3W Auto Impedance Estimator Equations
Given: Max MVA %Zps is Linearized from Empirical Data X/R Ratio is Estimated from ANSI C37.010
(OFAF) %𝑍𝑝𝑠 ≈ 0.0071 𝑂𝑁𝐴𝑁 + 5.225
3
𝑂𝐹𝐴𝑁 = 𝑂𝐹𝐴𝐹
4
3
𝑂𝑁𝐴𝑁 = 𝑂𝐹𝐴𝐹
5
Given: Rated MVA
(ONAN)
5
𝑂𝐹𝐴𝑁 = 𝑂𝑁𝐴𝑁
4
5
𝑂𝐹𝐴𝐹 = 𝑂𝑁𝐴𝑁
3 Positive Sequence
%𝑍
𝑍𝑝𝑠𝑝𝑢 =
100
𝑍𝑝𝑠𝑝𝑢
𝑅𝑝𝑠𝑝𝑢 =
1 + 𝑋𝑅𝑟𝑎𝑡𝑖𝑜 2
2 2
𝑋𝑝𝑠𝑝𝑢 = 𝑍𝑝𝑠𝑝𝑢 − 𝑅𝑝𝑠𝑝𝑢
3W Auto Δ Tertiary
Zpt and Zst
Positive Sequence
ONANTertiary is Estimated as 1/3 ONANPS
1
𝑂𝑁𝐴𝑁𝑇𝑒𝑟𝑖𝑎𝑟𝑦 ≈ 𝑂𝑁𝐴𝑁𝑃𝑆
3
Zpt/Zps is Linearized from Empirical Data Zst/Zps is Linearized from Empirical Data
𝑍𝑝𝑡 ≈ 𝑍𝑝𝑠 0.0022 𝑂𝑁𝐴𝑁𝑇𝑒𝑟𝑖𝑎𝑟𝑦 + 0.9931 𝑍𝑠𝑡 ≈ 𝑍𝑝𝑠 0.0025 𝑂𝑁𝐴𝑁𝑇𝑒𝑟𝑖𝑎𝑟𝑦 + 0.8179
Zero Sequence
Zps0 Zpt0 and Zst0 are Estimated Relative to Positive Sequence
𝑅𝑝𝑠0 = 𝑅𝑝𝑠+ 𝑍𝑝𝑡0 𝑍𝑝𝑠0 𝑅𝑝𝑡+ 𝑋𝑝𝑡+
= 𝑅𝑝𝑡0 = 𝑅𝑝𝑠0 𝑋𝑝𝑡0 = 𝑋𝑝𝑠0
𝑋𝑝𝑠0 ≈ 0.9𝑋𝑝𝑠+ 𝑍𝑝𝑡+ 𝑍𝑝𝑠+ 𝑅𝑝𝑠+ 𝑋𝑝𝑠+
𝑍𝑠𝑡0 𝑍𝑝𝑠0 𝑅𝑠𝑡+ 𝑋𝑠𝑡+
= 𝑅𝑠𝑡0 = 𝑅𝑝𝑠0 𝑋𝑠𝑡0 = 𝑋𝑝𝑠0
𝑍𝑠𝑡+ 𝑍𝑝𝑠+ 𝑅𝑝𝑠+ 𝑋𝑝𝑠+
3W Auto Δ Tertiary (Buried)
this method uses all windings with same MVABase = ONANPS
Zpt and Zst
Positive Sequence
Xpt is Estimated using Xps Xst is Estimated using Xps
3 1
𝑋𝑝𝑡 ≈ 𝑋𝑝𝑠 𝑋𝑠𝑡 ≈ 𝑋𝑝𝑠
2 2
Rpt is Estimated from X/R Ratio Rst is Estimated from X/R Ratio
𝑋𝑝𝑡 𝑋𝑠𝑡
𝑅𝑝𝑡 = 𝑅𝑠𝑡 =
𝑋𝑅𝑟𝑎𝑡𝑖𝑜 𝑋𝑅𝑟𝑎𝑡𝑖𝑜
Zero Sequence
Zps0 Zpt0 and Zst0 are Estimated Relative to Positive Sequence
𝑅𝑝𝑠0 = 𝑅𝑝𝑠+ 𝑍𝑝𝑡0 𝑍𝑝𝑠0 𝑅𝑝𝑡+ 𝑋𝑝𝑡+
= 𝑅𝑝𝑡0 = 𝑅𝑝𝑠0 𝑋𝑝𝑡0 = 𝑋𝑝𝑠0
𝑋𝑝𝑠0 ≈ 0.9𝑋𝑝𝑠+ 𝑍𝑝𝑡+ 𝑍𝑝𝑠+ 𝑅𝑝𝑠+ 𝑋𝑝𝑠+
𝑍𝑠𝑡0 𝑍𝑝𝑠0 𝑅𝑠𝑡+ 𝑋𝑠𝑡+
= 𝑅𝑠𝑡0 = 𝑅𝑝𝑠0 𝑋𝑠𝑡0 = 𝑋𝑝𝑠0
𝑍𝑠𝑡+ 𝑍𝑝𝑠+ 𝑅𝑝𝑠+ 𝑋𝑝𝑠+