The document outlines the minimum clearance requirements for a 33KV SC suspension type transmission line, including specific measurements for phase to earth, phase to phase, and ground clearances. It also includes a detailed bill of materials necessary for construction, specifying quantities and dimensions of various components. Additional notes emphasize the importance of maintaining clearances and proper construction practices.

Uploaded by

sachinshingne
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
59 views5 pages

SPSC 1

The document outlines the minimum clearance requirements for a 33KV SC suspension type transmission line, including specific measurements for phase to earth, phase to phase, and ground clearances. It also includes a detailed bill of materials necessary for construction, specifying quantities and dimensions of various components. Additional notes emphasize the importance of maintaining clearances and proper construction practices.

Uploaded by

sachinshingne
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

THE FOLLOWING MINIMUM CLEARANCES TO BE ADOPTED:

1 PHASE TO EARTH 1100MM


2 PHASE TO PHASE 1500MM
3 THE MINIMUM GROUND CLEARANCE 5200MM
OTHER THAN STREET BILL OF MATERIAL
4 THE MINIMUM GROUND CLEARANCE 5800MM S.No. DESCRIPTION LENGTH QTY.
ALONG THE STREET
5 1 RSJ 152X152 POLE 13 METER 1
THE MINIMUM GROUND CLEARANCE 6100MM
ACROSS THE STREET 2 H CROSS ARM FOR CONDUCTOR- 2250MM 2
6 ABOVE THE BUILDING A HORIZONTAL 2500MM 100X50X6MM.
CLEARANCE 3 H BRACING -50X50X5MM 1200MM 3
13 7 ADJACENT TO BUILDING A 2000MM 4 ANTI CLAMBING DEVICE GI BARBED WIRE 12 SWG 1
HORIZONTAL CLEARANCE 5 M 16 U BOLT 240 MM 3
8 7
8 MINIMUM ELECTRICAL CLEARANCE 320MM
3 AT JUMPER (PH-E) 6 33kV SUSPENSION DISC INSULATOR 90 kN 3
7 H CROSS ARM FOR Y CONDUCTOR- 1300MM 2
-100X50X6MM.
13 8 C CLAMP -50x08MM 380MM 8
8 2
6 9 STAY WIRE AND GUY SET and C Clamps AS REQUIRED
10 DANGER BOARD CLAMP 25X05 MM 540MM 1
3
11 BARBED WIRE CAMP 25X05 MM 380MM 4
12 DANGER BOARD 250 (W) X200 (H) X 2 (T)MM - 1
13 4 HOLE STRIP 50 X 08 MM 252MM 6
14 BOLT & NUTS OF REQUIRED SIZE AS REQUIRED

15 EARTHING BORING Ø 150MM 1500MM 1

16 EARTHING MIXTURE CHARCOAL AND SALT/


AS REQUIRED
BENTONITE IN ALTERNATE LAYERS

NOTES:- 17 G.I. WIRE 8 SWG/ 6 SWG AS REQUIRED


4

1. ALL DIMENSION ARE IN MM UNLESS OTHERWISE IS STATED.


2. TREE TRIMMING SHALL BE DONE TO MAINTAIN MINIMUM CLEARANCE.
3. STAY ARRANGEMENT SHALL BE REPLACED WITH STUD POLE WHEREVER MULTIPLE
STAY ARRANGEMENT IS NOT POSSIBLE AS PER SITE CONDITION.
4. STAY PLATE Ø250, 8MM SHALL BE USED
5. COPPING SHALL BE 300 MM HEIGHT WITH MUFFING.
FGL 6. GRADE OF CEMENT SHALL BE OPC 53 & GRADE OF CONCRETE 1:1.5:3.
AUGUR EXCAVATION 300MM O X 2200MM
15 CLIENT:

16 PCC
1:1.5:3 TURNKEY
17 CONTRACTOR:- URJA INFRA.
DRAWING
MAXIMUM SPAN LENGTH-45 METERS PREPARED BY:- URJA INFRA.
PROJECT:-

TRANSMISSION LINE:- 33KV SC SUSPENSION TYPE LINE LENGTH 8 KM.

THIS DOCUMENT IS THE PROPERTY OF URJA INFRA AND IT MUST NOT BE


USED DIRECTLY ON INDIRECTLY IN ANYWAY TO THE INTEREST OF THE COMPANY.
TITLE:- 33KV SC SUSPENSION TYPE LINE

DRG. NO.: SCALE: PAGE NO.- 01/01

REV.:
Ø17.5 mm DIA
170
450
100

140

40
6
158
FRONT VIEW 35 70 35 170 70 140 70
Ø17.5 mm DIA Ø17.5 mm DIA
50 50 CLAMP FOR OFC CABLE
Ø17.5 mm

Ø17.5 mm
Ø17.5 mm

65
65

TOP VIEW
H-CROSS ARM FOR CONDUCTOR

50
100

Ø17.5 mm DIA FRONT VIEW


50
Ø17.5 mm
1 NO NUTS &
1 NO PL WASHER 65
Ø17.5mm 1 NO SP WASHER

65

70
TOP VIEW

240
H-CROSS ARM FOR Y CONDUCTOR

50 1100 50
(G) M 16 U-BOLT WITH
2 NO NUTS & 2 NO PLAIN WASHER
1200
AND 2 NOS OF SPRING WASHERS
80MM NEED TO BE CUT AT ONE SIDE OF ANGLE
H BRACING ANGEL CLIENT:

TURNKEY
50 180 50 CONTRACTOR:- URJA INFRA.
25

DRAWING
280 PREPARED BY:- URJA INFRA.
25
50 180 50
280
140

160 Ø13.5 mm DIA Ø13.5 mm DIA PROJECT:-


28 224
60

28 160
28 225 28 TRANSMISSION LINE:- 33KV SC SUSPENSION TYPE LINE LENGTH 8 KM.
05

05

THIS DOCUMENT IS THE PROPERTY OF URJA INFRA AND IT MUST NOT BE


USED DIRECTLY ON INDIRECTLY IN ANYWAY TO THE INTEREST OF THE COMPANY.

CLAMP FOR DANGER BOARD CLAMP FOR BARBED WIRE TITLE:- 33KV SC SUSPENSION TYPE LINE

DRG. NO.: SCALE: PAGE NO.- 01/01

REV.:
C Clamp F 50x08x380mm

D Clamp F 50x08x540mm

CLIENT:

TURNKEY
CONTRACTOR:- URJA INFRA.
DRAWING
PREPARED BY:- URJA INFRA.
PROJECT:-

TRANSMISSION LINE:- 33KV SC SUSPENSION TYPE LINE LENGTH 8 KM.

THIS DOCUMENT IS THE PROPERTY OF URJA INFRA AND IT MUST NOT BE


USED DIRECTLY ON INDIRECTLY IN ANYWAY TO THE INTEREST OF THE COMPANY.
TITLE:- 33KV SC SUSPENSION TYPE LINE

DRG. NO.: SCALE: PAGE NO.- 01/01