P3T32 Relay Manual
P3T32 Relay Manual
www.schneider-electric.com
Transformer protection relay 2 Product introduction
2 Product introduction
2.1 Warranty
This product has a standard warranty of 10 years.
Protection functions
20 P3T/en M/J006
2 Product introduction Transformer protection relay
Virtual injection
Robust hardware
NOTE: If the device has been powered off for more than about one week, the
UMI language after starting is IEC but after about two minutes, it is
automatically updated to ANSI.
P3T/en M/J006 21
Transformer protection relay 2 Product introduction
Table 3 - Applications
4 3
1
Voltage – – –
Feeder P3F30
w.
directional
–
P3L30
w. line diff. &
P3U30 distance
with
Transformer directional P3T32
o/c – with
P3U10 P3U20
with voltage differential
protection
Motor P3M32
P3M30 with
differential
Generator P3G32
P3G30 with
differential
Measuring Phase current 1/5A CT (x3) 1/5A CT (x3) or 1/5A CT (x3) or 1/5A CT (x6)
inputs LPCT (x3) LPCT (x3)2)
Output – 0 or 4 3) 0 or 4 3)
22 P3T/en M/J006
2 Product introduction Transformer protection relay
4 3
1
Communication
IRIG/B ■ ■ ■
Ethernet – ■ ■ ■
IEC 60870-5-101 – ■ ■ ■ ■
IEC 60870-5-103 – ■ ■ ■ ■
DNP3 Over – ■ ■ ■ ■
Ethernet
Modbus serial – ■ ■ ■ ■
Modbus TCP/IP – ■ ■ ■ ■
Ethernet/IP – ■ ■ ■ ■
Profibus DP – ■ ■ ■ ■
SPAbus – ■ ■ ■ ■
Redundancy RSTP – ■ ■ ■ ■
protocols
PRP – ■ ■ ■ ■
Others
Logic Matrix ■ ■
Logic equations ■ ■
P3T/en M/J006 23
Transformer protection relay 2 Product introduction
Withdrawability (Pluggable ■ –
connector)
Remote UMI – ■
NOTE: The numbers in the following tables represent the amount of stages
available for each Easergy P3 type.
Protection functions ANSI Feeder Feeder P3U30 Motor P3U10/20 Motor P3U30
code P3U10/20
Synchronism check5) 25 – 2 – 2
Undervoltage 27 – 3 – 3
Phase undercurrent 37 1 1 1 1
Negative sequence 46 – – 2 2
overcurrent (motor,
generator)
Negative sequence 47 – 3 – 3
overvoltage protection
Thermal overload 49 1 1 1 1
SOTF 50HS 1 1 1 1
Voltage-dependent 51V – 1 – 1
overcurrent
Overvoltage 59 – 3 – 3
24 P3T/en M/J006
2 Product introduction Transformer protection relay
Protection functions ANSI Feeder Feeder P3U30 Motor P3U10/20 Motor P3U30
code P3U10/20
CT supervision 60 1 1 1 1
VT supervision 60FL – 1 – 1
Directional phase 67 – 4 – 4
overcurrent
Auto-Recloser 79 5 5 – –
Lockout 86 1 1 1 1
Programmable stages 99 8 8 8 8
Programmable curves – 3 3 3 3
Setting groups 8) – 4 4 4 4
5) The availability depends on the selected voltage measurement mode (in the Scaling setting view in Easergy Pro)
6) Using external RTD module
7) Capacitor bank unbalance protection is connected to the ground fault overcurrent input and shares two stages with the ground fault
overcurrent protection.
8) Not all protection functions have 4 setting groups. See details in the manual.
Protection functions ANSI P3F30 P3L30 P3M30 P3M32 P3G30 P3G32 P3T32
code
Distance 21 – 1 – – – – –
Under-impedance 21G – – – – 2 2 –
Overfluxing 24 – – – – 1 1 1
P3T/en M/J006 25
Transformer protection relay 2 Product introduction
Protection functions ANSI P3F30 P3L30 P3M30 P3M32 P3G30 P3G32 P3T32
code
Synchronism check9) 25 2 2 2 2 2 2 2
Undervoltage 27 3 3 3 3 3 3 3
Phase undercurrent 37 – – 1 1 – – –
Loss of field 40 – – – – 1 1 –
Under-reactance 21/40 – – – – 2 2 –
Negative sequence 46 – – 2 2 2 2 2
overcurrent (motor,
generator)
Negative sequence 47 3 3 3 3 3 3 3
overvoltage protection
Thermal overload 49 1 1 1 1 1 1 1
SOTF 50HS 1 1 1 1 1 1 1
Voltage-dependent 51V 1 1 – – 1 1 –
overcurrent
Overvoltage 59 3 3 3 3 3 3 3
CT supervision 60 1 1 1 1 1 2 2
VT supervision 60FL 1 1 1 1 1 1 1
26 P3T/en M/J006
2 Product introduction Transformer protection relay
Protection functions ANSI P3F30 P3L30 P3M30 P3M32 P3G30 P3G32 P3T32
code
Directional phase 67 4 4 4 4 4 4 4
overcurrent
Auto-Recloser 79 5 5 – – – – –
Over or under frequency 81 2/2 2/2 2/2 2/2 2/2 2/2 2/2
Lockout 86 1 1 1 1 1 1 1
Programmable stages 99 8 8 8 8 8 8 8
Programmable curves – 3 3 3 3 3 3 3
overcurrent protection.
12) Not all protection functions have 4 setting groups. See details in the manual.
P3T/en M/J006 27
Transformer protection relay 2 Product introduction
Control functions P3U10/ P3U30 P3F30 P3L30 P3M30 P3M32 P3G30 P3G32 P3T32
20
Switchgear monitoring – – 2 2 2 2 2 2 2
only
Programmable switchgear ■ ■ ■ ■ ■ ■ ■ ■ ■
interlocking
Local/remote function ■ ■ ■ ■ ■ ■ ■ ■ ■
Function keys 2 2 2 2 2 2 2 2 2
Table 8 - Measurements
Measurement P3U10/ P3U30 P3F30 P3L30 P3M30 P3M32 P3G30 P3G32 P3T32
20
Frequency ■ ■ ■ ■ ■ ■ ■ ■ ■
Fundamental frequency – ■ ■ ■ ■ ■ ■ ■ ■
voltage values
Fundamental frequency – ■ ■ ■ ■ ■ ■ ■ ■
active, reactive and
apparent power values
Power factor – ■ ■ ■ ■ ■ ■ ■ ■
28 P3T/en M/J006
2 Product introduction Transformer protection relay
Measurement P3U10/ P3U30 P3F30 P3L30 P3M30 P3M32 P3G30 P3G32 P3T32
20
Harmonic values of – ■ ■ ■ ■ ■ ■ ■ ■
voltage and THD
Logs and Records P3U10/ P3U30 P3F30 P3L30 P3M30 P3M32 P3G30 P3G32 P3T32
20
Disturbance record ■ ■ ■ ■ ■ ■ ■ ■ ■
P3T/en M/J006 29
Transformer protection relay 2 Product introduction
P3U10/
Monitoring functions P3U30 P3F30 P3L30 P3M30 P3M32 P3G30 P3G32 P3T32
20
Relay monitoring ■ ■ ■ ■ ■ ■ ■ ■ ■
NOTE: To log on via the front panel, you need a password that consists of
letters, digits, or other characters in the scope of ASCII 0x21~0x7E.
1. Press and on the front panel. The Enter password view opens.
30 P3T/en M/J006
2 Product introduction Transformer protection relay
Select a digit value using , and if the password is longer than one digit,
move to the next digit position using .
NOTE: There are 16 digit positions in the Enter password view. Enter the
password starting from the first digit position.
For example, if the password is 2, you can enter 2***, **2*, ***2, or 0002
to log on.
Related topics
2.4.3 Password management
NOTICE
CYBERSECURITY HAZARD
To improve cybersecurity:
• Change all passwords from their default values when taking the protection
device into use.
• Change all passwords regularly.
• Ensure a minimum level of password complexity according to common
password guidelines.
You can change the password for the operator or configurator user accounts in
the General > Device info setting view in Easergy Pro.
The password can contain letters, digits or other characters in the scope of ASCII
0x21~0x7E. However, the new password cannot be any of the default passwords
(digits 0–4 or 9999).
Follow these guidelines to improve the password complexity and thus device
security:
• Use a password of minimum 8 characters.
• Use alphabetic (uppercase and lowercase) and numeric characters in addition
to symbols.
• Avoid character repetition, number or letter sequences and keyboard patterns.
P3T/en M/J006 31
Transformer protection relay 2 Product introduction
Also, all users must be aware of the best practices concerning passwords
including:
• not sharing personal passwords
• not displaying passwords during password entry
• not transmitting passwords in email or by other means
• not saving the passwords on PCs or other devices
• no written passwords on any supports
• regularly reminding users about the best practices concerning passwords
Related topics
2.4.2 Logging on via the front panel
If you have lost or forgotten all passwords, contact Schneider Electric to restore
the default passwords.
A
A B D
D E F
F
F1 F2
I
A GJ
J GG
B B GC
B
C G
E J
D H
F
32 P3T/en M/J006
2 Product introduction Transformer protection relay
2.5.1 Push-buttons
Symbol Function
14) The default names of the function buttons are Function button 1 and 2. You can change the names
of the buttons in the Control > Names for function buttons setting view.
When the relay is powered, the power LED is green. During normal use, the
service LED is not active, it activates only when an error occurs or the relay is not
operating correctly. Should this happen, contact your local representative for
further guidance. The service LED and watchdog contact are assigned to work
together. Hardwire the status output into the substation's automation system for
alarm purposes.
The user-configurable LEDs may be red or green. You can configure them via
Easergy Pro.
P3T/en M/J006 33
Transformer protection relay 2 Product introduction
To customize the LED texts on the front panel for the user-configurable LEDs, the
text may be created using a template and then printed. The printed text may be
placed in the pockets beside the LEDs.
You can also customize the LED texts that are shown on the screen for active
LEDs via Easergy Pro.
2. To change a LED name, click the LED Description text and type a new
name. To save the new name, press Enter.
34 P3T/en M/J006
2 Product introduction Transformer protection relay
You can enable or disable the alarm screen either via the relay's local display or
using Easergy Pro:
NOTE: By nature, the LCD display changes its contrast depending on the
ambient temperature. The display may become dark or unreadable at low
temperatures. However, this condition does not affect the proper operation of
the protection or other functions.
P3T/en M/J006 35
Transformer protection relay 2 Product introduction
You can start the test sequence in any main menu window.
1. Press .
2. Press .
The relay tests the LCD screen and the functionality of all LEDs.
Prerequisite: You have logged in with the correct password and enabled selective
control in the Objects setting view.
– Press to cancel.
• Press to trip an object.
– Press to cancel.
Prerequisite: You have logged in with the correct password and enabled direct
control in the Objects setting view.
When direct control is enabled, the control operation is done without confirmation.
• Press to close an object.
• Press to trip an object.
2.5.10 Menus
This section gives an overview of the menus that you can access via the device's
front panel.
Press the right arrow to access more measurements in the main menu.
36 P3T/en M/J006
2 Product introduction Transformer protection relay
P3T/en M/J006 37
Transformer protection relay 2 Product introduction
38 P3T/en M/J006
2 Product introduction Transformer protection relay
OK
I pick-up setting
OK OK
P3T/en M/J006 39
Transformer protection relay 2 Product introduction
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC
FLASH
• General
• Measurements
• Inputs/outputs
• Protection
• Matrix
• Logs
• Communication
The contents of the tabs depend on the relay type and the selected application
mode.
Easergy Pro stores the relay configuration in a setting file. The configuration of
one physical relay is saved in one setting file. The configurations can be printed
out and saved for later use.
NOTICE
HAZARD OF EQUIPMENT DAMAGE
40 P3T/en M/J006
Transformer protection relay 5 Control functions
5 Control functions
Any internal signal can be connected to the digital outputs in the Matrix > Arc
matrix - output setting views.
The Output matrix and Relays setting views represent the state (de-energized /
energized) of the digital output's coil. For example, a bright green vertical line in
the Output matrix and a logical "1" in the Relays view represent the energized
state of the coil. The same principle applies for both NO and NC type digital
outputs. The actual position (open / closed) of the digital outputs' contacts in coil's
de-energized and energized state depends on the type (NO / NC) of the digital
outputs. De-energized state of the coil corresponds to the normal state of the
contacts. A digital output can be configured as latched or non-latched. 5.5
Releasing latches describes releasing latches procedure.
The difference between trip contacts and signal contacts is the DC breaking
capacity. The contacts are single pole single throw (SPST) normal open (NO)
type, except signal relay A1 which has a changeover contact single pole double
throw (SPDT).
In addition to this, the relay has so called heavy duty outputs available in the
power supply modules C and D. For more details, see Table 157.
Programming matrix
68 P3T/en M/J006
5 Control functions Transformer protection relay
NOTE: Logic outputs are assigned automatically in the output matrix as well
when logic is built.
Trip contact status can be viewed and forced to operate in the Relays setting
view. Logical "0" means that the output is not energized and logical "1" states that
the output is set active.
P3T/en M/J006 69
Transformer protection relay 5 Control functions
Enable NO / NC outputs in the Polarity setting view for the signals shown.
Default numbering of DI / DO
Every option card and slot has default numbering. Below is an example of model
P3x30 CGGII-AAEAA-BA showing the default numbering of digital outputs.
You can see the default digital output numbering and change the numbering of
the following option cards in the Inputs/Outputs > Relay config setting view: slot
2, 3, 4, 5: G, I.
70 P3T/en M/J006
5 Control functions Transformer protection relay
Power supply card outputs are not visible in the Relay config setting view.
P3T/en M/J006 71
Transformer protection relay 5 Control functions
The polarity normal open (NO) / normal closed (NC) and a delay can be
configured according to the application by using the front panel or Easergy Pro.
Digital inputs can be used in many operations. The status of the input can be
checked in the Output matrix and Digital inputs setting views. The digital inputs
make it possible to change group, block/enable/disable functions, to program
logics, indicate object status, etc.
The digital inputs require an external control voltage (ac or dc). The digital inputs
are activated after the activation voltage is exceeded. Deactivation follows when
the voltage drops below threshold limit. The activation voltage level of digital
inputs can be selected in the order code when such option cards are equipped.
72 P3T/en M/J006
5 Control functions Transformer protection relay
Digital inputs can be viewed, named and changed between NO/NC in the Digital
inputs and Names for digital inputs setting views.
P3T/en M/J006 73
Transformer protection relay 5 Control functions
All essential information on digital inputs can be found in the same location in the
Digital inputs setting view. DI on/off events and alarm display (pop-up) can be
enabled and disabled in Digital inputs setting view. Individual operation counters
are located in the same view as well.
Label and description texts can be edited with Easergy Pro according to the
demand. Labels are the short parameter names used on the local panel and
descriptions are the longer names used by Easergy Pro.
Digital input delay determines the activation and de-activation delay for the input.
Figure 25shows how the digital input behaves when the delay is set to 1 second.
1
VOLTAGE
0
1
DIGITAL INPUT
0
74 P3T/en M/J006
5 Control functions Transformer protection relay
For normal
closed contacts
(NC)
Active edge is 1
>0
P3T/en M/J006 75
Transformer protection relay 5 Control functions
Default is "DI1 –
DIx". x is the
maximum
number of the
digital input.
x is the
maximum
number of the
digital input.
24) Set = An editable parameter (password needed).
Every option card and slot has default numbering. After making any changes to
the numbering, read the settings from the relay after the relay has rebooted.
You can see the default digital input numbering and change the numbering of the
following option cards in the Inputs/Outputs > Digital inputs setting view: slot 2,
3, 4, 5: G, I.
76 P3T/en M/J006
5 Control functions Transformer protection relay
C: -
G: DI1–6
G: DI7–12
I: DI13–22
I: DI23–32
P3T/en M/J006 77
Transformer protection relay 5 Control functions
Virtual inputs can be used in many operations. The status of the input can be
checked in the Matrix > Output matrix and Control > Virtual inputs setting
views. The status is also visible on local mimic display, if so selected. Virtual
inputs can be selected to be operated with the function buttons F1 and F2, the
local mimic or simply by using the virtual input menu. Virtual inputs have similar
functions as digital inputs: they enable changing groups, block/enable/disable
functions, to program logics and other similar to digital inputs.
Number of outputs 20
Figure 28 - Virtual inputs and outputs can be used for many purpose in the
Output matrix setting view.
Virtual inputs and outputs can be used for many purposes in the Output matrix
setting view.
78 P3T/en M/J006
5 Control functions Transformer protection relay
Virtual inputs
The virtual inputs can be viewed, named and controlled in the Control > Virtual
inputs setting view.
P3T/en M/J006 79
Transformer protection relay 5 Control functions
Off
Default is "VIn",
n = 1–20
80 P3T/en M/J006
5 Control functions Transformer protection relay
Virtual outputs
In Easergy Pro, the Virtual outputs setting view is located under Control.
P3T/en M/J006 81
Transformer protection relay 5 Control functions
Off
82 P3T/en M/J006
5 Control functions Transformer protection relay
5.4 Matrix
The relay has several matrices that are used for configuring the relay:
• Output matrix used to link protection stage signals, digital inputs, virtual
inputs, function buttons, object control, logic output, relay's internal alarms,
GOOSE signals and release latch signals to outputs, disturbance recorder trig
input and virtual outputs
• Block matrix used to block protection stages
• LED matrix used to control LEDs on the front panel
• Object block matrix used to inhibit object control
• Auto-recloser matrix used to control auto-recloser
• Arc matrix used to control current and light signals to arc stages and arc
stages to the high-speed outputs
Virtual
inputs
Digital n
inputs
n Output relays Virtual
optional
DI delay and indicators outputs
n
and
inversion n
Output contacts
NOTE: Blocking matrix can not be used to block the arc flash detection
stages.
There are general-purpose LED indicators – "A", "B", "C" to ”N” – available for
customer-specific indications on the front panel. Their usage is define in a
separate LED matrix.
There are two LED indicators specified for keys F1 and F2. The triggering of the
disturbance recorder (DR) and virtual outputs are configurable in the output
matrix.
There is a common "release all latches" signal to release all the latched relays.
This release signal resets all the latched digital outputs and indicators. The reset
signal can be given via a digital input, via front panel or remotely through
P3T/en M/J006 83
Transformer protection relay 5 Control functions
Trip and alarm relays together with virtual outputs can be assigned in the output
matrix. Also automatic triggering of disturbance recorder is done in the output
matrix.
By means of a blocking matrix, the operation of any protection stage (except the
arc flash detection stages) can be blocked. The blocking signal can originate from
the digital inputs or it can be a start or trip signal from a protection stage or an
output signal from the user's programmable logic. In Figure 36, an active blocking
is indicated with a black dot (●) in the crossing point of a blocking signal and the
signal to be blocked.
All protection stages (except Arc stages) can be blocked in the block matrix
The Blocked status becomes visible only when the stage is about to activate.
84 P3T/en M/J006
5 Control functions Transformer protection relay
Figure 38 - Result for the I> stage when the DI is active and the stage exceeds its
current start value
NOTICE
RISK OF NUISANCE TRIPPING
The LED matrix is used to link digital inputs, virtual inputs, function buttons,
protection stage outputs, object statuses, logic outputs, alarm signals and
GOOSE signals to various LEDs located on the front panel.
In the LED configuration setting view, each LED has three checkboxes with
which the behavior of the LED is configured.
LEDs are assigned to control signals in the LED matrix setting view. It is not
possible to control LEDs directly with logics.
P3T/en M/J006 85
Transformer protection relay 5 Control functions
Normal setting
With no checkboxes selected, the assigned LED is active when the control signal
is active. After deactivation, the LED turns off. LED activation and deactivation
delay when controlled is approximately 10 ms.
Latch setting
A latched LED activates when the control signal activates but remains active
when the control signal deactivates. Latched LEDs are released using the
procedure described in 5.5 Releasing latches.
Blink setting
When the Blink setting is selected, the LED blinks when it is active.
Store setting
In the LED configuration setting view, you can configure the latched states of
LEDs to be stored after a restart. In Figure 39, storing has been configured for
LED A (green).
Inputs for LEDs can be assigned in the LED matrix. All 14 LEDs can be assigned
as green or red. The connection can be normal, latched or blink-latched. In
addition to protection stages, there are lots of functions that can be assigned to
output LEDs. See Table 33.
86 P3T/en M/J006
5 Control functions Transformer protection relay
Digital/Virtual inputs LED A–N Normal/ Latched/ All different type of Set
and function buttons BlinkLatch inputs can be assigned
green or red
to LEDs
Local control enabled LED A–N Normal/ Latched/ While remote/local Set
BlinkLatch state is selected as
green or red
local the “local control
enabled” is active
Logic output 1–20 LED A–N Normal/ Latched/ All logic outputs can be Set
BlinkLatch assigned to LEDs at
green or red
the LED matrix
Manual control LED A–N Normal/ Latched/ When the user has Set
indication BlinkLatch controlled the
green or red
objectives
COM 1–5 comm. LED A–N Normal/ Latched/ When the Set
BlinkLatch communication port 1 -
green or red
5 is active
Setting error, seldiag LED A–N Normal/ Latched/ Self diagnostic signal Set
alarm, pwd open and BlinkLatch
green or red
setting change
GOOSE NI1–64 LED A–N Normal/ Latched/ IEC 61850 goose Set
BlinkLatch communication signal
green or red
The object block matrix is used to link digital inputs, virtual inputs, function
buttons, protection stage outputs, logic outputs, alarm signals and GOOSE
signals to inhibit the control of objects, that is, circuit breakers, isolators and
grounding switches.
Typical signals to inhibit controlling of the objects like circuit breaker are:
P3T/en M/J006 87
Transformer protection relay 5 Control functions
These and other signals are linked to objects in the object block matrix.
There are also event-type signals that do not block objects as they are on only for
a short time, for example "Object1" open and "Object1 close" signals.
2. From the Easergy Pro toolbar, select Device > Release all latches.
Alternatively, go to Control > Release latches, and click the Release button.
88 P3T/en M/J006
5 Control functions Transformer protection relay
1. Press .
2. Press .
You can use the function buttons F1 or F2 to release all latches after configuring
this function in Easergy Pro. You can make the configuration either under Control
> Release Latches or under Control > Function buttons.
After this, pressing the F1 button on the relay’s front panel releases all
latches.
• To configure F1 to release latches under Control >Function buttons:
a. Under Function buttons, for F1, select PrgFncs from the Selected
control drop down menu.
c. Under Programmable functions for F1, select “On” from the Release all
latches drop-down menu.
P3T/en M/J006 89
Transformer protection relay 5 Control functions
After this, pressing the F1 button on the relay's front panel releases all
latches.
NOTE: The latch release signal can be activated only if the latched
output is active.
Object states
Open
Close
Undefined (11)
90 P3T/en M/J006
5 Control functions Transformer protection relay
Max ctrl pulse length 0.02–600 s Pulse length for open and
close commands. Control
pulse stops once object
changes its state
If changing the states takes longer than the time defined by the “Max ctrl pulse
length” setting, the object is inoperative and the “Object failure” matrix signal is
set. Also, an undefined event is generated. “Completion timeout” is only used for
the ready indication. If “DI for ‘obj ready’” is not set, the completion timeout has no
meaning.
These signals send control pulse when an object is controlled by digital input,
remote bus, auto-reclose etc.
Objects can be controlled with digital inputs, virtual inputs or virtual outputs. There
are four settings for each object:
Setting Active
If the relay is in local control state, the remote control inputs are ignored and vice
versa. An object is controlled when a rising edge is detected from the selected
input. The length of digital input pulse should be at least 60 ms.
P3T/en M/J006 91
Transformer protection relay 5 Control functions
In local mode, digital outputs can be controlled via the front panel but they cannot
be controlled via a remote serial communication interface.
In remote mode, digital outputs cannot be controlled via a front panel but they can
be controlled via a remote serial communication interface.
The local or remote mode can be selected by using the front panel or via one
selectable digital input. The digital input is normally used to change a whole
station to local or remote mode. You can select the L/R digital input in the Control
> Objects setting view in Easergy Pro.
The relay also has dedicated control buttons for objects. Close stands for object
closing and Trip controls object open command internally. Control buttons are
configured in the Control > Objects setting view.
92 P3T/en M/J006
5 Control functions Transformer protection relay
Button
opens selected
object if
password is
enabled
Control
operation is
done without
confirmation
You can configure the button funtions in the Control > Function buttons setting
view in Easergy Pro.
P3T/en M/J006 93
Transformer protection relay 5 Control functions
If ObjCtrl has been selected under Selected control, the selected object is
shown under Selected object. Otherwise, this column is empty.
When selecting ObjCtrl, link the function button to the appropriate object in the
Control > Objects setting view.
Logic functions No. of gates Max. no. of input Max. no. of logic
reserved gates outputs
AND 1
32
OR 1
(An input gate can 20
XOR 1 include any number
of inputs.)
AND+OR 2
94 P3T/en M/J006
5 Control functions Transformer protection relay
Logic functions No. of gates Max. no. of input Max. no. of logic
reserved gates outputs
CT (Count+Reset) 2
INVAND 2
INVOR 2
OR+AND 2
RS (Reset+Set) 2
The logic is operational as long the memory consumption of the inputs, gates or
outputs remains individually below or equal to 100%.
P3T/en M/J006 95
Transformer protection relay 5 Control functions
Truth tables
AND In Out
A Y
&
A Y
0 0
1 1
A Y In Out
&
A Y
0 1
1 0
A Y In Out
&
A B Y
B
0 1 0
1 0 0
1 1 1
0 0 0
A Y In Out
& A B Y
B
0 1 1
1 0 1
1 1 0
0 0 1
AND+OR A In Out
& Y
>1 A B Y
B
0 0 0
1 1 1
1 0 1
0 1 1
96 P3T/en M/J006
5 Control functions Transformer protection relay
CT (Count+Reset) A In Out
Count
Y
CT A B Y Y
Reset
B
Cou Rese Setti New
nt t ng
1 3 0
1 3 0
1 3 1
1 3 0
INVAND In Out
A Y
¬& A B Y
B 0 0 0
1 0 1
1 1 0
0 1 0
INVOR A Y In Out
¬>1 A B Y
B 0 0 1
1 1 1
1 0 1
0 1 0
P3T/en M/J006 97
Transformer protection relay 5 Control functions
OR A Y In Out
>1 A B Y
B
0 0 0
1 1 1
1 0 1
0 1 1
A Y In Out
>1
A B Y
B
0 0 1
1 1 0
1 0 0
0 1 0
A In Out
Y
B >1 A B C Y
C
0 0 0 1
1 1 0 1
1 0 0 1
0 1 0 1
1 1 1 1
A In Out
Y
B >1 A B C Y
C
0 0 0 1
1 0 0 0
1 1 0 0
0 1 0 0
1 1 1 0
98 P3T/en M/J006
5 Control functions Transformer protection relay
OR+AND A In Out
&
Y
>1 A B Y
B
0 0 0
1 1 1
1 0 0
0 1 0
RS (Reset+Set) A In Out
Set
Y
RS A B Y
Reset
B Set Reset Y
1 0 1
0 0 129)
0 0 030)
X 1 031)
29) Output = 1 (latched), if
previous state was 1, 0, 1.
30) Output = 0, if previous state
was X, 1, 0.
31) Output = 0, if RESET = 1
P3T/en M/J006 99
Transformer protection relay 5 Control functions
RS_D (Set+D+Load+Reset) A B C D Y
A
Set D Loa Re Stat
1 X X 0 1
1 X X 1 0
0 1 0 0 0
0 1 1 0 1
0 1 1 1 033)
32) Initial
state
33) Thestate remains 1 until
Reset is set active
X = Any state
XOR In Out
A
Y
B =1 A B C Y
C
0 0 0 0
0 0 1 1
0 1 0 1
0 1 1 0
1 0 0 1
1 0 1 0
1 1 0 0
1 1 1 1
After you have selected the required logic gate in Easergy Pro, you can change
the function of the gate in the Element properties window by clicking the gate.
Table 39 - Settings available for the logical gates depending on the selected
element
Property Description
Element properties
OFF delay Time delay for how long the gate remain
active even the logical condition is reset
Inputs
Property Description
All the main menus are located on the left side of the display. To get to a
submenu, move up and down the main menus.
The mimic view is set as the local panel's main view as default. You can modify
the mimic according to the application or disable it, if it is not needed, via the
Easergy Pro setting tool.
You can modify the mimic in the General > Mimic setting view in Easergy Pro
and disable the mimic view in the General > Local panel conf setting view.
NOTE: The mimic itself or the local mimic settings cannot be modified via the
local panel.
C A B F I G H F J
D
E
I
A. To clear an object or drawing, first point an F. The remote/local selection defines whether
empty square (A) with the mouse. Then point the certain actions are granted or not. In remote
object item with the mouse. The color of the object state, it is not possible to locally enable or
item turns red. To clear the whole mimic, click on disable auto-reclosing or to control objects. The
the empty area. remote/local state can be changed in Control >
Objects.
B. Text tool G. Creates auto-reclosing on/off selection to
mimic.
C. To move an existing drawing or object, point it H. Creates virtual input activation on the local
with the mouse. The color turns green. Hold down mimic view.
the left mouse button and move the object.
D. Different type of configurable objects. The I. Describes the relay's location. Text comes
object's number corresponds to the number in from the relay info menu.
Control > Objects.
E. Some predefined drawings. J. Up to six configurable measurements.
Set = Settable.
You can modify the local panel configuration in the General > Local panel conf
setting view in Easergy Pro.
f, P, Q, S, P.F.
CosPhi
ARStart,
ARFaill,
ARShot1–5
IFLT
Starts, Trips
IN Calc
Phase
currents
IA–Cda
IA–C max
IA–C min
IA–CdaMax
Pda, Qda,
Sda
T
fSYNC,
VSYNC
IA-2–IC-2
dIA–C
VAI1–5
ExtAI1–636)
SetGrp
When selected,
the mimic is the
local panel's
default main
view. When
unselected, the
measurement
view is the
default main
view.
6 Protection functions
Each protection stage can independently be enabled or disabled according to the
requirements of the intended application.
The condition to be fulfilled by the CT saturation current (Isat) depends on the type
of overcurrent protection operate time.
IDMT Isat > 1.5 x the curve value which is the smallest of these two values:
• Isc max., maximum installation short-circuit current
• 20 x Is (IDMT curve dynamic range)
A B
t t
I I
Is Isat Is Isat
C D
The method for calculating the saturation current depends on the CT accuracy
class.
Table 43 - CT requirements
For 5 A: Vk > 150 x (Rct + Rw); for example: 150 x 0.53 = 79.5 V
If the resistance Rct is known, it is possible to calculate the actual CT ALF which
takes account of the actual CT load. The saturation current equals the actual ALF
x Inp.
Equation 3
To have an ALF of at least 20, that is, a saturation current of 20 x Inp = 2 kA, the
load resistance Rw of the CT must be less than Equation 4.
Equation 4
VAct 2.5
Rw, max = 2 = = 0.1Ω
Ins 52
This represents 12 m (39 ft) of wire with cross-section 2.5 mm² (AWG 14) for a
resistance per unit length of approximately 8 Ω/km (2.4 mΩ/ft). For an installation
with 50 m (164 ft) of wiring with section 2.5 mm² (AWG 14), Rw = 0.4 Ω.
Equation 5
Equation 6
Vk Inp
Isat = ×
Rct + Rw Ins
CT Vk Rct Rw Saturation
Transformati current
on ratio
Two REF schemes are possible: the Low impedance REF and the High
impedance REF.
The Low impedance REF protection should be used with power networks X/R
only up to 15.
‘K’ depends on X/R and the maximum through-fault current (three-phase fault
current) as defined in Table 45.
Table 45 - K factor
X/R <= 10 45 60 70
X/R <= 15 55 70 80
For power system with an X/R ratio above 15, or when the above CT
requirements cannot be met, the high impedance REF protection shall be used
instead.
The CT requirements for high impedance REF are given in the Application Note
"P3APS17016EN_(HiZ-REF_87N)".
NOTE: The high impedance REF must use a different winding of the primary
CT than the Transformer Differential.
Table 46 - CT settings
Parameter Value
Slope1 50%
Slope2 150%
For maximum sub-synchronous through fault above 7 In and below 9 In, K = 25.
The minimum rated burden is SVA > ((K / Kalf) x (RCT + Rba) – RCT) x Isr2
where kalf is the CT accuracy limit factor (i.e. 20 for 5P20, i.e. 10 for 5P10)
B
C
E F
G D
H IEC 1263/2000
A. Current F. Ip
B. Top envelope G. A
C. d.c. component Id.c. of the short-circuit current H. Bottom envelope
D. 2√2 I’k I. Time
E. 2√2 Ik
For accuracy, class PX or class 5P CTs are recommended but TPY or 5PR can
also be used.
The CT requirements are based on the following settings based on the rated
current of the transformer “In”:
Table 47 - CT settings
Parameter Value
Slope1 50%
Slope2 150%
The maximum through fault measured by the protection device must be limited to
15 In. Thus, choose the CT ratio carefully to meet this requirement. With a
through fault flowing from both sides, choose the highest one.
For power network X/R up to 10 and for all the above-listed CT classes, K = 30.
7 15
X/R up to 10 TPX - 5P 30
TPY - 5PR
X/R up to 60 TPX - 5P 55
TPY - 5PR 30 40
5 7 15
X/R up to 10 TPX - 5P 30 33
TPY - 5PR
X/R up to 60 TPX - 5P 55 70
TPY - 5PR 30 40
K = 20
K = 20
The minimum rated burden is SVA > ((K / Kalf) x (RCT + Rba) – RCT) x Isr2
where Kalf is the CT accuracy limit factor (20 for 5P20, 10 for 5P10)
The individual protection stage and total load status can be found in the
Protection > Protection stage status setting view in the Easergy Pro setting
tool.
Setting groups are controlled by using digital inputs, function keys or virtual
inputs, via the front panel or custom logic. When none of the assigned inputs are
active, the setting group is defined by the parameter ‘SetGrp no control state’.
When controlled input activates, the corresponding setting group is activated as
well. If the control signal of the setting group is lost, the setting “Keep last” forces
the last active group into use. If multiple inputs are active at the same time, the
active setting group is defined by ‘SetGrp priority’. By using virtual I/O, the active
setting group can be controlled using the local panel display, any communication
protocol or the built-in programmable logic functions. All protection stages have
four setting groups.
Example
Any digital input can be used to control setting groups but in this example, DI1,
DI2, DI3 and DI4 are chosen to control setting groups 1 to 4. This setting is done
with the parameter “Set group x DI control” where x refers to the desired setting
group.
Use the 'SetGrp common change' parameter to force all protection stages to
group 1, 2, 3 or 4. The control becomes active if there is no local control in the
protection stage. You can activate this parameter using Easergy Pro.
Assuming that DI2 and DI3 are active at the same time and SetGrp priority is set
to “1 to 4”, setting group 2 becomes active. If SetGrp priority is reversed, that is,
set to “4 to 1”, the setting group 3 becomes active.
• Ok = ‘-‘
The stage is idle and is measuring the analog quantity for the protection. No
power system fault detected.
• Blocked
The blocking reason may be an active signal via the block matrix from other
stages, the programmable logic or any digital input. Some stages also have built-
in blocking logic. For more details about the block matrix, see 5.4.2 Blocking
matrix.
Each protection stage has start and trip counters that are incremented when the
stage starts or trips. The start and trip counters are reset on relay reboot.
There is a "Forcing flag" parameter which, when activated, allows forcing the
status of any protection stage to be "start" or "trip" for half a second. By using this
forcing feature, current or voltage injection is not necessary to check the output
matrix configuration, to check the wiring from the digital outputs to the circuit
breaker and also to check that communication protocols are correctly transferring
event information to a SCADA system.
After testing, the forcing flag is automatically reset five minutes after the last local
panel push button activity.
The force flag also enables forcing the digital outputs and the optional mA
outputs.
The force flag can be found in the Device/Test > Relays setting view.
Every protection stage has two internal binary output signals: start and trip. The
start signal is issued when a fault has been detected. The trip signal is issued
after the configured operation delay unless the fault disappears before the end of
the delay time.
Start level
> Start
Output matrix
Using the output matrix, you can connect the internal start and trip signals to the
digital outputs and indicators. For more details, see 5.4.1 Output matrix.
Blocking
Any protection function, except for arc flash detection, can be blocked with
internal and external signals using the block matrix (5.4.2 Blocking matrix).
Internal signals are for example logic outputs and start and trip signals from other
stages and external signals are for example digital and virtual inputs.
Some protection stages have also built-in blocking functions. For example under-
frequency protection has built-in under-voltage blocking to avoid tripping when the
voltage is off.
When a protection stage is blocked, it does not start if a fault condition is
detected. If blocking is activated during the operation delay, the delay counting is
frozen until the blocking goes off or the start reason, that is the fault condition,
disappears. If the stage is already tripping, the blocking has no effect.
The operate time in the dependent time mode is dependent on the magnitude of
the injected signal. The bigger the signal, the faster the stage issues a trip signal
and vice versa. The tripping time calculation resets if the injected quantity drops
below the start level.
IDMT DT
t (s)
If (A)
The operate time in the definite time mode is fixed by the Operation delay
setting. The timer starts when the protection stage activates and counts until the
set time has elapsed. After that, the stage issues a trip command. Should the
protection stage reset before the definite time operation has elapsed, then the
stage resets.
By default, the definite time delay cannot be set to zero because the value
contains processing time of the function and operate time of the output contact.
This means that the time indicated in the Definite time setting view is the actual
operate time of the function. Use the Accept zero delay setting in the protection
stage setting view to accept the zero setting for definite time function. In this case,
the minimum operate time of the function must be tested separately.
Overshoot time
Overshoot time is the time the protection device needs to notice that a fault has
been cleared during the operate time delay. This parameter is important when
grading the operate time delay settings between devices.
tFAULT
tRET < 50 ms
TRIP CONTACTS
If the delay setting would be slightly shorter, an unselective trip might occur (the
dash line pulse).
For example, when there is a big fault in an outgoing feeder, it might start both the
incoming and outgoing feeder relay. However, the fault must be cleared by the
outgoing feeder relay and the incoming feeder relay must not trip. Although the
operating delay setting of the incoming feeder is more than at the outgoing feeder,
the incoming feeder might still trip if the operate time difference is not big enough.
The difference must be more than the overshoot time of the incoming feeder relay
plus the operate time of the outgoing feeder circuit breaker.
Figure 60 shows an overvoltage fault seen by the incoming feeder when the
outgoing feeder clears the fault. If the operation delay setting would be slightly
shorter or if the fault duration would be slightly longer than in the figure, an
unselective trip might happen (the dashed 40 ms pulse in the figure). In Easergy
P3 devices, the overshoot time is less than 50 ms.
Reset time
Figure 61 shows an example of reset time, that is, release delay when the relay is
clearing an overcurrent fault. When the relay’s trip contacts are closed, the circuit
breaker (CB) starts to open. After the CB contacts are open, the fault current still
flows through an arc between the opened contacts. The current is finally cut off
when the arc extinguishes at the next zero crossing of the current. This is the start
moment of the reset delay. After the reset delay the trip contacts and start contact
are opened unless latching is configured. The precise reset time depends on the
fault size; after a big fault, the reset time is longer. The reset time also depends
on the specific protection stage.
The maximum reset time for each stage is specified under the characteristics of
every protection function. For most stages, it is less than 95 ms.
tSET
tCB
tRESET
TRIP CONTACTS
Reset time is the time it takes the trip or start relay contacts to open after the fault
has been cleared.
Start level
> Start
Start level
< Start
Time grading
When a fault occurs, the protection scheme only needs to trip circuit breakers
whose operation is required to isolate the fault. This selective tripping is also
called discrimination or protection coordination and is typically achived by time
grading. Protection systems in successive zones are arranged to operate in times
that are graded through the sequence of equipment so that upon the occurrence
of a fault, although a number of protections devices respond, only those relevant
to the faulty zone complete the tripping function.
δt TC m Tm δt
time
Δt
There is detailed information available on the last eight faults for each protection
stage. The recorded values are specific for the protection stages and can contain
information like time stamp, fault value, elapsed delay, fault current, fault voltage,
phase angle and setting group.
NOTE: The recorded values are lost if the relay power is switched off.
Squelch limit
Current inputs have a squelch limit (noise filter) at 0.005 x IN. When the
measured signal goes below this threshold level, the signal is forced to zero.
NOTE: If ICALC is used to measure the residual current, the squelch limit for
the ICALC signal is same as for the phase currents. The I0 setting range begins
at the level of phase currents' squelch limit. This can cause instability if the
minimum setting is used with the I0 CALC mode.
Dependent delay means that the operate time depends on the measured real
time process values during a fault. For example, with an overcurrent stage using
dependent delay, a bigger a fault current gives faster operation. The alternative to
dependent delay is definite delay. With definite delay, a preset time is used and
the operate time does not depend on the size of a fault.
Some protection functions have their own specific type of dependent delay.
Details of these dedicated dependent delays are described with the appropriate
protection function.
Operation modes
There are three operation modes to use the dependent time characteristics:
• Standard delays
selecting a curve family (IEC, IEEE, IEEE2) and defining one's own
parameters for the selected delay formula. This mode is activated by setting
delay type to ‘Parameters’, and then editing the delay function parameters A –
E. See 6.6.2 Custom curves.
• Fully programmable dependent delay characteristics
CAUTION
HAZARD OF NON-OPERATION
The relay shows a graph of the currently used dependent delay on the local panel
display. The up and down keys can be used for zooming. Also the delays at 20 x
ISET, 4 x ISET and 2 x ISET are shown.
If there are any errors in the dependent delay configuration, the appropriate
protection stage uses the definite time delay.
There is a signal ‘Setting Error’ available in the output matrix that indicates
different situations:
3. There are errors in formula parameters A – E, and the relay is not able to
build the delay curve.
4. There are errors in the programmable curve configuration, and the relay is not
able to interpolate values between the given points.
Limitations
Table 50 - Maximum measured secondary currents and settings for phase and
ground fault overcurrent inputs
IN1 = 5 A 50 A 2.5 A
IN1 = 1 A 10 A 0.5 A
Example of limitation
CT = 750 / 5
For overcurrent stage 50/51 - 1, Table 50 gives 12.5 A. Thus, the maximum
setting the for 50/51 - 1 stage giving full dependent delay range is 12.5 A / 5 A =
2.5 xIN = 1875 APrimary.
For ground fault stage 50N/51N-1, Table 50 gives 0.5 A. Thus, the maximum
setting for the 50N/51N-1 stage giving full dependent delay range is 0.5 A / 1 A =
0.5 xI0N = 50 APrimary.
1. Example of limitation
6.6.1 Standard dependent delays using IEC, IEEE, IEEE2 and RI curves
The available standard dependent delays are divided in four categories called
dependent curve families: IEC, IEEE, IEEE2 and RI. Each category contains a set
of different delay types according to Table 51.
The dependent time setting error signal activates if the delay category is changed
and the old delay type does not exist in the new category. See 6.6 Dependent
operate time for more details.
Limitations
The minimum definite time delay starts when the measured value is twenty times
the setting, at the latest. However, there are limitations at high setting values due
to the measurement range. See 6.6 Dependent operate time for more details.
Table 51 - Available standard delay families and the available delay types within
each family
DT Definite X
time
NI Normal X X
inverse
VI Very X X X
inverse
EI Extremely X X X
inverse
MI Moderately X X
inverse
RI Old ASEA X
type
The operate time depends on the measured value and other parameters
according to Equation 7. Actually this equation can only be used to draw graphs
or when the measured value I is constant during the fault. A modified version is
implemented in the relay for real time usage.
Equation 7
kA
t= B
I
− 1
I START
I = Measured value
There are three different dependent delay types according to IEC 60255-3,
Normal inverse (NI), Extremely inverse (EI), Very inverse (VI) and a VI extension.
In addition, there is a de facto standard Long time inverse (LTI).
Parameter
Delay type
A B
EI Extremely inverse 80 2
k = 0.50
I = 4 pu (constant current)
IPICKUP = 2 pu
A = 0.14
B = 0.02
Equation 8
0.50 ⋅ 0.14
t= 0.02
= 5. 0
4
−1
2
The operate time in this example is five seconds. The same result can be read
from Figure 65.
IEC NI
B inverseDelayIEC_NI
IEC EI
B inverseDelayIEC_EI
IEC VI
B inverseDelayIEC_VI
IEC LTI
B inverseDelayIEC_LTI
There are three different delay types according to IEEE Std C37.112-1996 (MI, VI,
EI) and many de facto versions according to Table 53. The IEEE standard defines
dependent delay for both trip and release operations. However, in the Easergy P3
relay only the trip time is dependent according to the standard but the reset time
is constant.
The operate delay depends on the measured value and other parameters
according to Equation 9. Actually, this equation can only be used to draw graphs
or when the measured value I is constant during the fault. A modified version is
implemented in the relay for real-time usage.
Equation 9
A
t=k C
+ B
I − 1
I START
k = User’s multiplier
I = Measured value
A B C
k = 0.50
I = 4 pu
IPICKUP = 2 pu
A = 0.0515
B = 0.114
C = 0.02
Equation 10
t = 0.50 ⋅ 0.0515
+ 0.1140 = 1.9
4 0.02
−1
2
The operate time in this example is 1.9 seconds. The same result can be read
from Figure 72.
IEEE LTI
B inverseDelayIEEE1_LTI
IEEE LTVI
B inverseDelayIEEE1_LTVI
IEEE LTEI
B inverseDelayIEEE1_LTEI
IEEE MI
B inverseDelayIEEE1_MI
IEEE STI
B inverseDelayIEEE1 STI
IEEE STEI
B inverseDelayIEEE1 STEI
Before the year 1996 and ANSI standard C37.112 microprocessor relays were
using equations approximating the behavior of various induction disc type relays.
A quite popular approximation is Equation 11 which in Easergy P3 relays is called
IEEE2. Another name could be IAC because the old General Electric IAC relays
have been modeled using the same equation.
There are four different delay types according to Table 54. The old
electromechanical induction disc relays have dependent delay for both trip and
release operations. However, in Easergy P3 relays, only the trip time is
dependent and the reset time is constant.
The operate delay depends on the measured value and other parameters
according to Equation 11. Actually, this equation can only be used to draw graphs
or when the measured value I is constant during the fault. A modified version is
implemented in the relay for real-time usage.
Equation 11
B D E
t = k A + + + 3
I 2
− C I − C I − C
I START I START
I
START
k = User’s multiplier
I = Measured value
Parameter
Delay type
A B C D E
k = 0.50
I = 4 pu
ISTART = 2 pu
A = 0.1735
B = 0.6791
C = 0.8
D = -0.08
E = 0.127
Equation 12
0.6791 − 0.08 0.127
t = 0.5 ⋅ 0.1735 + + + = 0.38
4 4
2
4
3
− 0.8 − 0.8 − 0.8
2 2 2
The operate time in this example is 0.38 seconds. The same result can be read
from Figure 75.
IEEE2 MI
B inverseDelayIEEE2_MI
IEEE2 NI
B inverseDelayIEEE2_NI
IEEE2 VI
B inverseDelayIEEE2_VI
IEEE2 EI
B inverseDelayIEEE2_EI
These two dependent delay types have their origin in old ASEA (nowadays ABB)
ground fault relays.
The operate delay of types RI and RXIDG depends on the measured value and
other parameters according to Equation 13 and Equation 14. Actually, these
equations can only be used to draw graphs or when the measured value I is
constant during the fault. Modified versions are implemented in the relay for real-
time usage.
Equation 13 Equation 14
k I
t RI = t RXIDG = 5.8 − 1.35 ln
0.236 k I START
0.339 −
I
I START
k = User’s multiplier
I = Measured value
k = 0.50
I = 4 pu
ISTART = 2 pu
Equation 15
0.5
t RI = = 2.3
0.236
0.339 −
4
2
The operate time in this example is 2.3 seconds. The same result can be read
from Figure 79.
k = 0.50
I = 4 pu
ISTART = 2 pu
Equation 16
4
t RXIDG = 5.8 − 1.35 ln = 3.9
0.5 ⋅ 2
The operate time in this example is 3.9 seconds. The same result can be read
from Figure 80.
RI
B inverseDelayRI
This mode is activated by the setting delay type to ‘Parameters’, and then editing
the delay function constants, that is, the parameters A – E. The idea is to use the
standard equations with one’s own constants instead of the standardized
constants as in the previous chapter.
k = 0.50
I = 4 pu
ISTART = 2 pu
A = 0.2078
B = 0.8630
C = 0.8000
D = - 0.4180
E = 0.1947
Equation 17
0.8630 − 0.4180 0.1947
t = 0.5 ⋅ 0.2078 + + + = 0.37
4 4
2
4
3
− 0.8 − 0.8 − 0.8
2 2 2
The resulting time/current characteristic of this example matches quite well the
characteristic of the old electromechanical IAC51 induction disc relay.
The dependent time setting error signal actives if interpolation with the given
parameters is not possible. See 6.6 Dependent operate time for more details.
Limitations
The minimum definite time delay starts at the latest when the measured value is
twenty times the setting. However, there are limitations at high setting values due
to the measurement range. See 6.6 Dependent operate time for more details.
Programming dependent time curves requires Easergy Pro setting tool and
rebooting the unit.
The [current, time] curve points are programmed using Easergy Pro PC program.
There are some rules for defining the curve points:
• the configuration must begin from the topmost line
• the line order must be as follows: the smallest current (longest operate time)
on the top and the largest current (shortest operate time) on the bottom
• all unused lines (on the bottom) should be filled with [1.00 0.00s]
1 1.00 10.00 s
2 2.00 6.50 s
3 5.00 4.00 s
4 10.00 3.00 s
5 20.00 2.00 s
6 40.00 1.00 s
7 1.00 0.00 s
8 1.00 0.00 s
9 1.00 0.00 s
10 1.00 0.00 s
11 1.00 0.00 s
12 1.00 0.00 s
13 1.00 0.00 s
14 1.00 0.00 s
15 1.00 0.00 s
16 1.00 0.00 s
The dependent time setting error signal activates if interpolation with the given
points fails. See 6.6 Dependent operate time for more details.
Limitations
The minimum definite time delay starts at the latest when the measured value is
twenty times the setting. However, there are limitations at high setting values due
to the measurement range. See 6.6 Dependent operate time for more details.
The used net frequency is automatically adopted according to the local network
frequency.
Overexcitation protection is needed for generators that are excitated even during
startup and shutdown. If such a generator is connected to a unit transformer, also
the unit transformer needs volts/hertz overexcitation protection. Another
application is sensitive overvoltage protection of modern transformers with no flux
density margin in networks with unstable frequency.
This figure shows the difference between volts/hertz and normal overvoltage
protection. The volts/hertz characteristics on the left depend on the frequency,
while the standard overvoltage function on the right is insensitive to frequency.
The network frequency, 50 Hz or 60 Hz, is automatically adopted by the relay.
%
V f> set t in g V f> set t in g 0
18
2.0 2.0
1.8 1.8
0%
30 35 40 45 50 55 60 65 30 35 40 45 50 55 60 65
30 36 42 48 54 60 66 72 30 36 42 48 54 60 66 72
OverVoltFreqChar VoltPerHerz
Frequency (Hz ) Frequency (Hz )
Setting groups
Characteristics
Inaccuracy:
f < 0.05 Hz
The relay includes a function that checks the synchronism before giving or
enabling the circuit breaker close command. The function monitors the voltage
amplitude, frequency and phase angle difference between two voltages. Since
there are two stages available, it is possible to monitor three voltages. The
voltages can be busbar and line or busbar and busbar (bus coupler).
Close
Request
cmd
Side 2 f1 = f2
φ1 = φ2 & & CB close
Register
V1 event
V2 & ≥1 Sync OK
The synchronism check stage includes two separate synchronism criteria that can
be used separately or combined:
• voltage only
• voltage, frequency, and phase
The voltage check simply compares voltage conditions of the supervised objects.
The supervised object is considered dead (not energized) when the measured
voltage is below the Vdead setting limit. Similarly, the supervised object is
considered live (energized) when the measured voltage is above the Vlive setting
limit. Based on the measured voltage conditions and the selected voltage check
criteria, synchronism is declared.
When the network sections to be connected are part of the same network, the
frequency and phase are the same. Therefore, the voltage check criteria is safe to
use without frequency and phase check.
The frequency and phase check compares the voltages, frequency and phase of
the supervised objects. Synchronism is declared if the voltages are above the
Vlive limit and all three difference criteria are within the given limits. This
synchronism check is dynamic by nature, and the object close command is given
at a certain moment of time, depending on the selected mode of operation.
When two networks are running at slightly different frequencies, there is also a
phase difference between these two networks. Because of the different frequency,
the phase angle tends to rotate. The time for one cycle depends on the frequency
difference. The stress for electrical components is lowest when two networks are
connected at zero phase difference.
In the “Sync” mode, the circuit breaker closing is aimed at the moment of zero
phase difference. Therefore, the close command is advanced by the time defined
by the CB close time setting. In the “Async” mode, the circuit breaker closing is
aimed at the moment when the synchronism conditions are met, that is, when the
phase difference is within the given phase difference limit.
When two network sections to be connected are from different sources or
generators, the voltage criteria alone is not safe, so also frequency and phase
check must be used.
When two networks with different frequencies are to be connected, the request
timeout setting must be long enough to allow the synchronism criteria to be met.
For example, if the frequency difference is 0.1 Hz, the synchronism criteria is met
only once in ten seconds.
The synchronism check stage starts from an object close command that
generates a request to close the selected circuit breaker (as per CONTROL
SETTINGS view) when the synchronism conditions are met. The synchronism
check stage provides a "request" signal that is active from the stage start until the
synchronism conditions are met or the request timeout has elapsed. When the
synchronism conditions are not met within the request timeout, a “fail” pulse is
generated. The fail pulse has a fixed length of 200 ms. When the synchronism
conditions are met in a timely manner, the object close command is initiated for
the selected object. This signal is purely internal and not available outside the
synchronism check stage. When the synchronism conditions are met, the “OK”
signal is always active. The activation of the bypass input bybasses the
synchronism check and declares synchronism at all times.
The request, OK, and fail signals are available in the output matrix.
The synchronized circuit breaker close execution order is shown in Figure 83.
1 2 3
A B C
4 5
2. Synchronism declared
4. Sync fail signal if request timeout elapsed before synchronism conditions met
A B
1
C D
1. Sync request
2. Sync OK
A. The object close command given (mimic or bus) actually only makes a sync request.
B. The sync request ends when the synchronism conditions are met and CB command is given or
if the request timeout elapsed.
C. If the request timeout elapsed before synchronism conditions are met, sync fail pulse is
generated.
D. Normal object close operation
The synchronism check function is available when one of the following analog
measurement modules and a suitable measuring mode are in use:
3LN+LLy 1
3LN+LNy 1
2LL+VN+LLy 1
2LL+VN+LNy 1
LL+VN+LLy+LLz 2
LN+VN+LNy+LNz 2
The voltage used for checking the synchronism is always line-to-line voltage VAB
even when VA is measured. The sychronism check stage 1 always compares VAB
with VABy. The compared voltages for the stage 2 can be selected (VAB/VABy,
VAB/VABz, VABy/VABz). See 10.8 Voltage system configuration.
NOTE: To perform its operation, the synchronism check stage 2 converts the
voltages LNy and LNz to line-to-line voltage VAB. As such, the measured
voltage for LNy and LNz must be VA-N.
See the synchronism check stage's connection diagrams in See 10.8 Voltage
system configuration.
Characteristics
Input signal V1 – V4
Synchronism check mode (SMODE) Off; Async; Sync 39) 40) 41)
Voltage check mode (VMODE) DD; DL; LD; DD/DL; DD/LD; DL/LD;
DD/DL/LD 42) 43) 44) 45)
Inaccuracy:
- voltage ±3% VN
limit setting).
44) L means that the side must be “live” when closing (live = The voltage is higher than the live voltage
limit setting).
45) Example: DL mode for stage 1: The U12 side must be “dead” and the U12y side must be “live”.
As all the protection stages, the undervoltage function can be blocked with any
internal or external signal using the block matrix. For example if the secondary
voltage of one of the measuring transformers disappears because of a fuse failure
(See the voltage transformer supervision function in 7.8 Voltage transformer
supervision (ANSI 60FL)). The blocking signal can also be a signal from the
custom logic (see 5.7 Logic functions).
The stages can be blocked with a separate low-limit setting. With this setting, the
particular stage is blocked when the biggest of the three line-to-line voltages
drops below the given limit. The idea is to avoid unwanted tripping when the
voltage is switched off. If the operate time is less than 0.08 s, the blocking level
setting should not be less than 15% for the blocking action to be fast enough. The
self blocking can be disabled by setting the low-voltage block limit equal to zero.
A
K K K
I
B
C
J J
H J
D
G
L L F
There are three separately adjustable stages: 27-1, 27-2 and 27-3. All these
stages can be configured for the definite time (DT) operation characteristic.
Setting groups
Characteristics
Input signal VA – VC
Inaccuracy:
Input signal VA – VC
Inaccuracy:
Inaccuracy:
Equation 18
K1
T= 2
I 2 − K 22
I
TN
T = Operate time
K1 = Delay multiplier
Example
K1 = 15 s
K2 = 5 % = 0.05 x ITN
15
t= 2
= 300.4
0.229
− 0.05
2
1
The operate time in this example is five minutes.
If more than one definite time delay stages are needed for negative sequence
overcurrent protection, the freely programmable stages can be used (6.32
Programmable stages (ANSI 99)).
500 K2 = 2 % K 2 = 40 % K 2 = 70 %
200
100 K1 = 50 s
A 50
K2 = 2 % K 2 = 40 % K 2 = 70 %
20
10
5
K1 = 1 s
2
1
0 20 40 60 80 100
B
Setting groups
Characteristics
Input signal IA – IC
Inaccuracy:
NOTE: The stage is operational when all secondary currents are above 250
mA.
This protection stage can be used to detect voltage unbalance and phase
reversal situations. It calculates the fundamental frequency value of the negative
sequence component V2 based on the measured voltages (for calculation of V2,
see 4.11 Symmetrical components).
Whenever the negative sequence voltage V2 raises above the user's start setting
of a particular stage, this stage starts, and a start signal is issued. If the fault
situation remains on longer than the user's operate time delay setting, a trip signal
is issued.
Like all the protection stages, the negative sequence overvoltage can be blocked
with any internal or external signal using the block matrix, for example, if the
secondary voltage of one of the measuring transformers disappears because of a
fuse failure (See VT supervision function in 7.8 Voltage transformer supervision
(ANSI 60FL)).
The blocking signal can also be a signal from the user's logic (see 5.7 Logic
functions).
There are three separately adjustable stages: 47-1, 47-2, and 47-3. Both stages
can be configured for the definite time (DT) operation characteristic.
Setting groups
There are four settings groups available for all stages. Switching between setting
groups can be controlled by digital inputs, virtual inputs (mimic display,
communication, logic) and manually.
Characteristics
Inaccuracy:
Thermal model
The temperature is calculated using RMS values of phase currents and a thermal
model according IEC60255-149. The RMS values are calculated using harmonic
components up to the 15th.
Trip time:
I2 − I
2
t = τ ⋅ ln 2 P2
I −a
Alarm (alarm 60% = 0.6):
a = k ⋅ kΘ ⋅ I TN ⋅ alarm
Trip:
a = k ⋅ kΘ ⋅ I TN
Reset time:
2
IP
t = τ ⋅ Cτ ⋅ ln
a − I2
2
Trip release:
a = 0.95 × k × I TN
a = 0.95 × k × I TN × alarm
T = Operate time
I =Measured RMS phase current (the max. value of three phase currents)
If the transformer's fan is stopped, the cooling will be slower than with an active
fan. Therefore there is a coefficient Cτ for thermal constant available to be used
as cooling time constant, when current is less than 0.3 x ITN.
The trip level is determined by the maximum allowed continuous current IMAX
corresponding to the 100% temperature rise ΘTRIP for example the heat
capacitance of the transformer. IMAX depends of the given service factor k and
ambient temperature ΘAMB and settings IMAX40 and IMAX70 according the following
equation.
I MAX = k ⋅ k Θ ⋅ I TN
k
1.2
IMAX40
1.0
0.8 IMAX70
0.6
10 20 30 40 50 60 70 80 (°C)
AMB
When the relay is switched on, an initial temperature rise of 70% is used.
Depending on the actual current, the calculated temperature rise then starts to
approach the final value.
Alarm function
The thermal overload stage is provided with a separately settable alarm function.
When the alarm limit is reached, the stage activates its start signal.
Θoverload
Θmax
Θalarm
Reset ratio=95%
Θp
Settings:
τ = 30 minutes
k = 1.06
Θalarm = 90%
Alarm
Trip
45 min
IP = 0.85*IN
Time
100 min 200 min 300 min 400 min 500 min
Setting groups
Characteristics
The circuit breaker failure protection stage (CBFP) can be used to operate any
upstream circuit breaker (CB) if the programmed output matrix signals, selected
to control the main breaker, have not disappeared within a given time after the
initial command. The supervised output contact is defined by the “Monitored Trip
Relay” setting. An alternative output contact of the relay must be used for this
backup control selected in the Output matrix setting view.
The CBFP operation is based on the supervision of the signal to the selected
output contact and the time. The following output matrix signals, when
programmed into use, start the CBFP function:
• protection functions
• control functions
• supporting functions
• GOOSE signals (through communication)
If the signal is longer than the CBFP stage’s operate time, the stage activates
another output contact defined in the Output matrix setting view. The output
contact remains activated until the signal resets. The CBFP stage supervises all
the signals assigned to the same selected output contact.
In Figure 89, both the trip and CBFP start signals activate simultaneously (left
picture). If T> trip fails to control the CB through T1, the CBFP activates T3 after
the breaker failure operate time.
Figure 89 - Trip and CBFP start signals in the Output matrix view
NOTE: For the CBFP, always select the ”Connected” crossing symbol in the
Output matrix setting view.
Characteristics
Inaccuracy:
Description
Power system protection should always have some sort of backup protection
available. Backup protection is intended to operate when a power system fault is
not cleared or an abnormal condition is not detected in the required time because
of a failure or the inability of the primary protection to operate or failure of the
appropriate circuit breakers to trip. Backup protection may be local or remote.
Circuit breaker failure protection (CBFP) is part of the local backup protection.
CBFP provides a backup trip signal to an upstream circuit breaker (CB) when the
CB nearest to fault fails to clear fault current. The CB may fail to operate for
several reasons, for example burnt open coil or a flashover in the CB.
Two separate stages are provided to enable re-trip and CBFP trip commands.
The first stage can be used to give re-trip command (for example to control
second/backup open coil of the main CB) while the second stage can give
dedicated CBFP trip command to an upstream circuit breaker. Select the required
outputs for re-trip and CBFP trip through the output matrix.
Block diagram
A I
IA
IB Imax > &
IC
& J
I0 > & ≥ t K
B
C & & J
D
&
E
F G H
CBFP operation
The CBFP function can be enabled and disabled with the Enable for BF2
selection. The CBFP function activates when any of the selected start signals
becomes and stays active.
The CBFP operation can be temporarily blocked by the stage block signal from
the block matrix. When the stage is blocked by the block signal, the stage timer
stops but it does not reset. The stage timer continues its operation when the block
signal is disabled. When the block signal is active, the stage output signals are
disabled.
Condition selectors
The CBFP function has four condition selectors that can be used separately or all
together to activate and reset the CBFP function.
The four condition selectors are almost identical. The only difference is that
condition selectors 1 and 2 are for all protection functions that benefit from zero-
current detection for resetting the CBFP as described in section Zero-current
detector, and selectors 3 and 4 are for all the protection functions that do not
benefit from zero-current detection for CBFP.
Figure 92 - Start signal and reset condition setting view for Condition 1
Separate zero-current detection with dedicated start settings exists for phase
overcurrent and ground fault overcurrent signals. Zero-current detection is
independent of the protection stages.
The condition criteria, available signals and reset conditions are listed in Table 65.
NOTE: The start signal can be selected for each condition in advance from
the pull-down menu even if the concerned stage is not enabled. For the CBFP
activation, the concerned stage must be enabled from the protection stage
menu and the stage has to start to activate the CBFP start signal.
In addition to the selection of the start signal, the CBFP reset condition needs to
be selected.
If no reset conditions are selected, the stage uses Reset by monitored stage as
the reset condition. This prevents a situation where the stage never releases.
The reset condition Reset by CB status is useful if the current is already zero
when the CB is opened (for example unloaded CB).
When more than one selection criteria are selected, AND condition is used, for
example “zero current detection” AND “object open”. See Figure 91 for details.
Stage timer
The operate delay timer is started by a signal activated by the monitored stages
(condition selectors). The operate time delay is a settable parameter. When the
given time delay has elapsed, the stage provides a trip signal through the output
matrix and the event codes.
Zero-current detector
The setting range of the zero-current detector is always associated with the CT
nominal value, even in case of motor and transformer protection. The setting
range minimum depends on the relay accuracy. Instead of zero, a small minimum
value can be accepted. See Table 66.
CBFP coordination
The CBFP delay setting has to be coordinated according to the CB operation time
and the reset time of protection stages monitored by the CBFP function as
described in Figure 94.
B
C E F
D G
A
H I
Characteristics
Zero-current detection:
Inaccuracy:
The switch-on-to-fault (SOTF) protection function offers fast protection when the
circuit breaker (CB) is closed manually against a faulty line. Overcurrent-based
protection does not clear the fault until the intended time delay has elapsed.
SOTF gives a trip signal without additional time delay if the CB is closed and a
fault is detected after closing the CB.
E
A
G
B
C
F
D
A. Start setting
B. Maximum of IA, IB, IC
C. Low limit 0.02 x IN
D. SOTF trip
E. Switch-on-to-fault does not activate if the CB has not been in open position before the fault.
Open CB detection is noticed from the highest phase current value which has to be under a fixed
low-limit threshold (0.02 x IN). Opening of the CB can be detected also with digital inputs (Dead
line detection input = DI1 – DIx, VI1 – VIx). The default detection input is based on the current
threshold, so the dead line detection input parameter has value “–“.
F. Dead line detection delay defines how long the CB has to be open so that the SOTF function is
active. If the set time delay is not fulfilled and the highest phase current value (maximum of IA, IB,
IC) rises over the start setting, the SOTF does not operate.
G.If the highest phase current value of IA, IB, IC goes successfully under the low limit and rises to a
value between the low limit and the start value, then if the highest phase current value rises over
the start setting value before the set SOTF active after CB closure time delay has elapsed, the
SOTF trips. If this time delay is exceeded, the SOTF does not trip even if the start setting value is
exceeded.
Setting groups
Characteristics
Block diagram
3vlsblock
Im1
Im2 MAX > ts tr
& H
Im3
& I
A t
>1 J
& I
B C D E F G
A. Block F. Multiplier
B. Setting I>s G. Enable events
C. Delay H. Start
D. Definite / dependent time I. Register event
E. Dependent time characteristics J. Trip
3vIssblock
Im1
Im2 MAX > & E
Im3 ts tr
& F
A
t
G
& F
B C D
A. Block E. Start
B. Setting I>>s F. Register event
C. Delay G. Trip
D. Enable events
There are three separately adjustable overcurrent stages: 50/51-1, 50/51-2 and
50/51-3. The first stage 50/51-1 can be configured for definite time (DT) or
dependent operate time (IDMT) characteristic. The stages 50/51-2 and 50/51-3
have definite time operation characteristic. By using the definite delay type and
setting the delay to its minimum, an instantaneous (ANSI 50) operation is
obtained.
Figure 96 shows a functional block diagram of the 50/51-1 overcurrent stage with
definite time and dependent time operate time. Figure 97 shows a functional block
diagram of the 50/51-2 and 50/51-3 overcurrent stages with definite time
operation delay.
Dependent operate time means that the operate time depends on the amount the
measured current exceeds the start setting. The bigger the fault current is, the
faster is the operation. The dependent time delay types are described in 6.6
Dependent operate time. The relay shows the currently used dependent operate
time curve graph on the local panel display.
The maximum measured secondary current is 50 x IN. This limits the scope of
dependent curves with high start settings. See 6.6 Dependent operate time for
more information.
The 50/51-1 and 50/51-2 (50/51) overcurrent protection stages have a setting
parameter to include harmonics. When this setting is activated, the overcurrent
stage calculates the sum of the base frequency and all measured harmonics. This
feature is used to determine the signal's true root mean square value to detect the
signal's real heating factor. The operate time is 5 ms more when harmonics are
included in the measurement. Activate the "Include harmonics" setting if the
overcurrent protection is used for thermal protection and the content of the
harmonics is known to exist in the power system.
Setting groups
Characteristics
Input signal IA – IC
IDMT function:
- RI curve 0.025–20.0
0.025–20.0
Inaccuracy:
Moderately Inverse
Input signal IA – IC
Inaccuracy:
±3% of the set value or 5 mA secondary
- Starting
±1% or ±25 ms
- operate time
51) This
is the instantaneous time, that is, the minimum total operate time including the fault detection
time and the operate time of the trip contacts. Use the Accept zero delay setting in the protection
stage setting view in Easergy Pro to accept the zero operate time setting for the DT function.
Input signal IA – IC
Inaccuracy:
52) This
is the instantaneous time, that is, the minimum total operate time including the fault detection
time and the operate time of the trip contacts. Use the Accept zero delay setting in the protection
stage setting view in Easergy Pro to accept the zero operate time setting for the DT function.
Block diagram
i0s1
A > ts tr
& I
& J
B t
>1 K
& J
C D E F G H
A. I0 G. Multiplier
B. Block H. Enable events
C. Setting I0>s I. Start
D. Delay J. Register event
E. Definite / inverse time K. Trip
F. Inverse time characteristics
Figure 99 - Block diagram of the ground fault stages overcurrent 50N/51N-2, 50N/
51N-3, 50N/51N-4
I0ssblock
A > ts tr
& F
& G
B
t
H
& G
C D E
A. I0 E. Enable events
B. Block F. Start
C. Setting I0>>s G. Register event
D. Delay H. Trip
Each stage can be connected to supervise any of the following inputs and signals:
• Input IN1 for all networks other than solidly grounded.
• Input IN2 for all networks other than solidly grounded.
• Calculated signal IN Calc for solidly and low-impedance grounded networks. IN
Calc = IA + IB + IC.
There are four separately adjustable ground fault overcurrent stages: 50N/51N-1,
50N/51N-2, 50N/51N-3, and 50N/51N-4. The first stage 50N/51N-1 can be
configured for definite time (DT) or dependent time operation characteristic
(IDMT). The other stages have definite time operation characteristic. By using the
definite delay type and setting the delay to its minimum, an instantaneous (ANSI
50N) operation is obtained.
The maximum measured secondary ground fault overcurrent is 10 x I0N and the
maximum measured phase current is 50 x IN. This limits the scope of dependent
curves with high start settings.
Setting groups
Characteristics
IDMT function:
0.025–20.0, except
Inaccuracy:
Moderately Inverse
Inaccuracy:
The ground fault overcurrent stage (ANSI 50N/51N) and directional ground fault
overcurrent stage (ANSI 67N) have an inbuilt detection algorithm to detect a faulty
phase. This algorithm is meant to be used in radial-operated distribution
networks. The faulty phase detection can be used in solidly-grounded,
impedance-grounded or resonant-grounded networks.
Operation
The faulty phase detection starts from the ground fault stage trip. At the moment
of stage start, the phase currents measured prior to start are registered and
stored as prior-to-fault currents. At the moment of trip, phase currents are
registered again. Finally, faulty phase detection algorithm is performed by
comparing prior-to-fault currents to fault currents. The algorithm also uses positive
sequence current and negative sequence current to detect faulty phase.
The detected faulty phase is registered in the protection stage fault log (and also
in the event list and alarm screen). Faulty phase is also indicated by a line alarm
and line fault signals in the output matrix.
Possible detections of faulty phases are A-N, B-N, C-N, AB-N, AC-N, BC-N, ABC-
N, and REV. If the relay protection coordination is incorrect, REV indication is
given in case of a relay sympathetic trip to a reverse fault.
Description
The relay enables capacitor, filter and reactor bank protection with its five current
measurement inputs. The fifth input is typically useful for unbalance current
measurement of a double-wye connected ungrounded bank.
As the capacitor elements are not identical and have acceptable tolerances, there
is a natural unbalance current between the starpoints of the capacitor banks. This
natural unbalance current can be compensated to tune the protection sensitive
against real faults inside the capacitor banks.
Figure 100 - Typical capacitor bank protection application with Easergy P3 relays
P3x3x_Capbank
8/E/1:1
IA 5A
8/E/1:2
8/E/1:3
IB 5A
8/E/1:4
8/E/1:5
IC 5A
8/E/1:6
8/E/1:7 I01 5A
8/E/1:8
I01 1A
8/E/1:9
8/E/1:10 I02 1A
8/E/1:11
I02 0,2A
8/E/1:12
Compensation method
This feature is implemented to the stage 50N/51N-4, while the other stage 50N/
51N-3 can still function as normal unbalance protection stage with the
compensation method. Normally, the 50N/51N-4 could be set as an alarming
stage while stage 50N/51N-3 trips the circuit breaker.
The stage 50N/51N-4 should be set based on the calculated unbalance current
change of one faulty element. You can calculate this using the following formula:
Equation 19
V L− N V L− N
−
(2 ⋅ π ⋅ f ⋅ C1 ) −1 (2 ⋅ π ⋅ f ⋅ C2 ) −1
3I 0 =
3
90
3I0
A
180 0
B
270
If there is an element failure in the bank, the algorithm checks the phase angle of
the unbalance current related to the phase angle of the phase current IA. Based
on this angle, the algorithm can increase the corresponding faulty elements
counter (there are six counters).
Figure 102 - How a failure in different branches of the bank affects the IN
measurement
Easergy P3 H I
G C
A B
F D
E
You can set for the stage 50N/51N-4 the allowed number of faulty elements. For
example, if set to three elements, the fourth fault element will issue the trip signal.
The fault location is used with internal fused capacitor and filter banks. There is
no need to use it with fuseless or external fused capacitor and filter banks, nor
with the reactor banks.
Application example
Figure 103 - 131.43 μF Y-Y connected capacitor bank with internal fuses
12kV A
I B
I0
Characteristics
Inaccuracy:
– via the Easergy P3 device's front panel: go to the 50N/51N-4 menu, scroll
right to 1 SET 50N/51N, and select Location for CMode.
– via the device's front panel: go to the 50N/51N-4 menu, scroll right to
SET2 50N/51N, and select Get for SaveBal.
Equation 20
V L− N V L− N
−
(2 ⋅ π ⋅ f ⋅ C1 ) −1
(2 ⋅ π ⋅ f ⋅ C 2 ) −1
3I 0 =
3
6928 6928
−
(2 ⋅ π ⋅ 50 ⋅ 43.81 ⋅ 10 −6 ) −1 (2 ⋅ π ⋅ 50 ⋅ 43.81 ⋅ 10 −6 ) −1
3I 0 =
3
3I 0 = 1.37 A
Failure of one element inside the bank on the left branch causes
approximately 1.37 ampere unbalance current at the star point. On the right
branch, there are two capacitor units in parallel, and therefore, a failure of one
element causes only 0.69 ampere unbalance. A different start value for each
branch is necessary. Set the start value to 80% of the calculated value.
0.80
0.60
0.40
0.20
0.00
Conduct testing by injecting current to channels IA and IN1 of the relay. In the
example above, 0.69 A primary current is injected to the IN1 channel. IN1 is
leading the phase current IA by 60 degrees. This means the fault has to be on
the right branch and in phase 2. Compensation happens automatically after
the set operate time until the allowed total amount of failed units is exceeded
(Max. allowed faults). In this application, the fourth failed element would cause
the stage to trip.
Overvoltage protection is used to detect too high system voltages or to check that
there is sufficient voltage to authorize a source transfer.
In solidly grounded, four-wire networks with loads between phase and neutral
voltages, overvoltage protection may be needed for line-to-neutral voltages, too.
In such applications, the programmable stages can be used. 6.32 Programmable
stages (ANSI 99).
There are three separately adjustable stages: 59-1, 59-2, and 59-3. All the stages
can be configured for the definite time (DT) operation characteristic.
The 59–1 stage has a settable reset delay that enables detecting intermittent
faults. This means that the time counter of the protection function does not reset
immediately after the fault is cleared, but resets after the release delay has
elapsed. If the fault appears again before the release delay time has elapsed, the
delay counter continues from the previous value. This means that the function
eventually trips if faults are occurring often enough.
Configurable hysteresis
The dead band is 3% by default. This means that an overvoltage fault is regarded
as a fault until the voltage drops below 97% of the start setting. In a sensitive
alarm application, a smaller hysteresis is needed. For example, if the start setting
is about only 2% above the normal voltage level, the hysteresis must be less than
2%. Otherwise, the stage does not release after fault.
Block diagram
Figure 108 - Block diagram of the three-phase overvoltage stages 59-1, 59-2, and
59-3
3vus
VmA
VmB MAX > & G
ts tr
VmC
& H
A
t
I
& H
B C D E F
Setting groups
Characteristics
Input signal VA – VC
Inaccuracy:
Input signal VA – VC
Inaccuracy:
57) This
is the instantaneous time, that is, the minimum total operate time including the fault detection
time and the operate time of the trip contacts. Use the Accept zero delay setting in the protection
stage setting view in Easergy Pro to accept the zero operate time setting for the DT function.
Input signal VA – VC
Inaccuracy:
The neutral overvoltage protection is used as unselective backup for ground faults
and also for selective ground fault protections for motors having a unit transformer
between the motor and the busbar.
Whenever the measured value exceeds the start setting of a particular stage, this
stage starts and a start signal is issued. If the fault situation remains on longer
than the operate time delay setting, a trip signal is issued.
The neutral overvoltage is either measured with three voltage transformers (for
example broken delta connection), one voltage transformer between the motor's
neutral point and ground or calculated from the measured phase-to-neutral
voltages according to the selected voltage measurement mode (see 10.8 Voltage
system configuration):
There are two separately adjustable stages: 59N-1 and 59N-2. Both stages can
be configured for the definite time (DT) operation characteristic.
Block diagram
Figure 109 - Block diagram of the neutral overvoltage stages 59N-1, 59N-2
U0sblock
A > ts tr
& G
& H
B
t
I
& H
C D E F
A. U0 F. Enable events
B. Blocking G. Start
C. Setting U0>s H. Register event
D. Release delay I. Trip
E. Delay
Setting groups
Characteristics
Input signal VN
Inaccuracy:
Input signal VN
Inaccuracy:
The restricted ground fault (REF) protection function is used to detect ground
faults in solidly-grounded or impedance-grounded power transformers, grounding
transformers and shunt reactors. REF protection can also be used to protect
rotating machines if the machine’s neutral point is grounded.
A A
B B
C C
Figure 111 - Restricted ground fault protection of a transformer and neutral point
reactor
A A
B B
C C
I 3 (S2)
N 64REF
I 3 (S1)
N
A A
B B
C C
A
B
C
The REF protection principle has several advantages. It is very selective because
the protection zone is limited between the current transformers that are used for
the REF protection. Because of its selectivity, the REF protection requires no
additional time delay for protection coordination. Therefore, REF protection is
especially suitable for the protection of transformers and rotating machines
against internal ground faults. Because of the differential protection principle, it is
also very sensitive which makes it suitable for detecting faults located near the
neutral point of transformers and rotating machines.
The REF protection function is based on the differential protection principle and is
sensitive to the fundamental frequency component of the measured currents.
Figure 114 depicts the differential protection principle applied to REF protection.
A
C C
I B I
64REF
IN Meas IN Calc = IA + IB + IC
The function is based on the difference of the current measured at the neutral
point (IN Meas) and the calculated residual current (IN Calc). The function calculates
the differential current ID according to Equation 21. So the function is based on
the absolute value of ID that is a sum of the current vectors IN Meas and IN Calc.
NOTE: Nominal current of the IN Meas and IN Calc are current transformer
ratings.
Equation 21
During healthy conditions, the neutral point current (IN Meas) is near or equal to
zero and the same is true for the residual current or the calculated sum of the
phase currents IN Calc = 3I0 = IA+IB +IC. During healthy conditions, the differential
current ID is also close to zero and the REF protection stage does not start.
Figure 115 depicts through-fault conditions and a fault in the protected zone.
During a through-fault condition, a ground fault current flowing from the faulty
phase to earth returns to the system’s neutral point. Because of the convention of
current directions, the resulting neutral point current (IN Meas) and calculated
residual current (IN Calc) are flowing in opposite directions resulting in zero or very
small differential current ID according to Equation 21.
When a fault occurs inside the protection zone, the neutral point current flowing
into the protection zone has a positive current direction according to the current
direction convention. Depending on the network conditions, an additional fault
current may or may not flow into the zone along the line. This additional fault
current manifests itself as a residual current. Additional fault currents flowing into
the protection zone have a positive current direction, too. In other words, the
neutral point current and residual current are in a phase which results in a high
differential current ID according to Equation 21.
Figure 115 - Through-fault condition (left) and ground fault in protected zone
(right)
A A A A
B B B B
C C C C
INCalc = IA + IB + IC INCalc = IA + IB + IC
IN Meas IN Meas
Id ≈ 0 Id > 0
During a through-fault or short-circuit fault outside the protection zone, the current
transformers may be exposed to very high currents. These high fault currents
may lead to different saturation of the phase current transformers resulting in an
erroneous residual current. To ensure correct operation of the protection stage, a
stabilization method is provided. Protection stage stabilisation is based on the
calculated bias current IB and programmable operating characteristics. The bias
current is calculated according to Equation 22.
Equation 22
|IA|+|IB|+|IC|
IB=
3
This bias current stabilization method is used in the dI0> stage. The dI0>> stage
does not consider the stabilization current IB and is purely based on the
differential current ID. Both the differential current ID and stabilization current IB
are current transformer ratings.
N
I K
L
D
J
M
E H
F G
A. ID/ IN H. IB / IN
B. 2 x IN I. Single-end-feed limit
C. IN J. ISTART
D. 50% IN K. Maximum setting
E. 5% IN L. Slope 1
F. IN M. Minimum setting
G. 3 x IN N. Slope 2
A
B
C I & J
D
>
& K
E F G H
Characteristics
64-1 64-2
Input signals - -
Start value - -
Slope 1 5–100 % -
Slope 2 100–200 % -
Inaccuracy of starting ±3% of set value or 0.02 x In ±3 % of the set value or ±0.5
when currents are < 200 mA % of the rated value
The directional phase overcurrent protection can be used for directional short-
circuit protection. Typical applications are:
For line-to-line and three-phase faults, the fault direction is determined with
positive-sequence polarization using the angles between the positive sequences
of currents and voltages.
For details on power direction, see 4.10 Power and current direction.
Voltage memory
Block diagrams
Figure 118 - Block diagram of directional phase overcurrent stage Iϕ > and Iϕ >>
3vlsblock_Idir>_Idir>>
K
U1 U1
I1 I1
Im1
Im2 MAX > ts tr
& H
Im3
& I
A t
>1 J
& I
B C D E F G
Figure 119 - Block diagram of directional phase overcurrent stage Iϕ >>> and Iϕ
>>>>
3vlsblock_Idir>>>_Idir>>>>
K
U1 U1
I1 I1
Im1
Im2 MAX > & H
Im3 ts tr
& I
A
t
J
& I
B C G
A. Block H. Start
B. Setting I>>>s I. Register event
C. Delay J. Trip
G. Enable events K. Directional discrimination by U1/I1 angle
Operation
The function has two conditions as shown in the block diagram. One is the current
threshold and the other is the fault direction or fault angle. If both conditions are
true, the stage starts and trips after the set trip delay. Whenever the highest three-
phase current exceeds the set value, there is an overcurrent condition.
For faults that do not involve ground, the fault direction or fault angle is
determined as an angle between the positive sequences of current and voltage.
The angle reference for the positive-sequence current is the positive-sequence
voltage that is rotated by the base-angle setting (also called relay characteristics
angle). The actual trip area is ± 88° from the base-angle setting. If the positive-
sequence current vector falls into the trip area, there is a directional condition.
If the current threshold and directional conditions are true, the stage starts and
trips after the set trip delay.
For faults that involve ground, the fault direction or fault angle is determined as an
angle between the healthy line-to-line voltage and the faulted phase current. The
angle reference for the faulted phase current is opposite to the healthy line-to-line
voltage that is rotated by the base-angle setting plus 90° to the positive direction.
The actual trip area is ± 88° from the base angle setting plus 90°. If the fault
current vector falls into the trip area, there is a directional condition. If both
conditions are true, the stage starts and trips after the set trip delay. If the current
threshold and directional conditions are true, the stage starts and trips after the
set trip delay.
A typical characteristic for the directional phase overcurrent protection for line-to-
line faults is shown in Figure 120. The base angle setting is -30°. The stage starts
if the maximum of the three-phase currents exceeds the current threshold and if
the tip of the positive-sequence current phasor gets into the grey area.
Figure 120 - Example of the directional phase overcurrent protection area for line-
to-line fault
+90°
Reverse Forward
+88°
0°
U1
-88°
-90° ldir_angle1
A typical characteristic for the directional phase overcurrent protection for line-to-
ground faults is shown in Figure 121. The base angle setting is -30°. The stage
starts if the maximum of the three-phase currents exceeds the current threshold
and if the tip of the fault current phasor gets into the grey area.
Figure 121 - Example of the directional phase overcurrent protection area for line-
to-ground fault , RCA internally rotated +90o CCW during ground fault
+90°
+60°
Forward
+88°
-88°
0°
U1
Reverse
-90° ldir_angle2
In the non-directional mode, the stage acts like an ordinary overcurrent 50/51
stage.
The directional + backup mode works like the directional mode, but it has non-
directional backup protection that is used if a close-up fault forces all voltages to
about zero. After the angle memory hold time, the direction would be lost.
The directional + backup mode is required when the operate time is set longer
than the voltage memory setting or no other non-directional backup protection is
used.
+90° +90°
-ind. +cap. -ind. +cap.
2°
DIRECTIONAL NON-DIRECTIONAL
SET SET
VALUE 0° VALUE 0°
-res. +res. -res. +res.
BASE ANGLE= 0°
-90° -90°
Figure 123 - Bidirectional application with two stages 67-1 and 67-2
+90°
ind. +cap.
4°
67-2 TRIP AREA
SET SET
VA LUE VA LUE 0°
res. +res.
BASE ANGLE = °
cap. +ind.
When any of the three-phase currents exceeds the setting value and, in
directional mode, the phase angle including the base angle is within the active
±88° wide sector, the stage starts and issues a start signal. If this fault remains on
longer than the time defined by the delay setting, a trip signal is issued.
There are four separately adjustable stages available: 67-1, 67-2, 67-3, and 67-4.
Stages 67-1 and 67-2 can be configured for definite time (DT) or dependent time
characteristic. See 6.6 Dependent operate time for details on the available
dependent delays.
Stages 67-3 and 67-4 have definite time operation delay. The relay shows a
scaleable graph of the configured delay on the local panel display.
The maximum measured secondary current is 50 x IN. This limits the scope of
dependent curves with high start settings. See 6.6 Dependent operate time for
more information.
Setting groups
Characteristics
Characteristic Value
Input signal IA – IC
VA – V C
Mode Directional/Directional+BackUp
IDMT function:
0.025...20.0, except
Characteristic Value
Inaccuracy:
- Starting (rated value IN= 1...5 A) ±3% of the set value or ±0.5% of the rated
value
- Angle
±2° V>5 V
±30° V = 0.1...5.0 V
- Operate time at DT function ±1% or ±25 ms
- Operate time at IDMT function ±5% or at least ±30 ms59)
59) This is the instantaneous time, that is, the minimum total operate time including the fault detection
time and the operate time of the trip contacts. Use the Accept zero delay setting in the protection
stage setting view in Easergy Pro to accept the zero operate time setting for the DT function.
60) EI = Extremely Inverse, NI = Normal Inverse, VI = Very Inverse, LTI = Long Time Inverse, MI=
Moderately Inverse
Characteristic Value
Input signal IA – IC
Va – VC
Mode Directional/Directional+BackUp
Characteristic Value
Inaccuracy:
- Starting (rated value IN= 1...5 A) ±3% of the set value or ±0.5% of the rated
value
- Angle
±2° V>5 V
±30° V = 0.1...5.0 V
- Operate time at DT function ±1% or ±25 ms
61) This
is the instantaneous time, that is, the minimum total operate time including the fault detection
time and the operate time of the trip contacts. Use the Accept zero delay setting in the protection
stage setting view in Easergy Pro to accept the zero operate time setting for the DT function.
The ground fault protection is adapted for various network ground systems.
Polarization
• 3LN/LLY, 3LN/LNY and 3LN/VN: the zero sequence voltage is calculated from
the line-to-line voltages and therefore any separate zero sequence voltage
transformers are not needed. The setting values are relative to the configured
voltage transformer (VT) voltage/√3.
• 3LN+VN, 2LL+VN, 2LL+VN+LLy, 2LL+VN+LNy, LL+VN+LLy+LLz, and LN+VN
+LNy+LNz: the neutral overvoltage is measured with voltage transformer(s)
for example using a broken delta connection. The setting values are relative
to the VTN secondary voltage defined in the configuration.
• 3LN: the zero sequence voltage is calculated from the line-to-line voltages
and therefore any separate zero sequence voltage transformers are not
needed. The setting values are relative to the configured voltage transformer
(VT) voltage/√3.
• 3LN+VN and 2LL+VN: the zero sequence voltage is measured with voltage
transformer(s) for example using a broken delta connection. The setting
values are relative to the VTN secondary voltage defined in configuration.
This mode consists of two sub modes, Res and Cap. A digital signal can be
used to dynamically switch between these two submodes. When the digital
input is active (DI = 1), Cap mode is in use and when the digital input is
inactive (DI = 0), Res mode is in use. This feature can be used with
compensated networks when the Petersen coil is temporarily switched off.
◦ Res
done with a Petersen coil between the neutral point of the main
transformer and ground. In this context, high resistance means that the
fault current is limited to be less than the rated phase current. The trip
area is a half plane as drawn in Figure 126. The base angle is usually set
to zero degrees.
◦ Cap
This mode is used with networks grounded with a small resistance. In this
context, "small" means that a fault current may be more than the rated phase
currents. The trip area has a shape of a sector as drawn in Figure 127. The
base angle is usually set to zero degrees or slightly on the lagging inductive
side (negative angle).
• Undir
This mode makes the stage equal to the non directional stage 50N/51N-1.
The phase angle and VN amplitude setting are discarded. Only the amplitude
of the selected IN input is supervised.
Each stage can be connected to supervise any of the following inputs and signals:
Short ground faults make the protection start but does not cause a trip. A short
fault means one cycle or more. For shorter than 1 ms transient type of intermittent
ground faults in compensated networks, there is a dedicated stage I0INT> 67NI.
When starting happens often enough, such intermittent faults can be cleared
using the intermittent time setting.
When a new start happens within the set intermittent time, the operation delay
counter is not cleared between adjacent faults and finally the stage trips.
There are two separately adjustable stages: 67N-1 and 67N-2. Both stages can
be configured for definite time delay (DT) or dependent time delay operate time.
Accomplished dependent delays are available for all stages 67N-1 and 67N-2.
The relay shows a scalable graph of the configured delay on the local panel
display.
The maximum measured secondary ground fault overcurrent is 10 x I0N and the
maximum measured phase current is 50 x IN. This limits the scope of dependent
curves with high start settings.
Block diagram
Figure 125 - Block diagram of the directional ground fault overcurrent stages
67N-1, 67N-2
I0fiisblock
A Isinφ
Icosφ
> & I
& J
B
C K
> t
& J
D E F G H
A. I0 G. Delay
B. Block H. Enable events
C. V0 I. Start
D. Choise Icosφ (Res) / Isinφ (Cap) J. Register event
E. Setting Iφ > s K. Trip
F. Setting I0 > s
67N-1
I0
Iocos φ
-V0
67N-1
Res mode can be used with compensated networks. Cap mode is used with ungrounded networks.
I0
TRIP AREA +152º +32º
I0φ> 120º
70º 0º 0º
-V0 120º -V0
70º I0φ>
-15º
I0
TRIP AREA
-85º -88º
IoDir_SectorAdj
The drawn IN phasor is inside the trip area. The angle offset and half sector size are user’s
parameters.
Setting groups
Characteristics
IN Calc = ( IA + IB + IC)
Mode Non-directional/Sector/ResCap
IDMT function:
0.025–20.0, except
Inaccuracy:
- Starting VN & IN (rated value IN= 1–5A) ±3% of the set value or ±0.3% of the rated
value
- Starting VN & IN (Peak Mode when, rated ±5% of the set value or ±2% of the rated
value I0n= 1–10A) value (Sine wave <65 Hz)
- Starting VN & IN (IN Calc) ±3% of the set value or ±0.5% of the rated
value
else ±20°
Moderately Inverse
IN Calc = ( IA + IB + IC)
Mode Non-directional/Sector/ResCap
IDMT function:
0.05–20.0, except
Inaccuracy:
- Starting VN & IN (rated value In= 1 – 5A) ±3% of the set value or ±0.3% of the rated
value
- Starting VN & IN (Peak Mode when, rated ±5% of the set value or ±2% of the rated
value I0n= 1 – 10A) value (Sine wave <65 Hz)
- Starting VN & IN (IN Calc) ±3% of the set value or ±0.5% of the rated
value
else ±20°
Moderately Inverse
The ground fault overcurrent stage (ANSI 50N/51N) and directional ground fault
overcurrent stage (ANSI 67N) have an inbuilt detection algorithm to detect a faulty
phase. This algorithm is meant to be used in radial-operated distribution
networks. The faulty phase detection can be used in solidly-grounded,
impedance-grounded or resonant-grounded networks.
Operation
The faulty phase detection starts from the ground fault stage trip. At the moment
of stage start, the phase currents measured prior to start are registered and
stored as prior-to-fault currents. At the moment of trip, phase currents are
registered again. Finally, faulty phase detection algorithm is performed by
comparing prior-to-fault currents to fault currents. The algorithm also uses positive
sequence current and negative sequence current to detect faulty phase.
The detected faulty phase is registered in the protection stage fault log (and also
in the event list and alarm screen). Faulty phase is also indicated by a line alarm
and line fault signals in the output matrix.
Possible detections of faulty phases are A-N, B-N, C-N, AB-N, AC-N, BC-N, ABC-
N, and REV. If the relay protection coordination is incorrect, REV indication is
given in case of a relay sympathetic trip to a reverse fault.
This stage can be used to block other stages and to indicate possible primary
faults in the power distribution network. The ratio between the second harmonic
component and the fundamental frequency component is measured on all the
phase currents. When the ratio in any phase exceeds the setting value, the stage
gives a start signal. After a settable delay, the stage gives a trip signal.
The start and trip signals can be used for blocking the other stages.
The trip delay is irrelevant if only the start signal is used for blocking.
The trip delay of the stages to be blocked must be more than 60 ms to ensure a
proper blocking.
Block diagram
Figure 128 - Block diagram of the second harmonic inrush detection stage
2ndHarm
Im1
Im2 MAX > & E
Im3 ts tr
& F
A
t
G
& F
B C D
A. Block E. Start
B. Setting 2nd harmonics F. Register event
C. Delay G. Trip
D. Enable events
Characteristics
Input signal IA – IC
Settings:
Inaccuracy:
The ratio between the fifth harmonic component and the fundamental frequency
component is measured on all the phase currents. When the ratio in any phase
exceeds the setting value, the stage activates a start signal. After a settable delay,
the stage operates and activates a trip signal.
The trip delay of the stages to be blocked must be more than 60 ms to ensure a
proper blocking.
Characteristics
Input signal IA – IC
Settings:
Inaccuracy:
Frequency protection is used for load sharing and shedding, loss of power system
detection and as a backup protection for overspeeding.
The frequency function measures the frequency from the two first voltage inputs.
At least one of these two inputs must have a voltage connected to be able to
measure the frequency. Whenever the frequency crosses the start setting of a
particular stage, this stage starts, and a start signal is issued. If the fault remains
on longer than the operating delay setting, a trip signal is issued. For situations
where no voltage is present, an adapted frequency is used.
The underfrequency stages are blocked when the biggest of the three line-to-line
voltages is below the low-voltage block limit setting. With this common setting,
LVBlk, all stages in underfrequency mode are blocked when the voltage drops
below the given limit. The idea is to avoid purposeless alarms when the voltage is
off.
When the biggest of the three line-to-line voltages has been below the block limit,
the underfrequency stages are blocked until the start setting has been reached.
There are five separately adjustable frequency stages: 81–1, 81–2, 81U–1,
81U-2, 81U-3. The two first stages can be configured for either overfrequency or
underfrequency usage. So totally five underfrequency stages can be in use
simultaneously. Using the programmable stages even more can be implemented
(chapter 6.32 Programmable stages (ANSI 99)). All the stages have definite
operate time delay (DT).
Setting groups
Characteristics
Input signal VA – VC
Inaccuracy:
NOTE: If the relay restarts for some reason, there is no trip even if the
frequency is below the set limit during the start-up (Start and trip is blocked).
To cancel this block, frequency has to rise above the set limit.
Table 87 - Underfrequency 81U–1, 81U–2, 81U–3 (81L)
Input signal VA – Vc
Inaccuracy:
The rate of change of frequency (ROCOF or df/dt) function is used for fast load
shedding, to speed up operate time in overfrequency and underfrequency
situations and to detect loss of grid. For example, a centralized dedicated load
shedding relay can be omitted and replaced with distributed load shedding, if all
outgoing feeders are equipped with Easergy P3 relays.
NOTE: Use ROCOF for load shedding only. Do not use it for loss of mains
detection.
Load switching and fault situations may generate change in frequency. A load
drop may increase the frequency and increasing load may decrease the
frequency, at least for a while. The frequency may also oscillate after the initial
change. After a while, the control system of any local generator may drive the
frequency back to the original value. However, in case of a heavy short-circuit
fault or if the new load exceeds the generating capacity, the average frequency
keeps on decreasing.
Figure 129 - An example of definite time df/dt operate time. At 0.6 s, which is the
delay setting, the average slope exceeds the setting 0.5 Hz/s and a trip signal is
generated.
FREQUENCY ROCOF1_v3
(Hz)
Settings:
df/dt = 0.5 Hz/s
1. t = 0.60 s
0
Hz 0.5
/s Hz tMin = 0.60 s
/s
0.7
2.0
5H
H
z/s TIME
z/s
(s)
START
TRIP
ROCOF implementation
The ROCOF function is sensitive to the absolute average value of the time
derivate of the measured frequency |df/dt|. Whenever the measured frequency
slope |df/dt| exceeds the setting value for 80 ms time, the ROCOF stage starts
and issues a start signal after an additional 60 ms delay. If the average |df/dt|,
since the start moment, still exceeds the setting, when the operation delay has
elapsed, a trip signal is issued. In this definite time mode the second delay
parameter "minimum delay, tMIN" must be equal to the operation delay parameter
"t".
If the frequency is stable for about 80 ms and the time t has already elapsed
without a trip, the stage resets.
One difference between the overfrequency and underfrequency and the df/dt
function is the speed. Often a df/dt function can predict an overfrequency or
underfrequency situation and is thus faster than a simple overfrequency or
underfrequency function. However, in most cases, standard overfrequency and
underfrequency stages must be used together with ROCOF to ensure tripping
also if the frequency drift is slower than the slope setting of ROCOF.
Figure 129 shows an example where the df/dt start value is 0.5 Hz/s and the
delay settings are t = 0.60 s and tMIN = 0.60 s. Equal times t = tMIN gives a definite
time delay characteristic. Although the frequency slope fluctuates, the stage does
not release but continues to calculate the average slope since the initial start. At
the defined operate time, t = 0.6 s, the average slope is 0.75 Hz/s. This exceeds
the setting, and the stage trips.
At slope settings less than 0.7 Hz/s, the fastest possible operate time is limited
according to the Figure 130.
Figure 130 - At very sensitive slope settings the fastest possible operate time is
limited.
ROCOF5_v3
Fastest possible operation time setting (s)
By setting the second delay parameter tMIN smaller than the operate time delay t,
a dependent type of operate time characteristic is achieved.
Figure 132 shows one example, where the frequency behavior is the same as in
the first figure, but the tMIN setting is 0.15 s instead of being equal to t. The
operate time depends on the measured average slope according to the following
equation:
Equation 23
s SET ⋅ t SET
t TRIP =
s
The minimum operate time is always limited by the setting parameter tMIN. In the
example, the fastest operate time, 0.15 s, is achieved when the slope is 2 Hz/s or
more. The leftmost curve in Figure 131 shows the dependent characteristics with
the same settings as in Figure 132.
ROCOF6_v3
Operation time (s)
Figure 132 - An example of dependent df/dt operate time. The time to trip will be
0.3 s, although the setting is 0.6 s, because the average slope 1 Hz/s is steeper
than the setting value 0.5 Hz/s.
FREQUENCY ROCOF3_v3
(Hz)
50.0 Settings:
df/dt = 0.5 Hz/s
t = 0.60 s
1.
0
0.5 tMin = 0.15s
H
Hz
z/
/s
s
0.7
2.0
5 Hz
Hz/
/s TIME
49.7
s
(s)
0.00 0.15 0.30 0.45 0.60
START
TRIP
Settings groups
Characteristics
Reset ratio 1
Inaccuracy:
- Operate time(overshoot ≥ 0.2 Hz/s) ±35 ms, when area is 0.2 – 1.0 Hz/s
68) This
is the instantaneous time, that is, the minimum total operate time including the fault detection
time and the operate time of the trip contacts. Use the Accept zero delay setting in the protection
stage setting view in Easergy Pro to accept the zero operate time setting for the DT function.
NOTE: ROCOF stage is using the same low voltage blocking limit as the
frequency stages.
The lockout feature, also called latching, can be programmed for outputs in the
Output matrix setting view. Any protection stage start or trip, digital input, logic
output, alarm and GOOSE signal connected to the following outputs can be
latched when required:
Figure 133 - The lockout programmed for LED A and 50/51-2 trip signals
In Figure 133, the latched signal is identified with a dot and circle in the matrix
signal line crossing.
The lockout can be released through the display or via the Easergy Pro. See
Chapter 4 Control functions.
In the General > Release latches setting view, select the Store latch state
setting to configure latched states of relay outputs, virtual outputs, binary outputs
(BO) and high-speed outputs (HSO) to be stored. If some of these outputs are
latched and in “on” state, and the device is restarted, their status is set back to
“on” after restart.
In the LED configuration setting view, you can configure the latched states of
LEDs to be stored after a restart. In this example, storing has been configured for
LED A (green).
The differential protection is based on the winding currents' difference between I-1
and I-2 side. In transformer applications, the current calculation depends on
transformer connection group. For example, in a Yy0 connection, the measured
currents are also winding currents, see Figure 136.
In the second example, if the transformer IL side is connected to open delta for
example Dy11, then the winding currents are calculated on the delta side (IL
side), see Figure 137.
(
IAW = IA − IB )
3
(
IBW = IB − IC )
3
(
ICW = IC − IA )
3
I ' AW = I ' A
I' BW = I' B
I ' CW = I ' C
IW + I ' W
Ib =
2
I d = IW + I ' W
Bias current calculation is only used in protection stage 87–1>. Bias current
describes the average current flow in the transformer. Bias and differential
currents are calculated individually for each phase.
If the transformer is grounded, for example having the connection group Dyn11,
then zero current must be compensated before differential and bias current
calculation. Zero current compensation can be selected individually for the IL and
I’L side.
Table 89 describes the connection group and zero current compensation for
different connection groups. If the protection area is only generator, then the
connection group setting is always Yy0, see Table 89. Also the settings of Vn and
V’n are set to be the same, for example generator nominal voltage.
YNyn0 Yy0 ON ON
YNyn6 Yy6 ON ON
difflslohko
IL1
IL2 H I M >1 & N
IL3
I'L1
I'L2 H J M
I'L3
& O
K M
L >
>
A B C D E F G
The stage ΔI> can be configured to operate as shown in Figure 139. This dual
slope characteristic allows more differential current at higher currents before
tripping.
A
M
B
N
K
J L
0.5
C 0.1
H
D E F G
A. ID/ITN H. IBIAS
B. Minimum trip area I. Maximum setting
C. ISTART J. Slope 1
Table 91 - Settings
The stage also includes second harmonic blocking. The second harmonic is
calculated from differential currents. Harmonic ratio is:
The fast differential overcurrent stage 87–1 does not include slope characteristics
or second harmonics blocking.
The differential CTS method uses the ratio between positive and negative
sequence currents at both sides of the protected transformer to determine a CT
failure. This algorithm is inbuilt in the dI> stage. When this ratio is small (zero),
one of the following four conditions is present:
When the ratio is non-zero, one of the following two conditions is present:
The I2 to I1 ratio is calculated at both sides of the protected transformer. With this
information, we can assume that:
• If the ratio is non-zero at both sides, there is a real fault in the network and the
CTS should not operate.
• If the ratio is non-zero only at one side, there is a change of CT failure and the
CTS should operate.
Another criterion for CTS is to check whether the differential system is loaded or
not. For this purpose, the positive sequence current I1 is checked at both sides of
the protected transformer.
If load current is detected only at one side, it is assumed that there is an internal
fault condition and CTS is prevented from operating, but if load current is detected
at both line ends, CTS operation is permitted.
Another criterion for CTS is to check whether the differential system is loaded or
not. For this purpose, the positive sequence current I1 is checked at both ends. If
load current is detected only at one end, it is assumed that there is an internal
fault condition and CTS is prevented from operating, but if load current is detected
at both line ends, CTS operation is permitted.
The differential CTS block mode is not recommended for two reasons:
• If there is a real fault during a CT failure, the differential protection would not
protect the line at all.
• Blocking the protection could slow down the operate time of the differential
protection because of transients in the beginning of the fault on the protected
line.
Setting groups
Characteristics
Slope 1 5–100 %
Slope 2 100–200 %
Inaccuracy:
Inaccuracy:
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The arc flash detection contains 8 arc stages that can be used to trip for example
the circuit breakers. Arc stages are activated with overcurrent and light signals (or
light signals alone). The allocation of different current and light signals to arc
stages is defined in arc flash detection matrices: current, light and output matrix.
The matrices are programmed via the arc flash detection menus. Available matrix
signals depend on the order code (see 13.1 Order codes).
The available signal inputs and outputs for arc flash detection depend on the
relay's hardware configuration.
The arc flash detection menus are located in the main menu under ARC. The
ARC menu can be viewed either on the front panel or by using Easergy Pro.
Arc protection
(Overshoot time
<35ms)
WARNING
HAZARD OF DELAYED OPERATION
Do not use the arc stage delay for primary trip. This delay is intended, with
the separate arc stage, for the circuit breaker failure scheme only
3. Wait until the Installation state shows Ready. The communication between
the system components is created.
4. The installed sensors and units can be viewed at the bottom of the Arc
protection group view.
6. Click the Trip delay[ms] value, set it to for example '0' and press Enter.
7. Click the DI block value, set it to for example '-' and press Enter.
The General > Scaling setting view contains the primary and secondary values
of the CT. However, the Arc protection menu calculates the primary value only
after the I start setting value is given.
For example:
2. Click the CT primary value, set it to for example 1200 A, and press Enter.
3. Click the CT secondary value, set it to for example 5 A, and press Enter.
4. On the Easergy Pro group list, select Protection > Arc protection.
Define the current signals that are received in the arc flash detection system’s
relay. Connect currents to Arc stages in the matrix.
For example:
The arc flash fault current is measured from the incoming feeder, and the current
signal is linked to Arc stage 1 in the current matrix.
2. In the matrix, select the connection point of Arc stage 1 and I>int.
Define what light sensor signals are received in the detection system. Connect
the light signals to the arc stages in the matrix.
For example:
Define the trip relays that the current and light signals affect.
For example:
2. In the matrix, select the connection point of Arc stage 1 and T1.
3. Select the connection points of Latched and T1 and T9.
Arc output matrix includes only outputs which are directly controlled by FPGA.
Define which arc events are written to the event list in this application.
For example:
The operation of the arc detection depends on the setting value of the I> int and
I01> int current limits.
The arc current limits cannot be set, unless the relay is provided with the optional
arc protection card.
Start current:
Operate time
- Light only ≤9 ms
- Light only ≤7 ms
- Light only ≤2 ms
Inaccuracy:
For special applications the user can built own detection stages by selecting the
supervised signal and the comparison mode.
f Frequency
P Active power
Q Reactive power
S Apparent power
Setting groups