SPM90 Single Phase DC Energy Meter
Installation & Operation Manual
V1.6
ZHUHAI PILOT TECHNOLOGY CO., LTD.
Danger and warning!
This device can be installed only by professionals.
The manufacturer shall not be held responsible for any accident caused by
the failure to comply with the instructions in this manual.
Risks of electric shocks, burning, or explosion
This device can be installed and maintained only by qualified people.
Before operating the device, isolate the voltage input and power supply
and short-circuit the secondary windings of all current transformers.
Use appropriate voltage tester to make sure the voltage has been
cut-off.
Put all mechanical parts, doors, or covers in their original positions
before energizing the device.
Always supply the device with the correct working voltage during its
operation.
Failure to take these preventive measures could cause damage to
equipment or injuries to people.
CONTENTS
1. Product Overview ...................................................................................................................... 1
2. Order Information ...................................................................................................................2
3. Appearance and Installation Dimension ........................................................................ 3
3.1 Outline Dimensional Drawing ............................................................................... 3
3.2 Installation Diagram ................................................................................................. 4
4. Display and Keyboard Instructions ...................................................................................5
4.1 Full Display ................................................................................................................... 5
4.2 Statue Inquiry .............................................................................................................. 5
4.3 Keyboard Instructions .............................................................................................. 5
4.4 Real-time Data Display Procedure ...................................................................... 6
4.5 Power On Display Interface ....................................................................................7
4.6 Parameters Settings .................................................................................................. 9
5. Measurement Capability ....................................................................................................10
5.1 Real-time Basic Electrical Parameters .................................................................10
5.2 Energy Parameters .................................................................................................. 11
5.3 Electric Energy Pulse .............................................................................................. 11
6. Communication ........................................................................................................................12
6.1 Overview ...................................................................................................................... 12
6.2 Communication Media ..........................................................................................13
6.3 Communication Protocol ..........................................................................................13
6.4 Communication Parameters ................................................................................13
6.5 Anti Strong Electricity Function of Communication Port ..................................13
7. Technical Parameters ............................................................................................................ 14
8. Appendix .................................................................................................................................. 16
8.1 Terminals Definition ................................................................................................16
8.2 Typical Wiring Diagram .........................................................................................17
1. Product Overview
SPM90 is designed for scenarios such as DC panel, charging pile and
telecom base stations. This meter series can measure voltage, current, power
and active energy in DC system. Not only can it be used as local display, but it
can also be used in measuring system by connecting with industrial control
equipment and computers. It is a high-performance automation meter that can
work with modern DC power distribution system in industrial and mining
industry, civil building and building automation.
Product performance fully meets the according technical requirements of
GB/T 29318-2012 (Energy measurement of non-vehicle charger of
electrombile) and Class 0.5 of DL/T 1484-2015 (Technical Regulations of DC
energy power).
Main function of this product:
Real-time measurement of electrical parameters: voltage, current
and power
Measurement of bidirectional energy
1CH RS485 communication, 1CH electric pulse output optional.
Supports MODBUS and DL/T645—2007 communication protocol.
1
2. Order Information
SPM90 - □ - □
① ②
①:Shunt specification (Required)
1 100A Shunt
1.5 150A Shunt
2 200A Shunt
3 300A Shunt
4 400A Shunt
②:Energy pulse (Optional)
P Energy pulse
If shunt in other specifications are needed, please contact us in advance.
Note: When selecting shunt, make sure the the actual current is within 80% of
scale span, preventing the influence on the accuracy on the shunt caused by
long-time large current.
2
3. Appearance and Installation Dimension
3.1 Outline Dimensional Drawing
Unit:mm
36.00 65.00
50.80
100.00
45.00
35.50
Pic. 1 DC meter dimensional drawing
a a
h1
h2
s
c
b
3
SPECS a b c s h1 h2 φ
100A 43±1 116±2 85±1 22±0.5 5.5±0.2 21±0.5 8.5±0.2
150A 43±1 116±2 85±1 22±0.5 5.5±0.2 21±0.5 8.5±0.2
200A 43±1 116±2 85±1 22±0.5 5.5±0.2 21±0.5 8.5±0.2
300A 43±1 126±2 100±1 26±0.5 5.5±0.2 21±0.5 10.5±0.2
400A 43±1 126±2 100±1 38±0.5 5.5±0.2 21±0.5 10.5±0.2
Pic. 2 Dimensional diagram of Shunt
3.2 Installation Diagram
4
4. Display and Keyboard Instructions
4.1 Full Display
There is a one-inch dot matrix LCD with
U 100.0 V
backlight on SPM 90, whose resolution is 128*64.
I 100.00 A
With 2 keys and menu prompt, switching among P 10.00 kW
E 20.125 kWh
different functions can be realized.
Note: Backlight turns off if the meter is left with
no operation for 60s. Backlight will not turn on
unless there is operation again.
4.2 Statue Inquiry
Indicator Color Indicating Indicated message
PULSE Red Flash Electric energy pulse
4.3 Keyboard Instructions
Note: Same keys play different functions if different interfaces.
Switching among equative menu
Exit/Confirm
5
4.4 Real-time Data Display Procedure
Menu tree diagram:
Pic.3 Operation Menu Tree Diagram
Keyboard instruction: Page down among equtive menu Next menu,
confirm button;
Editing Instruction: Editing options
switching Editing option execution.
6
4.5 Power On Display Interface
Data display 2, Main menu interface: Press
U:DC voltage
to select different submenu,
I :DC current
P:Power
press to enter submenu, as
E : Energy
1、 Startup interface: shown below:
The meter self-examines with
power on, LCD lights up, dot matrix set
info
fully displays, entering into startup
interface 3s later
U 100.0 V
I 100.00 A
P 10.00 kW
E 20.125 kWh 3, Set menu: After entering the set
menu, input the correct password to
enter the Set menu display
Note: Press confirm button to enter interface.
main menu check interface.
7
After inputting password 0001, 4, Info Menu: After entering the
entering submenu. info menu, program version
information, protocol and
protocol equipment information
and device ID can be viewed.
Detailed introduction of Set Menu
will be shown in “4.6 Parameters
Settings”.
8
4.6 Parameters Settings
Meter Programming 2, Communication Setting: Press
SPM90 can program the following
to enter communication
setting parameters:
Programmable items interface, communication address
Communication protocol and baud rate can be set, as shown
Communication Setting below. Communication address
range:
1, Communication protocol: Press Baud rate can be set: 2400, 4800,
9600, 19200.
to enter the communication
interface, alternatives of
communication protocol can be set.
Communication protocol can be set:
Modbus and DLT645, as shown
below:
9
5. Measurement Capability
5.1 Real-time Basic Electrical Parameters
SPM90 can measure basic electrical parameters including voltage, current
and power.
Real-time reading Measurement range
Current
Shunt 100A 0 ~ 100A
Shunt 150A 0 ~ 150A
Shunt 200A 0 ~ 200A
Shunt 300A 0 ~ 300A
Shunt 400A 0 ~ 400A
Voltage 2~1000V
Power 2W ~ 400kW
5.1.1 Voltage
Voltage measurement range of SPM90 is 2~1000V. Users should be noted
this to prevent saturation of internal measurement circuit, which may cause
inaccurate measurement.
Note: If “U ERR V” is displayed when voltage is over 50V, it means
that wires on port 1 and 2 are reversely connected.
10
5.1.2 Current
Shunt module is needed when SPM90 measures the current. The shunt is
actually a resistor with very small resistance. Voltage appears when there is
current running through, which can be shown on ampere meter. Shunt
specifications: 100A, 150A, 200A, 300A,400A.
Note: If “I ERR A” is displayed when the meter accessed load, then it
means that wires on the port 3 and 4 are reversely connected.
5.2 Energy Parameters
The maximum energy SPM90 can measure is 999999.999, with three
decimal places. When it reaches the maximum value, it automatically turns
over to 0.
5.3 Electric Energy Pulse
Pulse width fixes at 90ms, pulse constant is 100imp/kWh.
11
6. Communication
6.1 Overview
SPM90 get communicated with 1CH RS485. Please refer to picture shown
below for wiring diagram. In real application, to prevent signal reflection, a
resistor of about 120Ω will be connected at the end of RS485 network for signal
matching. Users should be noted this.
Pic.9 RS485 communication port wiring diagram on SPM90
12
6.2 Communication Media
30 pieces of SPM90 can work together in one network at most, which are
wired via NO. 22 shielded twisted pair. If no repeaters, then the longest
distance of wire should be 1200 meters.
6.3 Communication Protocol
SPM90 is in accordance with the MODBUS-RTU and DL/T 645-2007
protocol, which can be set via the setting interface. For detailed information of
protocol, please refer to the manual of “SPM90_MODBUS Communication
Protocol” and “SPM90_DL/T 645-2007 Communication Protocol”.
6.4 Communication Parameters
Whether the meter can communicate with the master station depends on
whether the communication parameters are correct. Communication
parameters include:
Meter address ID: This is the identification of the meter on the network. It’s
requested that the ID of every meter in the same network is the only one.
Baud rate of communication 1: 2400, 4800, 9600, 19200 are optional.
6.5 Anti Strong Electricity Function of Communication Port
Communication Port on SPM90 supports Anti Strong Electricity Function.
The meter won’t be burnt when wired into strong electricity (380VAC) for a
short time(within 5 mins). Communication function gets back to normal when
strong electricity is removed.
13
7. Technical Parameters
Parameter Range
Rated working
9-36VDC
Rated voltage
Working Rated current 100A、150A、200A、300A、400A
Parameter Rated input
1000VDC
voltage
Parameter Range Accuracy
Voltage 2-1000V 0.2%
Electrical 1% ~120% of rated
Current 0.2%
Parameter current
Accuracy Energy 0~999999.999kWh Class 0.5
Power 2W ~ 400 kW 0.5%
Parameter Performance
Consumption ≤ 1W
Pulse constant 100imp/kWh
Rated voltage of
75mV
shunt
Normal working
-20℃~+55℃
temperature
Extreme working
-25℃~+75℃
temperature
Environment Storage
-30℃~+80℃
Temperature temperature
Working humidity Under 95%
Insulation
≥ 100MΩ
resistance
Impulse voltage 6000V
IP Protection
Complete machine IP20
grade
14
Experimen
Item Reference standard
t grade
ElectroStatic GB/T17626.2-2006
Grade 3
Discharge (IEC61000-4-2:2001)
Radiated immunity
of radiofrequency GB/T17626.3-2006
Grade 4
electromagnetic (IEC61000-4-3:2002)
fields
Electrical fast
GB/T17626.4-2008
transient burst Grade 4
(IEC61000-4-4:2004)
immunity
Surge (impact) GB/T17626.5-2008
Electromagn Grade 4
immunity (IEC61000-4-5:2005)
etic compatib
Conduction
ility
noise immunity GB/T17626.6-2008
Grade 3
of radio-frequency (IEC61000-4-6:2006)
field induction
Electromagnetic e
GB 4824-2013
mission limiting Conformed
(CISPR11:2010)
value
Voltage sag、
shot-time GB/T17626.11-2008
Conformed
interruption (IEC61000-4-11:2004)
immunity
15
8. Appendix
8.1 Terminals Definition
No. Definition Description
1 V+ Positive polarity of voltage input
2 V- Negative polarity of voltage input
3 I+ Positive polarity of voltage input
4 I- Negative polarity of current input
5 485A RS485 positive polarity
6 485B RS485 negative polarity
7 POW- Negative polarity of power input
8 POW+ Positive polarity of power input
9 NC /
10 NC /
11 Pulse- Negative polarity of energy pulse
12 Pulse+ Positive polarity of energy pulse
16
8.2 Typical Wiring Diagram
Wiring of SPM90-1-P is as follows:
PULSE+ 12 8 POW+
PULSE- 11 No Incorrect Connection ! 7 POW-
NC 10 6 485B
NC 9 1 2 4 3 5 485A
V+ input
V- input Shunt LOAD
A B
Between A and B point, do not connect any other device !
Note:
1. If -P is not included in order, then terminal 9, 10, 11, 12 are not added
on the meter.
2. When installing and wiring, meter shall work with the shunt in the
same package. Otherwise, measuring accuracy will be influenced.
3. The current sampling circuit must be connected to the SPM90 and
cannot be mixed with other device. That is, it is not allowed to connect
any other device between A and B point in the above figure to prevent
damage to the instrument due to voltage circuit.
17
Examples of errors:
Example 1
PULSE+ 12 8 POW+
PULSE- 11 7 POW-
NC 10 6 485B
NC 9 1 2 4 3 5 485A
V+ input
V- input QF Shunt LOAD
A B
A circuit breaker is connected
between A and B point, which is
wrong!
Example 2
PULSE+ 12 8 POW+
PULSE- 11 7 POW-
NC 10 6 485B
NC 9 1 2 4 3 5 485A
V+ input
V- input FU Shunt LOAD
A fuse is connected between A
and B point, which is wrong!
18
Notice:
PILOT reserves the right to modify this manual without prior notice in
view of continued improvement.
ZHUHAI PILOT TECHNOLOGY CO., LTD
Add: No. 15, Keji 6 Road, Chuangxin Haian, Tangjia High-tech Zone, Zhuhai,
Guangdong, 519085 China
Tel: +86-0756-6931888 ext 6088
Email:marketing@pmac.com.cn
http://www.pmac.com.cn