24abr3 4PD
24abr3 4PD
Product Data
INDUSTRY LEADING
FEATURES / BENEFITS
Efficiency
S 13 SEER/11 EER (Nominal)
S Microtube Technologyt refrigeration system
S Indoor air quality accessories available
Sound
S Sound level as low as 76 dBA
S As low as 74 dBA with optional accessory sound hood
Comfort
S System supports Thermidistatt or standard thermostat
controls
Reliability
S Front--seating service valves
S Scroll compressor
S Internal pressure relief valve
S Internal thermal overload
S Filter drier
S Balanced refrigeration system for maximum reliability
Durability
WeatherArmort protection package:
S Solid, durable sheet metal construction
S Wire coil guard
As an Energy Starr Partner, Carrier Corporation has determined
that this product meets the Energy Starr guidelines for energy S Baked--on, complete outer coverage, powder paint
efficiency. Refer to the combination ratings in the Product Data Applications
for system combinations that meet Energy Starr guidelines.
S Long--line -- up to 250 feet (76.20 m) total equivalent
NOTE: Ratings contained in this document are subject to length, up to 200 feet (60.96 m) condenser above
change at any time. Always refer to the AHRI directory evaporator, or up to 60 ft. (18.28 m) evaporator above
(www.ahridirectory.org) for the most up--to--date ratings condenser (See Longline Guide for more information.)
information.
S Low ambient (down to --20_F/--28.9_C) with accessory
kit
Warranty
Single Phase
S 5--year limited compressor warranty
S 5--year limited parts warranty
Three Phase
S 5--year limited compressor warranty
S 1--year limited parts warranty
MODEL NUMBER NOMENCLATURE
1 2 3 4 5 6 7 8 9 10 11 12 13
N N A A A/N N N N A/N A/N A/N N N
2 4 A B R 3 3 6 A 0 0 3 0
ISO 9001:2000
REGISTERED
24ABR3
STANDARD FEATURES
Feature 18 24 30 36 42 48 60
Maximum SEER 14.5 14.25 14.5 14 14 14 13.5
Scroll Compressor X X X X X X X
Wire Coil Guard X X X X X X X
Field ---Installed Filter Drier X X X X X X X
Front---Seating Service Valves X X X X X X X
Internal Pressure Relief Valve X X X X X X X
Internal Thermal Overload X X X X X X X
Long ---Line capability X X X X X X X
Low Ambient capability with Kit X X X X X X X
X = Standard
2
PHYSICAL DATA
36--- 33, 42--- 31, 48--- 32, 60--- 36,
30--- 33, 36--- 53, 42--- 51, 48--- 52, 60--- 56,
UNIT SIZE SERIES 18--- 32 24--- 33
30--- 53 36--- 63, 42--- 61, 48--- 62, 60--- 66,
36--- 12 42--- 11 48--- 11 60--- 12
Operating Weight lb (kg) 120 (326.6) 120 (54.4) 130 (60.0) 139 (63.0) 192 (87.1) 206 (87.1) 222 (100.1)
Shipping Weight lb (kg) 154 (69.9) 156 (70.8) 170 (77.1) 177 (80.3) 220 (99.8) 242 (109.8) 265 (120.2)
Compressor Type Scroll
REFRIGERANT Freon (R---22)
Control TXV (R---22 Hard Shutoff)
Charge lb (kg) 3.9 (1.8) 4.5 (2.0) 4.9 (2.2) 5.4 (2.4) 7.15 (3.2)
7.73 (3.5) 9.2 (4.2)
COND FAN Propeller Type, Direct Drive
Air Discharge Vertical
Air Qty (CFM) 1880 2200 2730 3170 3155
4050 4050
Motor HP 1/12 1/10 1/5 1/5 1/41/4 1/4
Motor RPM 1100 1100 1100 1100 1100800 800
COND COIL
Face Area (Sq ft) 9.85 9.85 11.49 12.93 21.56 22.63 25.15
Fins per In. 20 20 25 25 25 25 25
Rows 1 1 1 1 1 1 1
Circuits 3 3 4 4 5 6 8
VALVE CONNECT. (In. ID)
Vapor 3/4 3/4 3/4 7/8 7/8 7/8 7/8
24ABR3
Liquid 3/8”
REFRIGERANT TUBES
(In. OD)
Rated Vapor* 3/4 3/4 3/4 7/8 7/8 7/8 1 ---1/8
Liquid 3/8”
*Units are rated with 25 ft (7.6 m) of lineset length. See Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of lineset.
Note: See unit Installation Instruction for proper installation.
Applications in this area are long line. Accessories are required as shown recommended on Long Line Application Guidelines
Applications in this area may have height restrictions that limit allowable total equivalent length, when outdoor unit is below indoor unit See Long Line
Application Guidelines.
3
24ABR3
ACCESSORIES
UNIT SIZE --- VOLTAGE, SERIES
ORDER NUMBER DESCRIPTION
18--- 32 24--- 33 30--- 33 30--- 53 36--- 33 36--- 53 36--- 63 36--- 12 42--- 31 42--- 51 42--- 61 42--- 11 48--- 32 48--- 52 48--- 62 48--- 11 60--- 36 60--- 33 60--- 56 60--- 66 60--- 12
KAACH1201AAA CRANKCASE HTR X X X X S S S S S
KAACH1301AAA CRANKCASE HTR X X X X
KAACH1401AAA CRANKCASE HTR X X X X X X
KAACH1501AAA CRANKCASE HTR X X
KSACY0101AAA CYCLE PROTECTOR X X X X X X X X X X X X X X X X X X X X X
KAAFT0101AAA FREEZE THERMOSTAT X X X X X X X X X X X X X X X X X X X X X
KSAHS1501AAA HARD START (CAP/RELAY) X X X X X X X
KSAHS1701AAA HARD START (CAP/RELAY) X
KSAHI0301R22 HIGH PRESS SW X X X X X X X X X X X X X X X X X X X X X
KSALA0201R22 LOW AMBIENT PSW X X X X X X X X X X X X X X X X X X X X X
KAALP0201R22 LOW PRESS SW X X X X X X X X X X X X X X X X X X X X X
HC32GE234 MOTOR FAN BALL BEARING (230v) X
HC34GE239 MOTOR FAN BALL BEARING (230v) X
HC38GE219 MOTOR FAN BALL BEARING (230v) X X
HC38GE227 MOTOR FAN BALL BEARING (230v) X X
HC40GE226 MOTOR FAN BALL BEARING (230v) X X
HC40GE228 MOTOR FAN BALL BEARING (230v) X X X X X
HC38GE462* MOTOR FAN BALL BEARING (460v) X
HC40GE466 MOTOR FAN BALL BEARING (460v) X
HC40GE467 MOTOR FAN BALL BEARING (460v) X X
KSALA0601AAA MOTORMASTER 230V X X X X X X X X X X X X X
KSALA0701AAA MOTORMASTER 460V X X X X
KAALS0101LLS SOLENOID VALVE X X X X X X X X X X X X X X X X X X X X
KSASH0601COP SOUND BLKT X X X X X X X X X X X X X X X X
KSASH2101COP SOUND BLKT X X X X X
KAACS0201PTC START ASSIST PTC X X X X X X X X
4
KSASF0101AAA SUPPORT FEET X X X X X X X X X X X X X X X X X X X X X
KAATD0101TDR TIME DELAY X X X X X X X X X X X X X X X X X X X X X
KSATX0601HSO TXV X X X X X X X X X X X X
KSATX0701HSO TXV X X X X
KSATX1001HSO TXV X X X X X
KAAWS0101AAA WINTER START X X X X X X X X X X X X X X X X X X X X
X = Accessory S = Standard
*LA01RA324 Fan Blade changeout required (must use with 3 ton 460V ball bearing motor fan) (RCD)
ACCESSORY THERMOSTATS
THERMOSTAT / SUBBASE PKG. DESCRIPTION
TSTATCCPRH01--- B Thermidistat Control --- Programmable / Non--- Programmable Thermostat with Humidity control
TSTATCCPAC01--- B Thermostat --- Auto Changeover, 7--- Day Programmable, _F/_C, 1--- Stage Heat, 1--- Stage Cool
TSTATCCNAC01--- C Thermostat --- Auto Changeover, Non--- Programmable, _F/_C, 1--- Stage Heat, 1--- Stage Cool
TSTATCCBAC01--- B Builder’s Thermostat --- Manual Changeover, Non--- Programmable, _F/_C, 1--- Stage Heat, 1--- Stage Cool
TSTATCCSEN01--- B Outdoor Air Temperature Sensor
TSTATXXBBP01 Backplate for Builder’s Thermostat
TSTATXXNBP01 Backplate for Non--- Programmable Thermostat
TSTATXXPBP01 Backplate for Programmable Thermostat
TSTATXXCNV10 Thermostat Conversion Kit (4 to 5 wires) --- 10 Pack
TP--- PRH--- 01 Programmable Thermidistat
TP--- NRH--- 01 Non--- programmable Thermidistat
TB--- PAC--- 01 Base Series Programmable AC Stat
TB--- NAC--- 01 Base Series Non--- programmable AC Stat
ACCESSORY USAGE GUIDELINE
REQUIRED FOR LOW --- AMBIENT REQUIRED FOR LONG LINE REQUIRED FOR
COOLING APPLICATIONS APPLICATIONS* SEA COAST
ACCESSORY APPLICATIONS
(Below 55°F/12.8_C) (Over 80 ft./24.38 m)
(Within 2 miles/3.22 km)
Ball Bearing Fan Motor Yes{ No No
Compressor Start Assist Capacitor and Relay Yes Yes No
Crankcase Heater Yes Yes No
Evaporator Freeze Thermostat Yes No No
Hard Shut--- Off TXV Yes Yes Yes
Liquid Line Solenoid Valve No No No
Motor Master® or Low--- ambient Pressure Switch Yes No No
Support Feet Recommended No Recommended
Winter Start Control Yes No No
* For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 20 ft. (6.09 m) vertical differential, refer to Residential Split---System Longline
Application Guideline.
{ Additional requirement for Low---Ambient Controller (full modulation feature) MotorMasterr Control.
24ABR3
Usage Guideline: Suggested for all commercial applications.
Required on all units when using MotorMasterr. 8. MotorMasterr Low--Ambient Controller
2. Compressor Start Assist -- Capacitor and Relay A fan--speed control device activated by a temperature sensor,
Start capacitor and relay gives a ”hard” boost to compressor designed to control condenser fan motor speed in response to the
motor at each start up. saturated condensing temperature during operation in cooling
mode only. For outdoor temperatures down to --20_F (--28.9_C),
Usage Guideline: it maintains condensing temperature at 100_F ±10_F (37.8_C ±
Required for single--phase scroll compressors in the --12_C).
following applications: Usage Guideline:
Long--Line A MotorMasterr Low Ambient Controller or
Low--ambient cooling Low--Ambient Pressure Switch must be used when
Suggested for all compressors in areas with a history of cooling operation is used at outdoor temperatures
low voltage problems. below 55_F (12.8_C).
3. Compressor Start Assist — PTC Type Suggested for all commercial applications.
Solid state electrical device which gives a ”soft” boost to the 9. Outdoor Air Temperature Sensor
compressor at each start--up. Designed for use with Carrier Thermostats listed in this
Usage Guideline: publication. This device enables the thermostat to display the
Suggested in installations with marginal power supply. outdoor temperature. This device is also required to enable
special thermostat features such as auxiliary heat lock out.
4. Crankcase Heater
Usage Guideline:
An electric resistance heater which mounts to the base of the
compressor to keep the lubricant warm during off cycles. Suggested for all Carrier thermostats listed in this
Improves compressor lubrication on restart and minimizes the publication.
chance of liquid slugging. 10. Sound Hood
Usage Guideline: Wraparound sound reducing cover for the compressor. Reduces
Required in low--ambient cooling applications. the sound level by about 2 dBA.
Required in Long--Line applications. Usage Guideline:
Suggested in all commercial applications. Suggested when unit is installed closer than 15 ft (4.57 m) to
quiet areas, bedrooms, etc.
5. Cycle Protector
Suggested when unit is installed between two houses less
The cycle protector is designed to prevent compressor short
than 10 ft (3.05 m) apart.
cycling. This control provides an approximate 5--minute delay
after power to the compressor has been interrupted for any 11. Support Feet
reason, including power outage, protector control trip, thermostat Four stick--on plastic feet that raise the unit 4 in. (101.6 mm)
jiggling, or normal cycling. above the mounting pad. This allows sand, dirt, and other debris
6. Evaporator Freeze Thermostat to be flushed from the unit base, minimizing corrosion.
An SPST temperature--actuated switch that stops unit operation Usage Guideline:
when evaporator reaches freeze--up conditions. Suggested in the following applications:
Usage Guideline: Coastal installations.
Required when low--ambient kit has been added. Windy areas or where debris is normally circulating.
7. Low--Ambient Pressure Switch Kit Rooftop installations.
A long--life pressure switch which is mounted to outdoor unit For improved sound ratings.
service valve. It is designed to cycle the outdoor fan motor in
order to maintain head pressure within normal operating limits.
The control will maintain working head pressure at low--ambient
temperatures down to 0_F (--18_C) when properly installed.
Usage Guideline:
5
CHARGING SUBCOOLING (TXV--TYPE EXPANSION DEVICE)
UNIT SIZE --- VOLTAGE, SERIES REQUIRED SUBCOOLING _F (_C)
18 ---32 10 (5.6)
24 ---33 11 (6.1)
30 ---33
30 ---53
10 (5.6)
36 ---33
36 ---53
36 ---63 7 (3.9)
36 ---12
42 ---31
42 ---51
42 ---61 11 (6.1)
42 ---11
48 ---32
48 ---52
48 ---62 8 (4.4)
48 ---11
60 ---36
60 ---56
60 ---66 10 (5.6)
60 ---12
24ABR3
ELECTRICAL DATA
MIN MIN MAX MAX MAX
UNIT SIZE --- OPER VOLTS* COMPR FAN WIRE WIRE LENGTH LENGTH FUSE**
VOLTAGE, V/PH MCA SIZE† SIZE† ft. (m)‡ ft. (m)‡ or CKT
SERIES BRK
MAX MIN LRA RLA FLA 60˚ C 75˚ C 60˚ C 75˚ C AMPS
18--- 32 40.3 7.7 0.5 10.1 14 14 78 (23.8) 74 (22.6) 15
24--- 33 54.0 10.4 0.75 13.8 14 14 57 (17.4) 54 (16.5) 20
30--- 33 68.0 14.1 1.1 18.7 14 14 42 (12.8) 40 (12.2) 30
36--- 33 208/230/1 253 197 77.0 14.4 1.1 19.1 12 12 65 (19.8) 62 (18.9) 30
42--- 31 104.0 19.2 1.4 25.4 10 10 79 (24.1) 75 (22.9) 40
48--- 31 137.0 20.2 1.2 26.4 10 10 76 (23.2) 72 (21.9) 40
60--- 36 141.0 25.3 1.2 32.9 8 8 94 (28.7) 90 (27.4) 50
30--- 53 58.0 7.7 1.1 10.7 14 14 85 (25.9) 81 (24.7) 15
36--- 53 73.0 9.6 1.1 13.1 14 14 69 (21.0) 66 (20.1) 20
42--- 51 208/230/3 253 197 88.0 12.8 1.4 17.4 12 12 83 (25.3) 79 (24.0) 25
48--- 51 83.1 13.1 1.2 17.6 12 12 82 (25.0) 78 (23.8) 25
60--- 56 110.0 15.4 1.2 20.4 10 10 113 (34.4) 108 (32.9) 30
36--- 63 38.0 5.8 0.5 7.7 14 14 236 (71.9) 225 (68.6) 10
42--- 61 44.0 6.0 0.7 8.2 14 14 222 (67.7) 211 (64.3) 15
460/3 506 414
48--- 61 41.0 6.1 0.6 8.2 14 14 222 (67.7) 211 (64.3) 15
60--- 66 52.0 7.1 0.6 9.4 14 14 193 (58.8) 184 (56.1) 15
36--- 12 27.8 4.0 0.5 5.5 14 14 303 (92.4) 288 (87.8) 10
42--- 11 33.0 4.6 0.5 6.3 14 14 260 (79.2) 247 (75.3) 15
575/3 632 518
48--- 11 33.0 4.6 0.5 6.3 14 14 260 (79.2) 247 (75.3) 15
60--- 12 38.9 5.4 0.5 7.3 14 14 227 (69.2) 216 (65.8) 10
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{ If wire is applied at ambient greater than 30˚C (86˚F), consult table 310 ---16 of the NEC (ANSI/NFPA 70). The ampacity of non ---metallic---sheathed cable
(NM), trade name ROMEX, shall be that of 60˚C (140˚F) conditions, per the NEC (ANSI/NFPA 70) Article 336 ---26. If other than uncoated (no ---plated), 60_
or 75˚C (140_ or 167˚F) insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables
of the NEC (ANSI/NFPA 70).
} Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.
** Time ---Delay fuse.
FLA --- Full Load Amps
LRA --- Locked Rotor Amps
MCA --- Minimum Circuit Amps
RLA --- Rated Load Amps
NOTE: Control circuit is 24 ---V on all units and requires external power source. Copper wire must be used from service disconnect to unit. All
motors/compressors contain internal overload protection.
6
A--WEIGHTED SOUND LEVEL
STANDARD TYPICAL OCTAVE BAND SPECTRUM (dB, without tone adjustment)
UNIT SIZE ---
RATING
VOLTAGE, SERIES 125 250 500 1000 2000 4000 8000
(dBA)
18--- 32 76 51.0 61.5 67.0 68.5 66.0 61.0 55.5
24--- 33 76 54.0 64.0 69.0 71.0 69.0 64.5 59.0
30--- 33
76 54.5 64.5 70.0 70.5 67.5 63.0 57.0
30--- 53
36--- 33
36--- 53
78 58.5 69.5 72.0 73.5 68.5 65.0 59.5
36--- 63
36--- 12
42--- 31
42--- 51
79 60.5 68.5 71.5 75.5 69.5 65.5 66.0
42--- 61
42--- 11
48--- 32
48--- 52
80 51.5 63.5 66.0 76.0 68.0 66.5 63.5
48--- 62
48--- 11
60--- 36
60--- 56
80 54.5 63.5 71.5 74.5 67.0 68.0 68.5
60--- 66
24ABR3
60--- 12
7
24ABR3
DIMENSIONS
8
DIMENSIONS
9
24ABR3
24ABR3
CLEARANCES
Clearances (various examples)
Wall Wall
6”
(152.4) 24”
(609.6)
24” Service
12”
(609.6) (304.8)
Service
12” 6”
Wall
(304.8) (152.4)
12”
(304.8)
12”
(304.8)
10
Wall
24” 24” 24”
(609.6) (609.6) (609.6)
Service Service Service
Note: Numbers in ( ) = mm
COMBINATION RATINGS
FACTORY SEER
UNIT SIZE --- VOLTAGE, INDOOR TOTAL CAP. FURNACE
SUPPLIED STANDARD EER
SERIES MODEL BTUH TDR{ MODEL
ENHANCEMENT RATING
*CAR**1814A** 17,100 TXV 13.00 11.20
CAR**1814A** 17,000 TDR&TXV 14.00 12.00 58CV(A,X)070---12
CAR**1814A** 17,200 TDR&TXV 14.50 12.20 58PH*045---08
24ABR3
CNRH*2417A** 17,400 TDR&TXV 14.00 12.00 58MV(B,C)080---14
CNRH*2417A** 17,400 TDR&TXV 14.00 12.00 58MVB040---14
CNRH*2417A** 17,700 TDR&TXV 14.50 12.20 58PH*045---08
24---33
CAR**3014A** 22,800 TDR&TXV 14.00 12.00 58CV(A,X)070---12
CAR**3014A** 23,800 TDR&TXV 14.25 12.00 58PH*045---08
CAR**3014A** 23,000 TXV 13.00 11.20
11
COMBINATION RATINGS CONTINUED
FACTORY SEER
UNIT SIZE --- VOLTAGE, INDOOR TOTAL CAP. FURNACE
SUPPLIED STANDARD EER
SERIES MODEL BTUH TDR{ MODEL
ENHANCEMENT RATING
12
COMBINATION RATINGS CONTINUED
FACTORY SEER
UNIT SIZE --- VOLTAGE, INDOOR TOTAL CAP. FURNACE
SUPPLIED STANDARD EER
SERIES MODEL BTUH TDR{ MODEL
ENHANCEMENT RATING
CSRH*3012A** 23,000 TDR&TXV 14.00 12.00 58MVB040---14
CSRH*3012A** 23,600 TDR&TXV 14.25 12.00 58PH*045---08
CSRH*3012A** 23,200 TXV 13.00 11.20
24ABR3
CAP**3617A** 28,600 TDR&TXV 14.00 12.00 58PH*070---16
13
COMBINATION RATINGS CONTINUED
FACTORY SEER
UNIT SIZE --- VOLTAGE, INDOOR TOTAL CAP. FURNACE
SUPPLIED STANDARD EER
SERIES MODEL BTUH TDR{ MODEL
ENHANCEMENT RATING
CNRH*3617A** 27,400 TDR&TXV 14.00 12.00 58CV(A,X)110---20
CNRH*3617A** 27,400 TDR&TXV 14.00 12.00 58CV(A,X)135---22
CNRH*3617A** 27,400 TDR&TXV 14.00 12.00 58CV(A,X)155---22
CNRH*3617A** 27,600 TDR&TXV 14.00 12.00 58MV(B,C)060---14
CNRH*3617A** 27,200 TDR&TXV 14.00 12.00 58MV(B,C)080---14
CNRH*3617A** 27,400 TDR&TXV 14.00 12.00 58MV(B,C)080---20
CNRH*3617A** 27,200 TDR&TXV 14.00 12.00 58MV(B,C)100---20
CNRH*3617A** 27,400 TDR&TXV 14.00 12.00 58MV(B,C)120---20
CNRH*3617A** 27,400 TDR&TXV 14.00 12.00 58MVB040---14
CNRH*3617A** 27,600 TXV 13.00 11.20
14
COMBINATION RATINGS CONTINUED
FACTORY SEER
UNIT SIZE --- VOLTAGE, INDOOR TOTAL CAP. FURNACE
SUPPLIED STANDARD EER
SERIES MODEL BTUH TDR{ MODEL
ENHANCEMENT RATING
*CAR**3617A** 33,800 TXV 13.00 11.20
24ABR3
CAR**4221A** 34,000 TDR&TXV 14.00 12.00 58CV(A,X)110---20
CAR**4221A** 34,000 TDR&TXV 14.00 12.00 58MV(B,C)080---14
CAR**4221A** 33,800 TDR&TXV 14.00 12.00 58MV(B,C)080---20
CAR**4221A** 34,000 TDR&TXV 14.00 12.00 58MV(B,C)100---20
CAR**4221A** 35,200 TDR&TXV 14.00 12.00 58PH*090---16
CAR**4221A** 35,400 TDR&TXV 14.00 12.00 58PH*110---20
CAR**4221A** 34,200 TXV 13.00 11.20
15
COMBINATION RATINGS CONTINUED
FACTORY SEER
UNIT SIZE --- VOLTAGE, INDOOR TOTAL CAP. FURNACE
SUPPLIED STANDARD EER
SERIES MODEL BTUH TDR{ MODEL
ENHANCEMENT RATING
CNRV*3617A** 33,600 TDR&TXV 13.50 11.70 58MV(B,C)060---14
CNRV*3617A** 34,400 TDR&TXV 13.50 11.70 58PH*070---16
CNRV*3617A** 33,800 TXV 13.00 11.20
16
COMBINATION RATINGS CONTINUED
FACTORY SEER
UNIT SIZE --- VOLTAGE, INDOOR TOTAL CAP. FURNACE
SUPPLIED STANDARD EER
SERIES MODEL BTUH TDR{ MODEL
ENHANCEMENT RATING
*CAR**4221A** 40,500 TXV 13.00 11.00
CAR**4221A** 40,500 TDR&TXV 13.50 11.20 58CV(A,X)110---20
CAR**4221A** 40,000 TDR&TXV 13.50 11.20 58MVB080---14
CAR**4221A** 40,000 TDR&TXV 13.50 11.20 58MVB080---20
CAR**4221A** 40,000 TDR&TXV 13.50 11.20 58MVB100---20
CAR**4221A** 40,000 TDR&TXV 13.50 11.70 58PH*090---16
CAR**4221A** 40,000 TDR&TXV 14.00 11.70 58PH*110---20
24ABR3
CAR**4817A** 40,500 TXV 13.00 11.00
17
COMBINATION RATINGS CONTINUED
FACTORY SEER
UNIT SIZE --- VOLTAGE, INDOOR TOTAL CAP. FURNACE
SUPPLIED STANDARD EER
SERIES MODEL BTUH TDR{ MODEL
ENHANCEMENT RATING
CNRV*4221A** 40,500 TXV 13.00 11.00
18
FACTORY SEER
UNIT SIZE --- VOLTAGE, INDOOR TOTAL CAP. FURNACE
SUPPLIED STANDARD EER
SERIES MODEL BTUH TDR{ MODEL
ENHANCEMENT RATING
CAR**6021A** 46,500 TDR&TXV 13.50 11.20 58MVB080---20
CAR**6021A** 46,500 TDR&TXV 13.50 11.20 58MVB100---20
CAR**6021A** 46,500 TDR&TXV 13.75 11.70 58PH*090---16
CAR**6021A** 46,500 TDR&TXV 14.00 12.00 58PH*110---20
CAR**6021A** 47,500 TXV 13.00 11.00
24ABR3
CNRH*4821A** 45,500 TDR&TXV 13.20 11.00 58MVB080---20
CNRH*4821A** 45,500 TDR&TXV 13.20 11.00 58MVB100---20
CNRH*4821A** 45,500 TDR&TXV 13.20 11.00 58MVB120---20
CNRH*4821A** 45,500 TDR&TXV 13.20 11.50 58PH*090---16
CNRH*4821A** 45,500 TDR&TXV 13.50 11.70 58PH*110---20
CNRH*4821A** 45,500 TDR&TXV 13.50 11.70 58PH*135---20
CNRH*4821A** 46,500 TXV 13.00 11.00
19
COMBINATION RATINGS CONTINUED
FACTORY SEER
UNIT SIZE --- VOLTAGE, INDOOR TOTAL CAP. FURNACE
SUPPLIED STANDARD EER
SERIES MODEL BTUH TDR{ MODEL
ENHANCEMENT RATING
CSRH*6012A** 47,000 TDR&TXV 14.00 11.50 58CV(A,X)135---22
CSRH*6012A** 47,000 TDR&TXV 14.00 11.50 58CV(A,X)155---22
CSRH*6012A** 46,500 TDR&TXV 13.50 11.20 58MVB080---20
CSRH*6012A** 47,000 TDR&TXV 13.50 11.20 58MVB100---20
CSRH*6012A** 47,000 TDR&TXV 13.50 11.20 58MVB120---20
CSRH*6012A** 47,000 TDR&TXV 13.75 11.70 58PH*090---16
48---32 CSRH*6012A** 47,000 TDR&TXV 14.00 12.00 58PH*110---20
48---52 CSRH*6012A** 47,000 TDR&TXV 13.75 11.70 58PH*135---20
48---62 CSRH*6012A** 48,000 TXV 13.00 11.00
48---11
FA4CN(F,C)048 47,000 TDR&TXV 13.00 11.00
FA4CN(F,C)060 48,000 TDR&TXV 13.00 11.00
FC4DN(F,B)048 47,500 TDR&TXV 13.50 11.20
FC4DN(F,B)060 48,500 TDR&TXV 14.00 11.50
FK4DNB006 47,500 TDR&TXV 14.50 11.70
FK4DNF005 47,000 TDR&TXV 14.00 11.50
*CAR**6024A** 56,000 TXV 11.00
24ABR3
20
DETAILED COOLING CAPACITIES#
CONDENSER ENTERING AIR TEMPERATURES deg _F (°C)
EVAPORATOR AIR
75 (23.9) 85 (29.4) 95 (35) 105 (40.6) 115 (46.1) 125 (51.7)
Capacity MBtuh{ Total Capacity MBtuh{ Total Capacity MBtuh{ Total Capacity MBtuh{ Total Capacity MBtuh{ Total Capacity MBtuh{ Total
CFM EWB
System System System System System System
_F (_C) Total Sens} Total Sens} Total Sens} Total Sens} Total Sens} Total Sens}
KW** KW** KW** KW** KW** KW**
24ABR318(A,G)*2 Outdoor Section With CAR**1814A Indoor Section
72 (22.2) 20.03 10.14 1.28 19.30 9.88 1.40 18.55 9.61 1.53 17.76 9.33 1.69 16.91 9.04 1.87 16.00 8.73 2.08
67 (19.4) 18.20 12.49 1.27 17.52 12.23 1.39 16.82 11.95 1.52 16.10 11.67 1.68 15.33 11.37 1.86 14.48 11.05 2.06
525
62 (16.7) 16.70 14.83 1.26 16.09 14.55 1.38 15.48 14.25 1.51 14.86 13.93 1.67 14.24 14.24 1.84 13.59 13.59 2.05
57 (13.9) 16.40 16.40 1.26 15.89 15.89 1.38 15.37 15.37 1.51 14.83 14.83 1.67 14.24 14.24 1.84 13.59 13.59 2.05
72 (22.2) 20.37 10.66 1.31 19.60 10.39 1.43 18.82 10.12 1.57 18.00 9.84 1.72 17.13 9.54 1.90 16.18 9.22 2.11
67 (19.4) 18.52 13.33 1.30 17.82 13.05 1.42 17.10 12.78 1.55 16.35 12.49 1.71 15.55 12.18 1.89 14.69 11.85 2.10
600
62 (16.7) 17.13 15.91 1.30 16.55 16.39 1.41 15.97 15.97 1.55 15.39 15.39 1.70 14.76 14.76 1.88 14.07 14.07 2.09
57 (13.9) 17.06 17.06 1.30 16.52 16.52 1.41 15.97 15.97 1.55 15.39 15.39 1.70 14.76 14.76 1.88 14.07 14.07 2.09
72 (22.2) 20.61 11.15 1.34 19.82 10.87 1.46 19.01 10.60 1.60 18.17 10.32 1.75 17.28 10.02 1.93 16.31 9.69 2.14
67 (19.4) 18.77 14.12 1.33 18.04 13.84 1.45 17.31 13.56 1.59 16.54 13.26 1.74 15.73 12.95 1.92 14.85 12.60 2.13
675
62 (16.7) 17.61 17.61 1.33 17.04 17.04 1.45 16.45 16.45 1.58 15.84 15.84 1.73 15.18 15.18 1.91 14.46 14.46 2.12
57 (13.9) 17.61 17.61 1.33 17.04 17.04 1.45 16.46 16.46 1.58 15.84 15.84 1.73 15.18 15.18 1.91 14.46 14.46 2.12
Cooling Indoor
Capacity Power Furnace Model
Model
*CAR**1814A** 1.00 1.00
CAR**2414A** 1.02 1.02
CAR**2417A** 1.02 1.02
CNRF*2418A** 1.02 1.02
CNRH*2417A** 1.02 1.02
CNRV*1814A** 1.00 1.00
CNRV*2414A** 1.02 1.02
CNRV*2417A** 1.03 1.03
CSRH*2412A** 1.02 1.02
FA4CN(F,C)018 1.01 1.01
FA4CN(F,C)024 1.01 1.01
FC4DNF018 1.03 0.96
21
FC4DNF024 1.04 0.97
FF1ENE018 0.99 0.99
FF1ENE024 1.02 0.99
FK4DNF001 1.02 0.96
FK4DNF002 0.99 0.92
CAR**1814A** 0.99 0.93 58CV(A,X)070--- 12
CAR**2414A** 1.01 0.94 58CV(A,X)070--- 12
CNRH*2417A** 1.02 0.95 58CV(A,X)070--- 12
CNRV*1814A** 1.01 0.94 58CV(A,X)070--- 12
CNRV*2414A** 1.02 0.95 58CV(A,X)070--- 12
CSRH*2412A** 1.02 0.95 58CV(A,X)070--- 12
CAR**2417A** 1.02 0.95 58CV(A,X)090--- 16
CNRH*2417A** 1.02 0.96 58CV(A,X)090--- 16
CNRV*2417A** 1.02 0.96 58CV(A,X)090--- 16
CSRH*2412A** 1.02 0.96 58CV(A,X)090--- 16
CAR**2417A** 1.02 0.95 58MV(B,C)060--- 14
CNRH*2417A** 1.02 0.95 58MV(B,C)060--- 14
CNRV*2417A** 1.02 0.95 58MV(B,C)060--- 14
CSRH*2412A** 1.02 0.95 58MV(B,C)060--- 14
CNRH*2417A** 1.02 0.95 58MV(B,C)080--- 14
CSRH*2412A** 1.02 0.95 58MV(B,C)080--- 14
CNRH*2417A** 1.02 0.95 58MVB040--- 14
CSRH*2412A** 1.03 0.96 58MVB040--- 14
CAR**1814A** 1.01 0.92 58PH*045--- 08
CAR**2414A** 1.04 0.95 58PH*045--- 08
CNRH*2417A** 1.04 0.95 58PH*045--- 08
CNRV*1814A** 1.01 0.92 58PH*045--- 08
CNRV*2414A** 1.04 0.95 58PH*045--- 08
CSRH*2412A** 1.04 0.95 58PH*045--- 08
See notes on pg. 26
24ABR3
24ABR3
22
FA4CN(F,C)024 0.99 0.99 CSRH*2412A** 1.02 0.95 58MV(B,C)060--- 14
FA4CN(F,C)030 1.00 1.00 CSRH*3012A** 1.02 0.95 58MV(B,C)060--- 14
FC4DNF024 1.01 0.94 CNRH*2417A** 0.99 0.93 58MV(B,C)080--- 14
FC4DNF030 1.02 0.95 CNRH*3017A** 1.00 0.93 58MV(B,C)080--- 14
FF1ENE024 0.98 0.98 CSRH*2412A** 1.00 0.93 58MV(B,C)080--- 14
FF1ENE030 1.00 1.00 CSRH*3012A** 1.00 0.93 58MV(B,C)080--- 14
FK4DN(B,F)003 1.01 0.94 CNRH*2417A** 0.98 0.92 58MV(B,C)080--- 20
FK4DNF001 1.00 0.93 CNRH*3017A** 0.99 0.93 58MV(B,C)080--- 20
FK4DNF002 0.99 0.93 CSRH*2412A** 1.00 0.93 58MV(B,C)080--- 20
CAR**2414A** 0.99 0.93 58CV(A,X)070--- 12 CSRH*3012A** 0.99 0.93 58MV(B,C)080--- 20
CAR**3014A** 0.99 0.93 58CV(A,X)070--- 12 CNRH*2417A** 0.99 0.93 58MV(B,C)100--- 20
CNRH*2417A** 0.99 0.93 58CV(A,X)070--- 12 CNRH*3017A** 1.00 0.93 58MV(B,C)100--- 20
CNRH*3017A** 1.00 0.93 58CV(A,X)070--- 12 CSRH*2412A** 1.01 0.94 58MV(B,C)100--- 20
CNRV*2414A** 0.99 0.93 58CV(A,X)070--- 12 CSRH*3012A** 1.00 0.93 58MV(B,C)100--- 20
CNRV*3014A** 0.99 0.93 58CV(A,X)070--- 12 CNRH*2417A** 1.00 0.93 58MV(B,C)120--- 20
CSRH*2412A** 1.00 0.93 58CV(A,X)070--- 12 CNRH*3017A** 1.00 0.93 58MV(B,C)120--- 20
CSRH*3012A** 1.00 0.93 58CV(A,X)070--- 12 CSRH*2412A** 1.01 0.94 58MV(B,C)120--- 20
CAR**2417A** 0.99 0.93 58CV(A,X)090--- 16 CSRH*3012A** 1.01 0.94 58MV(B,C)120--- 20
CAR**3017A** 1.00 0.93 58CV(A,X)090--- 16 CNRH*2417A** 0.99 0.93 58MVB040--- 14
CNRH*2417A** 0.99 0.93 58CV(A,X)090--- 16 CNRH*3017A** 1.00 0.93 58MVB040--- 14
CNRH*3017A** 1.00 0.93 58CV(A,X)090--- 16 CSRH*2412A** 1.01 0.94 58MVB040--- 14
CNRV*2417A** 0.99 0.93 58CV(A,X)090--- 16 CSRH*3012A** 1.00 0.93 58MVB040--- 14
CNRV*3017A** 1.00 0.93 58CV(A,X)090--- 16 CAR**2414A** 1.03 0.96 58PH*045--- 08
CSRH*2412A** 1.01 0.94 58CV(A,X)090--- 16 CAR**3014A** 1.03 0.97 58PH*045--- 08
CSRH*3012A** 1.01 0.94 58CV(A,X)090--- 16 CNRH*2417A** 1.03 0.96 58PH*045--- 08
CNRH*2417A** 0.99 0.93 58CV(A,X)110--- 20 CNRH*3017A** 1.03 0.96 58PH*045--- 08
CNRH*3017A** 1.00 0.93 58CV(A,X)110--- 20 CNRV*2414A** 1.03 0.96 58PH*045--- 08
CSRH*2412A** 1.01 0.94 58CV(A,X)110--- 20 CNRV*3014A** 1.03 0.96 58PH*045--- 08
CSRH*3012A** 1.01 0.94 58CV(A,X)110--- 20 CSRH*2412A** 1.03 0.96 58PH*045--- 08
CNRH*2417A** 0.99 0.93 58CV(A,X)135--- 22
DETAILED COOLING CAPACITIES# CONTINUED
CONDENSER ENTERING AIR TEMPERATURES deg _F (°C)
EVAPORATOR AIR
75 (23.9) 85 (29.4) 95 (35) 105 (40.6) 115 (46.1) 125 (51.7)
EWB Capacity MBtuh{ Total Sys- Capacity MBtuh{ Total Sys- Capacity MBtuh{ Total Sys- Capacity MBtuh{ Total Sys- Capacity MBtuh{ Total Sys- Capacity MBtuh{ Total Sys-
CFM
_F (_C) Total Sens} tem KW** Total Sens} tem KW** Total Sens} tem KW** Total Sens} tem KW** Total Sens} tem KW** Total Sens} tem KW**
24ABR330(A,G)*3 Outdoor Section With CAR**3014A Indoor Section
72 (22.2) 32.45 16.76 2.15 31.35 16.36 2.35 30.18 15.94 2.56 28.96 15.51 2.80 27.68 15.06 3.07 26.34 14.59 3.39
67 (19.4) 29.51 20.72 2.14 28.47 20.31 2.33 27.37 19.88 2.55 26.21 19.42 2.79 25.00 18.95 3.07 23.73 18.46 3.38
875
62 (16.7) 27.11 24.65 2.11 26.19 24.20 2.31 25.21 23.71 2.53 24.21 24.09 2.78 23.26 23.26 3.05 22.26 22.26 3.37
57 (13.9) 26.72 26.72 2.11 25.94 25.94 2.31 25.10 25.10 2.53 24.20 24.20 2.78 23.26 23.26 3.05 22.26 22.26 3.37
72 (22.2) 32.95 17.60 2.20 31.81 17.20 2.39 30.61 16.78 2.61 29.35 16.34 2.85 28.04 15.89 3.12 26.67 15.42 3.43
67 (19.4) 30.00 22.10 2.19 28.93 21.68 2.38 27.80 21.24 2.60 26.61 20.78 2.84 25.37 20.30 3.12 24.08 19.79 3.43
1000
62 (16.7) 27.82 26.39 2.17 26.91 26.91 2.37 26.04 26.04 2.59 25.10 25.10 2.83 24.11 24.11 3.11 23.07 23.07 3.43
57 (13.9) 27.76 27.76 2.17 26.93 26.93 2.37 26.04 26.04 2.59 25.10 25.10 2.83 24.11 24.11 3.11 23.07 23.07 3.43
72 (22.2) 33.31 18.40 2.25 32.14 17.99 2.44 30.91 17.57 2.65 29.62 17.13 2.89 28.28 16.68 3.16 26.89 16.21 3.47
67 (19.4) 30.37 23.40 2.24 29.28 22.97 2.43 28.12 22.53 2.65 26.92 22.06 2.89 25.66 21.56 3.17 24.35 21.05 3.48
1125
62 (16.7) 28.61 28.61 2.22 27.74 27.74 2.42 26.81 26.81 2.64 25.83 25.83 2.89 24.80 24.80 3.16 23.72 23.72 3.48
57 (13.9) 28.62 28.62 2.22 27.74 27.74 2.42 26.82 26.82 2.64 25.84 25.84 2.89 24.81 24.81 3.16 23.73 23.73 3.48
Cooling Indoor Cooling Indoor Cooling Indoor
Capacity Power Furnace Model Capacity Power Furnace Model Capacity Power Furnace Model
Model Model Model
*CAR**3014A** 1.00 1.00 CSRH*3012A** 0.99 0.93 58CV(A,X)110--- 20 CSRH*3612A** 0.99 0.93 58MVB040--- 14
CAR**3017A** 1.00 1.00 CSRH*3612A** 0.99 0.93 58CV(A,X)110--- 20 CAP**3017A** 1.04 0.97 58PH*070--- 16
CAR**3614A** 1.00 1.00 CNRH*3017A** 0.99 0.93 58CV(A,X)135--- 22 CAP**3617A** 1.04 0.97 58PH*070--- 16
CAR**3617A** 1.00 1.00 CNRH*3617A** 0.99 0.93 58CV(A,X)135--- 22 CNPH*3017A** 1.04 0.97 58PH*070--- 16
CAR**3621A** 1.00 1.00 CSRH*3012A** 0.99 0.93 58CV(A,X)135--- 22 CNPH*3617A** 1.04 0.97 58PH*070--- 16
CNRF*3618A** 1.00 1.00 CSRH*3612A** 0.99 0.93 58CV(A,X)135--- 22 CNPV*3017A** 1.04 0.97 58PH*070--- 16
CNRH*3017A** 1.00 1.00 CNRH*3017A** 0.99 0.93 58CV(A,X)155--- 22 CNPV*3617A** 1.04 0.97 58PH*070--- 16
CNRH*3617A** 1.00 1.00 CNRH*3617A** 0.99 0.93 58CV(A,X)155--- 22 CSPH*3012A** 1.04 0.97 58PH*070--- 16
CNRV*3014A** 1.00 1.00 CSRH*3012A** 0.99 0.93 58CV(A,X)155--- 22 CSPH*3612A** 1.04 0.97 58PH*070--- 16
CNRV*3017A** 1.00 1.00 CSRH*3612A** 0.99 0.93 58CV(A,X)155--- 22 CAP**3621A** 1.05 0.96 58PH*090--- 16
CNRV*3617A** 1.00 1.00 CAR**3017A** 0.99 0.93 58MV(B,C)060--- 14 CNPH*3017A** 1.04 0.97 58PH*090--- 16
CNRV*3621A** 1.00 1.00 CAR**3617A** 1.00 0.93 58MV(B,C)060--- 14 CNPH*3617A** 1.04 0.97 58PH*090--- 16
CSRH*3012A** 1.00 1.00 CNRH*3017A** 1.00 0.93 58MV(B,C)060--- 14 CNPV*3621A** 1.04 0.97 58PH*090--- 16
23
CSRH*3612A** 0.99 0.99 CNRH*3617A** 1.00 0.93 58MV(B,C)060--- 14 CSPH*3012A** 1.04 0.97 58PH*090--- 16
FA4CN(F,C)030 0.99 0.99 CNRV*3017A** 1.00 0.93 58MV(B,C)060--- 14 CSPH*3612A** 1.05 0.96 58PH*090--- 16
FA4CN(F,C)036 1.00 1.00 CNRV*3617A** 1.00 0.93 58MV(B,C)060--- 14 See notes on pg. 26
FC4DN(F,B)036 1.02 0.95 CSRH*3012A** 1.00 0.93 58MV(B,C)060--- 14
FC4DNF030 1.01 0.94 CSRH*3612A** 0.99 0.93 58MV(B,C)060--- 14
FF1ENE030 0.99 0.99 CAR**3621A** 1.02 0.95 58MV(B,C)080--- 14
FF1ENE036 1.00 1.00 CNRH*3017A** 0.99 0.92 58MV(B,C)080--- 14
FK4DN(B,F)003 1.01 0.94 CNRH*3617A** 0.99 0.92 58MV(B,C)080--- 14
FK4DN(B,F)005 1.04 0.97 CNRV*3621A** 0.99 0.92 58MV(B,C)080--- 14
FK4DNF001 0.99 0.93 CSRH*3012A** 0.99 0.93 58MV(B,C)080--- 14
FK4DNF002 1.01 0.94 CSRH*3612A** 0.99 0.93 58MV(B,C)080--- 14
CAR**3014A** 0.99 0.92 58CV(A,X)070--- 12 CAR**3621A** 1.02 0.95 58MV(B,C)080--- 20
CAR**3614A** 0.99 0.93 58CV(A,X)070--- 12 CNRH*3017A** 0.99 0.93 58MV(B,C)080--- 20
CNRH*3017A** 0.99 0.93 58CV(A,X)070--- 12 CNRH*3617A** 0.99 0.93 58MV(B,C)080--- 20
CNRH*3617A** 0.99 0.93 58CV(A,X)070--- 12 CNRV*3621A** 0.99 0.93 58MV(B,C)080--- 20
CNRV*3014A** 0.99 0.92 58CV(A,X)070--- 12 CSRH*3012A** 1.00 0.93 58MV(B,C)080--- 20
CSRH*3012A** 0.99 0.93 58CV(A,X)070--- 12 CSRH*3612A** 0.99 0.93 58MV(B,C)080--- 20
CSRH*3612A** 0.99 0.93 58CV(A,X)070--- 12 CAR**3621A** 1.02 0.95 58MV(B,C)100--- 20
CAR**3017A** 0.99 0.93 58CV(A,X)090--- 16 CNRH*3017A** 0.99 0.92 58MV(B,C)100--- 20
CAR**3617A** 0.99 0.93 58CV(A,X)090--- 16 CNRH*3617A** 0.99 0.92 58MV(B,C)100--- 20
CNRH*3017A** 0.99 0.93 58CV(A,X)090--- 16 CNRV*3621A** 0.99 0.92 58MV(B,C)100--- 20
CNRH*3617A** 0.99 0.93 58CV(A,X)090--- 16 CSRH*3012A** 0.99 0.93 58MV(B,C)100--- 20
CNRV*3017A** 0.99 0.93 58CV(A,X)090--- 16 CSRH*3612A** 0.99 0.93 58MV(B,C)100--- 20
CNRV*3617A** 0.99 0.93 58CV(A,X)090--- 16 CNRH*3017A** 0.99 0.93 58MV(B,C)120--- 20
CSRH*3012A** 0.99 0.93 58CV(A,X)090--- 16 CNRH*3617A** 0.99 0.93 58MV(B,C)120--- 20
CSRH*3612A** 0.99 0.93 58CV(A,X)090--- 16 CSRH*3012A** 1.00 0.93 58MV(B,C)120--- 20
CAR**3621A** 1.00 0.93 58CV(A,X)110--- 20 CSRH*3612A** 0.99 0.93 58MV(B,C)120--- 20
CNRH*3017A** 0.99 0.93 58CV(A,X)110--- 20 CNRH*3017A** 0.99 0.93 58MVB040--- 14
CNRH*3617A** 0.99 0.93 58CV(A,X)110--- 20 CNRH*3617A** 0.99 0.93 58MVB040--- 14
CNRV*3621A** 0.99 0.93 58CV(A,X)110--- 20 CSRH*3012A** 0.99 0.93 58MVB040--- 14
24ABR3
24ABR3
24
CSRH*4812A** 1.01 1.01 CNRH*4821A** 1.01 0.99 58MVB040--- 14 CNRH*4821A** 1.00 0.96 58PH*070--- 16
FA4CN(F,C)042 1.01 1.01 CNRV*4824A** 1.01 0.99 58MVB040--- 14 CSRH*4212A** 0.99 0.94 58PH*070--- 16
FA4CN(F,C)048 1.02 1.02 CSRH*4212A** 0.99 0.97 58MVB040--- 14 CSRH*4812A** 1.00 0.96 58PH*070--- 16
FC4DN(F,B)042 1.02 1.01 CSRH*4812A** 1.00 0.98 58MVB040--- 14 CAR**4221A** 0.99 0.93 58PH*090--- 16
FC4DN(F,B)048 1.05 1.00 CAR**4817A** 0.99 0.97 58MVB060--- 14 CAR**4821A** 1.00 0.92 58PH*090--- 16
FK4DNB006 1.05 1.00 CNRH*4221A** 0.99 0.97 58MVB060--- 14 CNRH*4221A** 0.99 0.93 58PH*090--- 16
FK4DNF003 0.99 0.94 CNRH*4821A** 1.01 0.99 58MVB060--- 14 CNRH*4821A** 1.00 0.92 58PH*090--- 16
FK4DNF005 1.04 0.99 CSRH*4212A** 0.99 0.97 58MVB060--- 14 CNRV*4221A** 0.99 0.93 58PH*090--- 16
CNRH*4221A** 0.99 0.97 58CV(A,X)070--- 12 CSRH*4812A** 1.00 0.98 58MVB060--- 14 CNRV*4821A** 1.00 0.92 58PH*090--- 16
CNRH*4821A** 1.01 0.99 58CV(A,X)070--- 12 CAR**4221A** 0.99 0.97 58MVB080--- 14 CSRH*4212A** 0.99 0.93 58PH*090--- 16
CSRH*4212A** 0.99 0.97 58CV(A,X)070--- 12 CAR**4821A** 1.00 0.98 58MVB080--- 14 CSRH*4812A** 1.00 0.92 58PH*090--- 16
CSRH*4812A** 1.00 0.98 58CV(A,X)070--- 12 CNRH*4221A** 0.99 0.97 58MVB080--- 14 CAR**4221A** 0.99 0.93 58PH*110--- 20
CAR**4817A** 0.99 0.94 58CV(A,X)090--- 16 CNRH*4821A** 1.01 0.99 58MVB080--- 14 CAR**4821A** 1.00 0.92 58PH*110--- 20
CNRH*4221A** 0.99 0.94 58CV(A,X)090--- 16 CNRV*4221A** 0.99 0.97 58MVB080--- 14 CNRH*4221A** 0.99 0.93 58PH*110--- 20
CNRH*4821A** 1.01 0.97 58CV(A,X)090--- 16 CNRV*4821A** 1.01 0.99 58MVB080--- 14 CNRH*4821A** 1.00 0.92 58PH*110--- 20
CSRH*4212A** 0.99 0.94 58CV(A,X)090--- 16 CSRH*4212A** 0.99 0.97 58MVB080--- 14 CNRV*4221A** 0.99 0.93 58PH*110--- 20
CSRH*4812A** 1.00 0.96 58CV(A,X)090--- 16 CSRH*4812A** 1.00 0.98 58MVB080--- 14 CNRV*4821A** 1.00 0.92 58PH*110--- 20
CAR**4221A** 1.00 0.98 58CV(A,X)110--- 20 CAR**4221A** 0.99 0.97 58MVB080--- 20 CSRH*4212A** 0.99 0.93 58PH*110--- 20
CAR**4821A** 1.01 0.97 58CV(A,X)110--- 20 CAR**4821A** 1.01 0.99 58MVB080--- 20 CSRH*4812A** 1.00 0.92 58PH*110--- 20
CNRH*4221A** 0.99 0.94 58CV(A,X)110--- 20 CNRH*4221A** 0.99 0.97 58MVB080--- 20 CAR**4224A** 0.99 0.93 58PH*135--- 20
CNRH*4821A** 1.01 0.97 58CV(A,X)110--- 20 CNRH*4821A** 1.01 0.99 58MVB080--- 20 CAR**4824A** 1.00 0.92 58PH*135--- 20
CNRV*4221A** 0.99 0.94 58CV(A,X)110--- 20 CNRV*4221A** 0.99 0.97 58MVB080--- 20 CNRH*4221A** 0.99 0.93 58PH*135--- 20
CNRV*4821A** 1.01 0.97 58CV(A,X)110--- 20 CNRV*4821A** 1.01 0.99 58MVB080--- 20 CNRH*4821A** 1.00 0.92 58PH*135--- 20
CSRH*4212A** 0.99 0.94 58CV(A,X)110--- 20 CSRH*4212A** 0.99 0.97 58MVB080--- 20 CNRV*4824A** 1.00 0.92 58PH*135--- 20
CSRH*4812A** 1.00 0.96 58CV(A,X)110--- 20 CSRH*4812A** 1.00 0.98 58MVB080--- 20 CSRH*4212A** 0.99 0.93 58PH*135--- 20
CAR**4224A** 1.00 0.96 58CV(A,X)135--- 22 CAR**4221A** 0.99 0.97 58MVB100--- 20 CSRH*4812A** 1.00 0.92 58PH*135--- 20
CAR**4824A** 1.01 0.97 58CV(A,X)135--- 22 CAR**4821A** 1.01 0.97 58MVB100--- 20 See notes on pg. 26
CNRH*4221A** 0.99 0.94 58CV(A,X)135--- 22 CNRH*4221A** 0.99 0.94 58MVB100--- 20
CNRH*4821A** 1.01 0.97 58CV(A,X)135--- 22 CNRH*4821A** 1.01 0.97 58MVB100--- 20
CNRV*4824A** 1.01 0.97 58CV(A,X)135--- 22 CNRV*4221A** 0.99 0.94 58MVB100--- 20
DETAILED COOLING CAPACITIES# CONTINUED
CONDENSER ENTERING AIR TEMPERATURES deg _F (°C)
EVAPORATOR AIR
75 (23.9) 85 (29.4) 95 (35) 105 (40.6) 115 (46.1) 125 (51.7)
Capacity MBtuh{ Total Capacity MBtuh{ Total Capacity MBtuh{ Total Capacity MBtuh{ Total Capacity MBtuh{ Total Capacity MBtuh{ Total
CFM EWB
System System System System System System
_F (_C) Total Sens} Total Sens} Total Sens} Total Sens} Total Sens} Total Sens}
KW** KW** KW** KW** KW** KW**
24ABR348(A,G)*1 Outdoor Section With CAR**4821A** Indoor Section
72 (22.2) 54.29 28.34 3.42 52.13 27.51 3.71 49.95 26.68 4.04 47.78 25.86 4.41 45.58 25.04 4.82 43.34 24.21 5.27
67 (19.4) 49.26 34.53 3.38 47.24 33.67 3.67 45.19 32.81 3.99 43.16 31.97 4.35 41.08 31.12 4.74 38.98 30.27 5.18
1400
62 (16.7) 44.79 40.67 3.34 42.95 39.78 3.63 41.11 38.89 3.94 39.27 37.98 4.29 37.46 37.03 4.68 35.80 35.80 5.11
57 (13.9) 43.36 43.36 3.33 41.90 41.90 3.61 40.41 40.41 3.93 38.91 38.91 4.28 37.37 37.37 4.67 35.80 35.80 5.11
72 (22.2) 55.34 29.69 3.50 53.08 28.85 3.80 50.82 28.01 4.13 48.57 27.18 4.50 46.28 26.35 4.90 43.96 25.51 5.36
67 (19.4) 50.23 36.68 3.46 48.13 35.81 3.75 46.00 34.94 4.07 43.90 34.09 4.43 41.76 33.24 4.83 39.60 32.37 5.27
1600
62 (16.7) 45.90 43.58 3.43 44.03 42.64 3.71 42.18 41.65 4.03 40.47 40.47 4.38 38.85 38.85 4.78 37.19 37.19 5.22
57 (13.9) 45.23 45.23 3.42 43.66 43.66 3.71 42.08 42.08 4.03 40.48 40.48 4.39 38.86 38.86 4.78 37.19 37.19 5.22
72 (22.2) 56.11 30.96 3.58 53.78 30.10 3.88 51.45 29.25 4.21 49.13 28.41 4.58 46.79 27.58 4.99 44.41 26.73 5.44
67 (19.4) 50.96 38.71 3.54 48.79 37.84 3.83 46.61 36.97 4.16 44.45 36.10 4.52 42.27 35.24 4.92 40.06 34.36 5.36
1800
62 (16.7) 46.90 46.19 3.51 45.07 45.07 3.80 43.45 43.45 4.12 41.77 41.77 4.48 40.06 40.06 4.88 38.32 38.32 5.32
57 (13.9) 46.76 46.76 3.51 45.12 45.12 3.80 43.45 43.45 4.12 41.77 41.77 4.48 40.07 40.07 4.88 38.33 38.33 5.32
Cooling Indoor Cooling Indoor Cooling Indoor
Capacity Power Furnace Model Capacity Power Furnace Model Capacity Power Furnace Model
Model Model Model
*CAR**4821A** 1.00 1.00 CNRV*4824A** 1.00 0.98 58CV(A,X)155--- 22 CNRH*4821A** 0.99 0.93 58PH*135--- 20
CAR**4817A** 1.00 1.00 CNRV*6024A** 1.02 0.98 58CV(A,X)155--- 22 CNRH*6024A** 1.02 0.96 58PH*135--- 20
CAR**6021A** 1.03 1.03 CSRH*4812A** 1.00 0.98 58CV(A,X)155--- 22 CNRV*4824A** 0.99 0.93 58PH*135--- 20
CAR**6024A** 1.03 1.03 CSRH*6012A** 1.02 0.98 58CV(A,X)155--- 22 CNRV*6024A** 1.02 0.96 58PH*135--- 20
CNRF*4818A** 0.98 0.98 CAR**4821A** 0.98 0.98 58MVB080--- 20 CSRH*4812A** 0.99 0.93 58PH*135--- 20
CNRH*4821A** 1.01 1.01 CAR**6021A** 1.01 0.99 58MVB080--- 20 CSRH*6012A** 1.02 0.96 58PH*135--- 20
CNRH*6024A** 1.03 1.03 CNRH*4821A** 0.99 0.99 58MVB080--- 20 See notes on pg. 26
CNRV*4821A** 1.01 1.01 CNRH*6024A** 1.01 0.99 58MVB080--- 20
CNRV*4824A** 1.01 1.01 CNRV*4821A** 0.99 0.99 58MVB080--- 20
CNRV*6024A** 1.03 1.03 CSRH*4812A** 1.00 1.00 58MVB080--- 20
CSRH*4812A** 1.02 1.02 CSRH*6012A** 1.01 0.99 58MVB080--- 20
CSRH*6012A** 1.04 1.04 CAR**4821A** 0.99 0.92 58MVB100--- 20
25
FA4CN(F,C)048 1.02 1.02 CAR**6021A** 1.01 0.99 58MVB100--- 20
FA4CN(F,C)060 1.04 1.04 CNRH*4821A** 0.99 0.99 58MVB100--- 20
FC4DN(F,B)048 1.03 1.01 CNRH*6024A** 1.01 0.99 58MVB100--- 20
FC4DN(F,B)060 1.05 1.01 CNRV*4821A** 0.99 0.99 58MVB100--- 20
FK4DNB006 1.03 0.97 CSRH*4812A** 1.00 1.00 58MVB100--- 20
FK4DNF005 1.02 0.98 CSRH*6012A** 1.02 1.00 58MVB100--- 20
CAR**4817A** 0.99 0.99 58CV(A,X)090--- 16 CAR**4824A** 0.98 0.98 58MVB120--- 20
CNRH*4821A** 0.99 0.97 58CV(A,X)090--- 16 CAR**6024A** 1.01 0.99 58MVB120--- 20
CNRH*6024A** 1.01 0.99 58CV(A,X)090--- 16 CNRH*4821A** 0.99 0.99 58MVB120--- 20
CSRH*4812A** 1.00 0.98 58CV(A,X)090--- 16 CNRH*6024A** 1.01 0.99 58MVB120--- 20
CSRH*6012A** 1.02 1.00 58CV(A,X)090--- 16 CNRV*4824A** 0.99 0.99 58MVB120--- 20
CAR**4821A** 0.99 0.99 58CV(A,X)110--- 20 CNRV*6024A** 1.01 0.99 58MVB120--- 20
CAR**6021A** 1.01 0.99 58CV(A,X)110--- 20 CSRH*4812A** 1.00 1.00 58MVB120--- 20
CNRH*4821A** 0.99 0.97 58CV(A,X)110--- 20 CSRH*6012A** 1.02 1.00 58MVB120--- 20
CNRH*6024A** 1.01 0.99 58CV(A,X)110--- 20 CAR**4821A** 0.99 0.95 58PH*090--- 16
CNRV*4821A** 0.99 0.97 58CV(A,X)110--- 20 CAR**6021A** 1.01 0.95 58PH*090--- 16
CSRH*4812A** 1.00 0.98 58CV(A,X)110--- 20 CNRH*4821A** 0.99 0.95 58PH*090--- 16
CSRH*6012A** 1.02 1.00 58CV(A,X)110--- 20 CNRH*6024A** 1.02 0.96 58PH*090--- 16
CAR**4824A** 0.99 0.97 58CV(A,X)135--- 22 CNRV*4821A** 0.99 0.95 58PH*090--- 16
CAR**6024A** 1.01 0.99 58CV(A,X)135--- 22 CSRH*4812A** 0.99 0.95 58PH*090--- 16
CNRH*4821A** 0.99 0.97 58CV(A,X)135--- 22 CSRH*6012A** 1.02 0.96 58PH*090--- 16
CNRH*6024A** 1.01 0.99 58CV(A,X)135--- 22 CAR**4821A** 0.99 0.93 58PH*110--- 20
CNRV*4824A** 0.99 0.97 58CV(A,X)135--- 22 CAR**6021A** 1.01 0.93 58PH*110--- 20
CNRV*6024A** 1.01 0.99 58CV(A,X)135--- 22 CNRH*4821A** 0.99 0.93 58PH*110--- 20
CSRH*4812A** 1.00 0.98 58CV(A,X)135--- 22 CNRH*6024A** 1.02 0.94 58PH*110--- 20
CSRH*6012A** 1.02 0.98 58CV(A,X)135--- 22 CNRV*4821A** 0.99 0.93 58PH*110--- 20
CAR**4824A** 0.99 0.95 58CV(A,X)155--- 22 CSRH*4812A** 0.99 0.93 58PH*110--- 20
CAR**6024A** 1.02 0.98 58CV(A,X)155--- 22 CSRH*6012A** 1.02 0.94 58PH*110--- 20
CNRH*4821A** 1.00 0.98 58CV(A,X)155--- 22 CAR**4824A** 0.99 0.93 58PH*135--- 20
CNRH*6024A** 1.02 0.98 58CV(A,X)155--- 22 CAR**6024A** 1.02 0.96 58PH*135--- 20
24ABR3
24ABR3
26
CAR**6024A** 1.00 0.98 58CV(A,X)155--- 22
CNRH*6024A** 0.99 0.95 58CV(A,X)155--- 22
CNRV*6024A** 0.99 0.95 58CV(A,X)155--- 22
CSRH*6012A** 1.00 0.96 58CV(A,X)155--- 22
CAR**6021A** 0.97 0.97 58PH*090--- 16
CNRH*6024A** 0.98 0.98 58PH*090--- 16
CSRH*6012A** 0.98 0.98 58PH*090--- 16
CAR**6021A** 0.98 0.96 58PH*110--- 20
CNRH*6024A** 0.99 0.97 58PH*110--- 20
CSRH*6012A** 1.00 0.98 58PH*110--- 20
CAR**6024A** 0.99 0.97 58PH*135--- 20
CNRH*6024A** 0.99 0.97 58PH*135--- 20
CNRV*6024A** 0.99 0.97 58PH*135--- 20
CSRH*6012A** 1.00 0.98 58PH*135--- 20
* Tested Combination
{ Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
} Sensible capacities shown are based on 80_F (27_C) entering air at the indoor coil. For sensible capacities at other than 80_F (27_C), deduct 835 Btuh
(245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80_F (27_C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air per degree above 80_F (27_C).
# Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240 ---94. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may
occur.
** System kw is total of indoor and outdoor unit kilowatts.
EWB — Entering Wet Bulb
NOTE: When the required data fall between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
CONDENSER ONLY RATINGS*
SST CONDENSER ENTERING AIR TEMPERATURES ˚F (˚C)
55 65 75 85 95 105 115 125
˚F (˚C)
(12.78) (18.33) (23.89) (29.44) (35.0) (40.56) (46.11) (51.67)
24ABR318(A,G)32
TCG 15.30 14.40 13.60 12.90 12.10 11.40 10.60 9.80
30 SDT 68.80 77.90 87.20 96.60 106.00 115.50 125.00 134.50
KW 0.83 0.93 1.03 1.14 1.26 1.40 1.56 1.75
TCG 17.00 16.00 15.10 14.30 13.50 12.70 11.90 10.90
35 SDT 70.30 79.30 88.50 97.80 107.20 116.60 126.10 135.50
KW 0.84 0.94 1.04 1.15 1.27 1.41 1.58 1.77
TCG 18.70 17.70 16.70 15.90 15.00 14.10 13.20 12.20
40 SDT 71.80 80.70 89.80 99.10 108.40 117.80 127.20 136.50
KW 0.85 0.95 1.05 1.16 1.28 1.43 1.60 1.79
TCG 20.50 19.40 18.40 17.50 16.50 15.60 14.60 13.50
45 SDT 73.30 82.20 91.20 100.40 109.70 119.00 128.30 137.60
KW 0.86 0.96 1.06 1.17 1.30 1.44 1.61 1.81
TCG 22.40 21.30 20.20 19.20 18.20 17.10 16.10 14.90
50 SDT 75.00 83.70 92.70 101.80 111.00 120.20 129.50 138.80
KW 0.87 0.97 1.07 1.18 1.31 1.46 1.63 1.83
24ABR3
TCG 24.40 23.20 22.10 21.00 19.90 18.80 17.60 16.40
55 SDT 76.70 85.30 94.20 103.20 112.30 121.50 130.70 140.00
KW 0.88 0.97 1.08 1.19 1.32 1.47 1.65 1.85
24ABR324(A,G)33
TCG 19.60 18.90 18.20 17.30 16.30 15.00 13.60 12.00
30 SDT 71.10 80.30 89.50 98.80 108.10 117.30 126.30 135.20
KW 1.14 1.24 1.37 1.51 1.69 1.89 2.12 2.38
TCG 21.70 20.90 20.10 19.20 18.10 16.90 15.50 13.90
35 SDT 72.80 81.80 91.00 100.20 109.50 118.60 127.70 136.70
KW 1.15 1.25 1.38 1.53 1.70 1.90 2.13 2.38
TCG 24.00 23.10 22.20 21.20 20.10 18.80 17.40 15.90
40 SDT 74.60 83.50 92.50 101.70 110.90 120.00 129.20 138.20
KW 1.16 1.27 1.39 1.54 1.71 1.91 2.14 2.39
TCG 26.50 25.40 24.30 23.30 22.10 20.80 19.40 17.80
45 SDT 76.60 85.30 94.20 103.20 112.30 121.50 130.60 139.60
KW 1.17 1.28 1.41 1.56 1.73 1.93 2.15 2.41
TCG 29.20 27.90 26.70 25.50 24.20 22.90 21.40 19.80
50 SDT 78.60 87.10 95.90 104.80 113.80 122.90 132.00 141.00
KW 1.17 1.29 1.42 1.57 1.75 1.95 2.17 2.42
TCG 32.10 30.60 29.20 27.80 26.40 25.00 23.50 21.90
55 SDT 80.80 89.20 97.70 106.50 115.40 124.40 133.40 142.40
KW 1.18 1.30 1.43 1.59 1.77 1.96 2.19 2.44
24ABR330(A,G)33
TCG 24.50 23.50 22.50 21.30 20.10 18.90 17.50 16.10
30 SDT 71.20 80.30 89.60 98.80 108.10 117.50 126.80 136.10
KW 1.30 1.46 1.63 1.81 2.00 2.21 2.44 2.70
TCG 27.30 26.10 24.90 23.70 22.30 20.90 19.50 17.90
35 SDT 73.00 82.00 91.10 100.20 109.50 118.70 128.00 137.20
KW 1.32 1.48 1.65 1.83 2.03 2.24 2.48 2.75
TCG 30.20 28.90 27.60 26.20 24.70 23.20 21.60 20.00
40 SDT 74.90 83.70 92.70 101.70 110.90 120.00 129.30 138.50
KW 1.35 1.51 1.68 1.86 2.06 2.28 2.52 2.80
TCG 33.30 31.80 30.30 28.80 27.20 25.60 23.90 22.20
45 SDT 76.80 85.50 94.40 103.30 112.40 121.50 130.60 139.80
KW 1.39 1.54 1.71 1.89 2.09 2.31 2.56 2.84
TCG 36.40 34.90 33.30 31.60 29.90 28.20 26.40 24.60
50 SDT 78.80 87.40 96.10 105.00 113.90 123.00 132.10 141.20
KW 1.42 1.57 1.73 1.91 2.11 2.33 2.58 2.86
TCG 39.70 38.00 36.30 34.60 32.80 31.00 29.10 27.20
55 SDT 80.80 89.30 97.90 106.70 115.60 124.60 133.60 142.70
KW 1.43 1.58 1.74 1.92 2.11 2.33 2.58 2.87
See notes on page 29
27
CONDENSER ONLY RATINGS*
SST CONDENSER ENTERING AIR TEMPERATURES ˚F (˚C)
55 65 75 85 95 105 115 125
˚F (˚C)
(12.78) (18.33) (23.89) (29.44) (35.0) (40.56) (46.11) (51.67)
24ABR336(A,G)33
TCG 30.10 29.00 27.70 26.30 24.80 23.00 21.10 19.00
30 SDT 73.40 82.30 91.20 100.30 109.30 118.40 127.50 136.40
KW 1.63 1.81 2.00 2.20 2.43 2.70 3.01 3.37
TCG 33.50 32.10 30.70 29.20 27.50 25.60 23.60 21.40
35 SDT 75.40 84.10 92.90 101.80 110.80 119.80 128.80 137.70
KW 1.67 1.85 2.04 2.24 2.47 2.73 3.04 3.40
TCG 37.00 35.50 33.90 32.20 30.40 28.40 26.30 24.00
40 SDT 77.60 86.10 94.70 103.50 112.40 121.30 130.20 139.10
KW 1.73 1.90 2.09 2.29 2.51 2.78 3.08 3.44
TCG 40.60 38.90 37.20 35.40 33.40 31.30 29.10 26.70
45 SDT 79.80 88.10 96.60 105.30 114.00 122.90 131.70 140.50
KW 1.77 1.95 2.13 2.33 2.56 2.82 3.13 3.49
TCG 44.30 42.50 40.60 38.60 36.50 34.30 32.00 29.40
50 SDT 82.00 90.10 98.50 107.10 115.70 124.50 133.20 142.00
KW 1.81 1.98 2.16 2.37 2.59 2.86 3.17 3.53
24ABR3
28
CONDENSER ONLY RATINGS*
SST CONDENSER ENTERING AIR TEMPERATURES ˚F (˚C)
55 65 75 85 95 105 115 125
˚F (˚C)
(12.78) (18.33) (23.89) (29.44) (35.0) (40.56) (46.11) (51.67)
24ABR360(A,G)36
TCG 52.00 49.50 47.10 44.60 41.90 39.10 36.10 32.80
30 SDT 75.00 83.90 93.00 102.20 111.30 120.50 129.60 138.60
KW 2.71 3.02 3.35 3.71 4.12 4.58 5.10 5.71
TCG 57.40 54.70 52.00 49.30 46.50 43.50 40.30 37.00
35 SDT 77.00 85.80 94.80 103.90 113.00 122.10 131.10 140.10
KW 2.79 3.09 3.41 3.77 4.18 4.65 5.19 5.81
TCG 63.20 60.20 57.30 54.40 51.30 48.20 44.80 41.30
40 SDT 79.10 87.80 96.70 105.60 114.70 123.70 132.70 141.70
KW 2.88 3.17 3.49 3.85 4.26 4.74 5.29 5.93
TCG 69.30 66.00 62.80 59.60 56.40 53.00 49.50 45.80
45 SDT 81.30 89.90 98.60 107.50 116.40 125.40 134.40 143.30
KW 2.98 3.26 3.57 3.93 4.34 4.82 5.39 6.03
TCG 75.60 72.00 68.50 65.10 61.60 58.00 54.20 50.30
50 SDT 83.50 92.00 100.60 109.40 118.20 127.10 136.00 144.90
KW 3.08 3.34 3.65 4.00 4.42 4.90 5.47 6.14
24ABR3
TCG 82.00 78.10 74.30 70.50 66.80 63.00 59.00 54.90
55 SDT 85.70 94.10 102.60 111.30 120.00 128.90 137.70 146.50
KW 3.17 3.42 3.72 4.06 4.48 4.97 5.55 6.22
* ARI listing applies only to systems shown in Combination Ratings table.
KW --- Outdoor Unit Kilowatts Only.
SDT --- Saturated Temperature Leaving Compressor (˚F/˚C)
SST --- Saturated Temperature Entering Compressor (˚F/˚C)
TCG --- Gross Cooling Capacity (1000 Btuh)
29
GUIDE SPECIFICATIONS AIR--COOLED, SPLIT--SYSTEM AIR CONDITIONER
24ABR3
GENERAL 1--1/2 TO 5 NOMINAL TONS
System Description Fans
Outdoor--mounted, air--cooled, split--system air conditioner unit — Condenser fan will be direct--drive propeller type,
suitable for ground or rooftop installation. Unit consists of a discharging air upward.
hermetic compressor, an air--cooled coil, propeller--type — Condenser fan motors will be totally enclosed, 1--phase
condenser fan, and a control box. Unit will discharge supply air type with class B insulation and permanently lubricated
upward as shown on contract drawings. Unit will be used in a bearings. Shafts will be corrosion resistant.
refrigeration circuit to match up to a packaged fan coil or coil — Fan blades will be statically and dynamically balanced.
unit.
— Condenser fan openings will be equipped with coated
Quality Assurance steel wire safety guards.
— Unit will be rated in accordance with the latest edition Compressor
of ARI Standard 210.
— Compressor will be hermetically sealed.
— Unit will be certified for capacity and efficiency, and
listed in the latest ARI directory. — Compressor will be mounted on rubber vibration
isolators.
— Unit construction will comply with latest edition of
ANSI/ ASHRAE and with NEC. Condenser Coil
— Unit will be constructed in accordance with UL — Condenser coil will be air cooled.
24ABR3
standards and will carry the UL label of approval. Unit — Coil will be constructed of aluminum fins mechanically
will have c--UL--us approval. bonded to copper tubes which are then cleaned,
— Unit cabinet will be capable of withstanding Federal dehydrated, and sealed.
Test Method Standard No. 141 (Method 6061) 500--hr Refrigeration Components
salt spray test. — Refrigeration circuit components will include
— Air--cooled condenser coils will be leak tested and liquid--line shutoff valve with sweat connections,
pressure tested. vapor--line shutoff valve with sweat connections,
— Unit constructed in ISO9001 approved facility. system charge of R--22 refrigerant, and compressor oil.
— Unit will be equipped with filter drier.
Delivery, Storage, and Handling
— Unit will be shipped as single package only and is Operating Characteristics
stored and handled per unit manufacturer’s — The capacity of the unit will meet or exceed _____
recommendations. Btuh at a suction temperature of _____ _F/_C. The
Warranty (for inclusion by specifying engineer) power consumption at full load will not exceed _____
kW.
— U.S. and Canada only.
— Combination of the unit and the evaporator or fan coil
PRODUCTS unit will have a total net cooling capacity of _____
Equipment Btuh or greater at conditions of _____ CFM entering
air temperature at the evaporator at _____ _F/_C wet
Factory--assembled, single--piece, air--cooled air conditioner unit.
bulb and _____ _F/_C dry bulb, and air entering the
Contained within the unit enclosure is all factory wiring, piping,
unit at _____ _F/_C.
controls, compressor, refrigerant charge, and special features
required prior to field start--up. — The system will have a SEER of _____ Btuh/watt or
greater at DOE conditions.
Unit Cabinet
Electrical Requirements
— Unit cabinet will be constructed of galvanized steel,
bonderized, and coated with a powder coat paint. — Nominal unit electrical characteristics will be _____ v,
single phase, 60 hz. The unit will be capable of
satisfactory operation within voltage limits of _____ v
to _____ v.
— Nominal unit electrical characteristics will be _____ v,
three phase, 60 hz. The unit will be capable of
satisfactory operation within voltage limits of _____ v
to _____ v.
— Unit electrical power will be single point connection.
— Control circuit will be 24v.
Special Features
— Refer to section of this literature identifying accessories
and descriptions for specific features and available
enhancements.
Copyright 2008 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 05/08 Catalog No. 24ABR3---4PD
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Replaces: 24ABR3--- 3PD
30