1440W/2400VA Inverter/Uninterruptible Product Code: FBI2400W
Barcode: 6002844069216
Power Supply (UPS) 24V DC to 230V AC
Automatic mains-to-battery switch over / transfer.
Selectable mains transfer voltage range.
10Amp or 20Amp selectable battery charging current.
Provides overload protection.
Auto restart on mains return.
Multi-function with LCD screen and buzzer alarm.
PRODUCT DESCRIPTION Highly efficient DC-to-AC conversion, minimizing energy loss.
The 2400VA converts DC power into modified sine wave AC Intelligent 2-stage battery charger control for efficient charging
power. With 1440 Watt continuous output and compact and preventing battery overcharge.
design, the unit is ideal for running TVs, Stereos, Laptop and
Desktop computers and many other home appliances.
2400VA will automatically transfer to inverter and provide
TECHNICAL INFORMATION
power when AC is interrupted unexpectedly. SPECIFICATIONS
TYPICAL APPLICATION Model 1440W / 2400VA
Inverter / UPS
Capacity 1440W / 2400VA
Front Panel Nominal voltage 220 / 230 / 240VAC
AC Input Input voltage range 90~280VAC
Nominal frequency 50 / 60Hz (Auto Detection)
1
POWER INVERTER
Input Voltage Narrow 170~280VAC
Range Selector Wide 90~280VAC
2
Voltage 230VAC + 10 / -18%
Frequency 50 / 60Hz ± 0.5Hz
1. Input/output voltage, load level, battery capacity, work status. Waveform Modified sine wave
2. Power ON/OFF. Inverter
Mode Output Efficiency (AC to AC) > 95%
Back Panel Efficiency (DC to AC) > 80%
No load input current Approx 2A DC
4 Battery Nominal voltage 24VDC
Charging voltage 27.4 +/- 0.4V
Charger Charging current 10A / 20A
5
Overcharging protection 32 +/- 0.8V
Transfer Transfer time Typical 15-20ms, 40ms max.
LCD Input/Battery, Output/Load/Fault, Load level, Battery capacity, Line mode,
1 2 3 Indicator Backup mode.
Low battery voltage
in battery mode Beeps every 2 seconds
1. DC input connector (battery terminal).
2. AC input. Audible Alarm Overload Beeps every 0.5 second
3. Output receptacles. Fault Beeps continuously
4. Input voltage range selector: (See specifications chapter).
5. Charge current selector: 10A/20A adjustable. Environment Temperature 0 ~ 40°C
Deep discharge, Overcharge, Short circuit, Overload, Battery short,
Protections Over voltage, Under voltage.
Caution! Always connect the battery first and then the inverter/UPS.
Caution! DO NOT place anything
between battery cable ring terminals PACKAGE CONTENTS
and battery terminals. The terminal
stud/bolt is not designed to carry
current. Apply Anti-oxidant paste 1x Inverter unit
to terminals after terminals have 1x Battery cable set
been torqued. 1x Instruction manual
NO washers PACKAGE DIMENSIONS
or other
wires here
Height Depth Width Weight QTY
Cable from battery
(mm) (mm) (mm) (kg)
D
Package 287 130 335 2.6 1
Carton 600 400 350 18.7 6
Tighten
nuts
securely
www.ellies.co.za