0% found this document useful (0 votes)
163 views204 pages

El600x El602xen

Beckhoff Documentation EL6000x, EL602x Serial Interface Terminals
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
163 views204 pages

El600x El602xen

Beckhoff Documentation EL6000x, EL602x Serial Interface Terminals
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 204

Documentation

EL600x, EL602x

Serial Interface Terminals

Version: 4.6
Date: 2018-09-24
Table of contents

Table of contents
1 Foreword .................................................................................................................................................... 5
1.1 Overview Serial Interface Terminals.................................................................................................. 5
1.2 Notes on the documentation.............................................................................................................. 5
1.3 Safety instructions ............................................................................................................................. 7
1.4 Documentation Issue Status.............................................................................................................. 8
1.5 Version identification of EtherCAT devices ....................................................................................... 9

2 Product overview..................................................................................................................................... 14
2.1 EL6001, EL6021 .............................................................................................................................. 18
2.1.1 Introduction ......................................................................................................................  18
2.1.2 Technical data .................................................................................................................  19
2.2 EL6002, EL6022 .............................................................................................................................. 20
2.2.1 Introduction ......................................................................................................................  20
2.2.2 Technical data .................................................................................................................  21
2.3 Start up ............................................................................................................................................ 21

3 Basics communication ........................................................................................................................... 22


3.1 EtherCAT basics.............................................................................................................................. 22
3.2 EtherCAT cabling – wire-bound....................................................................................................... 22
3.3 General notes for setting the watchdog ........................................................................................... 23
3.4 EtherCAT State Machine ................................................................................................................. 25
3.5 CoE Interface................................................................................................................................... 27
3.6 Distributed Clock ............................................................................................................................. 32

4 Mounting and Wiring ............................................................................................................................... 33


4.1 Instructions for ESD protection ........................................................................................................ 33
4.2 EL6001, EL6021 .............................................................................................................................. 33
4.2.1 Installation on mounting rails ...........................................................................................  33
4.2.2 Connection.......................................................................................................................  36
4.2.3 Positioning of passive Terminals .....................................................................................  40
4.2.4 LEDs and terminal connector assignments .....................................................................  41
4.3 EL6002, EL6022 .............................................................................................................................. 43
4.3.1 Mounting and demounting - terminals with front unlocking..............................................  43
4.3.2 Recommended mounting rails .........................................................................................  45
4.3.3 LEDs and pin assignment................................................................................................  46
4.4 Positioning of passive Terminals ..................................................................................................... 49
4.5 Installation instructions for enhanced mechanical load capacity ..................................................... 50
4.6 Installation positions ........................................................................................................................ 51
4.7 UL notice ......................................................................................................................................... 53
4.8 ATEX - Special conditions (extended temperature range) .............................................................. 54
4.9 ATEX Documentation ...................................................................................................................... 55

5 Commissioning........................................................................................................................................ 56
5.1 TwinCAT Quick Start ....................................................................................................................... 56
5.1.1 TwinCAT 2 .......................................................................................................................  58
5.1.2 TwinCAT 3 .......................................................................................................................  68
5.2 TwinCAT Development Environment .............................................................................................. 80

EL600x, EL602x Version: 4.6 3


Table of contents

5.2.1 Installation of the TwinCAT real-time driver.....................................................................  80


5.2.2 Notes regarding ESI device description...........................................................................  86
5.2.3 TwinCAT ESI Updater .....................................................................................................  90
5.2.4 Distinction between Online and Offline............................................................................  90
5.2.5 OFFLINE configuration creation ......................................................................................  91
5.2.6 ONLINE configuration creation ........................................................................................  96
5.2.7 EtherCAT subscriber configuration................................................................................  104
5.3 General Notes - EtherCAT Slave Application ................................................................................ 114
5.4 Operating modes and process data .............................................................................................. 122
5.5 Hints regarding TcVirtualComDriver .............................................................................................. 129
5.6 Communication features................................................................................................................ 131
5.7 LIN Master Feature EL6001 .......................................................................................................... 132
5.8 Example programs ........................................................................................................................ 136
5.8.1 Sample program 1 .........................................................................................................  136
5.8.2 Sample program 2 .........................................................................................................  139
5.8.3 Sample program 3 (LIN) ................................................................................................  141

6 Overview of CoE objects EL6001, EL6021 .......................................................................................... 144


6.1 Object description and parameterization ....................................................................................... 144
6.1.1 Objects for commissioning.............................................................................................  144
6.1.2 Standard objects (0x1000-0x1FFF) ...............................................................................  146
6.1.3 Profile-specific objects (0x6000-0xFFFF) [from hardware version 03] ..........................  162
6.2 Control and status word................................................................................................................. 165

7 Overview CoE objects EL6002, EL6022............................................................................................... 168


7.1 Object description and parameterization ....................................................................................... 168
7.1.1 Objects for commissioning.............................................................................................  168
7.1.2 Standard objects (0x1000-0x1FFF) ...............................................................................  169
7.1.3 Profile-specific objects (0x6000-0xFFFF) [from hardware version 03] ..........................  181
7.2 Control and status data ................................................................................................................. 184

8 Appendix ................................................................................................................................................ 186
8.1 EtherCAT AL Status Codes ........................................................................................................... 186
8.2 Firmware compatibility ................................................................................................................... 186
8.3 Firmware Update EL/ES/EM/EPxxxx ............................................................................................ 187
8.3.1 Device description ESI file/XML.....................................................................................  188
8.3.2 Firmware explanation ....................................................................................................  191
8.3.3 Updating controller firmware *.efw.................................................................................  192
8.3.4 FPGA firmware *.rbf.......................................................................................................  193
8.3.5 Simultaneous updating of several EtherCAT devices....................................................  197
8.4 Restoring the delivery state ........................................................................................................... 198
8.5 Support and Service ...................................................................................................................... 199

4 Version: 4.6 EL600x, EL602x


Foreword

1 Foreword

1.1 Overview Serial Interface Terminals


EL6001 [} 18] (1 channel Serial Interface Terminal, RS232C)
EL6021 [} 18] (1 channel Serial Interface Terminal, RS422/RS485)
EL6002 [} 20] (2 channel Serial Interface Terminal, RS232C)
EL6022 [} 20] (2 channel Serial Interface Terminal, RS422/RS485)

1.2 Notes on the documentation


Intended audience

This description is only intended for the use of trained specialists in control and automation engineering who
are familiar with the applicable national standards.
It is essential that the documentation and the following notes and explanations are followed when installing
and commissioning these components.
It is the duty of the technical personnel to use the documentation published at the respective time of each
installation and commissioning.

The responsible staff must ensure that the application or use of the products described satisfy all the
requirements for safety, including all the relevant laws, regulations, guidelines and standards.

Disclaimer

The documentation has been prepared with care. The products described are, however, constantly under
development.

We reserve the right to revise and change the documentation at any time and without prior announcement.

No claims for the modification of products that have already been supplied may be made on the basis of the
data, diagrams and descriptions in this documentation.

Trademarks

Beckhoff®, TwinCAT®, EtherCAT®, EtherCAT P®, Safety over EtherCAT®, TwinSAFE®, XFC® and XTS® are
registered trademarks of and licensed by Beckhoff Automation GmbH.
Other designations used in this publication may be trademarks whose use by third parties for their own
purposes could violate the rights of the owners.

Patent Pending

The EtherCAT Technology is covered, including but not limited to the following patent applications and
patents: EP1590927, EP1789857, DE102004044764, DE102007017835 with corresponding applications or
registrations in various other countries.

The TwinCAT Technology is covered, including but not limited to the following patent applications and
patents: EP0851348, US6167425 with corresponding applications or registrations in various other countries.

EtherCAT® is registered trademark and patented technology, licensed by Beckhoff Automation GmbH,
Germany

EL600x, EL602x Version: 4.6 5


Foreword

Copyright

© Beckhoff Automation GmbH & Co. KG, Germany.


The reproduction, distribution and utilization of this document as well as the communication of its contents to
others without express authorization are prohibited.
Offenders will be held liable for the payment of damages. All rights reserved in the event of the grant of a
patent, utility model or design.

6 Version: 4.6 EL600x, EL602x


Foreword

1.3 Safety instructions


Safety regulations

Please note the following safety instructions and explanations!


Product-specific safety instructions can be found on following pages or in the areas mounting, wiring,
commissioning etc.

Exclusion of liability

All the components are supplied in particular hardware and software configurations appropriate for the
application. Modifications to hardware or software configurations other than those described in the
documentation are not permitted, and nullify the liability of Beckhoff Automation GmbH & Co. KG.

Personnel qualification

This description is only intended for trained specialists in control, automation and drive engineering who are
familiar with the applicable national standards.

Description of instructions

In this documentation the following instructions are used.


These instructions must be read carefully and followed without fail!

DANGER
Serious risk of injury!
Failure to follow this safety instruction directly endangers the life and health of persons.

WARNING
Risk of injury!
Failure to follow this safety instruction endangers the life and health of persons.

CAUTION
Personal injuries!
Failure to follow this safety instruction can lead to injuries to persons.

NOTE
Damage to environment/equipment or data loss
Failure to follow this instruction can lead to environmental damage, equipment damage or data loss.

Tip or pointer
This symbol indicates information that contributes to better understanding.

EL600x, EL602x Version: 4.6 7


Foreword

1.4 Documentation Issue Status


Version Comment
4.6 • Correction RS232 level
• Update chapter "Technical data"
• Update structure
• Update revision status
4.5 • Update chapter "Commissioning"
• Update revision status
4.4 • Update chapter "Technical data"
• Update chapter "Operating modes and process data"
• Update chapter " Communication features"
• Update structure
• Update revision status
4.3 • Update chapter "Technical data"
• Addenda chapter "Instructions for ESD protection"
• Chapter "ATEX - Special conditions" replaced with chapter "ATEX - Special conditions (extended temperature
range)"
• Addenda chapter "TwinCAT Quickstart"
• Update revision status
4.2 • Update in section ”LEDs and terminal connector assignments”
4.1 • Addenda in section “LEDs and pin assignment”
4.0 • Migration and revision
• Section "Mounting and demounting" in section "EL6002, EL6022" in "Mounting and wiring" complemented with
"Front unlocking"
• Section "Installation instructions for enhanced mechanical load capacity" moved from subsection "EL6001,
EL6021" to section "Mounting and wiring"
• Section "Installation positions" removed from subsection "EL6001, EL6021" (since already present in higher-level
section)
• Section "Configuration with the TwinCAT System Manager" moved from section "Commissioning" to subsection
"TwinCAT 2.1x"
• Section "LIN Feature EL6001" moved to section "Commissioning"
• Sections "Sample program 1" and "Sample program 2" consolidated into new section "Sample programs"; new
section "Sample programs" integrated in section "Commissioning“
• Section "Sample program 3 (LIN)" added to section "Sample programs"
3.8 • "Technical data" section updated
• "Installation instructions for enhanced mechanical load capacity" section supplemented
• Structural update
• Revision version updated
3.7 • Update LED description
• Update revision status
3.6 • Update revision status
• Update structure
3.5 • Update chapter "Technical data"
• Update chapter "Object description and parameterization"
• Update chapter "Communication features"
• Update chapter "Technology"
• Update chapter "Process data"
• Update structure

8 Version: 4.6 EL600x, EL602x


Foreword

Version Comment
3.4 • Update chapter "Technology"
3.3 • Update Technical data
3.2 • Update Technical data
3.1 • Addenda of notes and description of command mode
3.0 • Update chapter "Object description"
2.9 • Addenda chapter "Communication features and TcVirtualComDriver"
2.8 • Update Technical data
2.7 • Update Technical data
2.6 • Update chapter "Technology" and "Process data"
2.5 • Update chapter "Technology"
2.4 • Object description and Technical notes added
2.3 • Firmware compatibility notice, Technical notes added
2.2 • Addenda
2.1 • Addenda
2.0 • First public issue
0.3 • Addenda
0.2 • Corrections and addenda
0.1 • Preliminary documentation for EL60xx

1.5 Version identification of EtherCAT devices


Designation

A Beckhoff EtherCAT device has a 14-digit designation, made up of


• family key
• type
• version
• revision
Example Family Type Version Revision
EL3314-0000-0016 EL terminal 3314 (4-channel thermocouple 0000 (basic type) 0016
(12 mm, non- terminal)
pluggable connection
level)
ES3602-0010-0017 ES terminal 3602 (2-channel voltage 0010 (high- 0017
(12 mm, pluggable measurement) precision version)
connection level)
CU2008-0000-0000 CU device 2008 (8-port fast ethernet switch) 0000 (basic type) 0000

Notes
• The elements mentioned above result in the technical designation. EL3314-0000-0016 is used in the
example below.
• EL3314-0000 is the order identifier, in the case of “-0000” usually abbreviated to EL3314. “-0016” is the
EtherCAT revision.
• The order identifier is made up of
- family key (EL, EP, CU, ES, KL, CX, etc.)
- type (3314)
- version (-0000)
• The revision -0016 shows the technical progress, such as the extension of features with regard to the
EtherCAT communication, and is managed by Beckhoff.
In principle, a device with a higher revision can replace a device with a lower revision, unless specified
otherwise, e.g. in the documentation.
Associated and synonymous with each revision there is usually a description (ESI, EtherCAT Slave

EL600x, EL602x Version: 4.6 9


Foreword

Information) in the form of an XML file, which is available for download from the Beckhoff web site.
From 2014/01 the revision is shown on the outside of the IP20 terminals, see Fig. “EL5021 EL terminal,
standard IP20 IO device with batch number and revision ID (since 2014/01)”.
• The type, version and revision are read as decimal numbers, even if they are technically saved in
hexadecimal.

Identification number

Beckhoff EtherCAT devices from the different lines have different kinds of identification numbers:

Production lot/batch number/serial number/date code/D number

The serial number for Beckhoff IO devices is usually the 8-digit number printed on the device or on a sticker.
The serial number indicates the configuration in delivery state and therefore refers to a whole production
batch, without distinguishing the individual modules of a batch.

Structure of the serial number: KK YY FF HH

KK - week of production (CW, calendar week)


YY - year of production
FF - firmware version
HH - hardware version

Example with
Ser. no.: 12063A02:    12 - production week 12 06 - production year 2006 3A - firmware version 3A 02 -
hardware version 02

Exceptions can occur in the IP67 area, where the following syntax can be used (see respective device
documentation):

Syntax: D ww yy x y z u

D - prefix designation
ww - calendar week
yy - year
x - firmware version of the bus PCB
y - hardware version of the bus PCB
z - firmware version of the I/O PCB
u - hardware version of the I/O PCB

Example: D.22081501 calendar week 22 of the year 2008 firmware version of bus PCB: 1 hardware version
of bus PCB: 5 firmware version of I/O PCB: 0 (no firmware necessary for this PCB) hardware version of I/O
PCB: 1

Unique serial number/ID, ID number

In addition, in some series each individual module has its own unique serial number.

See also the further documentation in the area


• IP67: EtherCAT Box
• Safety: TwinSafe
• Terminals with factory calibration certificate and other measuring terminals

10 Version: 4.6 EL600x, EL602x


Foreword

Examples of markings

Fig. 1: EL5021 EL terminal, standard IP20 IO device with serial/ batch number and revision ID (since
2014/01)

Fig. 2: EK1100 EtherCAT coupler, standard IP20 IO device with serial/ batch number

Fig. 3: CU2016 switch with serial/ batch number

EL600x, EL602x Version: 4.6 11


Foreword

Fig. 4: EL3202-0020 with serial/ batch number 26131006 and unique ID-number 204418

Fig. 5: EP1258-00001 IP67 EtherCAT Box with batch number/ date code 22090101 and unique serial
number 158102

Fig. 6: EP1908-0002 IP67 EtherCAT Safety Box with batch number/ date code 071201FF and unique serial
number 00346070

Fig. 7: EL2904 IP20 safety terminal with batch number/ date code 50110302 and unique serial number
00331701

12 Version: 4.6 EL600x, EL602x


Foreword

Fig. 8: ELM3604-0002 terminal with unique ID number (QR code) 100001051 and serial/ batch number
44160201

EL600x, EL602x Version: 4.6 13


Product overview

2 Product overview
Technology

The EL600x and EL602x serial interface terminals enable the connection of devices with an RS232 (or
RS485 / RS422) interface. In the case of the EL600x, the data is exchanged with the controller in full duplex
mode; in the case of the EL602x, half duplex mode is additionally possible. The terminal has one receive
buffer an one transmit buffer per channel, see technical data. Data transfer between the terminal and the
controller takes place via a handshake.

The factory setting of the terminals is:


• 9600 baud
• 8N1: 8 data bits, 1 stop bit, no parity
• in the EL600x the RTS/CTS control is active
• the EL602x operates in full duplex mode with deactivated point-to-point connection.

Basic principles

During transfer of several bytes of data, the data (x bytes or 8*x bits in total) are sent in individual telegrams
containing 7 or 8 bits, based on the coding specification (e.g. 7E2 or 8N1). A telegram consists of:
• Start bit
• Data bits (7 or 8, starting with the LSB [least significant bit])
• Optional: parity bit
◦ "E" EVEN: The parity bit is set by the sender such that the parity is even
◦ "O" ODD: The parity bit is set by the sender such that the parity is odd
◦ "N" NOT: no parity bit
◦ "M" MARK: The parity bit is set to 1 by the sender
◦ "S" SPACE: The parity bit is set to 0 by the sender
• Stop bit (1 or 2)

Accordingly, the coding specification 8N1 means: 8 data bits, no parity bit, 1 stop bit.

If 7-bit coding is selected, of each data byte that is transferred from the PLC to the terminal via the cyclic
process data, only the lower 7 bits are sent. In other words, if 10 bytes of data (consisting of 8 bits) are sent
to the EL60xx, 10 telegrams of 7 bits each are sent.

If 9-bit coding is selected, the 16-bit process data interface must be used. The terminal then expects the 9
useful bits in the lower 9 bits of the 16-bit word.

Frequency

The frequency of the data transfer must be known in the sender and receiver and match within a few
percent, in order to ensure that the receiver can correctly detect any changes in level on the line.

Handshake

An additional handshake between the sender and the receiver can be used so that the receiver can indicate
that it is ready to receive. The EL60xx supports two types of handshake:
• via special RTS/CTS data cables
◦ This features must be activated in the CoE.
◦ Only possible with EL6001/EL6002.
• via special data telegrams
◦ This features must be activated in the CoE.

14 Version: 4.6 EL600x, EL602x


Product overview

Level interfaces

The EL6001/6002 devices operate at an RS232 level with reference to GND, the EL6021/6022 devices with
a differential RS485/422 level.

Fig. 9: Level interfaces RS232, RS485/422

Termination and topology

The serial RS422 and RS485 communication technologies operate with voltage levels on a 2-wire line.
Reflections at high-resistance line ends can lead to signal distortion. For this reason termination resistors are
required at the receiver. For RS422/485 these are 120 Ω resistors, which together with the line resistance
result in a voltage drop over the transmission link.

Permitted cable length


The line resistance together with the termination resistor results in an overall voltage drop over the
transmission link. An unacceptably high number of termination resistors would result in excessive
attenuation of the signal.
The system design should ensure that the voltage does not drop below 200 mV at the receiver (see
Fig. ), which is the minimum voltage required.

In RS422 mode each line must be terminated with 120 Ω at the receiver.

Fig. 10: RS422 termination

In RS485 mode with several devices, termination resistors are only used at the two end devices.

EL600x, EL602x Version: 4.6 15


Product overview

Fig. 11: RS485 termination

The background is the different design of RS422/EIA-422 and RS485/EIA-485:


• RS422: 1 Rx → Tx n (maximum 10 receivers)
• RS485: n Rx → Tx m (maximum 32/128 devices, depending on the resulting bus loading)

Components for RS485 usually have a higher input impedance, resulting in lower bus load.

Termination with EL602x and BIAS resistors


The EL602x devices do not have integrated termination resistors, in order to enable operation in
bus mode. Any termination that may be required must be connected outside the terminal.
The EL602x devices feature integrated bias resistors < 1 kOhm, which bring the bus lines to defined
levels, even if the line is disconnected.
If several EL602x devices are connected in a bus, the parallel bias resistors may hamper the data
communication. In this case the EL6021-0021, which has significantly higher bias resistors, should
be used as an intermediate device.

Topology

The termination and the bias resistors generate a load on the bus. However, they are essential for
unambiguous bus levels and therefore have to be positioned with diligence. Ideally the RS422/485 bus
should be configured as a daisy chain or a simple chain, see Fig. [} 17] The following topologies may be
problematic:
• Star topologies: each end point should ideally be terminated, but this can lead to excessive bus loading
and ambiguous signal levels. Other potential issues are reflections and runtime variations.
• Intermeshed topologies: no clear end points, which means reflections and circulating currents are
possible.

Shielding/shield

NOTE
Do not use functional earth for discharge of residual currents or potential differences!
The EL60xx units offer a shielded connection for discharging EMC interference via the cable shield (FE,
functional earth). The shield must not be misused for discharging residual currents or potential differences.

The EL60xx units offer a shielded connection for discharging EMC interference via the cable shield (FE,
functional earth). The shield must not be misused for discharging residual currents or potential differences.

16 Version: 4.6 EL600x, EL602x


Product overview

Fig. 12: EL60xx shield connection

In the 2-channel versions the D-Sub 9 shield is connected with the mounting rail via a high-resistance RC
combination.

EL600x, EL602x Version: 4.6 17


Product overview

2.1 EL6001, EL6021

2.1.1 Introduction

Serial Interface Terminal (RS232C/RS422/RS485), 1 channel

The EL6001 and EL6021 serial interfaces enable the connection of devices with RS-232 or RS422/RS485
interface. The EL6001 operates in conformity with the CCITT V.28/DIN 66 259-1 standards.
The device connected to the EL6001 EtherCAT Terminal communicates with the automation device via the
coupler. The active communication channel operates independently of the higher-level bus system in full
duplex mode or selectable half duplex mode (EL6021) at up to 115.2 kbaud.
The RS232 interface guarantees high immunity to interference through electrically isolated signals, which is
additionally guaranteed for the EL6021 through differential signal transmission.

In conjunction with the TwinCAT Virtual Serial COM Driver (see TwinCAT Supplements – Communication)
the EL6001/EL6021 can be used as a normal Windows COM interface.

Quick links
• EtherCAT basics [} 22]
• Technology Serial Interface Terminals [} 14]
• Commissioning [} 56]
• Process data, general notes [} 122]
• CoE object description and parameterization EL60x1 [} 144]
• Control and status data EL60x1 [} 165]

18 Version: 4.6 EL600x, EL602x


Product overview

2.1.2 Technical data


Technical data EL6001 EL6021
Data transfer channels TxD and RxD, full duplex TxD and RxD, full/half duplex
Data transfer rate 2400...115200 baud, 2400...115200 baud,
default: 9600 baud, 8 data bits, default: 9600 baud, 8 data bits,
no parity, 1 stop bit no parity, 1 stop bit
from firmware 07 [} 186]:
also 12000 baud and
14400 baud
from firmware 11 [} 186]:
any integer baud rate 1000…
115200 Baud
Data buffer 864 byte receive buffer, 128 byte transmit buffer
EL6001 from FW08: 250 byte transmit buffer
Bit transfer - with differential signal
Level interface RS232 RS485/422
Bit distortion <3% -
Cable length max. 15 m max. 1000 m (Twisted Pair)
Line impedance - 120 Ω
Providing external supply - -
Diagnosis Status LEDs
Power supply via the E-Bus
Current consumption via E-bus typ. 120 mA typ. 170 mA
(in case of short circuit: typ.
250 mA)
Electrical isolation 500 V 500 V
(E-bus/RS232C) (E-bus/RS422, E-bus/RS485)
Bit width in process image 1 x 8 bit Control/Status, Inputs/Outputs: 3 x 8 bit user data or
1 x 8 bit Control/Status, Inputs/Outputs: 5 x 8 bit user data or
1 x 16 bit Control/Status, Inputs/Outputs: 22 x 8 bit user data
(configurable)
Configuration no address setting required
configuration via TwinCAT System Manager
Weight approx. 55 g
Permissible ambient temperature range -25°C ... +60°C (extended temperature range)
during operation
Permissible ambient temperature range -40°C ... +85°C
during storage
Permissible relative humidity 95%, no condensation
Dimensions (W x H x D) approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
Mounting on 35 mm mounting rail conforms to EN 60715
Vibration/shock resistance conforms to EN 60068-2-6 / EN 60068-2-27,
see also installation instructions [} 50] for enhanced mechanical
load capacity
EMC immunity/emission conforms to EN 61000-6-2 / EN 61000-6-4
Protection class IP20
Installation position variable
Approval CE CE
ATEX [} 54] ATEX [} 54]
cULus [} 53] cULus [} 53]
IECEx

EL600x, EL602x Version: 4.6 19


Product overview

2.2 EL6002, EL6022

2.2.1 Introduction

Serial Interface Terminal (RS232C/RS422/RS485), 2 channel

The EL6002 and EL6022 serial interfaces enable the connection of devices with two RS232 or two RS422/
RS485 interfaces each with one D-Sub connector (9 pin). The interfaces are electrically isolated from each
other and from the EtherCAT.
The devices connected to the EL6002/EL6022 EtherCAT Terminals communicate with the automation
device via the Coupler. The active communication channel operates independently of the higher-level
EtherCAT system in full duplex mode with 300 baud up to 115.2 kbaud.
The RS232/RS422/RS485 interfaces guarantee high interference immunity through electrically isolated
signals. The EL6022 can provide 2 x 5 V/20 mA from the E-bus supply (electrically isolated, short-circuit-
proof) as supply for external devices.

In conjunction with the TwinCAT Virtual Serial COM Driver, the EL60xx can be used as a normal Windows
COM interface.

Quick links
• EtherCAT basics [} 22]
• Technology Serial Interface Terminals [} 14]
• Commissioning [} 56]
• Process data, general notes [} 122]
• CoE object description and parameterization EL60x1 [} 168]
• Control and status data EL60x1 [} 184]

20 Version: 4.6 EL600x, EL602x


Product overview

2.2.2 Technical data


Technical data EL6002 EL6022
Data transfer channels 2, TxD and RxD, full duplex 2, TXD and RXD, full/half duplex
Connection 2 x D-sub connector (DE9), 9-pin 2 x D-sub connector (DE9), 9-pin
Data transfer rate 300...115200 baud
default: 9600 baud, 8 data bits, no parity, 1 stop bit
Data buffer 864 byte receive buffer, 128 byte transmit buffer per channel
Level interface RS232 RS485/422
Cable length max. 15 m max. 1000 m (Twisted Pair)
Providing external supply - 2x typ. 5V (± 20%),
from E-bus supply (electrically
isolated), max. 20 mA,
short-circuit-proof
Diagnosis Status LEDs
Power supply via the E-Bus
Current consumption via E-bus typ. 170 mA typ. 250 mA
(in case of short circuit: typ.
250 mA)
Electrical isolation 500 V 500 V
(E-bus/RS232C) (E-bus/RS422, E-bus/RS485)
Bit width in process image 1 x 16 bit Control/Status, Inputs/Outputs: 22 x 8 bit user data
Configuration no address setting required
configuration via TwinCAT System Manager
Permissible ambient temperature -25°C ... +60°C (extended temperature range)
range during operation
Permissible ambient temperature -40°C ... +85°C
range during storage
Permissible relative humidity 95%, no condensation
Weight approx. 70 g
Dimensions (W x H x D) approx. 26 mm x 100 mm x 52 mm (width aligned: 23 mm)
Mounting [} 43] on 35 mm mounting rail conforms to EN 60715
Vibration/shock resistance conforms to EN 60068-2-6 / EN 60068-2-27

EMC immunity/emission conforms to EN 61000-6-2 / EN 61000-6-4


Protection class IP20
Installation position variable
Approval CE
ATEX [} 54]
cULus [} 53]

2.3 Start up
Start

For commissioning:
• mount the EL600x / EL602x as described in the chapter Mounting and wiring [} 33]
• configure the EL600x / EL602x in TwinCAT as described in the chapter Commissioning [} 56]

EL600x, EL602x Version: 4.6 21


Basics communication

3 Basics communication

3.1 EtherCAT basics


Please refer to the chapter EtherCAT System Documentation for the EtherCAT fieldbus basics.

3.2 EtherCAT cabling – wire-bound


The cable length between two EtherCAT devices must not exceed 100 m. This results from the FastEthernet
technology, which, above all for reasons of signal attenuation over the length of the cable, allows a maximum
link length of 5 + 90 + 5 m if cables with appropriate properties are used. See also the Design
recommendations for the infrastructure for EtherCAT/Ethernet.

Cables and connectors

For connecting EtherCAT devices only Ethernet connections (cables + plugs) that meet the requirements of
at least category 5 (CAt5) according to EN 50173 or ISO/IEC 11801 should be used. EtherCAT uses 4 wires
for signal transfer.

EtherCAT uses RJ45 plug connectors, for example. The pin assignment is compatible with the Ethernet
standard (ISO/IEC 8802-3).

Pin Color of conductor Signal Description


1 yellow TD + Transmission Data +
2 orange TD - Transmission Data -
3 white RD + Receiver Data +
6 blue RD - Receiver Data -

Due to automatic cable detection (auto-crossing) symmetric (1:1) or cross-over cables can be used between
EtherCAT devices from Beckhoff.

Recommended cables
Suitable cables for the connection of EtherCAT devices can be found on the Beckhoff website!

E-Bus supply

A bus coupler can supply the EL terminals added to it with the E-bus system voltage of 5 V; a coupler is
thereby loadable up to 2 A as a rule (see details in respective device documentation).
Information on how much current each EL terminal requires from the E-bus supply is available online and in
the catalogue. If the added terminals require more current than the coupler can supply, then power feed
terminals (e.g. EL9410) must be inserted at appropriate places in the terminal strand.

The pre-calculated theoretical maximum E-Bus current is displayed in the TwinCAT System Manager. A
shortfall is marked by a negative total amount and an exclamation mark; a power feed terminal is to be
placed before such a position.

22 Version: 4.6 EL600x, EL602x


Basics communication

Fig. 13: System manager current calculation

NOTE
Malfunction possible!
The same ground potential must be used for the E-Bus supply of all EtherCAT terminals in a terminal block!

3.3 General notes for setting the watchdog


ELxxxx terminals are equipped with a safety feature (watchdog) that switches off the outputs after a
specifiable time e.g. in the event of an interruption of the process data traffic, depending on the device and
settings, e.g. in OFF state.

The EtherCAT slave controller (ESC) in the EL2xxx terminals features 2 watchdogs:
• SM watchdog (default: 100 ms)
• PDI watchdog (default: 100 ms)

SM watchdog (SyncManager Watchdog)

The SyncManager watchdog is reset after each successful EtherCAT process data communication with the
terminal. If no EtherCAT process data communication takes place with the terminal for longer than the set
and activated SM watchdog time, e.g. in the event of a line interruption, the watchdog is triggered and the
outputs are set to FALSE. The OP state of the terminal is unaffected. The watchdog is only reset after a
successful EtherCAT process data access. Set the monitoring time as described below.

The SyncManager watchdog monitors correct and timely process data communication with the ESC from the
EtherCAT side.

PDI watchdog (Process Data Watchdog)

If no PDI communication with the EtherCAT slave controller (ESC) takes place for longer than the set and
activated PDI watchdog time, this watchdog is triggered.
PDI (Process Data Interface) is the internal interface between the ESC and local processors in the EtherCAT
slave, for example. The PDI watchdog can be used to monitor this communication for failure.

The PDI watchdog monitors correct and timely process data communication with the ESC from the
application side.

The settings of the SM- and PDI-watchdog must be done for each slave separately in the TwinCAT System
Manager.

EL600x, EL602x Version: 4.6 23


Basics communication

Fig. 14: EtherCAT tab -> Advanced Settings -> Behavior -> Watchdog

Notes:
• the multiplier is valid for both watchdogs.
• each watchdog has its own timer setting, the outcome of this in summary with the multiplier is a
resulting time.
• Important: the multiplier/timer setting is only loaded into the slave at the start up, if the checkbox is
activated.
If the checkbox is not activated, nothing is downloaded and the ESC settings remain unchanged.

Multiplier

Multiplier

Both watchdogs receive their pulses from the local terminal cycle, divided by the watchdog multiplier:

1/25 MHz * (watchdog multiplier + 2) = 100 µs (for default setting of 2498 for the multiplier)

The standard setting of 1000 for the SM watchdog corresponds to a release time of 100 ms.

The value in multiplier + 2 corresponds to the number of basic 40 ns ticks representing a watchdog tick.
The multiplier can be modified in order to adjust the watchdog time over a larger range.

24 Version: 4.6 EL600x, EL602x


Basics communication

Example "Set SM watchdog"

This checkbox enables manual setting of the watchdog times. If the outputs are set and the EtherCAT
communication is interrupted, the SM watchdog is triggered after the set time and the outputs are erased.
This setting can be used for adapting a terminal to a slower EtherCAT master or long cycle times. The
default SM watchdog setting is 100 ms. The setting range is 0..65535. Together with a multiplier with a range
of 1..65535 this covers a watchdog period between 0..~170 seconds.

Calculation

Multiplier = 2498 → watchdog base time = 1 / 25 MHz * (2498 + 2) = 0.0001 seconds = 100 µs


SM watchdog = 10000 → 10000 * 100 µs = 1 second watchdog monitoring time

CAUTION
Undefined state possible!
The function for switching off of the SM watchdog via SM watchdog = 0 is only implemented in terminals
from version -0016. In previous versions this operating mode should not be used.

CAUTION
Damage of devices and undefined state possible!
If the SM watchdog is activated and a value of 0 is entered the watchdog switches off completely. This is
the deactivation of the watchdog! Set outputs are NOT set in a safe state, if the communication is inter-
rupted.

3.4 EtherCAT State Machine


The state of the EtherCAT slave is controlled via the EtherCAT State Machine (ESM). Depending upon the
state, different functions are accessible or executable in the EtherCAT slave. Specific commands must be
sent by the EtherCAT master to the device in each state, particularly during the bootup of the slave.

A distinction is made between the following states:


• Init
• Pre-Operational
• Safe-Operational and
• Operational
• Boot

The regular state of each EtherCAT slave after bootup is the OP state.

EL600x, EL602x Version: 4.6 25


Basics communication

Fig. 15: States of the EtherCAT State Machine

Init

After switch-on the EtherCAT slave in the Init state. No mailbox or process data communication is possible.
The EtherCAT master initializes sync manager channels 0 and 1 for mailbox communication.

Pre-Operational (Pre-Op)

During the transition between Init and Pre-Op the EtherCAT slave checks whether the mailbox was initialized
correctly.

In Pre-Op state mailbox communication is possible, but not process data communication. The EtherCAT
master initializes the sync manager channels for process data (from sync manager channel 2), the FMMU
channels and, if the slave supports configurable mapping, PDO mapping or the sync manager PDO
assignment. In this state the settings for the process data transfer and perhaps terminal-specific parameters
that may differ from the default settings are also transferred.

Safe-Operational (Safe-Op)

During transition between Pre-Op and Safe-Op the EtherCAT slave checks whether the sync manager
channels for process data communication and, if required, the distributed clocks settings are correct. Before
it acknowledges the change of state, the EtherCAT slave copies current input data into the associated DP-
RAM areas of the EtherCAT slave controller (ECSC).

In Safe-Op state mailbox and process data communication is possible, although the slave keeps its outputs
in a safe state, while the input data are updated cyclically.

Outputs in SAFEOP state


The default set watchdog [} 23] monitoring sets the outputs of the module in a safe state - depend-
ing on the settings in SAFEOP and OP - e.g. in OFF state. If this is prevented by deactivation of the
watchdog monitoring in the module, the outputs can be switched or set also in the SAFEOP state.

Operational (Op)

Before the EtherCAT master switches the EtherCAT slave from Safe-Op to Op it must transfer valid output
data.

In the Op state the slave copies the output data of the masters to its outputs. Process data and mailbox
communication is possible.

26 Version: 4.6 EL600x, EL602x


Basics communication

Boot

In the Boot state the slave firmware can be updated. The Boot state can only be reached via the Init state.

In the Boot state mailbox communication via the file access over EtherCAT (FoE) protocol is possible, but no
other mailbox communication and no process data communication.

3.5 CoE Interface


General description

The CoE interface (CANopen over EtherCAT) is used for parameter management of EtherCAT devices.
EtherCAT slaves or the EtherCAT master manage fixed (read only) or variable parameters which they
require for operation, diagnostics or commissioning.

CoE parameters are arranged in a table hierarchy. In principle, the user has read access via the fieldbus.
The EtherCAT master (TwinCAT System Manager) can access the local CoE lists of the slaves via
EtherCAT in read or write mode, depending on the attributes.

Different CoE parameter types are possible, including string (text), integer numbers, Boolean values or larger
byte fields. They can be used to describe a wide range of features. Examples of such parameters include
manufacturer ID, serial number, process data settings, device name, calibration values for analog
measurement or passwords.

The order is specified in 2 levels via hexadecimal numbering: (main)index, followed by subindex. The value
ranges are
• Index: 0x0000 …0xFFFF (0...65535dez)
• SubIndex: 0x00…0xFF (0...255dez)

A parameter localized in this way is normally written as 0x8010:07, with preceding "x" to identify the
hexadecimal numerical range and a colon between index and subindex.

The relevant ranges for EtherCAT fieldbus users are:


• 0x1000: This is where fixed identity information for the device is stored, including name, manufacturer,
serial number etc., plus information about the current and available process data configurations.
• 0x8000: This is where the operational and functional parameters for all channels are stored, such as
filter settings or output frequency.

Other important ranges are:


• 0x4000: In some EtherCAT devices the channel parameters are stored here (as an alternative to the
0x8000 range).
• 0x6000: Input PDOs ("input" from the perspective of the EtherCAT master)
• 0x7000: Output PDOs ("output" from the perspective of the EtherCAT master)

Availability
Not every EtherCAT device must have a CoE list. Simple I/O modules without dedicated processor
usually have no variable parameters and therefore no CoE list.

If a device has a CoE list, it is shown in the TwinCAT System Manager as a separate tab with a listing of the
elements:

EL600x, EL602x Version: 4.6 27


Basics communication

Fig. 16: "CoE Online " tab

The figure above shows the CoE objects available in device "EL2502", ranging from 0x1000 to 0x1600. The
subindices for 0x1018 are expanded.

Data management and function "NoCoeStorage"

Some parameters, particularly the setting parameters of the slave, are configurable and writeable. This can
be done in write or read mode
• via the System Manager (Fig. "CoE Online " tab) by clicking
This is useful for commissioning of the system/slaves. Click on the row of the index to be
parameterised and enter a value in the "SetValue" dialog.
• from the control system/PLC via ADS, e.g. through blocks from the TcEtherCAT.lib library
This is recommended for modifications while the system is running or if no System Manager or
operating staff are available.

Data management
If slave CoE parameters are modified online, Beckhoff devices store any changes in a fail-safe
manner in the EEPROM, i.e. the modified CoE parameters are still available after a restart.
The situation may be different with other manufacturers.

An EEPROM is subject to a limited lifetime with respect to write operations. From typically 100,000
write operations onwards it can no longer be guaranteed that new (changed) data are reliably saved
or are still readable. This is irrelevant for normal commissioning. However, if CoE parameters are
continuously changed via ADS at machine runtime, it is quite possible for the lifetime limit to be
reached. Support for the NoCoeStorage function, which suppresses the saving of changed CoE val-
ues, depends on the firmware version.
Please refer to the technical data in this documentation as to whether this applies to the respective
device.
• If the function is supported: the function is activated by entering the code word 0x12345678 once
in CoE 0xF008 and remains active as long as the code word is not changed. After switching the
device on it is then inactive. Changed CoE values are not saved in the EEPROM and can thus
be changed any number of times.
• Function is not supported: continuous changing of CoE values is not permissible in view of the
lifetime limit.

28 Version: 4.6 EL600x, EL602x


Basics communication

Startup list
Changes in the local CoE list of the terminal are lost if the terminal is replaced. If a terminal is re-
placed with a new Beckhoff terminal, it will have the default settings. It is therefore advisable to link
all changes in the CoE list of an EtherCAT slave with the Startup list of the slave, which is pro-
cessed whenever the EtherCAT fieldbus is started. In this way a replacement EtherCAT slave can
automatically be parameterized with the specifications of the user.
If EtherCAT slaves are used which are unable to store local CoE values permanently, the Startup
list must be used.

Recommended approach for manual modification of CoE parameters


• Make the required change in the System Manager
The values are stored locally in the EtherCAT slave
• If the value is to be stored permanently, enter it in the Startup list.
The order of the Startup entries is usually irrelevant.

Fig. 17: Startup list in the TwinCAT System Manager

The Startup list may already contain values that were configured by the System Manager based on the ESI
specifications. Additional application-specific entries can be created.

Online/offline list

While working with the TwinCAT System Manager, a distinction has to be made whether the EtherCAT
device is "available", i.e. switched on and linked via EtherCAT and therefore online, or whether a
configuration is created offline without connected slaves.

In both cases a CoE list as shown in Fig. “’CoE online’ tab” is displayed. The connectivity is shown as offline/
online.
• If the slave is offline
◦ The offline list from the ESI file is displayed. In this case modifications are not meaningful or
possible.
◦ The configured status is shown under Identity.
◦ No firmware or hardware version is displayed, since these are features of the physical device.
◦ Offline is shown in red.

EL600x, EL602x Version: 4.6 29


Basics communication

Fig. 18: Offline list

• If the slave is online


◦ The actual current slave list is read. This may take several seconds, depending on the size and
cycle time.
◦ The actual identity is displayed
◦ The firmware and hardware version of the equipment according to the electronic information is
displayed
◦ Online is shown in green.

Fig. 19: Online list

30 Version: 4.6 EL600x, EL602x


Basics communication

Channel-based order

The CoE list is available in EtherCAT devices that usually feature several functionally equivalent channels.
For example, a 4-channel analog 0..10 V input terminal also has 4 logical channels and therefore 4 identical
sets of parameter data for the channels. In order to avoid having to list each channel in the documentation,
the placeholder "n" tends to be used for the individual channel numbers.

In the CoE system 16 indices, each with 255 subindices, are generally sufficient for representing all channel
parameters. The channel-based order is therefore arranged in 16dec/10hex steps. The parameter range
0x8000 exemplifies this:
• Channel 0: parameter range 0x8000:00 ... 0x800F:255
• Channel 1: parameter range 0x8010:00 ... 0x801F:255
• Channel 2: parameter range 0x8020:00 ... 0x802F:255
• ...

This is generally written as 0x80n0.

Detailed information on the CoE interface can be found in the EtherCAT system documentation on the
Beckhoff website.

EL600x, EL602x Version: 4.6 31


Basics communication

3.6 Distributed Clock


The distributed clock represents a local clock in the EtherCAT slave controller (ESC) with the following
characteristics:
• Unit 1 ns
• Zero point 1.1.2000 00:00
• Size 64 bit (sufficient for the next 584 years; however, some EtherCAT slaves only offer 32-bit support,
i.e. the variable overflows after approx. 4.2 seconds)
• The EtherCAT master automatically synchronizes the local clock with the master clock in the EtherCAT
bus with a precision of < 100 ns.

For detailed information please refer to the EtherCAT system description.

32 Version: 4.6 EL600x, EL602x


Mounting and Wiring

4 Mounting and Wiring

4.1 Instructions for ESD protection


NOTE
Destruction of the devices by electrostatic discharge possible!
The devices contain components at risk from electrostatic discharge caused by improper handling.
ü Please ensure you are electrostatically discharged and avoid touching the contacts of the device di-
rectly.
a) Avoid contact with highly insulating materials (synthetic fibers, plastic film etc.).
b) Surroundings (working place, packaging and personnel) should by grounded probably, when handling
with the devices.
c) Each assembly must be terminated at the right hand end with an EL9011 or EL9012 bus end cap, to en-
sure the protection class and ESD protection.

Fig. 20: Spring contacts of the Beckhoff I/O components

4.2 EL6001, EL6021

4.2.1 Installation on mounting rails


WARNING
Risk of electric shock and damage of device!
Bring the bus terminal system into a safe, powered down state before starting installation, disassembly or
wiring of the bus terminals!

EL600x, EL602x Version: 4.6 33


Mounting and Wiring

Assembly

Fig. 21: Attaching on mounting rail

The bus coupler and bus terminals are attached to commercially available 35 mm mounting rails (DIN rails
according to EN 60715) by applying slight pressure:

1. First attach the fieldbus coupler to the mounting rail.


2. The bus terminals are now attached on the right-hand side of the fieldbus coupler. Join the compo-
nents with tongue and groove and push the terminals against the mounting rail, until the lock clicks
onto the mounting rail.
If the terminals are clipped onto the mounting rail first and then pushed together without tongue and
groove, the connection will not be operational! When correctly assembled, no significant gap should
be visible between the housings.

Fixing of mounting rails


The locking mechanism of the terminals and couplers extends to the profile of the mounting rail. At
the installation, the locking mechanism of the components must not come into conflict with the fixing
bolts of the mounting rail. To mount the mounting rails with a height of 7.5 mm under the terminals
and couplers, you should use flat mounting connections (e.g. countersunk screws or blind rivets).

34 Version: 4.6 EL600x, EL602x


Mounting and Wiring

Disassembly

Fig. 22: Disassembling of terminal

Each terminal is secured by a lock on the mounting rail, which must be released for disassembly:

1. Pull the terminal by its orange-colored lugs approximately 1 cm away from the mounting rail. In doing
so for this terminal the mounting rail lock is released automatically and you can pull the terminal out of
the bus terminal block easily without excessive force.
2. Grasp the released terminal with thumb and index finger simultaneous at the upper and lower grooved
housing surfaces and pull the terminal out of the bus terminal block.

Connections within a bus terminal block

The electric connections between the Bus Coupler and the Bus Terminals are automatically realized by
joining the components:
• The six spring contacts of the K-Bus/E-Bus deal with the transfer of the data and the supply of the Bus
Terminal electronics.
• The power contacts deal with the supply for the field electronics and thus represent a supply rail within
the bus terminal block. The power contacts are supplied via terminals on the Bus Coupler (up to 24 V)
or for higher voltages via power feed terminals.

Power Contacts
During the design of a bus terminal block, the pin assignment of the individual Bus Terminals must
be taken account of, since some types (e.g. analog Bus Terminals or digital 4-channel Bus Termi-
nals) do not or not fully loop through the power contacts. Power Feed Terminals (KL91xx, KL92xx
or EL91xx, EL92xx) interrupt the power contacts and thus represent the start of a new supply rail.

PE power contact

The power contact labeled PE can be used as a protective earth. For safety reasons this contact mates first
when plugging together, and can ground short-circuit currents of up to 125 A.

EL600x, EL602x Version: 4.6 35


Mounting and Wiring

Fig. 23: Power contact on left side

NOTE
Possible damage of the device
Note that, for reasons of electromagnetic compatibility, the PE contacts are capacitatively coupled to the
mounting rail. This may lead to incorrect results during insulation testing or to damage on the terminal (e.g.
disruptive discharge to the PE line during insulation testing of a consumer with a nominal voltage of 230 V).
For insulation testing, disconnect the PE supply line at the Bus Coupler or the Power Feed Terminal! In or-
der to decouple further feed points for testing, these Power Feed Terminals can be released and pulled at
least 10 mm from the group of terminals.

WARNING
Risk of electric shock!
The PE power contact must not be used for other potentials!

4.2.2 Connection

4.2.2.1 Connection system


WARNING
Risk of electric shock and damage of device!
Bring the bus terminal system into a safe, powered down state before starting installation, disassembly or
wiring of the bus terminals!

Overview

The Bus Terminal system offers different connection options for optimum adaptation to the respective
application:
• The terminals of ELxxxx and KLxxxx series with standard wiring include electronics and connection
level in a single enclosure.
• The terminals of ESxxxx and KSxxxx series feature a pluggable connection level and enable steady
wiring while replacing.
• The High Density Terminals (HD Terminals) include electronics and connection level in a single
enclosure and have advanced packaging density.

36 Version: 4.6 EL600x, EL602x


Mounting and Wiring

Standard wiring (ELxxxx / KLxxxx)

Fig. 24: Standard wiring

The terminals of ELxxxx and KLxxxx series have been tried and tested for years.
They feature integrated screwless spring force technology for fast and simple assembly.

Pluggable wiring (ESxxxx / KSxxxx)

Fig. 25: Pluggable wiring

The terminals of ESxxxx and KSxxxx series feature a pluggable connection level.
The assembly and wiring procedure is the same as for the ELxxxx and KLxxxx series.
The pluggable connection level enables the complete wiring to be removed as a plug connector from the top
of the housing for servicing.
The lower section can be removed from the terminal block by pulling the unlocking tab.
Insert the new component and plug in the connector with the wiring. This reduces the installation time and
eliminates the risk of wires being mixed up.

The familiar dimensions of the terminal only had to be changed slightly. The new connector adds about 3
mm. The maximum height of the terminal remains unchanged.

A tab for strain relief of the cable simplifies assembly in many applications and prevents tangling of individual
connection wires when the connector is removed.

Conductor cross sections between 0.08 mm2 and 2.5 mm2 can continue to be used with the proven spring
force technology.

The overview and nomenclature of the product names for ESxxxx and KSxxxx series has been retained as
known from ELxxxx and KLxxxx series.

High Density Terminals (HD Terminals)

Fig. 26: High Density Terminals

The Bus Terminals from these series with 16 terminal points are distinguished by a particularly compact
design, as the packaging density is twice as large as that of the standard 12 mm Bus Terminals. Massive
conductors and conductors with a wire end sleeve can be inserted directly into the spring loaded terminal
point without tools.

EL600x, EL602x Version: 4.6 37


Mounting and Wiring

Wiring HD Terminals
The High Density (HD) Terminals of the ELx8xx and KLx8xx series doesn't support pluggable
wiring.

Ultrasonically "bonded" (ultrasonically welded) conductors

Ultrasonically “bonded" conductors


It is also possible to connect the Standard and High Density Terminals with ultrasonically
"bonded" (ultrasonically welded) conductors. In this case, please note the tables concerning the
wire-size width below!

4.2.2.2 Wiring
WARNING
Risk of electric shock and damage of device!
Bring the bus terminal system into a safe, powered down state before starting installation, disassembly or
wiring of the Bus Terminals!

Terminals for standard wiring ELxxxx/KLxxxx and for pluggable wiring ESxxxx/KSxxxx

Fig. 27: Connecting a cable on a terminal point

Up to eight terminal points enable the connection of solid or finely stranded cables to the Bus Terminal. The
terminal points are implemented in spring force technology. Connect the cables as follows:

1. Open a terminal point by pushing a screwdriver straight against the stop into the square opening
above the terminal point. Do not turn the screwdriver or move it alternately (don't toggle).
2. The wire can now be inserted into the round terminal opening without any force.
3. The terminal point closes automatically when the pressure is released, holding the wire securely and
permanently.

See the following table for the suitable wire size width.

38 Version: 4.6 EL600x, EL602x


Mounting and Wiring

Terminal housing ELxxxx, KLxxxx ESxxxx, KSxxxx


Wire size width (single core wires) 0.08 ... 2.5 mm2 0.08 ... 2.5 mm2
Wire size width (fine-wire conductors) 0.08 ... 2.5 mm2 0,08 ... 2.5 mm2
Wire size width (conductors with a wire end sleeve) 0.14 ... 1.5 mm2 0.14 ... 1.5 mm2
Wire stripping length 8 ... 9 mm 9 ... 10 mm

High Density Terminals (HD Terminals [} 37]) with 16 terminal points

The conductors of the HD Terminals are connected without tools for single-wire conductors using the direct
plug-in technique, i.e. after stripping the wire is simply plugged into the terminal point. The cables are
released, as usual, using the contact release with the aid of a screwdriver. See the following table for the
suitable wire size width.
Terminal housing High Density Housing
Wire size width (single core wires) 0.08 ... 1.5 mm2
Wire size width (fine-wire conductors) 0.25 ... 1.5 mm2
Wire size width (conductors with a wire end sleeve) 0.14 ... 0.75 mm2
Wire size width (ultrasonically “bonded" conductors) only 1.5 mm2
Wire stripping length 8 ... 9 mm

4.2.2.3 Shielding
Shielding
Encoder, analog sensors and actors should always be connected with shielded, twisted paired
wires.

EL600x, EL602x Version: 4.6 39


Mounting and Wiring

4.2.3 Positioning of passive Terminals


Hint for positioning of passive terminals in the bus terminal block
EtherCAT Terminals (ELxxxx / ESxxxx), which do not take an active part in data transfer within the
bus terminal block are so called passive terminals. The passive terminals have no current consump-
tion out of the E-Bus.
To ensure an optimal data transfer, you must not directly string together more than 2 passive termi-
nals!

Examples for positioning of passive terminals (highlighted)

Fig. 28: Correct positioning

Fig. 29: Incorrect positioning

40 Version: 4.6 EL600x, EL602x


Mounting and Wiring

4.2.4 LEDs and terminal connector assignments

LEDs

Fig. 30: EL6001, EL6021 - LEDs and Connection

LED Color Meaning


RUN Green This LED indicates the terminal's operating state:
Off State of the EtherCAT State Machine [} 25]: INIT = initialization of the
terminal or BOOTSTRAP = function for firmware updates [} 187] of the
terminal
flashing State of the EtherCAT state machine: PREOP = function for mailbox
communication and variant standard settings
Single flash State of the EtherCAT state machine: SAFEOP = verification of the Sync
Manager [} 105] channels and the distributed clocks.
Outputs remain in safe state
On State of the EtherCAT State Machine: OP = normal operating state;
mailbox and process data communication is possible
TxD Green State of the transmit signal line (on: HI signal level on transmit line)
RxD Green State of the receive signal line (on: HI signal level on receive line)

EL600x, EL602x Version: 4.6 41


Mounting and Wiring

Connection

Fig. 31: EL6001, EL6021 - LEDs and Connection

EL6001 terminal connector assignments


Terminal point Name Signal
1 TxD Signal line (Transmit Data)
5 RxD Signal line (Receive Data)
2 RTS Control line (Request To Send)
6 CTS Control line (Clear To Send)
3 GND Ground (internally bridged with terminal 7)
7 GND Ground (internally bridged with terminal 3)
4 Shield Shield (internally bridged with terminal 8)
8 Shield Shield (internally bridged with terminal 4)

EL6021 terminal connector assignments


Terminal point Name Signal
1 TxD+ Signal line + (Transmit Data)
5 TxD- Signal line - (Transmit Data)
2 RxD+ Signal line + (Receive Data)
6 RxD- Signal line - (Receive Data)
3 GND Ground (internally bridged with terminal 7)
7 GND Ground (internally bridged with terminal 3)
4 Shield Shield (internally bridged with terminal 8)
8 Shield Shield (internally bridged with terminal 4)

42 Version: 4.6 EL600x, EL602x


Mounting and Wiring

Connection for RS422 transfer

In RS422 mode, data can be transferred in full duplex mode. Only point to point connections can be
established.

Fig. 32: Connection for RS422 transfer

Connection for RS485 transfer

In RS485 mode, data are exchanged in half duplex mode. A bus structure can be created in this mode of
operation.

Fig. 33: Connection for RS485 transfer

The transmit and receive lines are connected to one another in RS485 operating mode. As a result, the
terminal receives not only the data from other devices, but also its own transmitted data. This can be
suppressed with the index 0x8000:06 “Enable half duplex” in the Settings object.

In operating mode RS485, the reception of new data is only possible if transmission is complete.
“Enable half duplex” “Enable point to Mode
point connection
(RS422)”
0 0 RS485:
The terminal receives its own data and the data from other
devices
0 1 RS422:
Normal operating mode; the terminal operates in full duplex
mode.
1 0 RS485:
The terminal only receives data from other devices
1 1 RS422:
The receiver is only enabled after the last data has been
transmitted.

4.3 EL6002, EL6022

4.3.1 Mounting and demounting - terminals with front unlocking


The terminal modules are fastened to the assembly surface with the aid of a 35 mm mounting rail (e.g.
mounting rail TH 35-15).

EL600x, EL602x Version: 4.6 43


Mounting and Wiring

Fixing of mounting rails


The locking mechanism of the terminals and couplers extends to the profile of the mounting rail. At
the installation, the locking mechanism of the components must not come into conflict with the fixing
bolts of the mounting rail. To mount the recommended mounting rails under the terminals and cou-
plers, you should use flat mounting connections (e.g. countersunk screws or blind rivets).

WARNING
Risk of electric shock and damage of device!
Bring the bus terminal system into a safe, powered down state before starting installation, disassembly or
wiring of the Bus Terminals!

Mounting
• Fit the mounting rail to the planned assembly location.

and press (1) the terminal module against the mounting rail until it latches in place on the mounting
rail (2).
• Attach the cables.

Demounting
• Remove all the cables.
• Lever the unlatching hook back with thumb and forefinger (3). An internal mechanism pulls the two
latching lugs (3a) from the top hat rail back into the terminal module.

44 Version: 4.6 EL600x, EL602x


Mounting and Wiring

• Pull (4) the terminal module away from the mounting surface.
Avoid canting of the module; you should stabilize the module with the other hand, if required.

4.3.2 Recommended mounting rails


Terminal Modules und EtherCAT Modules of KMxxxx and EMxxxx series, same as the terminals of the
EL66xx and EL67xx series can be snapped onto the following recommended mounting rails:

DIN Rail TH 35-7.5 with 1 mm material thickness (according to EN 60715)

DIN Rail TH 35-15 with 1,5 mm material thickness

Pay attention to the material thickness of the DIN Rail


Terminal Modules und EtherCAT Modules of KMxxxx and EMxxxx series, same as the terminals of
the EL66xx and EL67xx series does not fit to the DIN Rail TH 35-15 with 2,2 to 2,5 mm material
thickness (according to EN 60715)!

EL600x, EL602x Version: 4.6 45


Mounting and Wiring

4.3.3 LEDs and pin assignment

Fig. 34: EL6002, EL6022 - LEDs

LEDs
LED Color Meaning
RUN Green This LED indicates the terminal's operating state:
Off State of the EtherCAT State Machine [} 25]: INIT = initialization of the
terminal or BOOTSTRAP = function for firmware updates [} 187] of the
terminal
flashing State of the EtherCAT State Machine: PREOP = function for mailbox
communication and variant standard settings
Single flash State of the EtherCAT State Machine: SAFEOP = verification of the Sync
Manager [} 105] channels and the distributed clocks.
Outputs remain in safe state
On State of the EtherCAT State Machine: OP = normal operating state; mailbox
and process data communication is possible
TxCh. 1 Orange Serial port at this connection sends data (channel 1)
RxCh. 1 Green Serial port at this connection receives data (channel 1)
TxCh. 2 Orange Serial port at this connection sends data (channel 2)
RxCh. 2 Green Serial port at this connection receives data (channel 2)

46 Version: 4.6 EL600x, EL602x


Mounting and Wiring

EL6002 pin assignment

 2 x D-Sub connector, male; 9-pin


D-Sub connector, male Pin assignment channel 1 Pin assignment channel 2
(plan view)
Pin RS232 Pin RS232
1 DCD (internally bridged with 1 DCD (internally bridged with pins
pins 4 and 6) 4 and 6)
2 RxCH1 2 RxCH2
3 TxCH1 3 TxCH2
4 DTR (internally bridged with 4 DTR (internally bridged with pins
pins 1 and 6) 1 and 6)
5 GND 5 GND
6 DSR (internally bridged with 6 DSR (internally bridged with pins
pins 1 and 4) 1 and 4)
7 RTS CH1 7 RTS CH2
8 CTS CH1 8 CTS CH2
9 - 9 -

GND connections
GND for both channels is internally connected via a high-resistance RC combination

EL6022 pin assignment

2 x D-Sub connection socket, 9-pin


D-Sub connector, female Pin assignment channel 1 Pin assignment channel 2
(plan view)
Pin RS485/RS422 Pin RS485/RS422
1 - 1 -
2 Tx+ CH1 2 Tx+ CH2
3 Rx+ CH1 3 Rx+ CH2
4 - 4 -
5 GND 5 GND
6 +5 V 6 +5 V
7 Tx- CH1 7 Tx- CH2
8 Rx- CH1 8 Rx- CH2
9 - 9 -

GND connections
GND for both channels is internally connected via a high-resistance RC combination

EL600x, EL602x Version: 4.6 47


Mounting and Wiring

Connection for RS422 transfer

In RS422 mode, data can be transferred in full duplex mode. Only point to point connections can be
established.

Fig. 35: Connection for RS422 transfer

Connection for RS485 transfer

In RS485 mode, data are exchanged in half duplex mode. A bus structure can be created in this mode of
operation.

Fig. 36: Connection for RS485 transfer

The transmit and receive lines are connected to one another in RS485 operating mode. As a result, the
terminal receives not only the data from other devices, but also its own transmitted data. This can be
suppressed with the index 0x8000:06 “Enable half duplex” in the Settings object.

In operating mode RS485, the reception of new data is only possible if transmission is complete.
“Enable half duplex” “Enable point to Mode
point connection
(RS422)”
0 0 RS485:
The terminal receives its own data and the data from other
devices
0 1 RS422:
Normal operating mode; the terminal operates in full duplex
mode.
1 0 RS485:
The terminal only receives data from other devices
1 1 RS422:
The receiver is only enabled after the last data has been
transmitted.

48 Version: 4.6 EL600x, EL602x


Mounting and Wiring

4.4 Positioning of passive Terminals


Hint for positioning of passive terminals in the bus terminal block
EtherCAT Terminals (ELxxxx / ESxxxx), which do not take an active part in data transfer within the
bus terminal block are so called passive terminals. The passive terminals have no current consump-
tion out of the E-Bus.
To ensure an optimal data transfer, you must not directly string together more than 2 passive termi-
nals!

Examples for positioning of passive terminals (highlighted)

Fig. 37: Correct positioning

Fig. 38: Incorrect positioning

EL600x, EL602x Version: 4.6 49


Mounting and Wiring

4.5 Installation instructions for enhanced mechanical load


capacity
WARNING
Risk of injury through electric shock and damage to the device!
Bring the Bus Terminal system into a safe, de-energized state before starting mounting, disassembly or
wiring of the Bus Terminals!

Additional checks

The terminals have undergone the following additional tests:

Verification Explanation
Vibration 10 frequency runs in 3 axes
6 Hz < f < 60 Hz displacement 0.35 mm, constant amplitude
60.1 Hz < f < 500 Hz acceleration 5 g, constant amplitude
Shocks 1000 shocks in each direction, in 3 axes
25 g, 6 ms

Additional installation instructions

For terminals with enhanced mechanical load capacity, the following additional installation instructions apply:
• The enhanced mechanical load capacity is valid for all permissible installation positions
• Use a mounting rail according to EN 60715 TH35-15
• Fix the terminal segment on both sides of the mounting rail with a mechanical fixture, e.g. an earth
terminal or reinforced end clamp
• The maximum total extension of the terminal segment (without coupler) is:
64 terminals (12 mm mounting with) or 32 terminals (24 mm mounting with)
• Avoid deformation, twisting, crushing and bending of the mounting rail during edging and installation of
the rail
• The mounting points of the mounting rail must be set at 5 cm intervals
• Use countersunk head screws to fasten the mounting rail
• The free length between the strain relief and the wire connection should be kept as short as possible. A
distance of approx. 10 cm should be maintained to the cable duct.

50 Version: 4.6 EL600x, EL602x


Mounting and Wiring

4.6 Installation positions


NOTE
Constraints regarding installation position and operating temperature range
Please refer to the technical data for a terminal to ascertain whether any restrictions regarding the installa-
tion position and/or the operating temperature range have been specified. When installing high power dissi-
pation terminals ensure that an adequate spacing is maintained between other components above and be-
low the terminal in order to guarantee adequate ventilation!

Optimum installation position (standard)

The optimum installation position requires the mounting rail to be installed horizontally and the connection
surfaces of the EL/KL terminals to face forward (see Fig. “Recommended distances for standard installation
position”). The terminals are ventilated from below, which enables optimum cooling of the electronics through
convection. "From below" is relative to the acceleration of gravity.

Fig. 39: Recommended distances for standard installation position

Compliance with the distances shown in Fig. “Recommended distances for standard installation position” is
recommended.

Other installation positions

All other installation positions are characterized by different spatial arrangement of the mounting rail - see
Fig “Other installation positions”.

The minimum distances to ambient specified above also apply to these installation positions.

EL600x, EL602x Version: 4.6 51


Mounting and Wiring

Fig. 40: Other installation positions

52 Version: 4.6 EL600x, EL602x


Mounting and Wiring

4.7 UL notice
Application
Beckhoff EtherCAT modules are intended for use with Beckhoff’s UL Listed EtherCAT Sys-
tem only.

Examination
For cULus examination, the Beckhoff I/O System has only been investigated for risk of fire
and electrical shock (in accordance with UL508 and CSA C22.2 No. 142).

For devices with Ethernet connectors


Not for connection to telecommunication circuits.

Basic principles

Two UL certificates are met in the Beckhoff EtherCAT product range, depending upon the components:

1. UL certification according to UL508. Devices with this kind of certification are marked by this sign:

2. UL certification according to UL508 with limited power consumption. The current consumed by the de-
vice is limited to a max. possible current consumption of 4 A. Devices with this kind of certification are
marked by this sign:

Almost all current EtherCAT products (as at 2010/05) are UL certified without restrictions.

Application

If terminals certified with restrictions are used, then the current consumption at 24 VDC must be limited
accordingly by means of supply
• from an isolated source protected by a fuse of max. 4 A (according to UL248) or
• from a voltage supply complying with NEC class 2.
A voltage source complying with NEC class 2 may not be connected in series or parallel with another
NEC class 2compliant voltage supply!

These requirements apply to the supply of all EtherCAT bus couplers, power adaptor terminals, Bus
Terminals and their power contacts.

EL600x, EL602x Version: 4.6 53


Mounting and Wiring

4.8 ATEX - Special conditions (extended temperature


range)
WARNING
Observe the special conditions for the intended use of Beckhoff fieldbus components with
extended temperature range (ET) in potentially explosive areas (directive 94/9/EU)!
• The certified components are to be installed in a suitable housing that guarantees a protection class of at
least IP54 in accordance with EN 60529! The environmental conditions during use are thereby to be
taken into account!
• If the temperatures during rated operation are higher than 70°C at the feed-in points of cables, lines or
pipes, or higher than 80°C at the wire branching points, then cables must be selected whose tempera-
ture data correspond to the actual measured temperature values!
• Observe the permissible ambient temperature range of -25 to 60°C for the use of Beckhoff fieldbus com-
ponents with extended temperature range (ET) in potentially explosive areas!
• Measures must be taken to protect against the rated operating voltage being exceeded by more than
40% due to short-term interference voltages!
• The individual terminals may only be unplugged or removed from the Bus Terminal system if the supply
voltage has been switched off or if a non-explosive atmosphere is ensured!
• The connections of the certified components may only be connected or disconnected if the supply volt-
age has been switched off or if a non-explosive atmosphere is ensured!
• The fuses of the KL92xx/EL92xx power feed terminals may only be exchanged if the supply voltage has
been switched off or if a non-explosive atmosphere is ensured!
• Address selectors and ID switches may only be adjusted if the supply voltage has been switched off or if
a non-explosive atmosphere is ensured!

Standards

The fundamental health and safety requirements are fulfilled by compliance with the following standards:
• EN 60079-0:2012+A11:2013
• EN 60079-15:2010

Marking

The Beckhoff fieldbus components with extended temperature range (ET) certified for potentially explosive
areas bear the following marking:

II 3G   KEMA 10ATEX0075 X Ex nA IIC T4 Gc   Ta: -25 … 60°C

or

II 3G   KEMA 10ATEX0075 X Ex nC IIC T4 Gc   Ta: -25 … 60°C

54 Version: 4.6 EL600x, EL602x


Mounting and Wiring

4.9 ATEX Documentation


Notes about operation of the Beckhoff terminal systems in potentially explosive ar-
eas (ATEX)
Pay also attention to the continuative documentation

Notes about operation of the Beckhoff terminal systems in potentially explosive areas (ATEX)

that is available in the download area of the Beckhoff homepage http:\\www.beckhoff.com!

EL600x, EL602x Version: 4.6 55


Commissioning

5 Commissioning

5.1 TwinCAT Quick Start


TwinCAT is a development environment for real-time control including multi-PLC system, NC axis control,
programming and operation. The whole system is mapped through this environment and enables access to a
programming environment (including compilation) for the controller. Individual digital or analog inputs or
outputs can also be read or written directly, in order to verify their functionality, for example.

For further information please refer to http://infosys.beckhoff.com:


• EtherCAT Systemmanual:
Fieldbus Components → EtherCAT Terminals → EtherCAT System Documentation → Setup in the
TwinCAT System Manager
• TwinCAT 2 → TwinCAT System Manager → I/O - Configuration
• In particular, TwinCAT driver installation:
Fieldbus components → Fieldbus Cards and Switches → FC900x – PCI Cards for Ethernet →
Installation

Devices contain the terminals for the actual configuration. All configuration data can be entered directly via
editor functions (offline) or via the "Scan" function (online):
• "offline": The configuration can be customized by adding and positioning individual components.
These can be selected from a directory and configured.
◦ The procedure for offline mode can be found under http://infosys.beckhoff.com:
TwinCAT 2 → TwinCAT System Manager → IO - Configuration → Adding an I/O Device
• "online": The existing hardware configuration is read
◦ See also http://infosys.beckhoff.com:
Fieldbus components → Fieldbus cards and switches → FC900x – PCI Cards for Ethernet →
Installation → Searching for devices

The following relationship is envisaged from user PC to the individual control elements:

56 Version: 4.6 EL600x, EL602x


Commissioning

Fig. 41: Relationship between user side (commissioning) and installation

The user inserting of certain components (I/O device, terminal, box...) is the same in TwinCAT 2 and
TwinCAT 3. The descriptions below relate to the online procedure.

Sample configuration (actual configuration)

Based on the following sample configuration, the subsequent subsections describe the procedure for
TwinCAT 2 and TwinCAT 3:
• Control system (PLC) CX2040 including CX2100-0004 power supply unit
• Connected to the CX2040 on the right (E-bus):
EL1004 (4-channel analog input terminal -10…+10 V)
• Linked via the X001 port (RJ-45): EK1100 EtherCAT Coupler
• Connected to the EK1100 EtherCAT coupler on the right (E-bus):
EL2008 (8-channel digital output terminal 24 V DC; 0.5 A)
• (Optional via X000: a link to an external PC for the user interface)

EL600x, EL602x Version: 4.6 57


Commissioning

Fig. 42: Control configuration with Embedded PC, input (EL1004) and output (EL2008)

Note that all combinations of a configuration are possible; for example, the EL1004 terminal could also be
connected after the coupler, or the EL2008 terminal could additionally be connected to the CX2040 on the
right, in which case the EK1100 coupler wouldn’t be necessary.

5.1.1 TwinCAT 2

Startup

TwinCAT basically uses two user interfaces: the TwinCAT System Manager for communication with the
electromechanical components and TwinCAT PLC Control for the development and compilation of a
controller. The starting point is the TwinCAT System Manager.

After successful installation of the TwinCAT system on the PC to be used for development, the TwinCAT 2
System Manager displays the following user interface after startup:

Fig. 43: Initial TwinCAT 2 user interface

58 Version: 4.6 EL600x, EL602x


Commissioning

Generally, TwinCAT can be used in local or remote mode. Once the TwinCAT system including the user
interface (standard) is installed on the respective PLC, TwinCAT can be used in local mode and thereby the
next step is "Insert Device [} 60]".

If the intention is to address the TwinCAT runtime environment installed on a PLC as development
environment remotely from another system, the target system must be made known first. In the menu under

"Actions" → "Choose Target System...", via the symbol " " or the "F8" key, open the following window:

Fig. 44: Selection of the target system

Use "Search (Ethernet)..." to enter the target system. Thus a next dialog opens to either:
• enter the known computer name after "Enter Host Name / IP:" (as shown in red)
• perform a "Broadcast Search" (if the exact computer name is not known)
• enter the known computer IP or AmsNetID.

Fig. 45: Specify the PLC for access by the TwinCAT System Manager: selection of the target system

Once the target system has been entered, it is available for selection as follows (a password may have to be
entered):

EL600x, EL602x Version: 4.6 59


Commissioning

After confirmation with "OK" the target system can be accessed via the System Manager.

Adding devices

In the configuration tree of the TwinCAT 2 System Manager user interface on the left, select "I/O Devices”
and then right-click to open a context menu and select "Scan Devices…", or start the action in the menu bar

via . The TwinCAT System Manager may first have to be set to "Config mode" via or via menu
“Actions" → "Set/Reset TwinCAT to Config Mode…" (Shift + F4).

Fig. 46: Select "Scan Devices..."

Confirm the warning message, which follows, and select "EtherCAT" in the dialog:

Fig. 47: Automatic detection of I/O devices: selection the devices to be integrated

Confirm the message "Find new boxes", in order to determine the terminals connected to the devices. "Free
Run" enables manipulation of input and output values in "Config mode" and should also be acknowledged.

Based on the sample configuration [} 57] described at the beginning of this section, the result is as follows:

60 Version: 4.6 EL600x, EL602x


Commissioning

Fig. 48: Mapping of the configuration in the TwinCAT 2 System Manager

The whole process consists of two stages, which may be performed separately (first determine the devices,
then determine the connected elements such as boxes, terminals, etc.). A scan can also be initiated by
selecting "Device ..." from the context menu, which then reads the elements present in the configuration
below:

Fig. 49: Reading of individual terminals connected to a device

This functionality is useful if the actual configuration is modified at short notice.

Programming and integrating the PLC

TwinCAT PLC Control is the development environment for the creation of the controller in different program
environments: TwinCAT PLC Control supports all languages described in IEC 61131-3. There are two text-
based languages and three graphical languages.
• Text-based languages
◦ Instruction List (IL)
◦ Structured Text (ST)

EL600x, EL602x Version: 4.6 61


Commissioning

• Graphical languages
◦ Function Block Diagram (FBD)
◦ Ladder Diagram (LD)
◦ The Continuous Function Chart Editor (CFC)
◦ Sequential Function Chart (SFC)

The following section refers to Structured Text (ST).

After starting TwinCAT PLC Control, the following user interface is shown for an initial project:

Fig. 50: TwinCAT PLC Control after startup

Sample variables and a sample program have been created and stored under the name "PLC_example.pro":

62 Version: 4.6 EL600x, EL602x


Commissioning

Fig. 51: Sample program with variables after a compile process (without variable integration)

Warning 1990 (missing "VAR_CONFIG") after a compile process indicates that the variables defined as
external (with the ID "AT%I*" or "AT%Q*") have not been assigned. After successful compilation, TwinCAT
PLC Control creates a "*.tpy" file in the directory in which the project was stored. This file (*.tpy) contains
variable assignments and is not known to the System Manager, hence the warning. Once the System
Manager has been notified, the warning no longer appears.

First, integrate the TwinCAT PLC Control project in the System Manager via the context menu of the PLC
configuration; right-click and select "Append PLC Project…":

Fig. 52: Appending the TwinCAT PLC Control project

EL600x, EL602x Version: 4.6 63


Commissioning

Select the PLC configuration "PLC_example.tpy" in the browser window that opens. The project including the
two variables identified with "AT" are then integrated in the configuration tree of the System Manager:

Fig. 53: PLC project integrated in the PLC configuration of the System Manager

The two variables "bEL1004_Ch4" and "nEL2008_value" can now be assigned to certain process objects of
the I/O configuration.

Assigning variables

Open a window for selecting a suitable process object (PDO) via the context menu of a variable of the
integrated project "PLC_example" and via "Modify Link..." "Standard":

Fig. 54: Creating the links between PLC variables and process objects

In the window that opens, the process object for the variable “bEL1004_Ch4” of type BOOL can be selected
from the PLC configuration tree:

64 Version: 4.6 EL600x, EL602x


Commissioning

Fig. 55: Selecting PDO of type BOOL

According to the default setting, certain PDO objects are now available for selection. In this sample the input
of channel 4 of the EL1004 terminal is selected for linking. In contrast, the checkbox "All types" must be
ticked for creating the link for the output variables, in order to allocate a set of eight separate output bits to a
byte variable. The following diagram shows the whole process:

Fig. 56: Selecting several PDOs simultaneously: activate "Continuous" and "All types"

Note that the "Continuous" checkbox was also activated. This is designed to allocate the bits contained in the
byte of the variable "nEL2008_value" sequentially to all eight selected output bits of the EL2008 terminal. In
this way it is possible to subsequently address all eight outputs of the terminal in the program with a byte
corresponding to bit 0 for channel 1 to bit 7 for channel 8 of the PLC. A special symbol ( ) at the yellow or
red object of the variable indicates that a link exists. The links can also be checked by selecting a "Goto Link
Variable” from the context menu of a variable. The object opposite, in this case the PDO, is automatically
selected:

EL600x, EL602x Version: 4.6 65


Commissioning

Fig. 57: Application of a "Goto Link" variable, using "MAIN.bEL1004_Ch4" as a sample

The process of assigning variables to the PDO is completed via the menu selection "Actions" → "Generate

Mappings”, key Ctrl+M or by clicking on the symbol in the menu.

This can be visualized in the configuration:

The process of creating links can also take place in the opposite direction, i.e. starting with individual PDOs
to variable. However, in this example it would then not be possible to select all output bits for the EL2008,
since the terminal only makes individual digital outputs available. If a terminal has a byte, word, integer or
similar PDO, it is possible to allocate this a set of bit-standardised variables (type "BOOL"). Here, too, a
"Goto Link Variable” from the context menu of a PDO can be executed in the other direction, so that the
respective PLC instance can then be selected.

Activation of the configuration

The allocation of PDO to PLC variables has now established the connection from the controller to the inputs
and outputs of the terminals. The configuration can now be activated. First, the configuration can be verified

via (or via "Actions" → "Check Configuration”). If no error is present, the configuration can be

activated via (or via "Actions" → "Activate Configuration…") to transfer the System Manager settings
to the runtime system. Confirm the messages "Old configurations are overwritten!" and "Restart TwinCAT
system in Run mode" with "OK".

A few seconds later the real-time status is displayed at the bottom right in the System Manager.
The PLC system can then be started as described below.

Starting the controller

Starting from a remote system, the PLC control has to be linked with the Embedded PC over Ethernet via
"Online" → “Choose Run-Time System…":

66 Version: 4.6 EL600x, EL602x


Commissioning

Fig. 58: Choose target system (remote)

In this sample "Runtime system 1 (port 801)" is selected and confirmed. Link the PLC with the real-time

system via menu option "Online" → "Login", the F11 key or by clicking on the symbol . The control
program can then be loaded for execution. This results in the message "No program on the controller!
Should the new program be loaded?", which should be acknowledged with "Yes". The runtime environment
is ready for the program start:

EL600x, EL602x Version: 4.6 67


Commissioning

Fig. 59: PLC Control logged in, ready for program startup

The PLC can now be started via "Online" → "Run", F5 key or .

5.1.2 TwinCAT 3

Startup

TwinCAT makes the development environment areas available together with Microsoft Visual Studio: after
startup, the project folder explorer appears on the left in the general window area (cf. "TwinCAT System
Manager" of TwinCAT 2) for communication with the electromechanical components.

After successful installation of the TwinCAT system on the PC to be used for development, TwinCAT 3
(shell) displays the following user interface after startup:

68 Version: 4.6 EL600x, EL602x


Commissioning

Fig. 60: Initial TwinCAT 3 user interface

First create a new project via (or under "File"→“New"→ "Project…"). In the
following dialog make the corresponding entries as required (as shown in the diagram):

Fig. 61: Create new TwinCAT project

The new project is then available in the project folder explorer:

EL600x, EL602x Version: 4.6 69


Commissioning

Fig. 62: New TwinCAT3 project in the project folder explorer

Generally, TwinCAT can be used in local or remote mode. Once the TwinCAT system including the user
interface (standard) is installed on the respective PLC, TwinCAT can be used in local mode and thereby the
next step is "Insert Device [} 71]".

If the intention is to address the TwinCAT runtime environment installed on a PLC as development
environment remotely from another system, the target system must be made known first. Via the symbol in
the menu bar:

expand the pull-down menu:

and open the following window:

Fig. 63: Selection dialog: Choose the target system

70 Version: 4.6 EL600x, EL602x


Commissioning

Use "Search (Ethernet)..." to enter the target system. Thus a next dialog opens to either:
• enter the known computer name after "Enter Host Name / IP:" (as shown in red)
• perform a "Broadcast Search" (if the exact computer name is not known)
• enter the known computer IP or AmsNetID.

Fig. 64: Specify the PLC for access by the TwinCAT System Manager: selection of the target system

Once the target system has been entered, it is available for selection as follows (a password may have to be
entered):

After confirmation with "OK" the target system can be accessed via the Visual Studio shell.

Adding devices

In the project folder explorer of the Visual Studio shell user interface on the left, select "Devices" within

element “I/O”, then right-click to open a context menu and select "Scan" or start the action via in the

menu bar. The TwinCAT System Manager may first have to be set to "Config mode" via or via the
menu "TwinCAT" → "Restart TwinCAT (Config mode)".

Fig. 65: Select "Scan"

Confirm the warning message, which follows, and select "EtherCAT" in the dialog:

EL600x, EL602x Version: 4.6 71


Commissioning

Fig. 66: Automatic detection of I/O devices: selection the devices to be integrated

Confirm the message "Find new boxes", in order to determine the terminals connected to the devices. "Free
Run" enables manipulation of input and output values in "Config mode" and should also be acknowledged.

Based on the sample configuration [} 57] described at the beginning of this section, the result is as follows:

Fig. 67: Mapping of the configuration in VS shell of the TwinCAT3 environment

The whole process consists of two stages, which may be performed separately (first determine the devices,
then determine the connected elements such as boxes, terminals, etc.). A scan can also be initiated by
selecting "Device ..." from the context menu, which then reads the elements present in the configuration
below:

72 Version: 4.6 EL600x, EL602x


Commissioning

Fig. 68: Reading of individual terminals connected to a device

This functionality is useful if the actual configuration is modified at short notice.

Programming the PLC

TwinCAT PLC Control is the development environment for the creation of the controller in different program
environments: TwinCAT PLC Control supports all languages described in IEC 61131-3. There are two text-
based languages and three graphical languages.
• Text-based languages
◦ Instruction List (IL)
◦ Structured Text (ST)
• Graphical languages
◦ Function Block Diagram (FBD)
◦ Ladder Diagram (LD)
◦ The Continuous Function Chart Editor (CFC)
◦ Sequential Function Chart (SFC)

The following section refers to Structured Text (ST).

In order to create a programming environment, a PLC subproject is added to the project sample via the
context menu of "PLC" in the project folder explorer by selecting "Add New Item….":

EL600x, EL602x Version: 4.6 73


Commissioning

Fig. 69: Adding the programming environment in "PLC"

In the dialog that opens select "Standard PLC project" and enter "PLC_example" as project name, for
example, and select a corresponding directory:

Fig. 70: Specifying the name and directory for the PLC programming environment

The "Main" program, which already exists by selecting "Standard PLC project", can be opened by double-
clicking on "PLC_example_project" in "POUs”. The following user interface is shown for an initial project:

74 Version: 4.6 EL600x, EL602x


Commissioning

Fig. 71: Initial "Main" program of the standard PLC project

To continue, sample variables and a sample program have now been created:

EL600x, EL602x Version: 4.6 75


Commissioning

Fig. 72: Sample program with variables after a compile process (without variable integration)

The control program is now created as a project folder, followed by the compile process:

Fig. 73: Start program compilation

The following variables, identified in the ST/ PLC program with "AT%", are then available in under
"Assignments" in the project folder explorer:

Assigning variables

Via the menu of an instance - variables in the "PLC” context, use the "Modify Link…" option to open a
window for selecting a suitable process object (PDO) for linking:

76 Version: 4.6 EL600x, EL602x


Commissioning

Fig. 74: Creating the links between PLC variables and process objects

In the window that opens, the process object for the variable "bEL1004_Ch4" of type BOOL can be selected
from the PLC configuration tree:

Fig. 75: Selecting PDO of type BOOL

According to the default setting, certain PDO objects are now available for selection. In this sample the input
of channel 4 of the EL1004 terminal is selected for linking. In contrast, the checkbox "All types" must be
ticked for creating the link for the output variables, in order to allocate a set of eight separate output bits to a
byte variable. The following diagram shows the whole process:

EL600x, EL602x Version: 4.6 77


Commissioning

Fig. 76: Selecting several PDOs simultaneously: activate "Continuous" and "All types"

Note that the "Continuous" checkbox was also activated. This is designed to allocate the bits contained in the
byte of the variable "nEL2008_value" sequentially to all eight selected output bits of the EL2008 terminal. In
this way it is possible to subsequently address all eight outputs of the terminal in the program with a byte
corresponding to bit 0 for channel 1 to bit 7 for channel 8 of the PLC. A special symbol ( ) at the yellow or
red object of the variable indicates that a link exists. The links can also be checked by selecting a "Goto Link
Variable” from the context menu of a variable. The object opposite, in this case the PDO, is automatically
selected:

Fig. 77: Application of a "Goto Link" variable, using "MAIN.bEL1004_Ch4" as a sample

The process of creating links can also take place in the opposite direction, i.e. starting with individual PDOs
to variable. However, in this example it would then not be possible to select all output bits for the EL2008,
since the terminal only makes individual digital outputs available. If a terminal has a byte, word, integer or
similar PDO, it is possible to allocate this a set of bit-standardised variables (type "BOOL"). Here, too, a
"Goto Link Variable” from the context menu of a PDO can be executed in the other direction, so that the
respective PLC instance can then be selected.

78 Version: 4.6 EL600x, EL602x


Commissioning

Activation of the configuration

The allocation of PDO to PLC variables has now established the connection from the controller to the inputs

and outputs of the terminals. The configuration can now be activated with or via the menu under
"TwinCAT" in order to transfer settings of the development environment to the runtime system. Confirm the
messages "Old configurations are overwritten!" and "Restart TwinCAT system in Run mode" with "OK". The
corresponding assignments can be seen in the project folder explorer:

A few seconds later the corresponding status of the Run mode is displayed in the form of a rotating symbol

at the bottom right of the VS shell development environment. The PLC system can then be started as
described below.

Starting the controller

Select the menu option "PLC" → "Login" or click on to link the PLC with the real-time system and load
the control program for execution. This results in the message "No program on the controller! Should the
new program be loaded?", which should be acknowledged with "Yes". The runtime environment is ready for

program start by click on symbol , the "F5" key or via "PLC" in the menu selecting “Start”. The started
programming environment shows the runtime values of individual variables:

Fig. 78: TwinCAT development environment (VS shell): logged-in, after program startup

The two operator control elements for stopping and logout result in the required action
(accordingly also for stop "Shift + F5", or both actions can be selected via the PLC menu).

EL600x, EL602x Version: 4.6 79


Commissioning

5.2 TwinCAT Development Environment


The Software for automation TwinCAT (The Windows Control and Automation Technology) will be
distinguished into:
• TwinCAT 2: System Manager (Configuration) & PLC Control (Programming)
• TwinCAT 3: Enhancement of TwinCAT 2 (Programming and Configuration takes place via a common
Development Environment)

Details:
• TwinCAT 2:
◦ Connects I/O devices to tasks in a variable-oriented manner
◦ Connects tasks to tasks in a variable-oriented manner
◦ Supports units at the bit level
◦ Supports synchronous or asynchronous relationships
◦ Exchange of consistent data areas and process images
◦ Datalink on NT - Programs by open Microsoft Standards (OLE, OCX, ActiveX, DCOM+, etc.)
◦ Integration of IEC 61131-3-Software-SPS, Software- NC and Software-CNC within Windows
NT/2000/XP/Vista, Windows 7, NT/XP Embedded, CE
◦ Interconnection to all common fieldbusses
◦ More…

Additional features:
• TwinCAT 3 (eXtended Automation):
◦ Visual-Studio®-Integration
◦ Choice of the programming language
◦ Supports object orientated extension of IEC 61131-3
◦ Usage of C/C++ as programming language for real time applications
◦ Connection to MATLAB®/Simulink®
◦ Open interface for expandability
◦ Flexible run-time environment
◦ Active support of Multi-Core- und 64-Bit-Operatingsystem
◦ Automatic code generation and project creation with the TwinCAT Automation Interface
◦ More…

Within the following sections commissioning of the TwinCAT Development Environment on a PC System for
the control and also the basically functions of unique control elements will be explained.

Please see further information to TwinCAT 2 and TwinCAT 3 at http://infosys.beckhoff.com.

5.2.1 Installation of the TwinCAT real-time driver


In order to assign real-time capability to a standard Ethernet port of an IPC controller, the Beckhoff real-time
driver has to be installed on this port under Windows.

This can be done in several ways. One option is described here.

In the System Manager call up the TwinCAT overview of the local network interfaces via Options → Show
Real Time Ethernet Compatible Devices.

80 Version: 4.6 EL600x, EL602x


Commissioning

Fig. 79: System Manager “Options” (TwinCAT 2)

This have to be called up by the Menü “TwinCAT” within the TwinCAT 3 environment:

Fig. 80: Call up under VS Shell (TwinCAT 3)

The following dialog appears:

Fig. 81: Overview of network interfaces

Interfaces listed under “Compatible devices” can be assigned a driver via the “Install” button. A driver should
only be installed on compatible devices.

A Windows warning regarding the unsigned driver can be ignored.

Alternatively an EtherCAT-device can be inserted first of all as described in chapter Offline configuration
creation, section “Creating the EtherCAT device” [} 91] in order to view the compatible ethernet ports via its
EtherCAT properties (tab „Adapter“, button „Compatible Devices…“):

EL600x, EL602x Version: 4.6 81


Commissioning

Fig. 82: EtherCAT device properties(TwinCAT 2): click on „Compatible Devices…“ of tab “Adapter”

TwinCAT 3: the properties of the EtherCAT device can be opened by double click on “Device .. (EtherCAT)”
within the Solution Explorer under “I/O”:

After the installation the driver appears activated in the Windows overview for the network interface
(Windows Start → System Properties → Network)

Fig. 83: Windows properties of the network interface

A correct setting of the driver could be:

82 Version: 4.6 EL600x, EL602x


Commissioning

Fig. 84: Exemplary correct driver setting for the Ethernet port

Other possible settings have to be avoided:

EL600x, EL602x Version: 4.6 83


Commissioning

Fig. 85: Incorrect driver settings for the Ethernet port

84 Version: 4.6 EL600x, EL602x


Commissioning

IP address of the port used

IP address/DHCP
In most cases an Ethernet port that is configured as an EtherCAT device will not transport general
IP packets. For this reason and in cases where an EL6601 or similar devices are used it is useful to
specify a fixed IP address for this port via the “Internet Protocol TCP/IP” driver setting and to disable
DHCP. In this way the delay associated with the DHCP client for the Ethernet port assigning itself a
default IP address in the absence of a DHCP server is avoided. A suitable address space is
192.168.x.x, for example.

Fig. 86: TCP/IP setting for the Ethernet port

EL600x, EL602x Version: 4.6 85


Commissioning

5.2.2 Notes regarding ESI device description

Installation of the latest ESI device description

The TwinCAT EtherCAT master/System Manager needs the device description files for the devices to be
used in order to generate the configuration in online or offline mode. The device descriptions are contained
in the so-called ESI files (EtherCAT Slave Information) in XML format. These files can be requested from the
respective manufacturer and are made available for download. An *.xml file may contain several device
descriptions.

The ESI files for Beckhoff EtherCAT devices are available on the Beckhoff website.

The ESI files should be stored in the TwinCAT installation directory.

Default settings:
• TwinCAT 2: C:\TwinCAT\IO\EtherCAT
• TwinCAT 3: C:\TwinCAT\3.1\Config\Io\EtherCAT

The files are read (once) when a new System Manager window is opened, if they have changed since the
last time the System Manager window was opened.

A TwinCAT installation includes the set of Beckhoff ESI files that was current at the time when the TwinCAT
build was created.

For TwinCAT 2.11/TwinCAT 3 and higher, the ESI directory can be updated from the System Manager, if the
programming PC is connected to the Internet; by
• TwinCAT 2: Option → “Update EtherCAT Device Descriptions”
• TwinCAT 3: TwinCAT → EtherCAT Devices → “Update Device Descriptions (via ETG Website)…”

The TwinCAT ESI Updater [} 90] is available for this purpose.

ESI
The *.xml files are associated with *.xsd files, which describe the structure of the ESI XML files. To
update the ESI device descriptions, both file types should therefore be updated.

Device differentiation

EtherCAT devices/slaves are distinguished by four properties, which determine the full device identifier. For
example, the device identifier EL2521-0025-1018 consists of:
• family key “EL”
• name “2521”
• type “0025”
• and revision “1018”

Fig. 87: Identifier structure

The order identifier consisting of name + type (here: EL2521-0010) describes the device function. The
revision indicates the technical progress and is managed by Beckhoff. In principle, a device with a higher
revision can replace a device with a lower revision, unless specified otherwise, e.g. in the documentation.
Each revision has its own ESI description. See further notes [} 9].

86 Version: 4.6 EL600x, EL602x


Commissioning

Online description

If the EtherCAT configuration is created online through scanning of real devices (see section Online setup)
and no ESI descriptions are available for a slave (specified by name and revision) that was found, the
System Manager asks whether the description stored in the device should be used. In any case, the System
Manager needs this information for setting up the cyclic and acyclic communication with the slave correctly.

Fig. 88: OnlineDescription information window (TwinCAT 2)

In TwinCAT 3 a similar window appears, which also offers the Web update:

Fig. 89: Information window OnlineDescription (TwinCAT 3)

If possible, the Yes is to be rejected and the required ESI is to be requested from the device manufacturer.
After installation of the XML/XSD file the configuration process should be repeated.

NOTE
Changing the ‘usual’ configuration through a scan
ü If a scan discovers a device that is not yet known to TwinCAT, distinction has to be made between two
cases. Taking the example here of the EL2521-0000 in the revision 1019
a) no ESI is present for the EL2521-0000 device at all, either for the revision 1019 or for an older revision.
The ESI must then be requested from the manufacturer (in this case Beckhoff).
b) an ESI is present for the EL2521-0000 device, but only in an older revision, e.g. 1018 or 1017.
In this case an in-house check should first be performed to determine whether the spare parts stock al-
lows the integration of the increased revision into the configuration at all. A new/higher revision usually
also brings along new features. If these are not to be used, work can continue without reservations with
the previous revision 1018 in the configuration. This is also stated by the Beckhoff compatibility rule.

Refer in particular to the chapter ‘General notes on the use of Beckhoff EtherCAT IO components’ and for
manual configuration to the chapter ‘Offline configuration creation’ [} 91].

If the OnlineDescription is used regardless, the System Manager reads a copy of the device description from
the EEPROM in the EtherCAT slave. In complex slaves the size of the EEPROM may not be sufficient for the
complete ESI, in which case the ESI would be incomplete in the configurator. Therefore it’s recommended
using an offline ESI file with priority in such a case.

The System Manager creates for online recorded device descriptions a new file
“OnlineDescription0000...xml” in its ESI directory, which contains all ESI descriptions that were read online.

EL600x, EL602x Version: 4.6 87


Commissioning

Fig. 90: File OnlineDescription.xml created by the System Manager

Is a slave desired to be added manually to the configuration at a later stage, online created slaves are
indicated by a prepended symbol “>” in the selection list (see Figure “Indication of an online recorded ESI of
EL2521 as an example”).

Fig. 91: Indication of an online recorded ESI of EL2521 as an example

If such ESI files are used and the manufacturer's files become available later, the file OnlineDescription.xml
should be deleted as follows:
• close all System Manager windows
• restart TwinCAT in Config mode
• delete "OnlineDescription0000...xml"
• restart TwinCAT System Manager

This file should not be visible after this procedure, if necessary press <F5> to update

OnlineDescription for TwinCAT 3.x


In addition to the file described above "OnlineDescription0000...xml" , a so called EtherCAT cache
with new discovered devices is created by TwinCAT 3.x, e.g. under Windows 7:

(Please note the language settings of the OS!)


You have to delete this file, too.

Faulty ESI file

If an ESI file is faulty and the System Manager is unable to read it, the System Manager brings up an
information window.

Fig. 92: Information window for faulty ESI file (left: TwinCAT 2; right: TwinCAT 3)

88 Version: 4.6 EL600x, EL602x


Commissioning

Reasons may include:


• Structure of the *.xml does not correspond to the associated *.xsd file → check your schematics
• Contents cannot be translated into a device description → contact the file manufacturer

EL600x, EL602x Version: 4.6 89


Commissioning

5.2.3 TwinCAT ESI Updater


For TwinCAT 2.11 and higher, the System Manager can search for current Beckhoff ESI files automatically, if
an online connection is available:

Fig. 93: Using the ESI Updater (>= TwinCAT 2.11)

The call up takes place under:


“Options” → "Update EtherCAT Device Descriptions"

Selection under TwinCAT 3:

Fig. 94: Using the ESI Updater (TwinCAT 3)

The ESI Updater (TwinCAT 3) is a convenient option for automatic downloading of ESI data provided by
EtherCAT manufacturers via the Internet into the TwinCAT directory (ESI = EtherCAT slave information).
TwinCAT accesses the central ESI ULR directory list stored at ETG; the entries can then be viewed in the
Updater dialog, although they cannot be changed there.

The call up takes place under:


“TwinCAT“ → „EtherCAT Devices“ → “Update Device Description (via ETG Website)…“.

5.2.4 Distinction between Online and Offline


The distinction between online and offline refers to the presence of the actual I/O environment (drives,
terminals, EJ-modules). If the configuration is to be prepared in advance of the system configuration as a
programming system, e.g. on a laptop, this is only possible in “Offline configuration” mode. In this case all
components have to be entered manually in the configuration, e.g. based on the electrical design.

If the designed control system is already connected to the EtherCAT system and all components are
energised and the infrastructure is ready for operation, the TwinCAT configuration can simply be generated
through “scanning” from the runtime system. This is referred to as online configuration.

In any case, during each startup the EtherCAT master checks whether the slaves it finds match the
configuration. This test can be parameterised in the extended slave settings. Refer to note “Installation of
the latest ESI-XML device description” [} 86].

For preparation of a configuration:


• the real EtherCAT hardware (devices, couplers, drives) must be present and installed
• the devices/modules must be connected via EtherCAT cables or in the terminal/ module strand in the
same way as they are intended to be used later

90 Version: 4.6 EL600x, EL602x


Commissioning

• the devices/modules be connected to the power supply and ready for communication
• TwinCAT must be in CONFIG mode on the target system.

The online scan process consists of:


• detecting the EtherCAT device [} 96] (Ethernet port at the IPC)
• detecting the connected EtherCAT devices [} 97]. This step can be carried out independent of the
preceding step
• troubleshooting [} 100]

The scan with existing configuration [} 101] can also be carried out for comparison.

5.2.5 OFFLINE configuration creation

Creating the EtherCAT device

Create an EtherCAT device in an empty System Manager window.

Fig. 95: Append EtherCAT device (left: TwinCAT 2; right: TwinCAT 3)

Select type ‘EtherCAT’ for an EtherCAT I/O application with EtherCAT slaves. For the present publisher/
subscriber service in combination with an EL6601/EL6614 terminal select “EtherCAT Automation Protocol
via EL6601”.

Fig. 96: Selecting the EtherCAT connection (TwinCAT 2.11, TwinCAT 3)

Then assign a real Ethernet port to this virtual device in the runtime system.

Fig. 97: Selecting the Ethernet port

EL600x, EL602x Version: 4.6 91


Commissioning

This query may appear automatically when the EtherCAT device is created, or the assignment can be set/
modified later in the properties dialog; see Fig. “EtherCAT device properties (TwinCAT 2)”.

Fig. 98: EtherCAT device properties (TwinCAT 2)

TwinCAT 3: the properties of the EtherCAT device can be opened by double click on “Device .. (EtherCAT)”
within the Solution Explorer under “I/O”:

Selecting the Ethernet port


Ethernet ports can only be selected for EtherCAT devices for which the TwinCAT real-time driver is
installed. This has to be done separately for each port. Please refer to the respective installation
page [} 80].

Defining EtherCAT slaves

Further devices can be appended by right-clicking on a device in the configuration tree.

Fig. 99: Appending EtherCAT devices (left: TwinCAT 2; right: TwinCAT 3)

The dialog for selecting a new device opens. Only devices for which ESI files are available are displayed.

Only devices are offered for selection that can be appended to the previously selected device. Therefore the
physical layer available for this port is also displayed (Fig. “Selection dialog for new EtherCAT device”, A). In
the case of cable-based Fast-Ethernet physical layer with PHY transfer, then also only cable-based devices
are available, as shown in Fig. “Selection dialog for new EtherCAT device”. If the preceding device has
several free ports (e.g. EK1122 or EK1100), the required port can be selected on the right-hand side (A).

Overview of physical layer


• “Ethernet”: cable-based 100BASE-TX: EK couplers, EP boxes, devices with RJ45/M8/M12 connector

92 Version: 4.6 EL600x, EL602x


Commissioning

• “E-Bus”: LVDS “terminal bus”, “EJ-module”: EL/ES terminals, various modular modules

The search field facilitates finding specific devices (since TwinCAT 2.11 or TwinCAT 3).

Fig. 100: Selection dialog for new EtherCAT device

By default only the name/device type is used as selection criterion. For selecting a specific revision of the
device the revision can be displayed as “Extended Information”.

Fig. 101: Display of device revision

In many cases several device revisions were created for historic or functional reasons, e.g. through
technological advancement. For simplification purposes (see Fig. “Selection dialog for new EtherCAT
device”) only the last (i.e. highest) revision and therefore the latest state of production is displayed in the
selection dialog for Beckhoff devices. To show all device revisions available in the system as ESI
descriptions tick the “Show Hidden Devices” check box, see Fig. “Display of previous revisions”.

EL600x, EL602x Version: 4.6 93


Commissioning

Fig. 102: Display of previous revisions

Device selection based on revision, compatibility


The ESI description also defines the process image, the communication type between master and
slave/device and the device functions, if applicable. The physical device (firmware, if available) has
to support the communication queries/settings of the master. This is backward compatible, i.e.
newer devices (higher revision) should be supported if the EtherCAT master addresses them as an
older revision. The following compatibility rule of thumb is to be assumed for Beckhoff EtherCAT
Terminals/ Boxes/ EJ-modules:
device revision in the system >= device revision in the configuration
This also enables subsequent replacement of devices without changing the configuration (different
specifications are possible for drives).

Example:

If an EL2521-0025-1018 is specified in the configuration, an EL2521-0025-1018 or higher (-1019, -1020) can


be used in practice.

Fig. 103: Name/revision of the terminal

If current ESI descriptions are available in the TwinCAT system, the last revision offered in the selection
dialog matches the Beckhoff state of production. It is recommended to use the last device revision when
creating a new configuration, if current Beckhoff devices are used in the real application. Older revisions
should only be used if older devices from stock are to be used in the application.

In this case the process image of the device is shown in the configuration tree and can be parameterised as
follows: linking with the task, CoE/DC settings, plug-in definition, startup settings, ...

94 Version: 4.6 EL600x, EL602x


Commissioning

Fig. 104: EtherCAT terminal in the TwinCAT tree (left: TwinCAT 2; right: TwinCAT 3)

EL600x, EL602x Version: 4.6 95


Commissioning

5.2.6 ONLINE configuration creation

Detecting/scanning of the EtherCAT device

The online device search can be used if the TwinCAT system is in CONFIG mode. This can be indicated by
a symbol right below in the information bar:

• on TwinCAT 2 by a blue display “Config Mode” within the System Manager window: .

• on TwinCAT 3 within the user interface of the development environment by a symbol .

TwinCAT can be set into this mode:

• TwinCAT 2: by selection of in the Menubar or by “Actions” → “Set/Reset TwinCAT to Config


Mode…”

• TwinCAT 3: by selection of in the Menubar or by „TwinCAT“ → “Restart TwinCAT (Config Mode)“

Online scanning in Config mode


The online search is not available in RUN mode (production operation). Note the differentiation be-
tween TwinCAT programming system and TwinCAT target system.

The TwinCAT 2 icon ( ) or TwinCAT 3 icon ( ) within the Windows-Taskbar always shows the
TwinCAT mode of the local IPC. Compared to that, the System Manager window of TwinCAT 2 or the user
interface of TwinCAT 3 indicates the state of the target system.

Fig. 105: Differentiation local/target system (left: TwinCAT 2; right: TwinCAT 3)

Right-clicking on “I/O Devices” in the configuration tree opens the search dialog.

Fig. 106: Scan Devices (left: TwinCAT 2; right: TwinCAT 3)

This scan mode attempts to find not only EtherCAT devices (or Ethernet ports that are usable as such), but
also NOVRAM, fieldbus cards, SMB etc. However, not all devices can be found automatically.

Fig. 107: Note for automatic device scan (left: TwinCAT 2; right: TwinCAT 3)

96 Version: 4.6 EL600x, EL602x


Commissioning

Ethernet ports with installed TwinCAT real-time driver are shown as “RT Ethernet” devices. An EtherCAT
frame is sent to these ports for testing purposes. If the scan agent detects from the response that an
EtherCAT slave is connected, the port is immediately shown as an “EtherCAT Device” .

Fig. 108: Detected Ethernet devices

Via respective checkboxes devices can be selected (as illustrated in Fig. “Detected Ethernet devices” e.g.
Device 3 and Device 4 were chosen). After confirmation with “OK” a device scan is suggested for all selected
devices, see Fig.: “Scan query after automatic creation of an EtherCAT device”.

Selecting the Ethernet port


Ethernet ports can only be selected for EtherCAT devices for which the TwinCAT real-time driver is
installed. This has to be done separately for each port. Please refer to the respective installation
page [} 80].

Detecting/Scanning the EtherCAT devices

Online scan functionality


During a scan the master queries the identity information of the EtherCAT slaves from the slave
EEPROM. The name and revision are used for determining the type. The respective devices are lo-
cated in the stored ESI data and integrated in the configuration tree in the default state defined
there.

Fig. 109: Example default state

NOTE
Slave scanning in practice in series machine production
The scanning function should be used with care. It is a practical and fast tool for creating an initial configu-
ration as a basis for commissioning. In series machine production or reproduction of the plant, however, the
function should no longer be used for the creation of the configuration, but if necessary for comparison
[} 101] with the defined initial configuration.Background: since Beckhoff occasionally increases the revision
version of the delivered products for product maintenance reasons, a configuration can be created by such
a scan which (with an identical machine construction) is identical according to the device list; however, the
respective device revision may differ from the initial configuration.

Example:

Company A builds the prototype of a machine B, which is to be produced in series later on. To do this the
prototype is built, a scan of the IO devices is performed in TwinCAT and the initial configuration ‘B.tsm’ is
created. The EL2521-0025 EtherCAT terminal with the revision 1018 is located somewhere. It is thus built
into the TwinCAT configuration in this way:

EL600x, EL602x Version: 4.6 97


Commissioning

Fig. 110: Installing EthetCAT terminal with revision -1018

Likewise, during the prototype test phase, the functions and properties of this terminal are tested by the
programmers/commissioning engineers and used if necessary, i.e. addressed from the PLC ‘B.pro’ or the
NC. (the same applies correspondingly to the TwinCAT 3 solution files).

The prototype development is now completed and series production of machine B starts, for which Beckhoff
continues to supply the EL2521-0025-0018. If the commissioning engineers of the series machine production
department always carry out a scan, a B configuration with the identical contents results again for each
machine. Likewise, A might create spare parts stores worldwide for the coming series-produced machines
with EL2521-0025-1018 terminals.

After some time Beckhoff extends the EL2521-0025 by a new feature C. Therefore the FW is changed,
outwardly recognizable by a higher FW version and a new revision -1019. Nevertheless the new device
naturally supports functions and interfaces of the predecessor version(s); an adaptation of ‘B.tsm’ or even
‘B.pro’ is therefore unnecessary. The series-produced machines can continue to be built with ‘B.tsm’ and
‘B.pro’; it makes sense to perform a comparative scan [} 101] against the initial configuration ‘B.tsm’ in order
to check the built machine.

However, if the series machine production department now doesn’t use ‘B.tsm’, but instead carries out a
scan to create the productive configuration, the revision -1019 is automatically detected and built into the
configuration:

Fig. 111: Detection of EtherCAT terminal with revision -1019

This is usually not noticed by the commissioning engineers. TwinCAT cannot signal anything either, since
virtually a new configuration is created. According to the compatibility rule, however, this means that no
EL2521-0025-1018 should be built into this machine as a spare part (even if this nevertheless works in the
vast majority of cases).

In addition, it could be the case that, due to the development accompanying production in company A, the
new feature C of the EL2521-0025-1019 (for example, an improved analog filter or an additional process
data for the diagnosis) is discovered and used without in-house consultation. The previous stock of spare
part devices are then no longer to be used for the new configuration ‘B2.tsm’ created in this way.Þ if series
machine production is established, the scan should only be performed for informative purposes for
comparison with a defined initial configuration. Changes are to be made with care!

If an EtherCAT device was created in the configuration (manually or through a scan), the I/O field can be
scanned for devices/slaves.

Fig. 112: Scan query after automatic creation of an EtherCAT device (left: TwinCAT 2; right: TwinCAT 3)

98 Version: 4.6 EL600x, EL602x


Commissioning

Fig. 113: Manual triggering of a device scan on a specified EtherCAT device (left: TwinCAT 2; right:
TwinCAT 3)

In the System Manager (TwinCAT 2) or the User Interface (TwinCAT 3) the scan process can be monitored
via the progress bar at the bottom in the status bar.

Fig. 114: Scan progressexemplary by TwinCAT 2

The configuration is established and can then be switched to online state (OPERATIONAL).

Fig. 115: Config/FreeRun query (left: TwinCAT 2; right: TwinCAT 3)

In Config/FreeRun mode the System Manager display alternates between blue and red, and the EtherCAT
device continues to operate with the idling cycle time of 4 ms (default setting), even without active task (NC,
PLC).

Fig. 116: Displaying of “Free Run” and “Config Mode” toggling right below in the status bar

Fig. 117: TwinCAT can also be switched to this state by using a button (left: TwinCAT 2; right: TwinCAT 3)

The EtherCAT system should then be in a functional cyclic state, as shown in Fig. “Online display example”.

EL600x, EL602x Version: 4.6 99


Commissioning

Fig. 118: Online display example

Please note:
• all slaves should be in OP state
• the EtherCAT master should be in “Actual State” OP
• “frames/sec” should match the cycle time taking into account the sent number of frames
• no excessive “LostFrames” or CRC errors should occur

The configuration is now complete. It can be modified as described under manual procedure [} 91].

Troubleshooting

Various effects may occur during scanning.


• An unknown device is detected, i.e. an EtherCAT slave for which no ESI XML description is available.
In this case the System Manager offers to read any ESI that may be stored in the device. This case is
described in the chapter "Notes regarding ESI device description".
• Device are not detected properly
Possible reasons include:
- faulty data links, resulting in data loss during the scan
- slave has invalid device description
The connections and devices should be checked in a targeted manner, e.g. via the emergency scan.
Then re-run the scan.

Fig. 119: Faulty identification

In the System Manager such devices may be set up as EK0000 or unknown devices. Operation is not
possible or meaningful.

100 Version: 4.6 EL600x, EL602x


Commissioning

Scan over existing Configuration

NOTE
Change of the configuration after comparison
With this scan (TwinCAT 2.11 or 3.1) only the device properties vendor (manufacturer), device name and
revision are compared at present! A ‘ChangeTo’ or ‘Copy’ should only be carried out with care, taking into
consideration the Beckhoff IO compatibility rule (see above). The device configuration is then replaced by
the revision found; this can affect the supported process data and functions.

If a scan is initiated for an existing configuration, the actual I/O environment may match the configuration
exactly or it may differ. This enables the configuration to be compared.

Fig. 120: Identical configuration (left: TwinCAT 2; right: TwinCAT 3)

If differences are detected, they are shown in the correction dialog, so that the user can modify the
configuration as required.

Fig. 121: Correction dialog

It is advisable to tick the “Extended Information” check box to reveal differences in the revision.

EL600x, EL602x Version: 4.6 101


Commissioning

Colour Explanation
green This EtherCAT slave matches the entry on the other side. Both type and revision match.
blue This EtherCAT slave is present on the other side, but in a different revision. This other
revision can have other default values for the process data as well as other/additional
functions.
If the found revision is higher than the configured revision, the slave may be used provided
compatibility issues are taken into account.
If the found revision is lower than the configured revision, it is likely that the slave cannot be
used. The found device may not support all functions that the master expects based on the
higher revision number.
light blue This EtherCAT slave is ignored (“Ignore” button)
red • This EtherCAT slave is not present on the other side.
• It is present, but in a different revision, which also differs in its properties from the one
specified.
The compatibility principle then also applies here: if the found revision is higher than the
configured revision, use is possible provided compatibility issues are taken into account,
since the successor devices should support the functions of the predecessor devices.
If the found revision is lower than the configured revision, it is likely that the slave cannot
be used. The found device may not support all functions that the master expects based on
the higher revision number.

Device selection based on revision, compatibility


The ESI description also defines the process image, the communication type between master and
slave/device and the device functions, if applicable. The physical device (firmware, if available) has
to support the communication queries/settings of the master. This is backward compatible, i.e.
newer devices (higher revision) should be supported if the EtherCAT master addresses them as an
older revision. The following compatibility rule of thumb is to be assumed for Beckhoff EtherCAT
Terminals/ Boxes/ EJ-modules:
device revision in the system >= device revision in the configuration
This also enables subsequent replacement of devices without changing the configuration (different
specifications are possible for drives).

Example:

If an EL2521-0025-1018 is specified in the configuration, an EL2521-0025-1018 or higher (-1019, -1020) can


be used in practice.

Fig. 122: Name/revision of the terminal

If current ESI descriptions are available in the TwinCAT system, the last revision offered in the selection
dialog matches the Beckhoff state of production. It is recommended to use the last device revision when
creating a new configuration, if current Beckhoff devices are used in the real application. Older revisions
should only be used if older devices from stock are to be used in the application.

In this case the process image of the device is shown in the configuration tree and can be parameterised as
follows: linking with the task, CoE/DC settings, plug-in definition, startup settings, ...

102 Version: 4.6 EL600x, EL602x


Commissioning

Fig. 123: Correction dialog with modifications

Once all modifications have been saved or accepted, click “OK” to transfer them to the real *.tsm
configuration.

Change to Compatible Type

TwinCAT offers a function “Change to Compatible Type…” for the exchange of a device whilst retaining the
links in the task.

Fig. 124: Dialog “Change to Compatible Type…” (left: TwinCAT 2; right: TwinCAT 3)

This function is preferably to be used on AX5000 devices.

Change to Alternative Type

The TwinCAT System Manager offers a function for the exchange of a device: Change to Alternative Type

Fig. 125: TwinCAT 2 Dialog Change to Alternative Type

EL600x, EL602x Version: 4.6 103


Commissioning

If called, the System Manager searches in the procured device ESI (in this example: EL1202-0000) for
details of compatible devices contained there. The configuration is changed and the ESI-EEPROM is
overwritten at the same time – therefore this process is possible only in the online state (ConfigMode).

5.2.7 EtherCAT subscriber configuration


In the left-hand window of the TwinCAT 2 System Manager or the Solution Explorer of the TwinCAT 3
Development Environment respectively, click on the element of the terminal within the tree you wish to
configure (in the example: EL3751 Terminal 3).

Fig. 126: Branch element as terminal EL3751

In the right-hand window of the TwinCAT System manager (TwinCAT 2) or the Development Environment
(TwinCAT 3), various tabs are now available for configuring the terminal. And yet the dimension of
complexity of a subscriber determines which tabs are provided. Thus as illustrated in the example above the
terminal EL3751 provides many setup options and also a respective number of tabs are available. On the
contrary by the terminal EL1004 for example the tabs "General", "EtherCAT", "Process Data" and “Online“
are available only. Several terminals, as for instance the EL6695 provide special functions by a tab with its
own terminal name, so “EL6695” in this case. A specific tab “Settings” by terminals with a wide range of
setup options will be provided also (e.g. EL3751).

„General“ tab

Fig. 127: “General” tab

Name Name of the EtherCAT device


Id Number of the EtherCAT device
Type EtherCAT device type
Comment Here you can add a comment (e.g. regarding the
system).
Disabled Here you can deactivate the EtherCAT device.
Create symbols Access to this EtherCAT slave via ADS is only
available if this control box is activated.

104 Version: 4.6 EL600x, EL602x


Commissioning

„EtherCAT“ tab

Fig. 128: „EtherCAT“ tab

Type EtherCAT device type


Product/Revision Product and revision number of the EtherCAT device
Auto Inc Addr. Auto increment address of the EtherCAT device. The
auto increment address can be used for addressing
each EtherCAT device in the communication ring
through its physical position. Auto increment
addressing is used during the start-up phase when
the EtherCAT master allocates addresses to the
EtherCAT devices. With auto increment addressing
the first EtherCAT slave in the ring has the address
0000hex. For each further slave the address is
decremented by 1 (FFFFhex, FFFEhex etc.).
EtherCAT Addr. Fixed address of an EtherCAT slave. This address is
allocated by the EtherCAT master during the start-up
phase. Tick the control box to the left of the input field
in order to modify the default value.
Previous Port Name and port of the EtherCAT device to which this
device is connected. If it is possible to connect this
device with another one without changing the order of
the EtherCAT devices in the communication ring,
then this combination field is activated and the
EtherCAT device to which this device is to be
connected can be selected.
Advanced Settings This button opens the dialogs for advanced settings.

The link at the bottom of the tab points to the product page for this EtherCAT device on the web.

“Process Data” tab

Indicates the configuration of the process data. The input and output data of the EtherCAT slave are
represented as CANopen process data objects (Process Data Objects, PDOs). The user can select a PDO
via PDO assignment and modify the content of the individual PDO via this dialog, if the EtherCAT slave
supports this function.

EL600x, EL602x Version: 4.6 105


Commissioning

Fig. 129: “Process Data” tab

The process data (PDOs) transferred by an EtherCAT slave during each cycle are user data which the
application expects to be updated cyclically or which are sent to the slave. To this end the EtherCAT master
(Beckhoff TwinCAT) parameterizes each EtherCAT slave during the start-up phase to define which process
data (size in bits/bytes, source location, transmission type) it wants to transfer to or from this slave. Incorrect
configuration can prevent successful start-up of the slave.

For Beckhoff EtherCAT EL, ES, EM, EJ and EP slaves the following applies in general:
• The input/output process data supported by the device are defined by the manufacturer in the ESI/XML
description. The TwinCAT EtherCAT Master uses the ESI description to configure the slave correctly.
• The process data can be modified in the system manager. See the device documentation.
Examples of modifications include: mask out a channel, displaying additional cyclic information, 16-bit
display instead of 8-bit data size, etc.
• In so-called “intelligent” EtherCAT devices the process data information is also stored in the CoE
directory. Any changes in the CoE directory that lead to different PDO settings prevent successful
startup of the slave. It is not advisable to deviate from the designated process data, because the
device firmware (if available) is adapted to these PDO combinations.

If the device documentation allows modification of process data, proceed as follows (see Figure “Configuring
the process data”).
• A: select the device to configure
• B: in the “Process Data” tab select Input or Output under SyncManager (C)
• D: the PDOs can be selected or deselected
• H: the new process data are visible as linkable variables in the system manager
The new process data are active once the configuration has been activated and TwinCAT has been
restarted (or the EtherCAT master has been restarted)
• E: if a slave supports this, Input and Output PDO can be modified simultaneously by selecting a so-
called PDO record (“predefined PDO settings”).

106 Version: 4.6 EL600x, EL602x


Commissioning

Fig. 130: Configuring the process data

Manual modification of the process data


According to the ESI description, a PDO can be identified as “fixed” with the flag “F” in the PDO
overview (Fig. “Configuring the process data”, J). The configuration of such PDOs cannot be
changed, even if TwinCAT offers the associated dialog (“Edit”). In particular, CoE content cannot be
displayed as cyclic process data. This generally also applies in cases where a device supports
download of the PDO configuration, “G”. In case of incorrect configuration the EtherCAT slave usu-
ally refuses to start and change to OP state. The System Manager displays an “invalid SM cfg” log-
ger message: This error message (“invalid SM IN cfg” or “invalid SM OUT cfg”) also indicates the
reason for the failed start.

A detailed description [} 112] can be found at the end of this section.

„Startup“ tab

The Startup tab is displayed if the EtherCAT slave has a mailbox and supports the CANopen over EtherCAT
(CoE) or Servo drive over EtherCAT protocol. This tab indicates which download requests are sent to the
mailbox during startup. It is also possible to add new mailbox requests to the list display. The download
requests are sent to the slave in the same order as they are shown in the list.

EL600x, EL602x Version: 4.6 107


Commissioning

Fig. 131: „Startup“ tab

Column Description
Transition Transition to which the request is sent. This can either be
• the transition from pre-operational to safe-operational (PS), or
• the transition from safe-operational to operational (SO).
If the transition is enclosed in "<>" (e.g. <PS>), the mailbox request is fixed and cannot be
modified or deleted by the user.
Protocol Type of mailbox protocol
Index Index of the object
Data Date on which this object is to be downloaded.
Comment Description of the request to be sent to the mailbox

Move Up This button moves the selected request up by one


position in the list.
Move Down This button moves the selected request down by one
position in the list.
New This button adds a new mailbox download request to
be sent during startup.
Delete This button deletes the selected entry.
Edit This button edits an existing request.

“CoE – Online” tab

The additional CoE - Online tab is displayed if the EtherCAT slave supports the CANopen over EtherCAT
(CoE) protocol. This dialog lists the content of the object list of the slave (SDO upload) and enables the user
to modify the content of an object from this list. Details for the objects of the individual EtherCAT devices can
be found in the device-specific object descriptions.

108 Version: 4.6 EL600x, EL602x


Commissioning

Fig. 132: “CoE – Online” tab

Object list display

Column Description
Index Index and sub-index of the object
Name Name of the object
Flags RW The object can be read, and data can be written to the object (read/write)
RO The object can be read, but no data can be written to the object (read only)
P An additional P identifies the object as a process data object.
Value Value of the object

EL600x, EL602x Version: 4.6 109


Commissioning

Update List The Update list button updates all objects in the
displayed list
Auto Update If this check box is selected, the content of the
objects is updated automatically.
Advanced The Advanced button opens the Advanced Settings
dialog. Here you can specify which objects are
displayed in the list.

Fig. 133: Dialog “Advanced settings”

Online - via SDO Information If this option button is selected, the list of the objects
included in the object list of the slave is uploaded
from the slave via SDO information. The list below
can be used to specify which object types are to be
uploaded.
Offline - via EDS File If this option button is selected, the list of the objects
included in the object list is read from an EDS file
provided by the user.

110 Version: 4.6 EL600x, EL602x


Commissioning

„Online“ tab

Fig. 134: „Online“ tab

State Machine

Init This button attempts to set the EtherCAT device to


the Init state.
Pre-Op This button attempts to set the EtherCAT device to
the pre-operational state.
Op This button attempts to set the EtherCAT device to
the operational state.
Bootstrap This button attempts to set the EtherCAT device to
the Bootstrap state.
Safe-Op This button attempts to set the EtherCAT device to
the safe-operational state.
Clear Error This button attempts to delete the fault display. If an
EtherCAT slave fails during change of state it sets an
error flag.
Example: An EtherCAT slave is in PREOP state (pre-
operational). The master now requests the SAFEOP
state (safe-operational). If the slave fails during
change of state it sets the error flag. The current state
is now displayed as ERR PREOP. When the Clear
Error button is pressed the error flag is cleared, and
the current state is displayed as PREOP again.
Current State Indicates the current state of the EtherCAT device.
Requested State Indicates the state requested for the EtherCAT
device.

DLL Status

Indicates the DLL status (data link layer status) of the individual ports of the EtherCAT slave. The DLL status
can have four different states:

EL600x, EL602x Version: 4.6 111


Commissioning

Status Description
No Carrier / Open No carrier signal is available at the port, but the port
is open.
No Carrier / Closed No carrier signal is available at the port, and the port
is closed.
Carrier / Open A carrier signal is available at the port, and the port is
open.
Carrier / Closed A carrier signal is available at the port, but the port is
closed.

File Access over EtherCAT

Download With this button a file can be written to the EtherCAT


device.
Upload With this button a file can be read from the EtherCAT
device.

"DC" tab (Distributed Clocks)

Fig. 135: "DC" tab (Distributed Clocks)

Operation Mode Options (optional):


• FreeRun
• SM-Synchron
• DC-Synchron (Input based)
• DC-Synchron
Advanced Settings… Advanced settings for readjustment of the real time determinant TwinCAT-
clock

Detailed information to Distributed Clocks are specified on http://infosys.beckhoff.com:

Fieldbus Components → EtherCAT Terminals → EtherCAT System documentation → EtherCAT basics →


Distributed Clocks

5.2.7.1 Detailed description of Process Data tab

Sync Manager

Lists the configuration of the Sync Manager (SM).


If the EtherCAT device has a mailbox, SM0 is used for the mailbox output (MbxOut) and SM1 for the mailbox
input (MbxIn).
SM2 is used for the output process data (outputs) and SM3 (inputs) for the input process data.

If an input is selected, the corresponding PDO assignment is displayed in the PDO Assignment list below.

PDO Assignment

PDO assignment of the selected Sync Manager. All PDOs defined for this Sync Manager type are listed
here:

112 Version: 4.6 EL600x, EL602x


Commissioning

• If the output Sync Manager (outputs) is selected in the Sync Manager list, all RxPDOs are displayed.
• If the input Sync Manager (inputs) is selected in the Sync Manager list, all TxPDOs are displayed.

The selected entries are the PDOs involved in the process data transfer. In the tree diagram of the System
Manager these PDOs are displayed as variables of the EtherCAT device. The name of the variable is
identical to the Name parameter of the PDO, as displayed in the PDO list. If an entry in the PDO assignment
list is deactivated (not selected and greyed out), this indicates that the input is excluded from the PDO
assignment. In order to be able to select a greyed out PDO, the currently selected PDO has to be deselected
first.

Activation of PDO assignment


ü If you have changed the PDO assignment, in order to activate the new PDO assignment,
a) the EtherCAT slave has to run through the PS status transition cycle (from pre-operational to
safe-operational) once (see Online tab [} 111]),
b) and the System Manager has to reload the EtherCAT slaves

( button for TwinCAT 2 or button for TwinCAT 3)

PDO list

List of all PDOs supported by this EtherCAT device. The content of the selected PDOs is displayed in the
PDO Content list. The PDO configuration can be modified by double-clicking on an entry.

Column Description
Index PDO index.
Size Size of the PDO in bytes.
Name Name of the PDO.
If this PDO is assigned to a Sync Manager, it appears as a variable of the slave with this
parameter as the name.
Flags F Fixed content: The content of this PDO is fixed and cannot be changed by the
System Manager.
M Mandatory PDO. This PDO is mandatory and must therefore be assigned to a
Sync Manager! Consequently, this PDO cannot be deleted from the PDO
Assignment list
SM Sync Manager to which this PDO is assigned. If this entry is empty, this PDO does not take
part in the process data traffic.
SU Sync unit to which this PDO is assigned.

PDO Content

Indicates the content of the PDO. If flag F (fixed content) of the PDO is not set the content can be modified.

Download

If the device is intelligent and has a mailbox, the configuration of the PDO and the PDO assignments can be
downloaded to the device. This is an optional feature that is not supported by all EtherCAT slaves.

PDO Assignment

If this check box is selected, the PDO assignment that is configured in the PDO Assignment list is
downloaded to the device on startup. The required commands to be sent to the device can be viewed in the
Startup [} 107] tab.

PDO Configuration

If this check box is selected, the configuration of the respective PDOs (as shown in the PDO list and the
PDO Content display) is downloaded to the EtherCAT slave.

EL600x, EL602x Version: 4.6 113


Commissioning

5.3 General Notes - EtherCAT Slave Application


This summary briefly deals with a number of aspects of EtherCAT Slave operation under TwinCAT. More
detailed information on this may be found in the corresponding sections of, for instance, the EtherCAT
System Documentation.

Diagnosis in real time: WorkingCounter, EtherCAT State and Status

Generally speaking an EtherCAT Slave provides a variety of diagnostic information that can be used by the
controlling task.

This diagnostic information relates to differing levels of communication. It therefore has a variety of sources,
and is also updated at various times.

Any application that relies on I/O data from a fieldbus being correct and up to date must make diagnostic
access to the corresponding underlying layers. EtherCAT and the TwinCAT System Manager offer
comprehensive diagnostic elements of this kind. Those diagnostic elements that are helpful to the controlling
task for diagnosis that is accurate for the current cycle when in operation (not during commissioning) are
discussed below.

Fig. 136: Selection of the diagnostic information of an EtherCAT Slave

In general, an EtherCAT Slave offers


• communication diagnosis typical for a slave (diagnosis of successful participation in the exchange of
process data, and correct operating mode)
This diagnosis is the same for all slaves.

as well as
• function diagnosis typical for a channel (device-dependent)
See the corresponding device documentation

The colors in Fig. “Selection of the diagnostic information of an EtherCAT Slave” also correspond to the
variable colors in the System Manager, see Fig. “Basic EtherCAT Slave Diagnosis in the PLC”.

Colour Meaning
yellow Input variables from the Slave to the EtherCAT Master, updated in every cycle
red Output variables from the Slave to the EtherCAT Master, updated in every cycle
green Information variables for the EtherCAT Master that are updated acyclically. This means that
it is possible that in any particular cycle they do not represent the latest possible status. It is
therefore useful to read such variables through ADS.

114 Version: 4.6 EL600x, EL602x


Commissioning

Fig. “Basic EtherCAT Slave Diagnosis in the PLC” shows an example of an implementation of basic
EtherCAT Slave Diagnosis. A Beckhoff EL3102 (2-channel analogue input terminal) is used here, as it offers
both the communication diagnosis typical of a slave and the functional diagnosis that is specific to a channel.
Structures are created as input variables in the PLC, each corresponding to the process image.

Fig. 137: Basic EtherCAT Slave Diagnosis in the PLC

The following aspects are covered here:

EL600x, EL602x Version: 4.6 115


Commissioning

Code Function Implementation Application/evaluation


A The EtherCAT Master's diagnostic infor- At least the DevState is to be evaluated for
mation the most recent cycle in the PLC.
updated acyclically (yellow) or provided The EtherCAT Master's diagnostic informa-
acyclically (green). tion offers many more possibilities than are
treated in the EtherCAT System Documenta-
tion. A few keywords:
• CoE in the Master for communication
with/through the Slaves
• Functions from TcEtherCAT.lib
• Perform an OnlineScan
B In the example chosen (EL3102) the Status In order for the higher-level PLC task (or cor-
EL3102 comprises two analogue input responding control applications) to be able to
• the bit significations may be
channels that transmit a single function rely on correct data, the function status must
found in the device
status for the most recent cycle. be evaluated there. Such information is
documentation
therefore provided with the process data for
• other devices may supply the most recent cycle.
more information, or none
that is typical of a slave
C For every EtherCAT Slave that has cyclic WcState (Working Counter) In order for the higher-level PLC task (or cor-
process data, the Master displays, using responding control applications) to be able to
0: valid real-time communication in
what is known as a WorkingCounter, rely on correct data, the communication sta-
the last cycle
whether the slave is participating success- tus of the EtherCAT Slave must be evaluated
fully and without error in the cyclic ex- 1: invalid real-time communication there. Such information is therefore provided
change of process data. This important, el- This may possibly have effects on with the process data for the most recent cy-
ementary information is therefore provided the process data of other Slaves cle.
for the most recent cycle in the System that are located in the same Syn-
Manager cUnit
1. at the EtherCAT Slave, and, with
identical contents
2. as a collective variable at the
EtherCAT Master (see Point A)
for linking.
D Diagnostic information of the EtherCAT State Information variables for the EtherCAT Mas-
Master which, while it is represented at the ter that are updated acyclically. This means
current Status (INIT..OP) of the
slave for linking, is actually determined by that it is possible that in any particular cycle
Slave. The Slave must be in OP
the Master for the Slave concerned and they do not represent the latest possible sta-
(=8) when operating normally.
represented there. This information cannot tus. It is therefore possible to read such vari-
be characterized as real-time, because it AdsAddr ables through ADS.
• is only rarely/never changed, The ADS address is useful for
except when the system starts up communicating from the PLC/task
via ADS with the EtherCAT Slave,
• is itself determined acyclically (e.g.
e.g. for reading/writing to the CoE.
EtherCAT Status)
The AMS-NetID of a slave corre-
sponds to the AMS-NetID of the
EtherCAT Master; communication
with the individual Slave is possible
via the port (= EtherCAT address).

NOTE
Diagnostic information
It is strongly recommended that the diagnostic information made available is evaluated so that the applica-
tion can react accordingly.

CoE Parameter Directory

The CoE parameter directory (CanOpen-over-EtherCAT) is used to manage the set values for the slave
concerned. Changes may, in some circumstances, have to be made here when commissioning a relatively
complex EtherCAT Slave. It can be accessed through the TwinCAT System Manager, see Fig. “EL3102,
CoE directory”:

116 Version: 4.6 EL600x, EL602x


Commissioning

Fig. 138: EL3102, CoE directory

EtherCAT System Documentation


The comprehensive description in the EtherCAT System Documentation (EtherCAT Basics --> CoE
Interface) must be observed!

A few brief extracts:


• Whether changes in the online directory are saved locally in the slave depends on the device. EL
terminals (except the EL66xx) are able to save in this way.
• The user must manage the changes to the StartUp list.

Commissioning aid in the TwinCAT System Manager

Commissioning interfaces are being introduced as part of an ongoing process for EL/EP EtherCAT devices.
These are available in TwinCAT System Managers from TwinCAT 2.11R2 and above. They are integrated
into the System Manager through appropriately extended ESI configuration files.

EL600x, EL602x Version: 4.6 117


Commissioning

Fig. 139: Example of commissioning aid for a EL3204

This commissioning process simultaneously manages


• CoE Parameter Directory
• DC/FreeRun mode
• the available process data records (PDO)

Although the "Process Data", "DC", "Startup" and "CoE-Online" that used to be necessary for this are still
displayed, it is recommended that, if the commissioning aid is used, the automatically generated settings are
not changed by it.

The commissioning tool does not cover every possible application of an EL/EP device. If the available setting
options are not adequate, the user can make the DC, PDO and CoE settings manually, as in the past.

EtherCAT State: automatic default behaviour of the TwinCAT System Manager and manual operation

After the operating power is switched on, an EtherCAT Slave must go through the following statuses
• INIT
• PREOP
• SAFEOP
• OP

to ensure sound operation. The EtherCAT Master directs these statuses in accordance with the initialization
routines that are defined for commissioning the device by the ES/XML and user settings (Distributed Clocks
(DC), PDO, CoE). See also the section on "Principles of Communication, EtherCAT State Machine [} 25]" in
this connection. Depending how much configuration has to be done, and on the overall communication,
booting can take up to a few seconds.

The EtherCAT Master itself must go through these routines when starting, until it has reached at least the
OP target state.

The target state wanted by the user, and which is brought about automatically at start-up by TwinCAT, can
be set in the System Manager. As soon as TwinCAT reaches the status RUN, the TwinCAT EtherCAT
Master will approach the target states.

118 Version: 4.6 EL600x, EL602x


Commissioning

Standard setting

The advanced settings of the EtherCAT Master are set as standard:


• EtherCAT Master: OP
• Slaves: OP
This setting applies equally to all Slaves.

Fig. 140: Default behaviour of the System Manager

In addition, the target state of any particular Slave can be set in the "Advanced Settings" dialogue; the
standard setting is again OP.

Fig. 141: Default target state in the Slave

EL600x, EL602x Version: 4.6 119


Commissioning

Manual Control

There are particular reasons why it may be appropriate to control the states from the application/task/PLC.
For instance:
• for diagnostic reasons
• to induce a controlled restart of axes
• because a change in the times involved in starting is desirable

In that case it is appropriate in the PLC application to use the PLC function blocks from the TcEtherCAT.lib,
which is available as standard, and to work through the states in a controlled manner using, for instance,
FB_EcSetMasterState.

It is then useful to put the settings in the EtherCAT Master to INIT for master and slave.

Fig. 142: PLC function blocks

Note regarding E-Bus current

EL/ES terminals are placed on the DIN rail at a coupler on the terminal strand. A Bus Coupler can supply the
EL terminals added to it with the E-bus system voltage of 5 V; a coupler is thereby loadable up to 2 A as a
rule. Information on how much current each EL terminal requires from the E-bus supply is available online
and in the catalogue. If the added terminals require more current than the coupler can supply, then power
feed terminals (e.g. EL9410) must be inserted at appropriate places in the terminal strand.

The pre-calculated theoretical maximum E-Bus current is displayed in the TwinCAT System Manager as a
column value. A shortfall is marked by a negative total amount and an exclamation mark; a power feed
terminal is to be placed before such a position.

120 Version: 4.6 EL600x, EL602x


Commissioning

Fig. 143: Illegally exceeding the E-Bus current

From TwinCAT 2.11 and above, a warning message "E-Bus Power of Terminal..." is output in the logger
window when such a configuration is activated:

Fig. 144: Warning message for exceeding E-Bus current

NOTE
Caution! Malfunction possible!
The same ground potential must be used for the E-Bus supply of all EtherCAT terminals in a terminal block!

EL600x, EL602x Version: 4.6 121


Commissioning

5.4 Operating modes and process data


Version notes

The single-channel EL60x1 has been developed and enhanced over a number of years. Through further
development of the EL6001/EL6021 the following functional extensions have been implemented:
• from firmware (FW) 05 / hardware (HW) 03, (EL6001); firmware (FW) 04 / hardware (HW) 03, (EL6021)
the objects for status monitoring and parameterization are also available from index 0x6000 (profile-
specific objects) and can be parameterized in the TwinCAT System Manager, depending on the
hardware.
• from firmware (FW) 06 / hardware (HW) 03, (EL6021) the command mode [} 127] is supported
• from firmware 08 (EL6001) the 16-bit process data interface for sending/receiving of > 8 bit is
supported
• from firmware 11 (EL6001) all integer baud rates 1000…115200 baud can be used.

Older versions of the EL6001/EL6021 do not support this functionality!


from FW/HW ESI Control/status/parameterizing objects
area
EL6001 01/01 from EL6001-0000-0000 Index 0x300n:01 (Control-Word)
EL6021 01/01 from EL6021-0000-0000 Index 0x310n:01 (Status-Word)
Index 0x4070 (Data bytes in send buffer)
Index 0x4071 (Data bytes in receive buffer)
Index 0x4072 (Diagnosis)
Index 0x4073 (Baud rate)
Index 0x4074 (Data frame)
Index 0x4075 (Feature bits)
EL6001 05/03 from EL6001-0000-0016 in addition to the above described objects:
EL6021 04/03 from EL6021-0000-0016 Index 0x6000 (COM inputs)
Index 0x7000 (COM outputs)
Index 0xA000 (COM Diag data
Index 0x8000 (COM settings)
EL6021 06/03 from EL6021-0000-0018 in addition to the above described objects:
Index 0xB000 (Command)
EL6001 08/03 from EL6001-0000-0019 in addition to the above described objects:
Objects for 16-bit PDO
EL6001 11/11 from EL6001-0000-0020 All baud rates 1000…115200 via
explicitBaudrate implemented

The EL6002/EL6022 devices with revision -0016 already feature objects in the 6000, 7000 and 8000 range
from the first release.

Compatibility in the case of service


Example: An EL6001/EL6021 employed and projected with Hardware 03 or higher cannot be re-
placed by an EL6001/EL6021 with an older hardware version (<03)! The reverse case can be imple-
mented without problem!

Process data monitoring


• WcState: if ≠ 0, this EtherCAT device does not take part in the process data traffic
• State: if ≠ 8, the EtherCAT device is not in OP (operational) status
• TxPDO state, SyncError: if ≠ 0, then no valid process data are available, e.g. caused by broken
wire
• TxPDO Toggle: if this bit is toggling, a new set of process data is available

122 Version: 4.6 EL600x, EL602x


Commissioning

StartUp entries (hardware < 03)

StartUp list entry


For the EL6001/EL6021 with hardware < 03, the startUp entries can only be set in the transition
from SafeOP to OP (S -> O). The default setting is PreOP -> SafeOP (P -> S). When creating
StartUp entries, ensure that the checkbox "S -> O" is ticked (see Fig.)!

Fig. 145: StartUp entry with transition S -> O

Process data

As delivered, 22 bytes of user data and 1 control/status word are transferred.

The process data are generated from CoE objects 0x6000 (Inputs) and 0x7000 (Outputs) and are described
in chapter Object description and parameterization [} 168] in detail.

Enlarged process image 50x 16-bit

An enlarged process data interface is necessary for communication with >8 data bits. If the terminal supports
this (see Communication features [} 131]) a 50-word interface can be set as an alternative to the 22-byte
interface (PDOs 0x1605 and 0x1A05). This can be used with every encryption regulation (7xx, 8xx), but only
makes sense with a regulation >8 bits, e.g. 9N1. In each case the least significant bits must be occupied by
the data bits, i.e. in the case of 9N1 the 9 least significant bits in the data words.

EL600x, EL602x Version: 4.6 123


Commissioning

Process data of the EL60x2 from revision -0016

EL60x2 from revision -0016

Sync Manager (SM) – PDO Assignment

SM2, PDO assignment 0x1C12


Index Index of ex- Size Name PDO content
cluded (byte.bit)
PDOs
0x1600 - 24.0 COM Outputs Channel1 Index 0x7000:01 - Ctrl__Transmit
request
Index 0x7000:02 - Ctrl__Receive
accepted
Index 0x7000:03 - Ctrl__Init request
Index 0x7000:04 - Ctrl__Send
continous
Index 0x7000:09 - Ctrl__Output
length
Index 0x7000:11 - Data out 0
--
Index 0x7000:26
0x1601 - 24.0 COM Outputs Channel2 Index 0x7010:01
Index 0x7010:02
Index 0x7010:03
Index 0x7010:04
Index 0x7010:09
Index 0x7010:11
--
Index 0x7010:26
0x1604 - 24.0 COM Outputs Channel1 Index 0x7001:01 - Ctrl
(default) Index 0x7000:11 - Data out 0
--
Index 0x7000:26
0x1605 - 24.0 COM Outputs Channel2 Index 0x7011:01 - Ctrl
(default) Index 0x7010:11 - Data out 0
--
Index 0x7010:26

124 Version: 4.6 EL600x, EL602x


Commissioning

SM2, PDO assignment 0x1C13


Index Index of ex- Size Name PDO content
cluded (byte.bit)
PDOs
0x1A00 - 24.0 COM Inputs Channel1 Index 0x6000:01 - Status__Transmit
accepted
Index 0x6000:02 - Status__Receive
request
Index 0x6000:03 - Status__Init
accepted
Index 0x6000:04 - Status__Buffer
full
Index 0x6000:05 - Status__Input
length
Index 0x6000:06 - Status__Framing
error
Index 0x6000:07 - Status__Overrun
error
Index 0x6000:09 - Status__Input
length
Index 0x6000:11 - Data in 0
--
Index 0x6000:26
0x1A01 - 24.0 COM Inputs Channel2 Index 0x6010:01
Index 0x6010:02
Index 0x6010:03
Index 0x6010:04 - Status__Buffer
full
Index 0x6010:05
Index 0x6010:06
Index 0x6010:07
Index 0x6010:09
Index 0x6010:11
--
Index 0x6010:26
0x1A04(defa - 24.0 COM Inputs Channel1 Index 0x6001:01
ult) Index 0x6000:11
--
Index 0x6000:26
0x1A05(defa - 24.0 COM Inputs Channel2 Index 0x6011:01
ult) Index 0x6010:11
--
Index 0x6010:26

Features and application notes

Optional features are generally set in the CoE directory (CAN over EtherCAT, index 0x80n0).

Parameterization via the CoE list (CAN over EtherCAT)


Please note the following general CoE information when using/manipulating the CoE parameters: -
Keep a startup list if components have to be replaced - Differentiate between online/offline dictio-
nary, ensure existence of current XML description - use “CoE reload” for resetting changes Please
note especially for the EL60xx, if any changes are made to the communication settings (baud rate,
data frame, feature bits), an InitRequest via the control word is required to apply the changes.

EL600x, EL602x Version: 4.6 125


Commissioning

The following CoE settings are possible from object 0x8000 and are shown below in their default settings:

Fig. 146: “CoE - Online, EL60x4 terminals” tab

Transfer rates

The terminal has a process image of 22 bytes of user data. It possible to transmit or receive these 22 bytes
every second cycle at the most.
The data is transferred from the terminal to the controller in the first cycle. In the second cycle, the controller
must acknowledge that it has accepted the data.
Therefore, if the cycle time is 10 ms, 50 times 22 bytes can be transmitted per second.

With a set data frame of 8N1, each transmitted byte consists of a start bit, eight data bits and a stop bit. This
is equivalent to 10 bits per user byte.

With the above mentioned settings, a continuous data transfer rate of:
 •    50[1/s]*22[Byte]*10[Bit] = 11000 bps
can be achieved.

The next lower baud rate is 9600 baud. Accordingly, continuous transfer at a maximum baud rate of 9600
can be secured with a cycle time of 10 ms.

From firmware 11 the CoE 0x8000:1B supports with explicitBaudrate all baud rates 1000…115200 baud.
When the baud rate is selected, the compatibility of the remote station to the set baud rate must be taken
into account.
If only low quantities of data are to be transmitted or received sporadically (e.g. bar code scanner) the baud
rate can also be set higher, or the cycle time can be enlarged.
If the controller cannot fetch the data quickly enough from the terminal, the data will be stored intermediately
in the internal buffer of the terminal. The buffer for received data has a size of 864 bytes. If this is exhausted,
all further data will be lost.

Another scenario: the controller transfers significantly more data to the terminal than the latter can transmit.
For a ‘baud rate’ setting of 300 and a ‘data frame’ setting of 8N1, the terminal can only transmit 30 bytes per
second. However, if more than these 30 bytes per second are received, a 128 byte transmit buffer will be
written to first in this case also. Once this is full, all further data will be lost.

126 Version: 4.6 EL600x, EL602x


Commissioning

Optimization of transfer rates

In normal operating mode the data received will be adopted immediately into the process image. In order to
enable a continuous flow of data, the ‘Enable transfer rate optimization’ option in the Settings object is
activated as standard. Due to this switch, the data will first be stored intermediately in the receive buffer
(864 bytes).

The data will only be copied into the process image if no further character is received for 16 bit periods or if
the buffer is full.

Continuous transmission of data

Usually the EL60xx terminal automatically decides when to send the data bytes contained in the buffer. For
many applications it is helpful to have a continuous data stream. For this purpose, the Beckhoff EL60xx
terminals feature the ‘Enable send FIFO data continuous’ setting in the Settings object. If this switch is set.
• The internal send buffer (128 bytes) must be filled first. To this end, data will be sent from the controller
to the terminal as in a normal data transfer.
• Data transfer from the buffer commences with a rising edge of the bit “Send continuous”
• If the data has been transferred, the terminal informs the controller by setting the “InitAccepted” bit. “Init
accepted” is cleared with “Send continuous”.

This setting enables up to 128 bytes to be transferred without long delays, even with slower EtherCAT cycle
times and high baud rates.

The terminal tries to leave as little distance as possible between the telegrams by seamlessly following each
stop bit with the next start bit. Nevertheless, in two-channel mode high baud rates may result in short pauses
between telegrams. A 20-byte data block may be sent in two blocks of 5 and 15 or 7 and 13 telegrams, for
example, or with a different distribution. In a two-channel terminal channel 1 is given priority.

Prioritization

Since received data normally cannot be repeated, it has a higher priority than data to be transmitted.
Furthermore, the priority decreases as the channel number increases. Hence, the reception of data on
channel 1 has the highest priority.

Command mode

From firmware 06 / revision -0018 the EL6021 supports the so-called command mode. Certain terminal
functions can be used and controlled through optional combination and/or sequence of commands. The
following functions are currently supported:
• Multi-data frame feature: (from firmware 06) change of coding during ongoing data communication
(sending)
To this end the send buffer of the terminal should be filled with the bytes to be sent (note the maximum
buffer size). As soon as the send process is started via the control word, the first n bytes are sent
based on coding A, the remaining bytes in the buffer are sent with coding B. The buffer can then be
refilled and sent accordingly. Example: The first byte is sent with mark parity, the remaining bytes with
space parity.
Sequence:
◦ After each startup/restart of the EL60xx EtherCAT slave the parameterization has to be repeated.
The command function is not stored in the event of a power failure.
◦ Activation of SendContinuous mode through writing of 0x1 after 0x8000:04
◦ Activation of the multi-data frame feature through writing of 0x2001 after request 0xB000:01 
Check that 0xB000:02 = 0
◦ Specify coding A through writing of 0x2100 + [date frame code] after 0xB000:01
Example: 8E2 = 0x12 --> write value 0x2112
Check that 0xB000:02 = 0
◦ Specify n bytes to be sent in coding A through writing of 0x2200 + [n] after 0xB000:01
Check that 0xB000:02 = 0
◦ Specify coding B through writing of 0x2300 + [date frame code] after 0xB000:01
Check that 0xB000:02 = 0

EL600x, EL602x Version: 4.6 127


Commissioning

◦ Start sending through rising edge of Ctrl SendContinuous


◦ Terminal signals completed transfer through InitAccepted = 1. InitAccepted is reset with
SendContinuous.
CmdNameMeaning0x2000 + ControlByteCmdControlByteBit 0: Enable MultiDataFrame feature Bit
1..7: do not use0x2100 + Valuefirst data frameselect preferred value from data frame table0x2200
+ NoOfBytesNo of bytesNo of bytes transfered with first data frame0x2300 + Valuesecond data
frameselect prefered value from data frame table
Note: In this mode coding 8M1 and 8S1 is also supported, although this coding cannot be selected
via 0x8000:15.
• Further features can be implemented on request

Data transfer examples

Initialization

Initialization is performed prior to the first transmission/reception. The terminal is thereby parameterized with
the data from the corresponding Settings object.

Procedure:

1. Set “Init request” to 1


2. The terminal confirms successful initialization by setting “Init accepted”
3. Reset “Init request”
4. The terminal sets “Init accepted” to 0

The terminal is now ready for data exchange.

Data transmission from the controller to the terminal (send 2 characters)

1. Set “Output length” to 2


2. Fill “Data Out 0” and “Data Out 1” with user data
3. Change the state of “Transmit request”
4. The terminal acknowledges receipt of the data by changing the state of the “Transmit accepted” bit.

Data transmission from the terminal to the controller (receive characters)

1. The terminal indicates that there is new data in the process image by changing the state of the “Re-
ceive request” bit.
2. The number of bytes received is written in “Input length”
3. The controller acknowledges acceptance of the bytes by changing the state of “Receive request”

128 Version: 4.6 EL600x, EL602x


Commissioning

5.5 Hints regarding TcVirtualComDriver


In case the EL60xx is to cooperate with the TwinCAT Virtual Serial COM Driver, here are a few hints:

Usually the customer-specific higher-level Windows application sets the desired feature of the COM interface
according to the application, e.g. 2400 baud and 7N2 coding. Therefore, the customer-specific entries made
before parameterization in the CoE StartUp entries, the Settings dialogue, the VirtualComPort or the device
CoE are usually irrelevant.

Fig. 147: Each higher level (if available or activated) dictates the communication features to the level below
it.

NOTE
TcVirtualComDriver version
Check whether the desired Baud rate/coding combination of the TcVirtualComDriver version and EL/EP ter-
minal used by you is also supported. If this is not the case:
   ● it may not be possible to open the COM port
   ● an ADS error message may appear in the ADS logger in the System Manager
   ● a CoE error message may appear in the ADS logger
The TcVirtualComDriver supports ExplicitBaudrate (CoE 0x80n0:1B) from version 1.18.

If the COM application has then set the features (such as baud rate) during the runtime, the correct setting
can be checked against it in the Online CoE, see fig.

EL600x, EL602x Version: 4.6 129


Commissioning

Fig. 148: Checking the settings desired by the COM application in the CoE

Fig. 149: Default startup entries of a EL6002 (example) – only the default entries (in this case 0x1C12 and
0x1C13) are required

Fig. 150: VirtualComDriver Settings (example)

The settings are relevant only if no specification of the COM features is made or can be made from the
application. The COM port is opened with these default settings.

Exception: TransferRateOptimization, SendFifoDataContinously and FiFoThreshold are to be set only from


TwinCAT.

130 Version: 4.6 EL600x, EL602x


Commissioning

5.6 Communication features


Central features of the EL60xx devices for serial communication are baud rate and data telegram structure/
coding on the field side. The devices differ in the available features. For a clearer overview, the devices are
listed here with the parameters available according to the firmware/hardware revision.

Check on the Beckhoff web page whether more up-to-date documentation is available.

Device overview
Available baud rate Available coding
Device Baud rate CoE Value from FW/HW Coding CoE Value from FW/HW
[baud] [0x80n0:11] [0x80n0:15]
EL6001 2400 4 7E1 1
4800 5 7O1 2
9600 6 8N1 3
12000 14 from FW07 8E1 4
14400 15 from FW07 8O1 5
19200 7 7E2 9
38400 8 7O2 10
57600 9 8N2 11
115200 10 8E2 12
104167 Explicit from FW08 8O2 13
Baudrate
[0x8000:1B]
9N1 32 from FW08
Extended data
frame [} 168]
[0x8000:1C]
1000…115200 Explicit from FW11
*) Baudrate
[0x8000:1B]
EL6002 110 Explicit from FW03 7E1 1
Baudrate
[} 129]
[0x80n0:1B]
150 Explicit from FW03 7O1 2
Baudrate
[} 129]
[0x80n0:1B]
300 1 8N1 3
600 2 8E1 4
1200 3 8O1 5
2400 4 7N2 8 from FW03
4800 5 7E2 9
9600 6 7O2 10
19200 7 8N2 11
38400 8 8E2 12
57600 9 8O2 13
115200 10

EL600x, EL602x Version: 4.6 131


Commissioning

Device overview
Available baud rate Available coding
Device Baud rate CoE Value from FW/HW Coding CoE Value from FW/HW
[baud] [x80n0:11] [x80n0:15]
EL6021 2400 4 7E1 1
4800 5 7O1 2
9600 6 8N1 3
19200 7 8E1 4
38400 8 8O1 5
57600 9 7E2 9
115200 10 7O2 10
8N2 11
8E2 12
8O2 13
8S1 18 Command
mode from
FW06
8M1 19 Command
mode from
FW06
EL6022 300 1 7E1 1
600 2 7O1 2
1200 3 8N1 3
2400 4 8E1 4
4800 5 8O1 5
9600 6 7E2 9
19200 7 7O2 10
38400 8 8N2 11
57600 9 8E2 12
115200 10 8O2 13
EP6022 300 1 7E1 1
600 2 7O1 2
1200 3 8N1 3
2400 4 8E1 4
4800 5 8O1 5
9600 6 7E2 9
19200 7 7O2 10
38400 8 8N2 11
57600 9 8E2 12
115200 10 8O2 13

  *) any integer baud rate can be set as an int32 value. The frequency error across all baud rates is < 0,6 %.

5.7 LIN Master Feature EL6001


Description of “LIN master support”

The EL6001 realizes a bus interface for RS232 levels. From software version 10, the EL6001 features an
auxiliary function for sending and receiving LIN telegrams. This function does not cover the formal treatment
of the protocol layers for LIN (“protocol stack”) or a physical LIN connection. Instead, the EL6001 can deal
with the prolonged start/end mark of a LIN telegram in write and read direction.

132 Version: 4.6 EL600x, EL602x


Commissioning

”Above” the terminal a LIN stack is required that is implemented in the PLC, for example, below the terminal
an RS232 <-> 5/12 V level converter is required.

Before using this function, please check the suitability in your system, since the EL6001 does not have a fully
comprehensive LIN implementation!

A complete LIN frame results from a master query with directly following slave response. As master
operating, the terminal sends the master frame and receives the slave data. With activated LIN functionality
of the EL6001 (since FW10) a “sync break” and a “sync byte” is always output before the “protected
identifier” (PID). In fact this terminal is therefore able to operate as a data receiving slave, too, but not as a
data sending slave node.

Activation

The addition of a “sync break” and “sync field” for sending, which is required for LIN, can be activated via the
“Command” object. To this end, enter the value 0x3000 in the CoE object 0xB000:01 [} 164]. The response
can be read in CoE object 0xB000:03 with the values 0x01 0x00 0x00 0x4C 0x49 0x4E (4C 49 4E = ASCII
“LIN”) as confirmation of the activation of this function. The terminal is then ready for receiving frames on the
LIN bus containing the 13-bit “sync break” and the “sync field” (0x55), and to make only the following
information in the receive data and to output these IDs during sending.

This setting is not permanently stored in the terminal and has to be written again after each new startup. The
startup [} 107] list can be used to circumvent this.

User-specific baud rate

Any already available baud rate and or the baud rate 10417 can be entered in the object “Explicit
baudrate” (0x8000:1B).

Further parameters

The following settings within CoE object 0x8000 [} 146] are necessary to ensure correct function in LIN
mode:

Index:Subindex Name Value


0x8000:01 Enable RTS/CTS FALSE
0x8000:02 Enable XON/XOFF supported tx FALSE
data
0x8000:03 Enable XON/XOFF supported rx FALSE
data
0x8000:04 Enable send FIFO data continuous FALSE
0x8000:05 Enable transfer rate optimization TRUE
0x8000:15 Dataframe 3 (8N1)
0x8000:1A Rx buffer full notification See objects for commissioning
[} 146].

Operation

The application of the control and status words remains unchanged in LIN mode.

In LIN mode, the EL6001 automatically precedes the user data with the “Break field” and the “Sync byte”
field. During receiving these two fields are automatically removed.

The process image should be used as follows:

EL600x, EL602x Version: 4.6 133


Commissioning

Process data Contents


Ctrl.Output length Number of user data bytes (n) + 2
Data Out 0 Protected ID field (PID = Protected identifier field)
Data Out 1 Data byte 1

Data Out n Data byte n


Data Out n+1 Checksum

EL6001 LIN example

The following LIN communication example is intended to illustrate that participation of a PLC controller via
the EL6001 terminal in a LIN cluster is possible by activating the complementary LIN functionality via the
0xB000 CoE “command” object in combination with a physical conversion of RS-232 to the LIN bus.

Hardware connection based on a UART-LIN converter

The implementation of the physical layer as a basic prerequisite for LIN communication includes the
provision of one-wire bus with corresponding signal levels 0V / 12V. This is best done with an RS232-LIN
converter, which is connected to a sub-D connector and on the other side provides three poles for ground,
power supply and the electrical connection to the one-wire LIN-bus.

The use of an RS232-LIN converter requires a sub-D 9-pin connector to be connected to the EL6001
terminal, as shown in the diagram:

Fig. 151: RS232-LIN sub-D connector connected to the EL6001 terminal

Electrical connections between the EL6001 terminal and the sub-D 9-pin connector:
• RxD →pin 2
• TxD →pin 3
• GND → pin 5

Programming in ST

A LIN communication can be represented by a PLC “master task”, whereby a master sends an
“unconditional frame”, as usual with a LIN bus, and only outputs the PID (protocol identifier) of a known slave
node on the LIN bus, thereby generally requesting data from the respective slave. The chapter on
commissioning contains a relevant programming example [} 136].

134 Version: 4.6 EL600x, EL602x


Commissioning

In this example the slave has the ID 0x07; the master therefore sends the ID 0x07 on the bus, including the
calculated parity, resulting in the PID field 0x47. The message on the LIN bus then looks as follows:

Fig. 152: LIN frame example: Query from master to node with ID 0x07

Fig. 153: LIN frame example: ID0x07 with data 0xEA,0xBD,0x08,0xB7 + checksum 0x97

Oscilloscope recordings LIN frame with ID 0x07:

Fig. 154: Left: Query on the LIN bus with PID 0x47, right: LIN frame with the same PID and data, including
checksum

EL600x, EL602x Version: 4.6 135


Commissioning

5.8 Example programs


Using the sample programs
This document contains sample applications of our products for certain areas of application. The
application notes provided here are based on typical features of our products and only serve as ex-
amples. The notes contained in this document explicitly do not refer to specific applications. The
customer is therefore responsible for assessing and deciding whether the product is suitable for a
particular application. We accept no responsibility for the completeness and correctness of the
source code contained in this document. We reserve the right to modify the content of this docu-
ment at any time and accept no responsibility for errors and missing information.

5.8.1 Sample program 1

https://infosys.beckhoff.com/content/1033/el600x_el602x/Resources/zip/1719190795.zip

Connection of a serial bar code scanner

In this example a bar code reader is connected to the EL6001. Characters will be read by the reader until the
ASCII character 0x0D (13dec, CR) is received.

Data:
• Quick task for executing the serial communication: 1 ms cycle time
• Standard PLC task: 10 ms cycle time
• Barcode scanner on channel 1
• TwinCAT 2.11 required
• “TwinCAT PLC Serial Communication” supplement is required

A detailed description for the use of the serial communication library is stored in the Beckhoff Information
System.

Beckhoff Information System -> TwinCAT -> TwinCAT PLC -> TwinCAT libraries for PC-based systems ->
TwinCAT PLC Library : Serial communication

Starting the example program

The application examples have been tested with a test configuration and are described accordingly.

Certain deviations when setting up actual applications are possible.

The following hardware and software were used for the test configuration:
• TwinCAT master PC with Windows XP Professional SP 3, TwinCAT version 2.11 (Build 1528) and
INTEL PRO/100 VE Ethernet adapter
• Beckhoff EK1100 EtherCAT coupler, EL6001 terminals
• Serial barcode scanner with 9-pole sub-D connector

Procedure for starting the program


• After clicking the Download button, save the zip file locally on your hard disk, and unzip the *.TSM
(configuration) and the *.PRO (PLC program) files into a temporary working folder
• Run the *.TSM file and the *.PRO file; the TwinCAT System Manager and TwinCAT PLC will open
• Connect the hardware in accordance with fig. 1 and connect the Ethernet adapter of your PC to the
EtherCAT coupler (further information on this can be found in the corresponding coupler manuals)
• Select the local Ethernet adapter (with real-time driver, if one) under System configuration, I/O
configuration, I/O devices, Device (EtherCAT); on the “Adapter” tab choose “Search...”, select the
appropriate adapter and confirm (see Fig. 2a + 2b)

136 Version: 4.6 EL600x, EL602x


Commissioning

Fig. 155: Searching the Ethernet adapter

Fig. 156: Selection and confirmation of the Ethernet adapter

Activation of the configuration and confirmation (Fig. 3a +3b)

Fig. 157: Activation of the configuration

EL600x, EL602x Version: 4.6 137


Commissioning

Fig. 158: Confirming the activation of the configuration

• Confirming new variable mapping, restart in RUN mode (Fig. 4a + 4b)

Fig. 159: Generating variable mapping

Fig. 160: Restarting TwinCAT in RUN mode

• In TwinCAT PLC, under the “Project” menu, select “Rebuild all” to compile the project (Fig. 5)

Fig. 161: Compile project

• In TwinCAT PLC: log in with the “F11” button, confirm loading the program (Fig. 6), run the program
with the “F5” button

138 Version: 4.6 EL600x, EL602x


Commissioning

Fig. 162: Confirming program start

• After the character 0x13 has been received, the barcode is stored in “LastBarcode”

Fig. 163: Received barcode

5.8.2 Sample program 2

https://infosys.beckhoff.com/content/1033/el600x_el602x/Resources/zip/1719192971.zip

Reading and interpreting time telegrams

This example shows a way to process and interpret the most diverse serial time protocols in the PLC. To this
end, IEC61131-PLC blocks will be presented that interpret the bit stream arriving at the PLC and, if
necessary, extract the time/place information. This information can be used, for example, to synchronize
controllers or record movements.

In this example, it is assumed that the data is delivered via a 22-byte interface by a Beckhoff EL/KL60xx
serial data exchange terminal.

Background information

Not only in maritime applications is time and place information transported via serial buses: In the majority of
cases an existing source distributes its information to lower level listeners/listeners cyclically or after a trigger
via RS232 / RS485, USB or Ethernet.
A very large number of telegram formats exists worldwide for the distribution of time and place information;
these are also known as ‘sentences’. Such a telegram consists of n bytes of data and is characterized by:
• Start and end characters STX, ETX for telegram recognition, possibly more than one end character
• a defined and fixed length
• a defined structure
• checksum (not necessary)
• type designations in the sentence if necessary

The most diverse organizations and companies have developed open or proprietary formats for specific
purposes of use. Therefore, two sample implementations will be presented in this example that can easily be
adapted to other specific protocols. The telegram formats in the example are the Meinberg Standard and
NMEA0183 v2.3 type RMC.

EL600x, EL602x Version: 4.6 139


Commissioning

Sources of information

GPS or radio controlled clock gateways are used as data transmitters in the serial sector. These devices
receive the respective time signal (GPS via satellite or radio controlled clock via long wave) and convert it to
the serial, wire-bound transmission e.g. RS232 with 8N1. The gateway often contains a local clock source in
order to be able to continue distributing reliable time information for a certain time in the event of a short-term
failure of the reference signal (GPS, radio transmitter). In Central Europe, the German DCF77 transmitter
can be used.
If necessary, further information from the reference signal can be used:
• GPS: location information (W/N and height), upcoming clock change DCF77: weather information,
major incidents
• DCF77: weather information, major incidents

Synchronization of lower level time slaves

In general, lower level slaves should be adjusted to the time gateway, i.e. they should synchronize their time.
The following are necessary for this:
• Offset: the absolute deviation of the slave’s own clock from the gateway reference time – this
information can be transmitted, for example, acyclically and serially if it is known when the time
information is to be considered valid. Gaining these offset-information is possible via the serial
transport route from this example.
• the frequency ratio: a high-precision cyclic signal from the gateway to the slaves allows drift processes
to be compensated and might state the time when the above absolute offset is valid. One example of
such a signal is the widespread PPS (pulses per second).

If the serial telegram from the gateway is placed cyclically to the bus, the time of the first bit can often be
interpreted as a PPS signal. In the block in this example, this information would be lost; only the absolute
time information is evaluated.

Time formats

Time telegrams conforming to the NMEA0183 standard are widespread. Please note:
• there are currently (as of 2009) 8 versions of NMEA0183 1.5 to 4.00 within the NMEA0183 standard –
the structure of telegrams may have changed between the versions.
• 70 different formats are defined in NMEA0183 v2.30 alone; device manufacturers can create their own
formats in addition.
• The telegram is called a sentence
• A TalkerID (2 characters) and a TypeID (3 characters) at the start define the type of sentence used.
• A checksum is calculated for the telegram.
• Information can be found online at www.nmea.org or elsewhere.

Furthermore, many proprietary formats exist, such as Meinberg Standard, Siemens SINEC H1 and SAT
1703, or military formats, such as the IRIG codes (USA).

Using the sample program

The PLC project contains 2 function blocks (FBs), which must be linked exclusively with an EL/KL600x. Then
collect the received bytes from the terminal and interpret the contents as far as possible. The FBs cover:
• Meinberg Standard
• NMEA0183 v2.3 type RMC

For other time formats, you can create your own interpretation FBs on the basis of a known telegram
structure; contact your device manufacturer regarding this.

Hardware used in the example: EK1100 and EL6001 (also EL600x, KL600x)
The FB to be tested must be linked with its process data to the terminal in the System Manager (22-byte
process image and control/status word).
The NMEA block is linked in the example. The baud rate of the terminal must be set to match your
transmitter.

140 Version: 4.6 EL600x, EL602x


Commissioning

References
• www.beuth.de, IEC61162: based on NMEA2000
• http://gpsinformation.net private, via NMEA, many formats: http://www.gpsinformation.org/dale/
nmea.htm
http://www.nmea.de/nmea0183datensaetze.html
• http://www.meinberg.de/german/info/irig.htm, IRIG codes

5.8.3 Sample program 3 (LIN)


Download (TwinCAT 3 example program):

https://infosys.beckhoff.com/content/1033/el600x_el602x/Resources/zip/1805853195.zip

Global variables for LIN master example program


VAR_GLOBAL
nSetBaudrate : UINT := 10417; // Für Rx-Delay-Berechnung
(* I/O variables for EL6001 terminal acting as Master*)
COMin_EL6001_MASTER AT %I* : EL6inData22B;(* linked to the EL6001 in the TwinCAT System Manager *)
COMout_EL6001_MASTER AT %Q*: EL6outData22B;(* linked to the EL6001 in the TwinCAT System Manager *)
RxBuffer_MASTER : ComBuffer;(* Receive data buffer; used with all receive function blocks *)
TxBuffer_MASTER : ComBuffer;(* Transmit data buffer; used with all receive function blocks *)
END_VAR

Data types for LIN master-slave example program


TYPE tDataFrame : ARRAY[0..8] OF BYTE; END_TYPE // Datentyp für ein LIN-Frame

Function for adding data length information and parity bits:

Declaration part:
FUNCTION F_ADD_LIN_NODE_PARITY : BYTE
VAR_INPUT
nNodeID:BYTE; // Inputvariable: node-Id
nReqLen:BYTE; // Inputvariable: length-identification: 2,4,8 Byte-Frame
END_VAR
VAR
bParity0:BYTE; // Internal intermediate value parity 0
bParity1:BYTE; // Internal intermediate value parity 1
nPrepId:BYTE; // Intermediate value for PID
END_VAR

Execution part:
nPrepId := nNodeID OR SHL(nReqLen,4);

bParity0 :=
(nNodeID AND 2#0001)
XOR (SHR((nNodeID AND 2#0010), 1))
XOR (SHR((nNodeID AND 2#0100), 2))
XOR (SHR((nNodeID AND 2#0001_0000), 4));

bParity1 := 16#01 AND (NOT(


SHR((nNodeID AND 2#0010), 1)
XOR (SHR((nNodeID AND 2#1000),3))
XOR (SHR((nNodeID AND 2#0001_0000), 4))
XOR (SHR((nNodeID AND 2#0010_0000), 5))));

F_ADD_LIN_NODE_PARITY := nPrepId OR SHL(bParity0,6) OR SHL(bParity1,7);

Function for calculating the checksum (conventional method)

Declaration part:
FUNCTION F_CALC_LIN_CHKSUM : BYTE
VAR_INPUT
pData:POINTER TO ARRAY[0..10] OF BYTE; // Pointer to source datafield
nLen:BYTE; // Number of bytes used for calculating the checksum
END_VAR
VAR

EL600x, EL602x Version: 4.6 141


Commissioning

i: BYTE; // Counter variable


wResult:WORD; // Resulting output value
END_VAR

Execution part:
wResult := BYTE_TO_WORD(pData^[0]);
FOR i := 1 TO (nLen-1) DO
wResult := wResult + BYTE_TO_WORD(pData^[i]);
IF wResult > 255 THEN
wResult := wResult - 255;
END_IF
END_FOR
F_CALC_LIN_CHKSUM := WORD_TO_BYTE(NOT(wResult));

This master program part should be called from a corresponding separate task. Here, a node in the LIN bus
with the ID 0x07 is queried every 200 ms.

Declaration part:
PROGRAM EL6001_MASTER
VAR
Timer: TON; // Timer for periodical requests by the master
Send: SendData; // Functionblock of TC2_SerialCom
SendBusy: BOOL; // Flag copy of SendData.Busy
SendErrorID: ComError_t; // Flag-Copy of Error-ID
aDataTX:tDataFrame; // Data frame being send
Receive: ReceiveData; // Functionblock of TC2_SerialCom
LastReceivedDataBytes: tDataFrame; // Copy (Latch) of received data
DataReceived: BOOL; // Flag copy of receive confirmation
ReceiveBusy: BOOL; // Flag copy of reception not ready
ReceiveError: BOOL; // Flag copy of receive error
ReceiveErrorID: ComError_t;// Error-ID copy
ReceiveTimeout: BOOL; // Flag copy of receive-timeout
ReceiveCounter: UDINT := 0; // Number of received frames
aDataRX:tDataFrame; // Receiving data frame buffer
nDataLen:BYTE := 4; // Fixed data length
nState:BYTE := 0; // Initial state (start)
bNodeId_SL1: BYTE := 16#07; // ID of slave node
bReqLen_SL1: BYTE := 0; // Optional entry for 4 Data bytes Value 2
nRxChecksum: BYTE; // Storage of received checksum
nCalcChecksum:BYTE; // Storage of calculated checksum
T_ReceiveDelay:TIME; // Storage of calculated delay time
END_VAR

Execution part:
(*==================================================================
Receive data
*)
CASE nState OF
0:
Timer(IN:=TRUE, PT:=T#0.5S); // Call timer for periodical master requests
IF Timer.Q THEN
// Put ID into Tranceive data:
aDataTX[0] := F_ADD_LIN_NODE_PARITY(bNodeId_SL1, bReqLen_SL1);
LastReceivedDataBytes[0] := aDataTX[0];
// Send request to Slave 1 (get Data)
Send(pSendData:= ADR(aDataTX), Length:= 1,
TXbuffer:= TxBuffer_MASTER,
Busy => SendBusy, Error => SendErrorID);
Timer(IN:=FALSE); (* reset timer *)
IF NOT SendBusy THEN // Wait until sending ends
nState := nState + 1;
END_IF
END_IF
1:
// Delaytime by 1/Tbaud * Number of Bytes * (8 Databits + 2 Bit:start-Stop) * 1000ms
T_ReceiveDelay := REAL_TO_TIME((1/DINT_TO_REAL(nSetBaudrate)) * 33 * 1000); // .. for 1 Byte
Timer(IN:=TRUE, PT:=T_ReceiveDelay);
IF Timer.Q THEN
// Wait until ID is send
nState := nState + 1;
Timer(IN:=FALSE); (* reset timer *)
END_IF
2:
Receive(
pReceiveData:= ADR(aDataRX),
SizeReceiveData:= (nDataLen + 1),
RXbuffer:= RxBuffer_MASTER,

142 Version: 4.6 EL600x, EL602x


Commissioning

Timeout:= T#1S,
DataReceived=> DataReceived,
busy=> ReceiveBusy,
Error=> ReceiveErrorID,
RxTimeout=> ReceiveTimeout );
IF DataReceived THEN
// DataReceived := FALSE;
ReceiveCounter := ReceiveCounter + 1;
IF NOT ReceiveBusy THEN
// Compare checksum
nRxChecksum := aDataRX[nDataLen];
nCalcChecksum := F_CALC_LIN_CHKSUM(pData := ADR(aDataRX), nLen := nDataLen);
IF(nRxChecksum = nCalcChecksum) THEN
// Response received - clear databuffer:
memset(ADR(LastReceivedDataBytes[1]), 0, (SIZEOF(aDataRX)-1));
// Take-over data when checksum OK:
memcpy(ADR(LastReceivedDataBytes[1]), ADR(aDataRX), (nDataLen +1));
END_IF
nState := 0;
END_IF
ELSE
Timer(IN:=TRUE, PT:=T#0.1S); // Receive-Timeout 100 ms: no data
IF Timer.Q THEN
nState := 0;
END_IF
END_IF
END_CASE
(*==================================================================
*)

Program fast task / RS232 background communication

In this example, third task should be created with as few “cycle ticks” as possible, which deals with the
background communication with the EL6001 terminal (as master).

Declaration part:
PROGRAM FAST
VAR
(* background communication with the EL6001 as Master device *)
COMportControl_MASTER: SerialLineControl;
COMportControlError_MASTER: BOOL;
COMportControlErrorID_MASTER: ComError_t;
END_VAR

Execution part:
COMportControl_MASTER(
Mode:= SERIALLINEMODE_EL6_22B,
pComIn:= ADR(COMin_EL6001_MASTER),(* I/O data; see global variables *)
pComOut:= ADR(COMout_EL6001_MASTER),(* I/O data; see global variables *)
SizeComIn:= SIZEOF(COMin_EL6001_MASTER),(* I/O data; see global variables *)
TxBuffer:= TxBuffer_MASTER,(* transmit buffer; see global variables *)
RxBuffer:= RxBuffer_MASTER,(* receive buffer; see global variables *)
Error=> COMportControlError_MASTER,(* indicating an error *)
ErrorID=> COMportControlErrorID_MASTER );(* contains the error-ID *)

EL600x, EL602x Version: 4.6 143


Overview of CoE objects EL6001, EL6021

6 Overview of CoE objects EL6001, EL6021

6.1 Object description and parameterization


EtherCAT XML Device Description
The display matches that of the CoE objects from the EtherCAT XML Device Description. We rec-
ommend downloading the latest XML file from the download area of the Beckhoff website and in-
stalling it according to installation instructions.

Parameterization
The terminal is parameterized via the CoE - Online tab [} 108] (with a double-click on the respective
object, see below).

Introduction

The CoE overview contains objects for different intended applications:


• Objects required for parameterization [} 144] during commissioning
• Objects for indicating internal settings [} 146] (may be fixed)
• Profile specific objects [} 162], which represent the status displays of the inputs and outputs (from
hardware version 03 [} 186])

The following section first describes the objects required for normal operation, followed by a complete
overview of missing objects.

6.1.1 Objects for commissioning

Index 0x1011 Restore default parameters


Index Name Meaning Data type Flags Default
(hex)
1011:0 Restore default Restore default parameters UINT8 RO 0x01 (1dec)
parameters
[} 198]
1011:01 SubIndex 0x001 If this object is set to “0x64616F6C” in the set value dialog, UINT32 RW 0x00000000
all backup objects are reset to their delivery state. (0dec)

Index 0x4073 Baud rate


Index Name Meaning Data type Flags Default
(hex)
4073:0 Baud rate Detailed information can be found in chapter Communication UINT16 RW 0x0006 (6dec)
features [} 131]

Index 0x4074 Data frame


Index Name Meaning Data type Flags Default
(hex)
4074:0 Data frame Detailed information can be found in chapter Communication UINT16 RW 0x0003 (3dec)
features [} 131]

144 Version: 4.6 EL600x, EL602x


Overview of CoE objects EL6001, EL6021

Index 0x4075 Feature bits


Index Name Meaning Data type Flags Default
(hex)
4075:0 Feature bits Length of this object UINT8 RO 0x06 (6dec)
4075:01 EL6001: 0: RTS/CTS not enabled BOOLEAN RW 0x00 (0dec)
Enable RTS/CTS 1: RTS/CTS enabled
EL6021: 0: Full-duplex mode
Enable half du- 1: Half-duplex mode
plex
4075:02 Enable XON/ 0: XON/XOFF is not supported for send data BOOLEAN RW 0x00 (0dec)
XOFF supported 1: XON/XOFF is supported for send data
tx data
4075:03 Enable XON/ 0: XON/XOFF is not supported for receive data BOOLEAN RW 0x00 (0dec)
XOFF supported 1: XON/XOFF is supported for receive data
rx data
4075:04 EL6001: 0: No continuous sending of data from the FIFO BOOLEAN RO 0x00 (0dec)
Enable send FIFO 1: The send buffer is filled (up to 128 bytes) by the controller.
data continous The buffer content is sent with rising edge of bit CW.3 [} 165]
in the control word. The terminal acknowledges the data
transfer to the controller through setting of bit SW.2 [} 166] in
the status word. SW.2 is reset with CW.3.
EL6021: 0: Point-to-point connection disabled
Enable point to 1: Point-to-point connection enabled
point connection
(RS422)
4075:05 EL6001: 0: Transfer rate optimization switched off BOOLEAN RO 0x00 (0dec)
Enable transfer 1: Transfer rate optimization switched on:
rate optimization
The content of the input buffer is automatically transferred
into the process image if
• no further byte was received for approx. 16 bit times
(i.e. the time it would have taken to receive 2 bytes)
after data were received;
• the input buffer is full
 EL6021: 0: No continuous sending of data from the FIFO
Enable send FIFO 1: The send buffer is filled (up to 128 bytes) by the controller.
data continuous The buffer content is sent with rising edge of bit CW.3 [} 165]
in the control word. The terminal acknowledges the data
transfer to the controller through setting of bit SW.2 [} 166] in
the status word. SW.2 is reset with CW.3.
4075:06 EL6021 only: 0: Transfer rate optimization switched off BOOLEAN RW 0x00 (0dec)
Enable transfer 1: Transfer rate optimization switched on:
rate optimization
The content of the input buffer is automatically transferred
into the process image if
• no further byte was received for approx. 16 bit times
(i.e. the time it would have taken to receive 2 bytes)
after data were received;
• the process image is filled

Index 0x4076 Rx buffer full notification


Index Name Meaning Data type Flags Default
(hex)
4076:0 Rx buffer full noti- The value determines the number of data in the receive FIFO UINT16 RW 0x0000 (0dec)
fication from which bit SW.3 [} 166] (BUF_F) is set in the status byte.

EL600x, EL602x Version: 4.6 145


Overview of CoE objects EL6001, EL6021

Index 0x8000 COM settings [from hardware version 03]


Index Name Meaning Data type Flags Default
(hex)
8000:0 COM Settings Max. SubIndex (hex) UINT8 RO 0x26 (38dec)
8000:01** Enable RTS/CTS FALSE RTS/CTS not enabled BOOLEAN RW 0x01 (1dec)
TRUE RTS/CTS enabled
8000:02 Enable XON/ FALSE XON/XOFF is not supported for send data BOOLEAN RW 0x00 (0dec)
XOFF supported TRUE XON/XOFF is supported for send data
tx data
8000:03 Enable XON/ FALSE XON/XOFF is not supported for receive data BOOLEAN RW 0x00 (0dec)
XOFF supported TRUE XON/XOFF is supported for receive data
rx data
8000:04 Enable send FIFO FALSE No continuous sending of data from the FIFO BOOLEAN RW 0x00 (0dec)
data continuous TRUE Continuous sending of data from the FIFO en-
abled:
The send buffer is filled (up to 128 bytes) by the
controller.
The filled buffer content is sent on rising edge of
bit “SendContinious [} 163]”.
The terminal acknowledges the data transfer to
the controller through setting of bit "InitAccepted".
“InitAccepted [} 162]” is reset with “SendContinu-
ous”.
8000:05 Enable transfer FALSE Transfer rate optimization switched off BOOLEAN RW 0x01 (1dec)
rate optimization TRUE Transfer rate optimization switched on:
The content of the input buffer is automatically
transferred into the process image if
• no further byte was received for approx.
16 bit times (i.e. the time it would have
taken to receive 2 bytes) after data were
received;
• the process image is filled
8000:06** Enable half du- FALSE Full-duplex mode BOOLEAN RW 0x00 (0dec)
* plex TRUE Half-duplex mode
8000:07** Enable point to FALSE Point-to-point connection disabled BOOLEAN RW 0x00 (0dec)
* point connection TRUE Point-to-point connection enabled
(RS422)
8000:11 Baud rate Detailed information can be found in chapter Communication BIT4 RW 0x06 (6dec)
features [} 131]
8000:15 Data frame Detailed information can be found in chapter Communication BIT4 RW 0x03 (3dec)
features [} 131]
8000:1A Rx buffer full noti- The value specifies the number of data in the receive FIFO, UINT16 RW 0x0360 (864dec)
fication from which the bit “buffer full [} 164]” is set.
8000:1B** Explicit baudrate In this object the desired baud rate can be entered directly as UINT32 RW 0x00000384
a number. (9600dec)
Only the baud rates specified in Communication features
[} 131] are supported. Changes to this object are also
adopted into the objects 0x8000:11 and 4073
8000:1C** Extended data In this object special formats can also be selected in addition ENUM16 RW 0x0003 (3dec)
frame to the usual data frames (e.g. 9N1). Changes to this object
are also adopted in the objects 0x8000:15 and 0x4074.

**) only EL6001


***) only EL6021

6.1.2 Standard objects (0x1000-0x1FFF)


The standard objects have the same meaning for all EtherCAT slaves.

146 Version: 4.6 EL600x, EL602x


Overview of CoE objects EL6001, EL6021

Index 0x1000 Device type


Index Name Meaning Data type Flags Default
(hex)
1000:0 Device type Device type of the EtherCAT slave: the Lo-Word contains the UINT32 RO 0x02581389
CoE profile used (5001). The Hi-Word contains the module (39326601dec)
profile according to the modular device profile.

Index 0x1008 Device name


Index Name Meaning Data type Flags Default
(hex)
1008:0 Device name Device name of the EtherCAT slave STRING RO EL6001
EL6021

Index 0x1009 Hardware version


Index Name Meaning Data type Flags Default
(hex)
1009:0 Hardware version Hardware version of the EtherCAT slave STRING RO 04

Index 0x100A Software version


Index Name Meaning Data type Flags Default
(hex)
100A:0 Software version Firmware version of the EtherCAT slave STRING RO 05

Index 0x1018 Identity


Index Name Meaning Data type Flags Default
(hex)
1018:0 Identity Information for identifying the slave UINT8 RO 0x04 (4dec)
1018:01 Vendor ID Vendor ID of the EtherCAT slave UINT32 RO 0x00000002
(2dec)
1018:02 Product code Product code of the EtherCAT slave UINT32 RO 0x17853052
(394604626dec)
1018:03 Revision Revision number of the EtherCAT slave; the low word (bit UINT32 RO 0x00100000
0-15) indicates the special terminal number, the high word (1048576dec)
(bit 16-31) refers to the device description
1018:04 Serial number Serial number of the EtherCAT slave; the low byte (bit 0-7) of UINT32 RO 0x00000000
the low word contains the year of production, the high byte (0dec)
(bit 8-15) of the low word contains the week of production,
the high word (bit 16-31) is 0

Index 0x10F0 Backup parameter handling


Index Name Meaning Data type Flags Default
(hex)
10F0:0 Backup parameter Information for standardized loading and saving of backup UINT8 RO 0x01 (1dec)
handling entries
10F0:01 Checksum Checksum across all backup entries of the EtherCAT slave UINT32 RO 0x00000000
(0dec)

Index 0x1400 RxPDO-Par Outputs


Index Name Meaning Data type Flags Default
(hex)
1400:0 RxPDO-Par Out- PDO Parameter RxPDO 1 UINT8 RO 0x06 (6dec)
puts
1400:06 Exclude RxPDOs Specifies the RxPDOs (index 0x of RxPDO mapping objects) OCTET- RO 01 16 02 16 04
that must not be transferred together with RxPDO 1 STRING[6] 16

EL600x, EL602x Version: 4.6 147


Overview of CoE objects EL6001, EL6021

Index 0x1401 RxPDO-Par Outputs


Index Name Meaning Data type Flags Default
(hex)
1401:0 RxPDO-Par Outputs PDO Parameter RxPDO 2 UINT8 RO 0x06 (6dec)
1401:06 Exclude RxPDOs Specifies the RxPDOs (index 0x of RxPDO mapping OCTET- RO 00 16 02 16 04
objects) that must not be transferred together with Rx- STRING[6] 16
PDO 2

Index 0x1402 RxPDO-Par Outputs


Index Name Meaning Data type Flags Default
(hex)
1402:0 RxPDO-Par Outputs PDO Parameter RxPDO 3 UINT8 RO 0x06 (6dec)
1402:06 Exclude RxPDOs Specifies the RxPDOs (index 0x of RxPDO mapping OCTET- RO 00 16 01 16 04
objects) that must not be transferred together with Rx- STRING[6] 16
PDO 3

Index 0x1600 RxPDO-Map Outputs


Index Name Meaning Data type Flags Default
(hex)
1600:0 RxPDO-Map Outputs PDO Mapping RxPDO 1 UINT8 RO 0x04 (4dec)
1600:01 SubIndex 0x001 1. PDO Mapping entry (object 0x3001 ( Outputs), entry UINT32 RO 0x3001:01, 8
0x01 (Ctrl))
1600:02 SubIndex 0x002 2. PDO Mapping entry (object 0x3001 ( Outputs), entry UINT32 RO 0x3001:02, 8
0x02 (Data Out 0))
1600:03 SubIndex 0x003 3. PDO Mapping entry (object 0x3001 ( Outputs), entry UINT32 RO 0x3001:03, 8
0x03 (Data Out 1))
1600:04 SubIndex 0x004 4. PDO Mapping entry (object 0x3001 ( Outputs), entry UINT32 RO 0x3001:04, 8
0x04 (Data Out 2))

Index 0x1601 RxPDO-Map Outputs


Index Name Meaning Data type Flags Default
(hex)
1601:0 RxPDO-Map Outputs PDO Mapping RxPDO 2 UINT8 RO 0x06 (6dec)
1601:01 SubIndex 0x001 1. PDO Mapping entry (object 0x3002 ( Outputs), entry UINT32 RO 0x3002:01, 8
0x01 (Ctrl))
1601:02 SubIndex 0x002 2. PDO Mapping entry (object 0x3002 ( Outputs), entry UINT32 RO 0x3002:02, 8
0x02 (Data Out 0))
1601:03 SubIndex 0x003 3. PDO Mapping entry (object 0x3002 ( Outputs), entry UINT32 RO 0x3002:03, 8
0x03 (Data Out 1))
1601:04 SubIndex 0x004 4. PDO Mapping entry (object 0x3002 ( Outputs), entry UINT32 RO 0x3002:04, 8
0x04 (Data Out 2))
1601:05 SubIndex 0x005 5. PDO Mapping entry (object 0x3002 ( Outputs), entry UINT32 RO 0x3002:05, 8
0x05 (Data Out 3))
1601:06 SubIndex 0x006 6. PDO Mapping entry (object 0x3002 ( Outputs), entry UINT32 RO 0x3002:06, 8
0x06 (Data Out 4))

148 Version: 4.6 EL600x, EL602x


Overview of CoE objects EL6001, EL6021

Index 0x1602 RxPDO-Map Outputs


Index Name Meaning Data type Flags Default
(hex)
1602:0 RxPDO-Map Outputs PDO Mapping RxPDO 3 UINT8 RO 0x17 (23dec)
1602:01 SubIndex 0x001 1. PDO Mapping entry (object 0x3003 (Outputs), entry UINT32 RO 0x3003:01, 16
0x01 (Ctrl))
1602:02 SubIndex 0x002 2. PDO Mapping entry (object 0x3003 (Outputs), entry UINT32 RO 0x3003:02, 8
0x02 (Data Out 0))
1602:03 SubIndex 0x003 3. PDO Mapping entry (object 0x3003 (Outputs), entry UINT32 RO 0x3003:03, 8
0x03 (Data Out 1))
1602:04 SubIndex 0x004 4. PDO Mapping entry (object 0x3003 (Outputs), entry UINT32 RO 0x3003:04, 8
0x04 (Data Out 2))
1602:05 SubIndex 0x005 5. PDO Mapping entry (object 0x3003 (Outputs), entry UINT32 RO 0x3003:05, 8
0x05 (Data Out 3))
1602:06 SubIndex 0x006 6. PDO Mapping entry (object 0x3003 (Outputs), entry UINT32 RO 0x3003:06, 8
0x06 (Data Out 4))
1602:07 SubIndex 0x007 7. PDO Mapping entry (object 0x3003 (Outputs), entry UINT32 RO 0x3003:07, 8
0x07 (Data Out 5))
1602:08 SubIndex 0x008 8. PDO Mapping entry (object 0x3003 (Outputs), entry UINT32 RO 0x3003:08, 8
0x08 (Data Out 6))
1602:09 SubIndex 0x009 9. PDO Mapping entry (object 0x3003 (Outputs), entry UINT32 RO 0x3003:09, 8
0x09 (Data Out 7))
1602:0A SubIndex 0x010 10. PDO Mapping entry (object 0x3003 (Outputs), en- UINT32 RO 0x3003:0A, 8
try 0x0A (Data Out 8))
1602:0B SubIndex 0x011 11. PDO Mapping entry (object 0x3003 (Outputs), en- UINT32 RO 0x3003:0B, 8
try 0x0B (Data Out 9))
1602:0C SubIndex 0x012 12. PDO Mapping entry (object 0x3003 (Outputs), en- UINT32 RO 0x3003:0C, 8
try 0x0C (Data Out 10))
1602:0D SubIndex 0x013 13. PDO Mapping entry (object 0x3003 (Outputs), en- UINT32 RO 0x3003:0D, 8
try 0x0D (Data Out 11))
1602:0E SubIndex 0x014 14. PDO Mapping entry (object 0x3003 (Outputs), en- UINT32 RO 0x3003:0E, 8
try 0x0E (Data Out 12))
1602:0F SubIndex 0x015 15. PDO Mapping entry (object 0x3003 (Outputs), en- UINT32 RO 0x3003:0F, 8
try 0x0F (Data Out 13))
1602:10 SubIndex 0x016 16. PDO Mapping entry (object 0x3003 (Outputs), en- UINT32 RO 0x3003:10, 8
try 0x10 (Data Out 14))
1602:11 SubIndex 0x017 17. PDO Mapping entry (object 0x3003 (Outputs), en- UINT32 RO 0x3003:11, 8
try 0x11 (Data Out 15))
1602:12 SubIndex 0x018 18. PDO Mapping entry (object 0x3003 (Outputs), en- UINT32 RO 0x3003:12, 8
try 0x12 (Data Out 16))
1602:13 SubIndex 0x019 19. PDO Mapping entry (object 0x3003 (Outputs), en- UINT32 RO 0x3003:13, 8
try 0x13 (Data Out 17))
1602:14 SubIndex 0x020 20. PDO Mapping entry (object 0x3003 (Outputs), en- UINT32 RO 0x3003:14, 8
try 0x14 (Data Out 18))
1602:15 SubIndex 0x021 21. PDO Mapping entry (object 0x3003 (Outputs), en- UINT32 RO 0x3003:15, 8
try 0x15 (Data Out 19))
1602:16 SubIndex 0x022 22. PDO Mapping entry (object 0x3003 (Outputs), en- UINT32 RO 0x3003:16, 8
try 0x16 (Data Out 20))
1602:17 SubIndex 0x023 23. PDO Mapping entry (object 0x3003 (Outputs), en- UINT32 RO 0x3003:17, 8
try 0x17 (Data Out 21))

EL600x, EL602x Version: 4.6 149


Overview of CoE objects EL6001, EL6021

Index 0x1604 COM RxPDO-Map Outputs [ab Hardwarestand 03]


Index Name Meaning Data type Flags Default
(hex)
1604:0 COM RxPDO-Map Out- PDO Mapping RxPDO 5 UINT8 RO 0x1C (28dec)
puts
1604:01 SubIndex 0x001 1. PDO Mapping entry (object 0x7000 (COM Outputs), UINT32 RO 0x7000:01, 1
entry 0x01 (Transmit request))
1604:02 SubIndex 0x002 2. PDO Mapping entry (object 0x7000 (COM Outputs), UINT32 RO 0x7000:02, 1
entry 0x02 (Receive accepted))
1604:03 SubIndex 0x003 3. PDO Mapping entry (object 0x7000 (COM Outputs), UINT32 RO 0x7000:03, 1
entry 0x03 (Init request))
1604:04 SubIndex 0x004 4. PDO Mapping entry (object 0x7000 (COM Outputs), UINT32 RO 0x7000:04, 1
entry 0x04 (Send continues))
1604:05 SubIndex 0x005 5. PDO Mapping entry (4 bits align) UINT32 RO 0x0000:00, 4
1604:06 SubIndex 0x006 6. PDO Mapping entry (object 0x7000 (COM Outputs), UINT32 RO 0x7000:09, 8
entry 0x09 (Output length))
1604:07 SubIndex 0x007 7. PDO Mapping entry (object 0x7000 (COM Outputs), UINT32 RO 0x7000:11, 8
entry 0x11 (Data Out 0))
1604:08 SubIndex 0x008 8. PDO Mapping entry (object 0x7000 (COM Outputs), UINT32 RO 0x7000:12, 8
entry 0x12 (Data Out 1))
1604:09 SubIndex 0x009 9. PDO Mapping entry (object 0x7000 (COM Outputs), UINT32 RO 0x7000:13, 8
entry 0x13 (Data Out 2))
1604:0A SubIndex 0x010 10. PDO Mapping entry (object 0x7000 (COM Out- UINT32 RO 0x7000:14, 8
puts), entry 0x14 (Data Out 3))
1604:0B SubIndex 0x011 11. PDO Mapping entry (object 0x7000 (COM Out- UINT32 RO 0x7000:15, 8
puts), entry 0x15 (Data Out 4))
1604:0C SubIndex 0x012 12. PDO Mapping entry (object 0x7000 (COM Out- UINT32 RO 0x7000:16, 8
puts), entry 0x16 (Data Out 5))
1604:0D SubIndex 0x013 13. PDO Mapping entry (object 0x7000 (COM Out- UINT32 RO 0x7000:17, 8
puts), entry 0x17 (Data Out 6))
1604:0E SubIndex 0x014 14. PDO Mapping entry (object 0x7000 (COM Out- UINT32 RO 0x7000:18, 8
puts), entry 0x18 (Data Out 7))
1604:0F SubIndex 0x015 15. PDO Mapping entry (object 0x7000 (COM Out- UINT32 RO 0x7000:19, 8
puts), entry 0x19 (Data Out 8))
1604:10 SubIndex 0x016 16. PDO Mapping entry (object 0x7000 (COM Out- UINT32 RO 0x7000:1A, 8
puts), entry 0x1A (Data Out 9))
1604:11 SubIndex 0x017 17. PDO Mapping entry (object 0x7000 (COM Out- UINT32 RO 0x7000:1B, 8
puts), entry 0x1B (Data Out 10))
1604:12 SubIndex 0x018 18. PDO Mapping entry (object 0x7000 (COM Out- UINT32 RO 0x7000:1C, 8
puts), entry 0x1C (Data Out 11))
1604:13 SubIndex 0x019 19. PDO Mapping entry (object 0x7000 (COM Out- UINT32 RO 0x7000:1D, 8
puts), entry 0x1D (Data Out 12))
1604:14 SubIndex 0x020 20. PDO Mapping entry (object 0x7000 (COM Out- UINT32 RO 0x7000:1E, 8
puts), entry 0x1E (Data Out 13))
1604:15 SubIndex 0x021 21. PDO Mapping entry (object 0x7000 (COM Out- UINT32 RO 0x7000:1F, 8
puts), entry 0x1F (Data Out 14))
1604:16 SubIndex 0x022 22. PDO Mapping entry (object 0x7000 (COM Out- UINT32 RO 0x7000:20, 8
puts), entry 0x20 (Data Out 15))
1604:17 SubIndex 0x023 23. PDO Mapping entry (object 0x7000 (COM Out- UINT32 RO 0x7000:21, 8
puts), entry 0x21 (Data Out 16))
1604:18 SubIndex 0x024 24. PDO Mapping entry (object 0x7000 (COM Out- UINT32 RO 0x7000:22, 8
puts), entry 0x22 (Data Out 17))
1604:19 SubIndex 0x025 25. PDO Mapping entry (object 0x7000 (COM Out- UINT32 RO 0x7000:23, 8
puts), entry 0x23 (Data Out 18))
1604:1A SubIndex 0x026 26. PDO Mapping entry (object 0x7000 (COM Out- UINT32 RO 0x7000:24, 8
puts), entry 0x24 (Data Out 19))
1604:1B SubIndex 0x027 27. PDO Mapping entry (object 0x7000 (COM Out- UINT32 RO 0x7000:25, 8
puts), entry 0x25 (Data Out 20))
1604:1C SubIndex 0x028 28. PDO Mapping entry (object 0x7000 (COM Out- UINT32 RO 0x7000:26, 8
puts), entry 0x26 (Data Out 21))

150 Version: 4.6 EL600x, EL602x


Overview of CoE objects EL6001, EL6021

Index 0x1605 COM ext. outputs


Index Name Meaning Data type Flags Default
(hex)
1605:0 COM ext. outputs PDO Mapping RxPDO 6 UINT8 RO 0x38 (56dec)
1605:01 SubIndex 0x001 1. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:01, 1
puts), entry 0x01 (Transmit request))
1605:02 SubIndex 0x002 2. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:02, 1
puts), entry 0x02 (Receive accepted))
1605:03 SubIndex 0x003 3. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:03, 1
puts), entry 0x03 (Init request))
1605:04 SubIndex 0x004 4. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:04, 1
puts), entry 0x04 (Send continues))
1605:05 SubIndex 0x005 5. PDO Mapping entry (4 bits align) UINT32 RO 0x0000:00, 4
1605:06 SubIndex 0x006 6. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:09, 8
puts), entry 0x09 (Output length))
1605:07 SubIndex 0x007 7. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:11, 16
puts), entry 0x11 (Data Out 0))
1605:08 SubIndex 0x008 8. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:12, 16
puts), entry 0x12 (Data Out 1))
1605:09 SubIndex 0x009 9. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:13, 16
puts), entry 0x13 (Data Out 2))
1605:0A SubIndex 0x010 10. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:14, 16
puts), entry 0x14 (Data Out 3))
1605:0B SubIndex 0x011 11. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:15, 16
puts), entry 0x15 (Data Out 4))
1605:0C SubIndex 0x012 12. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:16, 16
puts), entry 0x16 (Data Out 5))
1605:0D SubIndex 0x013 13. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:17, 16
puts), entry 0x17 (Data Out 6))
1605:0E SubIndex 0x014 14. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:18, 16
puts), entry 0x18 (Data Out 7))
1605:0F SubIndex 0x015 15. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:19, 16
puts), entry 0x19 (Data Out 8))
1605:10 SubIndex 0x016 16. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:1A, 16
puts), entry 0x1A (Data Out 9))
1605:11 SubIndex 0x017 17. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:1B, 16
puts), entry 0x1B (Data Out 10))
1605:12 SubIndex 0x018 18. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:1C, 16
puts), entry 0x1C (Data Out 11))
1605:13 SubIndex 0x019 19. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:1D, 16
puts), entry 0x1D (Data Out 12))
1605:14 SubIndex 0x020 20. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:1E, 16
puts), entry 0x1E (Data Out 13))
1605:15 SubIndex 0x021 21. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:1F, 16
puts), entry 0x1F (Data Out 14))
1605:16 SubIndex 0x022 22. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:20, 16
puts), entry 0x20 (Data Out 15))
1605:17 SubIndex 0x023 23. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:21, 16
puts), entry 0x21 (Data Out 16))
1605:18 SubIndex 0x024 24. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:22, 16
puts), entry 0x22 (Data Out 17))
1605:19 SubIndex 0x025 25. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:23, 16
puts), entry 0x23 (Data Out 18))
1605:1A SubIndex 0x026 26. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:24, 16
puts), entry 0x24 (Data Out 19))
1605:1B SubIndex 0x027 27. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:25, 16
puts), entry 0x25 (Data Out 20))
1605:1C SubIndex 0x028 28. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:26, 16
puts), entry 0x26 (Data Out 21))
1605:1D SubIndex 0x029 29. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:27, 16
puts), entry 0x27 (Data Out 22))
1605:1E SubIndex 0x030 30. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:28, 16
puts), entry 0x28 (Data Out 23))
1605:1F SubIndex 0x031 31. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:29, 16
puts), entry 0x29 (Data Out 24))

EL600x, EL602x Version: 4.6 151


Overview of CoE objects EL6001, EL6021

Index Name Meaning Data type Flags Default


(hex)
1605:20 SubIndex 0x032 32. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:2A, 16
puts), entry 0x2A (Data Out 25))
1605:21 SubIndex 0x033 33. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:2B, 16
puts), entry 0x2B (Data Out 26))
1605:22 SubIndex 0x034 34. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:2C, 16
puts), entry 0x2C (Data Out 27))
1605:23 SubIndex 0x035 35. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:2D, 16
puts), entry 0x2D (Data Out 28))
1605:24 SubIndex 0x036 36. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:2E, 16
puts), entry 0x2E (Data Out 29))
1605:25 SubIndex 0x037 37. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:2F, 16
puts), entry 0x2F (Data Out 30))
1605:26 SubIndex 0x038 38. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:30, 16
puts), entry 0x30 (Data Out 31))
1605:27 SubIndex 0x039 39. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:31, 16
puts), entry 0x31 (Data Out 32))
1605:28 SubIndex 0x040 40. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:32, 16
puts), entry 0x32 (Data Out 33))
1605:29 SubIndex 0x041 41. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:33, 16
puts), entry 0x33 (Data Out 34))
1605:2A SubIndex 0x042 42. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:34, 16
puts), entry 0x34 (Data Out 35))
1605:2B SubIndex 0x043 43. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:35, 16
puts), entry 0x35 (Data Out 36))
1605:2C SubIndex 0x044 44. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:36, 16
puts), entry 0x36 (Data Out 37))
1605:2D SubIndex 0x045 45. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:37, 16
puts), entry 0x37 (Data Out 38))
1605:2E SubIndex 0x046 46. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:38, 16
puts), entry 0x38 (Data Out 39))
1605:2F SubIndex 0x047 47. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:39, 16
puts), entry 0x39 (Data Out 40))
1605:30 SubIndex 0x048 48. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:3A, 16
puts), entry 0x3A (Data Out 41))
1605:31 SubIndex 0x049 49. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:3B, 16
puts), entry 0x3B (Data Out 42))
1605:32 SubIndex 0x050 50. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:3C, 16
puts), entry 0x3C (Data Out 43))
1605:33 SubIndex 0x051 51. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:3D, 16
puts), entry 0x3D (Data Out 44))
1605:34 SubIndex 0x052 52. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:3E, 16
puts), entry 0x3E (Data Out 45))
1605:35 SubIndex 0x053 53. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:3F, 16
puts), entry 0x3F (Data Out 46))
1605:36 SubIndex 0x054 54. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:40, 16
puts), entry 0x40 (Data Out 47))
1605:37 SubIndex 0x055 55. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:41, 16
puts), entry 0x41 (Data Out 48))
1605:38 SubIndex 0x056 56. PDO Mapping entry (object 0x7001 (COM ext. out- UINT32 RO 0x7001:42, 16
puts), entry 0x42 (Data Out 49))

Index 0x1800 TxPDO-Par Inputs


Index Name Meaning Data type Flags Default
(hex)
1800:0 TxPDO-Par Inputs PDO Parameter TxPDO 1 UINT8 RO 0x06 (6dec)
1800:06 Exclude TxPDOs Specifies the TxPDOs (index 0x of TxPDO mapping OCTET- RO 01 1A 02 1A 04
objects) that must not be transferred together with Tx- STRING[6] 1A
PDO 1

152 Version: 4.6 EL600x, EL602x


Overview of CoE objects EL6001, EL6021

Index 0x1801 TxPDO-Par Inputs


Index Name Meaning Data type Flags Default
(hex)
1801:0 TxPDO-Par Inputs PDO Parameter TxPDO 2 UINT8 RO 0x06 (6dec)
1801:06 Exclude TxPDOs Specifies the TxPDOs (index 0x of TxPDO mapping OCTET- RO 00 1A 02 1A 04
objects) that must not be transferred together with Tx- STRING[6] 1A
PDO 2

Index 0x1802 TxPDO-Par Inputs


Index Name Meaning Data type Flags Default
(hex)
1802:0 TxPDO-Par Inputs PDO Parameter TxPDO 3 UINT8 RO 0x06 (6dec)
1802:06 Exclude TxPDOs Specifies the TxPDOs (index 0x of TxPDO mapping OCTET- RO 00 1A 01 1A 04
objects) that must not be transferred together with Tx- STRING[6] 1A
PDO 3

Index 0x1804 COM TxPDO-Par Inputs


Index Name Meaning Data type Flags Default
(hex)
1804:0 COM TxPDO-Par Inputs PDO Parameter TxPDO 5 UINT8 RO 0x06 (6dec)
1804:06 Exclude TxPDOs Specifies the TxPDOs (index 0x of TxPDO mapping OCTET- RO 00 1A 01 1A 02
objects) that must not be transferred together with Tx- STRING[8] 1A 05 1A
PDO 5

Index 0x1805 COM ext. inputs


Index Name Meaning Data type Flags Default
(hex)
1805:0 COM ext. inputs PDO Parameter TxPDO 6 UINT8 RO 0x06 (6dec)
1805:06 Exclude TxPDOs Specifies the TxPDOs (index 0x of TxPDO mapping OCTET- RO 00 1A 01 1A 02
objects) that must not be transferred together with Tx- STRING[8] 1A 04 1A
PDO 6

Index 0x1A00 TxPDO-Map Inputs


Index Name Meaning Data type Flags Default
(hex)
1A00:0 TxPDO-Map Inputs PDO Mapping TxPDO 1 UINT8 RO 0x04 (4dec)
1A00:01 SubIndex 0x001 1. PDO Mapping entry (object 0x3101 (Inputs), entry UINT32 RO 0x3101:01, 8
0x01 (Status))
1A00:02 SubIndex 0x002 2. PDO Mapping entry (object 0x3101 (Inputs), entry UINT32 RO 0x3101:02, 8
0x02 (Data In 0))
1A00:03 SubIndex 0x003 3. PDO Mapping entry (object 0x3101 (Inputs), entry UINT32 RO 0x3101:03, 8
0x03 (Data In 1))
1A00:04 SubIndex 0x004 4. PDO Mapping entry (object 0x3101 (Inputs), entry UINT32 RO 0x3101:04, 8
0x04 (Data In 2))

Index 0x1A01 TxPDO-Map Inputs


Index Name Meaning Data type Flags Default
(hex)
1A01:0 TxPDO-Map Inputs PDO Mapping TxPDO 2 UINT8 RO 0x06 (6dec)
1A01:01 SubIndex 0x001 1. PDO Mapping entry (object 0x3102 (Inputs), entry UINT32 RO 0x3102:01, 8
0x01 (Status))
1A01:02 SubIndex 0x002 2. PDO Mapping entry (object 0x3102 (Inputs), entry UINT32 RO 0x3102:02, 8
0x02 (Data In 0))
1A01:03 SubIndex 0x003 3. PDO Mapping entry (object 0x3102 (Inputs), entry UINT32 RO 0x3102:03, 8
0x03 (Data In 1))
1A01:04 SubIndex 0x004 4. PDO Mapping entry (object 0x3102 (Inputs), entry UINT32 RO 0x3102:04, 8
0x04 (Data In 2))
1A01:05 SubIndex 0x005 5. PDO Mapping entry (object 0x3102 (Inputs), entry UINT32 RO 0x3102:05, 8
0x05 (Data In 3))
1A01:06 SubIndex 0x006 6. PDO Mapping entry (object 0x3102 (Inputs), entry UINT32 RO 0x3102:06, 8
0x06 (Data In 4))

EL600x, EL602x Version: 4.6 153


Overview of CoE objects EL6001, EL6021

Index 0x1A02 TxPDO-Map Inputs


Index Name Meaning Data type Flags Default
(hex)
1A02:0 TxPDO-Map Inputs PDO Mapping TxPDO 3 UINT8 RO 0x17 (23dec)
1A02:01 SubIndex 0x001 1. PDO Mapping entry (object 0x3103 (Inputs), entry UINT32 RO 0x3103:01, 16
0x01 (Status))
1A02:02 SubIndex 0x002 2. PDO Mapping entry (object 0x3103 (Inputs), entry UINT32 RO 0x3103:02, 8
0x02 (Data In 0))
1A02:03 SubIndex 0x003 3. PDO Mapping entry (object 0x3103 (Inputs), entry UINT32 RO 0x3103:03, 8
0x03 (Data In 1))
1A02:04 SubIndex 0x004 4. PDO Mapping entry (object 0x3103 (Inputs), entry UINT32 RO 0x3103:04, 8
0x04 (Data In 2))
1A02:05 SubIndex 0x005 5. PDO Mapping entry (object 0x3103 (Inputs), entry UINT32 RO 0x3103:05, 8
0x05 (Data In 3))
1A02:06 SubIndex 0x006 6. PDO Mapping entry (object 0x3103 (Inputs), entry UINT32 RO 0x3103:06, 8
0x06 (Data In 4))
1A02:07 SubIndex 0x007 7. PDO Mapping entry (object 0x3103 (Inputs), entry UINT32 RO 0x3103:07, 8
0x07 (Data In 5))
1A02:08 SubIndex 0x008 8. PDO Mapping entry (object 0x3103 (Inputs), entry UINT32 RO 0x3103:08, 8
0x08 (Data In 6))
1A02:09 SubIndex 0x009 9. PDO Mapping entry (object 0x3103 (Inputs), entry UINT32 RO 0x3103:09, 8
0x09 (Data In 7))
1A02:0A SubIndex 0x010 10. PDO Mapping entry (object 0x3103 (Inputs), entry UINT32 RO 0x3103:0A, 8
0x0A (Data In 8))
1A02:0B SubIndex 0x011 11. PDO Mapping entry (object 0x3103 (Inputs), entry UINT32 RO 0x3103:0B, 8
0x0B (Data In 9))
1A02:0C SubIndex 0x012 12. PDO Mapping entry (object 0x3103 (Inputs), entry UINT32 RO 0x3103:0C, 8
0x0C (Data In 10))
1A02:0D SubIndex 0x013 13. PDO Mapping entry (object 0x3103 (Inputs), entry UINT32 RO 0x3103:0D, 8
0x0D (Data In 11))
1A02:0E SubIndex 0x014 14. PDO Mapping entry (object 0x3103 (Inputs), entry UINT32 RO 0x3103:0E, 8
0x0E (Data In 12))
1A02:0F SubIndex 0x015 15. PDO Mapping entry (object 0x3103 (Inputs), entry UINT32 RO 0x3103:0F, 8
0x0F (Data In 13))
1A02:10 SubIndex 0x016 16. PDO Mapping entry (object 0x3103 (Inputs), entry UINT32 RO 0x3103:10, 8
0x10 (Data In 14))
1A02:11 SubIndex 0x017 17. PDO Mapping entry (object 0x3103 (Inputs), entry UINT32 RO 0x3103:11, 8
0x11 (Data In 15))
1A02:12 SubIndex 0x018 18. PDO Mapping entry (object 0x3103 (Inputs), entry UINT32 RO 0x3103:12, 8
0x12 (Data In 16))
1A02:13 SubIndex 0x019 19. PDO Mapping entry (object 0x3103 (Inputs), entry UINT32 RO 0x3103:13, 8
0x13 (Data In 17))
1A02:14 SubIndex 0x020 20. PDO Mapping entry (object 0x3103 (Inputs), entry UINT32 RO 0x3103:14, 8
0x14 (Data In 18))
1A02:15 SubIndex 0x021 21. PDO Mapping entry (object 0x3103 (Inputs), entry UINT32 RO 0x3103:15, 8
0x15 (Data In 19))
1A02:16 SubIndex 0x022 22. PDO Mapping entry (object 0x3103 (Inputs), entry UINT32 RO 0x3103:16, 8
0x16 (Data In 20))
1A02:17 SubIndex 0x023 23. PDO Mapping entry (object 0x3103 (Inputs), entry UINT32 RO 0x3103:17, 8
0x17 (Data In 21))

154 Version: 4.6 EL600x, EL602x


Overview of CoE objects EL6001, EL6021

Index 0x1A04 COM TxPDO-Map Inputs [ab Hardwarestand 03]


Index Name Meaning Data type Flags Default
(hex)
1A04:0 COM TxPDO-Map In- PDO Mapping TxPDO 5 UINT8 RO 0x1F (31dec)
puts
1A04:01 SubIndex 0x001 1. PDO Mapping entry (object 0x6000 (COM Inputs), UINT32 RO 0x6000:01, 1
entry 0x01 (Transmit accepted))
1A04:02 SubIndex 0x002 2. PDO Mapping entry (object 0x6000 (COM Inputs), UINT32 RO 0x6000:02, 1
entry 0x02 (Receive request))
1A04:03 SubIndex 0x003 3. PDO Mapping entry (object 0x6000 (COM Inputs), UINT32 RO 0x6000:03, 1
entry 0x03 (Init accepted))
1A04:04 SubIndex 0x004 4. PDO Mapping entry (object 0x6000 (COM Inputs), UINT32 RO 0x6000:04, 1
entry 0x04 (Buffer full))
1A04:05 SubIndex 0x005 5. PDO Mapping entry (object 0x6000 (COM Inputs), UINT32 RO 0x6000:05, 1
entry 0x05 (Parity error))
1A04:06 SubIndex 0x006 6. PDO Mapping entry (object 0x6000 (COM Inputs), UINT32 RO 0x6000:06, 1
entry 0x06 (Framing error))
1A04:07 SubIndex 0x007 7. PDO Mapping entry (object 0x6000 (COM Inputs), UINT32 RO 0x6000:07, 1
entry 0x07 (Overrun error))
1A04:08 SubIndex 0x008 8. PDO Mapping entry (1 bits align) UINT32 RO 0x0000:00, 1
1A04:09 SubIndex 0x009 9. PDO Mapping entry (object 0x6000 (COM Inputs), UINT32 RO 0x6000:09, 8
entry 0x09 (Input length))
1A04:0A SubIndex 0x010 10. PDO Mapping entry (object 0x6000 (COM Inputs), UINT32 RO 0x6000:11, 8
entry 0x11 (Data In 0))
1A04:0B SubIndex 0x011 11. PDO Mapping entry (object 0x6000 (COM Inputs), UINT32 RO 0x6000:12, 8
entry 0x12 (Data In 1))
1A04:0C SubIndex 0x012 12. PDO Mapping entry (object 0x6000 (COM Inputs), UINT32 RO 0x6000:13, 8
entry 0x13 (Data In 2))
1A04:0D SubIndex 0x013 13. PDO Mapping entry (object 0x6000 (COM Inputs), UINT32 RO 0x6000:14, 8
entry 0x14 (Data In 3))
1A04:0E SubIndex 0x014 14. PDO Mapping entry (object 0x6000 (COM Inputs), UINT32 RO 0x6000:15, 8
entry 0x15 (Data In 4))
1A04:0F SubIndex 0x015 15. PDO Mapping entry (object 0x6000 (COM Inputs), UINT32 RO 0x6000:16, 8
entry 0x16 (Data In 5))
1A04:10 SubIndex 0x016 16. PDO Mapping entry (object 0x6000 (COM Inputs), UINT32 RO 0x6000:17, 8
entry 0x17 (Data In 6))
1A04:11 SubIndex 0x017 17. PDO Mapping entry (object 0x6000 (COM Inputs), UINT32 RO 0x6000:18, 8
entry 0x18 (Data In 7))
1A04:12 SubIndex 0x018 18. PDO Mapping entry (object 0x6000 (COM Inputs), UINT32 RO 0x6000:19, 8
entry 0x19 (Data In 8))
1A04:13 SubIndex 0x019 19. PDO Mapping entry (object 0x6000 (COM Inputs), UINT32 RO 0x6000:1A, 8
entry 0x1A (Data In 9))
1A04:14 SubIndex 0x020 20. PDO Mapping entry (object 0x6000 (COM Inputs), UINT32 RO 0x6000:1B, 8
entry 0x1B (Data In 10))
1A04:15 SubIndex 0x021 21. PDO Mapping entry (object 0x6000 (COM Inputs), UINT32 RO 0x6000:1C, 8
entry 0x1C (Data In 11))
1A04:16 SubIndex 0x022 22. PDO Mapping entry (object 0x6000 (COM Inputs), UINT32 RO 0x6000:1D, 8
entry 0x1D (Data In 12))
1A04:17 SubIndex 0x023 23. PDO Mapping entry (object 0x6000 (COM Inputs), UINT32 RO 0x6000:1E, 8
entry 0x1E (Data In 13))
1A04:18 SubIndex 0x024 24. PDO Mapping entry (object 0x6000 (COM Inputs), UINT32 RO 0x6000:1F, 8
entry 0x1F (Data In 14))
1A04:19 SubIndex 0x025 25. PDO Mapping entry (object 0x6000 (COM Inputs), UINT32 RO 0x6000:20, 8
entry 0x20 (Data In 15))
1A04:1A SubIndex 0x026 26. PDO Mapping entry (object 0x6000 (COM Inputs), UINT32 RO 0x6000:21, 8
entry 0x21 (Data In 16))
1A04:1B SubIndex 0x027 27. PDO Mapping entry (object 0x6000 (COM Inputs), UINT32 RO 0x6000:22, 8
entry 0x22 (Data In 17))
1A04:1C SubIndex 0x028 28. PDO Mapping entry (object 0x6000 (COM Inputs), UINT32 RO 0x6000:23, 8
entry 0x23 (Data In 18))
1A04:1D SubIndex 0x029 29. PDO Mapping entry (object 0x6000 (COM Inputs), UINT32 RO 0x6000:24, 8
entry 0x24 (Data In 19))
1A04:1E SubIndex 0x030 30. PDO Mapping entry (object 0x6000 (COM Inputs), UINT32 RO 0x6000:25, 8
entry 0x25 (Data In 20))
1A04:1F SubIndex 0x031 31. PDO Mapping entry (object 0x6000 (COM Inputs), UINT32 RO 0x6000:26, 8
entry 0x26 (Data In 21))

EL600x, EL602x Version: 4.6 155


Overview of CoE objects EL6001, EL6021

Index 0x1A05 COM ext. inputs


Index Name Meaning Data type Flags Default
(hex)
1A05:0 COM ext. inputs PDO Mapping TxPDO 6 UINT8 RO 0x3B (59dec)
1A05:01 SubIndex 0x001 1. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:01, 1
puts), entry 0x01 (Transmit accepted))
1A05:02 SubIndex 0x002 2. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:02, 1
puts), entry 0x02 (Receive request))
1A05:03 SubIndex 0x003 3. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:03, 1
puts), entry 0x03 (Init accepted))
1A05:04 SubIndex 0x004 4. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:04, 1
puts), entry 0x04 (Buffer full))
1A05:05 SubIndex 0x005 5. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:05, 1
puts), entry 0x05 (Parity error))
1A05:06 SubIndex 0x006 6. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:06, 1
puts), entry 0x06 (Framing error))
1A05:07 SubIndex 0x007 7. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:07, 1
puts), entry 0x07 (Overrun error))
1A05:08 SubIndex 0x008 8. PDO Mapping entry (1 bits align) UINT32 RO 0x0000:00, 1
1A05:09 SubIndex 0x009 9. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:09, 8
puts), entry 0x09 (Input length))
1A05:0A SubIndex 0x010 10. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:11, 16
puts), entry 0x11 (Data In 0))
1A05:0B SubIndex 0x011 11. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:12, 16
puts), entry 0x12 (Data In 1))
1A05:0C SubIndex 0x012 12. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:13, 16
puts), entry 0x13 (Data In 2))
1A05:0D SubIndex 0x013 13. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:14, 16
puts), entry 0x14 (Data In 3))
1A05:0E SubIndex 0x014 14. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:15, 16
puts), entry 0x15 (Data In 4))
1A05:0F SubIndex 0x015 15. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:16, 16
puts), entry 0x16 (Data In 5))
1A05:10 SubIndex 0x016 16. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:17, 16
puts), entry 0x17 (Data In 6))
1A05:11 SubIndex 0x017 17. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:18, 16
puts), entry 0x18 (Data In 7))
1A05:12 SubIndex 0x018 18. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:19, 16
puts), entry 0x19 (Data In 8))
1A05:13 SubIndex 0x019 19. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:1A, 16
puts), entry 0x1A (Data In 9))
1A05:14 SubIndex 0x020 20. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:1B, 16
puts), entry 0x1B (Data In 10))
1A05:15 SubIndex 0x021 21. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:1C, 16
puts), entry 0x1C (Data In 11))
1A05:16 SubIndex 0x022 22. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:1D, 16
puts), entry 0x1D (Data In 12))
1A05:17 SubIndex 0x023 23. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:1E, 16
puts), entry 0x1E (Data In 13))
1A05:18 SubIndex 0x024 24. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:1F, 16
puts), entry 0x1F (Data In 14))
1A05:19 SubIndex 0x025 25. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:20, 16
puts), entry 0x20 (Data In 15))
1A05:1A SubIndex 0x026 26. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:21, 16
puts), entry 0x21 (Data In 16))
1A05:1B SubIndex 0x027 27. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:22, 16
puts), entry 0x22 (Data In 17))
1A05:1C SubIndex 0x028 28. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:23, 16
puts), entry 0x23 (Data In 18))
1A05:1D SubIndex 0x029 29. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:24, 16
puts), entry 0x24 (Data In 19))
1A05:1E SubIndex 0x030 30. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:25, 16
puts), entry 0x25 (Data In 20))
1A05:1F SubIndex 0x031 31. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:26, 16
puts), entry 0x26 (Data In 21))

156 Version: 4.6 EL600x, EL602x


Overview of CoE objects EL6001, EL6021

Index Name Meaning Data type Flags Default


(hex)
1A05:20 SubIndex 0x032 32. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:27, 16
puts), entry 0x27 (Data In 22))
1A05:21 SubIndex 0x033 33. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:28, 16
puts), entry 0x28 (Data In 23))
1A05:22 SubIndex 0x034 34. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:29, 16
puts), entry 0x29 (Data In 24))
1A05:23 SubIndex 0x035 35. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:2A, 16
puts), entry 0x2A (Data In 25))
1A05:24 SubIndex 0x036 36. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:2B, 16
puts), entry 0x2B (Data In 26))
1A05:25 SubIndex 0x037 37. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:2C, 16
puts), entry 0x2C (Data In 27))
1A05:26 SubIndex 0x038 38. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:2D, 16
puts), entry 0x2D (Data In 28))
1A05:27 SubIndex 0x039 39. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:2E, 16
puts), entry 0x2E (Data In 29))
1A05:28 SubIndex 0x040 40. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:2F, 16
puts), entry 0x2F (Data In 30))
1A05:29 SubIndex 0x041 41. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:30, 16
puts), entry 0x30 (Data In 31))
1A05:2A SubIndex 0x042 42. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:31, 16
puts), entry 0x31 (Data In 32))
1A05:2B SubIndex 0x043 43. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:32, 16
puts), entry 0x32 (Data In 33))
1A05:2C SubIndex 0x044 44. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:33, 16
puts), entry 0x33 (Data In 34))
1A05:2D SubIndex 0x045 45. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:34, 16
puts), entry 0x34 (Data In 35))
1A05:2E SubIndex 0x046 46. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:35, 16
puts), entry 0x35 (Data In 36))
1A05:2F SubIndex 0x047 47. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:36, 16
puts), entry 0x36 (Data In 37))
1A05:30 SubIndex 0x048 48. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:37, 16
puts), entry 0x37 (Data In 38))
1A05:31 SubIndex 0x049 49. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:38, 16
puts), entry 0x38 (Data In 39))
1A05:32 SubIndex 0x050 50. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:39, 16
puts), entry 0x39 (Data In 40))
1A05:33 SubIndex 0x051 51. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:3A, 16
puts), entry 0x3A (Data In 41))
1A05:34 SubIndex 0x052 52. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:3B, 16
puts), entry 0x3B (Data In 42))
1A05:35 SubIndex 0x053 53. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:3C, 16
puts), entry 0x3C (Data In 43))
1A05:36 SubIndex 0x054 54. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:3D, 16
puts), entry 0x3D (Data In 44))
1A05:37 SubIndex 0x055 55. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:3E, 16
puts), entry 0x3E (Data In 45))
1A05:38 SubIndex 0x056 56. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:3F, 16
puts), entry 0x3F (Data In 46))
1A05:39 SubIndex 0x057 57. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:40, 16
puts), entry 0x40 (Data In 47))
1A05:3A SubIndex 0x058 58. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:41, 16
puts), entry 0x41 (Data In 48))
1A05:3B SubIndex 0x059 59. PDO Mapping entry (object 0x6001 (COM ext. in- UINT32 RO 0x6001:42, 16
puts), entry 0x42 (Data In 49))

EL600x, EL602x Version: 4.6 157


Overview of CoE objects EL6001, EL6021

Index 0x1C00 Sync manager type


Index Name Meaning Data type Flags Default
(hex)
1C00:0 Sync manager type Using the sync managers UINT8 RO 0x04 (4dec)
1C00:01 SubIndex 0x001 Sync-Manager Type Channel 1: Mailbox Write UINT8 RO 0x01 (1dec)
1C00:02 SubIndex 0x002 Sync-Manager Type Channel 2: Mailbox Read UINT8 RO 0x02 (2dec)
1C00:03 SubIndex 0x003 Sync-Manager Type Channel 3: Process Data Write UINT8 RO 0x03 (3dec)
(Outputs)
1C00:04 SubIndex 0x004 Sync-Manager Type Channel 4: Process Data Read UINT8 RO 0x04 (4dec)
(Inputs)

Index 0x1C12 RxPDO assign


Index Name Meaning Data type Flags Default
(hex)
1C12:0 RxPDO assign PDO Assign Outputs UINT8 RW 0x01 (1dec)
1C12:01 SubIndex 0x001 1st allocated RxPDO (contains the index 0x of the as- UINT16 RW 0x1602
sociated RxPDO mapping object) (5634dec)
1C12:02 SubIndex 0x002 2nd allocated RxPDO (contains the index 0x of the as- UINT16 RW 0x0000 (0dec)
sociated RxPDO mapping object)

Index 0x1C13 TxPDO assign


Index Name Meaning Data type Flags Default
(hex)
1C13:0 TxPDO assign PDO Assign Inputs UINT8 RW 0x01 (1dec)
1C13:01 SubIndex 0x001 1st allocated TxPDO (contains the index 0x of the as- UINT16 RW 0x1A02
sociated TxPDO mapping object) (6658dec)
1C13:02 SubIndex 0x002 2nd allocated TxPDO (contains the index 0x of the as- UINT16 RW 0x0000 (0dec)
sociated TxPDO mapping object)

Index 0x1C32 SM output parameter [from hardware version 03]


Index Name Meaning Data type Flags Default
(hex)
1C32:0 SM output parameter Synchronization parameters for the outputs UINT8 RO 0x20 (32dec)
1C32:01 Sync mode Current synchronization mode: UINT16 RW 0x0001 (1dec)
• 0: Free Run
• 1: Synchron with SM 2 Event
• 2: DC-Mode - Synchron with SYNC0 Event
• 3: DC-Mode - Synchron with SYNC1 Event
1C32:02 Cycle time Cycle time (in ns): UINT32 RW 0x0007A120
(500000dec)
• Free Run: Cycle time of the local timer
• Synchronous with SM 2 event: Master cycle
time
• DC-Mode: SYNC0/SYNC1 Cycle Time
1C32:03 Shift time Time between SYNC0 event and output of the outputs UINT32 RO 0x00000000
(in ns, DC mode only) (0dec)
1C32:04 Sync modes supported Supported synchronization modes: UINT16 RO 0xC007
(49159dec)
• Bit 0 = 1: free run is supported
• Bit 1 = 1: Synchronous with SM 2 event is
supported
• Bit 2-3 = 01: DC mode is supported
• Bit 4-5 = 10: Output shift with SYNC1 event
(only DC mode)
• Bit 14 = 1: dynamic times (measurement
through writing of 1C32:08 [} 158])
1C32:05 Minimum cycle time Minimum cycle time (in ns) UINT32 RO 0x00004E20
(20000dec)

158 Version: 4.6 EL600x, EL602x


Overview of CoE objects EL6001, EL6021

Index Name Meaning Data type Flags Default


(hex)
1C32:06 Calc and copy time Minimum time between SYNC0 and SYNC1 event (in UINT32 RO 0x00000000
ns, DC mode only) (0dec)
1C32:08 Command • 0: Measurement of the local cycle time is UINT16 RW 0x0000 (0dec)
stopped
• 1: Measurement of the local cycle time is
started
The entries 1C32:03, 1C32:05, 1C32:06, 1C32:09 [} 158],
1C33:03, 1C33:06, 1C33:09 [} 159] are updated with the
maximum measured values.
For a subsequent measurement the measured values
are reset
1C32:09 Delay time Time between SYNC1 event and output of the outputs UINT32 RO 0x00000000
(in ns, DC mode only) (0dec)
1C32:0B SM event missed Number of missed SM events in OPERATIONAL (DC UINT16 RO 0x0000 (0dec)
counter mode only)
1C32:0C Cycle exceeded counter Number of occasions the cycle time was exceeded in UINT16 RO 0x0000 (0dec)
OPERATIONAL (cycle was not completed in time or
the next cycle began too early)
1C32:0D Shift too short counter Number of occasions that the interval between SYNC0 UINT16 RO 0x0000 (0dec)
and SYNC1 event was too short (DC mode only)
1C32:20 Sync error The synchronization was not correct in the last cycle BOOLEAN RO 0x00 (0dec)
(outputs were output too late; DC mode only)

Index 0x1C33 SM input parameter [from hardware version 03]


Index Name Meaning Data type Flags Default
(hex)
1C33:0 SM input parameter Synchronization parameters for the inputs UINT8 RO 0x20 (32dec)
1C33:01 Sync mode Current synchronization mode: UINT16 RW 0x0022 (34dec)
• 0: Free Run
• 1: Synchronous with SM 3 event (no outputs
available)
• 2: DC - Synchron with SYNC0 Event
• 3: DC - Synchron with SYNC1 Event
• 34: Synchronous with SM 2 event (outputs
available)
1C33:02 Cycle time as 1C32:02 [} 158] UINT32 RW 0x0007A120
(500000dec)
1C33:03 Shift time Time between SYNC0 event and reading of the inputs UINT32 RO 0x00000000
(in ns, only DC mode) (0dec)
1C33:04 Sync modes supported Supported synchronization modes: UINT16 RO 0xC007
(49159dec)
• Bit 0: free run is supported
• Bit 1: synchronous with SM 2 event is supported
(outputs available)
• Bit 1: synchronous with SM 3 event is supported
(no outputs available)
• Bit 2-3 = 01: DC mode is supported
• Bit 4-5 = 01: input shift through local event
(outputs available)
• Bit 4-5 = 10: input shift with SYNC1 event (no
outputs available)
• Bit 14 = 1: dynamic times (measurement
through writing of 1C32:08 [} 158] or 1C33:08
[} 159])
1C33:05 Minimum cycle time as 1C32:05 [} 158] UINT32 RO 0x00004E20
(20000dec)
1C33:06 Calc and copy time Time between reading of the inputs and availability of UINT32 RO 0x00000000
the inputs for the master (in ns, only DC mode) (0dec)
1C33:08 Command as 1C32:08 [} 158] UINT16 RW 0x0000 (0dec)

EL600x, EL602x Version: 4.6 159


Overview of CoE objects EL6001, EL6021

Index Name Meaning Data type Flags Default


(hex)
1C33:09 Delay time Time between SYNC1 event and reading of the inputs UINT32 RO 0x00000000
(in ns, only DC mode) (0dec)
1C33:0B SM event missed as 1C32:11 [} 158] UINT16 RO 0x0000 (0dec)
counter
1C33:0C Cycle exceeded counter as 1C32:12 [} 158] UINT16 RO 0x0000 (0dec)
1C33:0D Shift too short counter as 1C32:13 [} 158] UINT16 RO 0x0000 (0dec)
1C33:20 Sync error as 1C32:32 [} 158] BOOLEAN RO 0x00 (0dec)

Index 0x3001 Outputs


Index Name Meaning Data type Flags Default
(hex)
3001:0 Outputs Length of this object UINT8 RO 0x04 (4dec)
3001:01 Ctrl Control-Byte [} 165] UINT8 RO 0x00 (0dec)
3001:02 Data Out 0 Output byte 0 UINT8 RO 0x00 (0dec)
3001:03 Data Out 1 Output byte 1 UINT8 RO 0x00 (0dec)
3001:04 Data Out 2 Output byte 2 UINT8 RO 0x00 (0dec)

Index 0x3002 Outputs


Index Name Meaning Data type Flags Default
(hex)
3002:0 Outputs Length of this object UINT8 RO 0x06 (6dec)
3002:01 Ctrl Control-Byte [} 165] UINT8 RO 0x00 (0dec)
3002:02 Data Out 0 Output byte 0 UINT8 RO 0x00 (0dec)
3002:03 Data Out 1 Output byte 1 UINT8 RO 0x00 (0dec)
3002:04 Data Out 2 Output byte 2 UINT8 RO 0x00 (0dec)
3002:05 Data Out 3 Output byte 3 UINT8 RO 0x00 (0dec)
3002:06 Data Out 4 Output byte 4 UINT8 RO 0x00 (0dec)

Index 0x3003 Outputs


Index Name Meaning Data type Flags Default
(hex)
3003:0 Outputs Length of this object UINT8 RO 0x17 (23dec)
3003:01 Ctrl Control word [} 165] UINT16 RO 0x0000 (0dec)
3003:02 Data Out 0 Output byte 0 UINT8 RO 0x00 (0dec)
3003:03 Data Out 1 Output byte 1 UINT8 RO 0x00 (0dec)
3003:04 Data Out 2 Output byte 2 UINT8 RO 0x00 (0dec)
3003:05 Data Out 3 Output byte 3 UINT8 RO 0x00 (0dec)
3003:06 Data Out 4 Output byte 4 UINT8 RO 0x00 (0dec)
3003:07 Data Out 5 Output byte 5 UINT8 RO 0x00 (0dec)
3003:08 Data Out 6 Output byte 6 UINT8 RO 0x00 (0dec)
3003:09 Data Out 7 Output byte 7 UINT8 RO 0x00 (0dec)
3003:0A Data Out 8 Output byte 8 UINT8 RO 0x00 (0dec)
3003:0B Data Out 9 Output byte 9 UINT8 RO 0x00 (0dec)
3003:0C Data Out 10 Output byte 10 UINT8 RO 0x00 (0dec)
3003:0D Data Out 11 Output byte 11 UINT8 RO 0x00 (0dec)
3003:0E Data Out 12 Output byte 12 UINT8 RO 0x00 (0dec)
3003:0F Data Out 13 Output byte 13 UINT8 RO 0x00 (0dec)
3003:10 Data Out 14 Output byte 14 UINT8 RO 0x00 (0dec)
3003:11 Data Out 15 Output byte 15 UINT8 RO 0x00 (0dec)
3003:12 Data Out 16 Output byte 16 UINT8 RO 0x00 (0dec)
3003:13 Data Out 17 Output byte 17 UINT8 RO 0x00 (0dec)
3003:14 Data Out 18 Output byte 18 UINT8 RO 0x00 (0dec)
3003:15 Data Out 19 Output byte 19 UINT8 RO 0x00 (0dec)
3003:16 Data Out 20 Output byte 20 UINT8 RO 0x00 (0dec)
3003:17 Data Out 21 Output byte 21 UINT8 RO 0x00 (0dec)

160 Version: 4.6 EL600x, EL602x


Overview of CoE objects EL6001, EL6021

Index 0x3101 Inputs


Index Name Meaning Data type Flags Default
(hex)
3101:0 Inputs Length of this object UINT8 RO 0x04 (4dec)
3101:01 Status Status byte [} 165] UINT8 RO 0x00 (0dec)
3101:02 Data In 0 Input byte 0 UINT8 RO 0x00 (0dec)
3101:03 Data In 1 Input byte 1 UINT8 RO 0x00 (0dec)
3101:04 Data In 2 Input byte 2 UINT8 RO 0x00 (0dec)

Index 0x3102 Inputs


Index Name Meaning Data type Flags Default
(hex)
3102:0 Inputs Length of this object UINT8 RO 0x06 (6dec)
3102:01 Status Status byte [} 165] UINT8 RO 0x00 (0dec)
3102:02 Data In 0 Input byte 0 UINT8 RO 0x00 (0dec)
3102:03 Data In 1 Input byte 1 UINT8 RO 0x00 (0dec)
3102:04 Data In 2 Input byte 2 UINT8 RO 0x00 (0dec)
3102:05 Data In 3 Input byte 3 UINT8 RO 0x00 (0dec)
3102:06 Data In 4 Input byte 4 UINT8 RO 0x00 (0dec)

Index 0x3103 Inputs


Index Name Meaning Data type Flags Default
(hex)
3103:0 Inputs Length of this object UINT8 RO 0x17 (23dec)
3103:01 Status Status word [} 165] UINT16 RO 0x0000 (0dec)
3103:02 Data In 0 Input byte 0 UINT8 RO 0x00 (0dec)
3103:03 Data In 1 Input byte 1 UINT8 RO 0x00 (0dec)
3103:04 Data In 2 Input byte 2 UINT8 RO 0x00 (0dec)
3103:05 Data In 3 Input byte 3 UINT8 RO 0x00 (0dec)
3103:06 Data In 4 Input byte 4 UINT8 RO 0x00 (0dec)
3103:07 Data In 5 Input byte 5 UINT8 RO 0x00 (0dec)
3103:08 Data In 6 Input byte 6 UINT8 RO 0x00 (0dec)
3103:09 Data In 7 Input byte 7 UINT8 RO 0x00 (0dec)
3103:0A Data In 8 Input byte 8 UINT8 RO 0x00 (0dec)
3103:0B Data In 9 Input byte 9 UINT8 RO 0x00 (0dec)
3103:0C Data In 10 Input byte 10 UINT8 RO 0x00 (0dec)
3103:0D Data In 11 Input byte 11 UINT8 RO 0x00 (0dec)
3103:0E Data In 12 Input byte 12 UINT8 RO 0x00 (0dec)
3103:0F Data In 13 Input byte 13 UINT8 RO 0x00 (0dec)
3103:10 Data In 14 Input byte 14 UINT8 RO 0x00 (0dec)
3103:11 Data In 15 Input byte 15 UINT8 RO 0x00 (0dec)
3103:12 Data In 16 Input byte 16 UINT8 RO 0x00 (0dec)
3103:13 Data In 17 Input byte 17 UINT8 RO 0x00 (0dec)
3103:14 Data In 18 Input byte 18 UINT8 RO 0x00 (0dec)
3103:15 Data In 19 Input byte 19 UINT8 RO 0x00 (0dec)
3103:16 Data In 20 Input byte 20 UINT8 RO 0x00 (0dec)
3103:17 Data In 21 Input byte 21 UINT8 RO 0x00 (0dec)

Index 0x4070 Data bytes in send buffer


Index Name Meaning Data type Flags Default
(hex)
4070:0 Data bytes in send buf- Number of data bytes in the send FIFO UINT16 RO 0x0000 (0dec)
fer

EL600x, EL602x Version: 4.6 161


Overview of CoE objects EL6001, EL6021

Index 0x4071 Data bytes in receive buffer


Index Name Meaning Data type Flags Default
(hex)
4071:0 Data bytes in receive Number of data bytes in the receive FIFO UINT16 RO 0x0000 (0dec)
buffer

Index 0x4072 Diagnostic


Index Name Meaning Data type Flags Default
(hex)
4072:0 Diagnostic Length of this object UINT8 RO 0x05 (5dec)
4072:01 Buffer overflow A buffer overflow has occurred. BOOLEAN RO 0x00 (0dec)
4072:02 Parity error A parity error has occurred. The affected data item is BOOLEAN RO 0x00 (0dec)
not loaded into the receive FIFO of the terminal and is
lost.
4072:03 Framing error A framing error has occurred. The affected data item is BOOLEAN RO 0x00 (0dec)
not loaded into the receive FIFO of the terminal and is
lost.
4072:04 Overrun error An overrun error has occurred. The affected data item BOOLEAN RO 0x00 (0dec)
is not loaded into the receive FIFO of the terminal and
is lost.
4072:05 Buffer full The reception FIFO is full. All further incoming data will BOOLEAN RO 0x00 (0dec)
be lost!

6.1.3 Profile-specific objects (0x6000-0xFFFF) [from hardware


version 03]
The profile-specific objects have the same meaning for all EtherCAT slaves that support the profile 5001.

Index 0x6000 COM Inputs


Index Name Meaning Data type Flags Default
(hex)
6000:0 COM Inputs Max. SubIndex (hex) UINT8 RO 0x26 (38dec)
6000:01 Transmit accepted The terminal acknowledges receipt of data by changing BOOLEAN RO 0x00 (0dec)
the state of this bit. Only now new data can be trans-
ferred from the controller to the terminal.
6000:02 Receive request By changing the state of this bit, the terminal informs BOOLEAN RO 0x00 (0dec)
the controller that the DataIn bytes contain the number
of bytes displayed in “Input length [} 162]”. The con-
troller must acknowledge receipt of the data by chang-
ing the state of the ReceiveAccepted [} 163] bit. Only
then new data can be transferred from the terminal to
the controller.
6000:03 Init accepted 0 The terminal is ready again for serial data ex- BOOLEAN RO 0x00 (0dec)
change.
1 Initialization was completed by the terminal.
6000:04 Buffer full The reception FIFO is full. All incoming data will be lost BOOLEAN RO 0x00 (0dec)
from this point on!
6000:05 Parity error A parity error has occurred. BOOLEAN RO 0x00 (0dec)
6000:06 Framing error A framing error has occurred. BOOLEAN RO 0x00 (0dec)
6000:07 Overrun error An overrun error has occurred. BOOLEAN RO 0x00 (0dec)
6000:09 Input length Number of input bytes available for transfer from the UINT8 RO 0x00 (0dec)
terminal to the controller.
6000:11 Data In 0 Input byte 0 UINT8 RO 0x00 (0dec)
... ... .... ... ... ...
6000:26 Data In 21 Input byte 21 UINT8 RO 0x00 (0dec)

162 Version: 4.6 EL600x, EL602x


Overview of CoE objects EL6001, EL6021

Index 0x6001 COM ext. inputs


Index Name Meaning Data type Flags Default
(hex)
6001:0 COM ext. inputs UINT8 RO 0x00 (0dec)
6001:01 Transmit accepted identical to index 0x6000 BOOLEAN RO 0x00 (0dec)
6001:02 Receive request BOOLEAN RO 0x00 (0dec)
6001:03 Init accepted BOOLEAN RO 0x00 (0dec)
6001:04 Buffer full BOOLEAN RO 0x00 (0dec)
6001:05 Parity error BOOLEAN RO 0x00 (0dec)
6001:06 Framing error BOOLEAN RO 0x00 (0dec)
6001:07 Overrun error BOOLEAN RO 0x00 (0dec)
6001:09 Input length UINT8 RO 0x00 (0dec)
6001:11 Data In 0 UINT16 RO 0x0000 (0dec)
....
6001:42 Data In 49 UINT16 RO 0x0000 (0dec)

Index 0x7000 COM Outputs


Index Name Meaning Data type Flags Default
(hex)
7000:0 COM Outputs Max. SubIndex (hex) UINT8 RO 0x26 (38dec)
7000:01 Transmit request By changing the state of this bit, the controller informs BOOLEAN RO 0x00 (0dec)
the terminal that the DataOut bytes contain the number
of bytes displayed in “Output length [} 163]”. The ter-
minal acknowledges receipt of the data by changing
the state of the “TransmitAccepted [} 162]” bit. Only
now new data can be transferred from the controller to
the terminal.
7000:02 Receive accepted The controller acknowledges receipt of data by chang- BOOLEAN RO 0x00 (0dec)
ing the state of this bit. Only then new data can be
transferred from the terminal to the controller.
7000:03 Init request 0 The controller once again requests the terminal to BOOLEAN RO 0x00 (0dec)
prepare for serial data exchange.
1 The controller requests terminal for initialization.
The transmit and receive functions will be blocked,
the FIFO pointer will be reset and the interface will
be initialized with the values of the responsible Set-
tings object. The execution of the initialization will
be acknowledged by the terminal with the ‘Init ac-
cepted [} 162]’ bit.
7000:04 Send continuous Continuous sending of data from the FIFO. BOOLEAN RO 0x00 (0dec)
The send buffer is filled (up to 128 bytes) by the con-
troller. The filled buffer contents will be sent on the ris-
ing edge of the bit. If the data has been transmitted, the
terminal informs the controller by setting the “Init ac-
cepted [} 162]” bit. “Init accepted [} 162]” is cleared
with “SendContinuous [} 163]”.
7000:09 Output length Number of output bytes available for transfer from the UINT8 RO 0x00 (0dec)
controller to the terminal.
7000:11 Data Out 0 Output byte 0 UINT8 RO 0x00 (0dec)
... ... .... ... ... ...
7000:26 Data Out 21 Output byte 21 UINT8 RO 0x00 (0dec)

EL600x, EL602x Version: 4.6 163


Overview of CoE objects EL6001, EL6021

Index 0x7001 COM ext. outputs


Index Name Meaning Data type Flags Default
(hex)
7001:0 COM ext. outputs UINT8 RO 0x00 (0dec)
7001:01 Transmit request identical to index 0x7000 BOOLEAN RO 0x00 (0dec)
7001:02 Receive accepted BOOLEAN RO 0x00 (0dec)
7001:03 Init request BOOLEAN RO 0x00 (0dec)
7001:04 Send continuous BOOLEAN RO 0x00 (0dec)
7001:09 Output length UINT8 RO 0x00 (0dec)
7001:11 Data Out 0 UINT16 RO 0x0000 (0dec)
… < < <
7001:42 Data Out 49 UINT16 RO 0x0000 (0dec)

Index 0xA000 COM Diag data


Index Name Meaning Data type Flags Default
(hex)
A000:0 COM Diag data Max. SubIndex (hex) UINT8 RO 0x21 (33dec)
A000:01 Buffer overflow A buffer overflow has occurred. BOOLEAN RO 0x00 (0dec)
A000:02 Parity error A parity error has occurred. BOOLEAN RO 0x00 (0dec)
A000:03 Framing error A framing error has occurred BOOLEAN RO 0x00 (0dec)
A000:04 Overrun error An overrun error has occurred. BOOLEAN RO 0x00 (0dec)
A000:05 Buffer full The reception FIFO is full. All incoming data will be lost BOOLEAN RO 0x00 (0dec)
from this point on!
A000:11 Data bytes in send buf- Number of data bytes in the send FIFO UINT16 RO 0x0000 (0dec)
fer
A000:21 Data bytes in receive Number of data bytes in the receive FIFO UINT16 RO 0x0000 (0dec)
buffer

Index 0xB000 Command

Only EL6021 since FW06 and EL6001 since FW08.


Index Name Meaning Data type Flags Default
(hex)
B000:0 Command Max. SubIndex (hex) UINT8 RO 0x03 (3dec)
B000:01 Request Commands can be sent to the terminal via the request OCTET- RW {0}
object STRING[2]
see command mode [} 125]
B000:02 Status Status of the command currently being executed UINT8 RO 0x00 (0dec)
0: Command executed without error.
255: Command is being executed
B000:03 Response Optional response value of the command OCTET- RO {0}
Byte 0: see B000:02 STRING[6]
Byte 1: not used
2-n: Service response Data

Index 0xF000 Modular device profile


Index Name Meaning Data type Flags Default
(hex)
F000:0 Modular device profile General information for the modular device profile UINT8 RO 0x02 (2dec)
F000:01 Module Index 0xdistance Index (hex) interval of the objects of the individual UINT16 RO 0x0010 (16dec)
channels
F000:02 Maximum number of Number of channels UINT16 RO 0x0002 (2dec)
modules

Index 0xF008 Code word


Index Name Meaning Data type Flags Default
(hex)
F008:0 Code word reserved UINT32 RW 0x00000000
(0dec)

164 Version: 4.6 EL600x, EL602x


Overview of CoE objects EL6001, EL6021

Index 0xF010 Module list


Index Name Meaning Data type Flags Default
(hex)
F010:0 Module list Max. SubIndex (hex) UINT8 RW 0x02 (2dec)
F010:01 SubIndex 0x001 - UINT32 RW 0x00000000
(0dec)
F010:02 SubIndex 0x002 - UINT32 RW 0x00000258
(600dec)

6.2 Control and status word


Control word

The control word (CW) is located in the output process image, and is transmitted from the controller to the
terminal.
Bit CW.15 CW.14 CW.13 CW.12 CW.11 CW.10 CW.9 CW.8 CW.7 CW.6 CW.5 CW.4 CW.3 CW.2 CW.1 CW.0
Name OL7 OL6 OL5 OL4 OL3 OL2 OL1 OL0 - OL2* OL1* OL0* SC IR RA TR

Bits CW.15 to CW.8 are only shown if the large process image is used.
If the small or medium process image is used, only bits CW.7 to CW.0 are shown as control bytes! The
number of output bytes available for transfer from the controller to the terminal is displayed by bits OL2* ...
OL0*.

Legend
Bit Name Description
CW.15 ... CW8 OL7 ... OL0 1dec... 22dec If the large process image is used: Number of output bytes available for
(OutLenght) transfer from the controller to the terminal.
- If the small/medium process image is used: not shown
CW.7 - 0bin reserved
CW.6 ... CW.4 OL2* ... OL0* 0 If the large process image is used: reserved
(OutLenght*) 1 ... 6 If the medium process image is used: Number of output bytes available for
transfer from the controller to the terminal.
1 ... 4 If the small process image is used: Number of output bytes available for
transfer from the controller to the terminal.
CW.3 SC rise Continuous sending of data from the FIFO.
(SendContinuous)
The send buffer is filled (up to 128 bytes) by the controller. The buffer content
is sent with rising edge of bit SC. The terminal acknowledges the data trans-
fer to the controller through setting of bit SW.2. SW.2 is cancelled with CW.3.
CW.2 IR 1bin The controller requests terminal for initialization. The send and receive func-
(InitRequest) tions are blocked, the FIFO pointers are reset, and the interface is initialized
with the values of the responsible objects (baud rate 4073 [} 144], data frame
4074 [} 144], feature bits 4075 [} 145]). The terminal acknowledges comple-
tion of the initialization via bit SW.2 [} 166] (IA).
0bin The controller once again requests the terminal to prepare for serial data ex-
change.
CW.1 RA toggle The controller acknowledges receipt of data by changing the state of this bit.
(ReceiveAccepted) Only then new data can be transferred from the terminal to the controller.
CW.0 TR toggle Via a change of state of this bit the controller notifies the terminal that the
(TransmitRequest) DataOut bytes contain the number of bytes indicated via the OL bits. The ter-
minal acknowledges receipt of the data in the status byte via a change of
state of bit SW.0 [} 166] (TA). Only now new data can be transferred from the
controller to the terminal.

EL600x, EL602x Version: 4.6 165


Overview of CoE objects EL6001, EL6021

Status word

The status word (SW) is located in the input process image, and is transmitted from terminal to the controller.
Bit SW. SW. SW. SW. SW. SW. SW. SW. SW. SW.6 SW.5 SW.4 SW.3 SW. SW. SW.
15 14 13 12 11 10 9 8 7 2 1 0
Name - - - - - - - - - IL2* IL1* IL0* BUF_F IA RR TA
(small and
medium
process im-
age)
Name IL7 IL6 IL5 IL4 IL3 IL2 IL1 IL0 - OVERRUN FRAMING PARITY BUF_F IA RR TA
(large process ERR ERR ERR
image)

If the small or medium process image is used, only bits SW.7 to SW.0 are shown as status bytes! The
number of input bytes available for transfer from the terminal to the controller is displayed by bits IL2* ... IL0*.

Legend
Bit Name Description
SW.15 ... SW8 IL7 ... IL0 1dec ... 22dec If the large process image is used: Number of input bytes available for trans-
(InLenght*) fer from the terminal to the controller.
- If the small/medium process image is used: not shown
SW.7 - 0bin reserved
SW.6 IL2*  0 ... 1 If the large process image is used: An overrun error has occurred. The af-
(InLenght*) fected data item is not loaded into the receive FIFO of the terminal and is lost.
1 ... 6 If the medium process image is used: Number of input bytes available for
OVERRUN ERR transfer from the terminal to the controller.
1 ... 4 If the small process image is used: Number of input bytes available for trans-
fer from the terminal to the controller.
SW.5 IL1*  0 ... 1 If the large process image is used: A framing error has occurred. The affected
(InLenght*) data item is not loaded into the receive FIFO of the terminal and is lost.
1 ... 6 If the medium process image is used: Number of input bytes available for
FRAMING ERR transfer from the terminal to the controller.
1 ... 4 If the small process image is used: Number of input bytes available for trans-
fer from the terminal to the controller.
SW.4 IL0* 0 ... 1 If the large process image is used: A parity error has occurred. The affected
(InLenght*) data item is not loaded into the receive FIFO of the terminal and is lost
1 ... 6 If the medium process image is used: Number of input bytes available for
PARITY ERR transfer from the terminal to the controller.
1 ... 4 If the small process image is used: Number of input bytes available for trans-
fer from the terminal to the controller.
SW.3 BUF_F 1bin The reception FIFO is full. All further incoming data will be lost!
SW.2 IA 1bin Initialization was completed by the terminal.
(InitAccepted-Bit) 0bin The terminal is ready again for serial data exchange.
SW.1 RR toggle Via a change of state of this bit the terminal notifies the controller that the
(ReceiveRequest) DataIn bytes contain the number of bytes indicated via the IL bits. The con-
troller has to acknowledge receipt of the data in the control byte via a change
of state of bit CW.1 [} 165] (RA). Only then new data can be transferred from
the terminal to the controller.
SW.0 TA toggle The terminal acknowledges receipt of data by changing the state of this bit.
(TransmitAccepted) Only now new data can be transferred from the controller to the terminal.

166 Version: 4.6 EL600x, EL602x


Overview of CoE objects EL6001, EL6021

Data transfer examples

The examples use the large process image.


• Initialization:
Control word Status word Comment
CW.15 ... CW.8 CW.7 ... CW.0 SW.15 ... SW.8 SW.7 ... SW.0
xxxx xxxxbin xxxx xxxxbin xxxx xxxxbin xxxx xxxxbin Start of data transmission
0000 0000bin 0000 0100bin 0000 0000bin 0000 0000bin The controller requests terminal
initialization
0000 0000bin 0000 0100bin 0000 0000bin 0000 0100bin Command is executed: Terminal
initialization is complete
0000 0000bin 0000 0000bin 0000 0000bin 0000 0100bin The controller requests the terminal to
prepare for serial data exchange
0000 0000bin 0000 0000bin 0000 0000bin 0000 0000bin Command is executed: Terminal is ready
for serial data exchange

• Data transfer from the controller to the terminal:


Control word Status word Comment
CW.15 ... CW.8 CW.7 ... CW.0 SW.15 ... SW.8 SW.7 ... SW.0
0000 0000bin 0000 0000bin xxxx xxxxbin 0000 x0x0bin Start of data transmission
0000 0010bin 0000 0001bin xxxx xxxxbin 0000 x0x0bin The controller requests transmission of 2
bytes by the terminal
0000 0010bin 0000 0001bin xxxx xxxxbin 0000 x0x1bin Command is executed: Terminal has
loaded 2 bytes into the transmission FIFO
0001 0000bin 0000 0000bin xxxx xxxxbin 0000 x0x1bin The controller requests transmission of 16
bytes by the terminal
0001 0000bin 0000 0000bin xxxx xxxxbin 0000 x0x0bin Command is executed: Terminal has
loaded 16 bytes into the transmission FIFO

• Data transfer from the terminal to the controller:


Control word Status word Comment
CW.15 ... CW.8 CW.7 ... CW.0 SW.15 ... SW.8 SW.7 ... SW.0
xxxx xxxxbin 0000 000xbin 0000 0000bin 0000 000xbin Start of data transmission
xxxx xxxxbin 0000 000xbin 0000 0011bin 0000 001xbin The terminal requests transfer of 3 bytes
from the controller
xxxx xxxxbin 0000 001xbin 0000 0011bin 0000 001xbin Acknowledgement: Controller has received
3 bytes from the reception FIFO
xxxx xxxxbin 0000 001xbin 0001 0110bin 0000 000xbin The terminal requests transfer of 22 bytes
from the controller
xxxx xxxxbin 0000 000xbin 0001 0110bin 0000 000xbin Acknowledgement: Controller has received
22 bytes from the reception FIFO

EL600x, EL602x Version: 4.6 167


Overview CoE objects EL6002, EL6022

7 Overview CoE objects EL6002, EL6022

7.1 Object description and parameterization


EtherCAT XML Device Description
The display matches that of the CoE objects from the EtherCAT XML Device Description. We rec-
ommend downloading the latest XML file from the download area of the Beckhoff website and in-
stalling it according to installation instructions.

Parameterization
The terminal is parameterized via the CoE - Online tab [} 108] (with a double-click on the respective
object, see below).

Introduction

The CoE overview contains objects for different intended applications:


• Objects required for parameterization [} 168] during commissioning
• Objects for indicating internal settings [} 169] (may be fixed)
• Profile specific objects [} 181], which represent the status displays of the inputs and outputs.

The following section first describes the objects required for normal operation, followed by a complete
overview of missing objects.

7.1.1 Objects for commissioning

Index 0x1011 Restore default parameters


Index Name Meaning Data type Flags Default
(hex)
1011:0 Restore default parame- Restore default parameters UINT8 RO 0x01 (1dec)
ters [} 198]
1011:01 SubIndex 0x001 If this object is set to "0x64616F6C" in the set value di- UINT32 RW 0x00000000
alog, all backup objects are reset to their delivery state. (0dec)

168 Version: 4.6 EL600x, EL602x


Overview CoE objects EL6002, EL6022

Index 0x80n0 COM Settings Ch. 1 (n = 0), Ch. 2 (n = 1)


Index Name Meaning Data type Flags Default
(hex)
80n0:0 COM Settings Ch. 1 + Max. SubIndex (hex) UINT8 RO 0x1A (26dec)
Ch. 2
80n0:01** Enable RTS/CTS FALSE RTS/CTS not enabled BOOLEAN RW 0x01 (1dec)
TRUE RTS/CTS enabled
80n0:02 Enable XON/XOFF sup- FALSE XON/XOFF is not supported for send data BOOLEAN RW 0x00 (0dec)
ported tx data TRUE XON/XOFF is supported for send data
80n0:03 Enable XON/XOFF sup- FALSE XON/XOFF is not supported for receive data BOOLEAN RW 0x00 (0dec)
ported rx data TRUE XON/XOFF is supported for receive data
80n0:04 Enable send FIFO data FALSE No continuous sending of data from the FIFO BOOLEAN RW 0x00 (0dec)
continuous TRUE Continuous sending of data from the FIFO en-
abled:
The send buffer is filled (up to 128 bytes) by
the controller.
The filled buffer content is sent on rising edge
of bit “SendContinious”.
The terminal acknowledges the data transfer
to the controller through setting of bit “InitAc-
cepted”.
“InitAccepted” is reset with “SendContinuous”.
80n0:05 Enable transfer rate op- FALSE Transfer rate optimization switched off BOOLEAN RW 0x01 (1dec)
timization TRUE Transfer rate optimization switched on:
The content of the input buffer is automatically
transferred into the process image if
• no further byte was received for
approx. 16 bit times (i.e. the time it
would have taken to receive 2 bytes)
after data were received;
• the process image is filled
80n0:06** Enable half duplex FALSE Full-duplex mode BOOLEAN RW 0x00 (0dec)
* TRUE Half-duplex mode
80n0:07** Enable point to point FALSE Point-to-point connection disabled BOOLEAN RW 0x00 (0dec)
* connection (RS422) TRUE Point-to-point connection enabled
80n0:11 Baud rate Detailed information can be found in chapter Communi- BIT4 RW 0x06 (6dec)
cation features [} 131]
80n0:15 Data frame Detailed information can be found in chapter Communi- BIT4 RW 0x03 (3dec)
cation features [} 131]
80n0:1A Rx buffer full notification The value specifies the number of data in the receive UINT16 RW 0x0360 (864dec)
FIFO, from which the bit “buffer full” is set.
80n0:1B** Explicit baudrate More detailed information can be found in chapters UINT32 RW 0x00002580
** TcVirtualComDriver [} 129] and Communication fea- (9600dec)
tures [} 131]

**) only EL6002


***) only EL6022
****) only EL6002 from firmware 03 [} 186]

7.1.2 Standard objects (0x1000-0x1FFF)


The standard objects have the same meaning for all EtherCAT slaves.

Index 0x1000 Device type


Index Name Meaning Data type Flags Default
(hex)
1000:0 Device type Device type of the EtherCAT slave: the Lo-Word con- UINT32 RO 0x02581389
tains the CoE profile used (5001). The Hi-Word con- (39326601dec)
tains the module profile according to the modular de-
vice profile.

EL600x, EL602x Version: 4.6 169


Overview CoE objects EL6002, EL6022

Index 0x1008 Device name


Index Name Meaning Data type Flags Default
(hex)
1008:0 Device name Device name of the EtherCAT slave STRING RO EL60xx

Index 0x1009 Hardware version


Index Name Meaning Data type Flags Default
(hex)
1009:0 Hardware version Hardware version of the EtherCAT slave STRING RO 00

Index 0x100A Software version


Index Name Meaning Data type Flags Default
(hex)
100A:0 Software version Firmware version of the EtherCAT slave STRING RO 01

Index 0x1018 Identity


Index Name Meaning Data type Flags Default
(hex)
1018:0 Identity Information for identifying the slave UINT8 RO 0x04 (4dec)
1018:01 Vendor ID Vendor ID of the EtherCAT slave UINT32 RO 0x00000002
(2dec)
1018:02 Product code Product code of the EtherCAT slave UINT32 RO EL6002:
0x17723052
(393359442dec)
EL6022:
0x17863052
(394670162dec)
1018:03 Revision Revision number of the EtherCAT slave; the low word UINT32 RO 0x00100000
(bit 0-15) indicates the special terminal number, the (1048576dec)
high word (bit 16-31) refers to the device description
1018:04 Serial number Serial number of the EtherCAT slave; the low byte (bit UINT32 RO 0x00000000
0-7) of the low word contains the year of production, (0dec)
the high byte (bit 8-15) of the low word contains the
week of production, the high word (bit 16-31) is 0

Index 0x10F0 Backup parameter handling


Index Name Meaning Data type Flags Default
(hex)
10F0:0 Backup parameter han- Information for standardized loading and saving of UINT8 RO 0x01 (1dec)
dling backup entries
10F0:01 Checksum Checksum across all backup entries of the EtherCAT UINT32 RO 0x00000000
slave (0dec)

170 Version: 4.6 EL600x, EL602x


Overview CoE objects EL6002, EL6022

Index 0x1600 COM RxPDO-Map Outputs Ch.1


Index Name Meaning Data type Flags Default
(hex)
1600:0 COM RxPDO-Map Out- PDO Mapping RxPDO 1 UINT8 RO 0x1C (28dec)
puts Ch.1
1600:01 SubIndex 0x001 1. PDO Mapping entry (object 0x7000 (COM Outputs BOOLEAN RO 0x7000:01, 1
Ch.1), entry 0x01 (Transmit request))
1600:02 SubIndex 0x002 2. PDO Mapping entry (object 0x7000 (COM Outputs BOOLEAN RO 0x7000:02, 1
Ch.1), entry 0x02 (Receive accepted))
1600:03 SubIndex 0x003 3. PDO Mapping entry (object 0x7000 (COM Outputs BOOLEAN RO 0x7000:03, 1
Ch.1), entry 0x03 (Init request))
1600:04 SubIndex 0x004 4. PDO Mapping entry (object 0x7000 (COM Outputs BOOLEAN RO 0x7000:04, 1
Ch.1), entry 0x04 (Send continuous))
1600:05 SubIndex 0x005 5. PDO Mapping entry (4 bits align) Align4 RO 0x0000:00, 4
1600:06 SubIndex 0x006 6. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:09, 8
Ch.1), entry 0x09 (Output length))
1600:07 SubIndex 0x007 7. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:11, 8
Ch.1), entry 0x11 (Data Out 0))
1600:08 SubIndex 0x008 8. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:12, 8
Ch.1), entry 0x12 (Data Out 1))
1600:09 SubIndex 0x009 9. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:13, 8
Ch.1), entry 0x13 (Data Out 2))
1600:0A SubIndex 0x010 10. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:14, 8
Ch.1), entry 0x14 (Data Out 3))
1600:0B SubIndex 0x011 11. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:15, 8
Ch.1), entry 0x15 (Data Out 4))
1600:0C SubIndex 0x012 12. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:16, 8
Ch.1), entry 0x16 (Data Out 5))
1600:0D SubIndex 0x013 13. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:17, 8
Ch.1), entry 0x17 (Data Out 6))
1600:0E SubIndex 0x014 14. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:18, 8
Ch.1), entry 0x18 (Data Out 7))
1600:0F SubIndex 0x015 15. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:19, 8
Ch.1), entry 0x19 (Data Out 8))
1600:10 SubIndex 0x016 16. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:1A, 8
Ch.1), entry 0x1A (Data Out 9))
1600:11 SubIndex 0x017 17. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:1B, 8
Ch.1), entry 0x1B (Data Out 10))
1600:12 SubIndex 0x018 18. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:1C, 8
Ch.1), entry 0x1C (Data Out 11))
1600:13 SubIndex 0x019 19. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:1D, 8
Ch.1), entry 0x1D (Data Out 12))
1600:14 SubIndex 0x020 20. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:1E, 8
Ch.1), entry 0x1E (Data Out 13))
1600:15 SubIndex 0x021 21. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:1F, 8
Ch.1), entry 0x1F (Data Out 14))
1600:16 SubIndex 0x022 22. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:20, 8
Ch.1), entry 0x20 (Data Out 15))
1600:17 SubIndex 0x023 23. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:21, 8
Ch.1), entry 0x21 (Data Out 16))
1600:18 SubIndex 0x024 24. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:22, 8
Ch.1), entry 0x22 (Data Out 17))
1600:19 SubIndex 0x025 25. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:23, 8
Ch.1), entry 0x23 (Data Out 18))
1600:1A SubIndex 0x026 26. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:24, 8
Ch.1), entry 0x24 (Data Out 19))
1600:1B SubIndex 0x027 27. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:25, 8
Ch.1), entry 0x25 (Data Out 20))
1600:1C SubIndex 0x028 28. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:26, 8
Ch.1), entry 0x26 (Data Out 21))

EL600x, EL602x Version: 4.6 171


Overview CoE objects EL6002, EL6022

Index 0x1601 COM RxPDO-Map Outputs Ch.2


Index Name Meaning Data type Flags Default
(hex)
1601:0 COM RxPDO-Map Out- PDO Mapping RxPDO 2 UINT8 RO 0x1C (28dec)
puts Ch.2
1601:01 SubIndex 0x001 1. PDO Mapping entry (object 0x7010 (COM Outputs BOOLEAN RO 0x7010:01, 1
Ch.2), entry 0x01 (Transmit request))
1601:02 SubIndex 0x002 2. PDO Mapping entry (object 0x7010 (COM Outputs BOOLEAN RO 0x7010:02, 1
Ch.2), entry 0x02 (Receive accepted))
1601:03 SubIndex 0x003 3. PDO Mapping entry (object 0x7010 (COM Outputs BOOLEAN RO 0x7010:03, 1
Ch.2), entry 0x03 (Init request))
1601:04 SubIndex 0x004 4. PDO Mapping entry (object 0x7010 (COM Outputs BOOLEAN RO 0x7010:04, 1
Ch.2), entry 0x04 (Send continuous))
1601:05 SubIndex 0x005 5. PDO Mapping entry (4 bits align) Align4 RO 0x0000:00, 4
1601:06 SubIndex 0x006 6. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:09, 8
Ch.2), entry 0x09 (Output length))
1601:07 SubIndex 0x007 7. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:11, 8
Ch.2), entry 0x11 (Data Out 0))
1601:08 SubIndex 0x008 8. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:12, 8
Ch.2), entry 0x12 (Data Out 1))
1601:09 SubIndex 0x009 9. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:13, 8
Ch.2), entry 0x13 (Data Out 2))
1601:0A SubIndex 0x010 10. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:14, 8
Ch.2), entry 0x14 (Data Out 3))
1601:0B SubIndex 0x011 11. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:15, 8
Ch.2), entry 0x15 (Data Out 4))
1601:0C SubIndex 0x012 12. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:16, 8
Ch.2), entry 0x16 (Data Out 5))
1601:0D SubIndex 0x013 13. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:17, 8
Ch.2), entry 0x17 (Data Out 6))
1601:0E SubIndex 0x014 14. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:18, 8
Ch.2), entry 0x18 (Data Out 7))
1601:0F SubIndex 0x015 15. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:19, 8
Ch.2), entry 0x19 (Data Out 8))
1601:10 SubIndex 0x016 16. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:1A, 8
Ch.2), entry 0x1A (Data Out 9))
1601:11 SubIndex 0x017 17. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:1B, 8
Ch.2), entry 0x1B (Data Out 10))
1601:12 SubIndex 0x018 18. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:1C, 8
Ch.2), entry 0x1C (Data Out 11))
1601:13 SubIndex 0x019 19. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:1D, 8
Ch.2), entry 0x1D (Data Out 12))
1601:14 SubIndex 0x020 20. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:1E, 8
Ch.2), entry 0x1E (Data Out 13))
1601:15 SubIndex 0x021 21. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:1F, 8
Ch.2), entry 0x1F (Data Out 14))
1601:16 SubIndex 0x022 22. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:20, 8
Ch.2), entry 0x20 (Data Out 15))
1601:17 SubIndex 0x023 23. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:21, 8
Ch.2), entry 0x21 (Data Out 16))
1601:18 SubIndex 0x024 24. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:22, 8
Ch.2), entry 0x22 (Data Out 17))
1601:19 SubIndex 0x025 25. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:23, 8
Ch.2), entry 0x23 (Data Out 18))
1601:1A SubIndex 0x026 26. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:24, 8
Ch.2), entry 0x24 (Data Out 19))
1601:1B SubIndex 0x027 27. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:25, 8
Ch.2), entry 0x25 (Data Out 20))
1601:1C SubIndex 0x028 28. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:26, 8
Ch.2), entry 0x26 (Data Out 21))

172 Version: 4.6 EL600x, EL602x


Overview CoE objects EL6002, EL6022

Index 0x1604 COM RxPDO-Map Outputs Ch.1


Index Name Meaning Data type Flags Default
(hex)
1604:0 COM RxPDO-Map Out- PDO Mapping RxPDO 1 UINT8 RO 0x17 (23dec)
puts Ch.1
1604:01 SubIndex 0x001 1. PDO Mapping entry (object 0x7001 (Ctrl Ch.1), en- UINT16 RO 0x7001:01, 16
try 0x01 (Ctrl))
1604:02 SubIndex 0x002 2. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:11, 8
Ch.1), entry 0x11 (Data Out 0))
1604:03 SubIndex 0x003 3. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:12, 8
Ch.1), entry 0x12 (Data Out 1))
1604:04 SubIndex 0x004 4. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:13, 8
Ch.1), entry 0x13 (Data Out 2))
1604:05 SubIndex 0x005 5. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:14, 8
Ch.1), entry 0x14 (Data Out 3))
1604:06 SubIndex 0x006 6. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:15, 8
Ch.1), entry 0x15 (Data Out 4))
1604:07 SubIndex 0x007 7. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:16, 8
Ch.1), entry 0x16 (Data Out 5))
1604:08 SubIndex 0x008 8. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:17, 8
Ch.1), entry 0x17 (Data Out 6))
1604:09 SubIndex 0x009 9. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:18, 8
Ch.1), entry 0x18 (Data Out 7))
1604:0A SubIndex 0x010 10. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:19, 8
Ch.1), entry 0x19 (Data Out 8))
1604:0B SubIndex 0x011 11. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:1A, 8
Ch.1), entry 0x1A (Data Out 9))
1604:0C SubIndex 0x012 12. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:1B, 8
Ch.1), entry 0x1B (Data Out 10))
1604:0D SubIndex 0x013 13. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:1C, 8
Ch.1), entry 0x1C (Data Out 11))
1604:0E SubIndex 0x014 14. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:1D, 8
Ch.1), entry 0x1D (Data Out 12))
1604:0F SubIndex 0x015 15. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:1E, 8
Ch.1), entry 0x1E (Data Out 13))
1604:10 SubIndex 0x016 16. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:1F, 8
Ch.1), entry 0x1F (Data Out 14))
1604:11 SubIndex 0x017 17. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:20, 8
Ch.1), entry 0x20 (Data Out 15))
1604:12 SubIndex 0x018 18. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:21, 8
Ch.1), entry 0x21 (Data Out 16))
1604:13 SubIndex 0x019 19. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:22, 8
Ch.1), entry 0x22 (Data Out 17))
1604:14 SubIndex 0x020 20. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:23, 8
Ch.1), entry 0x23 (Data Out 18))
1604:15 SubIndex 0x021 21. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:24, 8
Ch.1), entry 0x24 (Data Out 19))
1604:16 SubIndex 0x022 22. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:25, 8
Ch.1), entry 0x25 (Data Out 20))
1604:17 SubIndex 0x023 23. PDO Mapping entry (object 0x7000 (COM Outputs UINT8 RO 0x7000:26, 8
Ch.1), entry 0x26 (Data Out 21))

EL600x, EL602x Version: 4.6 173


Overview CoE objects EL6002, EL6022

Index 0x1605 COM RxPDO-Map Outputs Ch.2


Index Name Meaning Data type Flags Default
(hex)
1605:0 COM RxPDO-Map Out- PDO Mapping RxPDO 1 UINT8 RO 0x17 (23dec)
puts Ch.1
1605:01 SubIndex 0x001 1. PDO Mapping entry (object 0x7011 (Ctrl Ch.2), en- UINT16 RO 0x7011:01, 16
try 0x01 (Ctrl))
1605:02 SubIndex 0x002 2. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:11, 8
Ch.2), entry 0x11 (Data Out 0))
1605:03 SubIndex 0x003 3. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:12, 8
Ch.2), entry 0x12 (Data Out 1))
1605:04 SubIndex 0x004 4. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:13, 8
Ch.2), entry 0x13 (Data Out 2))
1605:05 SubIndex 0x005 5. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:14, 8
Ch.2), entry 0x14 (Data Out 3))
1605:06 SubIndex 0x006 6. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:15, 8
Ch.2), entry 0x15 (Data Out 4))
1605:07 SubIndex 0x007 7. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:16, 8
Ch.2), entry 0x16 (Data Out 5))
1605:08 SubIndex 0x008 8. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:17, 8
Ch.2), entry 0x17 (Data Out 6))
1605:09 SubIndex 0x009 9. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:18, 8
Ch.2), entry 0x18 (Data Out 7))
1605:0A SubIndex 0x010 10. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:19, 8
Ch.2), entry 0x19 (Data Out 8))
1605:0B SubIndex 0x011 11. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:1A, 8
Ch.2), entry 0x1A (Data Out 9))
1605:0C SubIndex 0x012 12. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:1B, 8
Ch.2), entry 0x1B (Data Out 10))
1605:0D SubIndex 0x013 13. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:1C, 8
Ch.2), entry 0x1C (Data Out 11))
1605:0E SubIndex 0x014 14. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:1D, 8
Ch.2), entry 0x1D (Data Out 12))
1605:0F SubIndex 0x015 15. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:1E, 8
Ch.2), entry 0x1E (Data Out 13))
1605:10 SubIndex 0x016 16. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:1F, 8
Ch.2), entry 0x1F (Data Out 14))
1605:11 SubIndex 0x017 17. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:20, 8
Ch.2), entry 0x20 (Data Out 15))
1605:12 SubIndex 0x018 18. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:21, 8
Ch.2), entry 0x21 (Data Out 16))
1605:13 SubIndex 0x019 19. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:22, 8
Ch.2), entry 0x22 (Data Out 17))
1605:14 SubIndex 0x020 20. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:23, 8
Ch.2), entry 0x23 (Data Out 18))
1605:15 SubIndex 0x021 21. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:24, 8
Ch.2), entry 0x24 (Data Out 19))
1605:16 SubIndex 0x022 22. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:25, 8
Ch.2), entry 0x25 (Data Out 20))
1605:17 SubIndex 0x023 23. PDO Mapping entry (object 0x7010 (COM Outputs UINT8 RO 0x7010:26, 8
Ch.2), entry 0x26 (Data Out 21))

174 Version: 4.6 EL600x, EL602x


Overview CoE objects EL6002, EL6022

Index 0x1A00 COM TxPDO-Map Inputs Ch.1


Index Name Meaning Data type Flags Default
(hex)
1A00:0 COM TxPDO-Map In- PDO Mapping TxPDO 1 UINT8 RO 0x1F (31dec)
puts Ch.1
1A00:01 SubIndex 0x001 1. PDO Mapping entry (object 0x6000 (COM Inputs BOOLEAN RO 0x6000:01, 1
Ch.1), entry 0x01 (Transmit accepted))
1A00:02 SubIndex 0x002 2. PDO Mapping entry (object 0x6000 (COM Inputs BOOLEAN RO 0x6000:02, 1
Ch.1), entry 0x02 (Receive request))
1A00:03 SubIndex 0x003 3. PDO Mapping entry (object 0x6000 (COM Inputs BOOLEAN RO 0x6000:03, 1
Ch.1), entry 0x03 (Init accepted))
1A00:04 SubIndex 0x004 4. PDO Mapping entry (object 0x6000 (COM Inputs BOOLEAN RO 0x6000:04, 1
Ch.1), entry 0x04 (Buffer full))
1A00:05 SubIndex 0x005 5. PDO Mapping entry (object 0x6000 (COM Inputs BOOLEAN RO 0x6000:05, 1
Ch.1), entry 0x05 (Parity error))
1A00:06 SubIndex 0x006 6. PDO Mapping entry (object 0x6000 (COM Inputs BOOLEAN RO 0x6000:06, 1
Ch.1), entry 0x06 (Framing error))
1A00:07 SubIndex 0x007 7. PDO Mapping entry (object 0x6000 (COM Inputs BOOLEAN RO 0x6000:07, 1
Ch.1), entry 0x07 (Overrun error))
1A00:08 SubIndex 0x008 8. PDO Mapping entry (1 bits align) Align1 RO 0x0000:00, 1
1A00:09 SubIndex 0x009 9. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:09, 8
Ch.1), entry 0x09 (Input length))
1A00:0A SubIndex 0x010 10. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:11, 8
Ch.1), entry 0x11 (Data In 0))
1A00:0B SubIndex 0x011 11. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:12, 8
Ch.1), entry 0x12 (Data In 1))
1A00:0C SubIndex 0x012 12. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:13, 8
Ch.1), entry 0x13 (Data In 2))
1A00:0D SubIndex 0x013 13. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:14, 8
Ch.1), entry 0x14 (Data In 3))
1A00:0E SubIndex 0x014 14. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:15, 8
Ch.1), entry 0x15 (Data In 4))
1A00:0F SubIndex 0x015 15. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:16, 8
Ch.1), entry 0x16 (Data In 5))
1A00:10 SubIndex 0x016 16. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:17, 8
Ch.1), entry 0x17 (Data In 6))
1A00:11 SubIndex 0x017 17. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:18, 8
Ch.1), entry 0x18 (Data In 7))
1A00:12 SubIndex 0x018 18. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:19, 8
Ch.1), entry 0x19 (Data In 8))
1A00:13 SubIndex 0x019 19. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:1A, 8
Ch.1), entry 0x1A (Data In 9))
1A00:14 SubIndex 0x020 20. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:1B, 8
Ch.1), entry 0x1B (Data In 10))
1A00:15 SubIndex 0x021 21. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:1C, 8
Ch.1), entry 0x1C (Data In 11))
1A00:16 SubIndex 0x022 22. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:1D, 8
Ch.1), entry 0x1D (Data In 12))
1A00:17 SubIndex 0x023 23. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:1E, 8
Ch.1), entry 0x1E (Data In 13))
1A00:18 SubIndex 0x024 24. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:1F, 8
Ch.1), entry 0x1F (Data In 14))
1A00:19 SubIndex 0x025 25. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:20, 8
Ch.1), entry 0x20 (Data In 15))
1A00:1A SubIndex 0x026 26. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:21, 8
Ch.1), entry 0x21 (Data In 16))
1A00:1B SubIndex 0x027 27. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:22, 8
Ch.1), entry 0x22 (Data In 17))
1A00:1C SubIndex 0x028 28. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:23, 8
Ch.1), entry 0x23 (Data In 18))
1A00:1D SubIndex 0x029 29. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:24, 8
Ch.1), entry 0x24 (Data In 19))
1A00:1E SubIndex 0x030 30. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:25, 8
Ch.1), entry 0x25 (Data In 20))
1A00:1F SubIndex 0x031 31. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:26, 8
Ch.1), entry 0x26 (Data In 21))

EL600x, EL602x Version: 4.6 175


Overview CoE objects EL6002, EL6022

Index 0x1A01 COM TxPDO-Map Inputs Ch.2


Index Name Meaning Data type Flags Default
(hex)
1A01:0 COM TxPDO-Map In- PDO Mapping TxPDO 2 UINT8 RO 0x1F (31dec)
puts Ch.2
1A01:01 SubIndex 0x001 1. PDO Mapping entry (object 0x6010 (COM Inputs BOOLEAN RO 0x6010:01, 1
Ch.2), entry 0x01 (Transmit accepted))
1A01:02 SubIndex 0x002 2. PDO Mapping entry (object 0x6010 (COM Inputs BOOLEAN RO 0x6010:02, 1
Ch.2), entry 0x02 (Receive request))
1A01:03 SubIndex 0x003 3. PDO Mapping entry (object 0x6010 (COM Inputs BOOLEAN RO 0x6010:03, 1
Ch.2), entry 0x03 (Init accepted))
1A01:04 SubIndex 0x004 4. PDO Mapping entry (object 0x6010 (COM Inputs BOOLEAN RO 0x6010:04, 1
Ch.2), entry 0x04 (Buffer full))
1A01:05 SubIndex 0x005 5. PDO Mapping entry (object 0x6010 (COM Inputs BOOLEAN RO 0x6010:05, 1
Ch.2), entry 0x05 (Parity error))
1A01:06 SubIndex 0x006 6. PDO Mapping entry (object 0x6010 (COM Inputs BOOLEAN RO 0x6010:06, 1
Ch.2), entry 0x06 (Framing error))
1A01:07 SubIndex 0x007 7. PDO Mapping entry (object 0x6010 (COM Inputs BOOLEAN RO 0x6010:07, 1
Ch.2), entry 0x07 (Overrun error))
1A01:08 SubIndex 0x008 8. PDO Mapping entry (1 bits align) Align1 RO 0x0000:00, 1
1A01:09 SubIndex 0x009 9. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:09, 8
Ch.2), entry 0x09 (Input length))
1A01:0A SubIndex 0x010 10. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:11, 8
Ch.2), entry 0x11 (Data In 0))
1A01:0B SubIndex 0x011 11. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:12, 8
Ch.2), entry 0x12 (Data In 1))
1A01:0C SubIndex 0x012 12. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:13, 8
Ch.2), entry 0x13 (Data In 2))
1A01:0D SubIndex 0x013 13. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:14, 8
Ch.2), entry 0x14 (Data In 3))
1A01:0E SubIndex 0x014 14. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:15, 8
Ch.2), entry 0x15 (Data In 4))
1A01:0F SubIndex 0x015 15. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:16, 8
Ch.2), entry 0x16 (Data In 5))
1A01:10 SubIndex 0x016 16. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:17, 8
Ch.2), entry 0x17 (Data In 6))
1A01:11 SubIndex 0x017 17. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:18, 8
Ch.2), entry 0x18 (Data In 7))
1A01:12 SubIndex 0x018 18. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:19, 8
Ch.2), entry 0x19 (Data In 8))
1A01:13 SubIndex 0x019 19. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:1A, 8
Ch.2), entry 0x1A (Data In 9))
1A01:14 SubIndex 0x020 20. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:1B, 8
Ch.2), entry 0x1B (Data In 10))
1A01:15 SubIndex 0x021 21. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:1C, 8
Ch.2), entry 0x1C (Data In 11))
1A01:16 SubIndex 0x022 22. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:1D, 8
Ch.2), entry 0x1D (Data In 12))
1A01:17 SubIndex 0x023 23. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:1E, 8
Ch.2), entry 0x1E (Data In 13))
1A01:18 SubIndex 0x024 24. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:1F, 8
Ch.2), entry 0x1F (Data In 14))
1A01:19 SubIndex 0x025 25. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:20, 8
Ch.2), entry 0x20 (Data In 15))
1A01:1A SubIndex 0x026 26. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:21, 8
Ch.2), entry 0x21 (Data In 16))
1A01:1B SubIndex 0x027 27. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:22, 8
Ch.2), entry 0x22 (Data In 17))
1A01:1C SubIndex 0x028 28. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:23, 8
Ch.2), entry 0x23 (Data In 18))
1A01:1D SubIndex 0x029 29. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:24, 8
Ch.2), entry 0x24 (Data In 19))
1A01:1E SubIndex 0x030 30. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:25, 8
Ch.2), entry 0x25 (Data In 20))
1A01:1F SubIndex 0x031 31. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:26, 8
Ch.2), entry 0x26 (Data In 21))

176 Version: 4.6 EL600x, EL602x


Overview CoE objects EL6002, EL6022

Index 0x1A04 COM TxPDO-Map Inputs Ch.1


Index Name Meaning Data type Flags Default
(hex)
1A04:0 COM TxPDO-Map In- PDO Mapping TxPDO 1 UINT8 RO 0x17 (23dec)
puts Ch.1
1A04:01 SubIndex 0x001 1. PDO Mapping entry (object 0x6001 (Status Ch.1), UINT16 RO 0x6001:01, 16
entry 0x01 (Status))
1A04:02 SubIndex 0x002 2. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:11, 8
Ch.1), entry 0x11 (Data In 0))
1A04:03 SubIndex 0x003 3. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:12, 8
Ch.1), entry 0x12 (Data In 1))
1A04:04 SubIndex 0x004 4. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:13, 8
Ch.1), entry 0x13 (Data In 2))
1A04:05 SubIndex 0x005 5. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:14, 8
Ch.1), entry 0x14 (Data In 3))
1A04:06 SubIndex 0x006 6. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:15, 8
Ch.1), entry 0x15 (Data In 4))
1A04:07 SubIndex 0x007 7. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:16, 8
Ch.1), entry 0x16 (Data In 5))
1A04:08 SubIndex 0x008 8. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:17, 8
Ch.1), entry 0x17 (Data In 6))
1A04:09 SubIndex 0x009 9. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:18, 8
Ch.1), entry 0x18 (Data In 7))
1A04:0A SubIndex 0x010 10. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:19, 8
Ch.1), entry 0x19 (Data In 8))
1A04:0B SubIndex 0x011 11. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:1A, 8
Ch.1), entry 0x1A (Data In 9))
1A04:0C SubIndex 0x012 12. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:1B, 8
Ch.1), entry 0x1B (Data In 10))
1A04:0D SubIndex 0x013 13. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:1C, 8
Ch.1), entry 0x1C (Data In 11))
1A04:0E SubIndex 0x014 14. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:1D, 8
Ch.1), entry 0x1D (Data In 12))
1A04:0F SubIndex 0x015 15. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:1E, 8
Ch.1), entry 0x1E (Data In 13))
1A04:10 SubIndex 0x016 16. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:1F, 8
Ch.1), entry 0x1F (Data In 14))
1A04:11 SubIndex 0x017 17. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:20, 8
Ch.1), entry 0x20 (Data In 15))
1A04:12 SubIndex 0x018 17. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:21, 8
Ch.1), entry 0x21 (Data In 16))
1A04:13 SubIndex 0x019 19. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:22, 8
Ch.1), entry 0x22 (Data In 17))
1A04:14 SubIndex 0x020 20. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:23, 8
Ch.1), entry 0x23 (Data In 18))
1A04:15 SubIndex 0x021 21. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:24, 8
Ch.1), entry 0x24 (Data In 19))
1A04:16 SubIndex 0x022 22. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:25, 8
Ch.1), entry 0x25 (Data In 20))
1A04:17 SubIndex 0x023 23. PDO Mapping entry (object 0x6000 (COM Inputs UINT8 RO 0x6000:26, 8
Ch.1), entry 0x26 (Data In 21))

EL600x, EL602x Version: 4.6 177


Overview CoE objects EL6002, EL6022

Index 0x1A05 COM TxPDO-Map Inputs Ch.2


Index Name Meaning Data type Flags Default
(hex)
1A05:0 COM TxPDO-Map In- PDO Mapping TxPDO 1 UINT8 RO 0x17 (23dec)
puts Ch.2
1A05:01 SubIndex 0x001 1. PDO Mapping entry (object 0x6011 (Status Ch.2), UINT16 RO 0x6011:01, 16
entry 0x01 (Status))
1A05:02 SubIndex 0x002 2. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:11, 8
Ch.2), entry 0x11 (Data In 0))
1A05:03 SubIndex 0x003 3. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:12, 8
Ch.2), entry 0x12 (Data In 1))
1A05:04 SubIndex 0x004 4. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:13, 8
Ch.2), entry 0x13 (Data In 2))
1A05:05 SubIndex 0x005 5. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:14, 8
Ch.2), entry 0x14 (Data In 3))
1A05:06 SubIndex 0x006 6. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:15, 8
Ch.2), entry 0x15 (Data In 4))
1A05:07 SubIndex 0x007 7. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:16, 8
Ch.2), entry 0x16 (Data In 5))
1A05:08 SubIndex 0x008 8. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:17, 8
Ch.2), entry 0x17 (Data In 6))
1A05:09 SubIndex 0x009 9. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:18, 8
Ch.2), entry 0x18 (Data In 7))
1A05:0A SubIndex 0x010 10. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:19, 8
Ch.2), entry 0x19 (Data In 8))
1A05:0B SubIndex 0x011 11. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:1A, 8
Ch.2), entry 0x1A (Data In 9))
1A05:0C SubIndex 0x012 12. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:1B, 8
Ch.2), entry 0x1B (Data In 10))
1A05:0D SubIndex 0x013 13. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:1C, 8
Ch.2), entry 0x1C (Data In 11))
1A05:0E SubIndex 0x014 14. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:1D, 8
Ch.2), entry 0x1D (Data In 12))
1A05:0F SubIndex 0x015 15. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:1E, 8
Ch.2), entry 0x1E (Data In 13))
1A05:10 SubIndex 0x016 16. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:1F, 8
Ch.2), entry 0x1F (Data In 14))
1A05:11 SubIndex 0x017 17. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:20, 8
Ch.2), entry 0x20 (Data In 15))
1A05:12 SubIndex 0x018 17. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:21, 8
Ch.2), entry 0x21 (Data In 16))
1A05:13 SubIndex 0x019 19. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:22, 8
Ch.2), entry 0x22 (Data In 17))
1A05:14 SubIndex 0x020 20. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:23, 8
Ch.2), entry 0x23 (Data In 18))
1A05:15 SubIndex 0x021 21. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:24, 8
Ch.2), entry 0x24 (Data In 19))
1A05:16 SubIndex 0x022 22. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:25, 8
Ch.2), entry 0x25 (Data In 20))
1A05:17 SubIndex 0x023 23. PDO Mapping entry (object 0x6010 (COM Inputs UINT8 RO 0x6010:26, 8
Ch.2), entry 0x26 (Data In 21))

Index 0x1C00 Sync manager type


Index Name Meaning Data type Flags Default
(hex)
1C00:0 Sync manager type Using the sync managers UINT8 RO 0x04 (4dec)
1C00:01 SubIndex 0x001 Sync-Manager Type Channel 1: Mailbox Write UINT8 RO 0x01 (1dec)
1C00:02 SubIndex 0x002 Sync-Manager Type Channel 2: Mailbox Read UINT8 RO 0x02 (2dec)
1C00:03 SubIndex 0x003 Sync-Manager Type Channel 3: Process Data Write UINT8 RO 0x03 (3dec)
(Outputs)
1C00:04 SubIndex 0x004 Sync-Manager Type Channel 4: Process Data Read UINT8 RO 0x04 (4dec)
(Inputs)

178 Version: 4.6 EL600x, EL602x


Overview CoE objects EL6002, EL6022

Index 0x1C12 RxPDO assign


Index Name Meaning Data type Flags Default
(hex)
1C12:0 RxPDO assign PDO Assign Outputs UINT8 RO 0x04 (4dec)
1C12:01 SubIndex 0x001 1st allocated RxPDO (contains the index 0x of the as- UINT16 RO 0x1600 (5632dec)
sociated RxPDO mapping object)
1C12:02 SubIndex 0x002 2nd allocated RxPDO (contains the index 0x of the as- UINT16 RO 0x1601 (5633dec)
sociated RxPDO mapping object)

Index 0x1C13 TxPDO assign


Index Name Meaning Data type Flags Default
(hex)
1C13:0 TxPDO assign PDO Assign Inputs UINT8 RO 0x04 (4dec)
1C13:01 SubIndex 0x001 1st allocated TxPDO (contains the index 0x of the as- UINT16 RO 0x1A00 (6656dec)
sociated TxPDO mapping object)
1C13:02 SubIndex 0x002 2nd allocated TxPDO (contains the index 0x of the as- UINT16 RO 0x1A01 (6657dec)
sociated TxPDO mapping object)

EL600x, EL602x Version: 4.6 179


Overview CoE objects EL6002, EL6022

Index 0x1C32 SM output parameter


Index Name Meaning Data type Flags Default
(hex)
1C32:0 SM output parameter Synchronization parameters for the outputs UINT8 RO 0x20 (32dec)
1C32:01 Sync mode Current synchronization mode: UINT16 RW 0x0000 (0dec)
• 0: Free Run
• 1: Synchron with SM 2 Event
• 2: DC-Mode - Synchron with SYNC0 Event
• 3: DC-Mode - Synchron with SYNC1 Event
1C32:02 Cycle time Cycle time (in ns): UINT32 RW 0x0003D090
(250000dec)
• Free Run: Cycle time of the local timer
• Synchronous with SM 2 event: Master cycle
time
• DC-Mode: SYNC0/SYNC1 Cycle Time
1C32:03 Shift time Time between SYNC0 event and output of the outputs UINT32 RO 0x00000000 (0dec)
(in ns, DC mode only)
1C32:04 Sync modes supported Supported synchronization modes: UINT16 RO 0xC007 (49159dec)
• Bit 0 = 1: free run is supported
• Bit 1 = 1: Synchronous with SM 2 event is
supported
• Bit 2-3 = 01: DC mode is supported
• Bit 4-5 = 10: Output shift with SYNC1 event
(only DC mode)
• Bit 14 = 1: dynamic times (measurement
through writing of 1C32:08)
1C32:05 Minimum cycle time Minimum cycle time (in ns) UINT32 RO 0x00004E20
(20000dec)
1C32:06 Calc and copy time Minimum time between SYNC0 and SYNC1 event (in UINT32 RO 0x00000000 (0dec)
ns, DC mode only)
1C32:08 Command • 0: Measurement of the local cycle time is UINT16 RW 0x0000 (0dec)
stopped
• 1: Measurement of the local cycle time is
started
The entries 1C32:03, 1C32:05, 1C32:06, 1C32:09,
1C33:03, 1C33:06, and 1C33:09 are updated with the
maximum measured values.
For a subsequent measurement the measured values
are reset
1C32:09 Delay time Time between SYNC1 event and output of the outputs UINT32 RO 0x00000000 (0dec)
(in ns, DC mode only)
1C32:0B SM event missed counter Number of missed SM events in OPERATIONAL (DC UINT16 RO 0x0000 (0dec)
mode only)
1C32:0C Cycle exceeded counter Number of occasions the cycle time was exceeded in UINT16 RO 0x0000 (0dec)
OPERATIONAL (cycle was not completed in time or
the next cycle began too early)
1C32:0D Shift too short counter Number of occasions that the interval between UINT16 RO 0x0000 (0dec)
SYNC0 and SYNC1 event was too short (DC mode
only)
1C32:20 Sync error The synchronization was not correct in the last cycle BOOLEAN RO 0x00 (0dec)
(outputs were output too late; DC mode only)

180 Version: 4.6 EL600x, EL602x


Overview CoE objects EL6002, EL6022

Index 0x1C33 SM input parameter


Index Name Meaning Data type Flags Default
(hex)
1C33:0 SM input parameter Synchronization parameters for the inputs UINT8 RO 0x20 (32dec)
1C33:01 Sync mode Current synchronization mode: UINT16 RW 0x0000 (0dec)
• 0: Free Run
• 1: Synchronous with SM 3 event (no outputs
available)
• 2: DC - Synchronous with SYNC0 Event
• 3: DC - Synchronous with SYNC1 Event
• 34: Synchronous with SM 2 event (outputs
available)
1C33:02 Cycle time as 1C32:02 UINT32 RW 0x0003D090
(250000dec)
1C33:03 Shift time Time between SYNC0 event and reading of the in- UINT32 RO 0x00000000 (0dec)
puts (in ns, only DC mode)
1C33:04 Sync modes supported Supported synchronization modes: UINT16 RO 0xC007 (49159dec)
• Bit 0: free run is supported
• Bit 1: synchronous with SM 2 event is
supported (outputs available)
• Bit 1: synchronous with SM 3 event is
supported (no outputs available)
• Bit 2-3 = 01: DC mode is supported
• Bit 4-5 = 01: input shift through local event
(outputs available)
• Bit 4-5 = 10: input shift with SYNC1 event
(no outputs available)
• Bit 14 = 1: dynamic times (measurement
through writing of 1C32:08 or 1C33:08)
1C33:05 Minimum cycle time as 1C32:05 UINT32 RO 0x00004E20
(20000dec)
1C33:06 Calc and copy time Time between reading of the inputs and availability UINT32 RO 0x00000000 (0dec)
of the inputs for the master (in ns, only DC mode)
1C33:08 Command as 1C32:08 UINT16 RW 0x0000 (0dec)
1C33:09 Delay time Time between SYNC1 event and reading of the in- UINT32 RO 0x00000000 (0dec)
puts (in ns, only DC mode)
1C33:0B SM event missed counter as 1C32:11 UINT16 RO 0x0000 (0dec)
1C33:0C Cycle exceeded counter as 1C32:12 UINT16 RO 0x0000 (0dec)
1C33:0D Shift too short counter as 1C32:13 UINT16 RO 0x0000 (0dec)
1C33:20 Sync error as 1C32:32 BOOLEAN RO 0x00 (0dec)

7.1.3 Profile-specific objects (0x6000-0xFFFF) [from hardware


version 03]
The profile-specific objects have the same meaning for all EtherCAT slaves that support the profile 5001.

EL600x, EL602x Version: 4.6 181


Overview CoE objects EL6002, EL6022

Index 0x60n0 COM Inputs Ch. 1 (n = 0), Ch. 2 (n = 1)


Index Name Meaning Data type Flags Default
(hex)
60n0:0 COM Inputs Ch. 1 + Ch. 2 Max. SubIndex (hex) UINT8 RO 0x26 (38dec)
60n0:01 Transmit accepted The terminal acknowledges receipt of data by BOOLEAN RO 0x00 (0dec)
changing the state of this bit. Only now new
data can be transferred from the controller to the
terminal.
60n0:02 Receive request By changing the state of this bit, the terminal in- BOOLEAN RO 0x00 (0dec)
forms the controller that the DataIn bytes con-
tain the number of bytes displayed in “Input
length [} 182]”. The controller must acknowl-
edge receipt of the data by changing the state of
the ReceiveAccepted [} 183] bit. Only then new
data can be transferred from the terminal to the
controller.
60n0:03 Init accepted 0 The terminal is ready again for serial data BOOLEAN RO 0x00 (0dec)
exchange.
1 Initialization was completed by the terminal.
60n0:04 Buffer full The reception FIFO is full. All incoming data will BOOLEAN RO 0x00 (0dec)
be lost from this point on!
60n0:05 Parity error A parity error has occurred. BOOLEAN RO 0x00 (0dec)
60n0:06 Framing error A framing error has occurred. BOOLEAN RO 0x00 (0dec)
60n0:07 Overrun error An overrun error has occurred. BOOLEAN RO 0x00 (0dec)
60n0:09 Input length Number of input bytes available for transfer from UINT8 RO 0x00 (0dec)
the terminal to the controller.
60n0:11 Data In 0 Input byte 0 UINT8 RO 0x00 (0dec)
... ... .... ... ... ...
60n0:26 Data In 21 Input byte 21 UINT8 RO 0x00 (0dec)

Index 0x60n1 Status Ch. 1 (n = 0), Ch. 2 (n = 1)


Index Name Meaning Data type Flags Default
(hex)
60n1:0 Status Ch. 1 + Ch. 2 Max. SubIndex (hex) UINT8 RO 0x01 (01dec)
60n1:01 Status Status word UINT16 RO 0x00 (0dec)

182 Version: 4.6 EL600x, EL602x


Overview CoE objects EL6002, EL6022

Index 0x70n0 COM Outputs Ch. 1 (n = 0), Ch. 2 (n = 1)


Index Name Meaning Data type Flags Default
(hex)
70n0:0 COM Outputs Ch. 1 + Max. SubIndex (hex) UINT8 RO 0x26 (38dec)
Ch. 2
70n0:01 Transmit request By changing the state of this bit, the controller in- BOOLEAN RO 0x00 (0dec)
forms the terminal that the DataOut bytes contain
the number of bytes displayed in “Output length
[} 183]”. The terminal acknowledges receipt of the
data by changing the state of the “TransmitAccepted
[} 182]” bit. Only now new data can be transferred
from the controller to the terminal.
70n0:02 Receive accepted The controller acknowledges receipt of data by BOOLEAN RO 0x00 (0dec)
changing the state of this bit. Only then new data
can be transferred from the terminal to the con-
troller.
70n0:03 Init request 0 The controller once again requests the terminal BOOLEAN RO 0x00 (0dec)
to prepare for serial data exchange.
1 The controller requests terminal for initialization.
The transmit and receive functions will be
blocked, the FIFO pointer will be reset and the
interface will be initialized with the values of the
responsible Settings object. The execution of
the initialization will be acknowledged by the ter-
minal with the ‘Init accepted [} 182]’ bit.
70n0:04 Send continuous Continuous sending of data from the FIFO. BOOLEAN RO 0x00 (0dec)
The send buffer is filled (up to 128 bytes) by the
controller. The filled buffer contents will be sent on
the rising edge of the bit. If the data has been trans-
mitted, the terminal informs the controller by setting
the “Init accepted [} 182]” bit. “Init accepted [} 182]”
is cleared with “SendContinuous [} 183]”.
70n0:09 Output length Number of output bytes available for transfer from UINT8 RO 0x00 (0dec)
the controller to the terminal.
70n0:11 Data Out 0 Output byte 0 UINT8 RO 0x00 (0dec)
... ... .... ... ... ...
70n0:26 Data Out 21 Output byte 21 UINT8 RO 0x00 (0dec)

Index 0x70n1 Ctrl Ch. 1 (n = 0), Ch. 2 (n = 1)


Index Name Meaning Data type Flags Default
(hex)
70n1:0 Crtl Ch. 1 + Ch. 2 Max. SubIndex (hex) UINT8 RO 0x01 (01dec)
70n1:01 Status Control word UINT16 RO 0x00 (0dec)

Index 0xA0n0 COM Diag data Ch. 1 (n = 0), Ch. 2 (n = 1)


Index Name Meaning Data type Flags Default
(hex)
A0n0:0 COM Diag data Ch. 1 + Max. SubIndex (hex) UINT8 RO 0x12 (18dec)
Ch. 2
A0n0:01 Buffer overflow A buffer overflow has occurred. BOOLEAN RO 0x00 (0dec)
A0n0:02 Parity error A parity error has occurred. BOOLEAN RO 0x00 (0dec)
A0n0:03 Framing error A framing error has occurred BOOLEAN RO 0x00 (0dec)
A0n0:04 Overrun error An overrun error has occurred. BOOLEAN RO 0x00 (0dec)
A0n0:05 Buffer full The reception FIFO is full. All incoming data will be BOOLEAN RO 0x00 (0dec)
lost from this point on!
A0n0:11 Data bytes in send buf- Number of data bytes in the send FIFO UINT16 RO 0x0000 (0dec)
fer
A0n0:21 Data bytes in receive Number of data bytes in the receive FIFO UINT16 RO 0x0000 (0dec)
buffer

EL600x, EL602x Version: 4.6 183


Overview CoE objects EL6002, EL6022

Index 0xF000 Modular device profile


Index Name Meaning Data type Flags Default
(hex)
F000:0 Modular device profile General information for the modular device profile UINT8 RO 0x02 (2dec)
F000:01 Module Index 0xdistance Index (hex) interval of the objects of the individual UINT16 RO 0x0010 (16dec)
channels
F000:02 Maximum number of Number of channels UINT16 RO 0x0004 (4dec)
modules

Index 0xF008 Code word


Index Name Meaning Data type Flags Default
(hex)
F008:0 Code word reserved UINT32 RW 0x00000000
(0dec)

Index 0xF010 Module list


Index Name Meaning Data type Flags Default
(hex)
F010:0 Module list Max. SubIndex (hex) UINT8 RW 0x04 (4dec)
F010:01 SubIndex 0x001 - UINT32 RW 0x00000258
(600dec)
F010:02 SubIndex 0x002 - UINT32 RW 0x00000258
(600dec)

7.2 Control and status data


The control and status data are located in the first 16 bits of the input and output process image.
Communication between the terminal and the controller is controlled via this data.

Status data
Bit position Name Meaning Data type
0 Transmit The terminal acknowledges receipt of data by changing the BOOLEAN
accepted state of this bit. Only now new data can be transferred from the
controller to the terminal.
1 Receive request By changing the state of this bit, the terminal informs the BOOLEAN
controller that the DataIn bytes contain the number of bytes
displayed in “Input length”. The controller must acknowledge
receipt of the data by changing the state of the
ReceiveAccepted bit. Only then new data can be transferred
from the terminal to the controller.
2 Init accepted 0 The terminal is ready again for serial data exchange. BOOLEAN
1 Initialization was completed by the terminal.
3 Buffer full The reception FIFO is full. All incoming data will be lost from BOOLEAN
this point on!
4 Parity error A parity error has occurred. BOOLEAN
5 Framing error A framing error has occurred. BOOLEAN
6 Overrun error An overrun error has occurred. BOOLEAN
7 -
8...15 Input length Number of input bytes available for transfer from the terminal UINT8
to the controller.

184 Version: 4.6 EL600x, EL602x


Overview CoE objects EL6002, EL6022

Control data
Bit position Name Meaning Data type
0 Transmit request By changing the state of this bit, the controller informs the BOOLEAN
terminal that the DataOut bytes contain the number of bytes
displayed in “Output length”. The terminal acknowledges
receipt of the data by changing the state of the
“TransmitAccepted” bit. Only now new data can be transferred
from the controller to the terminal.
1 Receive accepted The controller acknowledges receipt of data by changing the BOOLEAN
state of this bit. Only then new data can be transferred from
the terminal to the controller.
2 Init request 0 The controller once again requests the terminal to prepare BOOLEAN
for serial data exchange.
1 The controller requests terminal for initialization. The
transmit and receive functions will be blocked, the FIFO
pointer will be reset and the interface will be initialized with
the values of the responsible Settings object. The execution
of the initialization will be acknowledged by the terminal
with the ‘Init accepted’ bit.
3 Send continuous Continuous sending of data from the FIFO. BOOLEAN
The send buffer is filled (up to 128 bytes) by the controller. The
filled buffer contents will be sent on the rising edge of the bit. If
the data has been transmitted, the terminal informs the
controller by setting the “Init accepted” bit. “Init accepted” is
cleared with “SendContinuous”.
4...7 -
8...15 Output length Number of output bytes available for transfer from the UINT8
controller to the terminal.

PDO Assignment

The terminal makes two input/output process images available for each channel. These differ only in the
representation of the control/status data.

In the case of bitwise representation, the data is made available as shown in the tables above. In the case of
word-wise representation, the first 16 bits of the process data are combined in one word.

The process data objects begin as standard with a control/status word. This PDO assignment is required in
order to use the ‘TwinCAT PLC Serial Communication’ library.

Status Inputs Control Outputs Representation


0x1A00 0x1600 bitwise Ch. 1
0x1A01 0x1601 bitwise Ch. 2
0x1A02 0x1602 bitwise Ch. 3
0x1A03 0x1603 bitwise Ch. 4
0x1A04 0x1604 word-wise Ch 1
0x1A05 0x1605 word-wise Ch 2
0x1A06 0x1606 word-wise Ch 3
0x1A07 0x1607 word-wise Ch 4

EL600x, EL602x Version: 4.6 185


Appendix

8 Appendix

8.1 EtherCAT AL Status Codes


For detailed information please refer to the EtherCAT system description.

8.2 Firmware compatibility


Note
• It is recommended to use the newest possible firmware for the respective hardware.
• Beckhoff is not under any obligation to provide customers with free firmware updates for delivered
products.

NOTE
Risk of damage to the device
Pay attention to the instructions for firmware updates on the separate page [} 187].
If a device is placed in BOOTSTRAP mode for a firmware update, it does not check when downloading
whether the new firmware is suitable.
This can result in damage to the device!
Therefore, always make sure that the firmware is suitable for the hardware version!

EL6001
Hardware (HW) Firmware (FW) Revision no. Release date
00 - 02 01 05/2006
02 12/2006
03 04/2008
04 04/2008
04 - 11* 05 EL6001-0000-0016 12/2009
06 04/2010
07 EL6001-0000-0017 03/2011
EL6001-0000-0018 10/2012
08 EL6001-0000-0019 05/2014
09 EL6001-0000-0020 08/2014
10 05/2015
11* 06/2017

EL6002
Hardware (HW) Firmware (FW) Revision no. Release date
00 - 14* 01 EL6002-0000-0016 12/2009
02 06/2010
03 EL6002-0000-0017 11/2012
EL6002-0000-0018 08/2013
04* EL6002-0000-0019 05/2014

186 Version: 4.6 EL600x, EL602x


Appendix

EL6021
Hardware (HW) Firmware (FW) Revision no. Release date
00 - 02 01 05/2005
02 12/2006
03 04/2008
03 - 12* 04 EL6021-0000-0016 11/2009
05 04/2010
EL6021-0000-0017 10/2012
06 EL6021-0000-0018 08/2013
07 EL6021-0000-0019 06/2014
08* EL6021-0000-0020 10/2014

EL6022
Hardware (HW) Firmware (FW) Revision no. Release date
00 - 14* 01 EL6022-0000-0016 01/2010
02 06/2010
03* 09/2011
EL6022-0000-0017 08/2012
EL6022-0000-0018 08/2013
EL6022-0000-0019 03/2015

*) This is the current compatible firmware/hardware version at the time of the preparing this documentation.
Check on the Beckhoff web page whether more up-to-date documentation is available.

8.3 Firmware Update EL/ES/EM/EPxxxx


This section describes the device update for Beckhoff EtherCAT slaves from the EL/ES, EM, EK and EP
series. A firmware update should only be carried out after consultation with Beckhoff support.

Storage locations

An EtherCAT slave stores operating data in up to 3 locations:


• Depending on functionality and performance EtherCAT slaves have one or several local controllers for
processing I/O data. The corresponding program is the so-called firmware in *.efw format.
• In some EtherCAT slaves the EtherCAT communication may also be integrated in these controllers. In
this case the controller is usually a so-called FPGA chip with *.rbf firmware.
• In addition, each EtherCAT slave has a memory chip, a so-called ESI-EEPROM, for storing its own
device description (ESI: EtherCAT Slave Information). On power-up this description is loaded and the
EtherCAT communication is set up accordingly. The device description is available from the download
area of the Beckhoff website at (http://www.beckhoff.de). All ESI files are accessible there as zip files.

Customers can access the data via the EtherCAT fieldbus and its communication mechanisms. Acyclic
mailbox communication or register access to the ESC is used for updating or reading of these data.

The TwinCAT System Manager offers mechanisms for programming all 3 parts with new data, if the slave is
set up for this purpose. Generally the slave does not check whether the new data are suitable, i.e. it may no
longer be able to operate if the data are unsuitable.

Simplified update by bundle firmware

The update using so-called bundle firmware is more convenient: in this case the controller firmware and the
ESI description are combined in a *.efw file; during the update both the firmware and the ESI are changed in
the terminal. For this to happen it is necessary

EL600x, EL602x Version: 4.6 187


Appendix

• for the firmware to be in a packed format: recognizable by the file name, which also contains the
revision number, e.g. ELxxxx-xxxx_REV0016_SW01.efw
• for password=1 to be entered in the download dialog. If password=0 (default setting) only the firmware
update is carried out, without an ESI update.
• for the device to support this function. The function usually cannot be retrofitted; it is a component of
many new developments from year of manufacture 2016.

Following the update, its success should be verified


• ESI/Revision: e.g. by means of an online scan in TwinCAT ConfigMode/FreeRun – this is a convenient
way to determine the revision
• Firmware: e.g. by looking in the online CoE of the device

NOTE
Risk of damage to the device!
Note the following when downloading new device files

• Firmware downloads to an EtherCAT device must not be interrupted


• Flawless EtherCAT communication must be ensured. CRC errors or LostFrames must be avoided.
• The power supply must adequately dimensioned. The signal level must meet the specification.

In the event of malfunctions during the update process the EtherCAT device may become unusable and re-
quire re-commissioning by the manufacturer.

8.3.1 Device description ESI file/XML


NOTE
Attention regarding update of the ESI description/EEPROM
Some slaves have stored calibration and configuration data from the production in the EEPROM. These are
irretrievably overwritten during an update.

The ESI device description is stored locally on the slave and loaded on start-up. Each device description has
a unique identifier consisting of slave name (9 characters/digits) and a revision number (4 digits). Each slave
configured in the System Manager shows its identifier in the EtherCAT tab:

Fig. 164: Device identifier consisting of name EL3204-0000 and revision -0016

The configured identifier must be compatible with the actual device description used as hardware, i.e. the
description which the slave has loaded on start-up (in this case EL3204). Normally the configured revision
must be the same or lower than that actually present in the terminal network.

For further information on this, please refer to the EtherCAT system documentation.

188 Version: 4.6 EL600x, EL602x


Appendix

Update of XML/ESI description


The device revision is closely linked to the firmware and hardware used. Incompatible combinations
lead to malfunctions or even final shutdown of the device. Corresponding updates should only be
carried out in consultation with Beckhoff support.

Display of ESI slave identifier

The simplest way to ascertain compliance of configured and actual device description is to scan the
EtherCAT boxes in TwinCAT mode Config/FreeRun:

Fig. 165: Scan the subordinate field by right-clicking on the EtherCAT device

If the found field matches the configured field, the display shows

Fig. 166: Configuration is identical

otherwise a change dialog appears for entering the actual data in the configuration.

EL600x, EL602x Version: 4.6 189


Appendix

Fig. 167: Change dialog

In this example in Fig. Change dialog, an EL3201-0000-0017 was found, while an EL3201-0000-0016 was
configured. In this case the configuration can be adapted with the Copy Before button. The Extended
Information checkbox must be set in order to display the revision.

Changing the ESI slave identifier

The ESI/EEPROM identifier can be updated as follows under TwinCAT:


• Trouble-free EtherCAT communication must be established with the slave.
• The state of the slave is irrelevant.
• Right-clicking on the slave in the online display opens the EEPROM Update dialog, Fig. EEPROM
Update

Fig. 168: EEPROM Update

The new ESI description is selected in the following dialog, see Fig. Selecting the new ESI. The checkbox
Show Hidden Devices also displays older, normally hidden versions of a slave.

190 Version: 4.6 EL600x, EL602x


Appendix

Fig. 169: Selecting the new ESI

A progress bar in the System Manager shows the progress. Data are first written, then verified.

The change only takes effect after a restart.


Most EtherCAT devices read a modified ESI description immediately or after startup from the INIT.
Some communication settings such as distributed clocks are only read during power-on. The Ether-
CAT slave therefore has to be switched off briefly in order for the change to take effect.

8.3.2 Firmware explanation

Determining the firmware version

Determining the version on laser inscription

Beckhoff EtherCAT slaves feature serial numbers applied by laser. The serial number has the following
structure: KK YY FF HH

KK - week of production (CW, calendar week)


YY - year of production
FF - firmware version
HH - hardware version

Example with ser. no.: 12 10 03 02:

12 - week of production 12
10 - year of production 2010
03 - firmware version 03
02 - hardware version 02

Determining the version via the System Manager

The TwinCAT System Manager shows the version of the controller firmware if the master can access the
slave online. Click on the E-Bus Terminal whose controller firmware you want to check (in the example
terminal 2 (EL3204)) and select the tab CoE Online (CAN over EtherCAT).

CoE Online and Offline CoE


Two CoE directories are available:
• online: This is offered in the EtherCAT slave by the controller, if the EtherCAT slave supports this.
This CoE directory can only be displayed if a slave is connected and operational.
• offline: The EtherCAT Slave Information ESI/XML may contain the default content of the CoE.
This CoE directory can only be displayed if it is included in the ESI (e.g. "Beckhoff EL5xxx.xml").
The Advanced button must be used for switching between the two views.

In Fig. Display of EL3204 firmware version the firmware version of the selected EL3204 is shown as 03 in
CoE entry 0x100A.

EL600x, EL602x Version: 4.6 191


Appendix

Fig. 170: Display of EL3204 firmware version

In (A) TwinCAT 2.11 shows that the Online CoE directory is currently displayed. If this is not the case, the
Online directory can be loaded via the Online option in Advanced Settings (B) and double-clicking on
AllObjects.

8.3.3 Updating controller firmware *.efw


CoE directory
The Online CoE directory is managed by the controller and stored in a dedicated EEPROM, which
is generally not changed during a firmware update.

Switch to the Online tab to update the controller firmware of a slave, see Fig. Firmware Update.

Fig. 171: Firmware Update

192 Version: 4.6 EL600x, EL602x


Appendix

Proceed as follows, unless instructed otherwise by Beckhoff support. Valid for TwinCAT 2 and 3 as
EtherCAT master.
• Switch TwinCAT system to ConfigMode/FreeRun with cycle time >= 1 ms (default in ConfigMode is 4
ms). A FW-Update during real time operation is not recommended.

• Switch EtherCAT Master to PreOP

• Switch slave to INIT (A)


• Switch slave to BOOTSTRAP
• Check the current status (B, C)
• Download the new *efw file (wait until it ends). A pass word will not be neccessary usually.

• After the download switch to INIT, then PreOP


• Switch off the slave briefly (don't pull under voltage!)
• Check within CoE 0x100A, if the FW status was correctly overtaken.

8.3.4 FPGA firmware *.rbf


If an FPGA chip deals with the EtherCAT communication an update may be accomplished via an *.rbf file.
• Controller firmware for processing I/O signals
• FPGA firmware for EtherCAT communication (only for terminals with FPGA)

EL600x, EL602x Version: 4.6 193


Appendix

The firmware version number included in the terminal serial number contains both firmware components. If
one of these firmware components is modified this version number is updated.

Determining the version via the System Manager

The TwinCAT System Manager indicates the FPGA firmware version. Click on the Ethernet card of your
EtherCAT strand (Device 2 in the example) and select the Online tab.

The Reg:0002 column indicates the firmware version of the individual EtherCAT devices in hexadecimal and
decimal representation.

Fig. 172: FPGA firmware version definition

If the column Reg:0002 is not displayed, right-click the table header and select Properties in the context
menu.

Fig. 173: Context menu Properties

The Advanced Settings dialog appears where the columns to be displayed can be selected. Under
Diagnosis/Online View select the '0002 ETxxxx Build' check box in order to activate the FPGA firmware
version display.

194 Version: 4.6 EL600x, EL602x


Appendix

Fig. 174: Dialog Advanced Settings

Update

For updating the FPGA firmware


• of an EtherCAT coupler the coupler must have FPGA firmware version 11 or higher;
• of an E-Bus Terminal the terminal must have FPGA firmware version 10 or higher.

Older firmware versions can only be updated by the manufacturer!

Updating an EtherCAT device

The following sequence order have to be met if no other specifications are given (e.g. by the Beckhoff
support):
• Switch TwinCAT system to ConfigMode/FreeRun with cycle time >= 1 ms (default in ConfigMode is
4 ms). A FW-Update during real time operation is not recommended.

EL600x, EL602x Version: 4.6 195


Appendix

• In the TwinCAT System Manager select the terminal for which the FPGA firmware is to be updated (in
the example: Terminal 5: EL5001) and
click the Advanced Settings button in the EtherCAT tab:

• The Advanced Settings dialog appears. Under ESC Access/E²PROM/FPGA click on Write FPGA
button:

196 Version: 4.6 EL600x, EL602x


Appendix

• Select the file (*.rbf) with the new FPGA firmware, and transfer it to the EtherCAT device:

• Wait until download ends


• Switch slave current less for a short time (don't pull under voltage!). In order to activate the new FPGA
firmware a restart (switching the power supply off and on again) of the EtherCAT device is required.
• Check the new FPGA status

NOTE
Risk of damage to the device!
A download of firmware to an EtherCAT device must not be interrupted in any case! If you interrupt this
process by switching off power supply or disconnecting the Ethernet link, the EtherCAT device can only be
recommissioned by the manufacturer!

8.3.5 Simultaneous updating of several EtherCAT devices


The firmware and ESI descriptions of several devices can be updated simultaneously, provided the devices
have the same firmware file/ESI.

Fig. 175: Multiple selection and firmware update

Select the required slaves and carry out the firmware update in BOOTSTRAP mode as described above.

EL600x, EL602x Version: 4.6 197


Appendix

8.4 Restoring the delivery state


To restore the delivery state for backup objects in ELxxxx terminals, the CoE object Restore default
parameters, SubIndex 001 can be selected in the TwinCAT System Manager (Config mode) (see Fig.
Selecting the Restore default parameters PDO)

Fig. 176: Selecting the "Restore default parameters" PDO

Double-click on SubIndex 001 to enter the Set Value dialog. Enter the value 1684107116 in field Dec or the
value 0x64616F6C in field Hex and confirm with OK (Fig. Entering a restore value in the Set Value dialog).
All backup objects are reset to the delivery state.

Fig. 177: Entering a restore value in the Set Value dialog

Alternative restore value


In some older terminals the backup objects can be switched with an alternative restore value: Deci-
mal value: 1819238756, Hexadecimal value: 0x6C6F6164An incorrect entry for the restore value
has no effect.

198 Version: 4.6 EL600x, EL602x


Appendix

8.5 Support and Service


Beckhoff and their partners around the world offer comprehensive support and service, making available fast
and competent assistance with all questions related to Beckhoff products and system solutions.

Beckhoff's branch offices and representatives

Please contact your Beckhoff branch office or representative for local support and service on Beckhoff
products!

The addresses of Beckhoff's branch offices and representatives round the world can be found on her internet
pages:
http://www.beckhoff.com

You will also find further documentation for Beckhoff components there.

Beckhoff Headquarters

Beckhoff Automation GmbH & Co. KG

Huelshorstweg 20
33415 Verl
Germany

Phone: +49(0)5246/963-0
Fax: +49(0)5246/963-198
e-mail: info@beckhoff.com

Beckhoff Support

Support offers you comprehensive technical assistance, helping you not only with the application of
individual Beckhoff products, but also with other, wide-ranging services:
• support
• design, programming and commissioning of complex automation systems
• and extensive training program for Beckhoff system components

Hotline: +49(0)5246/963-157
Fax: +49(0)5246/963-9157
e-mail: support@beckhoff.com

Beckhoff Service

The Beckhoff Service Center supports you in all matters of after-sales service:
• on-site service
• repair service
• spare parts service
• hotline service

Hotline: +49(0)5246/963-460
Fax: +49(0)5246/963-479
e-mail: service@beckhoff.com

EL600x, EL602x Version: 4.6 199


List of illustratrions

List of illustratrions
Fig. 1 EL5021 EL terminal, standard IP20 IO device with serial/ batch number and revision ID (since
2014/01)....................................................................................................................................... 11
Fig. 2 EK1100 EtherCAT coupler, standard IP20 IO device with serial/ batch number......................... 11
Fig. 3 CU2016 switch with serial/ batch number.................................................................................... 11
Fig. 4 EL3202-0020 with serial/ batch number 26131006 and unique ID-number 204418 ................... 12
Fig. 5 EP1258-00001 IP67 EtherCAT Box with batch number/ date code 22090101 and unique se-
rial number 158102...................................................................................................................... 12
Fig. 6 EP1908-0002 IP67 EtherCAT Safety Box with batch number/ date code 071201FF and
unique serial number 00346070 .................................................................................................. 12
Fig. 7 EL2904 IP20 safety terminal with batch number/ date code 50110302 and unique serial num-
ber 00331701............................................................................................................................... 12
Fig. 8 ELM3604-0002 terminal with unique ID number (QR code) 100001051 and serial/ batch num-
ber 44160201............................................................................................................................... 13
Fig. 9 Level interfaces RS232, RS485/422............................................................................................ 15
Fig. 10 RS422 termination ....................................................................................................................... 15
Fig. 11 RS485 termination ....................................................................................................................... 16
Fig. 12 EL60xx shield connection ............................................................................................................ 17
Fig. 13 System manager current calculation .......................................................................................... 23
Fig. 14 EtherCAT tab -> Advanced Settings -> Behavior -> Watchdog .................................................. 24
Fig. 15 States of the EtherCAT State Machine........................................................................................ 26
Fig. 16 "CoE Online " tab ........................................................................................................................ 28
Fig. 17 Startup list in the TwinCAT System Manager ............................................................................. 29
Fig. 18 Offline list ..................................................................................................................................... 30
Fig. 19 Online list .................................................................................................................................... 30
Fig. 20 Spring contacts of the Beckhoff I/O components......................................................................... 33
Fig. 21 Attaching on mounting rail ........................................................................................................... 34
Fig. 22 Disassembling of terminal............................................................................................................ 35
Fig. 23 Power contact on left side............................................................................................................ 36
Fig. 24 Standard wiring............................................................................................................................ 37
Fig. 25 Pluggable wiring .......................................................................................................................... 37
Fig. 26 High Density Terminals................................................................................................................ 37
Fig. 27 Connecting a cable on a terminal point ....................................................................................... 38
Fig. 28 Correct positioning....................................................................................................................... 40
Fig. 29 Incorrect positioning..................................................................................................................... 40
Fig. 30 EL6001, EL6021 - LEDs and Connection.................................................................................... 41
Fig. 31 EL6001, EL6021 - LEDs and Connection.................................................................................... 42
Fig. 32 Connection for RS422 transfer .................................................................................................... 43
Fig. 33 Connection for RS485 transfer .................................................................................................... 43
Fig. 34 EL6002, EL6022 - LEDs .............................................................................................................. 46
Fig. 35 Connection for RS422 transfer .................................................................................................... 48
Fig. 36 Connection for RS485 transfer .................................................................................................... 48
Fig. 37 Correct positioning....................................................................................................................... 49
Fig. 38 Incorrect positioning..................................................................................................................... 49
Fig. 39 Recommended distances for standard installation position ........................................................ 51
Fig. 40 Other installation positions .......................................................................................................... 52
Fig. 41 Relationship between user side (commissioning) and installation............................................... 57

200 Version: 4.6 EL600x, EL602x


List of illustratrions

Fig. 42 Control configuration with Embedded PC, input (EL1004) and output (EL2008) ........................ 58
Fig. 43 Initial TwinCAT 2 user interface................................................................................................... 58
Fig. 44 Selection of the target system ..................................................................................................... 59
Fig. 45 Specify the PLC for access by the TwinCAT System Manager: selection of the target system .. 59
Fig. 46 Select "Scan Devices..." .............................................................................................................. 60
Fig. 47 Automatic detection of I/O devices: selection the devices to be integrated................................. 60
Fig. 48 Mapping of the configuration in the TwinCAT 2 System Manager............................................... 61
Fig. 49 Reading of individual terminals connected to a device................................................................ 61
Fig. 50 TwinCAT PLC Control after startup ............................................................................................. 62
Fig. 51 Sample program with variables after a compile process (without variable integration) ............... 63
Fig. 52 Appending the TwinCAT PLC Control project ............................................................................. 63
Fig. 53 PLC project integrated in the PLC configuration of the System Manager ................................... 64
Fig. 54 Creating the links between PLC variables and process objects .................................................. 64
Fig. 55 Selecting PDO of type BOOL ...................................................................................................... 65
Fig. 56 Selecting several PDOs simultaneously: activate "Continuous" and "All types".......................... 65
Fig. 57 Application of a "Goto Link" variable, using "MAIN.bEL1004_Ch4" as a sample ........................ 66
Fig. 58 Choose target system (remote) ................................................................................................... 67
Fig. 59 PLC Control logged in, ready for program startup ....................................................................... 68
Fig. 60 Initial TwinCAT 3 user interface................................................................................................... 69
Fig. 61 Create new TwinCAT project....................................................................................................... 69
Fig. 62 New TwinCAT3 project in the project folder explorer .................................................................. 70
Fig. 63 Selection dialog: Choose the target system ................................................................................ 70
Fig. 64 Specify the PLC for access by the TwinCAT System Manager: selection of the target system .. 71
Fig. 65 Select "Scan" ............................................................................................................................... 71
Fig. 66 Automatic detection of I/O devices: selection the devices to be integrated................................. 72
Fig. 67 Mapping of the configuration in VS shell of the TwinCAT3 environment..................................... 72
Fig. 68 Reading of individual terminals connected to a device................................................................ 73
Fig. 69 Adding the programming environment in "PLC" .......................................................................... 74
Fig. 70 Specifying the name and directory for the PLC programming environment ................................ 74
Fig. 71 Initial "Main" program of the standard PLC project...................................................................... 75
Fig. 72 Sample program with variables after a compile process (without variable integration) ............... 76
Fig. 73 Start program compilation............................................................................................................ 76
Fig. 74 Creating the links between PLC variables and process objects .................................................. 77
Fig. 75 Selecting PDO of type BOOL ...................................................................................................... 77
Fig. 76 Selecting several PDOs simultaneously: activate "Continuous" and "All types".......................... 78
Fig. 77 Application of a "Goto Link" variable, using "MAIN.bEL1004_Ch4" as a sample ........................ 78
Fig. 78 TwinCAT development environment (VS shell): logged-in, after program startup....................... 79
Fig. 79 System Manager “Options” (TwinCAT 2)..................................................................................... 81
Fig. 80 Call up under VS Shell (TwinCAT 3) ........................................................................................... 81
Fig. 81 Overview of network interfaces ................................................................................................... 81
Fig. 82 EtherCAT device properties(TwinCAT 2): click on „Compatible Devices…“ of tab “Adapter” ..... 82
Fig. 83 Windows properties of the network interface............................................................................... 82
Fig. 84 Exemplary correct driver setting for the Ethernet port ................................................................. 83
Fig. 85 Incorrect driver settings for the Ethernet port ............................................................................. 84
Fig. 86 TCP/IP setting for the Ethernet port ............................................................................................ 85
Fig. 87 Identifier structure ....................................................................................................................... 86

EL600x, EL602x Version: 4.6 201


List of illustratrions

Fig. 88 OnlineDescription information window (TwinCAT 2) ................................................................... 87


Fig. 89 Information window OnlineDescription (TwinCAT 3) ................................................................... 87
Fig. 90 File OnlineDescription.xml created by the System Manager ...................................................... 88
Fig. 91 Indication of an online recorded ESI of EL2521 as an example .................................................. 88
Fig. 92 Information window for faulty ESI file (left: TwinCAT 2; right: TwinCAT 3).................................. 88
Fig. 93 Using the ESI Updater (>= TwinCAT 2.11).................................................................................. 90
Fig. 94 Using the ESI Updater (TwinCAT 3)............................................................................................ 90
Fig. 95 Append EtherCAT device (left: TwinCAT 2; right: TwinCAT 3) ................................................... 91
Fig. 96 Selecting the EtherCAT connection (TwinCAT 2.11, TwinCAT 3)............................................... 91
Fig. 97 Selecting the Ethernet port ......................................................................................................... 91
Fig. 98 EtherCAT device properties (TwinCAT 2) ................................................................................... 92
Fig. 99 Appending EtherCAT devices (left: TwinCAT 2; right: TwinCAT 3)............................................. 92
Fig. 100 Selection dialog for new EtherCAT device ................................................................................. 93
Fig. 101 Display of device revision ........................................................................................................... 93
Fig. 102 Display of previous revisions ...................................................................................................... 94
Fig. 103 Name/revision of the terminal ...................................................................................................... 94
Fig. 104 EtherCAT terminal in the TwinCAT tree (left: TwinCAT 2; right: TwinCAT 3).............................. 95
Fig. 105 Differentiation local/target system (left: TwinCAT 2; right: TwinCAT 3)....................................... 96
Fig. 106 Scan Devices (left: TwinCAT 2; right: TwinCAT 3) ...................................................................... 96
Fig. 107 Note for automatic device scan (left: TwinCAT 2; right: TwinCAT 3)........................................... 96
Fig. 108 Detected Ethernet devices .......................................................................................................... 97
Fig. 109 Example default state .................................................................................................................. 97
Fig. 110 Installing EthetCAT terminal with revision -1018 ......................................................................... 98
Fig. 111 Detection of EtherCAT terminal with revision -1019 .................................................................... 98
Fig. 112 Scan query after automatic creation of an EtherCAT device (left: TwinCAT 2; right: Twin-
CAT 3) ......................................................................................................................................... 98
Fig. 113 Manual triggering of a device scan on a specified EtherCAT device (left: TwinCAT 2; right:
TwinCAT 3).................................................................................................................................. 99
Fig. 114 Scan progressexemplary by TwinCAT 2 ..................................................................................... 99
Fig. 115 Config/FreeRun query (left: TwinCAT 2; right: TwinCAT 3)......................................................... 99
Fig. 116 Displaying of “Free Run” and “Config Mode” toggling right below in the status bar .................... 99
Fig. 117 TwinCAT can also be switched to this state by using a button (left: TwinCAT 2; right: Twin-
CAT 3) ......................................................................................................................................... 99
Fig. 118 Online display example ............................................................................................................... 100
Fig. 119 Faulty identification ...................................................................................................................... 100
Fig. 120 Identical configuration (left: TwinCAT 2; right: TwinCAT 3) ......................................................... 101
Fig. 121 Correction dialog ......................................................................................................................... 101
Fig. 122 Name/revision of the terminal ...................................................................................................... 102
Fig. 123 Correction dialog with modifications ........................................................................................... 103
Fig. 124 Dialog “Change to Compatible Type…” (left: TwinCAT 2; right: TwinCAT 3) .............................. 103
Fig. 125 TwinCAT 2 Dialog Change to Alternative Type ........................................................................... 103
Fig. 126 Branch element as terminal EL3751............................................................................................ 104
Fig. 127 “General” tab................................................................................................................................ 104
Fig. 128 „EtherCAT“ tab............................................................................................................................. 105
Fig. 129 “Process Data” tab....................................................................................................................... 106
Fig. 130 Configuring the process data....................................................................................................... 107
Fig. 131 „Startup“ tab................................................................................................................................. 108

202 Version: 4.6 EL600x, EL602x


List of illustratrions

Fig. 132 “CoE – Online” tab ....................................................................................................................... 109


Fig. 133 Dialog “Advanced settings”.......................................................................................................... 110
Fig. 134 „Online“ tab .................................................................................................................................. 111
Fig. 135 "DC" tab (Distributed Clocks)....................................................................................................... 112
Fig. 136 Selection of the diagnostic information of an EtherCAT Slave ................................................... 114
Fig. 137 Basic EtherCAT Slave Diagnosis in the PLC............................................................................... 115
Fig. 138 EL3102, CoE directory ................................................................................................................ 117
Fig. 139 Example of commissioning aid for a EL3204 .............................................................................. 118
Fig. 140 Default behaviour of the System Manager .................................................................................. 119
Fig. 141 Default target state in the Slave .................................................................................................. 119
Fig. 142 PLC function blocks .................................................................................................................... 120
Fig. 143 Illegally exceeding the E-Bus current ......................................................................................... 121
Fig. 144 Warning message for exceeding E-Bus current ......................................................................... 121
Fig. 145 StartUp entry with transition S -> O ............................................................................................ 123
Fig. 146 “CoE - Online, EL60x4 terminals” tab ......................................................................................... 126
Fig. 147 Each higher level (if available or activated) dictates the communication features to the level
below it. ....................................................................................................................................... 129
Fig. 148 Checking the settings desired by the COM application in the CoE ............................................ 130
Fig. 149 Default startup entries of a EL6002 (example) – only the default entries (in this case 0x1C12
and 0x1C13) are required............................................................................................................ 130
Fig. 150 VirtualComDriver Settings (example) .......................................................................................... 130
Fig. 151 RS232-LIN sub-D connector connected to the EL6001 terminal................................................. 134
Fig. 152 LIN frame example: Query from master to node with ID 0x07..................................................... 135
Fig. 153 LIN frame example: ID0x07 with data 0xEA,0xBD,0x08,0xB7 + checksum 0x97 ....................... 135
Fig. 154 Left: Query on the LIN bus with PID 0x47, right: LIN frame with the same PID and data, in-
cluding checksum ........................................................................................................................ 135
Fig. 155 Searching the Ethernet adapter................................................................................................... 137
Fig. 156 Selection and confirmation of the Ethernet adapter..................................................................... 137
Fig. 157 Activation of the configuration...................................................................................................... 137
Fig. 158 Confirming the activation of the configuration.............................................................................. 138
Fig. 159 Generating variable mapping....................................................................................................... 138
Fig. 160 Restarting TwinCAT in RUN mode .............................................................................................. 138
Fig. 161 Compile project............................................................................................................................ 138
Fig. 162 Confirming program start ............................................................................................................ 139
Fig. 163 Received barcode ....................................................................................................................... 139
Fig. 164 Device identifier consisting of name EL3204-0000 and revision -0016 ...................................... 188
Fig. 165 Scan the subordinate field by right-clicking on the EtherCAT device .......................................... 189
Fig. 166 Configuration is identical ............................................................................................................. 189
Fig. 167 Change dialog ............................................................................................................................. 190
Fig. 168 EEPROM Update ........................................................................................................................ 190
Fig. 169 Selecting the new ESI.................................................................................................................. 191
Fig. 170 Display of EL3204 firmware version ............................................................................................ 192
Fig. 171 Firmware Update ......................................................................................................................... 192
Fig. 172 FPGA firmware version definition ............................................................................................... 194
Fig. 173 Context menu Properties ............................................................................................................ 194
Fig. 174 Dialog Advanced Settings ........................................................................................................... 195
Fig. 175 Multiple selection and firmware update ...................................................................................... 197

EL600x, EL602x Version: 4.6 203


List of illustratrions

Fig. 176 Selecting the "Restore default parameters" PDO ........................................................................ 198
Fig. 177 Entering a restore value in the Set Value dialog.......................................................................... 198

204 Version: 4.6 EL600x, EL602x

You might also like