DZ6/DZ7 Moulded Case Circuit Breakers
User Centric Innovation
The DZ range of Moulded Case Circuit Breakers (MCCB) is a culmination of innovation.
Designed to meet the requirements of today’s evolving electrical systems in modern installations, the range
features significantly higher fault breaking capacities.
Considering the changing expectations of customers and a need for economical and reliable solution, we
introduce DZ6-400 & DZ7-800 MCCB with operational voltages Ue upto 800V a.c.
Key Feature
• Rated currents: 125A*, 160A*, 200A, 250A, 320A, • All MCCB's are Ambient temperature compensated
400A, 500A, 630A, 800A • 6 cavities in the MCCB for variety of accessories
• 3P/4P, 1250V AC Ui rated insulation voltage - Auxiliary contacts- 3 nos
• Double break high breaking capacity contact system - Trip Alarm Contact-1 nos
- Under voltage release-2 nos or shunt release -2 nos
• Double insulation
• Conforms to IS 60947-2, IEC 60947-2 and
• Positive isolation EN 60947-2
• Thermal Magnetic & Microprocessor Release variants • RoHS compliant
• High Electrical & Mechnical operations
4
Protection Releases
• Wide range of protection setting
• Provision for release testing
• Thermal Memory with option of defeat
• Ambient Temperature Compensation :
Solar applications are mainly outdoor installations and hence the ambient temperature has direct impact on
tripping characteristics of MCCB according to the time of the day, season or location. For example, ambient
temperature is very low in some areas of Jammu & Kashmir where a conventional MCCB will take higher time
to trip, where as ambient temperature is very high in desert areas of Rajasthan where a conventional MCCB
will take lesser time to trip.
In order to cater to this variation, all - DZ MCCBs are ambient temperature compensated, which means the trip
ping characteristics will remain constant irrespective of ambient temperature up to 55°C.
Other Accessories
• Extended Rotary handle & Direct Rotary handle
• Spreaders
Accessories
Termination Types
Spreader
5
Technical Specification
Release Specification
6
Technical Specification
Current Setting
Ir = x In 0.20 to 1 x In 0.20 to 1 x In
(in step of 0.05)
Current Setting Ineutral = x Ir OFF / 0.5/ 1.0/ 2.0 x Ir OFF / 0.5/ 1.0/ 2.0 x Ir
“OverLoad
Time delay (Inverse) Tr As per Overload Curve Setting As per Overload Curve Setting
(Neutral)”
Protection Mode ON/OFF ON/OFF
Short Circuit Time delay tsd As per I2t curve /100ms/200ms As per I2t curve /100ms/200ms
Current Setting Ig = x In 0.2, 0.4, 0.5, 0.7 x In 0.2, 0.4, 0.5, 0.7 x In
Rated Continuous
Altitude (m) Rated Voltage (V)
Current (In)
7
Tripping Characteristics
8
Tripping Characteristics
9
Tripping Characteristics
10
Tripping Characteristics
11
Power Loss Curves for MCCB
12
Power Loss Curves for MCCB
13
DZ6
14
DZ7
15
DZ6
16
DZ7
17
DZ6
18
DZ7
19
800V AC Rated Voltage Applications:
Specially designed OMEGA ACB range offers a solution for electrical applications with system voltages of
800Va.c. This range of ACBs maintain the same dimension and accessories as the standard 690V a.c. range.
Key Feature
• Range: 1000 to 5000A, 800V a.c., 3P/4P • Modular & snap-fit accessories such as UVR, SR &
• Variants: Manually & Electrically operated, CR modules, redefi ne the modularity on a time
Fixed & Draw-out scale of 5 mins.
• High short-time Fault withstanding capacity, • Unique breaker front-facia architecture displays the
upto Icu = Ics = Icw (1 sec) = 65kA electrical accessories mounted on the ACB
• Conforms to IS 60947-2, IEC 60947-2 and • Ease of on-site convertibility from Manual to
EN 60947-2 Electrical & Fixed to Draw-out version
MTX 1.0 L S I
MTX 1.0G L S I N G
MTX 1.5G L S I N G + Display + Current Metering
Microprocessor
+ fault history
MTX 3.5 + L S I N G + Display + Current metering
communication module + Inbuilt Communication
20
Accessories
External Neutral CTs Shunt Release Under Voltage Release + Delay Module
Electrical charging device Auxiliary contact block (4 NO+4 NC) Closing Release
Release Type
• Wide range of protection setting
• Query button for last trip information details such as cause of tripping, date and time stamping of tripping
• Inbuilt Earth-Fault & neutral protection in MTX1G • Front accessible test port
& MTX1.5G
• Query button for last trip record
• Switchable thermal memory for cable protection on
repetitive overloads • Inbuilt rating-plug through DIP switches
• I2t ON curve for Short-circuit & Earth-fault protection • Test button to check the health of protection release
21
Technical Specification
Frame 1 2 3
Utilization Category B
22
Release Specification
Altitude derating
Altitude H (m) <2000 3000 4000 5000
Rated service voltage (at 50/60 Hz) Ue (V) Ue 0.9Ue 0.8Ue 0.7Ue
Rated Uninterrupted Current at 400 C In (A) In 0.98In 0.96In 0.94In
Impulse withstand voltage Uimp (kV) 12 11 10 8
Rated insulation voltage Ui (V) 1250 900 780 700
23
Overload - I2t Instantaneous
(UW-MTX 1.0/1G/1.5G/3.5C) (UW-MTX 1.0/1G/1.5G/3.5C)
24
Ground Fault - I2t ON Ground Fault - I2t OFF
(UW-MTX 1.0/1G/1.5G/3.5C) (UW-MTX 1.0/1G/1.5G/3.5C
Overload - I2t
(UW-MTX1.0)
25
Mounting and Bus Bar Support
CAUTION:
Inadequate termination support may result in
overheating & adversely affect performance
during short circuit conditions.
26
Mounting
27
Mounting
All Dimensions in mm
A Mounting holes suitable for M10 / Equivalent BS bolt "* 4000A only in drawout version
28
Mounting
3200-5000A
1000-2000AFr.3
Fr.13P
3PFixed
FixedCircuit
Circuitbreaker
Breaker
Draw-out
3200-5000A Circuit
Fr.3 3P FixedBreaker
Circuit Breaker
29
Termination - Fixed Breakers
All Dimensions in mm
30
Termination - Fixed Breakers
Mounting
1000-2000A
3200A Fr.2Fr.1 3P FixedTermination*
3P Vertical Circuit Breaker
All Dimensions in mm
31
Termination - Fixed Breakers
All Dimensions in mm
32
Accessories & Features
CZ Switch disconnector
Highlights
• Wide range of current 125A to 630A gives flexibility in designing ACCB with
multiple number of incomers for 800V a.c. application
• Wide range of current 125A to 630A gives flexibility in designing SMB with multiple
number of incomers for 1000V - 1500V d.c. application
• For CZ1 maximum Al cable cross section termination capacity for 50oC is 185 sqmm upto 250A
and 240 sqmm for 315A
• For CZ2 maximum Al cable cross section termination capacity is 2x300 sqmm
Key Feature
• Range: FGS range - 63A, 800V a.c.
CZ1 range - 125A to 315A ,800V a.c.
CZ2 range - 315A to 630A ,800V a.c.
CZ1 range - 125A to 315A ,1500V d.c.
CZ2 range - 315A to 630A ,1500V d.c.
• Variants : Extended handle and direct handle versions
• Conforms to IEC 60947-3
• RoHS compliant
Key Feature
• Operating Shaft
• Phase Barriers
• Terminals Shrouds
• Direct handle kit
• Shorting Link PV DC
• Extended handle kit
33
MountingSpecification
Technical
AC Switch Disconnector
Frame Size Unit FGS CZ 1 CZ 2
Current Range In A 63 125 160 200 250 315 315 400 630
Rated Operational
Ue V a.c. 800
Voltage
Short circuit making kA
Icm - 30 45 45
capacity (peak)
Rated Breaking
Capacity (AC 22A at kA 1 1 1.3 1.6 2 2.5 2.5 3.2 3
800Vac)
DC Switch Disconnector
34
Dimensions and Mounting
CZ1 AC SD 125/160/200/250/315A
MINIMUM : 140
MAXIMUM : 322
MINIMUM : 120
E 139.4 104 MAXIMUM : 302
C 42.5 3 42.5
D (Mounting) 3
10 10
B
A
PANEL DOOR
320
99
180
8
35
Technical Specification
Dimensions and Mounting
CZ1 AC SD 125/160/200/250/315A
Panel Cutout
A
B
4 Holes,Ø4
73
No. of
SD Mounting Holes A B
Poles
2P 69 0
3P 118 0
4P 139 69
Mounting Orientation
180°
90° 90°
Reference
Termination Capacity
125/160/200/250A 315A
36
Accessories & Features
CZ1 AC SD 125/160/200/250/315A
Phase Barrier
Terminal Shroud
ON ON
I I
O O
OF OF
F F
37
Accessories & Features
CZ1 AC SD 125/160/200/250/315A
Shaft Locking
38
Dimensions and Mounting
CZ2 AC SD 315/400/630
Shaft Locking
Arrangement
1. Unscrew shaft locking 2. Adjust/Cut the shaft as per 3. Tighten the Nut-Bolts.
arrangement and insert panel requirement.(Min. (T ighten Torque : 1.6 N-m)
Ensure that shaft pin is
CAUTION vertical for any mounting shaft as per required length. Engagement Length, X=60mm
orientation of the switch Inside Mechanism)
No. of
Rating(A) A B C D E F
poles
39
Technical Specification
Dimensions and Mounting
CZ2 AC SD 315/400/630
Panel Cutout
No. of
A B
Poles
2P 90 0
3P 155 0
4P - SIDE 220 0
4P - CEN-
180 90
TER
Mounting Orientation
Termination Capacity
315/400A 630A
Note: For Aluminum cable, Tin plated lugs are recommended.Termination bolt head should be on bottom side as shown in figures
* : Higher length (M10 X 40 for 250A; M12 X 40 for 315A) of termination bolt required to connect 2 busbar of 10mm .
40
Dimensions and Mounting
CZ1 DC SD 125/160/200/250/315A
41
Technical Specification
Dimensions and Mounting
CZ1 DC SD 125/160/200/250/315A
Termination Capacity
125/160/200/250A 315A
Note: For Aluminum cable, Tin plated lugs are recommended.Termination bolt head should be on bottom side as shown in figures
* : Higher length (M10 X 40 for 250A; M12 X 40 for 315A) of termination bolt required to connect 2 busbar of 10mm .
42
Accessories & Features
CZ1 DC SD 125/160/200/250/315A
43
Technical Specification
Dimensions and Mounting
CZ2 DC SD 315/400/630
No. of
Rating(A) A B C D E F D
poles
44
Dimensions and Mounting
CZ2 DC SD 315/400/630
Mounting Orientation
Terminal Capacity
315/400A 630A
45
Dimensions and mounting
Technical Specification
Accessories & Features
CZ2 DC SD 315/400/630
Circuit Diagrams
46
Accessories & Features
Key Feature
• Type 2: Protection against indirect lightning and switching surges
• Type 1+2: Protection against direct and indirect lightning surge
AUSP023P40-1500
47
AUSP123P50-1360
• Type 1 + 2 SPD power surge protector
• For 3-Phase AC power network
• Uc up to 880 Vac L/L
• Uc up to 1360 Vac L/PE
• In : 20 kA
• Iimp : 12,5 kA
• Pluggable module for each phase
• EN 61643-11, IEC 61643-11 and UL 1449 ed.4 compliance
AUSP123P50-1360
48
AUSP123P50-880
• Type 1 + 2 AC power surge protector
• For 3-Phase AC power network
• Uc up to 880 Vac L/L
• Uc up to 1360 Vac L/PE
• In : 20 kA
• Iimp : 12,5 kA
• Pluggable module for each phase
• EN 61643-11, IEC 61643-11 and UL 1449 ed.4 compliance
AUSP123P50-880
49
Exora MCBs Miniature Circuit Breaker
Highlights
• Conforms to IEC 60947-2, IEC60898-1
Key Feature
• Conforms to IS/IEC 60898-1, IEC 60947-2
• Characteristic Tripping curves B, C & D
• Energy limiting Class 3 allows low let-through energy in the system
• Unique patented design gives both label holder and true contact indication facility For individual poles
• Low watt loss – almost 50% of the values prescribed by IEC 60898-1 saves energy
• Trip free mechanism to ensure maximum safety
• Design based on advanced current limiting hammer trip mechanism ensures quick breaking
• No line load bias gives flexibility for incomer supply termination on either sides
• Connection - Biconnect on both sides of MCB
• Accessories – wide range of accessories like aux contact, trip alarm contact and shunt release
• DC MCB as per IEC 60947-2 : Rated Voltage: 130/250V d.c. (SP/DP), 250/500V d.c. (SP/DP)
• CE conformity
50
Technical Specification
Dimensions
-
ON
ON
20.5
20.5
87.3
87.3
45
85
45
85
47°
47°
OFF
OFF
39.5
39.5
++ -
31 5.5 31 5.5
36.5 35 36.5 17.5 35
17.5
41 41
43 43
59.6 SP DP 59.6 SP DP
69 69
- -
+ + - + +-
SP DP SP DP
51
BBT Busbar Trunking System
Highlights
• Type tested design as per IEC 61439 Part-1 & 6
• Higher joint overlapping area ensures less voltage drop and less heat loss
Key Feature
• Range (A): Al-250 to 5000; Cu-400 to 6300
52
Technical Specification
Specification Detail
Busduct Construction Sandwich Type
Busduct Rating Aluminium - 250 A to 5000 A Copper - 400 A to 6300 A
Rated Operational Voltage (Ue) 415 V / 690 V and maximum upto 1000 V
Rated Insulation Voltage ( Ui) 1100 V
Rated Impulse Voltage (Uimp) 8kV/12 Kv (1.2/50 micros)
Rated Dielectric Voltage 2.5 Kv for 5 sec
Rated Frequency 50 Hz/ 60 Hz
Pole Configurations 3P 3W with or without 50% internal earth and provision for
munting external earth
Insulation Class Class-F (155 degree C)
Insulation Material Multilayer Polyethylene Terephthalate (UL listed)
Surface Coating on Enclosure Epoxy Powder Coating
Paint Shade RAL 7032
Degree of protection IP54 / IP55 for Indoor and IP55 / IP 66 for Outdoor
Joint Block Uniblock Joint with twin-headed maintenance-free nut
Seismic Compliance Zone-5, as per IS 1893 (Part 1) - 2002 and IEEE 693 - 2005
Tested with Vertical + Horizontal busduct and Plug-in Box
assembly
Fire Resistance in Building Penetration Verified for Integrity: 240 minutes
Resistance to Flame Propagation Verified
Accessories
Flanged End Feeder Horizontal Elbow Vertical Offset Elbows Vertical Elbow
53
Dimensions (Aluminium Busduct)
400A 1 - 6 x 40 135 80 8
*Weight given in above table is straight feeder weight; it can vary by +/-5%
400A 1 - 4 x 40 135 78 8
630A 1 - 6 x 40 135 78 10
800A 1 - 6 x 40 135 88 12
1000A 1 - 6 x 55 135 93 13
*Weight given in above table is straight feeder weight; it can vary by +/-5%
54
Impedance at 50Hz (Copper Busduct)
55
Line-to-Line Voltage Drop at 50Hz (Aluminium Busduct)
*Power Factor
*Power Factor
56
Electrical Characteristics
• (6+0) digits backlit display & (2+4) digits high resolution display.
57
Technical Specifications
Dimensions
58
Electrical Characteristics
• Store energy values in every 15 mints block along with avg frequency in same interval
• ABT meters are also available as per PGCIL specs, guidelines & capable of convert data in NPC format (Power Grid's report format)
• Anti-tamper features
• Display and data reading in power OFF condition
• Capable of recording Load Survey data & easy download through Base Computer Software
• SAMAST Complaint
59
Technical Specifications
Dimensions
60
Electrical Characteristics
Specifications
Connection 3 Phase 4 Wire
Standards Applicable IS 14697, IEC 62052-11, IEC 62053-22, CBIP 325
Accuracy Class Cl 0.2s
Rated Voltage 3 x 63.5V (P-N)
Voltage Variation -40% to +20%
-/1A
Current Rating
-/5A
Starting Current 0.1% of basic current
Accuracy up to 200% of basic current
Frequency 50Hz
Frequency Variation -5% to +5%
Power Consumption As per IS 15959
Operating Temperature -10ºC to +55ºC
Ingress Protection IP 51
61
Supported parameters (As per customer requirement)
Phase wise voltages and currents, system PF, active power, reactive power
Instantaneous
and apparent power Frequency, Phase sequence, Total harmonic distortion
Energy Measurement 4 quadrant measurement of kWh, kVArh, and kVAh
Maximum Demand kW and kVA along with date and time
Time of Day Up to 8 registers, profiles and seasons
Display
LCD 8 digit backlit display
Display mode Auto scroll, push button and high resolution modes
LED Pulse LEDs for kWh and kVArh
Other Features
Day wise energies
Load survey profile
Tariff wise energies
Display and data reading in absence of power
Tamper detection
Bi-directional energy recording available
Data security Multi-level password for data reading and programming
Communication Electrically isolated optical port as per IEC62056-21
Optional communication RS 232 / RS 485 / TCP/IP communication port
Interface
Protocol supported IEC / DLMS / MODBUS / Customer specific
Tamper proofing provision Ultrasonic welding available (optional)
62
Accessories & Features
Technical Chart
Type of measurement Type 3 Phase 4 Wire, 3 Phase 3 Wire, 1 Phase
True RMS, 128 samples per cycle
1 sec update time, 4 Quadrant Power & Energy
Measurement Accuracy Class 0.5S as per IEC 62053-22
Display type and 4 digit for instantaneous and 8 digits for
LED
resolution cummulative
Measuring circuit 50 - 600 VLL
PT Primary and Secondary user programmable for
Input voltage
LT and HT applications
Burden: 0.2VA max per phase
-/5A and -/1A site selectable
Current range from 20mA-5A with overload
capacity upto 120% In (i.e. 6A)
Input current Burden: 0.2VA max per phase
CT Primary and Secondary user programmable for
LT and HT applications
Frequency 45-65 Hz
Auxilliary circuit Aux voltage 80 - 300V a.c./d.c
Aux burden <5VA
Freq range 45-70Hz
63
Power Details Test of power as per IEC 62053-21
consumption
Voltage dips and as per IEC 62053-21
interrupts 10A max continuous, 20 times of In for 3 sec
Short time over current
protection
Electro-Magnetic Fast transients burst test ±4 kV as per IEC 61000-4-4
Compatibility (EMC) Immunity to electrostatic ±8 kV air discharge, ±6 kV contact discharge as per
discharge IEC 61000-4-2
Radiated, radio- 10 V/m as per 61000-4-3
frequency,
electromagnetic field 10 V/m as per IEC 61000-4-6
Immunity test Immunity
to electromagnetic HF ±6 kV as per IEC 61000-4-5
fields 1 A/m as per IEC 61000-4-8
through conducted lines Class B as per CISPR 22
Surge immunity test
Rated power frequency
magnetic fields
Emission
Insulation Properties Impulse voltage test ±6 kV as per IEC 62052-11
AC voltage test 4 kV double insulation as per IEC 62053-21
Operating Conditions Operating temperature -10 C to +55 C
Storage temperature -25 C to +70 C
Humidity 5% to 95% relative humidity non-condensing
Recommended 12 to 14 SWG with U type lug of max 6.75mm
connecting wire width
Mechanical Conditions Shock As per standard IEC 60068-2
Vibration 10 to 55 Hz, 0.15 mm amplitude
Casing Plastic mould protected to IP51 from front side
Safety Measurement category CAT III
Pollution degree 2
Protection IP20 at terminals, IP 51 when mounted on panel
Weight and Dimensions Product weight 275 gms
Bezel dimension 96 X 96 X 30 mm
(W X H X D) 90 X 90 +2.0-0.0 mm
Panel cutout
Outputs Meter constant :10000/ (external CT ratio X PT ratio)
Communication RS485 port Modbus RTU
Type 2400, 4800, 9600, 19200, 38400 bps (preferred
Baud rate 9600)
Parity Odd, Even, None
Slave id 1 to 247 (programmable)
Isolation 2 kVAC isolation for 1 minute between
communication and other circuits
64
Parameter List
WL4415 Parameters
65
Get the Switchgear Training Edge!
Aimed at maximizing productivity, conserving energy, minimizing costs and enhancing safety, our Electrical &
Automation training programmes have benefitted Lakhs of professionals over the last three decades. These
training programmes are highly beneficial as they provide right exposure and impart knowledge on selection,
installation, maintenance and testing of Electrical & Automation products. Options to connect on Digital
platform, At Training Centre or on-site Programs
L&T Electrical & Automation Training Centre L&T Electrical & Automation Training Centre L&T Electrical & Automation Training Centre,
T-156/157, MIDC, Bhosari, Pune - 411 026 C-6 & 7, UPSIDC, P. O. Sarojininagar, A-25, Imperia Complex, First Floor, Mohan
Tel: 020 2712 0037 / 2712 0653 Lucknow - 226 008 Cooperative Industrial Estate,
E-mail: stc-pune@Lntebg.com Tel: 0522 247 6015/97944 54455 Near Sarita Vihar / Mohan Estate Metro
E-mail: stc-lucknow@Lntebg.com Station Mathura Road, New Delhi - 110 044
Tel: 011 42260600/9899020306
E-mail: stc-delhi@Lntebg.com
L&T Electrical & Automation Training Centre L&T Electrical & Automation Training Centre L&T Electrical & Automation Training Centre
Ooty-Coonoor Main Road Yellanahalli P.O., Behind L&T Knowledge City, Near Village 4th Floor, 3B, Shakespeare Sarani, Landmark -
The Nilgiris - 643 243 Ankhol, Vadodara 390019 Kenil Worth Hotel, Kolkata - 700071
Tel.: 0423 251 7107 Tel: 0265 6147805 / 6147808 Tel: 033 42005975/44085974 / 44085978
E-mail: stc-coonoor@Lntebg.com E-mail: stc-vadodara@Lntebg.com E-mail: stc-kolkata@Lntebg.com
66