 16

Index 1C00 Sync manager type


Index (hex) Name Meaning Data type Flags Default
1C00:0 Sync manager type Using the sync managers UINT8 RO 0x02 (2dec)
1C00:01 SubIndex 001 Sync-Manager Type Channel 1: Mailbox Write UINT8 RO 0x01 (1dec)
1C00:02 SubIndex 002 Sync-Manager Type Channel 2: Mailbox Read UINT8 RO 0x02 (2dec)
1C00:03 SubIndex 003 Sync-Manager Type Channel 3: Outputs UINT8 RO 0x02 (2dec)
1C00:04 SubIndex 004 Sync-Manager Type Channel 4: Inputs UINT8 RO 0x02 (2dec)

Index 1C12 RxPDO assign


Index (hex) Name Meaning Data type Flags Default
1C12:0 RxPDO assign PDO Assign Outputs UINT8 RW -
1C32:01 SubIndex 001 1. allocated RxPDO (contains the index of the associated UINT32 RW 0x1600
RxPDO mapping object) (5632dec)
...
1C12:80 SubIndex 128 128. allocated RxPDO (contains the index of the associ- UINT32 RW 0x167F
ated RxPDO mapping object) (5759dec)
1C12:81 SubIndex 129 PDO Control UINT32 RW 0x1680
(5760dec)

Index 1C13 TxPDO assign


Index (hex) Name Meaning Data type Flags Default
1C13:0 TxPDO assign PDO Assign Inputs UINT8 RW -
1C13:01 SubIndex 001 1. allocated TxPDO (contains the index of the associated UINT32 RW 0x1A00
TxPDO mapping object) (6656dec)
...
1C13:80 SubIndex 128 128. allocated TxPDO (contains the index of the associ- UINT32 RW 0x1A7F
ated TxPDO mapping object) (6783dec)
1C13:81 SubIndex 129 PDO status UINT32 RW 0x1A80
(6784dec)

92 Version: 4.2 EL6601, EL6614


Commissioning

Index 1C32 SM output parameter (only with network variables)


Index (hex) Name Meaning Data type Flags Default
1C32:0 SM output parameter Synchronization parameters for the outputs UINT8 RW 0x0E (14dec)
1C32:01 Sync mode Current synchronization mode: UINT16 RW 0x0001 (1dec)
• 1: Synchronous with SM 2 event
1C32:02 Cycle time Cycle time (in ns): UINT32 RW 0x00000000
(0dec)
• Free Run: Cycle time of the local timer
• Synchronous with SM 2 event: Master cycle time
• DC mode: SYNC0/SYNC1 Cycle Time
1C32:03 Shift time Time between SYNC0 event and output of the outputs (in UINT32 RW 0x00000000
ns, DC mode only) (0dec)
1C32:04 Sync modes sup- Supported synchronization modes: UINT16 RW 0x0002 (2dec)
ported
• Bit 1 = 1: Synchron with SM 2 event is supported

Index 1C33 SM input parameter (only with network variables)


Index (hex) Name Meaning Data type Flags Default
1C33:0 SM input parameter Synchronization parameters for the inputs UINT8 RW 0x0E (14dec)
1C33:01 Sync mode Current synchronization mode: UINT16 RW 0x0022 (34dec)
• 34: Synchron with SM 2 Event (outputs available)
1C33:02 Cycle time as 0x1C32:02 [} 93] UINT32 RW 0x00000000
(0dec)
1C33:03 Shift time Time between SYNC0 event and reading of the inputs (in UINT32 RW 0x00000000
ns, only DC mode) (0dec)
1C33:04 Sync modes sup- Supported synchronization modes: UINT16 RW 0x0002 (2dec)
ported
• Bit 1: Synchronous with SM 2 Event is supported
(outputs available)

EL6601, EL6614 Version: 4.2 93


Commissioning

5.3.4 Profile-specific objects (0x6000-0xFFFF)


The profile-specific objects have the same meaning for all EtherCAT slaves that support the profile 5001.

Index 6000-67F8 Receiving Frame Data (Net Var Subscriber)


Index (hex) Name Meaning Data type Flags Default
6000+n*8:0 Receiving Frame Max. subindex UINT8 RW P 0x05 (5dec)
Data (each module gets its own entry (Index 0x6000+n*8),
(Net Var Subscriber) 0 ≤ n < maximum number of modules
(6000+n*8): Net Id Source AMS Net Id UINT48 RW P -
01
(6000+n*8): Var Id Identification of network variables UINT16 RW P 0x0001 (1dec)
02
(6000+n*8): Quality Period over which the variable was not updated (resolu- UINT16 RO P 0x0000 (0dec)
03 tion 100 µs)
(6000+n*8): Cycle Index Entry is incremented with each Publisher cycle UINT16 RO P 0x0000 (0dec)
04
(6000+n*8): Data area 001 Data range OCTED_STRI RO P 00 00
05 NG

Index 6001-67F9 Sending frame State (Frame status)


Index (hex) Name Meaning Data type Flags Default
6001+n*8:0 Sending frame State Max. subindex UINT8 RW P 0x01 (1dec)
(Frame status) (each module gets its own entry (Index 0x6001+n*8),
0 ≤ n < maximum number of modules
(6001+n*8): Frame status Status UINT16 RW P 0x0000 (0dec)
01
• Bit 0: Frame bypassed
• Bit 1: Frame too large

Index 6002-67FA Receiving Frame Identification (Ignore Item Net Var Subscriber)
Index (hex) Name Meaning Data type Flags Default
6002+n*8:0 Receiving Frame Max. subindex UINT8 RW P 0x05 (5dec)
Identification (each module gets its own entry (Index 0x6002+n*8),
(Ignore Item Net Var 0 ≤ n < maximum number of modules
Subscriber)
(6002+n*8): Net Id "Net Id" 0: Entry is checked. If equality is de- UINT8 RW P 0x01 (1dec)
01 tected, the associated data areas are
(6002+n*8): Var Id "Var Id" transferred in the process data. UINT8 RW P 0x00 (0dec)
02 1: Entry is skipped. Associated data
(6000+n*8): Quality "Quality" areas are not transferred in the UINT8 RW P 0x01 (1dec)
03 process data.
(6002+n*8): Cycle Index "Cycle Index" UINT8 RW P 0x01 (1dec)
04
(6002+n*8): Data area 001 "Data area 001" UINT8 RW P 0x01 (1dec)
05

Index 6003-67FB Receiving Frame Length (Area Length Nat Var Subscriber)
Index (hex) Name Meaning Data type Flags Default
6003+n*8:0 Receiving Frame Max. subindex UINT8 RW P 0x05 (5dec)
Length (each module gets its own entry (Index 0x6003+n*8),
(Area Length Nat Var 0 ≤ n < maximum number of modules
Subscriber)
(6003+n*8): Net Id Length of the "Net Id" field UINT16 RW P 0x0006 (6dec)
01
(6003+n*8): Var Id Length of the "Var Id" field UINT16 RW P 0x0002 (2dec)
02
(6003+n*8): Quality Length of the "Quality" field UINT16 RW P 0x0002 (2dec)
03
(6003+n*8): Cycle Index Length of the "Cycle Index" field UINT16 RW P 0x0002 (2dec)
04
(6003+n*8): Data area 001 Length of the "Data area" field UINT16 RW P 0x0002 (2dec)
05

94 Version: 4.2 EL6601, EL6614


Commissioning

Index 7000-77F8 Sending Frame Data (Net Var Publisher)


Index (hex) Name Meaning Data type Flags Default
7000+n*8:0 Sending Frame Data Max. subindex UINT8 RW P -
(Net Var Publisher) (each module gets its own entry (Index 0x7000+n*8),
0 ≤ n < maximum number of modules
(7000+n*8): Destination MAC ad- MAC-Destination address Ethernet telegram UINT48 RW P -
01 dress
(7000+n*8): Source MAC address MAC-Source address Ethernet telegram UINT48 RW P -
02
(7000+n*8): Ethernet type Beckhoff Ethertype UINT16 RW P 0x88A4
03 (42120dec)
(7000+n*8): Header Bit 0-10: UINT16 RW P -
04 Length of the following entries
Bit 11: 0,
Bit 12-15: 4, Network variable -type
(7000+n*8): Net Id Source AMS Net Id UINT48 RW P -
05
(7000+n*8): # of Vars Number of variables UINT16 RW P -
06
(7000+n*8): Cycle Index Entry is incremented with each Publisher cycle UINT16 RO P -
07
(7000+n*8): reserved reserved UINT16 RW P -
08
(7000+n*8): Net Var 001 Id Identification of network variables UINT16 RW P -
09
(7000+n*8): Net Var 001 Header Byte 0,1: Hash value UINT48 RW P -
0A Byte 2,3: Length of the data
Byte 4,5: Quality
(7000+n*8): Net Var 001 Data Data range STRING RO P -
0B
-
(7000+n*8) Net Var y Id Identification of network variables UINT16 RW P -
:(3*y+6)
(7000+n*8) Net Var y Header Byte 0,1: Hash value UINT48 RW P -
:(3*y+7) Byte 2,3: Length of the data
Byte 4,5: Quality
(7000+n*8) Net Var y Data Data range OCTED_STRI RO P -
:(3*y+8) NG

Index 7001-77F9 Sending Frame Control (Frame control)


Index (hex) Name Meaning Data type Flags Default
7001+n*8:0 Sending Frame Con- Max. subindex UINT8 RW P 0x01 (1dec)
trol (each module gets its own entry (Index 0x7001+n*8),
(Frame control) 0 ≤ n < maximum number of modules
(7001+n*8): Frame Control Frame Control UINT8 RW P 0x00 (0dec)
01
• Bit 0 = 0: Send Frame
• Bit 0 = 1: Skip Frame

EL6601, EL6614 Version: 4.2 95


Commissioning

Index 7003-77FB Sending Frame Length (Area length Net Var Publisher)
Index (hex) Name Meaning Data type Flags Default
7003+n*8:0 Sending Frame Max. subindex UINT8 RW P -
Length (each module gets its own entry (Index 0x7003+n*8),
(Area length Net Var 0 ≤ n < maximum number of modules
Publisher)
(7003+n*8): Destination MAC ad- MAC-Destination address Ethernet telegram UINT48 RW P -
01 dress
(7003+n*8): Source MAC address MAC-Source address Ethernet telegram UINT48 RW P -
02
(7003+n*8): Ethernet type Beckhoff Ethertype UINT16 RW P 0x88A4
03 (42120dec)
(7003+n*8): Header Bit 0-10: UINT16 RW P -
04 Length of the following entries
Bit 11: 0,
Bit 12-15: 4, Network variable -type
(7003+n*8): Net Id Source AMS Net Id UINT48 RW P -
05
(7003+n*8): # of Vars Number of variables UINT16 RW P -
06
(7003+n*8): Cycle Index Entry is incremented with each Publisher cycle UINT16 RW P -
07
(7003+n*8): reserved reserved UINT16 RW P -
08
(7000+n*8): Net Var 001 Id Identification of network variables UINT16 RW P -
09
(7003+n*8): Net Var 001 Header Byte 0,1: Hash value UINT48 RW P -
0A Byte 2,3: Length of the data
Byte 4,5: Quality
(7003+n*8): Net Var 001 Data Data range STRING RW P -
0B
-
(7003+n*8) Net Var y Id Identification of network variables UINT16 RW P -
:(3*y+6)
(7003+n*8) Net Var y Header Byte 0,1: Hash value UINT48 RW P -
:(3*y+7) Byte 2,3: Length of the data
Byte 4,5: Quality
(7003+n*8) Net Var y Data Data range OCTED_STRI RW P -
:(3*y+8) NG

Index 8000-87F8 Frame Config


Index (hex) Name Meaning Data type Flags Default
8000+n*8:0 Frame Config Max. SubIndex UINT8 RW 0x04 (4dec)
(8000+n*8): Device type 3: Subscriber network variable, UINT16 RW -
04 corresponding indexes 600x are being created.

4: Publisher network variable,


corresponding indexes 0x700x are being created.

Index F000 Modular device profile


Index (hex) Name Meaning Data type Flags Default
F000:0 Modular device profile General information for the modular device profile UINT8 RO 0x04 (4dec)
F000:01 Module index dis- Index distance of the objects of the individual channels UINT16 RO 0x0008 (8dec)
tance
F000:02 Maximum number of Number of channels UINT16 RO 0x00FF
modules (255dec)
F000:03 Standard Entries in Standard Entries in the Objects 0x8yy0 UINT32 RO 0x00000000
Object 0x8yy0 (0dec)
F000:04 Standard Entries in Standard Entries in the Objects 0x8yy0 UINT32 RO 0x00000000
Object 0x9yy0 (0dec)

96 Version: 4.2 EL6601, EL6614


Commissioning

5.4 Beckhoff network variables

5.4.1 Introduction
Network variables are any variables that are cyclically exchanged between PC/CX1000 via TwinCAT.
Variables with any data types, including complex types, can be exchanged. The Publisher/Subscriber model
is used. For highly deterministic communication, the real-time Ethernet driver for TwinCAT must be installed.

Publisher/Subscriber model

In the Publisher/Subscriber model, the Publisher makes variables available. Subscribers can subscribe to a
variable. The Publisher can make the variable available to a Subscriber, several Subscribers or all
Subscribers. In Broadcast mode the variable is made available to all PCs, in Multicast mode to selected PCs
and in Unicast mode only to one selected PC. A Subscriber can also be Publisher at the same time. In this
way, a bidirectional data link can be provided.

Fig. 113: Publisher/Subscriber model

EL6601, EL6614 Version: 4.2 97


Commissioning

Unicast

The Publisher makes the network variable available to a single selected PC.

Multicast

The Publisher makes the network variable available to selected PCs.

Broadcast

The Publisher makes the network variable available to all PCs.

5.4.2 Configuration of the Publisher


In the TwinCAT System Manager, a new box is added for the Publisher under the RT Ethernet device.

Insert a Publisher Box

A Publisher box must be added under the RT Ethernet device.

Fig. 114: Insertion of a Publisher Box in the TwinCAT configuration

Insert a Network Variable

The network variables are inserted underneath the box. Enter a name (nCounterPub in the sample) and a
data type (UINT32 in the sample, corresponding to UDINT).

98 Version: 4.2 EL6601, EL6614


Commissioning

Fig. 115: Adding a network variable

Inputs and outputs are created underneath the added variables.

Fig. 116: Inputs/Outputs of the inserted variables

The FrameState input under the box indicates the current status of the sent Ethernet frames.

The following values are possible for the FrameState:

Short description Value Description


Not sent (frame skipped) 0x0001
Error (frame oversized) 0x0001 The maximum size of an Ethernet frames was exceeded. The
linked variable should be smaller.

EL6601, EL6614 Version: 4.2 99


Commissioning

A Control Word can be written in the FrameCtrl output under the box.

The following values are possible for FrameCtrl:

Short description Value Description


Disable sending 0x0001 Sending of a frame is interrupted. Sending of the frame does not
restart until the value is 0 again.

The VarState input under the network variable indicates the current status of the network variable.
The following values are possible for VarState:

Short description Value Description


Not sent (variable 0x0001
skipped)

A Control Word can be written in the VarCtrl output under the network variable.

The following values are possible for FrameCtrl:

Short description Value Description


Disable publishing 0x0001 Sending of the network variable is interrupted. Sending of the
network variable does not restart until the value is 0 again.

Mappings

The network variable of the Publisher can be mapped to any output variable with a suitable data type. In the
sample, the network variable is linked to the output variable of a PLC.

Fig. 117: Mapping of the network variable with an output variable of the PLC

100 Version: 4.2 EL6601, EL6614


Commissioning

5.4.3 Configuration of the Subscriber


In the TwinCAT System Manager, a new box is added for the Subscriber under the RT Ethernet device.

Adding a Subscriber box and linking the network variables

A Subscriber box must be added under the RT Ethernet device.

Fig. 118: Creation of an RT-Ethernet device

Fig. 119: Creation of a Subscriber Box (“Box 1”)

A network variable is then created under the Subscriber box.

Fig. 120: TwinCAT tree with “Box 1” Subscriber Box

EL6601, EL6614 Version: 4.2 101


Commissioning

Fig. 121: Create network variable with right click

The link to a Publisher variable can be created automatically. First, you need to find the Publisher computer.
All variables of this Publisher are then shown in a list.

Fig. 122: Searching for Publisher computer

Inputs and outputs were created under the added variable.

102 Version: 4.2 EL6601, EL6614


Commissioning

Fig. 123: Created in/outputs of the inserted variables

The FrameState input and the FrameCtrl output underneath the box give information about the current status
or control of the received Ethernet Frames. FrameState and FrameCtrl are reserved and are currently not
supported.

The VarState input and the VarCtrl output under the network variable indicate the current status (or control)
of the received network variable. VarState and VarCtrl are reserved and are currently not supported.

Quality of the network variables

The quality of a network variable is assessed on the Subscriber side. Two input variables are available for
this purpose under the network variable. The Quality variable provides a counter with a resolution of 100 µs.
The counter value indicates the variable delay. The sample below shows the online value of Quality when
the network connector is unplugged (counter increases) and reconnected (counter value 0).

EL6601, EL6614 Version: 4.2 103


Commissioning

Fig. 124: Time diagram (Online value) of the Quality variables

In addition to the Quality variables, the CycleIndex variable is incremented in each Publisher cycle.

Fig. 125: Time diagram (Online value) of the CycleIndex variables

104 Version: 4.2 EL6601, EL6614


Commissioning

5.4.4 Beckhoff network variables - Settings


Beckhoff network variables (NWV) can be used for cyclic or acyclic sending of data between Windows-based
PCs. In a device declared as a publisher (sender), such a network variable is received on the other side by a
subscriber declared as the same type. As the name suggests, this data traffic is network-based, and the
configuration is directly based on the protocols used.

A choice of two protocols is available:


• MAC: An ISO Layer 2 frame is sent with a sender and receiver MAC address, Ethertype 0x0806. An IP
part with the destination IP address (e.g. 192.168.0.1) is not included. The telegram can therefore be
further processed via a switch, but usually not via a router.
MAC stands for media access control and in this case refers to the (unique) hardware address
assigned to each Ethernet device during production. For sample, the Ethernet port of a Beckhoff PC
might have the MAC ID 00:01:05:34:05.84, with "00:01:05" representing the Beckhoff ID and the rest
assigned during production. The route of each Ethernet telegram between two Ethernet cable ends is
determined by the source MAC and the destination MAC.
The Ethernet telegram is identified as Beckhoff real-time Ethernet by the Ethertype 0x88A4. As a real-
time Ethernet telegram (RT Ethernet) it bypasses the regular Windows TCP stack and is sent with
higher priority, i.e. "immediately", via the specified Ethernet port of the PC.
An option is available for configuring whether the sent telegram is received by all (broadcast), many
(multicast) or a single subscriber (unicast).
• UDP/IP: The recipient is identified via an additional IP header in the Ethernet telegram. The UDP
Ethernet frame can thus be further processed via a router.
Once again, broadcast, multicast and unicast are available as options. The Ethernet telegram is
identified as Beckhoff real-time Ethernet through the Ethertype 0x88A4 and treated as an RT protocol
in the TwinCAT PC.
In contrast to TCP, as a connection-less protocol UDP requires no acknowledgement of receipt for the
message, i.e. the publisher does not know whether the subscriber has received the message. The ARP
protocol [} 109] is therefore used for remote terminal monitoring in TwinCAT.

The telegram with the process data arrives at the recipient device (network port) via these addressing
modes. In the Ethernet device/TwinCAT several transported process data are allocated via a variable ID

All network variables must be declared in the System Manager before they can be used.

The following intervention options are then available during operation:


• Sending of a configured network variable can be blocked dynamically
• The destination IP or destination MAC can be changed dynamically
• The variable ID "variable ID" can be changed dynamically
• The NWV content can be changed, but not the size (bit size)

Diagnostic variables on the publisher and subscriber side provide information about the connection quality.

If network variables are used, the temporal boundary conditions for the network topology used must be taken
into account: in the case of IP addressing (routed) on a case-by-case basis several 100 ms communications
cycle can be achieved, in the case of MAC addressing (switched) approximately 10 ms and less.

Diagnostic variable "quality"


If the processing tasks operate with different cycle times or the user changes the DataExchangeDi-
vider, this must be taken into account in the analysis of the diagnostic variables. In conjunction with
a fast Subscriber (e.g. 10 ms), a slow Publisher (e.g. 100 ms) leads to poor connection quality (as
reported by the diagnostic variable "Quality").
Dynamic temporary blocking of sending a Publisher must also be taken into account. In this case
the Subscriber registers poor quality.

Diagnostic variable "CycleIndex"


Please note the following information in order to decide whether you have to serve the variable Cy-
cleIndex.

EL6601, EL6614 Version: 4.2 105


Commissioning

Basic principles of Beckhoff network variables


• Quality:
Time in [100 µs] by which arrival of the NWV at the Publisher was delayed.
Relative arrival location:
Input process image of the TwinCAT system
Relative arrival time:
Time at which the next cycle is loaded into the input image

Note:
The reason for determining the delay so precisely is that the NWVs are managed directly by the IO
driver, independent of the cycle. Nevertheless, the data of an NWV that is delayed by a few percent of
the cycle time will not be taken into account until the input process image is read during the next task
cycle.

Note EL6601/EL6614:
Even with the EL66xx the NWV arrival time is defined as the time when the data are available in the
input process image of the RT device, not the time of arrival at the EL66xx or in the input image of the
EtherCAT device.

Fig. 126: Interrelationship between quality and delayed network variable

• Variable ID
The variable ID (16 bit) is used for global identification of the individual process data. Therefore, an ID
in the Publisher or Subscriber group may only be used once within a TwinCAT device, see Fig. Sample
for communication via network variables: Publishers 1 and 2 on PC1 must have different IDs (10 and
8), although the same ID (8) may be used in Publisher 2 and Subscriber 1.

Selecting the variable ID


In order to achieve unambiguous allocation we recommend using different IDs for each data com-
munication between connected PCs. Reason: In Fig. Sample for communication via network vari-
ables, PC2/Subscriber2 not only receives the designed ID=8-variable from PC1/Publisher2, but,
since it is sent as a broadcast (!), it also receives the NWV from PC3/Publisher1. Differentiation is
then no longer possible in PC2.

• Cycle Index
The 16-bit cycle index is a counter sent by the Publisher together with the data. It is generally
incremented with each transmission and can therefore be used as an indicator for flawless transfer. It
can be read on the subscriber side as CycleIndex. Its appearance depends on the Publisher platform:
- Publisher on a PC: The variable CycleIndex is not visible and is automatically and cyclically
incremented by the System Manager
- Publisher on an EL66xx: The variable CycleIndex is visible and must be incremented/served by the
user such that it is not equal 0 on the subscriber side.

106 Version: 4.2 EL6601, EL6614


Commissioning

Fig. 127: Sample for communication via network variables

EL6601, EL6614 Version: 4.2 107


Commissioning

Data representation on different platforms


Please note that simple and complex data (WORD, ARRAYs, REAL, STRING, user-defined struc-
tures) are represented internally in a different manner on different platforms!
x86 platforms use byte-alignment, others (ARM) 2-byte or 4-byte alignment.
This means that if a complex structure is created in an x86/PC PLC project and an ARM PLC
project, they can each have a different effective size and a different internal structure. (see Fig.
“Data representation e.g. x86 Systems vs. ARM Systems”)
In the sample, the structure in the CX (and hence the network variable to be created there) is larger
than in the PC; also the word and real variables do not match each other because a variable can
begin at any byte position in the PC, but only at every even-numbered one in the CX.
Consequences
Recommendation for structures that are identical on both end devices
- firstly, all 4-byte variables (must lie at an address that is divisible by 4)
- then all 2-byte variables (must lie at an address that is divisible by 2)
- then all 1-byte variables
Further recommendations
- if STRING(x) is used, the "EndOfString" zero is also interpreted as a character, otherwise x+1
must be divisible by 4
- the above rules also apply to sub-structures.
Please refer to the notes in the Structure section of the Infosys.
Consequences
Use of Bus Terminal Controllers (BICxxxx, BXxxxx)
Since the representation of floating point numbers (REAL) on Bus Terminal Controllers (BCxxxx,
BXxxxx) differs from that in the x86, these cannot be transmitted. "SINT", for sample, can be used
for signed values.

Fig. 128: Data representation e.g. x86 Systems vs. ARM Systems

Settings in the System Manager

Appearance of the variables


Depending on the platform used (PC or EL66xx), the publisher/subscriber will appear differently. A
publisher/subscriber can be created
• On a PC network interface, see Fig. Publisher settings - RT Ethernet
• on an EL66xx, see Beckhoff network variables - Settings [} 105]

The following settings options are available in the Beckhoff System Manager TwinCAT 2.10 build 1328:

108 Version: 4.2 EL6601, EL6614


Commissioning

Publisher, Box

Fig. 129: Publisher RT Ethernet settings

RT Ethernet settings:
• MAC-Broadcast: Sent to all network devices, destination MAC FF:FF:FF:FF:FF:FF.
• Multicast: A destination MAC address becomes a multicast address if the first bit in the first byte of the
MAC (the so-called group bit) is set. With the Beckhoff ID "00 01 05" the default target address "01 01
05 04 00 00" is formed, as shown in Fig. Publisher RT Ethernet settings.
The MAC range 01:00:5E:00:00:00 to 01:00:5E:FF:FF:FF is intended for general multicast application,
with the first 3 bytes specified by the IEEE and the last 3 bytes derived from the lower part of the IP
address of the destination PC. The resulting destination MAC therefore never physically exists in the
network. Instead, the destination network card detects Ethernet frames formed in this way as multicast
frames sent to it, although the Ethernet port itself can have another, unique MAC address. Please refer
to the relevant literature for further rules relating to the formation of multicast MAC/IP addresses.
• Unicast: Either direct entry of the destination MAC or via the AMS Net ID of the destination device, e.g.
123.456.123.456.1.1, in which case this route must be entered in the local AMS router (right-click on
the TwinCAT icon in the taskbar --> Properties --> AMS router)

Use of broadcast and multicast


Network variables sent as broadcast or multicast at MAC or IP level can generate high network load
(depending on the cycle time), since they are multiplied into the whole connected network. This may
cause simple network devices such as printers to crash. With short cycle times all network traffic
may become blocked. We strongly recommend using unicast addressing, taking into account vari-
able identification, as described above.

Advanced Settings:
• Data exchange: The task cycle time * divider is the rhythm at which this network variable is sent. (not
for EL66xx).
• VLAN support: In conjunction with manageable switches the Ethernet frame parameterized here can
be assigned a fixed route via VLAN tagging (Virtual Local Area Network).

EL6601, EL6614 Version: 4.2 109


Commissioning

Fig. 130: Publisher settings - UDP/IP

UDP/IP settings - the addressing technique of the IP network layer with IP addresses is used. UDP is a
connection-less protocol without feedback.
• Broadcast: Sent to all device with destination IP (v4) 255.255.255.255
• Multicast: The destination IP must be specified, see notes on MAC multicast
• Unicast: Specify the target device (e.g.: 192.168.0.1), making sure that it can be reached through the
subnet mask

Use of broadcast and multicast


Network variables sent as broadcast or multicast at MAC or IP level can generate high network load
(depending on the cycle time), since they are multiplied into the whole connected network. This may
cause simple network devices such as printers to crash. With short cycle times all network traffic
may become blocked. We strongly recommend using unicast addressing, taking into account vari-
able identification, as described above.

Advanced Settings:
• "ARP Retry Interval": In order to ascertain the presence of the recipient, the publisher sends an ARP
request to the target device at these intervals. If the network administration of the recipient is
operational, it sends an ARP reply. This is only meaningful with unicast.
In the event of an error bit 3 is set (0x0004) in the diagnostic FrameState variable.
Note: ARP handling (ARP = Address Resolution Protocol: allocation of hardware/MAC addresses to
network addresses [IP]) is managed by the operating system (Windows).
• "Disable Subscriber Monitoring": deactivates the procedure described above.
• "Target Address changeable": In this case the destination IP can be changed dynamically.

110 Version: 4.2 EL6601, EL6614


Commissioning

Publisher, Variable

Fig. 131: Publisher variable settings

Settings:
• "Variable ID": Identification number with which the variable is sent. Can be changed online via PLC
where appropriate.
• "Data exchange": see above (not for EL66xx).
• "On change only": NWV is only sent if the value changes (not for EL66xx).

Subscriber, Box

Fig. 132: Subscriber settings

Settings:
• "Receiving Options": Only permits NWVs from a certain publisher for this subscriber

EL6601, EL6614 Version: 4.2 111


Commissioning

• "Multicast Configuration": ditto.

Process data:
• "VarId": If activated, the variable ID can be modified online

Subscriber, variable

Fig. 133: Subscriber variable settings

Settings:
• "Variable ID": Only permits NWVs with a certain ID for this subscriber. Can be changed dynamically via
PLC where appropriate.
• "Ignore Data Type Hash": Hash calculation is currently not supported

Process data:
• "Quality": See explanatory notes above.
• "CycleIndex": This index is incremented with each successful transfer, IF this is done by the opposite
side, i.e. the publisher. If the publisher is an EL66x, the user must increment CycleIdx there.
• "VarData": Transferred data.

112 Version: 4.2 EL6601, EL6614


Application samples

6 Application samples

6.1 Sample programs


Using the sample programs
This document contains sample applications of our products for certain areas of application. The
application notices provided here are based on typical features of our products and only serve as
samples. The notices contained in this document explicitly do not refer to specific applications. The
customer is therefore responsible for assessing and deciding whether the product is suitable for a
particular application. We accept no responsibility for the completeness and correctness of the
source code contained in this document. We reserve the right to modify the content of this docu-
ment at any time and accept no responsibility for errors and missing information.

Sample 1: Determine Publisher/Subscriber data throughput

Sample program (https://infosys.beckhoff.com/content/1033/el6601_el6614/Resources/


zip/2349555083.zip)

With appropriate EtherCAT cycle time and depending on the scale and number of the publishers/subscribers
configured in the EL66xx, real-time cycle times down to 500 µs or below are possible.

Typical throughput values for EL6601, FW08, Rev. EL6601-0000-0018 are


• 1 publisher with 1000 bytes, 1 subscriber with 1000 bytes, simultaneous bidirectional operation: 2 ms
• 1 publisher with 100 bytes, 1 subscriber with 100 bytes, simultaneous bidirectional operation: 300 µs

Both characteristic values were determined with this https://infosys.beckhoff.com/content/1033/


el6601_el6614/Resources/zip/2349555083.zip. TwinCAT from version 2.11 is required for the *.tsm System
Manager file.

The EL6601 is used as a sample to explain configuration as publisher or subscriber for network variables.
The dialogs under TwinCAT 2.10 and TwinCAT 2.11 here are slightly different.

Sample 2: Online diagnostics

Sample program (https://infosys.beckhoff.com/content/1033/el6601_el6614/Resources/


zip/2349552907.zip)

The following objects are available for initial diagnostic in the CoE directory:
• 0xFA01, subindex 01: Frame Counter Rx (incoming to RJ45 socket)
• 0xFA01, subindex 02: Frame Counter Tx (outgoing from RJ45 socket)

The values can be read from the controller using PLC function blocks (FB_EcCoeSdoRead in
TcEtherCAT.lib).

This and further diagnostic information from the CoE of the EL66xx are accessible via https://
infosys.beckhoff.com/content/1033/el6601_el6614/Resources/zip/2349552907.zip.

EL6601, EL6614 Version: 4.2 113


Application samples

6.2 Application sample - network printer


The application samples have been tested with a test configuration and are described accordingly.
Certain deviations when setting up actual applications are possible.

The following hardware was used for the test configuration:


• TwinCAT master PC with Windows XP Professional SP 2, TwinCAT version 2.10 (Build 1305) and
INTEL PRO/100 VE Ethernet adapter
• Beckhoff Ethernet coupler terminal EK1100, terminals EL1012, EL6601 and EL9010
• Printer HP LaserJet 4200tn

A network printer is connected to the EL6601 within the terminal network via the Control Panel of the control
system IPC:

Fig. 134: Connection of a network printer

Legend:
EtherCAT connection

Ethernet connection

Checking the network address of the TwinCAT master PC


• Start the TwinCAT System Manager in Config mode, read the Bus Terminal configuration, and activate
free-run mode

114 Version: 4.2 EL6601, EL6614


Application samples

• The EL6601 should appear in the system configuration being in OP mode (see Online [} 73] tab
EtherCAT Status Machine)

Fig. 135: EL6601 in the configuration

• Connect the network printer with the EL6601 via a CAT-5 (1:1) cable
• In the Control Panel of the controller IPC, check the network adapter via which the EtherCAT system is
operated:
Network Connections [Properties] -> Local Area Connection (TwinCAT LAN adapter), [Properties]->
Internet Protocol (TCP/IP) [Properties]

Fig. 136: Context Menu Network Environment -> “Properties”

EL6601, EL6614 Version: 4.2 115


Application samples

Fig. 137: Context Menu “LAN Connection (TwinCAT-LAN-Adapter),” -> “Properties”

Fig. 138: Properties Internet Protocol (TCP/IP)

• Enter an IP address for the subnet of the network printer (e.g. 192.168.0.1/255.255.255.0) and confirm
with OK

116 Version: 4.2 EL6601, EL6614


Application samples

Fig. 139: Entry of the IP address of the subnetwork of the network printer

Network address
The network address in the sample is only used for the purpose of illustrating the configuration.
Please note that in your application the IP address of network printer must match the IP number
range/subnet mask of the master PC.

• Configure the network printer (in the configuration menu of the printer) and allocate the printer an IP
address from the IP number range of the subnet defined above
(Follow the user guide of your printer), e.g.: 192.168.0.37
• Configure the network printer via the Control Panel:
Printers & Faxes -> Add a printer , in the Add Printer Wizard select Local printer, and in the following
pull-down menu Create a new port. .. select Standard TCP/IP Port

Fig. 140: Control Panel “Add a Printer” under “Printers and Faxes”

EL6601, EL6614 Version: 4.2 117


Application samples

Fig. 141: Select “Local Printer” radio button

Fig. 142: Select Connection Type

• In the following menu under Printer Name or IP Address enter the IP address of the printer defined in
the configuration menu (in the sample 192.168.0.37)

118 Version: 4.2 EL6601, EL6614


Application samples

Fig. 143: Entry of the IP address and printer name

• Confirm the port properties and exit the wizard


• In the Add Printer Wizard install the drivers from your printer manufacturer

6.3 Application sample - Service interface with remote


desktop
The application samples have been tested with a test configuration and are described accordingly.
Certain deviations when setting up actual applications are possible.

The following hardware was used for the test configuration:


• TwinCAT master PC with Windows XP Professional SP 2, TwinCAT version 2.10 (Build 1305) and
INTEL PRO/100 VE Ethernet adapter
• Beckhoff Ethernet coupler terminal EK1100, terminals EL1012, EL6601 and EL9010
• Notebook (service PC) for remote desktop connection with Windows XP Professional SP 2 and
standard Ethernet interface

EL6601, EL6614 Version: 4.2 119


Application samples

Fig. 144: Integration of a Service interface with remote desktop-PC

Configuration at the TwinCAT master PC


• Start the TwinCAT System Manager in Config mode, read the Bus Terminal configuration, and activate
free-run mode
• The EL6601 should appear in the system configuration being in OP mode (see Online [} 73] tab
EtherCAT Status Machine)

120 Version: 4.2 EL6601, EL6614


Application samples

Fig. 145: EL6601 in the configuration

• In analogy to the configuration of a network printer the IP number of the EtherCAT network port of the
TwinCAT Master-PC in the subnet is e.g. 192.168.0.1
• Open the Control Panel of the TwinCAT master PC and click on Security Center -> Windows Firewall

Fig. 146: Selection of “Security Center” in the View Control Panel Category

EL6601, EL6614 Version: 4.2 121


Application samples

Fig. 147: Choose security settings for Windows Firewall

• If the Windows firewall is activated click on tab Exceptions


• Select Remote Desktop and confirm with OK

122 Version: 4.2 EL6601, EL6614


Application samples

Fig. 148: At the “Exceptions” Tab activate the “Remote desktop” service

• Return to the Control Panel of TwinCAT master PC and select Performance and Maintenance ->
System

EL6601, EL6614 Version: 4.2 123


Application samples

Fig. 149: Select “Service and Maintenance” from “System” in the View Control Panel

• Click on the Remote tab, and in the Remote Desktop category select the option Allow users to
establish a remote desktop connection

124 Version: 4.2 EL6601, EL6614


Application samples

Fig. 150: Check “Allow users to establish a remote desktop connection”

• Open the list of remote desktop users via the button Select remote users... and add additional users if
required
• Confirm with OK.

Fig. 151: Adding remote desktop users

Configuration at the service PC

For a remote desktop connection with the TwinCAT master PC via the EL6601 the network address of the
service PC has to be set according to the IP number range of the TwinCAT master PC subnet.
• Connect the Ethernet port of the service PC with the EL6601 via a CAT-5 (1:1) cable
• In the Control Panel of the Service-PC check the Ethernet network adapter, via which the EtherCAT
system is operated:
Network Connections [Properties] -> Local Area Connection (Ethernet LAN adapter), [Properties]->
Internet Protocol (TCP/IP) [Properties]

EL6601, EL6614 Version: 4.2 125


Application samples

Fig. 152: Context Menu Network Environment -> “Properties”

Fig. 153: Context Menu “LAN Connection (Ethernet-LAN-Adapter),” -> “Properties”

126 Version: 4.2 EL6601, EL6614


Application samples

Fig. 154: Properties Internet Protocol (TCP/IP)

• Enter an IP address for the subnet of the network printer (e.g. 192.168.0.38/255.255.255.0) and
confirm with OK

Fig. 155: Entry of the IP address of the subnetwork of the Service-PC

• The Ethernet connection to the TwinCAT master PC is now tunneled via the EL6601 through the
EtherCAT terminal network and can be established via the remote desktop.

Establishing the remote desktop connection


• On the service PC start the remote desktop connection via Start -> Programs -> Accessories ->
Communication -> Remote desktop connection

EL6601, EL6614 Version: 4.2 127


Application samples

Fig. 156: Start remote desktop connection

• Enter the IP address of the TwinCAT master PC (e.g. 192.168.0.1) and click Connect

Fig. 157: Entry of the IP address of the Remote-PC

• The login window of the TwinCAT master PC appears on the desktop of the service PC
• Enter your user name and password for the TwinCAT master PC and confirm with OK
The IP address of the TwinCAT master PC is shown above the remote desktop

128 Version: 4.2 EL6601, EL6614


Application samples

Fig. 158: Login window of the remote PC via the remote desktop connection

Login via remote desktop


Users can only log in via a remote desktop if a user name and password have been set up in the
TwinCAT master PC!

• The TwinCAT system can now be remotely controlled via the service PC.
To log out close the remote desktop window.

Fig. 159: Closing the remote desktop connection

Access to the remote system


When controlling the TwinCAT master PC via a remote desktop TwinCAT must be executed in Run
mode or Config mode (free run). If the task is interrupted the service PC can no longer access the
remote system!

6.4 Application sample - Lower-level control system


The application samples have been tested with a test configuration and are described accordingly.
Certain deviations when setting up actual applications are possible.

EL6601, EL6614 Version: 4.2 129


Application samples

The following hardware was used for the test configuration:


• TwinCAT master PC with Windows XP Professional SP 2, TwinCAT version 2.10 (Build 1305) and
INTEL PRO/100 VE Ethernet adapter
• Beckhoff Ethernet coupler terminal EK1100, terminals EL1012, EL6601 and EL9010
• Beckhoff Embedded PC CX9000 (subordinate control unit) with Windows CE v5.00, HW 1.4, terminals
EL2032, EL9010

Fig. 160: Integration of a lower-level control system

Configuration of the subordinate control system

For a connection with the TwinCAT master PC via the EL6601 the network address of the subordinate
control system has to be set according to the IP number range of the TwinCAT master PC subnet.
• From the desktop of the lower-level control system (Windows CE) choose Start -> Settings -> Network
and Dial-up Connections to start the configuration of the network settings
(You can also find information about setting the network address of a lower-level control system from
the Documentation on TwinCAT System Manager)

130 Version: 4.2 EL6601, EL6614


Application samples

Fig. 161: Select Configuration of network connections

• Open the network settings for this connection by double-clicking on the TCIXPNPE1 connection
(Ethernet port)

Fig. 162: Select network settings for Ethernet port

• Enter an IP number from the IP number range of the subnet (e.g. 192.168.0.39/255.255.255.0) for the
TwinCAT master PC and confirm with OK.

EL6601, EL6614 Version: 4.2 131


Application samples

Fig. 163: Enter IP address

Configuration at the TwinCAT master PC and establishing a connection


• Start the TwinCAT System Manager in Config mode, read the Bus Terminal configuration, and activate
free-run mode
• The EL6601 should appear in the system configuration being in OP mode (see Online [} 73] tab
EtherCAT Status Machine)

Fig. 164: EL6601 in the configuration

• In analogy to the configuration of a network printer, the IP number of the TwinCAT master PC in the
subnet might be 192.168.0.1, for sample
• Connect the subordinate control unit (target system) with the EL6601 via a CAT-5 (1:1) cable
• Start another system manager session in Config mode and click on Select Target System...-> Search
(Ethernet)

132 Version: 4.2 EL6601, EL6614


Application samples

Fig. 165: Select target system

• Enter the IP address of the subordinate control system in the field next to Enter Host Name / IP:
• After confirming the button Enter Host Name / IP: the name of the target system appears in the
selection box

Fig. 166: In the “Route Dialog” add the route of the target system

• Click on Add Route and enter the access data for the target system as required
• After closing the dialog box the name of the target system appears in the selection menu
• Make your selection and confirm with OK

EL6601, EL6614 Version: 4.2 133


Application samples

Fig. 167: Confirm selection

• Activate free-run mode for reading the Bus Terminal configuration of the subordinate control system

Fig. 168: Enable FreeRun

6.5 Application sample – setting up an EtherCAT Master


PC as a network bridge
The application samples have been tested with a test configuration and are described accordingly.
Certain deviations when setting up actual applications are possible.
In this sample, transmission is intended to take place from a subordinate PC via the EL6601 and EtherCAT
and a Master PC into a superordinate network.

The following hardware was used:


• Computers A and B: Windows XP SP2

134 Version: 4.2 EL6601, EL6614


Application samples

• Computer C: Windows XP Embedded

Fig. 169: Setting up an EtherCAT-Master-PC as Network Bridge

To do this, the Master PC "TwinCAT Master" (B) must be setup as a TCP/IP bridge in order to route TCP/IP
telegrams through to the subordinate CX1020 (C) or to relay them in the opposite direction. The partner
device is a PC (A).
Distinction must be made between two cases here: static addresses [} 135] and DHCP address assignment
[} 138] (network).

The following explanations assume the preceding samples as basic knowledge.

Computers (A), (B) and (C) have a static IP address

Fig. 170: Configuration of the network PC

• Configure the three PCs as shown in the diagram. The dialogs for the properties of the Internet
protocol were explained in the preceding samples.
• Using the registry editor (Start --> Run --> regedit), set the entry "IPEnableRouter" in the "bridge" PC B
to the value 1. The entry is usually located under HKEY_LOCAL_MACHINE\SYSTEM
\ControlSet001\Services\TCPIP\Parameters or also under HKEY_LOCAL_MACHINE\SYSTEM
\CurrentControlSet\Services\TCPIP\Parameters.
• Following a restart, routing for IP telegrams is active for this PC. The connection can then be checked
by means of a ping (Start --> Run --> cmd --> ping 192.168.1.1) to the EtherCAT port 192.168.1.1.
• If the EtherCAT master is in a normal and error-free state (TwinCAT in "Config"/"FreeRun" or "Run"
mode), the connected Ethernet device with the IP address 192.168.1.10 can be reached via the
EL6601.

EL6601, EL6614 Version: 4.2 135


Application samples

• Explanation of the entry Gateway, using PC A as an sample: PC A has the IP address 10.16.2.8 with a
subnet mask 255.255.255.0. This means that it can reach all IP telegrams within a range from
10.16.2.0 to 10.16.2.255. If it is required to send an IP telegram to a different address range (e.g. to
192.168.1.1), this must run via the defined gateway, in this case 10.16.2.21, which in turn can relay the
telegram to 192.168.1.10 via the configured IP routing.
• Windows offers the useful command line command ipconfig for checking the configuration. If PC A is
configured correctly, the command Start Run cmd ipconfig/all displays the following screen:

Fig. 171: Checking the configuration with command line command “ipconfig /all”

• IP routing is disabled (default) and the IP address of the selected adaptor (here called LAN) is
assigned fixedly. Since DHCP was set beforehand, WINS entries are still present.
• The same command on PC C displays:

Fig. 172: Checking the configuration PC C

• This was entered under XP in the dialog

136 Version: 4.2 EL6601, EL6614


Application samples

Fig. 173: Entry of network parameters

• Accordingly, the command on the bridge PC B displays:

Fig. 174: Checking the Configuration Bridge PC B

"ipconfig" switches
Using the switches /release and /renew, the command ipconfig can be used to re-establish IP con-
nections.

Checklist for connection settings:


• Bridge PC configured for "IP routing" by means of registry entry
• Fixed IP addresses in correlating ranges for all 4 Ethernet ports involved
• Firewalls disabled if need be (unnecessary in the case of the default setting)
• EtherCAT/TwinCAT in "Freerun" or "Run" mode
• Link display on all ports involved

EL6601, EL6614 Version: 4.2 137


Application samples

• "Ping" works

Observation of network traffic


Experienced users can observe and evaluate the network traffic using a network sniffer, such as
Wireshark.

Notice on Operating system Windows CE/embedded


Under Windows CE IP Routing must be set in the CX Configuration Dialog (see Fig. “Setting IP
Routing in Windows CE”)
The entry “TCP/IP Settings” -> “IP Routing” sets the Registry-Key “IPEnableRouter”= 1 under
[HKEY_LOCAL_MACHINE\Comm\Tcpip\Parms]
Restart required.
See also Microsoft Developer Network: Routing for IPv4 - Explanation on Routing.
Ordinarily the Routing table is automatically maintained, if necessary routes will still have to be
added with “Route Add” command, see also Windows XP/7 etc.
Windows CE does not support some Routing protocols such as RIP or OSPF.

Fig. 175: Setting “IP Routing” in Windows CE

Network with DHCP address assignment

A connection between the PCs C and A (or the network) is not possible.

Explanation: Computers (A) and (B) receive their IP addresses from the DHCP server if the Ethernet ports
are configured accordingly. One possible sequence is as follows (see RFC1541 and RFC2131):
• A newly connected PC sends a DHCPDISCOVER message with its MAC address via MAC Broadcast
to all other network devices
• The DHCP server offers the requesting device one or more IP addresses in the DHCPOFFER
message
• The requesting PC selects an IP address and answers via MAC Broadcast with a DHCPREQUEST
message to the DHCP server
• The DHCP server confirms the selection with a DHCPACK message.

138 Version: 4.2 EL6601, EL6614


Application samples

This works for computers (A) and (B). The DHCPDISCOVER messages from computer (C) are accepted by
the EL6601 and relayed in computer (B) to Windows via the EtherCAT port, but Windows (B) does not route
these messages (and all other DHCP telegrams) through to the relaying Ethernet port – this function, known
as DHCP Relay Agent, is only available in the server version of Windows.

This is the normal operating case when Windows PCs configured as DHCP devices are linked with each
other.

Remedy:
• Install a local DHCP server on computer (B), taking care that no conflict arises with the superordinate
network DHCP server
• It is possible that two Windows PCs, which are configured as DHCP devices and connected to each
other, will only establish their addresses after a short time (several minutes)

6.6 Application sample - Flexible Ethernet Port


The application samples have been tested with a test configuration and are described accordingly.
Certain deviations when setting up actual applications are possible.

This sample illustrates the principle of remote access from a subordinate PC to the central EtherCAT
controller via a flexibly connected EL6601 and EtherCAT.

The following elements were used:


• IPC with Windows XP SP2
• TwinCAT 2.11 b1534
• EL6601, SN xxxx0605

The approach

The task is to commission an extensive system with EtherCAT topology. To this end frequent access to the
TwinCAT System Manager on the central PC is required. In practice the technician will primarily be at the
local terminals/EtherCAT slaves during commissioning. The central System Manager as the TwinCAT target
system should therefore be accessed from the respective coupler location via a remote PC and Ethernet.

Two mechanisms are used for this purpose:


• EtherCAT tunnels standard IP telegrams through dedicated slaves, e.g. EL6601, via the acyclic
mailbox procedure
• Via the HotConnect functionality a coupler station (coupler + terminals) can be classified as freely
pluggable in the configuration (.tsm). Special couplers must be used for this purpose.

A freely pluggable combination of EK1101 and EL6601 (HotConnect group) can now be used as a flexible
Ethernet interface.

Possible configuration

A possible configuration is described below:

EL6601, EL6614 Version: 4.2 139


Application samples

Fig. 176: Structure HotConnect Group

The system offers EK1110 (end couplers), EK1122 (junction terminals) and free EK1100 ports for connecting
the HotConnect group. The IP addresses should be regarded as samples, the notes from the previous
samples must be taken into account.

No further settings are required at the TwinCAT/EtherCAT master. EoE is automatically forwarded in
TwinCAT 2.11.

Remote access operability and EtherCAT state


The process of Ethernet pass-through described here only works as long as the EtherCAT master
and the EL66xx are at least in state PREOP. Otherwise no mailbox traffic and therefore no Ethernet
transport takes place. However, if the network structure is already functional, this does not repre-
sent an insurmountable obstacle for general commissioning.

Change of location and EtherCAT state


Once the HotConnect group is reconnected with the EtherCAT network it may take several seconds
for the group to participate in the data traffic again, the EL66xx to be in OP state again and the link
(see link LED) to be restored.

Sample configuration

A small EtherCAT system is commissioned, the offline topology view in the System Manager shows two
coupler stations and one non-localized station with an EK1101.
• In offline state the System Manager does not know where the EK1101 station with its ID was
connected.

140 Version: 4.2 EL6601, EL6614


Application samples

Fig. 177: EK1101 localized with EL6601

• The current assignment is visible online, the EK1101 with the EL6601 is connected to the second port
of the EK1100.

Fig. 178: EK1101 localized with EL6601

• All slaves are in OP state, so that this system can now be accessed as target system from the remote
PC.
• In the remote system an empty System Manager is opened and the EtherCAT computer with the IP
172.1.1.1 (in this sample) is located as the target system via IP
(Tab Actions -> Choose Target System -> "Search (Ethernet)" -> [enter IP 172.1.1.1] -> "Enter Host
Name / IP")

Fig. 179: Selection of the target system

EL6601, EL6614 Version: 4.2 141


Application samples

Fig. 180: Enter target system 172.1.1.1

• After double-clicking on the line showing the found target system the user can log into the target
system:

Fig. 181: Entry of logon information on target system

• After successful connection the configuration can be loaded by the target system through "Open from
target system".

142 Version: 4.2 EL6601, EL6614


Application samples

Fig. 182: Opening of target system and loading of configuration

Checklist

The following checklist can be used for a successful configuration up to remote access:

1. Successful EtherCAT configuration


- no LostFrames
- EtherCAT master and all slaves in OP state
- all WorkingCounters = 0; if necessary, set up special SyncUnits for deliberately inactive slaves
2. Set a different IP address for the EtherCAT port and the port used at the laptop, but within the same
subnet section.
(here: 172.1.1.1 and 172.1.1.2)
3. Check the connection from both sides through ping commands
4. Establish connection as target system

Ethernet connection
It is advisable to use credible addresses in the Properties dialog of the network interface, IP proto-
col (Windows XP SP2) Default gateway and DNS server, although they are not actually required.
Settings of the remote PC from the sample:

Fig. 183: Entry of network addresses in the remote system

EL6601, EL6614 Version: 4.2 143


Appendix

7 Appendix

7.1 UL notice
Application
Beckhoff EtherCAT modules are intended for use with Beckhoff’s UL Listed EtherCAT Sys-
tem only.

Examination
For cULus examination, the Beckhoff I/O System has only been investigated for risk of fire
and electrical shock (in accordance with UL508 and CSA C22.2 No. 142).

For devices with Ethernet connectors


Not for connection to telecommunication circuits.

Basic principles

Two UL certificates are met in the Beckhoff EtherCAT product range, depending upon the components:

1. UL certification according to UL508. Devices with this kind of certification are marked by this sign:

2. UL certification according to UL508 with limited power consumption. The current consumed by the de-
vice is limited to a max. possible current consumption of 4 A. Devices with this kind of certification are
marked by this sign:

Almost all current EtherCAT products (as at 2010/05) are UL certified without restrictions.

Application

If terminals certified with restrictions are used, then the current consumption at 24 VDC must be limited
accordingly by means of supply
• from an isolated source protected by a fuse of max. 4 A (according to UL248) or
• from a voltage supply complying with NEC class 2.
A voltage source complying with NEC class 2 may not be connected in series or parallel with another
NEC class 2compliant voltage supply!

These requirements apply to the supply of all EtherCAT bus couplers, power adaptor terminals, Bus
Terminals and their power contacts.

144 Version: 4.2 EL6601, EL6614


Appendix

7.2 Firmware compatibility


Beckhoff EtherCAT devices are delivered with the latest available firmware version. Compatibility of firmware
and hardware is mandatory; not every combination ensures compatibility. The overview below shows the
hardware versions on which a firmware can be operated.

Note
• It is recommended to use the newest possible firmware for the respective hardware.
• Beckhoff is not under any obligation to provide customers with free firmware updates for delivered
products.

NOTE
Risk of damage to the device!
Pay attention to the instructions for firmware updates on the separate page [} 146]. If a device is placed in
BOOTSTRAP mode for a firmware update, it does not check when downloading whether the new firmware
is suitable. This can result in damage to the device! Therefore, always make sure that the firmware is suit-
able for the hardware version!

EL6601
Hardware (HW) Firmware (FW) Revision No. Date of release
05 - 14 06 2009/07
07 EL6601-0000-0017 2009/09
08 2009/11
09 2010/07
EL6601-0000-0018 2010/09
10 2011/09
EL6601-0000-0019 2012/10
11 2013/04
12 EL6601-0000-0020 2014/07
15 – 16* 13 EL6601-0000-0021 2014/12
14 2015/07
15* 2017/02

EL6614
Hardware (HW) Firmware (FW) Revision No. Date of release
00 - 09* 01 EL6614-0000-0017 2008/05
02 2008/12
03 2009/08
04 2009/11
05 2010/07
EL6614-0000-0018 2010/09
06 2011/09
EL6614-0000-0019 2012/10
07 2013/04
08 EL6614-0000-0020 2014/07
10 – 13* 09 EL6614-0000-0021 2014/12
10 2015/07
11* 2017/02

*) This is the current compatible firmware/hardware version at the time of the preparing this documentation.
Check on the Beckhoff web page whether more up-to-date documentation is available.

EL6601, EL6614 Version: 4.2 145


Appendix

7.3 Firmware Update EL/ES/EM/ELM/EPxxxx


This section describes the device update for Beckhoff EtherCAT slaves from the EL/ES, ELM, EM, EK and
EP series. A firmware update should only be carried out after consultation with Beckhoff support.

Storage locations

An EtherCAT slave stores operating data in up to 3 locations:


• Depending on functionality and performance EtherCAT slaves have one or several local controllers for
processing I/O data. The corresponding program is the so-called firmware in *.efw format.
• In some EtherCAT slaves the EtherCAT communication may also be integrated in these controllers. In
this case the controller is usually a so-called FPGA chip with *.rbf firmware.
• In addition, each EtherCAT slave has a memory chip, a so-called ESI-EEPROM, for storing its own
device description (ESI: EtherCAT Slave Information). On power-up this description is loaded and the
EtherCAT communication is set up accordingly. The device description is available from the download
area of the Beckhoff website at (https://www.beckhoff.de). All ESI files are accessible there as zip files.

Customers can access the data via the EtherCAT fieldbus and its communication mechanisms. Acyclic
mailbox communication or register access to the ESC is used for updating or reading of these data.

The TwinCAT System Manager offers mechanisms for programming all 3 parts with new data, if the slave is
set up for this purpose. Generally the slave does not check whether the new data are suitable, i.e. it may no
longer be able to operate if the data are unsuitable.

Simplified update by bundle firmware

The update using so-called bundle firmware is more convenient: in this case the controller firmware and the
ESI description are combined in a *.efw file; during the update both the firmware and the ESI are changed in
the terminal. For this to happen it is necessary
• for the firmware to be in a packed format: recognizable by the file name, which also contains the
revision number, e.g. ELxxxx-xxxx_REV0016_SW01.efw
• for password=1 to be entered in the download dialog. If password=0 (default setting) only the firmware
update is carried out, without an ESI update.
• for the device to support this function. The function usually cannot be retrofitted; it is a component of
many new developments from year of manufacture 2016.

Following the update, its success should be verified


• ESI/Revision: e.g. by means of an online scan in TwinCAT ConfigMode/FreeRun – this is a convenient
way to determine the revision
• Firmware: e.g. by looking in the online CoE of the device

NOTE
Risk of damage to the device!
Note the following when downloading new device files

• Firmware downloads to an EtherCAT device must not be interrupted


• Flawless EtherCAT communication must be ensured. CRC errors or LostFrames must be avoided.
• The power supply must adequately dimensioned. The signal level must meet the specification.

In the event of malfunctions during the update process the EtherCAT device may become unusable and re-
quire re-commissioning by the manufacturer.

146 Version: 4.2 EL6601, EL6614


Appendix

7.3.1 Device description ESI file/XML


NOTE
Attention regarding update of the ESI description/EEPROM
Some slaves have stored calibration and configuration data from the production in the EEPROM. These are
irretrievably overwritten during an update.

The ESI device description is stored locally on the slave and loaded on start-up. Each device description has
a unique identifier consisting of slave name (9 characters/digits) and a revision number (4 digits). Each slave
configured in the System Manager shows its identifier in the EtherCAT tab:

Fig. 184: Device identifier consisting of name EL3204-0000 and revision -0016

The configured identifier must be compatible with the actual device description used as hardware, i.e. the
description which the slave has loaded on start-up (in this case EL3204). Normally the configured revision
must be the same or lower than that actually present in the terminal network.

For further information on this, please refer to the EtherCAT system documentation.

Update of XML/ESI description


The device revision is closely linked to the firmware and hardware used. Incompatible combinations
lead to malfunctions or even final shutdown of the device. Corresponding updates should only be
carried out in consultation with Beckhoff support.

Display of ESI slave identifier

The simplest way to ascertain compliance of configured and actual device description is to scan the
EtherCAT boxes in TwinCAT mode Config/FreeRun:

EL6601, EL6614 Version: 4.2 147


Appendix

Fig. 185: Scan the subordinate field by right-clicking on the EtherCAT device

If the found field matches the configured field, the display shows

Fig. 186: Configuration is identical

otherwise a change dialog appears for entering the actual data in the configuration.

Fig. 187: Change dialog

In this example in Fig. Change dialog, an EL3201-0000-0017 was found, while an EL3201-0000-0016 was
configured. In this case the configuration can be adapted with the Copy Before button. The Extended
Information checkbox must be set in order to display the revision.

148 Version: 4.2 EL6601, EL6614


Appendix

Changing the ESI slave identifier

The ESI/EEPROM identifier can be updated as follows under TwinCAT:


• Trouble-free EtherCAT communication must be established with the slave.
• The state of the slave is irrelevant.
• Right-clicking on the slave in the online display opens the EEPROM Update dialog, Fig. EEPROM
Update

Fig. 188: EEPROM Update

The new ESI description is selected in the following dialog, see Fig. Selecting the new ESI. The checkbox
Show Hidden Devices also displays older, normally hidden versions of a slave.

Fig. 189: Selecting the new ESI

A progress bar in the System Manager shows the progress. Data are first written, then verified.

The change only takes effect after a restart.


Most EtherCAT devices read a modified ESI description immediately or after startup from the INIT.
Some communication settings such as distributed clocks are only read during power-on. The Ether-
CAT slave therefore has to be switched off briefly in order for the change to take effect.

EL6601, EL6614 Version: 4.2 149


Appendix

7.3.2 Firmware explanation

Determining the firmware version

Determining the version on laser inscription

Beckhoff EtherCAT slaves feature serial numbers applied by laser. The serial number has the following
structure: KK YY FF HH

KK - week of production (CW, calendar week)


YY - year of production
FF - firmware version
HH - hardware version

Example with ser. no.: 12 10 03 02:

12 - week of production 12
10 - year of production 2010
03 - firmware version 03
02 - hardware version 02

Determining the version via the System Manager

The TwinCAT System Manager shows the version of the controller firmware if the master can access the
slave online. Click on the E-Bus Terminal whose controller firmware you want to check (in the example
terminal 2 (EL3204)) and select the tab CoE Online (CAN over EtherCAT).

CoE Online and Offline CoE


Two CoE directories are available:
• online: This is offered in the EtherCAT slave by the controller, if the EtherCAT slave supports this.
This CoE directory can only be displayed if a slave is connected and operational.
• offline: The EtherCAT Slave Information ESI/XML may contain the default content of the CoE.
This CoE directory can only be displayed if it is included in the ESI (e.g. "Beckhoff EL5xxx.xml").
The Advanced button must be used for switching between the two views.

In Fig. Display of EL3204 firmware version the firmware version of the selected EL3204 is shown as 03 in
CoE entry 0x100A.

Fig. 190: Display of EL3204 firmware version

In (A) TwinCAT 2.11 shows that the Online CoE directory is currently displayed. If this is not the case, the
Online directory can be loaded via the Online option in Advanced Settings (B) and double-clicking on
AllObjects.

150 Version: 4.2 EL6601, EL6614


Appendix

7.3.3 Updating controller firmware *.efw


CoE directory
The Online CoE directory is managed by the controller and stored in a dedicated EEPROM, which
is generally not changed during a firmware update.

Switch to the Online tab to update the controller firmware of a slave, see Fig. Firmware Update.

Fig. 191: Firmware Update

Proceed as follows, unless instructed otherwise by Beckhoff support. Valid for TwinCAT 2 and 3 as
EtherCAT master.
• Switch TwinCAT system to ConfigMode/FreeRun with cycle time >= 1 ms (default in ConfigMode is 4
ms). A FW-Update during real time operation is not recommended.

EL6601, EL6614 Version: 4.2 151


Appendix

• Switch EtherCAT Master to PreOP

• Switch slave to INIT (A)


• Switch slave to BOOTSTRAP
• Check the current status (B, C)
• Download the new *efw file (wait until it ends). A pass word will not be neccessary usually.

• After the download switch to INIT, then PreOP


• Switch off the slave briefly (don't pull under voltage!)
• Check within CoE 0x100A, if the FW status was correctly overtaken.

7.3.4 FPGA firmware *.rbf


If an FPGA chip deals with the EtherCAT communication an update may be accomplished via an *.rbf file.
• Controller firmware for processing I/O signals
• FPGA firmware for EtherCAT communication (only for terminals with FPGA)

The firmware version number included in the terminal serial number contains both firmware components. If
one of these firmware components is modified this version number is updated.

Determining the version via the System Manager

The TwinCAT System Manager indicates the FPGA firmware version. Click on the Ethernet card of your
EtherCAT strand (Device 2 in the example) and select the Online tab.

The Reg:0002 column indicates the firmware version of the individual EtherCAT devices in hexadecimal and
decimal representation.

152 Version: 4.2 EL6601, EL6614


Appendix

Fig. 192: FPGA firmware version definition

If the column Reg:0002 is not displayed, right-click the table header and select Properties in the context
menu.

Fig. 193: Context menu Properties

The Advanced Settings dialog appears where the columns to be displayed can be selected. Under
Diagnosis/Online View select the '0002 ETxxxx Build' check box in order to activate the FPGA firmware
version display.

EL6601, EL6614 Version: 4.2 153


Appendix

Fig. 194: Dialog Advanced Settings

Update

For updating the FPGA firmware


• of an EtherCAT coupler the coupler must have FPGA firmware version 11 or higher;
• of an E-Bus Terminal the terminal must have FPGA firmware version 10 or higher.

Older firmware versions can only be updated by the manufacturer!

Updating an EtherCAT device

The following sequence order have to be met if no other specifications are given (e.g. by the Beckhoff
support):
• Switch TwinCAT system to ConfigMode/FreeRun with cycle time >= 1 ms (default in ConfigMode is
4 ms). A FW-Update during real time operation is not recommended.

154 Version: 4.2 EL6601, EL6614


Appendix

• In the TwinCAT System Manager select the terminal for which the FPGA firmware is to be updated (in
the example: Terminal 5: EL5001) and
click the Advanced Settings button in the EtherCAT tab:

• The Advanced Settings dialog appears. Under ESC Access/E²PROM/FPGA click on Write FPGA
button:

EL6601, EL6614 Version: 4.2 155


Appendix

• Select the file (*.rbf) with the new FPGA firmware, and transfer it to the EtherCAT device:

• Wait until download ends


• Switch slave current less for a short time (don't pull under voltage!). In order to activate the new FPGA
firmware a restart (switching the power supply off and on again) of the EtherCAT device is required.
• Check the new FPGA status

NOTE
Risk of damage to the device!
A download of firmware to an EtherCAT device must not be interrupted in any case! If you interrupt this
process by switching off power supply or disconnecting the Ethernet link, the EtherCAT device can only be
recommissioned by the manufacturer!

7.3.5 Simultaneous updating of several EtherCAT devices


The firmware and ESI descriptions of several devices can be updated simultaneously, provided the devices
have the same firmware file/ESI.

Fig. 195: Multiple selection and firmware update

Select the required slaves and carry out the firmware update in BOOTSTRAP mode as described above.

156 Version: 4.2 EL6601, EL6614


Appendix

7.4 Restoring the delivery state


To restore the delivery state for backup objects in ELxxxx terminals, the CoE object Restore default
parameters, SubIndex 001 can be selected in the TwinCAT System Manager (Config mode) (see Fig.
Selecting the Restore default parameters PDO)

Fig. 196: Selecting the "Restore default parameters" PDO

Double-click on SubIndex 001 to enter the Set Value dialog. Enter the value 1684107116 in field Dec or the
value 0x64616F6C in field Hex and confirm with OK (Fig. Entering a restore value in the Set Value dialog).
All backup objects are reset to the delivery state.

Fig. 197: Entering a restore value in the Set Value dialog

Alternative restore value


In some older terminals the backup objects can be switched with an alternative restore value: Deci-
mal value: 1819238756, Hexadecimal value: 0x6C6F6164An incorrect entry for the restore value
has no effect.

EL6601, EL6614 Version: 4.2 157


Appendix

7.5 Support and Service


Beckhoff and their partners around the world offer comprehensive support and service, making available fast
and competent assistance with all questions related to Beckhoff products and system solutions.

Beckhoff's branch offices and representatives

Please contact your Beckhoff branch office or representative for local support and service on Beckhoff
products!

The addresses of Beckhoff's branch offices and representatives round the world can be found on her internet
pages:
http://www.beckhoff.com

You will also find further documentation for Beckhoff components there.

Beckhoff Headquarters

Beckhoff Automation GmbH & Co. KG

Huelshorstweg 20
33415 Verl
Germany

Phone: +49(0)5246/963-0
Fax: +49(0)5246/963-198
e-mail: info@beckhoff.com

Beckhoff Support

Support offers you comprehensive technical assistance, helping you not only with the application of
individual Beckhoff products, but also with other, wide-ranging services:
• support
• design, programming and commissioning of complex automation systems
• and extensive training program for Beckhoff system components

Hotline: +49(0)5246/963-157
Fax: +49(0)5246/963-9157
e-mail: support@beckhoff.com

Beckhoff Service

The Beckhoff Service Center supports you in all matters of after-sales service:
• on-site service
• repair service
• spare parts service
• hotline service

Hotline: +49(0)5246/963-460
Fax: +49(0)5246/963-479
e-mail: service@beckhoff.com

158 Version: 4.2 EL6601, EL6614


List of illustrations

List of illustrations
Fig. 1 EL5021 EL terminal, standard IP20 IO device with serial/ batch number and revision ID (since
2014/01)....................................................................................................................................... 9
Fig. 2 EK1100 EtherCAT coupler, standard IP20 IO device with serial/ batch number......................... 10
Fig. 3 CU2016 switch with serial/ batch number.................................................................................... 10
Fig. 4 EL3202-0020 with serial/ batch number 26131006 and unique ID-number 204418 ................... 10
Fig. 5 EP1258-00001 IP67 EtherCAT Box with batch number/ date code 22090101 and unique se-
rial number 158102...................................................................................................................... 11
Fig. 6 EP1908-0002 IP67 EtherCAT Safety Box with batch number/ date code 071201FF and
unique serial number 00346070 .................................................................................................. 11
Fig. 7 EL2904 IP20 safety terminal with batch number/ date code 50110302 and unique serial num-
ber 00331701............................................................................................................................... 11
Fig. 8 ELM3604-0002 terminal with unique ID number (QR code) 100001051 and serial/ batch num-
ber 44160201............................................................................................................................... 11
Fig. 9 EL6601, EL6614 .......................................................................................................................... 12
Fig. 10 EL6601 as a virtual, field-distributed switch................................................................................. 13
Fig. 11 EL66xx data diagram................................................................................................................... 15
Fig. 12 IP settings EtherCAT port ............................................................................................................ 16
Fig. 13 Connection failure between primary EtherCAT port and 1st slave (X) ........................................ 17
Fig. 14 Real frame structure from the TwinCAT System Manager .......................................................... 18
Fig. 15 Default setting of the EL66xx as switch port without IP address assignment.............................. 19
Fig. 16 From FW03: Settings for dynamically assigned IP address ........................................................ 19
Fig. 17 Default mailbox settings............................................................................................................... 20
Fig. 18 Increasing the mailbox................................................................................................................. 21
Fig. 19 TwinCAT 2.11, virtual TwinCAT switch........................................................................................ 21
Fig. 20 TwinCAT 2.11, virtual TwinCAT switch........................................................................................ 22
Fig. 21 Notice on exceeding configured data volume.............................................................................. 24
Fig. 22 Network variable sample configuration on an EL6601 ................................................................ 24
Fig. 23 Append device ............................................................................................................................. 27
Fig. 24 Select EL6601 ............................................................................................................................. 27
Fig. 25 Append box.................................................................................................................................. 28
Fig. 26 Append network variable ............................................................................................................. 28
Fig. 27 Link device with EL6601 .............................................................................................................. 28
Fig. 28 Append new device ..................................................................................................................... 29
Fig. 29 Select EtherCAT Automation Protocol......................................................................................... 29
Fig. 30 Device assignment to the EL66xx ............................................................................................... 29
Fig. 31 Append box.................................................................................................................................. 30
Fig. 32 Publisher/Subscriber.................................................................................................................... 30
Fig. 33 Topology view.............................................................................................................................. 30
Fig. 34 Virtual TwinCAT switch in the CX20x0 & CX50x0 system........................................................... 31
Fig. 35 Dialog for selection of the PCI port .............................................................................................. 31
Fig. 36 Insertion of the EL66xx in the Configuration................................................................................ 32
Fig. 37 New Network “Local Area Connection” in the Windows network connections ............................ 32
Fig. 38 System manager current calculation .......................................................................................... 34
Fig. 39 EtherCAT tab -> Advanced Settings -> Behavior -> Watchdog .................................................. 35
Fig. 40 States of the EtherCAT State Machine........................................................................................ 37
Fig. 41 "CoE Online " tab ........................................................................................................................ 39

EL6601, EL6614 Version: 4.2 159


List of illustrations

Fig. 42 Startup list in the TwinCAT System Manager ............................................................................. 40


Fig. 43 Offline list ..................................................................................................................................... 41
Fig. 44 Online list .................................................................................................................................... 41
Fig. 45 Correct positioning....................................................................................................................... 46
Fig. 46 Incorrect positioning..................................................................................................................... 46
Fig. 47 Recommended distances for standard installation position ........................................................ 47
Fig. 48 Other installation positions .......................................................................................................... 48
Fig. 49 System Manager “Options” (TwinCAT 2)..................................................................................... 51
Fig. 50 Call up under VS Shell (TwinCAT 3) ........................................................................................... 51
Fig. 51 Overview of network interfaces ................................................................................................... 51
Fig. 52 EtherCAT device properties(TwinCAT 2): click on „Compatible Devices…“ of tab “Adapter” ..... 52
Fig. 53 Windows properties of the network interface............................................................................... 52
Fig. 54 Exemplary correct driver setting for the Ethernet port ................................................................. 53
Fig. 55 Incorrect driver settings for the Ethernet port ............................................................................. 54
Fig. 56 TCP/IP setting for the Ethernet port ............................................................................................ 55
Fig. 57 Identifier structure ....................................................................................................................... 56
Fig. 58 OnlineDescription information window (TwinCAT 2) ................................................................... 57
Fig. 59 Information window OnlineDescription (TwinCAT 3) ................................................................... 57
Fig. 60 File OnlineDescription.xml created by the System Manager ...................................................... 58
Fig. 61 Indication of an online recorded ESI of EL2521 as an example .................................................. 58
Fig. 62 Information window for faulty ESI file (left: TwinCAT 2; right: TwinCAT 3).................................. 58
Fig. 63 Append EtherCAT device (left: TwinCAT 2; right: TwinCAT 3) ................................................... 60
Fig. 64 Selecting the EtherCAT connection (TwinCAT 2.11, TwinCAT 3)............................................... 60
Fig. 65 Selecting the Ethernet port ......................................................................................................... 60
Fig. 66 EtherCAT device properties (TwinCAT 2) ................................................................................... 61
Fig. 67 Appending EtherCAT devices (left: TwinCAT 2; right: TwinCAT 3)............................................. 61
Fig. 68 Selection dialog for new EtherCAT device ................................................................................. 62
Fig. 69 Display of device revision ........................................................................................................... 62
Fig. 70 Display of previous revisions ...................................................................................................... 63
Fig. 71 Name/revision of the terminal ...................................................................................................... 63
Fig. 72 EtherCAT terminal in the TwinCAT tree (left: TwinCAT 2; right: TwinCAT 3).............................. 64
Fig. 73 Differentiation local/target system (left: TwinCAT 2; right: TwinCAT 3)....................................... 65
Fig. 74 Scan Devices (left: TwinCAT 2; right: TwinCAT 3) ...................................................................... 65
Fig. 75 Note for automatic device scan (left: TwinCAT 2; right: TwinCAT 3)........................................... 65
Fig. 76 Detected Ethernet devices .......................................................................................................... 66
Fig. 77 Example default state .................................................................................................................. 66
Fig. 78 Installing EthetCAT terminal with revision -1018 ......................................................................... 67
Fig. 79 Detection of EtherCAT terminal with revision -1019 .................................................................... 67
Fig. 80 Scan query after automatic creation of an EtherCAT device (left: TwinCAT 2; right: Twin-
CAT 3) ......................................................................................................................................... 67
Fig. 81 Manual triggering of a device scan on a specified EtherCAT device (left: TwinCAT 2; right:
TwinCAT 3).................................................................................................................................. 68
Fig. 82 Scan progressexemplary by TwinCAT 2 ..................................................................................... 68
Fig. 83 Config/FreeRun query (left: TwinCAT 2; right: TwinCAT 3)......................................................... 68
Fig. 84 Displaying of “Free Run” and “Config Mode” toggling right below in the status bar .................... 68
Fig. 85 TwinCAT can also be switched to this state by using a button (left: TwinCAT 2; right: Twin-
CAT 3) ......................................................................................................................................... 68

160 Version: 4.2 EL6601, EL6614


List of illustrations

Fig. 86 Online display example ............................................................................................................... 69


Fig. 87 Faulty identification ...................................................................................................................... 69
Fig. 88 Identical configuration (left: TwinCAT 2; right: TwinCAT 3) ......................................................... 70
Fig. 89 Correction dialog ......................................................................................................................... 70
Fig. 90 Name/revision of the terminal ...................................................................................................... 71
Fig. 91 Correction dialog with modifications ........................................................................................... 72
Fig. 92 Dialog “Change to Compatible Type…” (left: TwinCAT 2; right: TwinCAT 3) .............................. 72
Fig. 93 TwinCAT 2 Dialog Change to Alternative Type ........................................................................... 72
Fig. 94 Branch element as terminal EL3751............................................................................................ 73
Fig. 95 “General” tab................................................................................................................................ 73
Fig. 96 „EtherCAT“ tab............................................................................................................................. 74
Fig. 97 “Process Data” tab....................................................................................................................... 75
Fig. 98 Configuring the process data....................................................................................................... 76
Fig. 99 „Startup“ tab................................................................................................................................. 77
Fig. 100 “CoE – Online” tab ....................................................................................................................... 78
Fig. 101 Dialog “Advanced settings”.......................................................................................................... 79
Fig. 102 „Online“ tab .................................................................................................................................. 79
Fig. 103 "DC" tab (Distributed Clocks)....................................................................................................... 80
Fig. 104 Selection of the diagnostic information of an EtherCAT Slave ................................................... 82
Fig. 105 Basic EtherCAT Slave Diagnosis in the PLC............................................................................... 83
Fig. 106 EL3102, CoE directory ................................................................................................................ 85
Fig. 107 Example of commissioning aid for a EL3204 .............................................................................. 86
Fig. 108 Default behaviour of the System Manager .................................................................................. 87
Fig. 109 Default target state in the Slave .................................................................................................. 87
Fig. 110 PLC function blocks .................................................................................................................... 88
Fig. 111 Illegally exceeding the E-Bus current ......................................................................................... 89
Fig. 112 Warning message for exceeding E-Bus current ......................................................................... 89
Fig. 113 Publisher/Subscriber model......................................................................................................... 97
Fig. 114 Insertion of a Publisher Box in the TwinCAT configuration.......................................................... 98
Fig. 115 Adding a network variable ........................................................................................................... 99
Fig. 116 Inputs/Outputs of the inserted variables ...................................................................................... 99
Fig. 117 Mapping of the network variable with an output variable of the PLC........................................... 100
Fig. 118 Creation of an RT-Ethernet device .............................................................................................. 101
Fig. 119 Creation of a Subscriber Box (“Box 1”)........................................................................................ 101
Fig. 120 TwinCAT tree with “Box 1” Subscriber Box ................................................................................. 101
Fig. 121 Create network variable with right click ....................................................................................... 102
Fig. 122 Searching for Publisher computer ............................................................................................... 102
Fig. 123 Created in/outputs of the inserted variables ................................................................................ 103
Fig. 124 Time diagram (Online value) of the Quality variables ................................................................. 104
Fig. 125 Time diagram (Online value) of the CycleIndex variables .......................................................... 104
Fig. 126 Interrelationship between quality and delayed network variable ................................................. 106
Fig. 127 Sample for communication via network variables........................................................................ 107
Fig. 128 Data representation e.g. x86 Systems vs. ARM Systems ........................................................... 108
Fig. 129 Publisher RT Ethernet settings .................................................................................................... 109
Fig. 130 Publisher settings - UDP/IP ......................................................................................................... 110
Fig. 131 Publisher variable settings........................................................................................................... 111

EL6601, EL6614 Version: 4.2 161


List of illustrations

Fig. 132 Subscriber settings ...................................................................................................................... 111


Fig. 133 Subscriber variable settings......................................................................................................... 112
Fig. 134 Connection of a network printer................................................................................................... 114
Fig. 135 EL6601 in the configuration ......................................................................................................... 115
Fig. 136 Context Menu Network Environment -> “Properties” ................................................................... 115
Fig. 137 Context Menu “LAN Connection (TwinCAT-LAN-Adapter),” -> “Properties” ............................... 116
Fig. 138 Properties Internet Protocol (TCP/IP) .......................................................................................... 116
Fig. 139 Entry of the IP address of the subnetwork of the network printer ................................................ 117
Fig. 140 Control Panel “Add a Printer” under “Printers and Faxes”........................................................... 117
Fig. 141 Select “Local Printer” radio button .............................................................................................. 118
Fig. 142 Select Connection Type............................................................................................................... 118
Fig. 143 Entry of the IP address and printer name .................................................................................... 119
Fig. 144 Integration of a Service interface with remote desktop-PC.......................................................... 120
Fig. 145 EL6601 in the configuration ......................................................................................................... 121
Fig. 146 Selection of “Security Center” in the View Control Panel Category ............................................ 121
Fig. 147 Choose security settings for Windows Firewall .......................................................................... 122
Fig. 148 At the “Exceptions” Tab activate the “Remote desktop” service.................................................. 123
Fig. 149 Select “Service and Maintenance” from “System” in the View Control Panel.............................. 124
Fig. 150 Check “Allow users to establish a remote desktop connection” .................................................. 125
Fig. 151 Adding remote desktop users ...................................................................................................... 125
Fig. 152 Context Menu Network Environment -> “Properties” ................................................................... 126
Fig. 153 Context Menu “LAN Connection (Ethernet-LAN-Adapter),” -> “Properties”................................. 126
Fig. 154 Properties Internet Protocol (TCP/IP) .......................................................................................... 127
Fig. 155 Entry of the IP address of the subnetwork of the Service-PC...................................................... 127
Fig. 156 Start remote desktop connection ................................................................................................. 128
Fig. 157 Entry of the IP address of the Remote-PC .................................................................................. 128
Fig. 158 Login window of the remote PC via the remote desktop connection ........................................... 129
Fig. 159 Closing the remote desktop connection....................................................................................... 129
Fig. 160 Integration of a lower-level control system .................................................................................. 130
Fig. 161 Select Configuration of network connections .............................................................................. 131
Fig. 162 Select network settings for Ethernet port..................................................................................... 131
Fig. 163 Enter IP address ......................................................................................................................... 132
Fig. 164 EL6601 in the configuration ......................................................................................................... 132
Fig. 165 Select target system .................................................................................................................... 133
Fig. 166 In the “Route Dialog” add the route of the target system ............................................................ 133
Fig. 167 Confirm selection ......................................................................................................................... 134
Fig. 168 Enable FreeRun .......................................................................................................................... 134
Fig. 169 Setting up an EtherCAT-Master-PC as Network Bridge .............................................................. 135
Fig. 170 Configuration of the network PC.................................................................................................. 135
Fig. 171 Checking the configuration with command line command “ipconfig /all” ..................................... 136
Fig. 172 Checking the configuration PC C................................................................................................. 136
Fig. 173 Entry of network parameters........................................................................................................ 137
Fig. 174 Checking the Configuration Bridge PC B..................................................................................... 137
Fig. 175 Setting “IP Routing” in Windows CE ............................................................................................ 138
Fig. 176 Structure HotConnect Group ....................................................................................................... 140
Fig. 177 EK1101 localized with EL6601 ................................................................................................... 141

162 Version: 4.2 EL6601, EL6614


List of illustrations

Fig. 178 EK1101 localized with EL6601 ................................................................................................... 141


Fig. 179 Selection of the target system ..................................................................................................... 141
Fig. 180 Enter target system 172.1.1.1...................................................................................................... 142
Fig. 181 Entry of logon information on target system ................................................................................ 142
Fig. 182 Opening of target system and loading of configuration ............................................................... 143
Fig. 183 Entry of network addresses in the remote system....................................................................... 143
Fig. 184 Device identifier consisting of name EL3204-0000 and revision -0016 ...................................... 147
Fig. 185 Scan the subordinate field by right-clicking on the EtherCAT device .......................................... 148
Fig. 186 Configuration is identical ............................................................................................................. 148
Fig. 187 Change dialog ............................................................................................................................. 148
Fig. 188 EEPROM Update ........................................................................................................................ 149
Fig. 189 Selecting the new ESI.................................................................................................................. 149
Fig. 190 Display of EL3204 firmware version ............................................................................................ 150
Fig. 191 Firmware Update ......................................................................................................................... 151
Fig. 192 FPGA firmware version definition ............................................................................................... 153
Fig. 193 Context menu Properties ............................................................................................................ 153
Fig. 194 Dialog Advanced Settings ........................................................................................................... 154
Fig. 195 Multiple selection and firmware update ...................................................................................... 156
Fig. 196 Selecting the "Restore default parameters" PDO ........................................................................ 157
Fig. 197 Entering a restore value in the Set Value dialog.......................................................................... 157