Pressure Exchanger PX q400
Pressure Exchanger PX q400
TABLE OF CONTENTS
1.   INTRODUCTION ................................................................................................................. 3
           ABOUT THIS MANUAL ......................................................................................... 3
           DEVICE BASICS .................................................................................................... 3
           PX DEVICE IN RO SYSTEMS................................................................................... 4
           CIRCULATION PUMP WITH PX DEVICES ............................................................... 4
           PX OPERATIONAL LIMITS ..................................................................................... 4
2.   SAFETY ............................................................................................................................... 5
           HIGH PRESSURE REMAINS AFTER SHUTDOWN .................................................... 6
           LOW PRESSURE ISOLATION AND OVER-PRESSURIZATION .................................... 6
           HYDROSTATIC TESTING ....................................................................................... 7
3.   STORAGE AND HANDLING INFORMATION ......................................................................... 7
           STORAGE AND HANDLING INFORMATION ........................................................... 7
           LIFTING ............................................................................................................... 7
           LIFTING EQUIPMENT .............................................................................................. 7
           HORIZONTAL LIFTING PROCEDURE ........................................................................ 8
           VERTICAL LIFTING PROCEDURE .............................................................................. 9
           INSTALLATION .................................................................................................... 9
4.   OPERATION........................................................................................................................ 10
           FEEDWATER SUPPLY ........................................................................................... 10
           START AND STOP PROCEDURES........................................................................... 10
           STARTUP SEQUENCE .............................................................................................. 10
           SHORT TERM SHUTDOWN SEQUENCE ................................................................... 11
           LONG TERM SHUTDOWN SEQUENCE ..................................................................... 12
           FEEDWATER FILTRATION .................................................................................... 12
           FLOW CONTROL.................................................................................................. 12
           LUBRICATION FLOW RATE ...................................................................................... 12
           HIGH- AND LOW-PRESSURE FLOW RATES .............................................................. 13
           FLOW BALANCE ...................................................................................................... 13
     4.5. FLUSHING ........................................................................................................... 14
     4.6. PURGE AIR .......................................................................................................... 15
5.   SERVICE ............................................................................................................................. 15
           SPARE PARTS AND TOOL KITS .............................................................................. 15
           DISASSEMBLY PROCEDURE ................................................................................. 16
           DISASSEMBLY PROCEDURE FOR THE PX DEVICE ON THE RACK OR PIPING ............. 17
           PX DISASSEMBLY..................................................................................................... 18
           ASSEMBLY PROCEDURE ...................................................................................... 24
           CARTRIDGE ASSEMBLY ........................................................................................... 24
6.   TROUBLESHOOTING .......................................................................................................... 30
           PRELIMINARY PROCEDURES ................................................................................ 30
           INSTRUMENTATION............................................................................................ 30
           TROUBLESHOOTING GUIDE ................................................................................ 31
7.   LEARNING MORE AND CONTACTING ENERGY RECOVERY.................................................. 33
8.   REVISION LOG.................................................................................................................... 33
1. INTRODUCTION
This manual contains instructions for the installation and operation of Energy Recovery, Inc.
PX Q400 energy recovery devices for Reverse Osmosis (RO) systems. This information is
provided to ensure the long life and safe operation of your PX® Pressure Exchanger® (PX)
energy recovery device. This manual is intended for use by personnel with training and
experience in the installation and operation of fluid handling systems. For additional information
regarding using the PX device in RO systems, refer to Energy Recovery’s website:
www.energyrecovery.com or contact Energy Recovery customer service.
Device Basics
The PX energy recovery device transfers pressure energy from the RO high-pressure concentrate
reject stream to a low-pressure feedwater stream. It does this by putting the streams in direct,
momentary contact in the ducts of a rotor. The rotor is fit into a ceramic sleeve enclosed
between two ceramic end covers with precise clearances that, when filled with high-pressure
water, create an almost frictionless hydrodynamic bearing. The rotor spinning inside the
hydrodynamic bearing is the only moving part within the device.
                                 C
                                                          F                               I
B H
PX Device in RO Systems
Figure 1-1 illustrates a typical flow schematic for a RO system equipped with a PX device. There
are two independent flow paths in the PX device, the low-pressure (LP) side [B to H] and the
high-pressure (HP) side [G to D]. The reject concentrate from the RO membranes [G] passes
through the PX device or an array of devices operating in parallel. The pressure of the
concentrate reject is transferred directly to a portion of the incoming feedwater at up to 98%
efficiency. This pressurized feedwater stream [D], which is nearly equal in volume and pressure
to the concentrate reject stream [G], passes through a circulation pump. The circulation pump
propels flow in the high-pressure loop [E-F-G-D] at a rate controlled by either a variable
frequency driver on the motor or a control valve at the discharge of the circulation pump. Fully
pressurized feedwater from the circulation pump merges with flow from the high-pressure
pump discharge [C] to feed the membranes [F].
In the typical RO system illustrated in Figure 1-1, a circulation pump is required to move water
through the membranes and PX device or array. The high-pressure flow through the PX unit(s)
is controlled by either a variable frequency drive operating the circulation pump or a flow control
valve at the circulation pump discharge. Recommended practice is to use a slightly oversized
circulation pump to accommodate for the projected range of concentrate flow and head
requirements. The head requirements are a sum of the pressure losses from the membrane,
piping, and PX device differential pressure (head). Seasonal variations, membrane fouling, and
other process variations should also be considered when sizing your circulation pump. Energy
Recovery carries a line of circulation pumps with capacities from 20 gpm (4.5 m3/hr) up to 2,200
gpm (500 m3/hr). Energy Recovery circulation pumps can be installed on the same manifold to
run in parallel to achieve higher capacities.
PX Operational Limits
Successful operation of the PX Q400 energy recovery device requires observation of some basic
operating conditions and precautions. The PX unit must be installed and operated in accordance
with this manual and good industrial practice to ensure safe operation and a long service life.
Failure to observe these conditions and precautions can result in reduced service life, damage
to the equipment, and/or harm to personnel. For operational conditions, refer to the Technical
Data Sheet of the product. Table 1-1 provides a summary of system performance limits.
Further information about PX or other Energy Recovery products or service can be found by
contacting Energy Recovery at:
2. SAFETY
The PX device is designed to provide safe and reliable service; however, it is used in a high-
pressure industrial process. Operations and maintenance personnel must follow the basic safety
rules associated with high-pressure equipment and seawater RO processes. Proper installation
and maintenance of shutdown devices and over-pressure and over-flow protection equipment
are an essential part of any RO system. Operation of the PX device outside of the designed
operating range can result in damage and may be unsafe.
 CAUTION                These flags denote items that, if not strictly observed, can result in
                        damage or destruction to equipment.
   DANGER               These flags denote items that, if not strictly observed, can result in
                        serious injury to personnel.
The flags shown and defined below are used throughout this manual. They should be given
special attention when they appear in the manual.
Hydrostatic testing
PX devices are packed with plugs installed on the connection ports. Keep the plugs in place until
the unit is to be fitted to the piping. This will keep the inside of the unit clean.
   • The PX units must never be exposed to temperatures below 33F (1C) or above 120F (49C)
     during storage or operation. If possible, store in a climate-controlled building or
     warehouse.
   • Avoid direct sunlight, rain or weather.
   • Never lift or support the units with the end ports or side ports.
   • Use a crane for lifting whenever one is available.
       Lifting
                     Always use caution when working with heavy objects – The ERI PX-Q400
 DANGER              weighs approximately 360 LBS (164 KG) – and can be difficult to move and
                     manipulate.
Lifting Equipment
  1) Space two (2) Flat-Eye Web Sling along the outer diameter of the PX as shown in Figure
     3-1. Ensure slings are equally spaced with respect to the center-plane of the PX.
  2) One sling can be used if configured as “Double Choker Hitch” shown in Figure 3-2.
Center-Plane
Figure 3-1: Space slings evenly along the PX housing. Figure 3-2: Single sling Double Choker Hitch method
  3) Once unit is properly strapped it can be lifted and transported, to final destination,
     carefully using either of these methods:
        a. Overhead lift and/or Jib Crane
        b. Fork Lift
        c. Floor Crane
   1) Wrap the PX using the single Sling “Choker” method shown in Figure 3-3.
   2) Place Sling below top side-port shown in Figure 3-4. Carefully lift and place unit as
      required.
Figure 3-3: Single Choker method Figure 3-4: Single sling use on PX
Installation
PX devices can be installed and operated in any orientation. Each unit has four connections
labeled HP IN, HP OUT, LP IN, and LP OUT.
The PX unit must be supported by its housing and not by the pipe fittings. Prevent the PX unit
from supporting piping or manifolds. The PX device should be kept in its original packing until
the initial startup of the RO train. Proper piping, piping support, and housing support must be
employed to minimize external stresses on all pipe fittings. Use shims to support and align the
housing. Suitable flexible couplings should be used for joining fittings and piping. Use only water-
soluble lubricants such as glycerin on coupling gaskets; do not use grease. Please request
dimensional drawings of a PX device and a piping detail for use for piping, manifold, and support
rack design.
Prior to installation of the PX device, all associated piping should be thoroughly flushed to assure
that no debris enters and/or damages the PX unit. Temporary installation of basket strainers at
both inlets to the PX device or PX device array can be used.
  CAUTION               Thoroughly flush associated piping with clean water before installing the
                        PX unit. Foreign material entering the unit may cause damage.
4. OPERATION
Feedwater Supply
The following procedures are general guidelines for the startup and shutdown of PX unit
systems. Procedure details will vary by plant design. Contact Energy Recovery if your process
design significantly differs from that shown in Figure 1-1. Always ensure that the operating limits
listed in Section 1.5 are followed.
Startup Sequence
2. Start the feedwater supply pump. The feed flow through the PX unit(s) may or may not
    cause the rotor to begin to rotate. Rotation will produce a humming sound that is audible
    at close proximity to the PX unit(s).
3. Adjust the feedwater flow to the desired flow rate using the low-pressure outlet flow
    control valve (FCV).
4. Open air vent valves to vent the high-pressure piping. This is necessary to allow air to
    escape the system and to allow the high-pressure piping to fill with water pushed through
    the high-pressure pump by the feedwater supply pump.
5. After the high-pressure piping is full of water, start the circulation pump. Rotor speed will
    increase. Bleed any remaining air from the system.
6. Adjust the high and low-pressure flows to the PX unit to make them equal.
7. After the feedwater supply and circulation pump have run for sufficient time to purge all
    air from the system, start the high-pressure pump. The RO system pressure will increase
    to the point where the permeate flow will approximately equal the flow from the high-
    pressure pump. The sound level from the PX unit will increase. Small variations in sound
    level and rotor speed are normal.
8. Close the air vent valves.
9. Verify that pressure at the device low-pressure outlet exceeds minimum requirements.
10. Verify the high and low-pressure flow rates. Adjust flows as necessary to achieve balanced
    flow to the PX units.
1. Throttle the LPOUT FCV to avoid overflow in the LP side of the unit when the high-
   pressure pump is turned off.
2. Shut off the main high-pressure pump.
3. Wait until the system pressure drops to the osmotic pressure of the seawater, e.g. 400
   psig (28 bar).
4. Shut off the circulation pump.
5. Shut off the feedwater supply pump.
6. If necessary, open a purge valve to expedite depressurization.
If the process is to be shut down for long term (the time frame depends on the characteristics
of the RO system and feedwater), the RO system including the PX units must be thoroughly
flushed with fresh water to remove any salt, and precautions should be taken to inhibit
biological growth. The high-pressure and low-pressure sides of the PX unit must be flushed
separately. The low-pressure side should be flushed with fresh water through the feedwater
feed line to the PX unit and to the concentrate drain. The high-pressure flush is typically
performed by circulating water through the PX unit and the membranes using the circulation
pump. Lubrication flow for the PX device rotors must be provided through the high-pressure
pump or some other injection point in the high-pressure loop during fresh water flushing. The
PX units should receive a final flush with the same solution used to preserve the RO membranes.
Feedwater Filtration
Like the RO membranes, the PX device requires filtered water. Particulates entering the PX
device are passed through to the membranes. Particles entering the PX device may also prevent
the rotor from spinning and can effect performance, resulting in the need to service the device.
The PX device filtration requirement applies during commissioning, normal operation, as well as
the membrane Clean in Place (CIP) process; refer to the technical data sheet for filtration
requirements.
Flow Control
Flow rates and pressures in a typical RO plant will vary slightly over the life of a plant due to
temperature variations, membrane fouling, and feed salinity variations. The PX unit’s rotor is
turned by the flow of fluid through the device. The speed of the rotor is self-adjusting over the
PX unit’s operating range. The ratio of the high and low-pressure flow rates affects the degree
of mixing between the feedwater and concentrate streams that occurs within the unit.
In a PX device, some of the high-pressure water flows through the hydrodynamic bearing to low-
pressure regions in the assembly. The lubrication flow rate varies with system pressure
according to the PX’s performance curves. If the PX device has a damaged o-ring or is damaged
by debris, overflow, or insufficient discharge pressure, excess lubrication flow may occur.
Monitoring lubrication flow is a good way to check the integrity of an operating PX unit.
Lubrication flow can be monitored using any of the following three methods:
   • Measure the flow rate of the low-pressure feedwater to the high-pressure pump and the
      flow rate of the permeate. The difference is approximately the lubrication flow rate.
   • Measure the flow rate of the high-pressure concentrate to the PX unit and the high-
      pressure feedwater from the PX unit. The difference is approximately the lubrication flow
      rate.
   • Measure the flow rate of the low-pressure concentrate from the PX unit and the low-
      pressure feedwater to the PX unit. The difference is approximately the lubrication flow
      rate.
Please note that this method of monitoring is to help establish trends. The value obtain may not
be exact.
The high-pressure flow through the PX unit is set by adjusting the circulation pump with a
variable frequency drive or with a flow control valve and verified with a high-pressure flow
meter. The flow rate of the high-pressure feedwater out of the PX unit equals the flow rate of
the high-pressure concentrate to the PX unit minus the bearing lubrication flow.
The low-pressure flow through the PX unit is controlled by the feedwater supply pump and a
control valve in the concentrate discharge from the PX unit(s). This valve also adds backpressure
on the PX device required to prevent cavitation. The low-pressure flow rate must be verified
with a flow meter. The flow rate of the low-pressure concentrate from the PX unit equals the
flow rate of the low-pressure feedwater to the PX unit plus the bearing lubrication flow rate.
Flow Balance
The high and low-pressure flows to and from the PX device should be equal or “balanced” for
optimum RO operation. Operating the PX unit with unbalanced flows can result in higher
contamination of the feedwater feed by the concentrate reject. Balanced flows help limit the
mixing of concentrate with the feed. A feedwater inlet flow that is much less than the feedwater
outlet flow will result in lower quality permeate, increased feed pressure, and higher energy
consumption. For more information refer to Energy Recovery document 80088-01 Mixing
Technical Bulletin or contact Energy Recovery customer service.
4.5. Flushing
There are two types of flush: Feedwater Flush and Fresh Water or Permeate Flush. Regardless
of the flush water used, all parts of the PX device must be flushed, i.e. low-pressure flow
channels, high-pressure flow channels, and lubrication channels.
Feedwater Flushing is part of a normal shutdown sequence as described in Section 4. After both
permeate and concentrate production have ceased, flow on both the high-pressure and low-
pressure sides of the PX devices continues. The flow path of the Feedwater Flush, with reference
to Figure 1-1, is B-C-D-E-F-G-H driven by the feedwater pump and the circulation pump. A
Feedwater Flush is typically continued until conductivity measurements at process locations G
and H are satisfactory (TDS close to feedwater TDS).
A Permeate Flush or Fresh Water Flush is performed on a partially or fully depressurized system.
This is accomplished by introducing permeate simultaneously to the PX device low-pressure
inlet [B] and either to the high-pressure pump inlet [A] or through some other injection point
such as a CIP connection. Permeate may be produced during this flushing process. If so, it may
be necessary to block permeate flow to divert lubrication flow through the PX devices. The
circulation pump must be run to flush HP side of the PX device (s).
For more detail information refer to relevent Energy Recovery technical bulletins.
Entrained or trapped air or other gases must always be purged from the RO system before
pressurizing the system. Entrained air in a pressurized system can result in damage to the PX
unit. Prior to pressurizing the RO system, vent or flush for sufficient time to allow for the removal
of all air from the RO system.
 CAUTION                 Entrained or trapped air must be purged from the RO system before every
                         pressurization.
5. SERVICE
The PX Q400 energy recovery device needs no scheduled periodic maintenance. However, in the
event that disassembly is desired or required, the PX Q400 unit is designed so that it can be
assembled and disassembled in the field with only basic tools and equipment. These tools are
listed in Table 5-1. These tools, with the exception of the hoist and torque wrench, are included
in the PX Q400 tool kit (Energy Recovery Part Number 20469-01). In addition, the PX Q400 unit
can be mounted on a stand or on blocks to facilitate service, or the LP connection port can be
unthreaded in order to support the unit on the housing.
 Replacement seals and alignment pins are included in Energy Recovery’s standard spare parts
 kits (Energy Recovery Part Number 20467-01). One spare parts kit should be used each time a
 PX unit is opened for service.
 Replacements for other components in the PX assembly are available. Refer to assembly
 drawing for PX component descriptions, part numbers, and the bill of materials.
Disassembly Procedure
                              Metal objects can chip or crack ceramic. Use caution when handling ceramic
    CAUTION                   components to avoid damage.
1. Depressurize all high-pressure and low-pressure piping to and from the PX unit.
2. Close all valves to and from the PX unit/rack or drain system.
3. Disconnect and remove the low-pressure piping from the upward facing end of the unit.
   See Figure 5-2 as reference.
4. If more access is required, the PX can be removed from the rack.
       a. Remove the all HP and LP couplings from the PX.
       b. Remove the all HP and LP pipes connected to the PX.
       c. Install sling around the PX as described in Section 3.2.
       d. Remove the Saddle and Strap from the PX.
       e. Remove the PX from the rack following the procedure listed in Section 3.2.
              i. Bottom LP port may need to be removed if access is needed. Refer to
                  Section 5.2.2 Step 1.
5. Proceed with disassembly as directed in Section 5.2.2.
Figure 5-1: PX device on array rack Figure 5-2: LP port removed on array rack
PX Disassembly
1. Unscrew and remove the bottom LP port Figure 5-3. Otherwise, use blocks or a stand to
   support the unit by the bottom end of the fiberglass housing shown in Figure 5-4. Do not
   support the unit or apply stress to the low-pressure port.
Figure 5-3: PX Q400 with Pipe Strap tool Figure 5-4: PX Support block shown as reference
2. Remove four (4) 5/16-inch socket-head cap screws, two (2) Securing Ring, and three (3)
   Segmented Lock Ring from the top of the PX unit using a 1/4-inch Allen wrench as shown
   in Figure 5-5.
       a. Tip: Segmented Lock Ring maybe compressed due to pressurization of the PX. In
          this instance, gently tap on the Bearing Plate with a plastic or wooden rod to loosen
          the Head Assembly.
Bearing Plate
  3. Extract Head Assembly from the housing using an Energy Recovery Head Puller tool
     20471-01 shown in Figure 5-6. Assisted lifting can be achieved using the All-thread and
     Lifting Eye 5/8-11” as shown in Figure 5-7. Take care not to apply stress to the LP port if
     it is still in place. Always use a wood block to protect the edge of the housing if force is
     necessary to remove the head assembly.
          a. Estimated weight of the Head Assembly is 25 lbs (11.3 kgs).
Figure 5-6: Head puller tool, PN 20471-01 Figure 5-7: Assisted lifting of the Head Assembly
4. Remove the Interconnect using Interconnect removal tool 10608-01. See Figure 5-8.
     a. Tip: If more access is needed, proceed with removing the cartridge before
        removing the Interconnect. See Section 5.2.2 step 5 for cartridge removal.
              Remove Interconnect
              using 10608-01 tool
                                                                     Lifting tool
                                                                           • Lifting Eye 10506-01
                                                                           • All thread 10606-01
                                                                           • Coupling Nut 30092-01
                      O-ring
                      installation tool
                      43684-01
7. Support PX Cartridge and allow room for Tension Rod and wrench. Refer to Figure 5-11
   for PX Cartridge construction and Figure 5-12 for reference support dimensions.
       a. Note: Concentrate and Feedwater orientation is dependent on orientation of PX
          during disassembly.
Tension Rod
Feedwater Endcover
Rotor-Sleeve Assembly
Concentrate Endcover
Figure 5-11: PX Cartridge construction Figure 5-12: Cartridge reference support dimensions
9. Lift the Rotor-Sleeve off the bottom Endcover as shown in Figure 5-14.
                i. Note: Be sure to keep the Rotor from coming out of the sleeve.
       a. If the rotor comes out of the sleeve, the following procedure should be applied:
                i. Clean the rotor and sleeve. Rinse liberally with water.
               ii. Inspect rotor and sleeve. Remove all debris. Avoid getting lint or dirt onto
                   the ceramic. Re-rinse if necessary.
              iii. Identify the end of the rotor marked “CHK”. Place the rotor on a flat clean
                   surface with the end marked “CHK” oriented upward.
              iv. Identify the end of the sleeve marked “CHK” and orient it upward. If the
                   sleeve is marked “CHK SWP” orient the "CHK SWP" end downward.
               v. Hold the sleeve over the rotor. Slowly slide the sleeve onto the rotor. This is
                   a very tight fit and requires a gentle touch. Do not force the sleeve on by
                   pressing or hitting it. The sleeve should slide on easily. If the rotor and sleeve
                   become bound, use hot water on the sleeve to loosen it from the rotor.
              vi. Contact Energy Recovery, Inc. if problems are encountered.
Figure 5-13: Disassembly of Spacer and Endcover Figure 5-14: Rotor-Sleeve removal
Assembly Procedure
This assembly procedure assumes that the PX Q400 unit has been disassembled per the previous
section. All parts should be carefully cleaned with clear water prior to assembly to ensure that
no dirt or debris contaminates the PX device. All parts should be thoroughly inspected for
damage and/or debris prior to reassembly. O-rings should be replaced with a new set. Do not
attempt to reassemble a PX unit with damaged or broken parts.
                                                                         Improper lubrication.
                                                                         Excess lubricant shown.
Proper Lubrication
For best results, pre-lubricate all new O-rings with a very thin coating of Dow Corning 111 Valve
Lubricant and Sealant prior to installation. Wipe off any excess lubricant using a lint free cloth.
O-rings should appear wet but not feel sticky or have any excess lubricant on the surface. See
Figure 5-17. Dirt and debris can stick to pre-lubricated O-rings. Use appropriate precautions to
keep them clean during handling and storage.
Always lubricate all O-ring mating surfaces immediately prior to assembly with a suitable water-
soluble lubricant such as glycerin or liquid soap.
Cartridge Assembly
5. Place Endcover and Tension-rod onto support block as shown in Figure 5-19.
      a. Tip: Placing a block under the Tension-rod will prevent it from falling down.
                                                                                                       (3) Dowel Pin
Figure 5-18: Interconnect Spacer install Figure 5-19: Dowel Pin install on Endcover
6. Insert three (3) Dowel Pins into the three (3) holes on the face of the Endcover as shown
   in Figure 5-19. Make sure the Dowel Pins are fully seated in the Endcover and the sharp
   ceramic edge has not created a burr. If a pin binds, remove and clear the pin and hole of
   any debris.
7. Carefully place the assembled Rotor-Sleeve onto the Endcover. Make sure that the Dowel
   Pins in the Endcover line up with the three (3) holes in the Sleeve as shown in Figure 5-
   20.
8. Install two (2) washers and one (1) hex nut finger tight. The fiberglass washer should be
   against the ceramic followed by the metal washer and then the hex nut as shown in Figure
   5-21.
                                                                                              Hex Nut
                                                                                              Metal Washer
                                                                                              Fiberglass Washer
Figure 5-20: Rotor-Sleeve assembly Figure 5-21: Top Endcover and Cartridge hardware
9. Carefully inspect the contact lines between the sleeve and the Endcovers to be sure there
   are no gaps, see Figure 5-22. If a gap is present, disassemble and clean to ensure no debris
   is in the cartridge.
       a. Tip: Debris can often be trapped in the circumferential groove on the Endcover and
           in the Dowel Pin counter-bore.
11. Verify that the both inner nut (closest to the Endcovers), both are secured.
12. Verify that the rotor can spin freely. Use a wooden or plastic dowel to advance rotor as
    illustrated in Figure 5-24.
DANGER DO NOT SPIN ROTOR WITH FINGER. Spinning Rotor can cause harm.
23. If LP Port was removed, install following the procedure below. See Figure 5-26 for
    reference.
        a. Apply food grade anti-seize to LP port thread.
        b. Lubricate O-ring.
               i. Tip: Inspect O-ring for to ensure no tears, rips, or any other defects are
                   present. Replace O-ring if required.
        c. Install O-ring into Seal Plate groove, highlighted green in Figure 5-26.
        d. Thread LP Port into Bearing Plate by hand. Use strap wrench shown in Figure 5-3 if
           necessary.
LP Port
O-Ring
6. TROUBLESHOOTING
This section is designed to guide the operator in identifying and correcting most of the problems
that could occur in the PX energy recovery device. The instructions provided below are intended
for use by personnel with general training and experience in the operation and maintenance of
fluid handling systems. This is not intended as a comprehensive maintenance guide. Conditions
not covered in this section may be resolved by contacting Energy Recovery’s Service
Department.
Preliminary Procedures
   • Always check for proper valve configuration for the operation mode selected.
   • Always inspect and test equipment or apparatus for possible causes of malfunctions
     before performing replacements.
Instrumentation
The following list of instrumentation is useful in monitoring and diagnosing the operation of PX
devices.
   • Energy Recovery requires that one flowmeter be installed in the PX unit(s) HP flow circuit
      and one in the LP flow path.
   • Energy Recovery requires a pressure instrument be installed between the low-pressure
      outlet and any control valve to monitor device backpressure.
   • Energy Recovery recommends that high flow and pressure alarms/shutdowns be
      incorporated into the system design to protect the PX unit(s) from potential damage by
      high flows.
   • Energy Recovery suggests using a TDS meter to check the conductivity of the streams
      entering and exiting the PX device to monitor device performance.
When using this troubleshooting guide, please read all the probable causes before taking any
action. Use common sense and select the cause that seems to best fit the given situation.
Troubleshooting Guide
A. Excessive       sound 4. PX unit or ceramic cartridge Verify that the PX unit has been installed
   levels                  installed upside down         with the end marked “HPIN” oriented
                                                         toward the concentrate inlet. If service
                                                         was performed, verify the orientation of
                                                         the ceramic cartridge by removing the
                                                         concentrate-side port bearing plate
                                                         assembly.     The    endcover     marked
                                                         “Concentrate” should be oriented toward
                                                         the concentrate inlet/outlet.
                          5. Damaged ceramic                     Contact the Energy Recovery Service
                                                                 Department
                          1. Membrane fouling or scaling         Contact membrane manufacturer for
                                                                 cleaning recommendations.
                         2. Excessively high recovery in the RO Reduce recovery by increasing and
                            system                              balancing flows through the PX unit(s). Do
                                                                not exceed recommended maximum PX
B.     Excessive    high                                        unit flow rates.
     pressure            3. HPP is operating at too high of a Adjust flow rates.
                            flow rate
                          4. Low pressure flow is less than Adjust flow rates. See Section 4.
                            high-pressure flow, resulting in
                            mixing and high RO feed water
                            salinity
Energy Recovery’s Technical Services staff offers commissioning service for all Energy Recovery
products during field installation and/or at a RO system manufacturer’s location. Service rate
quotes are available upon request.
8. REVISION LOG