AII Gauge FKG

The FCX – A2 pressure transmitter is designed for accurate gauge pressure measurement, offering a 4 to 20mA output signal and utilizing advanced micromachined silicon sensor technology. It features high accuracy, minimal environmental influence, and compatibility with various communication protocols, making it suitable for diverse applications. The transmitter also includes options for local adjustment, indicators, and robust environmental protection, ensuring reliable performance in various conditions.

Uploaded by

Jorge Muñiz
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
72 views8 pages

AII Gauge FKG

The FCX – A2 pressure transmitter is designed for accurate gauge pressure measurement, offering a 4 to 20mA output signal and utilizing advanced micromachined silicon sensor technology. It features high accuracy, minimal environmental influence, and compatibility with various communication protocols, making it suitable for diverse applications. The transmitter also includes options for local adjustment, indicators, and robust environmental protection, ensuring reliable performance in various conditions.

Uploaded by

Jorge Muñiz
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

PRESSURE TRANSMITTER

DATA SHEET FKG...4

The FCX – A2 pressure transmitter accurately measures


gauge pressure and transmits a proportional 4 to 20mA
signal.
The transmitter utilizes a unique micromachined capaci-
tance silicon sensor with state-of-the-art microprocessor
technology to provide exceptional performance and func-
tionality.

FEATURES
1. High accuracy ±0.07%
0.07% accuracy is a standard feature. Fuji’s micro-ca-
pacitance silicon sensor assures this accuracy for all el-
evated or suppressed calibration ranges without additional
adjustment.
2. Minimum environmental influence
The “Advance Floating Cell” design which protects the
SPECIFICATIONS
pressure sensor against changes in temperature, and
overpressure substantially reduces total measurement Functional specifications
error in actual field applications.
Service: Liquid, gas, or vapour
3. Fuji/HART ® bilingual communications protocol and
Span, range and overrange limit:
FOUNDATION™ fieldbus and Profibus™ compatibility
FCX–A2 series transmitter offers bilingual communica- Range limit
Span limit [kPa] {bar} Overrange
Type [kPa] {bar}
tions to speak both Fuji proprietary protocol and HART®. limit
Min. Max. Lower limit Upper limit [MPa] {bar}
Any HART® compatible devices can communicate with
F KG 01 1.3 130 –100 130 1
FCX–A2. Further, by upgrading electronics FOUNDA-
{0.013} {13} {–1} {0.13} {10}
TION™ fieldbus and Profibus™ are also available. F KG 02 5 500 –100 500 1.5
4. Application flexibility {0.05} {5} {–1} {5} {15}
F KG 03 30 3000 –100 3000 9
Various options that render the FCX – A2 suitable for al- {0.3} {30} {–1} {30} {90}
most any process applications include: F KG 04 100 10000 –100 10000 15
– Analog indicator at either the electronics side or ter- {1} {100} {–1} {100} {150}
F KG 05 500 50000 –100 50000 75
minal side {5} {500} {–1} {500} {750}
– Full range of hazardous area approvals
– Built-in RFI filter and lightning arrester Remark: To minimize environmental influence, span should be greater
than 1/40 of the max. span in most applications.
– 5-digit LCD meter with engineering unit
– Stainless steel electronics housing – Lower range limit (vacuum limit) ;
5. Burnout current flexibility (Under Scale: 3.2 to 3.8mA, Silicone fill sensor: See Fig. 1
Over Scale: 20.8 to 21.6mA) Fluorinated fill sensor: 66kPa abs (500mmHg abs) at
Burnout signal level is adjustable using Model FXW Hand below 60°C
Held Communicator (HHC) to comply with NAMUR NE43. – Conversion factors to different units;
6. Dry calibration without reference pressure 1 MPa=103 kPa=10bar=10.19716kgf/cm2= 145.0377psi
Thanks to the best combination of unique construction 1kPa=10mbar=101.9716mmH2O =4.01463inH2O
of mechanical parts (Sensor unit) and high performance Output signal: 4 to 20mA DC with digital signal super-
electronics circuit (Electronics unit), reliability of dry imposed on the 4 to 20mA signal.
calibration without reference pressure is at equal level
as wet calibration.

EDSX5-80f
EDS5-62b
Date Apr. 1, 2003
FKG...4

Power supply: Transmitter operates on 10.5V to 45V DC “Output Underscale”:


at transmitter terminals. Adjustable within the range 3.2mA to
10.5V to 32V DC for the units with optional 3.8mA from HHC
arrester.
Load limitations: see figure below 3.2 3.8 4 20 20.8 21.6 [mA]
Over scale
[Ω]
Burnout
2000
1533Ω
Under scale Normal operating range
Load resistance

Probable over range


Burnout Probable under range
1500

(Note) (1) HHC: Hand Held Communicator


1000
600Ω Loop-check output:
Operating Transmitter can be configured to provide
500 area
constant signal 3.8mA through 21.6mA by
250 24V 45V
HHC.
10 16.1 50 [V]
Temperature limit:
10.5V Ambient: – 40 to +85°C
Power voltage (–20 to +80°C for LCD indicator)
Note: For communication with HHC (1) (Model: FXW), min. of 250 Ω
(– 40 to +60°C for arrester option)
required.
(–10 to +60°C for fluorinated oil fill
transmitter)
Hazardous locations: For explosionproof units (flameproof or
intrinsic safety), ambient temperature
Type n
Authorities Flameproof Intrinsic safety Nonincendive must be within the limits specified by
each standard.
ATEX Ex II 2 GD Ex II 1 GD Ex II 3 GD
- EExd IIC T5/T6 - EExia IIC T4/T5 - EExn IIC T4/T5 Process: – 40 to +100°C for silicone fill
Factory Class I II III Class I II III Class I II III sensor
Mutual Div. 1 Div. 1 Div. 2
–20 to +80°C for fluorinated oil fill sen-
Groups B thru. G Groups A thru. F Groups A thru. G
CSA Class I II III Class I II III Class I II III sor
Div. 1 Div. 1 Div. 2 Storage: –40 to +90°C
Groups C thru. G Groups A thru. G Groups A thru. G
TIIS Ex do IIB+H2 T4 Ex ia II C T4 (*) — Humidity limit: 0 to 100% RH
Communication: With HHC(1) (Model FXW, consult Data
(*) Approval pending Sheet No. EDS8-47), following informa-
tion can be remotely displayed or recon-
Zero/span adjustment:
figured.
Zero and span are adjustable from the
Note: HHC’s version must be more than
HHC(1). Zero and span are also adjustable
6.0 (or FXW 1– 3), for FCX-
externally from the adjustment screw
A2.
(span adjustment is not available with 9th
digit code “L, P, Q, S”). Items Display Set
Damping: Adjustable from HHC or local adjustment Tag No. v v
unit with LCD display. Model No. v v
The time constant is adjustable between Serial No. v —
0.12 to 32 seconds. Engineering unit v v
Zero elevation/suppression: Range limit v —
Zero can be elevated or suppressed within
Measuring range v v
the specified range limit of each sensor
Damping v v
model.
Normal/reverse action: Output mode v —
Selectable from HHC(1). Burnout direction v v
Indication: Analog indicator or 5-digit LCD meter, as Calibration v v
specified. Output adjust — v
Burnout direction: Selectable from HHC(1) Data v —
If self-diagnostic detect transmitter fail- Self diagnoses v —
ure, the analog signal will be driven to ei- — —
Printer
ther “Output Hold”, “Output Overscale”
External switch lock v v
or “Output Underscale” modes.
Transmitter display v v
“Output Hold”:
Output signal is hold as the value just be- Linearize v v
fore failure happens. Rerange v v
“Output Overscale”:
Adjustable within the range 20.8mA to
21.6mA from HHC(1)

2
Performance specifications Physical specifications

Reference conditions, silicone oil fill, 316SS isolating diaphragms, Electrical connections:
4 to 20mA analog output in linear mode. G1 /2, 1/2-14 NPT, Pg13.5, or M20 × 1.5
Accuracy rating: (including linearity, hysteresis, and re- conduit, as specified.
peatability) 1-port (standard) or 2-port with each con-
Max span below 10000kPa model: duit, as spcified.
For spans greater than 1/10 of URL: ± 0.07% of span Process connections:
For spans below 1/10 of URL: 1/4-18 NPT or Rc1/4 on 54mm centers, as
0.1 × URL
(
± 0.02+0.05
Span )
% of span specified.
Meet DIN 19213
Max span 50000kPa model: Process-wetted parts material:
For spans greater than 1/10 of URL: ± 0.1% of span
Material
For spans below 1/10 of URL: code Wetted
0.1 × URL
(
± 0.05+0.05
Span )
% of span (7th digit Process cover
in Code
Diaphragm sensor body Vent/drain

symbols)
Stability: ± 0.1% of upper range limit (URL) for 6
month. V 316 stainless 316L stainless 316 stainless 316 stainless
steel(*1) steel steel steel
Temperature effect: J 316 stainless 316L stainless 316 stainless 316 stainless
Effects per 28°C change between the lim- steel(*1) steel steel steel
+Au coating
its of –40°C and +85°C H 316 stainless Hastelloy-C Hastelloy-C 316 stainless
URL
Zero shift: ± (0.075+0.0125 span )% steel(*1) lining steel
M 316 stainless Monel Monel lining 316 stainless
URL steel(*1) steel
Total effect: ± (0.095+0.0125 span )% T 316 stainless Tantalum Tantalum 316 stainless
steel(*1) lining steel
Overrange effect: Zero shift; 0.2% of URL for any overrange B Hastelloy-C Hastelloy-C Hastelloy-C Hastelloy-C
to maximum limit lining lining
L Monel lining Monel Monel lining Monel
Supply voltage effect: U Tantalum Tantalum Tantalum Hastelloy-C
Less than 0.005% of calibrated span per lining lining
1V
Note: *(1) SCS14 per JIS G 5121
RFI effect: Less than 0.2% of URL for the frequen- Remark: Sensor O-rings: Viton O-ring and teflon gasket select-
cies of 20 to 1000MHz and field strength able
30 V/m when electronics covers on. Availability of above material design depends on
ranges. Refer to “Code symbols”.
(Classification: 2-abc: 0.2% span per
SAMA PMC 33.1) Non-wetted parts material:
Step response: Time constant: 0.2s *) Electronics housing: Low copper die-cast
Dead time: approximately 0.2s *) aluminum alloy finished with epoxy/
(without electrical damping) polyurethane double coating (stan-
*) Faster response is available as option dard), or 316 stainless steel (SCS14 per
(maximum update rate: 25 times per JIS G5121), as specified.
second). Bolts and nuts: Cr-Mo alloy (standard), or
Mounting position effect: 304 stainless steel (630 stainless steel
Zero shift, less than 0.1kPa {1m bar} for a for 50MPa unit).
10° tilt in any plane. Fill fluid: Silicone oil (standard) or fluori-
No effect on span. This error can be cor- nated oil
rected by adjusting Zero. Mounting bracket: 304 stainless steel
Dielectric strength: Environmental protection:
500V AC, 50/60Hz 1 min., between circuit IEC IP67 and NEMA 6/6P
and earth. Mounting: On 60.5mm (JIS 50A) pipe using mount-
Insulation resistance: ing bracket, direct wall mounting, or direct
More than 100MΩ at 500V DC. process mounting.
Turn-on time: 4 sec. Mass {weight}: Transmitter approximately 3.4kg without
Internal resistance for external field indicator: options.
12Ω or less Add; 0.5kg for mounting bracket
0.8kg for indicator option
4.5kg for stainless steel housing
option

3
FKG...4

Optional features ACCESSORIES


Indicator: A plug-in analog indicator (1.5% accuracy) Oval flanges: (Model FFP, refer to Data Sheet No.
can be housed in the electronics compart- EDS6-10)
ment or in the terminal box of the hous- Converts process connection to 1 /2-14
ing. NPT or to Rc1/2; in carbon steel or in 316
An optional 5-digit LCD meter with engi- stainless steel.
neering unit is also available. Hand-held communicator:
Local adjustment unit with LCD display: (Model FXW, refer to Data Sheet No.
An optional 5-digit LCD meter with Zero/ EDS8-47)
Span adjustment function, loop-check Z/S board: Parts No.=ZZPFCX4-A070
function and damping adjustment func- When Z/S board is mounted on the FCX–
tion, is available. A2 amplifier unit, external adjustment
Arrester: A built-in arrester protects the electronics screw will be available for zero and span
from lightning surges. adjustment.
Lightning surge immunity:
4kV (1.2 × 50µs)
The product conforms to the requirements of the
Oxygen service: Special cleaning procedures are followed
Electromagnetic compatibility Directive 94/9/EC as detailed
throughout the process to maintain all pro-
within the technical construction file number TN513035.
cess wetted parts oil-free.
The fill fluid is fluorinated oil. The applicable standards used to demonstrate compliance
Chlorine service: The fill fluid is fluorinated oil. are :
Degreasing: Process-wetted parts are cleaned, but the EMI (Emission) EN61326 : 1997
fill fluid is standard silicone oil. Not for use Class A (standard for Industrial Location)
on oxygen or chlorine measurement. Frequency range Reference
MHz Limits standard
NACE specification:
40dB (µV/m) quasi peak, CISPR16-1 and
Metallic materials for all pressure bound- 30 to 230
measured at 10m distance CISPR16-2
ary parts comply with NACE MR-01-75. 47dB (µV/m) quasi peak,
230 to 1000
ASTM B7M or L7M bolts and 2HM nuts measured at 10m distance
(Class II) are available.
EMI (Immunity) EN61326: 1997
Vacuum service: Special silicone oil and filling procedure
Annex A (standard for Industrial Location)
are applied. Basic Performance
See Fig.1. Phenomenon Test value standard criteria
Optional tag plate: Electrostatic 4kV (Contact)
IEC61000-4-2 B
discharge 8kV (Air)
An extra stainless steel tag with customer
tag data is wired to the transmitter. 80 to 1000MHz
Electromagnetic
10V/m IEC61000-4-3 A
Coating of cell: Cell’s surface is finished with epoxy/poly- field
80%AM (1kHz)
urethane double coating. Specify if envi- Rated power
ronment is extermely corrosive. 30A/m
frequency IEC61000-4-8 A
50Hz
magnetic field
Silicone oil (Code:Y,G,N) 2kV
Burst IEC61000-4-4 B
5kHz
Silicone oil (Code:R)
1.2µs/50µs
[kPa abs] Surge 1kV (Line to line) IEC61000-4-5 B
{mbar abs} 2kV (Line to ground)
101 0.15 to 80MHz
{1010}
Conducted RF 3V IEC61000-4-6 A
80%AM (1kHz)
Operating pressure

Operating
Note) Definition of performance criteria
area
20 A: During testing, normal performance within the
{200} specification limits.
B: During testing, temporary degradation, or loss of
function or performance which is self-recovering.
4
{40}

2.7
{27} None-operating
area
–40 –15 60 85 120
Process temperature[°C ]

Fig. 1 Relation between process temperature and


operating pressure

4
CODE SYMBOLS
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Digit No.
Digit Description Note F KG 0 4 of code
4 <Connections>
Process Oval flange Conduit
connection screw connection
Rc1/4 7/16-20UNF G1/2 (×1) A
1/4-18NPT 7/16-20UNF 1/2-14NPT
Combination with
(×1) B
1/4-18NPT
12th digit code
M10 (or M12)(*1) Pg13.5 (×1) Note 1 C
1/4-18NPT
"C, E, P, Q" are not
M10 (or M12)(*1) M20×1.5 (×1) Note 1 D
1/4-18NPT 7/16-20UNF
available.
Pg13.5 (×1) E
Rc1/4 7/16-20UNF G1/2 (×2) S
1/4-18NPT 7/16-20UNF 1/2-14NPT (×2) T
1/4-18NPT M10 (or M12)(*1) Pg13.5 (×2) Note 1 V
1/4-18NPT M10 (or M12)(*1) M20×1.5 (×2) Note 1 W
1/4-18NPT 7/16-20UNF Pg13.5 (×2) X
6, 7 <Span and materials>
Span limit Process cover Diaphragm Wetted cell body
[kPa]{bar}(*2) Note 2
1.3…130 316 stainless steel 316L stainless steel 316 stainless steel 1V
{0.013…1.3} 316 stainless steel 316L stainless steel 316 stainless stee 1J
+Au coating
316 stainless steel Hast. C Hast. C lining 1H
316 stainless steel Monel Monel lining 1M
316 stainless steel Tantalum Tantalum lining 1T
Hast. C lining Hast. C Hast. C lining 1B
Monel lining Monel Monel lining 1L
Tantalum lining Tantalum Tantalum lining 1U
5…500 316 stainless steel 316L stainless steel 316 stainless steel 2V
{0.05…5} 316 stainless steel 316L stainless steel 316 stainless stee 2J
+Au coating
316 stainless steel Hast. C Hast. C lining 2H
316 stainless steel Monel Monel lining 2M
316 stainless steel Tantalum Tantalum lining 2T
Hast. C lining Hast. C Hast. C lining 2B
Monel lining Monel Monel lining 2L
Tantalum lining Tantalum Tantalum lining 2U
30…3000 316 stainless steel 316L stainless steel 316 stainless steel 3V
{0.3…30} 316 stainless steel 316L stainless steel 316 stainless stee 3J
+Au coating
316 stainless steel Hast. C Hast. C lining 3H
316 stainless steel Monel Monel lining 3M
316 stainless steel Tantalum Tantalum lining 3T
Hast. C lining Hast. C Hast. C lining 3B
Monel lining Monel Monel lining 3L
Tantalum lining Tantalum Tantalum lining 3U
100…10000 316 stainless steel 316L stainless steel 316 stainless steel 4V
{1…100} 316 stainless steel 316L stainless steel 316 stainless stee 4J
+Au coating
316 stainless steel Hast. C Hast. C lining 4H
316 stainless steel Monel Monel lining 4M
316 stainless steel Tantalum Tantalum lining 4T
Hast. C lining Hast. C Hast. C lining 4B
Monel lining Monel Monel lining 4L
Tantalum lining Tantalum Tantalum lining 4U
500…50000 316 stainless steel 316L stainless steel 316 stainless steel 5V
{5…500}
9 <Indicator and arrester>
Indicator Arrester
None None Z/S board A
Analog, 0 to 100% linear scale None attached. B
Analog, custom scale None Approval D
None Yes pending for E
Analog, 0 to 100% linear scale Yes 10th digit F
Analog, custom scale Yes code "G, H, H
Digital, 0 to 100% None J, K, P" L
Digital, custom scale None P
Digital, 0 to 100% Yes Q
Digital, custom scale Yes S
Digital, 0 to 100% 1
(Local adjustment unit with LCD display) None Approval
Digital, custom scale pending for 2
(Local adjustment unit with LCD display) None 10th digit
Digital, 0 to 100% code "D, E, 4
(Local adjustment unit with LCD display) Yes G, H, J, K,
Digital, custom scale P" 5
(Local adjustment unit with LCD display) Yes
Note 1 : (*1) For 50MPa {500bar} units, M12 is provided rather than M10.
Note 2 : (*2) 100: 1 turn down is possible, but should be used at the span greater than
1/40 of the maximum span for better performance.

5
FKG...4

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Digit No.
Digit Description Note F KG 0 4 of code
10 <Approvals for hazardous locations>
None (for ordinary locations) A
TIIS, Flameproof (Conduit seal) (Available for 4th digit code “A“, “S“) B
TIIS, Flameproof (Cable gland seal) (Available for 4th digit code “A“, “S“) C
FM, Flameproof (or explosionproof) (Available for 4th digit code “B“, “T“) D
CSA, Flameproof (or explosionproof) (Available for 4th digit code “B“, “T“) E
ATEX, Flameproof X
TIIS, Intrinsic safety (Approval pending) G
FM, Intrinsic safety and Nonincendive H
CSA, Intrinsic safety and Nonincendive J
ATEX, Intrinsic safety K
ATEX, Type n P
11 <Vent/ drain and mounting bracket>
Vent/drain Mounting bracket
Standard None Specify "A", or "C" for the 7th A
Standard Yes, stainless steel digit code "B", "L", or "U" C
Side None D
Side Yes, stainless steel F
12 <Options>
Extra SS tag plate Stainless steel elec. housing Coating of cell
None None None Y
Yes None None B
None Yes None Note3 C
Yes (*3) Yes None E
None None Yes M
Yes None Yes N
None Yes Yes P
Yes Yes Yes Q
13 <Special applications and fill fluid>
Treatment Fill fluid
Standard Silicone oil Y
Standard Fluorinated oil W
Degreasing Silicone oil G
Oxygen service Fluorinated oil (7th digit code "V", "J" only) A
Chlorine service Fluorinated oil (7th digit code "H", "T" ,"B", "U") D
NACE specification Silicone oil (Not available for 6th digit code "5", 7th N
digit code "T", "U", 15th digit code "A", "B")
Vacuum service Silicone oil for vacuum use R
14 <Sensor O-ring / Gasket>
Viton (O-ring) A
Teflon (gasket) B
15 <Bolt/nut>
Cr-Mo alloy hexagon socket head cap screw/carbon steel nut A
Cr-Mo alloy hexagon bolt/nut B
NACE bolt/nut (ASTM A193 B7M/A194 2HM) C
Not available for 6th digit
NACE bolt/nut (ASTM A320 L7M/A194 2HM) D
code "5"
304 stainless steel bolt/304 stainless steel nut E
630 stainless steel bolt/304 stainless steel nut Available for 6th digit code "5" F
Note 3 : (*3) Costomer tag number can be engraved on standartd stainless steel
name plate. If extra tag plate is required, select "Yes".

ORDERING INFORMATION
When ordering this instrument, specify.
1. CODE SYMBOLS
2. Measuring range
3. Output orientation (burnout direction) when abnormality is occured in the transmitter.
Hold/Overscale (21.6mA)/Overscale (3.2mA)
Unless otherwise specified, output hold function is supplied.
4. Indication method (indicated value and unit) in case of the actual scale (code D,H,P,S on 9th digit).
5. Tag No.(up to 26 alphanumerical characters), if required.

6
OUTLINE DIAGRAM (Unit:mm)
< 7th digit code : V, J, H, M, T, J >

Note2)
Vent/drain plug
(When the vent/drain plug In case of 4th digit
attached on the upper side code "S,V,W,X"
of the detector) Fastener
"B" Conduit conn.2
(Flameproof only)
MTG. Pipe JIS 50A Zero ADJ. screw

(10)
(2B) "A" Press. conn.

Up

ø80

105

130
104

ø80
123
70

52.5
Down
41

38

88
U - bolt M8 Note1)
58 37 Vent/drain plug Cable gland
(option)
210 (27)
4 holes "B" Conduit conn.1 "C" Conduit conn.
9 dia. 189 (6th digital code “5”)

With field ind. (option)


Approx. 147
43
Detail "A" Detail "B" Detail "C" Earth terminal
(Press. conn.) (Conduit conn.)
ø18.5
ø13
H ø15
2.5

Electronics
unit
Oval flange

210 (6th digit code “5”)


screw
F
8

See table 1
17
E

ø7 Sensor
41.3

D G 1/2 unit

Side
See table 1 See table 1
231
vent
(option)
4-M8 12

4th digit of the Conduit conn. Press.conn.


code symbols Oval flange screw
D E F H
7/16-20UNF
A, S G1/2 17 8 Rc1/4 Screw depth15
7/16-20UNF
B, T 1/2-14NPT 16 5 1/4-18NPT
Screw depth15 27
C, V Pg13.5 8 4.5 1/4-18NPT M10 54
Screw depth15 70
M10
D, W M20 1.5 16 5 1/4-18NPT
Screw depth15 104
7/16-20UNF
E, X Pg13.5 8 4.5 1/4-18NPT
Screw depth15
Table 1
CONNECTION
DIAGRAM
Note1) Cable gland is supplied in case of 10th digit code "C".
ø11 cable is suitable. CK CK
Note2) The pressure connector is located on the down side surface of (M4 screws)
the detector, when the vent / drainplug is attatched on the upper
side of the detector

7
FKG...4

< 7th digit code : B, L, U >


Zero ADJ. screw In case of 4th digit code "S,V,W,X" Fastener
MTG. Pipe (Flameproof only)
JIS 50A (2B) U - bolt M8 "C" Conduit conn.2

(10)
Up

105
ø80

104

ø80
70

52.5
Down
41

38

88
58 40 Cable gland
4 holes (option) Note)
9 dia. 213 (27)
"D" Conduit conn.

With field ind. "C" Conduit conn.1


155
Detail "A" Detail "C" Detail "D" 43
(Press. conn.) Earth terminal
(Conduit conn.)
4th digit code "A. S" ø13
ø15
ø16
+0.2
2 -0.1

ø12 +0.1
0

Electronics
1

unit
17
F

ø4
G1/2

234
E
Sensor
unit
See table 1 P
Detail "B"
4th digit code
View from P
"B,C,D,E,T,V,W,X" 4-M8 12
ø16
1/4-18NPT "A" or "B" Vent/drain
Press. conn. plug
10

41.3

54
70
98

Oval flange 104


ø4 screw
See table 1

4th digit of the Conduit conn.


code symbols
Oval flange screw
D E F
7/16-20UNF CONNECTION
A, S G1/2 17 8 Screw depth10 DIAGRAM
7/16-20UNF
B, T 1/2-14NPT 16 5 Screw depth10 CK CK
M10 (M4 screws)
C, V Pg13.5 8 4.5 Screw depth10
M10
D, W M20 1.5 16 5 Screw depth10
7/16-20UNF
E, X Pg13.5 8 4.5 Screw depth10

Table 1

Note) Cable gland is supplied in case of 10th digit code "C".


ø11 cable is suitable.

Head office Sales Div.


11-2 Osaki 1-chome, Shinagawa-ku, Tokyo, 141-0032 Japan International Sales Dept.
http://www.fujielectric.co.jp No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan
Phone: 81-42-585-6201, 6202
Fax: 81-42-585-6187
http://www.fic-net.co.jp

Information in this catalog is subject to change without notice. Printed in Japan